Fundamental of Air Conditioning
Fundamental of Air Conditioning
A. For the staircase pressurization system, the total force required to open the door when applied at the designed door
opening handle or push plate shall not exceed 133 N.
The distance from the doorknob side of the door is 0.15 m and the pressure differential across the door should be 50 Pa.
For an exit door of 0.9 m (W) x 2.2 m (H), what is the force to overcome the door closer? (5 marks)
Total force to open the door (F(N)) when applied at the designed door opening handle or push plate, shall not exceed 133N,
in a smoke control system
Given:
F = Total force to open the door = 133N
W = Door width (m) = 0.9m
A = Door area (m2) = 0.9 x 2.2 = 1.98m2
P = Pressure differential across the door (Pa) = 50Pa
d = Distance from the doorknob side of the door (m) =0.15m
F = Total force to open the door (N) = 133
𝐹𝑑𝑐 + (𝑊 × 𝐴 × ∆𝑃)
𝐹=
2 × (𝑊 − 𝑑)
𝐹𝑑𝑐 + (0.98 × 1.98 × 50)
133 =
2 × (0.98 − 0.15)
𝐹𝑑𝑐 = 110.4N
B. For a shopping mall at basement level B3, the width and length of the shopping mall is 60m and 120m respectively. The
clear height is determined at 4m. What is the HK statutory requirement of Smoke Extraction Flowrate and the Makeup Air
Flowrate in m3/s?
Under Code of Practice, smoke extraction system is required if there is more than 2 stories.
Compartment volume: 60 x 120 x 4m = 28800m3
Minimum extraction rate shall be equivalent to not less than 8 air changes per hour of the total compartment volume
Minimum extraction rate = 28800 x 8 = 230400 m3/hr
Minimum make-up air rate shall be 80% of the extraction rate
Minimum make-up air rate: 230400 x 80% = 184300 m3/hr
1
Psychrometry, Air Conditioning and Cycles
A. Definition: study of thermodynamic properties of moist air, e.g. temperature, relative humidity, moisture content
a. Moist air: Dry air with water vapour
b. Air and water vapour behave independent of each other and follow ideal gas laws.
c. Conservation of energy and mass principles can be applied
Dry bulb temperature °C Air temperature
Wet bulb temperature °C Air temperature when it is cooled to saturation (100% relative
humidity)
Humidity ration/specific kg/kg Mass of water vapour per unit mass of dry air
humidity/moisture content (w) 𝑚𝑤
𝑤= 𝑘𝑔/𝑘𝑔
𝑚𝑎
Masses of water vapour mw In a given volume
Masses of dry air ma In a given volume
Relative humidity % Extent of saturation
Dew point °C temperature to which air be cooled at constant pressure to become
saturated
Specific enthalpy (h) kJ/kg Energy content of moist air per unit mass of dry air
Specific heat of moist air at Amount of energy required to raise temperature of moisture air by
constant pressure (CP) 1°C for unit mass of dry air.
It can normally be taken as 1.02 kJ/kg K.
Specific volume (ν) m3/kg Volume of moisture air per unit mass of dry air
Density (ρ) kg/m3 1
ν
B. Psychrometric Chart
a. For a moist air sample at point X
Dry bulb 25 °C
Wet bulb 18 °C
Moisture content 0.01 kg/kg
Relative humidity 50 %
Specific volume 0.858 m3/kg
Specific enthalpy 50.5 kJ/kg
𝑞 = ℎ2 − ℎ1
𝑄 = 𝑚𝑎 𝑞
𝑄 = 𝑚𝑎 (ℎ2 − ℎ1 )
q kJ/kg Energy transfer per kg of dry air
1 Entering air condition
2 Leaving air condition
Q kW Total rate of energy transfer
ma kg/s mass flow rate of dry air
d. Various types of A/C processes are shown in the following psychrometric chart where O represents the entering air
conditions.
2
Sensible An increase or decrease in dry bulb temperature
Heating (OC)/ of air without change in moisture content.
Cooling (OG) In cooling, the surface temperature of the coil
shall be above the dew point temperature of
the incoming air.
a. Adiabatic Mixing
2 or more air streams mix with each other to form a combined
stream.
Mixture (m) of 2 entering streams 1 and 2 will lie on the
straight line joining 2 state points.
Divides the line into segments with regards to the relative
mass flows of the entering streams.
𝑚1 𝑡1 + 𝑚2 𝑡2 𝑚1 𝑤1 + 𝑚2 𝑤2 𝑚1 ℎ + 𝑚2 ℎ
𝑡𝑚 = 𝑤𝑚 = ℎ𝑚 =
𝑚1 + 𝑚2 𝑚1 + 𝑚2 𝑚1 + 𝑚2
3
b. Space Conditioning Process
i. Conditioned air (s) enters the space and
there is heat and mass transfer between the supplied air and the space air (r).
ii. In summer
1. Cool and dry air is used to remove the energy generated in the space (Q) which can be in the
form of sensible (Qs) and latent (Ql) heats.
2. Sensible heat: raise the space air temperature while
3. Latent heat: increase the moisture content.
Process
Sensible cc -> s Supply air will gain heat energy as it passes
heating through the supply air fan and duct to the
space.
Space s -> r Cool and dry supply air at s will be supplied
conditioning to the space and absorbs the energy
generated to become r
Sensible r -> ru As return air passes through the return air
heating ductwork and fan, heat energy will be
gained similar to the supply system heat
gain
Adiabatic ru -> o -> Return air at ru will mix with outdoor air at o
mixing m in the air handling unit resulting in a
mixture of m.
Position of m depends on the amount of
outdoor air admitted.
Cooling & m -> cc Mixture will pass through the cooling coil
dehumidifying where the total energy absorbed
throughout the cycle is removed at the coil
by the cooling chilled water
4
E. An Illustration of Air Conditioning Cycle Analysis
a. An office employs a basic air conditioning system.
The space total and sensible cooling loads are estimated to be 40 kW and 34 kW respectively.
Summer outdoor design dry bulb temperatures 33°C
Wet Bulb Temperature 28°C
Indoor design conditions: dry bulb temperature 25°C
Relative humidity 50%
Condition of air leaving cooling coil (off coil) relative humidity 95%
Outdoor ventilation air 0.5 m3/s
b. Supply and return system heat gains are neglected
c. The followings are to be determined in order to specify the air handling plant for the system:
i. Condition of supply air
ii. Supply air volume flow rate
iii. Condition of mixture of outdoor and return air
iv. Cooling coil load
d. Calculation procedures
5
3 Since no supply system heat gain, state point cc is
the same as state point s.
The return system temperature increase can be easily drawn starting from r.
A horizontal line has to be drawn so that one end lies on the off coil relative humidity curve while the other
lies on the SHR line with its length equals to the temperature increase.
6
11 If supply system heat gain is considered, say 2°C, the
temperature difference between cc and s is equal to
2°C.
7
Refrigeration Plant and Components
A. Types of Refrigerants
a. Refrigerant
i. A fluid capable of transferring heat in a refrigeration system.
ii. Boil at not a too high temperature and liquify at a moderate pressure.
A high latent heat of vaporization is also desired.
iii. Classifications depending on its composition: e.g. chlorine, hydrogen, halogen
d. Numbering in refrigerants
i. Add 90 to the refrigerant number
ii. Result shows the number of C, H, F atoms
iii. e.g. HCFC-141b: 141+90 = 231 (2 “C”, 3 “H”, 1 ”F”)
iv. Since 2 “C” should have 6 bonds (saturated)
v. Remaining will be 2 “Cl”
vi. Thus, HCFC-141b = C2H3FCl2
vii. Letter “b” describe the isomer for the chemical
b. Increased chance of depletion with presence of chlorine as a catalyst and higher degree of stability of refrigerant
Example: CFC-11 and CFC-12.
c. CFC is more harmful than HCFC while HFC will not cause any problem
8
d. CFCs (chlorofluorocarbons)
i. High ozone-depleting potential (ODP) contributing to the breakdown of the ozone layer,
are banned by the Montreal Protocol
ii. CFCs (e.g. R11, R12 and R114) would be phased out production and consumption of CFCs by year 2000.
iii. Copenhagen amendments to Montreal Protocol (1992): quicken the pace of phasing out of CFCs in 1/1/1
e. HCFCs (Hydrochlorofluorocarbons)
i. Have limited ODP are classified under the Montreal Protocol as transitional substances and
ii. Copenhagen amendments to Montreal Protocol (1992):
restricted the use of HCFCs with gradual phase-out until completion in 2030
f. HFCs (hydrofluorocarbons)
i. Contain no chlorine and therefore have zero ODP and not controlled by the Montreal Protocol.
ii. Examples: R125, R134a and R152a.
iii. R134a can be substituted directly, requiring replacement of some serviceable components only for R12.
c. Prevention of Leakage
i. Limit the volume of refrigerant gas in a system
ii. Improve standards of design and installation for refrigerant pipework
f. Ideal refrigerants
i. Having the desired thermodynamic properties
ii. Non-toxic
iii. Non-flammable
iv. Completely stable inside a system
v. Environmentally friendly even after decomposition of products and abundantly available or easy to
manufacture
vi. Compatible with other materials used to fabricate and service refrigeration systems
vii. Easy to handle and detect
viii. System not operating at extreme pressures, either high or low
9
G. Basic Refrigeration Principles
a. Principles of Refrigeration
i. Liquids absorb heat when changed from liquid to gas
ii. Gases give off heat when changed from gas to liquid.
b. For an air conditioning system to operate with economy, the refrigerant must be used repeatedly.
c. All air conditioners use the same cycle of compression, condensation, expansion & evaporation in a closed circuit.
d. Same refrigerant is used to move the heat from one area, to cool this area, and to expel this heat in another area.
t: temperature
s: entropy
h: enthaply
p: pressure
10
Evaporator Low Pressure Liquid to Low Pressure Gas
(Vaporization) Low-pressure liquid then moves to the evaporator,
where heat from the inside air is absorbed and changes it from a
liquid to a gas.
Heat extraction from the evaporator through vaporisation of
refrigerant.
Refrigeration effect (RE)
o Energy transfer per kg of refrigerant
o Cooling effect produced in a refrigerator
o RE = h1 – h4 kJ/kg
Compressor Low Pressure Gas to High Pressure Gas
(Compression) Refrigerant comes into the compressor as a low-pressure gas, it is
compressed and then moves out of the compressor as a high-
pressure gas.
iii. When there are losses in the compression process, the entropy will always increase s2’’ > s1.
iv. State point 2’’ is determined using the isentropic efficiency (ηisen) with state 2’ located initially (s1 = s2’):
𝑖𝑑𝑒𝑎𝑙 𝑊𝑜𝑟𝑘 𝐼𝑛𝑝𝑢𝑡 ℎ −ℎ
v. 𝜂𝑖𝑠𝑒𝑛 = = 2′ 1
𝐴𝑐𝑡𝑢𝑎𝑙 𝑊𝑜𝑟𝑘 𝐼𝑛𝑝𝑢𝑡 ℎ2" −ℎ1
12
I. Calculation on Vapour Compression Refrigeration Cycles
a. Consider a refrigeration cycle using R-134a is plotted based on the following information:
i. Condenser temperature = 45°C
ii. Evaporator temperature = 10°C
iii. Sub-cooling at condenser = 3°C
iv. Superheating at evaporator = 3°C
v. Compressor efficiency = 90%
b. Refrigeration cycle for single stage compression is plotted
c. Refrigeration effect and the COP are to be found
Step 1 Plot the condenser and evaporator pressure line (based on temperature)
13
Step 3 Plot the isentropic line and determine the enthalpy of the refrigerant
14
Step 5 Complete the refrigeration cycle and identify the enthalpy of all the points
15
J. Types of Compressors
a. Positive displacement type
i. Increase the pressure of vapour refrigerant by reducing the volume of the compression chamber through
mechanical force applied to the compressor.
ii. Example: Reciprocating, screw, rotary and scroll compressors.
K. Types of Construction
a. Hermetic type:
i. Compressor and motor are sealed in the same housing with the minimum leakage of refrigerant.
ii. Assembly is small and cheap.
iii. Rotary compressors and reciprocating compressors.
b. Semi-hermetic type:
i. Similar to the hermetic type but with access to the compressor for repairs.
ii. Medium-size compressors.
c. Open type:
i. Compressor and motor are enclosed in two separate housings.
ii. Large-size compressors
iii. Example centrifugal compressors with cooling capacity greater than 1200 TR.
d. Reciprocating Compressors
i. Intake, compression and discharge strokes in cylinder
ii. A no. of 2-8 cylinders in a compressor with up to 200TR
iii. Total refrigeration capacity from 50TR to 500TR with the use of multiple compressors in a chiller plant
iv. Examples of Refrigeration system using reciprocating compressors
e. Screw Compressors
i. Male rotor driven by a motor which enables the meshing female rotar to rotate with compression of
trapped refrigerant.
ii. A screw compressor can have a refrigeration capacity from 50 to 500TR.
iii. With multiple units, a refrigeration plant can provide up to 1250TR.
f. Scroll Compressors
i. 2 identical scroll: one stationary and one revolving eccentrically with compression of trapped refrigerant.
ii. No valves are required and valve losses are eliminated.
iii. Maintenance, noise and vibration are reduced.
iv. Small refrigeration capacity (up to 60 TR).
g. Rotary Compressors
i. 2 types: Rotating piston and rotating blade.
ii. Cylinder is stationary with a rotor revolving.
iii. Small refrigerators of up to 4 TR, e.g. window units.
iv. Quiet and smooth in operation.
16
h. Centrifugal Compressors
i. Several impellers are installed in series to increase the pressure and refrigerant volume flow.
ii. Vapour refrigerant is drawn through the inlet vanes to the impellers.
iii. Refrigerant is whirled at a high speed by the impellers which impart centrifugal force throwing it to the
outside of the impeller.
iv. Housing contains the refrigerant and forces it to exit at the discharge.
v. Generally used for large installations (100 - 10,000TR).
17
Air Side System
A. Basic Concepts
a. 4 methods of environmental control:
i. Natural ventilation
ii. Mechanical ventilation
iii. Comfort cooling
iv. Air conditioning
c. Comfort Air-conditioning
i. A process of controlling the air temperature, relative humidity, ventilation, air movement and air
cleanliness of a given space in order to provide the occupants with a comfortable indoor temperature.
b. Designer should consider various system options and recommend 1 or several that will be likely to perform as
desired.
18
C. Classification of Air Conditioning Systems
a. To provide a background for selecting the optimum air conditioning system based on building requirements.
b. 3 Main categories:
i. Individual Systems
1. Use a self-contained, factory-made air conditioner to serve 1-2 rooms
2. Example: room/ window air conditioner and split-type units
19
c. Package Air Conditioning Systems
i. Factory assembled (floor mounting) package
1. Placed indoor, containing direct expansion coil, controls, fan and compressor, with the condenser
remotely placed outdoor.
2. Commonly used in Hong Kong for restaurants, café shops, factories, etc
ii. Refrigerant compressor: installed inside the indoor unit, making the machine less quiet than the split
system.
iii. Allow a larger cooling capacity for the indoor unit, which will be floor-mount usually.
iv. Application: Outdoor unit (condenser only) is put on the roof top, with the indoor unit a few floors below
20
c. Single Zone CAV System
i. A variable supply air temperature to meet with the cooling load requirements of the space while the
supply air volume flow rate will be unchanged
ii. Basic central system which can supply a constant air volume or a variable air volume at low, medium or
high pressure.
iii. Equipment:
located outside the conditioned space normally but
can also be installed within the conditioned space if conditions permit.
d. Reheat System
i. A modification of the single-zone system.
ii. Zone/ space control for areas of unequal loading.
iii. Heating/ cooling of perimeter areas with different exposures.
iv. Air throughout the reheat system can be:
1. Warmed up.
2. Removed moisture (for humidity control).
v. Close control for process or comfort applications.
Heat is added as a secondary process to either preconditioned primary air/ recirculated room air in the
system
Heating medium: Hot water, steam or electricity
21
e. Variable Air Volume (VAV) System
i. Compensates for varying cooling loads by regulating the volume of cooling air supplied through a single
duct.
ii. Simple VAV systems typically cools only and have no requirement for simultaneous heating and cooling in
various zones.
b.Fan-Coil System
i. Elements: Finned-tube coil + fan section.
ii. Fan section:
1. Recirculates air continuously from within the perimeter space through the coil
2. Supplied with either hot or chilled water
iii. System Description
1. Each space has its own fan coil unit(s) through which cooling and/or heating can be provided.
2. Mixture of primary air and recirculating room air is passed through the cooling and/or heating
coils in the FCU for treatment before being admitted to the space.
3. PAU: provides preliminary treatment of the outdoor air.
4. Heating:
a. Provided by the FCU through hot water heating coil or electric heater
b. Catered for by the warm PA.
G. All Water Systems
Advantages Less ductwork and space
Flexible and readily adaptable to many building module requirements.
Provides individual room control.
Less expensive
Disadvantages No positive ventilation is provided unless wall openings are used.
No humidification is provided.
Maintenance and service work has to be done in the occupied areas.
22
Components of Air Side Systems
A. Basic Concepts
a. Duct Insulation
i. Mounted or inner-lined
ii. To reduce heat loss and heat gain
iii. To prevent the condensation on the outer surface of the duct.
iv. Duct wrap (outer surface)/ duct inner liner/ fiberglass duct boards.
v. Duct liner provides both thermal insulation and sound attenuation.
vi. Thickness: based on economical analysis.
C. Ceiling Diffuser
a. A series of concentric rings/ inner cones made up of vanes arranged in fixed directions + an outer shell/frame.
b. Shape: Round, square, or rectangular.
c. Most widely used: Suitable for low headroom situations.
d. Supply air is discharged through the concentric air passages or directional passages in 1, 2, 3 or
in all directions by using different types of inner cone and vanes.
D. Slot Diffuser
a. A plenum box with single or multiple slots and air deflecting vanes for flow direction control.
b. Air discharged from a slot diffuser can be projected horizontally or vertically.
c. With multiple slots, air can be horizontally discharged either left or right, or a combination of both,
or one slot can discharge vertically while another discharge horizontally.
d. To distribute the air more evenly at the slot.
e. Insulated internally.
E. Side Grilles
a. Various types (fixed blade, single/double deflection)
b. Low entrainment ratio and longer throw.
c. Not suitable for rooms with low ceiling and great depth
23
d. Heat source: location, shape and heat flux
e. Location of obstacles and furniture.
f. Radiation and heat loss through the walls.
g. Infiltration and exfiltration through door gaps and other leak areas.
h. Movement of equipment and people.
I. Air Filters
J. AHU/PAU-Filters
a. Air filtration is an important component to achieve an acceptable indoor air quality.
b. Low-efficiency filters of the panel type as prefilter.
c. Medium- and high-efficiency bag type for filtering the air.
d. Carbon-activated gaseous absorption filters for removal of objectionable odors.
24
Water Side Systems: System Design
A. Basic Concepts
a. Water system design needs evaluation of
i. Space loads: Transmission, solar radiation, infiltration, ventilation air, people, lights, power, appliances
ii. Occupancy patterns
iii. Indoor environmental requirements
iv. Full-load and part-load conditions
25
d. Open water systems, e.g. using cooling tower
e. Closed water systems
i. Chilled water (CHW) system [4-13˚C, 825 kPa]
ii. Condenser water (CW) system
iii. Dual temperature water system
iv. Low temp. water (LTW) system [Max.120°C, <1100 kPa]
v. Medium temp. water (MTW) system [120-125°C, <1100 kPa]
vi. High temp. water (HTW) system [>175°C, >2070 kPa]
f. Once-through system, e.g. sea water system
g. Hydronic systems
i. Use of liquid heat transfer medium in heating and cooling system
ii. Convey heat to or from a conditioned space or process with hot or chilled water.
iii. Water flows through piping that connects a boiler, water heater, or chiller to suitable terminal heat
transfer units located at the space or process
B. System Components
Source system (chiller or boiler)
Load system
Pump system
Distribution system
Expansion chambers
a. Source VS Load
Source Load
Boiler Air Coil
Chiller Heat Exchanger
Heat Pump Storage Tank
Solar Panel Process
b. Source
i. Point where heat is removed from a cooling system or added in a heating system.
ii. Source efficiency as a function of load.
iii. Considerations in selecting a source device
1. Design capacity
2. Part-load capability
c. Load systems:
i. Devices (terminal units) that convey heat to the water for cooling or from the water for heating of the
space or process.
26
e. Cooling load devices & Heating load devices
Cooling Load devices Heating Load devices
Fan-coil units (AHU) Fan-coil units (AHU)
Air-to-water heat exchanger Air-to-water heat exchanger
Water-to-water heat exchangers Water-to-water heat exchangers
Steam-to-water heat exchanger
Radiant cooling panels Radiant/ Solar heating panels
Coils in central units Preheat & Heating coils in central units
Heat pump evaporator Heat pump condenser
Induction unit coils Finned-tube radiators
Electric compression chiller Convectors
Thermal absorption chiller Unit heaters
Hot water generator/ boiler
Heat recovery or salvage heat device
Exhaust gas heat exchanger Incinerator
𝑀𝑖𝑛.𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦
f. 𝑇𝑢𝑟𝑛𝑑𝑜𝑤𝑛 𝑅𝑎𝑡𝑖𝑜 = × 100%
𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦
𝑅𝑎𝑡𝑖𝑜 𝑜𝑓 𝐴𝑐𝑡𝑢𝑎𝑙 𝐿𝑜𝑎𝑑
g. 𝐷𝑖𝑣𝑒𝑟𝑠𝑖𝑡𝑦 𝐹𝑎𝑐𝑡𝑜𝑟 =
𝐷𝑒𝑠𝑖𝑔𝑛 𝐿𝑜𝑎𝑑
i. Design trade-offs
i. Improved efficiency vs initial installation cost
j. System temperatures
Design temperatures and temperature
ranges by considering the performance
and economies of the components.
Example:
if conditioned space at 25°C, 50% RH
has dewpoint temperature 13°C,
max return water temperature should be
near 13°C.
27
C. Heat Transfer Calculations
Depends on surface area, overall heat transfer coefficient, geometry of heat transfer surfaces, etc.
𝑞 = 1.2𝑄𝑎 ∆𝑡
𝑞 = 1.2(2.5𝑚3 /𝑠)(55°𝐶 − 15°𝐶)
𝑞 = 120𝑘𝑊
∆𝑡𝑚𝑎𝑥 − ∆𝑡𝑚𝑖𝑛
𝐿𝑀𝑇𝐷 =
𝐼𝑛(∆𝑡𝑚𝑎𝑥 − ∆𝑡𝑚𝑖𝑛 )
Δtmax = 60 – 15 = 45
Δtmin = 70 – 55 = 15
45 − 15
𝐿𝑀𝑇𝐷 =
45
𝐼𝑛( )
15
𝐿𝑀𝑇𝐷 = 27.3˚𝐶
𝑞 = 𝑈𝐴(𝐿𝑀𝑇𝐷)
𝑞 = 850(1.2 × 0.9)27.3(4 𝑟𝑜𝑤𝑠)
𝑞 = 100246𝑊
𝑞 = 100.246𝑘𝑊
28
c. Latent cooling and dehumidification of air
Both sensible & latent heat transfer
𝑞𝑡𝑜𝑡𝑎𝑙 = 𝑊∆ℎ(𝑘𝑊)
W = mass flow rate of cooled
medium (kg/s)
Δh = enthalpy difference of entering
and leaving conditions of cooled
medium (kJ/kg)
𝑞𝑡𝑜𝑡𝑎𝑙 = 𝑄𝑎 𝜌𝑎 ∆ℎ𝑗
𝑞𝑡𝑜𝑡𝑎𝑙 = 1.2𝑄𝑎 ∆ℎ
29
Pressure Drop Diagram
b. A combination of direct and reverse systems: Direct return Riser & Reserve Zone Piping
Raisers are direct return
First load return first
30
Components of Water Side Systems
A. Basic System
d. Temperature of water leaving the water chiller should be no lower than 2.8°C to prevent freezing.
e. Performance of a chilled water system is closely related to:
i. Temperature of water entering the coil (TWE)
ii. Temperature of water leaving the coil (TWL)
iii. Difference differential (TWE-TWL)
f. Note:
i. Temperature TWE directly affects the power consumption in the compressor.
ii. Temperature differential is closely related to the volume flow of chilled water and thus the size of the
water pipes and pumping power.
C. Piping Design
Maximum water velocity in pipes is governed mainly by:
Pressure drop Select a pipe size for desired total flow rate and available or allowable pressure drop
Pipe erosion Impingement of rapidly moving water containing air bubbles and impurities on the inner
surface of the pipes and fittings.
Erosion occurs only if solid matter is contained in water flowing at high velocity
Noise Flow turbulence
Cavitation
Release of entrained air
Water hammer Transient pressure impact on a sudden closed valve
31
D. Design Criteria for Chilled Water System
a. Water velocity ≥ 0.6 m/s: Transport the entrained air to air vents
b. From friction chart, with the aforesaid criteria, the pipe diameter could be read out.
100 to 400 Pa/m Compromise energy costs, investments, age corrosion
< 250 Pa/m Pipe diameter: < 50mm or less
200 Pa/m Closed water systems
135 Pa/m Open water systems
F. Air Elimination
a. If air and other gases are not eliminated from the flow circuit,
they may slow or stop the flow through the terminal heat transfer elements and
cause corrosion, noise, reduced pumping capacity, and loss of hydraulic stability.
b. Air can be removed by an elimination valve installed at the point of lowest solubility.
c. Manual vents: installed at high points to remove all air trapped during initial operation.
d. Shutoff valves: installed on any automatic air removal device to permit servicing without draining the system
H. Water Treatment
Aims to evaluate the following parameters in the chilled water system:
a. PH value
b. Turbidity
c. Total iron increment
d. Total copper increment
e. Total dissolved solid
f. Nitrite
g. Bacteria count
32
L. Pipe Insulation
a. External pipe insulation should be provided to chilled and hot water system for the sake of
i. Energy saving.
ii. Prevention of surface condensation.
iii. High-temperature safety protection.
b. Depends on the operating temperature of the inside water, the pipe diameter, and the types of service.
M. Expansion Tank
a. Provides a space into which the non-compressible liquid can expand or from which
it can contract as the liquid undergoes volumetric changes with changes in temperature.
b. Provides an interface point between the system fluid and a compressible gas,
to allow for this expansion or contraction,
c. 2 basic configurations:
Open tank A tank open to the atmosphere)
Diaphragm tank A flexible membrane is inserted between the air and the water
(Bladder tank)
N. Types of Valve
a. Valves are used to regulate or stop the water flow in pipes
b. Manually
i. Hand-operated valves are used to stop or isolate flow, regulate flow, prevent reverse flow and regulate
water pressure.
c. Automatic control systems
i. Valves used in automatic control systems are called control valves.
d. Basic construction of a valve:
i. A disk to open or close the water flow.
ii. A valve body to seat the disk and provide the flow passage.
iii. A stem to lift or rotate the disk, with a hand wheel or a handle.
O. Gate Valves
a. Disk of a gate valve is in the shape of a “gate” or wedge.
b. When the wedge is raised at the open position, a gate valve does not add much flow resistance.
c. Either fully opened or closed, an on/off arrangement.
d. Used as isolating valves for pieces of equipment or key components,
Example: Control valves, for service during maintenance and repair
Q. Check Valves
a. Use to prevent, or check, reverse flow.
b. Swing check valve
i. It has a hinged disk.
ii. When the water flow reverses, water pressure pushes the disk and closes the valve.
c. Lift check valve
i. Upward regular flow raises the disk and opens the valve, and reverse flow pushes the disk down to its seat
and stops the backflow.
ii. Install at the discharge of pump
R. Butterfly Valves
a. Has a thin rotating disk.
b. Varies within a quarter-turn from fully open to fully close.
c. Exhibits low flow resistance when it is fully opened.
d. With an actuator, a butterfly valve used for control purposes.
e. May be used for throttling purposes in addition to on/off control.
f. Used in large pipes.
33
S. Water Control Valves
a. Regulate or stop water flow in a pipe either manually or by means of automatic control systems.
b. Adopted in water systems can modulate water flow rates by means of automatic control systems
T. Valve Actuators
a. A device which receives an electric or pneumatic analog control signal from the controller.
b. Closes or opens a valve, modulating the associated process plant,
and causes the controlled variable to change toward its set point.
c. Used to position control valves
d. Solenoid Actuators
i. A magnetic coil to move a movable plunger connected with the valve stem.
ii. For on and off control
iii. For small valves
e. Electric Actuators
i. Move the valve stem by means of a gear train and linkage.
ii. On/off mode: Motor moves the valve in one direction, and when the electric circuit breaks,
the spring returns the valve stem to the top position.
iii. Modulating mode: Motor can rotate in both directions, with spring return when the electric circuit breaks.
V. Cooling Coil
a. Corrugated fins can increase convective heat transfer coefficient and hence higher transfer rate
W. Centrifugal Pumps
a. Transporting chilled water, hot water, and condenser water because of their high efficiency and reliable operation.
b. Accelerate liquid and convert the velocity of the liquid to static head.
c. Consists of an impeller rotating inside a spiral casing, a shaft, mechanical seals and bearings on both ends of the
shaft, suction inlets, and a discharge outlet.
d. Types of Pumps
i. End Suction
ii. Horizontal Split-casing
iii. Vertical Inline
34
Smoke Extraction System
A. Smoke Extraction System
a. To remove hot smoky gases from the upper parts of a compartment and
b. To introduce air from outside into the lower parts of the compartment.
b. An alternative to the dynamic smoke extraction system if the following 3 conditions are satisfied:
i. Each smoke reservoir <500 m2 in area should be provided under the ceiling by fixed or automatically
operated smoke screen.
ii. Horizontal distance between the perimeter of any smoke reservoir and the external wall of building
where smoke outlets are installed,
<30m and 1 side of its reservoir shall abut the external wall.
iii. Aggregate area of smoke outlets > 2% of the floor area, and that
at least half of these outlets are openable by automatic actuating devices.
c. May only viable for single storey warehouse, depot or hanger etc.
35
C. Requirements for Premises
i. Basements >3 levels or which exceed 230 m2 of usable floor.
ii. Hotels: Both low rise and high rise.
iii. Industrial/ godown buildings: Both low rise and high rise.
iv. Audio/Visual Production Facilities.
v. Container Terminal Yards and Freight Stations.
vi. Railway Marshalling Yards
b. Might be exempted where the compartment is small, the fire risk is low, or smoke can be purged alternatively.
36
E. Multi-zone Smoke Extraction Systems
a. Under normal situation, smoke extraction fan and supply/makeup air fan are shut down,
and all the motorized fire and smoke dampers in both extraction and supply systems are closed.
b. Under an emergency situation,
if a fire occurs in zone 1, the smoke detector will be activated and automatically send a signal to start up both the
extraction and supply/make-up air fans.
c. Move the motorized fire and smoke dampers serving zone 1 to the open position.
All other motorized fire and smoke dampers shall remain closed.
d. If the smoke reaches zone 1 and moves into an adjourning zone, say zone 2,
the smoke detector in zone 2 will open the motorized fire and smoke dampers for zone 2.
This will reduce the airflow previously being handled in zone 1 by approximately 50%.
e. If there is a failure of the smoke extraction fan,
both the supply and extraction systems shall shut down and all motorized fire and smoke dampers return to the
closed position.
f. If there is a failure of the supply/make-up fan,
only the supply system shall be shut down and all motorized fire and smoke dampers on the supply duct return to
the closed position.
g. Extraction system shall continue to function.
h. 1 smoke extraction/make-up air system can serve up to 10 separate above ground fire compartments.
The system shall be capable of fully operating any 1 of the compartment
except for “Internal means of escape” in hotel where 2 compartments shall be capable of operating simultaneously
f. Except for simple devices, all instruments, meters, etc. used for testing purposes shall:
i. Be provided in duplicate.
ii. Have a manufacturer‘s claimed accuracy of not more than plus or minus two percent of range.
iii. Be manufactured to an appropriate British Standard or recognized equivalent standard.
iv. Calibrated by a recognized testing or calibration laboratory < 3 months prior to the date of test.
v. Calibration certificate provided by the laboratory shall be available during the test
g. Full and complete records should be taken of all tests and the results thereof including :
i. Records of pressure testing during construction.
ii. Serial no. type and owner of all instruments used, with a copy of the calibration certificates.
iii. Actual measurements taken.
iv. Corrected measurement.
v. Resulting air flows.
vi. Serial no. type and use of every device checked.
vii. Date and time of test.
viii. Signature of operator/tester or supervisor and any witness for each test.
ix. Signature of acceptance of and by designer.
37
G. Maintenance of Dynamic Smoke Extraction System
a. For dedicated systems that only operate in emergency,
they should be actuated by the owner at an interval of < 3 months,
and checked to ensure that all functions and sequences are operating correctly.
b. For dual purpose systems that operate continuously at a low level and at an increased level in emergency,
they should be actuated into emergency mode by the owner < 6 monthly intervals and checked to
ensure that all emergency functions sequence and operate correctly.
e. A record log should be maintained by the owner and all systems providing a complete record of the actions carried
out and the results thereof under signature of the supervisor and witness.
Records should be retained for a period of at least 7 years and shall be made available at the request of FSD.
38
Staircase Pressurization System
A. Pressurization of Staircases
a. A system to protect the staircases against the ingress of smoke by maintaining the air within staircases at pressures
higher than adjacent parts of building
b. Purpose:
i. To maintain a tenable environment in the staircase for occupants to evacuate from the building during
the early period of a fire incident.
ii. To provide conditions within the staircase to assist FSD personnel to conduct search and rescue
operations, locate and control the fire.
b. No of pressurized staircase shall be determined by the cubical extent of the basement or building
Cubical Extent (CE(m3)) No. of Staircases
For basements of ≥3 levels 7000 <CE< 56000 1
56000 <CE< 112000 2
112000 <CE< 168000 3
CE>168000 4
For buildings other than hotels, hospitals & sanatoria 28000 <CE< 56000 1
56000 <CE< 112000 2
112000 <CE< 168000 3
CE>168000 4
For hotels, hospitals and sanatoria 7000 <CE< 56000 1
56000 <CE< 112000 2
112000 <CE< 168000 3
CE>168000 4
Compartmentation
39
Single point injection Multiple point injection
Pressurized air is supplied to the staircase at 1 location, For tall buildings, a number of injection points is used to
normally at the top (for building height < 30 m). prevent loss of pressurization due to opening of doors
near the air supply point (for building height > 30 m).
40
b. Over-pressure relief
i. Air flow rate will vary from a minimum based on the total door leakage when all door are closed,
to a maximum when 3 single leaf entry doors and the exit door are open.
ii. A method of varying the air volumes must be introduced if over pressurization of the staircase is to be
avoided.
D. Design Parameters
a. Leakage area
i. It is necessary to identify the leakage paths through which air can escape from the pressurized space and
assess their size
ii. Example: Area of the cracks round doors, windows and other places where air will escape
iii. By analogue to electrical circuits, the effective leakage area of a flow path is given by:
41
b. Other essential requirements:
i. Provision of pressure relief system.
ii. Activation of smoke detection system with smoke detectors within 1m of access door at the approach
side.
iii. Installation of smoke detection at the intake to stop pressurization fans if smoke is detected
iv. Installation of air flow switch at the discharge to confirm air flow.
v. All electrical equipment are rated for 250˚C for at least 1 hr.
vi. Duplicate fans and motors for hotels and hospitals.
vii. Manual on/off control required at control panel.
viii. Position of intake shall be 5m from discharge point and shielded by upstair wall extending 1 m above the
intake point.
ix. Availability of low resistance air path for air vented through the doors.
f. Identify all leakage paths which air can escape from the pressurized space and determine the rate of air leakage for
the appropriate pressure differential.
g. Air flow through a restriction is given by:
1
𝑄 = 0.827 × 𝐴 × 𝑃𝑁
For cracks around doors, N is taken as 2.
h. Air velocity through open doors should be estimated and compared with the minimum requirements.
i. If the requirements are not satisfied, the air supply proposed must be increase.
j. FSI Code specifies a minimum average egress velocity through doorways of 0.75 m/s
where 3 single leaf doors and the largest exit door are opened.
k. Total all airflow out of each pressurized space and increase this total by 25% for unidentified leakage from
pressurized space.
l. This will give the proposed air supply for each pressurized space.
m. Air supply estimated in above must be provided at the duct terminated in each pressurized space.
n. Fan capacity, duct size and position of intake grilles must be decided.
The air supply with allowance made for duct leakage should be used to determine the fan capacity.
o. Escape of the pressurizing air from the building should be considered and appropriate method of venting specified.
p. Operation of system must be considered.
q. Position of smoke detectors should be specified
42
s. Calculation Example
i. Determine the design supply flow rate of the staircase pressurization system using the leakage data given
in the following Table.
iii. Equation:
A1, A2, A3 Area of entry doors (single leaf) 1.6m2
Aexit Area of exit door 3.2m2
1
Qleakage Leakage flow rate through other doors
0.827 × 𝐴 × 𝑃 2
P Pressure differential and taken 50Pa
1
v. 𝑄𝑙𝑒𝑎𝑘𝑎𝑔𝑒 = 0.827 × 0.19 × 502 = 1.111𝑚3 /𝑠
7.111𝑚3
vi. 𝑄𝑡𝑜𝑡𝑎𝑙 = 0.75(1.6 × 3 + 3.2) + 1.111 =
𝑠
vii. To allow for unidentified leakage as suggested by BS 5588: Part 4, 25% safety factor is added,
air supply flow rate of 7.111 x 1.25 = 8.889 m3/s is therefore designed.
viii. If the building height is 63m,
the minimum number of injection points is 63/12 = 5.25 (say 6) and
the air supply flow rate at each point is 1.482 m3/s.
43
Ventilation/ Air Conditioning Control System
A. Definition
a. An automatic control system, designed to stop mechanically induced air movement within a designated fire
compartment,
i.e. allow smoke to rise and form a layer at ceiling level which will not be disturbed by air into the smoke layer.
b. System is actuated by smoke detectors/ building fire alarm system and provided with a central, manually operated
back up facility.
C. Override Control
Any one of the following methods of override control shall be used:
Method “A” If the compartment/unit is provided with a smoke detector,
fire alarm system or sprinkler system,
on activation of that system,
all fans serving the compartment shall be shut down.
Method “B” Smoke detectors of a type suitable for use in air ducts,
shall be installed in the exhaust and/or recirculation ductwork serving the compartment/unit.
When sensing smoke, all fans in the mechanical ventilating system serving the compartment/unit will be
automatically shut down
Method “C” Override control can be arranged to completely shut down all the fans in the building instead of isolated
compartments/units.
When the smoke detector activated, all the fans in the affected compartment will be shut down
b. For buildings where central mechanical fresh air supply and/or exhaust systems are installed,
either the central fresh air supply and/or exhaust system shall be shut down,
or the fresh air and/or exhaust to the affected compartment/unit shall be closed off from the central system by
actuation of a local motorized smoke damper.
c. Shut down of the mechanical ventilating systems utilizing a multiplex automatic fire alarm or building automation
system shall be permitted by FSD.
44
D. Acceptance Testing of Ventilation/ Air Conditioning Control System
a. Override control of the ventilation/air conditioning control system shall be tested to ensure satisfactory operation
at alarm condition to the satisfaction of FSD
45
Testing and Commissioning of Automatic Control Systems
A. Summary of Commissioning Requirements
a. Building services plant and control system should be inherently commissionable.
b. Contractor and client must allow sufficient time for the complete commissioning process.
c. Formation of a commissioning management team.
d. Maximizing off-site pre-commissioning activities.
e. Adoption of thorough commissioning procedures.
f. Implementation of post occupancy checks to confirm the performance of the control system and the attainment of
required internal environmental conditions.
B. Energy Consumption
a. In order to minimize energy consumption, it is crucial that the buildings services systems are controlled properly.
b. Set-up and operation of a control system should be checked.
c. Incorrectly controlled building services systems can result in excessive energy consumption:
i. Unnecessary periods of plant operation.
ii. Poor control to set points.
46