New Microsoft Word Document
New Microsoft Word Document
An alternating current of steady state value passes through the earth path from
E to A and the voltage drop between E and B is measured.
The auxiliary earth electrode A must be driven in at a point further away from E
and the above test repeated until the group of three readings obtained are in
good agreement.The alternating current source is used to eliminate the
electrolytic effect.
The test can be performed, with current at power frequency from a double
wound transformer, using a voltmeter and an ammeter as shown in the figure
above by mean of an earth tester.
The earth tester is a special type of Megger, which sends AC through earth and
DC through the measuring instrument. It has got four terminals. Two terminals
are shorted to form a common point which is connected to the earth electrode
under test. The other two terminals are connected to the auxiliary electrode A
and B respectively. The value of the earth resistance is indicated by the
instrument directly when its handle is turned at a uniform speed.
The resistivity of the soil is usually measured by the four spike methods. In this
method the four spikes arranged in the straight line are driven into the soil at
equal distance. A known current is passed between electrode C1 and C2 and
potential drop V is measured across P1 and P2. The current I developed an
electric field which is proportional to current density and soil resistivity. The
voltage V is proportional to this field.
The soil resistivity is proportional to the ratio of the voltage V and current I and
is given as
ρ=2∏SR
Where ρ is the resistivity of the soil and their unit is ohmmeters. S is the
horizontal space between the spikes in m and b is the depth of burial in metre.
The earthing calculation aids in the proper design of the earthing system.
Using the results of this calculation, you can:
Prerequisites
is
is the thermal capacity of the conductor per unit
volume(Jcm - 3ºC - 1)
The material constants Tm, αr, ρr and TCAP for common conductor
materials can be found in IEEE STD 80. For example. Commercial hard-
drawn copper has material constants:
Tm = 1084 ºC
αr = 0.00381 ºC - 1
ρr = 1.78 μΩ.cm
TCAP = 3.42 Jcm - 3ºC - 1.
The resistivity properties of the soil where the earthing grid will be laid
is an important factor in determining the earthing grid's resistance with
respect to remote earth. Soils with lower resistivity lead to lower overall
grid resistances and potentially smaller earthing grid configurations can
be designed (i.e. that comply with safe step and touch potentials).
IEEE Std 80 gives typical values for surface layer material resistivity in
dry and wet conditions (e.g. 40mm crushed granite = 4,000 Ω.m (dry)
and 1,200 Ω.m (wet)).
This derating factor will be used later in Step 5 when calculating the
maximum allowable touch and step voltages.
A good earthing grid has low resistance (with respect to remote earth) to
minimize ground potential rise (GPR) and consequently avoid dangerous
touch and step voltages. Calculating the earthing grid resistance usually
goes hand in hand with earthing grid design - that is, you design the
earthing grid to minimize grid resistance. The earthing grid resistance
mainly depends on the area taken up by the earthing grid, the total length
of buried earthing conductors and the number of earthing rods /
electrodes.
IEEE STD 80 offers two alternative options for calculating the earthing
grid resistance (with respect to remote earth) - 1) the simplified method
and 2) the Schwarz equations, both of which are outlined briefly below.
IEEE Std 80 also includes methods for reducing soil resistivity and a
treatment for concrete-encased earthing electrodes (in Section 14.6).
Simplified Method
Where is the earthing grid resistance with respect to remote earth (Ω)
The Schwarz equations are a series of equations that are more accurate
in modeling the effect of earthing rods / electrodes. The equations are
found in IEEE Std 80, as follows:
Where is the earthing grid resistance with respect to remote earth (Ω)
is the earth resistance of the grid conductors (Ω)
is the earth resistance of the earthing electrodes (Ω)
is the mutual earth resistance between the grid conductors and
earthing electrodes (Ω) .And the grid, earthing electrode and
mutual earth resistances are:
The maximum grid current is the worst case earth fault current that
would flow via the earthing grid back to remote earth. To calculate the
maximum grid current, you firstly need to calculate the worst case
symmetrical earth fault current at the facility that would have a return
path through remote earth (call this ). This can be found from the
power systems studies or from manual calculation. Generally speaking,
the highest relevant earth fault level will be on the primary side of the
largest distribution transformer (i.e. either the terminals or the delta
windings).
Not all of the earth fault current will flow back through remote earth. A
portion of the earth fault current may have local return paths (e.g. local
generation) or there could be alternative return paths other than remote
earth (e.g. overhead earth return cables, buried pipes and cables, etc).
Therefore a current division factor must be applied to account for the
proportion of the fault current flowing back through remote earth.
One of the goals of a safe earthing grid is to protect people against lethal
electric shocks in the event of an earth fault. The magnitude of ac
electric current (at 50Hz or 60Hz) that a human body can withstand is
typically in the range of 60 to 100mA, when ventricular fibrillation and
heart stoppage can occur. The duration of an electric shock also
contributes to the risk of mortality, so the speed at which faults are
cleared is also vital. Given this, we need to prescribe maximum tolerable
limits for touch and step voltages that do not lead to lethal shocks.
The maximum tolerable voltages for step and touch scenarios can be
calculated empirically from IEEE STD for body weights of 50kg and
70kg:
50kg person:
70kg person:
50kg person:
70kg person:
Normally, the potential difference between the local earth around the site
and remote earth is considered to be zero (i.e. they are at the same
potential). However an earth faults (where the fault current flows back
through remote earth), the flow of current through the earth causes local
potential gradients in and around the site. The maximum potential
difference between the site and remote earth is known as the ground
potential rise (GPR). It is important to note that this is a maximum
potential difference and that earth potentials around the site will vary
relative to the point of fault.
Now we just need to verify that the earthing grid design is safe for touch
and step potential. If the maximum GPR calculated above does not
exceed either of the touch and step voltage limits (from Step 5), then the
grid design is safe.
However if it does exceed the touch and step voltage limits, then some
further analysis is required to verify the design, namely the calculation
of the maximum mesh and step voltages as per IEEE Std 80.
Geometric Factor n
The geometric factor is calculated from IEEE Std 80:
With
Irregularity Factor Ki
For grids with earthing electrodes on the corners and along the
perimeter:
The maximum allowable step voltage is calculated from IEEE Std 80:
The effective buried length for all cases can be calculated by IEEE
Std 80:
What Now?
Now that the mesh and step voltages are calculated, compare them to the
maximum tolerable touch and step voltages respectively. If:
, and
Then by the initial specification of the earthing grid and the following
equation we can calculate the resistance of the grid
We can change in the specification of the grid to get the desired
resistance
then we calculate the resistance of all ground rods from the following
equation:
Rg=(Rh*Rn)/(Rh+Rn)
By changing in the specification of the ground rods and the
earthing conductor we can get the desired resistance of the
grid.
3.Neutral Grounding
In neutral grounding system, the neutral of the system or rotating system or transformer is
connected to the ground. The neutral grounding is an important aspect of power system design
because the performance of the system regarding short circuits, stability, protection, etc., is
greatly affected by the condition of the neutral. A three phase system can be operated in two
possible ways
For the solidly neutral grounded system, it is necessary that the ground fault
current should not exceed 80% of the three-phase fault. It is usually used for
keeping the fault current within safe limits.
Resistance grounding
In this type of neutral grounding, the neutral of the system is connected to
ground through one or more resistance. Resistance grounding limits the fault
currents. It protects the system from transient overvoltages. Resistance
grounding decreases the arcing grounding risk and permits ground-fault
protection.
The value of resistance used in the neutral grounding system should neither be
very high nor be very low shown in the figure below.
Reactance Grounding
In reactance grounded system, a reactance is inserted between the neutral and
ground to limit the fault current as shown in the figure below.
To minimize transient overvoltages, the
ground fault current in a reactance grounded system should not be less than
25% of the three phase fault current. This is considerably more than the
minimum current desirable in resistance grounded systems.