Earthmat Calculation (Rev.a)
Earthmat Calculation (Rev.a)
Isc tC ts h K p ps d A mm 2 D Lx By NE
kA sec sec mts o-m o-m DATA mts mm2 mts mts mts
4 1 0.5 0.60 80 600 3000 0.026 520 3 81.0 15.8 22
Tcap ρr αr Tm Ko Ta
J/cm3 µΩ/cm Factor at20.c Temp.in 0C Temp.in 0C
3.85 8.62 0.00378 1084 245 45
0.000385 m Refer Table no. 1 of IEEE 80-2000
I SC
AS per IEEE-80-2000
Amm2 =
TCAP. K 0 + Tm
.Ln
α ρ
c r r K 0 + Ta
t
Amm2 = 29.82
1 − ρ / ρs
Cs = 1 − 0.09 hs = 0.15
2hs + 0.09
Cs = 0.82
0.157
E step70 = (1000 + 6c s * ρ s )
ts
0.157
Etouch70 = (1000 + 1.5 * C s * ρ s )
ts
h
K h = 1+ = 1.26 h0 = 1 AS per IEEE-80-2000
h0
Km = 0.38
Ls = 0.75 Lc+0.85 LR Ls = 768.6 Mtrs. Ls= length of effective buried conductor with
ground rod
I G = D f * S f * I sc IG = 2000 Df = 1
Sf = 0.5
1 1 1 1
KS =
2Π 2 h
+ + 1 − 0. 5 n − 2 ( )
D+h D
Ks = 0.23
ρ * K S * Ki * IG
ES = Es = 837.7
LS LT Total length of buried
LT = 1016.0 Mtrs. conductor = Lm
100 * ρ (L )2
Rg = ( ) * log e ( 2 * T Rg = 1.87
Π * 2 * LT h *t
100 * ρ 4l
R= * LN RROD = 42 d = 3.2 cm
2 * Π * l d Nos. of rods = 22 Nos.
Since the rod are inserted parallel, overall resistance of all = 1.91
rods
R ROD * R g
The rod resistance is again parallel to the grid =
resistance ,the overal resistance will be R
ROD + R g
RNET Net Resistance = 0.95 Ohm.
Ground Potential rise I G * R NET = 1891.1
Summary of results :
Power House on which the design of earth mat is done = 81 x 15.8 mtrs
NOTES :
a) Size of the conductor choosen is 65X8mm (Mild steel coated with copper)
b) Rod (Electrode) diameter choosen to be 32mm (Mild steel coated with copper)
c) Calculations are as per IEEE-80 & 665