En 1996-1-1 Reinforced Masonry Design Example 1: (Note: This Uses The Uk National Annex NDP Values)
En 1996-1-1 Reinforced Masonry Design Example 1: (Note: This Uses The Uk National Annex NDP Values)
112.5
3.00
4.0m
900 c/c
42.50
20.00
440
10.00
Therefore uls design moment = (1,35 x 41,27 x 3,65 / 3) + (1,50 x 10,76 x 3,65 / 2)
1
The design total lateral force at the ultimate limit state has been derived from the soil
pressure, nominal surcharge loading and partial safety factors for loading as
71,85kN/m and the design bending moment is to be taken as 97,24kN.m/m.
Design wall as flanged beam, assume pocket width along wall length of 235mm (1-
brick)
Flange depth, tf = d/2 = 270/2 = 135mm
From Clause 5.5.3 (3) width of flange, beft is lesser of:
a) 235 + (12 x 135) = 1855mm
b) 900 mm (actual pocket spacing to be used)
c) 3650/3 = 1217mm
Therefore flange width to be used, beft = 900mm
The declared compressive strength of the brick masonry units is 50N/mm2, Group 1.
Thus normalised compressive strength of the bricks, fb, is given by:
fb = 1,0 x 0,85 x 50N/mm2
fb = 42,50N/mm2
where test moisture conditioning factor is 1,0 and 0,85 is the shape factor δ, both
taken from BS EN 772 Part 1
Using Category I bricks with Class 1 Execution Control the partial factor for materials
properties γM is 2,0 from Table NA.1 of the UK National Annex
Hence fd = fk/γM = 11,63/2,0 = 5,82N/mm2
Using the Q factor approach from BS5628 Part 2 which is compatible with the
Eurocode 6 methodology then:
The moment of resistance factor Q is given by:
Q = MEd/bd2 = 97,24 x 106 x 0,9 / 900 x 2702 = 1,334
And Q = 2c(1-c)fd
Therefore 1,334 = 11,63c – 11,63c2
2
c = 0,868 which is the lever arm factor which does not exceed 0,95 limiting
Hence the lever arm z is 0,868 x 270 = 234mm
As required = MRd/fyd z from Eqn (6.22)
Using Grade 500 deformed steel bars with a yield strength, fyk, of 500 N/mm2 and
with γM as 1,15 from the UK National Annex
fyd = 500/1,15 = 435N/mm2
As required = 97,24 x 0,9 x 106 / 435 x 234
As required 860mm2
Therefore use 2no. deformed 25mm diameter bars, Grade 500, which provide 982
mm2. If the bars are placed centrally in the pocket the cover is (113/2 - 25/2) = 44mm
which is adequate for durability protection when a C35/45 concrete infilling to BS
EN 206 Part 1 and BS 8500 is used for exposure situation MX3. (Table NA.9 of the
UK National Annex requires a minimum thicness of concrete cover of 30mm using a
20mm aggregate size).
Main tensile steel provides 3,7% of area of infill pocket which is less than 4% limiting
given in Clause 8.2.7(4).
Check that the limiting compressive moment of the brickwork section is not exceeded
MRd ≤ fd bef tf (d – 0,5tf) Eqn (6.28)
This very slightly falls short of the design shear applied, VEd, of 71,85kN/m run of
wall (by 2,3%) and hence 6mm diameter Grade 200 austenitic stainless steel formed
closed shear links will be provided at pocket positions only at 225mm vertical centres
and placed in brickwork bed joints. Localised protection of 25mm diameter bars
3
against stainless steel bars will be required at link to main vertical steel spot contact
points to avoid potential galvanic action between dissimiliar steel types.
Therefore using nominal shear reinforcement localised in pocket positions, VRd2 is:
VRd2 = 0,9d (Asw /s) fyd (1 + cot α)sin α from Eqn. 6.42 considering reinforced
pocket alone as vertical beam element with 235mm width pocket dimension
where fyd = 200/1,15 = 174N/mm2 for Grade 200 steel
VRd2 = 0,9 x 270 x 56mm2 x 174 x 10-3 /225 = 10,52kN (11,69kN/m run of wall)
where Asw is 56mm2 for 2no. 6mm diameter bars as formed closed shear link
and (1 + cotα)sinα = 1,0 for horizontally placed shear links (α = 90°)
VRd1 + VRd2 = 70,20 + 11,69 = 81,89kN/m run of wall
This exceeds the design shear applied, VEd, of 71,85kN/m run of wall
(VRd1 + VRd2)/ t l = (81,89 x 0,9 x103) / (328 x 900) = 0,25N/mm2
And (VRd1 + VRd2)/ t l ≤ 2,0N/mm2 limiting from Eqn. 6.37
And VRd1 + VRd2 ≤ 0,25fd bd limiting from Eqn. 6.43 as an additional verification for
beam element
0,25fd bd = 0,25 x 5,82 x 235 x 270 x 10-3 = 92,32kN (102,58kN/m run of wall)
And 102,58kN/m is greater than 81,89kN/m run of wall.
Note that spacing of shear links at 225mm vertical centres slightly exceeds 0,75d
(203mm) or 300mm, whichever is lesser, as given by Clause 8.2.7(6), but as any shear
steel requirement is very marginal here this is considered practically acceptable in
this particular design case.
Reinforcement lapping
Consider now whether the main tensile reinforcement can be curtailed
Use 20mm diameter reinforcement to lap on. In order to curtail the 25mm diameter
bars in the tension zone, Clause 8.2.5.4 must be satisfied. The moment condition is
appropriate and therefore the design moment capacity of the 20mm diameter bars
must be at least twice the design moment due to applied lateral loads for curtailment.
Design moment capacity of 2 no. 20mm diameter bars per pocket, As = 628mm2,
assume c = 0,905
MRd = (628 x 0,905 x 270 x 435 x 10-6) = 66,75kN.m per 900mm pocket spacing
Q = M/bd2 = (66,75 x 106) / (900 x 2702) = 1,017 and fd = 5,82N/mm2 as before.
c = 0,905 is the correct assumption substituting into and solving the interaction
equation for c from above
Thus 25mm diameter bars may be stopped where the design moment due to applied
lateral loads, MEd = (66,75 x 0,5/0,9) = 37,08kN.m/m run of wall.
From a consideration of the design lateral loads upon the wall stem the applied design
moment of 37,08kN.m/m run of wall is achieved at 2,56m from the top of the wall
(from retained earth level).
Check that 25mm diameter bars will extend at least an effective depth or 12 bar
diameters, whichever is greater, beyond the point where they are no longer needed.
The 20mm diameter bars will resist a design a moment of:
4
66,75/0,9 = 74,17kN.m/m run of wall
From a consideration of the design lateral loads this will occur at 3,32m from the top
of the wall. Therefore curtailment of 25mm diameter bars at 2,56m below top of wall
is satisfactory because:
a) An effective depth above this level is (3,32 – 0,270) = 3,05m, therefore curtailment
of 25mm diameter bars at 2,56m from top of wall is satisfactory,
b) And 12 diameters above this level (3,32 - 12 x 0,025) = 3,02m, therefore
curtailment of 25mm diameter bars at 2,56m from top of wall is also satisfactory
T20
T25
1400
12.63
13.81
T20
150
1.17
T25
It may be noted that at 2074mm above the spread foundation base the applied design
shear load is 17,36kN/m run of wall from a consideration of the lateral loads acting
on the wall stem and the corresponding design shear resistance is 54,00kN/m run of
wall taking fvd as 0,20N/mm2 minimum for 20mm diameter continuing bars with no
shear span enhancement and without shear link contribution.
5
Consider the necessary extent up the wall stem for the 6mm diameter shear links
If shear links are provided from the base of the wall stem (from the top of the spread
foundation level) to 1000mm above this position only then from a consideration of the
design lateral loads upon the wall stem the design shear force applied at this level,
VEd, is 41,09kN/m run of wall
And minimum design shear resistance of section at this level ignoring any shear span
enhancement and without shear link contribution is:
VRd1 = fvd bd = (0,21 x 900 x 270 x 10-3) = 51,03kN for a 900 mm flange length
(56,70kN/m run of wall)
And 56,70kN/m exceeds 41,09kN/m run of wall
Therefore 6mm diameter formed closed shear links at 225mm vertical centres should
be provided for a distance of 1,0m up from the base of the wall stem (top of spread
foundation) only to each reinforced pocket position along the wall length.