Process Instrumentation Terminology Performance Chara
Process Instrumentation Terminology Performance Chara
Accuracy, measured - The maximum positive and negative deviation observed in testing
a device under specified conditions and by a specified procedure.
Note 1: It is usually measured as an inaccuracy and expressed as accuracy.
Note 2: It is typically expressed in terms of the measured variable, percent of span,
percent of upper range- value, percent of scale length or percent of actual output reading.
Accuracy rating - A number or quantity that defines a limit that errors will not exceed
when a device is used under specified operating conditions. See Figure 1.
Note 1: When operating conditions are not specified, reference operating conditions shall
be assumed.
Note 2: As a performance specification, accuracy (or reference accuracy) shall be
assumed to mean accuracy rating of the device, when used at reference operating
conditions.
Note 3: Accuracy rating includes the combined effects of conformity, hysteresis, dead
band and repeatability errors. The units being used are to be stated explicitly. It is
preferred that a ± sign precede the number or quantity. The absence of a sign indicates a
+ and a - sign.
Accuracy rating can be expressed in a number of forms. The following five examples are
typical:
a. Accuracy rating expressed in terms of the measured variable. Typical expression:
The accuracy rating is + 1"C, or ± 20 F.
b. Accuracy rating expressed in percent of span. Typical expression: The accuracy
rating is ±0.5% of span. (This percentage is calculated using scale units such as
degrees F, psig, etc.)
c. Accuracy rating expressed in percent of the upper range-value. Typical expression:
The accuracy rating is ±0.5% of upper-range value. (This percentage is calculated
using scale units such as kPa, degrees F, etc.)
d. Accuracy rating expressed in percent of scale length. Typical expression: The
accuracy rating is ±0.5% of scale length.
e. Accuracy rating expressed in percent of actual output reading. Typical expression:
The accuracy rating is ±1% of actual output reading.
Accuracy, reference - see accuracy, rating.
Actuating error signal - see signal, actuating error. adaptive control - see control,
adaptive.
Adjustment, span - Means provided in an instrument to change the slope of the input-
output curve. See span shift.
Accuracy Rating
Dead band – The range through which an input can be varied without initiating
observable response.
Dead time – The interval of time between initiation of an input change or stimulus and
the start of the resulting observable response.
Range – The region between the limits within which a quantity is measured, received or
transmitted, expressed as lower and upper values
Transducer - An element or device that receives information in the form of one quantity
and converts it to information in the form of the same or another quantity.
Note: This is a general term and definition and as used here applies to specific classes of
devices such as primary element, signal transducer, and transmitter.
Transmitter - A transducer which responds to a measured variable by means of a
sensing element, and converts it to a standardized transmission signal which is a function
only of the measured variable.
A measurement error is the difference between the measured value and the true value.
This difference from the true value can be a problem of precision or accuracy.
Several sources of error exist in most instruments - non- linearity, hysteresis (e.g., gear
back-lash), and sensitivity to environmental factors such as temperature, magnetic or
electrical fields are a few examples. Instrument error is often magnified by the fixturing
required in the measuring process. Poor electrical connection, improper fastening of
mechanical linkages, and loose clamps are examples of fixturing problems. Temperature
induced error, in addition to its effects on measuring instruments, affects the specimen
being measured. As temperature changes, the length (L) of a specimen changes.
The observed σ or standard deviation is a function of the causes contributing to the
variation. The equation is:
Response Times
Dead Time - The interval of time between initiation of an input change or stimulus and
the start of the resulting observable response.
Rise Time – The time required for the output of a system (other than first order) to
change from a small-specified percentage of steady state to a large specified percentage
of steady state.
Drawings and Symbols
EFD, Engineering Flow Diagram – A drawing showing all the major engineering details
of a plant or facility. This included the piping details; pipe size and specifications,
insulation, vessel sizes and ratings, pump sizes and instruments. There is little to no
information about the flow rates and energy transfers.
PFD, Process Flow Diagram – A drawing of a plant or facility that shows process flows,
instrumentation, controls. Missing are the piping details, sizes etc. The PFD frequently
has, in table form, the process and energy flows, capacity, etc. This document is used
frequently used to define control strategy or basis.
x x x x x x x
Hysteresis and Dead band – Did your valve move, how much?
Terms Used Interchangeably for Process Control
attenuation – filtering
open loop time constant – plant time constant – process time constant
total loop dead time – system dead time – plant dead time – process dead time
action – relative direction of change in output for a change in input (“direct” for changes in same
direction and “reverse” for changes in opposite direction)
automatic mode – PID controller mode to enable its set point to be locally adjusted by the
operator (also known as LOCAL and AUTO mode)
A/D – analog to digital converter typically used to convert an analog input to its digital value with a
resolution of 0.05% for a 12 bit converter with one sign bit
closed loop time constant – time it takes for the process variable to reach 63% of its change
after a time delay for a step change in the controller set point when the controller is in automatic.
The controller tuning must provide a non-oscillatory response for this term to be valid. For
integrating or runaway processes, the controller gain must be large enough for the control action
to bend over the response within the scale range.
controller action – relative direction of change in controller output for a change in the controlled
variable (”direct” for same direction and ”reverse” for opposite direction)
controller gain – tuning parameter multiplier for the proportional mode (dimensionless). It is the
multiplier for the integral and derivative modes in most industrial PI and PID controllers. It is the
100 percent divided by the proportional band.
controller output – the output of a PID controller (normally in percent for the control algorithm)
controller tuning – adjustment of the proportional, integral (reset), and derivative mode settings
for a PID controller
control interval – time interval between successive executions for digital devices (same as scan
or update time and the inverse of scan rate or frequency)
controlled variable – a controller input to be kept at a set point. It is often a process output such
as concentration, pH, pressure, temperature, or level but is normally in percent for the control
algorithm)
D/A – digital to analog converter typically used to convert a digital value to an analog output with
a resolution of 0.05% for a 12 bit converter with one sign bit
DDC mode – PID controller direct digital control mode to enable its output to be adjusted by a
sequence, interlock, or a computer (also known as ROUT mode)
dead band – minimum change in the input for a reversal of direction that will cause a change in
the output (important for a control valve and a manipulated variable)
dead time – time it takes for the process variable to get out of the noise band after a change in
the manipulated variable (same as time delay)
derivative action – controller output changes that are proportional to the rate of change of the
error or the controlled variable (derivative mode of a PID controller)
digital filter – a first order time constant in a digital device to attenuate noise
Distributed Component Object Model (DCOM) – a protocol that enables software components
to communicate directly over a network in a reliable and secure way
dynamic gain – ratio of the output amplitude to a sinusoidal input amplitude after transients have
decayed (also known as amplitude ratio and magnitude ratio)
feedback control – a control algorithm to reduce the error between the set point and the
controlled variable (most often a PID or model predictive controller algorithm is used)
filter time – time constant of a signal filter that is usually applied to the PV but can be inserted
anywhere in the configuration as a function block (seconds or minutes)
final element – device used to adjust the manipulated variable (typically it is a control valve but it
can be a variable speed drive, compressor vane, or an electrical heater)
I/P – current to pneumatic converter mounted on the valve to convert a controller output to a
pneumatic signal for the actuator (often integrated with positioner)
integral action – controller output changes that are proportional to the integral of the error
(integral mode of PID controller)
integrating process – a process that ramps at a constant rate for a change in the manipulated
variable when the controller is in manual if there are no disturbances
integrating process gain – per cent change in ramp rate per percent change in controller output
(%/sec/%).
limit cycle – continuous oscillation of nearly equal amplitude that persists for a variety of
controller gains (caused by a resolution limit or a nonlinearity such as stick-slip and pH)
manipulated variable – variable adjusted by a controller output (most often it is a process input
such as flow but it can be the set point of a process variable for cascade control) (normally in
process engineering units).
manual mode – operator adjusts the controller output directly (PID algorithm is suspended but
will provide a bumpless transfer to automatic, cascade, or supervisory control)
matrix condition number – a measure of the sensitivity of a matrix and of the ability of MPC to
effectively decouple the process so that each controlled variable can be maintained at its target.
Matrices that have a condition number around 1 are considered well conditioned, while those
much greater than 1 are considered ill conditioned.
model predictive control – model based control of future trajectory of a process variable from
the changes of manipulated variables (same as constrained multivariable predictive control)
move limit – largest change in the manipulated variable per execution of a model predictive
controller (normally set large for simulation test but reduced during commissioning)
nonlinear system – gain, time constant, or time delay and hence controller tuning settings are
not constant but a function of time, direction, operating point, or load
open loop gain – final % change in the controller input divided by the % change in the controller
output with the controller in manual for a self-regulating process. It is dimensionless steady state
gain that is the product of the gains for the manipulated variable (e.g. valve gain), the process
variable, (i.e. process gain), and controlled variable (e.g. measurement span). It is often simply
referred to as the process gain.
open loop time constant – time it takes for the process variable to reach 63% of its change after
its time delay for a step change in controller output when the controller is in manual. It can
originate in the final element, process, or measurement. It is often simply referred to as the
process time constant.
oscillation period – time between successive peaks in any type (damped or undamped) of
oscillation (the period of damped oscillations is usually larger than the ultimate period)
penalty on error (PE) – an MPC controlled or constraint variable tuning value that determines
how much the variable is penalized for errors and violations. The higher the value, the more
aggressively the controller provides feedback correction
penalty on move (PM) – a tuning value of an MPC manipulated variable that determines how
much the manipulated variable is penalized for moving (also known as move suppression). The
higher the value, the slower the moves
positioner – controller mounted on the valve whose set point is desired position and whose
controlled variable is shaft position (also known as a digital valve controller)
primary controller – master or outer loop controller whose output is the set point (CAS set point)
of a secondary controller in a cascade control system
process action – relative direction of change in process variable for a change in the manipulated
variable (“direct” for same direction and “reverse” for opposite direction)
process gain – final change in the process variable divided by the change in the manipulated
variable (commonly used as the open loop gain)
proportional band – percent change in control error that causes a 100 percent change in
controller output (%). It is equivalent to 100 percent divided by controller gain.
rate time – tuning parameter multiplier for the derivative mode of a PID controller (seconds)
remote cascade – mode where the preferred value for the controlled variable comes from model
predictive control, sequence, or supervisory controller (RCAS)
remote output – mode where the controller algorithm is suspended and the controller output is
set by a discrete action, interlock, or sequence (ROUT)
reset time – tuning parameter divisor for the integral mode of a PID controller (seconds per
repeat). It is the inverse of the reset setting given in repeats per second
repeatability – short-term maximum scatter in the output for the same input approached from the
same direction and at the same conditions (see reproducibility)
reproducibility – long-term maximum scatter in the output for the same input approached from
both directions and at the same conditions (includes repeatability and drift)
resolution – minimum change in the input in the same direction that will cause a change in the
output (important for a control valve and a manipulated variable)
runaway process - a process that accelerates for a change in the manipulated variable when the
controller is in manual if there are no disturbances
saturation – controller output is at either low or high limits that are normally set to match the
valve being shut and wide open, respectively (controller is effectively disabled)
scan time – time interval between successive scans for digital devices (same as update time or
control interval and the inverse of scan rate or frequency)
secondary controller – slave or inner loop controller whose (CAS) set point is manipulated by
the output of a primary controller in a cascade control system
self-regulating process – a process that decelerates and reaches a steady state for a change in
the manipulated variable when the controller is in manual if there are no disturbances (no
integrating or runaway response)
sensitivity – ratio of the steady state change in output to the change in the input (poor sensitivity
is caused by poor resolution and a low steady state gain or flat curve)
slip – rapid movement of valve trim caused by dynamic changes in friction (the zipping past the
desired position means the controller will never reach its set point)
steady state gain – final change in the output of loop components (controller, valve, process,
measurement) divided by the change in input (static or zero frequency gain)
static gain – see steady state gain
stick – lack of valve trim movement for a change in input signal caused by friction or an
undersized actuator (major source of a valve’s resolution limit)
time delay – time it takes for the process variable to get out of the noise band for a change in the
manipulated variable (same as dead time)
time constant – time it takes for the process variable to reach 63% of its change after its time
delay for a step change.
time to steady state (Tss) – the time it takes the process variable or controlled variable to reach
its final value (or about 99 percent of the change in the process variable) after a change to the
manipulated variable.
ultimate gain – controller gain at equal amplitude oscillations for proportional only control (occurs
at 180 deg phase shift and is inverse of static gain and amplitude ratio)
ultimate period – period of equal amplitude oscillations for proportional only control (occurs at
180 deg phase shift and is the inverse of the natural period in radians/sec)
update time – time interval between successive updates for digital devices (same as scan time
or control interval and the inverse of scan rate or frequency)
valve action – relative direction of change in flow for a change in the input signal to a valve
(“direct or inc-open” for fail closed and ”reverse” or ”inc-close” for fail open)