Abstract: This paper deals with the controlling of temperature position of a control valve, a damper, or the power supplied to
in a water bath system using a PID controller. This project a heating element.
involves two stages, the first stage is designing the transfer
function for the water bath system. The second stage is
interfacing the predefined PID controller with the water bath Describtion Of Water Bath System
system. This project is designed in a way as user defined data. The water bath process consist of several things mainly water
The user sets up the required temperature limit in the PID tank, sensor, data acquisition system, controller and heater.
controller as the controller set point. An heating element is Here RTD is used as the temperature sensor DAQ is used for
used for heating the water in the water bath and the RTD inter connection between sensor and controller as well as
sensor placed in the water bath is responsible for sensing the controller and driver circuit. The RTD output is in terms of
water bath temperature. Based on the controller constant mille volt range so we use a amplifier circuit for increasing the
values and the temperature of the water bath, the temperature voltage range. The working of the system is described as,
is controlled by controlling the water inlet to the water bath. when the temperature is measured by the RTD it is converted
Ziegler Nichols tuning method is used for the PID controller into the voltage, which is going to the controller through
tuning method. The performance analysis of PD, PI and PID DAQ. The difference between set point and actual value is
controllers is done for the water bath system. applied to the controller, nothing but error .The PWM signal is
produced corresponding to the 10 output voltage of the sensor.
Keywords: Ziegler Nichols tuning method, RTD sensor, PID to control the temperature of the water bath process, it’s tuned
Controller automatically and correcting the error in the process its shown
figure 1.
Introduction
Process control system is often nonlinear and difficult to
control accurately for the process. Their dynamic models of
the system are more difficult to derive. The conventional PID
controllers, in various combinations have been widely used for
industrial processes due to their simplicity and effectiveness
for linear systems, especially for first and second order
systems. It has been well known that Proportional Integral
Derivative (PID) controllers can be effectively used for linear
systems, but usually cannot be used for higher order and
nonlinear systems [1].
up, when input change is given commonly used for feedback controller. A PID controller
7. Time constant (t) =t2-t1 calculates an "error" value as the difference between a
9. The general form of the first order transfer function is measured process variable and a fixed set point. The controller
given by used to minimize the error by adjusting the process control
inputs. A PID controller will be called a P, P or I, PD
controller in the absence of the respective control actions
According to the open loop test, the readings are listed above.
The transfer function obtained from this reading is given by
Where
Controller Kp KI KD
PID 14.16 8.98 5.57
3444
International Journal of Applied Engineering Research, ISSN 0973-4562 Vol. 10 No.4 (2015)
© Research India Publications; http://www.ripublication.com/ijaer.htm
Figure 4 Simulation circuit of water bath system Figure 7 simulation PD output of water bath system
Conclusion
In this paper the temperature process and the control strategy
adopted is PID controller. The temperature controller was
identified based the simulation output curve of PI , PD, PID
responses respectively .with this rise time, settling time, delay
time and maximum peak overshoot values are tabulated in the
table1.from the above table it is clear that the PID controller
Figure 5 Simulation PID output of water bath system has the less settling time, delay time, rise time and maximum
peak overshoot when compared to the other controllers by
using the transfer function model, simulation of Proportional
Integral Derivative controller was implemented. This
controller controls the temperature inside the water bath and
also maintains it while comparing with the other controllers
this PID controller enhances different tuning methods for
sensing and controlling the temperature.