Type Testing of Generator Transformer
Type Testing of Generator Transformer
K. Sedlazeck S. Lindholm
C. Richter J. Pipkin
S. Strack F. Fu
B. Humphries
L. Montgomery
Siemens Energy Siemens Energy
Mülheim, Germany Orlando, FL USA
Abstract— Type tests completed in August 2008 have validated all I. INTRODUCTION
electrical and mechanical design parameters of the 1992 MVA 4-
pole, 1500 RPM turbogenerator that Teollisuuden Voima Oy is The first EPR turbogenerator with its brushless exciter is
now installing in the Olkiluoto 3 nuclear power station. Olkiluoto shown fully assembled on the test field in Figure 1 at the
3 is the first European Pressurized Reactor (EPR) power station. conclusion of a 3 week type test that was completed in August
In response to TVO’s requirement that the generator capability 2008. A few days after this photograph was taken, the
be at least 10% above the 1992 MVA nameplate rating, Siemens generator was disassembled and shipped to the Olkiluoto 3
Energy designed the generator so that its capability is above 2222 power station, where it is now being installed on the turbine
MVA (2000 MW, 0.90 power factor). Besides being designed to deck.
have this high capability, the generator is also designed to be very
efficient (tested generator efficiency is nearly 99% at the 1992
MVA nameplate rating), and it is designed to exhibit very low
In this paper the authors outline design features that have
mechanical vibration levels. In this paper the authors report the been previously described in more detail in References 2 and 3,
following highlights of the electrical and mechanical and we also describe the main electrical and mechanical
characteristics that were observed during recent type tests: characteristics that were observed during the recent type test.
• Confirmation of expected steady state MVA capability
• Confirmation of expected dynamic stability parameters
Successfully completing the type test of this 2000 MW
turbogenerator marks a major milestone in a journey that began
• Confirmation of expected acceptable mechanical vibration
nearly 40 years ago with the initiation of nuclear
Index Terms— turbogenerator, nuclear power station, turbogenerator designs in this rating class. Some discussions
hydrogen cooling, water cooling, type testing, MVA capability, of the work of those earlier days are recorded in Reference 1.
efficiency, vibration, stability parameters
Figure 1 - Olkiluoto 3 turbogenerator with its brushless exciter at the conclusion of the type test
Generator Cooling: As illustrated in Figures 2 and 3, this • Steady-state short circuit tests
hydrogen-cooled generator is equipped with an all water- Short circuit heat runs with collector set
cooled stator winding. The rotor winding is axially hydrogen- Short circuit losses and saturation curve
cooled. The stator core is primarily axially hydrogen-cooled,
with radial ducts at each end for supplemental cooling. Short circuit heat runs with brushless exciter
Hydrogen is circulated with one multi-stage, axial flow blower • Steady state open circuit tests
located at the turbine end of the generator, between two Open circuit heat runs at 27 kV
vertical coolers.
Open circuit saturation curve and core losses
Voltage wave shape analysis
• Rotor moment of inertia (retardation test)
• Sudden short circuit tests (with brushless exciter)
466
Figure 7 - Summary of test results for steady state thermal capability
Figure 5 - EPR generator and test field collector set on the test field at the
beginning of the test program
Figure 6 - EPR generator and its brushless exciter on the test field at the
end of the test program
467
As shown in Figures 7, 8 and 9, from the point of view of
IEC Class 130 thermal limits for the windings, the tested
capability exceeds the target maximum apparent power, 2222
MVA, by over 20%.
Figure 10 - Terminals of EPR turbogenerator, showing 6 main leads, 6 Figure 12 - Comparison of tested and calculated current distributions in
flexible connector assemblies and 6 bushings flexible connector assemblies between main leads and bushings
468
Validating calculated magnetic saturation and calculated VI. CONFIRMATION OF DYNAMIC CHARACTERISTICS
synchronous reactances was an important aspect of the test
As shown in Figures 15 and 16, all tested reactances were
program. As shown in Figures 13 and 14, the tested saturation
within the calculated min/max range, thus validating grid
curves closely matched the curves calculated by finite element
stability studies completed with reactances calculated during
analysis (FEA) of the generator electromagnetic performance.
the development of this generator design.
30 test unsat
2.5
25 calc unsat min
20 2.0
Rated Voltage
15 Calculated by FEA 1.5
10 Test Points
1.0
5
0.5
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 0.0
field current normalized by xd x’d x’’d
27 kV open circuit field current
Figure 13 - Calculated and tested open circuit saturation curves Figure 15 – Calculated and tested unsaturated reactances
45
stator phase current [kA]
469
VII. TEST CONFIRMATION OF ACCEPTABLE VIBRATION VIII. CONCLUSIONS
During the type test the stator was extensively instrumented Results from the August 2008 type test of the 2222 MVA,
with vibration sensors. These sensors included fiberoptic 2000 MW turbogenerator designed and manufactured for the
vibration sensors on the high voltage windings, piezoelectric first EPR nuclear power station showed excellent agreement
sensors on the core and frame and bearing brackets, and between design values and tested values of the generator
standard sensors to measure rotor shaft vibration. All sensors parameters. All results met or exceeded requirements set by
were monitored and recorded with computer data acquisition Siemens and by IEC standards.
systems that provided both real time output for immediate
inspection by the engineers monitoring the test and also orderly Successfully completing the type test of this 2000 MW
storage of the data for post processing. As shown in Figure 17, turbogenerator has marked a major milestone in a journey that
all tested stator and rotor vibrations were less than specified began over 40 years ago with the initiation of nuclear
limits. The Rigi-Flex stator winding vibration levels were turbogenerator designs in the rating class above 1200 MW.
quite low, less than 60% of allowable levels. Nearly all All people who conducted and supported this type test, all
vibration levels were less than 80% of specified limits. people who contributed to the previous years of development
of the generator design, and all people who contributed to
manufacturing the generator have good reason to be pleased
with the excellent results after this years-long and very difficult
work.
470