API 521 Summary
API 521 Summary
the material or energy or both in some part of the system. PRDs are installed to ensure that a process
system or its component is not subjected to pressures that exceed maximum allowable accumulated
pressure.
Double or multiple jeopardy - the simultaneous occurrence of two or more unrelated causes of
overpressure is not a basis for design; API 521 describes single jeopardy scenarios as a basis of design
The liquid or vapor rates used to establish relief rate are developed by the net energy input – heat
(vaporization or thermal expansion) and direct pressure input
Pressure and temperature should be considered as they affect the volumetric and compositional
behavior of liquids and vapors.
Blocked Outlet
Evaluate if Source pressure of liquid feed > design pressure of the equipment or PRD set pressure
Automatic Controls
Gas blowby = loss of liquid level followed by high pressure vapor flow; it is the discharge of gas from a
process equipment through a liquid outlet; occurs due to failure of liquid level control system or an
inadvertent opening of cv bypass; can lead to overpressure in downstream equipment. Relief rate = full
vapor flow through the liquid cv
One inlet is in fully open position regardless of CV failure position; relief rate = maximum
expected inlet flow – normal outlet flow from valves that are open
If manual bypass on inlet cv is partially open, total flow = flow through cv wide open and the
bypass
One of the control valves at fail close on outlet, relief rate = maximum expected inlet flow –
maximum outlet flow through remaining outlets
Reboilers, other process heating equipment: abnormal heat input may cause vapor generation >
condensation; relief rate = max vapor inflow – condensation or vapor outflow
Relief load depends on the maximum operating pressure upstream of the valve and the downstream
equipment pressure at relieving conditions
When a spare pump is brought online, if check valve has leakage, spare pump may see discharge
pressure of the operating pump and lead to overpressure situation
Reverse flow through check valves in series is a scenario when the maximum operating pressure of the
high-pressure system is greater than the corrected hydrotest pressure of the low pressure equipment
Transient Pressure Surges – Water hammer or hydraulic shock waves/steam hammer/ condensate
hammer – due to rapid closure of valves – cannot be controlled by typical PRD – avoid the use of quick
closing valves
Chemical Reactions
Cryogenic fluids and loss of process control – reduction in pressure lowers temperature to minimum
allowable design temperature of the equipment = low-temperature brittle failure
Exothermic reactions – runaway reaction causes pressure above MAWP – DIERS Methodology for relief
rate – if PRDs are infeasible, use reaction inhibitors, depressuring, quench, automatic shutdown
Equipment or piping – liquid-filled, blocked and heated up by solar radiation or heat tracing
Exchanger – blocked in on the cold side with flow on the hot side; hydraulic expansion relief device on
cold side
Phase change – If the blocked-in liquid has vapor pressure higher than the relief design pressure, the
PRD should be capable of handling the vapor generated
Required relief rate is small; relief valve with nominal diameter DN (20) x DN (25) or NPS (3/4”) X NPS
(1”) specified
Fire
Pool fire (confined or open) – ignited liquid spill; open pool fire – design basis for fire case
Jet fire – ignited pressurized leak; occurs when any flammable fluid under pressure is released to
atmosphere; PRDs ineffective; focus on prevention of leaks
Vapor formation – consider portion of vessel wetted by internal liquid up to a height of 25 ft or 7.6 m
above the base of a pool fire – any level at which a substantial spill or pool fire could be sustained;
usually ground level; for a sphere, wetted area is higher of the maximum horizontal diameter and 25 ft;
column – normal level in the bottom plus liquid holdup from trays upto 25 ft (if reboiler part of column,
add reboiler level)
For vessels with liquids: Q = 21,000 FA^0.82; F – environment factor = 1 for bare vessel’ A^ 0.82 – area
exposure factor/ratio; if no adequate drainage or firefighting, Q = 34500 FA^0.82; at subcritical
conditions, relief rate = rate of vapor formation = Q/heat of vaporization; Orifice Area – calculate and
select from D to T; rated capacity = relief rate * (selected/calculated orifice area); near the critical point,
latent heat of vaporization approaches zero and sensible heat takes over and so 50 BTU/lb taken as
approximation; above critical point, no phase change occurs and relief depends on the expansion of the
liquid due to heat input
Tube failure
Power failure