Control Valve Interview Question
Control Valve Interview Question
4.
5. The DC current loop is used extensively in the instrumentation field to transmit
process variable to indicators and controllers (PLC,DCS,Standalone controllers
etc).It is also used to send control signals to field device to manipulate process
variables such as temperature,level and flow. This can be done by sending
signals from a controller (PLC,DCS,or other control equipment) to final control
element such as control valve,pumps etc.
6. The standard current range used in these loops is 4 to 20 mA (milli ampere) and
this value is normally converted to 1 to 5 VDC by a 250 ohm resistor at the input
to controllers and indicator.These instruments are normally high input impedance
electronic devices that draw virtually no current from the instrument loop.
What are the different process variables?
Flow.
Pressure.
Temperature.
Level.
Quality i.e. % O2, CO2, pH etc
Flow, pressure, temperature is the basic three variables.
Define all the process Variable and state their unit of measurement
Flow: It is defined as volume per unit of time at specified temperature and
pressure Conditions, is generally measured by positive-displacement or rate meters.
Units: kg / hr, litter / min, gallon / min, m3 / hr, Nm3 / hr.
Pressure: It is defined as Force per unit Area. P = F/A
Units : bar, Pascal, kg / cm2, lb / in2.
Level: The height of the water column, liquid and powder etc., at the desired
measurement of height between minimum level points to maximum level point is called
level.
Units: Meters, mm, cm, percentage.
Temperature: It is the degree of hotness or coldness of a body is called temperature.
Units : Degree Centigrade, Degree Fahrenheit, Degree Kelvin, Degree Rankin.
What are the primary elements used for flow measurement?
The primary elements used for flow measurement are:
Orifice Plate.
Venturi tube.
Pitot tube.
Annubars.
Flow Nozzle.
Weir & Flumes
How do you identify an orifice in the pipeline?
An orifice tab is welded on the orifice plate which extends outer of the line giving an
indication of the orifice plate.
Why flow is measured in square root?
The differential pressure measured has nonlinear relation with flow through the
pipeline. Differential pressure developed by a venturi, orifice plate, pitot tube, or any
other acceleration-based flow element is proportional to the square of the flow rate.
The square root extractor is used to convert the measured differential pressure into
the flow rate.
How do you calibrate a D. P. transmitter?
The following steps are to be taken which calibrating:
1. Adjust zero of the Tx’r.
2. Static pressure test: Give equal pressure on both sides of the transmitter. Zero
should not shift. If it is shifting carry out static alignment.
3. Vacuum test: Apply equal vacuum to both the sides. The zero should not shift.
4. Calibration Procedure:
* Give 20 psi air or 24V DC supply to the transmitter
* Vent the L.P. side to atmosphere.
* Connect the output of the Instrument to a standard test gauge or Multimeter and adjust
zero.
5. Apply required pressure to high-pressure side of the transmitter and adjust the span.
6. Adjust zero again if necessary.
How do you do zero checks on a D. P. transmitter?
Close one of the valves either H. P. or L.P. opens the equalizing valve. The O/P should
read zero.