High-Performance

Process Manager
Parameter Reference Dictionary
HP09-540
Implementation
High-Performance Process Manager - 2

High-Performance
Process Manager
Parameter Reference Dictionary
HP09-540
Release 530
8/97
Copyright, Trademarks, and Notices

© Copyright 1995 - 1997 by Honeywell Inc.

Revision 04 - August 1, 1997

While this information is presented in good faith and believed to be accurate,


Honeywell disclaims the implied warranties of merchantability and fitness for a
particular purpose and makes no express warranties except as may be stated in its
written agreement with and for its customer.

In no event is Honeywell liable to anyone for any indirect, special or consequential


damages. The information and specifications in this document are subject to
change without notice.

TotalPlant and TDC 3000 are U.S. registered trademarks of Honeywell Inc.
Other brand or product names are trademarks of their respective owners.
About This Publication
This publication defines the parameters for the HPM data point types implemented through
TotalPlant Solution (TPS) system network Release 500 - 530. TPS is the evolution of
TDC 3000 X .

Change bars are used to indicate paragraphs, tables, or illustrations containing changes
that have been made to this manual effective with Release 530. Pages revised only to
correct minor typographical errors contain no change bars.

HPM Parameter Reference Dictionary 8/97


HPM Parameter Reference Dictionary 8/97
Table of Contents

1 INTRODUCTION

1.1 Purpose
1.2 Use of This Publication
1.3 Parameter Definition Format
1.4 Parameters Per Point Type and Algorithm Type
1.5 Full Points and Component Points
1.6 Abbreviations
1.7 CL Access
1.7.1 Parameters Not Accessible to CL
1.7.2 CL Restricted Parameters
2 PARAMETERS PER POINT TYPE

2.1 Analog Input (AnalgIn)


2.2 Analog Output (AnalgOut)
2.3 Array
2.4 Box (HPM Box)
2.5 Box Flag
2.6 Box Numeric
2.7 Box Timer
2.8 Device Control (DevCont)
2.9 Digital Composite (DigComp)
2.10 Digital Input (DigIn)
2.11 Digital Output (DigOut)
2.12 Reserved
2.13 IOP
2.14 Logic
2.15 Process Module (ProcMod)
2.16 UCN Network
2.17 UCN Node
3 PARAMETERS PER ALGORITHM TYPE

3.1 Auto Manual (AutoMan)


3.2 Calculator (Calcultr)
3.3 Data Acquisition (DataAcq)
3.4 Flow Compensation (FlowComp)
3.5 General Linearization (GenLin)
3.6 High-Low Average (HiLoAvg)
3.7 Incremental Summer (IncrSum)
3.8 Middle-of-3 (MidOf3)
3.9 Override Selector (ORSel)

HPM Parameter Reference Dictionary i 8/97


Table of Contents

3.10 Pid
3.11 Pid with External Reset Feedback (PidErfb)
3.12 Pid with Feed Forward (PidFf)
3.13 Pid with Position Proportional (PidPosPr)
3.14 Position Proportional (PosProp)
3.15 Ramp Soak (RampSoak)
3.16 Ratio Control (RatioCtl)
3.17 Summer (RegCtl)
3.18 Summer (RegPV)
3.19 Switch
3.20 Totalizer (Totalizr)
3.21 Variable Dead Time with Lead/Lag (VdtLdLag)

$–Y PARAMETER DEFINITIONS

HPM Parameter Reference Dictionary ii 5/97


1

INTRODUCTION
Section 1

1.1 PURPOSE

This publication defines the user-visible parameters that exist in the TotalPlant Solution
(TPS) System High-Performance Process Manager (HPM) and Network Interface Module
(NIM). It also provides listings of parameters that are applicable to various HPM point
types and algorithms.

For information on how the parameters are related to each other in terms of point types and
algorithms, refer to the High-Performance Process Manager Control Functions and
Algorithms manual in the Implementation/High-Performance Process Manager - 1 binder.

1.2 USE OF THIS PUBLICATION

Use this publication during configuration and during operation when detailed information
about HPM and NIM parameters is required.

For use in data point configuration, this publication provides definitions for each entry that
can be made on the High-Performance Process Manager Point Configuration Forms,
HP88-500 in the Implementation/High-Performance Process Manager - 1 binder, and in the
Parameter Entry Displays at the Universal Station.

For use in process operation, this publication provides information about the parameters
that appear for the process data points and HPM Box Data Point on the displays of
Universal Stations that are running with the Operator personality.

1.3 PARAMETER DEFINITION FORMAT

In this dictionary, the parameter definitions are listed in alphabetical order according to the
parameter name, which can be up to eight characters in length. Each parameter in this
publication is defined using the format shown below for the ALMOPT parameter, as an
example. The following paragraphs describe the entries that appear within each parameter
definition.

ALMOPT (DigIn)
Type: e($ALMOPT) Alarming Option—Defines the alarming option for a digital input point whose
Lock: Eng/PB DITYPE is Status.
Default: None
PtRes: APM
Range: 0-None (No alarms are to be detected)
1-Offnorml (Off Normal; alarm if current PV state is not the PVNORMAL state. PVNORMAL is
defined by the STATETXT(0) or STATETXT(1) descriptor, as configured by the user.)
2-ChngofSt (An alarm is generated when the digital input changes state in either direction).

Helpful Hint: ALMOPT configuration requires DITYPE = Status.

HPM Parameter Reference Dictionary 1-1 8/97


1.3

For many parameters, the function of the parameter is described using the long name of the
parameter (Alarm Option), followed by a description as shown in the above example. Some
parameters in this dictionary do not have functional descriptions following the long name;
this is because the long name of the parameter sufficiently describes the parameter function.

Type
This entry is the data type that defines how the parameter is viewed by the system. The
following data types are used in this dictionary:

• E:—Enumeration; the value for the parameter is chosen from a set of predefined
character strings. In the above example, the enumerations of $ALMOPT are None,
Offnorml.

• SD_ENM:—Self-Defining Enumeration; the value for the parameter is chosen from the
user-defined character strings.

• Ent.Prm—consists of a 1-16 character tag name, a period, and a 1-8 character


parameter name.

• Integer—a 16-bit whole number that does not contain a decimal point (+ 32767).

• Logical—a binary type with the values of ON (True) and OFF (False), or 0 (Off) and 1
(On).

• NaN—although not a data type, is used to represent "Not A Number" and is stored in
IEEE format.

• Prm_Id—1-8 character parameter name.

• Real—a 32-bit floating-point number in IEEE format.

• String_L—a character string of maximum length = L. Same as Ascii_L.

• Time—The time of day in one of the following formats: DDD HH:MM:SS for
durations, and DDMMYY HH:MM:SS for an absolute date or time stamp.

• Universal Ent.Prm—Universal Entity Parameter Identifier. It is basically the same as


Ent.Prm, but the entity name can be entered as an external 16-character tag name or as
the HPM's internal hardware reference address. The hardware reference address
syntax can be used to access parameters of points (within this same HPM) that are
untagged or tagged.

HPM Parameter Reference Dictionary 1-2 8/97


1.3

The following are examples of hardware reference addresses*:

Type Hardware Reference Address

AO Processor Output !AO11S03.OP (Parameter OP of Slot #3 of AO processor #11)

DI Processor PV !DI05S07.PVFL (Parameter PVFL of Slot #7 of DI processor #5)

DO Processor !DO15S12.SO (Parameter SO of Slot #12 of DO processor #15)


Status Output

DO Processor !DO15S12.ONPULSE (Parameter ONPULSE of Slot #12 of DO


ON Pulse Command processor #15)

DO Processor !DO15S12.OFFPULSE (Parameter OFFPULSE of Slot #12 of


OFF Pulse Command DO processor #15)

Lock
The access lock defines "who" or "what" can change the parameter's value or option and the
access level defines "who" or "what" is requesting a parameter value or option change. For
example, if a requestor with an access level of Supr tries to change a parameter that has an
access lock of Engr, the request will be denied. The two charts below describe how access
levels and access locks work.
Access Level Used By Who Or What When A
Parameter Change Request Is Made

Oper Operator
Supr or Sup Supervisor
Engr, Eng, or Eg Engineer
Cont Continuous_Control (from a Module on the LCN)
OnProc On Process
HPMMCc HPMM_Continuous_Control (from HPMM)
Prog CL/HPM Sequence_Programs
PtBld or PB Point_Builder (Data Entity Builder)

Access Lock Access Level of Requestors That Can Change The Parameter

Oper Oper Supr Engr Cont HPMMCc Prog PtBld


Supr Supr Engr Cont HPMMCc Prog PtBld
Engr Engr Cont HPMMCc Prog PtBld
OnProc Oper Supr Engr
Sup/Eg Supr Engr
EgOnly Engr
Prog Cont HPMMCc Prog PtBld
Eng/PB Engr PtBld
PtBld PtBld
View (Read Only)

______________
*The Analog Input address !AImmSss.Parameter is not supported because the Analog Input point does not have
a useable default database.

HPM Parameter Reference Dictionary 1-3 8/97


1.4

Default
The default for the parameter is the default value assigned by the system. The system
automatically enters the default value for a parameter when a range or a selection is not
entered for a parameter during point building. The default values are also shown on the
configuration forms and parameter entry displays.
PtRes
This defines where the parameter physically resides. The following residency locations are
used in the parameter definitions:
PtRes Definition

HPM High-Performance Process Manager


NIM Network Interface Module
SI Serial Interface

Range
This defines the range of the value that can be entered for this parameter. Integers that
precede HPM resident enumeration parameters are sometimes needed by advanced CL
users. These integers specify the member’s position within the set (that is, the ordinal).
CL programs external to the UCN (such as AM/CL) will see the same enumeration strings,
but in some cases, with different ordinal values.

Helpful Hint
Some parameter definitions contain a Helpful Hint box at the end of the definition. This
box contains additional information about the parameter, such as prerequisites, etc.

1.4 PARAMETERS PER POINT TYPE AND ALGORITHM TYPE


In addition to the parameter definitions, this dictionary also contains listings of the
parameters that are applicable to each HPM point type and algorithm type. Parameters-per-
point-type are defined in Section 2; parameters-per-algorithm-type are defined in Section 3.

1.5 FULL POINTS AND COMPONENT POINTS


Separate functional elements of the HPM are used to implement various parts of typical
control loops and control strategies. Each of these functional elements can be assigned a
user-defined tag name to allow for location-independent reference to the data associated
with that function. For example, point tags are assigned by the user for analog input and
analog output slots. The I/O Processor data (engineering-unit range for inputs,
characterization option for outputs, etc.) is configured as part of the point-build process for
these points. A separate tag is configured for each regulatory control (RegCtl) slot that is
linked to the assigned analog I/O tags through input/output connections.

HPM Parameter Reference Dictionary 1-4 8/97


1.6

The HPM provides a configurable parameter called PNTFORM (Point Form) that allows
the user to define which points are to be used as the primary operator interface for point
data. The PNTFORM parameter provides the user with two choices for point form: "Full"
and "Component." Points that are configured as having "Full" point form include alarm-
related parameters and sometimes, some other miscellaneous parameters. This information
is needed when the point is to be used as the primary operator interface to the point's data.

Points that are configured as having "Component" point form should be used to provide
inputs to the "Full" point and also for those points that handle the outputs from the "Full"
points. "Component" points should be used as part of the "Full" point that has been
designated a primary operator interface point.

1.6 ABBREVIATIONS

AM Application Module
AnalgIn Analog Input Data Point
AnalgOut Analog Output Data Point
AO Analog Output
HPM High-Performance Process Manager
HPMM High-Performance Process Manager Module
HPM Box HPM Box Data Point
Array Array Data Point
AutoMan Auto Manual algorithm
Box Box Data Point
Calcultr Calculator algorithm
CM Computing Module 50 or 60
DevCtl Device Control Data Point
DI Digital Input
DigComp Digital Composite Data Point
DigIn Digital Input Data Point
DigOut Digital Output Data Point
DISOE Digital Input Sequence of Events
DO Digital Output
ESI Extended Standard International Engineering Units
FBus Field Bus
Flag Flag Data Point
FlowComp Flow Compensation algorithm
FTA Field Termination Assembly
GenLin General Linearization algorithm

HPM Parameter Reference Dictionary 1-5 8/97


1.6

HiLoAvg High Low Average algorithm


HLAI High Level Analog Input
IncrSum Incremental Summer algorithm
IOL I/O Link
IOP I/O Processor
Logic Logic Data Point (Slot)
LCN Local Control Network
LLAI Low Level Analog Input (or LLAI-8)
LLMUX Low Level Analog Input Multiplexer (or LLAI-16/32)
MidOf3 Middle-of-3 Selector algorithm
MulDiv Multiply Divide algorithm
NIM Network Interface Module
ORSel Override Selector algorithm
PI Pulse Input
Pid Proportional, Integral, Derivative,
PidErfb Proportional, Integral, Derivative with External Reset Feedback algorithm
PidFf PID with Feedforward algorithm
PidPosPr PID With Position Proportional algorithm
PosProp Position Proportional algorithm
ProcMod Process Module Data Point
PSDP Processor Status Data Point
RampSoak Ramp Soak algorithm
RatioCtl Ratio Control algorithm
RegCtl Regulatory Control Data Point or algorithm
RegPV Regulatory PV Data Point or algorithm
RHMUX Remote Hardened Analog Input Multiplexer (or RHMUX–16/32)

SI Serial Interface
SDI Serial Device Interface
STI Smart Transmitter Interface
Switch Switch algorithm
Summer Summer algorithm
Timer Timer Data Point
Totalizr Totalizer algorithm
UCN Universal Control Network
VdtLdLag Variable Deadtime Lead Lag algorithm

HPM Parameter Reference Dictionary 1-6 8/97


1.7

1.7 CL ACCESS

1.7.1 Parameter Not Accessible to CL

Parameter $EVNTREC is not accessible to Control Language (CL) sequences.

1.7.2 CL Restricted Parameters

The following parameters are not accessible to PM/CL sequences. They are not directly
available to AM/CL sequences. Access to AM/CL is through a custom data segment
parameters attached to AM regulatory points as described below.
BHALMFL1-BHALMFL7
NODESTS
NODETYP
UCNRECHN
These parameters are available to user schematics using the NIM reserved data point, e.g.,
$NMuuBnn.param, where uu = UCN number and nn = UCN node number.

AM/CL programs can access the restricted parameters as Regulatory Point General inputs
(using ordinary point parameter access). They must be transferred to parameters of AM
regulatory points. There are two ways to do this:

1. Boolean parameters (BHALMFLn), can be referenced as general inputs to a Switch


algorithm. A CL program can access the switch parameters.

2. For Enumerations (NODEOPER, NODESTS, NODETYP, POSITION, AND


UNRECHN) a custom data segment is created to allow the parameters to be referenced
as general inputs and transferred to user-defined parameters (of a RegCtl Point) that can
be accessed by Cl.

HPM Parameter Reference Dictionary 1-7 8/97


HPM Parameter Reference Dictionary 1-8 8/97
2

PARAMETERS PER POINT TYPE


Section 2

This section contains listings of parameters that are applicable to each data point type in the HPM,
except for the Regulatory Control and Regulatory PV data points which can be found in Section 3.
Refer to Sections $ - X for the definitions of the parameters.

2.1 Analog Input (AI)

The parameters of the Analog Input Data points are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) LRL PVALDB (F) PVLLPR (F) PVTVP (F)
ALENBST (F) LRV PVALDBEU (F) PVLLTP (F) RJTEMP
ASSOCDSP MODNUM PVAUTO PVLOFL S1
AVDELTHS NAME PVAUTOST PVLOPR (F) SECVAR
AVSTS NODENUM PVCALC PVLOTP (F) SENSRTYP
BADPVFL (F) NODETYP PVCHAR PVP SERIALNO
BADPVPR (F) NTWKNUM PVCLAMP PVRAW SFSTS
C1 OTDENBLE PVEUHI PVRAWHI SLOTNUM
C2 OVERVAL (F) PVEULO PVRAWLO SLWSRCID
CJTACT PIUOTDCF PVEXEUHI PVROCNFL STATE
COMMAND PNTFORM PVEXEULO PVROCNPR (F) STI_EU
CONTCUT (F) PNTMODTY PVEXHIFL PVROCNTP (F) STISWVER
DAMPING PNTNODTY PVEXLOFL PVROCPFL STITAG
DECONF PNTSTATE PVFORMAT PVROCPPR (F) TCRNGOPT
EUDESC PNTTYPE PVHHFL PVROCPTP (F) TF
HIGHAL (F) PRIMMOD (F) PVHHPR (F) PVSOURCE (F) TIMEBASE
HIGHALPR (F) PTDESC PVHHTP (F) PVSRCOPT (F) UNIT
INPTDIR PTEXECST PVHIFL PVSTS URL
KEYWORD PTINAL PVHIPR (F) PVTV (F) URV
LASTPV PV PVHITP (F)
LOCUTOFF PVLLFL

2.2 Analog Output (AO)

The parameters of the Analog Output Data point are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
ASSOCDSP MODNUM OPFINAL OPOUT2 PNTTYPE
CASREQ (F) NAME OPIN0 OPOUT3 PRIMMOD (F)
EUDESC NMODATTR (F) OPIN1 OPOUT4 PTDESC
KEYWORD NMODE (F) OPIN2 OPOUT5 PTEXECST
LOCALMAN NODENUM OPIN3 OPTDIR RCASOPT
MODATTR (F) NODETYP OPIN4 $OPTOL REDTAG (F)
MODE (F) NTWKNUM OPIN5 PNTFORM RINITREQ (F)
MODEAPPL (F) OP OPOUT0 PNTMODTY SLOTNUM
MODEPERM (F) OPCHAR OPOUT1 PNTNODTY STDBYMAN
PNTSTATE UNIT

HPM Parameter Reference Dictionary 2-1 8/97


2.3

2.3 Array

The parameters of the Array Data Point are listed below in alphabetical order. The Point
Form parameter is set to Full.
AB_DATA1 DEVADDR NN PNTFORM STR64
AB_DATA2 ERRCODE NNDESC PNTNODTY STRDESC
AB_DATA3 EXTDATA NNUMERIC PNTTYPE STRLEN
AB_DATA4 FL NNSTIX PRIMMOD STRSTIX
ASSOCDSP FLDESC NODENUM PTDESC STSMSG
AUXDATA1 FLSTIX NODETYP SCANPRI TIME
AUXDATA2 FTANUM NSTRING SLOTNUM TIMEDESC
AUXDATA3 INITREQ NTIME SPLOCK TIMESECS
AUXDATA4 IOPNUM NTWKNUM STR8 TIMESTIX
BADPVFL KEYWORD OVERLAP STR16 UNIT
CNFMU NFLAG PERIOD STR32 USERID
CNFPU

2.4 Box (HPM Box)

The parameters of the High-Performance Process Manager Box Data Point are listed below
in alphabetical order.
ASSOCDSP FTA1TYPE IOP MNFMDDAY NODFSTAT RELVERS
BADPVTXT FTA2TYPE IOPIDAY MNFMDINF NOPTS RELREV
CHPINOPR HOUR IOPIMON MNFMDMTH NORQUMAX RJTEMP
CMFLTIME IOLASTS IOPIYEAR MNFMDINF NORSPAVG SAFOPCMD
CMIDTXT IOLBSTS IOPNUM MNFMDMTH NORSPMAX SCANPER
CNFPU IOLCHAER IOPSTR1 MNFMDSER NOTRAAVG SECOND
CNFPUP IOLCHASL IOPSTR2 MNFMDYR NOTRAMAX SEQPRGSZ
COMHOUR IOLCHBER IORECCHN MONPER NPARAVG SRQUTAVG
COMMIN IOLCHBSL IOSSTS MONTH NPARMAX SRSPTAVG
CRIOLORN IOLCHERT IOSTKNDR MOVPVTXT NPMSLOT SRSPTMAX
CRPPXORN IOLCMD IOTKNSTL MPCFWREV NPVSLOT STR8
CRUCNORN IOLHWREV LSIOLORN MPCHWREV NSTRING SUMSLTSZ
CTFLTIME IOLPERSW LSPPXORN NARRSLOT NTIME SWTCHACT
CTIDTXT IOLREV LSUCNORN NCTLSLOT NTIMER TIERTYPE
CTLHOUR IOLVERS MAXCNFPU NDCSLOT NTRAAVG TIME
CTLMIN IOMCARD MDMHWREV NDEVSLOT NTRAMAX TMCMD
CTLOPT IOMCHAER MINUTE NFASTCTL PKGOPT TMPV
CTLPATCH IOMCHASL MNFASIC NFASTDC PMMCHAER TMRV
CYCLETIM IOMCHBER MNFCCDAY NFASTDEV PMMCHASL TMSO
DATE IOMCHBSL MNFDAY NFASTLOG PMMCHBER TMSP
DAY IOMCMD MNFCCINF NFASTPV PMMCHBSL TMST
DB_VALID IOMCOMER MNFCCMTH NFLAG PMMCMD TMTB
DIAGCMD IOMFILE MNFCCSER NLOGSLOT PMMCOMER TRATAVG
EUNDESC IOMOPER MNFCCYR NN PMMCTLST TRATMAX
FL IOMREALT MNFFPGA NNUMERIC PMMOPER UTSDRIFT
FRQUTAVG IOMRECHN MNFIODAY NODEASSN PMMRECCH UTSNODE
FRQUTMAX IOMSEVER MNFIOINF NODECMD PMMSEVER UTSTBCRV
FRSPTAVG IOMSTS MNFIOMTH NODECONF PMMSFSTS UTSTIME
FRSPTMAX IOMTYPE MNFIOSER NODENUM PMMSTS UTSTIMST
IONTOKEN MNFIOYR NODESTS PNTNODTY WEEKDAY
NODETYP POSITION YEAR

Some of the parameters in the above listing are arrays and are not defined in this
publication.

HPM Parameter Reference Dictionary 2-2 8/97


2.5

2.5 Box Flag

The parameters of the Box Flag Data Point are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full; an * indicates that the
parameter is applicable to flag slots 1-128.
$AUXUNIT (F)* CONTCUT (F)* NODETYP PRIMMOD (F)* S1BOXCLR
ALENBST (F)* EIPPCODE (F)* NTWKNUM PTDESC SLOTNUM
ALPRIOR EUDESC OFFNRMPR (F)* PV STATE0
ASSOCDSP HIGHAL (F)* PNTFORM PVFL STATE1
BOXCLR KEYWORD PNTNODTY S0BOXCLR STATETXT
CNFMU NAME PNTTYPE UNIT
CNFPU NODENUM

2.6 Box Numeric

The parameters of the Box Numeric Data Point are listed below in alphabetical order. The
Point Form parameter is set to Full.
ASSOCDSP EUDESC NODETYP PNTNODTY PV
CNFMU KEYWORD NTWKNUM PNTTYPE PVFORMAT
CNFPU NAME PNTFORM PRIMMOD SLOTNUM
NODENUM PTDESC UNIT

2.7 Box Timer

The parameters of the Box Timer Data Point are listed below in alphabetical order. The
Point Form parameter is set to Full.
ASSOCDSP NAME PNTNODTY PV SP
COMMAND NODENUM PNTTYPE RV STATE
EUDESC NODETYP PRIMMOD SLOTNUM TIMEBASE
KEYWORD NTWKNUM PTDESC SO TIMOUTFL
PERIOD UNIT

HPM Parameter Reference Dictionary 2-3 8/97


2.8

2.8 Device Control (DevCtl)

The parameters of the Device Control Data Point are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) (#Inputs>0) LOCALMAN (#Outputs>0) OVRCTIM
ACCELTIM LODSTN 1-2 OVRDCONF
ALENBST (F) LOENBL 1-2 OVRDDESC
ASSOCDSP LOGICSRC OVRDI0FL
BADPVFL (F) LOSRC 1-2 OVRD1FL
BADPVPR (F) MAINDAT OVRD2FL
BADPVTXT MAINTOPT OVRDALOP
BADSVFL (#Inputs>0) MANMODFL OVRDALPR (F)
BADSVPR (F) MASKTIM OVRDSIFL
BOXCLR MAXTIM0H P0 (#Outputs>0)
BYPASS MAXTIM1H P1 (#Outputs>0)
CMDDISFL MAXTIM2H P2 (#Outputs>0)
CMDDISPR (F) MAXTRAN0 PAUSETIM
CMDFALFL MAXTRAN1 PERIOD
CMDFALTM MAXTRAN2 PFDLYFL
CNFERRFL MODATTR (#Outputs>0) PGALGID 1-4
CNFMU MODE (#Outputs>0) PGDSTN 1-4
CNFPU MODEAPPL (#Outputs>0) PGPLSWTH 1-4
CONTCUT MODEPERM (#Outputs>0) PGSO 1-4
D1 MODNUM PIALGID 1-12
D1_0 MOMSTATE (#Outputs>0) PIDEADBD1-12
D1_1 (#Inputs>0) MOVPVFL (#Inputs>0) PINN 1-12
D2 (#Inputs=1) MOVPVTXT PISO 1-12
D2D1_00 (#Inputs=1) NAME PISRC 1-12
D2D1_01 (#Inputs=2) NI0 (#Outputs>0) PNTFORM
D2D1_10 (#Inputs=2) NI1 (#Outputs>0) PNTMODTY
D2D1_11 (#Inputs=2) NI2 (#Outputs>0) PNTNODTY
D3 (#Inputs=2) NMODATTR (#Outputs>0) PNTSTATE
D4 (#Inputs=2) NMODE (#Outputs>0) PNTTYPE
D5 NN PRGATRFL
DB_VALID NNINSET 1-10 PRIMMOD (F)
DEADBAND NODENUM PSDLYFL
DEADTIME NODETYP PTDESC
DISRC NODINPTS PTEXECST
DODSTN NODOPTS PTINAL
EIPPCODE (F) (#Inputs>0) NOLINPTS PULSEWTH (#Outputs>0)
EUDESC (#Outputs>0) NOLOPTS PV (#Inputs>0)
EVTOPT (F) NONECONF PVAUTO (#Inputs>0)
FBTIME (F) NONE_OP1-3 PVFL (#Inputs>0)
FL 1-12 (#Inputs>0) NOPGATE PVNORMAL (F)
HIGHAL (F) NORMCYCL PVNORMFL
HIGHALPR NOSGATE PVSOURCE (F) (#Inputs>0)
HISVPEAK NOSIOVRD PVSRCOPT (F) (#Inputs>0)
I0 NOSTATES PVSTATES 0-4 (#Inputs>0)
I0CONF NOTRANS0 PVTXTOPT
I1 (#Outputs>0) NOTRANS1 REDTAG (F) (#Outputs>0)
I1CONF NOTRANS2 RESETFL
I2 (#Outputs>0) NRMATRFL S0BOXCLR
I2CONF NSI0 (#Outputs>0) S1BOXCLR
INITMAN (#Outputs>0) NTWKNUM S2BOXCLR
INITREQ OFFNRMFL SCHSTS
KEYWORD OFFNRMPR (F) SEALOPT
L OP (#Outputs>0) SECVAR
LIBADOPT OPCMD (#Outputs>0) SGALGID 1-2
LIDESC OPFINAL (#Outputs>0) SGDSTN 1-2
LISRC 1-12 OPRATRFL (#Outputs>0) SGPLSWTH 1-2
LMREV OROPT (#Outputs>0) SGSO 1-2
LMSRC

HPM Parameter Reference Dictionary 2-4 8/97


2.8

2.8 Device Control (DevCtl) con’t

Continuation of the Device Control parameters are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
SI0 STATE0 SVHHPR (F)
SI0ALOPT STATE1 SVHHTP
SI0ALPR (F) STATE2 SVHHTPP
SI0CONF STATTIM0 SVHIFL
SIALGID 1-12 STATTIM1 SVHIPR (F)
SIDLYTIM 1-12 STATTIM2 SVHITP
SIDSTN 1-12 STATETXT0-4 SVHITPP
SISO 1-12 STCHGOPT SVP
SLOTNUM STSMSG SVPEAK
SO 0-2 SVALDB SVSRC
SOCMD SVALDBEU SVTV
ST0_OP1 (#Outputs>0) SVDESC SVTVP
ST0_OP2 (#Outputs>=2) SVEUDESC TRANTIM0
ST0_OP3 (#Outputs>=3) SVEUHI TRANTIM1
ST1_OP1 (#Outputs>0) SVEULO TRANTIM2
ST1_OP2 (#Outputs>=2) SVHHFL UNCMDFL
ST1_OP3 (#Outputs>=3) UNIT
ST2_OP1 (#Outputs>0) USERID
ST2_OP2 (#Outputs>=2)
ST2_OP3 (#Outputs>=3)

HPM Parameter Reference Dictionary 2-5 8/97


2.9

2.9 Digital Composite (DigComp)

The parameters of the Digital Composite Data Point are listed below in alphabetical order.
(F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) (#Inputs>0) MODATTR (#Outputs>0) PRIMMOD (F)
ALENBST (F) MODE (#Outputs>0) PRGATRFL
ALPRIOR MODEAPPL (#Outputs>0) PSDLYFL
ASSOCDSP MODEPERM (#Outputs>0) PTDESC
BADCTLPR MODNUM PTEXECST
BADPVFL (F) (#Inputs>0) MOMSTATE (#Outputs>0) PTINAL
BADPVPR (F) MOVPVFL (#Inputs>0) PULSEWDTH
BADPVTXT MOVPVTXT PV (#Outputs>0)
BOXCLR NAME PVAUTO (#Inputs>0)
BYPASS NI0 (#Outputs>0) PVFL 0-2 (#Inputs>0)
CMDDISFL NI1 (#Outputs>0) PVNORMAL (F) (#Inputs>0)
CMDDISPR NI2 (#Outputs>0) PVSOURCE (F)
CMDFALFL NMODATTR (#Outputs>0) PVSRCOPT (F) (#Inputs>0)
CMDFALTM NMODE (#Outputs>0) PVSTATES 0-4 (#Inputs>0)
CNFERRFL NODENUM PVTXTOPT (#Inputs>0)
CNFMU NODETYP REDTAG (F)
CNFPU NODINPTS RESETFL (#Outputs>0)
CONTCUT (F) NODOPTS S0BOXCLR
D1 NONECONF S1BOXCLR
D1_0 NONE_OP1-3 S2BOXCLR
D1_1 (#Inputs>0) NORMCYCL SCHSTS
D2 (#Inputs=1) NOSIOVRD SEALOPT
D2D1_00 (#Inputs=1) NOSTATES SI0
D2D1_01 (#Inputs=2) NOTRANS1 SI0ALOPT
D2D1_10 (#Inputs=2) NOTRANS0 SI0ALPR (F)
D2D1_11 (#Inputs=2) NOTRANS2 SI0CONF
DISRC 1-2 (#Inputs=2) NRMATRFL SLOTNUM
DODSTN 1-3 (#Inputs=2) NSI0 (#Outputs>0) SO
EIPPCODE (F) (#Inputs>0) NTWKNUM SOCMD (#Outputs>0)
EUDESC (#Outputs>0) OFFNRMFL ST0_OP1 (#Outputs>0)
EVTOPT (F) OFFNRMPR (F) ST0_OP2 (#Outputs>0)
FBTIME (F) OP (#Outputs>0) ST0_OP3 (#Outputs>=2)
HIGHAL (F) (#Inputs>0) OPCMD (#Outputs>0) ST1_OP1 (#Outputs>=3)
HIGHALPR OPFINAL (#Outputs>0) ST2_OP1 (#Outputs>0)
I0 (#Outputs>0) OPRATRFL (#Outputs>0) ST1_OP2 (#Outputs>0)
I0CONF OVRDALOP ST2_OP2 (#Outputs>=2)
I0DESC OPSTTEXT ST1_OP3 (#Outputs>=2)
I1 (#Outputs>0) OVRDALPR (F) ST2_OP3 (#Outputs>=3)
I1CONF OROPT (#Outputs>0) STATE0 (#Outputs>=3)
I1DESC OVRDCONF STATE1
I2 (#Outputs>0) OVRDDESC STATE2
I2CONF OVRDI0FL STATETXT 0-4
I2DESC OVRDI1FL STATTIM0
INITMAN OVRDI2FL STATTIM1
INITREQ OVRDSIFL STATTIM2
KEYWORD P0 (#Outputs>0) STCHGOPT
LOCALMAN P1 (#Outputs>0) STSMSG
LOGICSRC P2 (#Outputs>0) TRANTIM1
MAINDAT (#Outputs>0) PAUSETIM TRANTIM2
MAINTOPT PERIOD UNCMDFL
MAXTIM0H PFDLYFL UNIT
MAXTIM1H PNTFORM USERID
MAXTIM2H PNTMODTY
MAXTRAN0 PNTNODTY
MAXTRAN1 PNTSTATE
MAXTRAN2 PNTTYPE

HPM Parameter Reference Dictionary 2-6 8/97


2.10

2.10 Digital Input (DigIn)

The parameters of the Digital Input Data point are listed below in alphabetical order. (L),
(S), or (A)—parameter applies only when DITYPE = Latched, Status, or Accum. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) DLYTIME (S) (F) OVERVAL (A) (F) PVSOURCE (L) (F)
ALENBST (S) (F) EIPPCODE (S) (L) (F) PNTFORM PVSRCOPT (S) (L) (F)
ALMOPT (S) (F) EUDESC PNTNODTY RESETFL (A)
ALPRIOR EVTOPT (L) (F) PNTMODTY RESETVAL (A)
ASSOCDSP HIGHAL (S) PNTSTATE S0BOXCLR (S) (L)
AV (A) INPTDIR (F) PNTTYPE S1BOXCLR (S) (L)
AVTV (A) KEYWORD PRIMMOD (F) SLOTNUM
AVTVFL (A) MODNUM PTDESC STARTFL (A)
BADPVFL (F) NAME PTEXECST STATE (A)
BADPVPR NODENUM PV (S) (L) STATE0 (S) (L)
BOXCLR (L) NODETYP PVAUTO (S) (L) STATE1 (S) (L)
COMMAND (A) NTWKNUM PVCHGDLY (S) (L) (F) STATETXT 0-2 (S) (L)
CONTCUT (S) (F) OFFNRMFL (S) PVFL (S) (L) STOPFL (A)
COUNTDWN (A) OFFNRMPR (S) (F) PVNORMAL (S) (F) UNIT
DEBOUNCE (S) (L) OLDAV (A) PVNORMFL (S)
DITYPE (F) OVERFLOW (A) PVRAW

2.11 Digital Output (DigOut)

The parameters of the Digital Output Data point are listed below in alphabetical order. (S)
or (P) parameter applies only when DOTYPE = Status or Pulse Width Modulated (PWM).
This point type is available only in the component form.
ASSOCDSP NAME OP (P) PNTSTATE SLOTNUM
DOTYPE NODENUM OPTDIR (P) PNTTYPE SO (S)
EUDESC NODETYP PERIOD (P) PTDESC STATE0 (S)
INITREQ NTWKNUM PNTFORM PTEXECST STATE1 (S)
KEYWORD OFFPULSE (S) PNTMODTY S0BOXCLR (S) STDBYMAN
MODNUM ONPULSE (S) PNTNODTY S1BOXCLR (S) UNIT

HPM Parameter Reference Dictionary 2-7 8/97


2.12

2.12 Reserved

HPM Parameter Reference Dictionary 2-8 8/97


2.13

2.13 IOP

The parameters of the Input/Output Processor Point are listed below in alphabetical order.
CALIBALL IOMACTYP IOMTYPE IORECCHN RJRAW
CALIBRJ IOMFWREV IOMSTS LINEPERD SLOT0SF
FAILOPT IOMHWREV IONTOKEN MAXSLOTS STDBYSTS
FTAPRES IOMLHFST IOPSTR1 NODETYP SWTCHACT
FREQ6050 IOMOPER IOPSTR2 PIUOTDCF WARMSTRT

Some of the parameters in the above listing are arrays and are not defined in this
publication.

2.14 Logic

The parameters of the Logic Data Point (otherwise referred to as the Logic Slot) are listed
below in alphabetical order. (F) indicates that the parameter is applicable when the
PNTFORM = Full.
$AUXUNIT (F) C2SRC LISRC 1-12 NORMCYCL R2 1-24
ALENBST (F) C3SRC LODSTN 1-12 NTWKNUM S1 1-24
ASSOCDSP C4SRC LOENBL 1-12 PERIOD S1REV 1-24
C1DESC CNFERRFL LOGALGID 1-24 PFDLYFL S2 1-24
C2DESC CNFMU LOGMIX PNTFORM S2REV 1-24
C3DESC CNFPU LOSRC 1-12 PNTMODTY S3 1-24
C4DESC CONTCUT MODNUM PNTNODTY S3REV 1-24
C1FL DEADBAND 1-24 NAME PNTSTATE S4 1-24
C2FL DLYTIME 1-24 NN1-8 PRIMMOD (F) SCHSTS
C3FL EIPPCODE (F) NODENUM PRMDESC 1-12 (F) SLOTNUM
C4FL FL1-12 NODESC (F) PSDLYFL SO 1-24
C1PR (F) GENDESC (F) 1-12 NODETYP PTDESC STSMSG
C2PR (F) HIGHAL NOLINPTS PTEXECST UNIT
C3PR (F) HIGHALPR NOLOGBLK PTINAL USERID
C4PR (F) L1-12 NOLOPTS R1 1-24
C1SRC LIBADOPT

HPM Parameter Reference Dictionary 2-9 8/97


2.15

2.15 Process Module (ProcMod)


The parameters of the Process Module Data Point are listed below in alphabetical order.
(F) indicates that the parameter is applicable when the PNTFORM = Full.
ABHEMSD DIAGCMD OVERSTEP PTDESC SSTMT 1-2
ABHHOLD FL 1-27 OVRRUNFL RESTART STATMENT
ABHRSTR IOLPSERR OVRRUNPR RSTROPT STEP
ABHSHDN IOLPSOPT PERIOD RUNSTATE STR8 1-16
ACP (F) LSTWHNER PFDLYFL SEQERR STR16 1-8
ALPRIOR (F) MAXPU PHASE SEQEXEC STR32 1-4
ANAME 1-3 MSGPEND PHASEAL SEQMODE STR64 1-2
ASSOCDSP NAME (F) PHASETIM SEQNAME STRLEN
ASTEP 1-3 NN 1-80 PHREMTIM SEQOBJSZ STSMSG
ASTMT 1-3 NODENUM PNTFORM SEQPR (F) SUSPSTAT
AVGPU NODETYP PNTNODTY SEQSLTSZ SUSPTIME
BADIOLPF NOOVRRUN PNTTYPE SLOTNUM TIME 1-4
CNFMU NTWKNUM PROCMOD SNAME 1-2 UNIT
CNFPU OVERPHAS PRIMMOD (F) SPLOCK USERID
CNTLLOCK OVERSTAT PSDLYFL SSTEP 1-2
CLBACK

2.16 UCN Network

Listed below in alphabetical order are the parameters of the UCN Network Data Point
(system parameter $NTWRKnn where nn = the UCN number).
CHPINHWY HWYCTLST NIMADDR NIMREV NMSGTXT
CLPZMXC LOADSCOP NIMDAY NIMVERS TIMESYNC
CLPZMXP MSGTXT 0-15 NIMMONTH NIMYEAR UPGRADE

2.17 UCN Node

The parameters of the UCN Node Data Point are listed below in alphabetical order. They
can be accessed as follows:
$NMuuNnn.parameter where,
uu is the UCN network number, and nn is the UCN node number.
$UCNLSB 1-50 NODESTS NTRQUAVG* UCNRECHN
CABLESTS NODESTAT NTRQUMAX* UPGRADE
CLPZMXC NODETYP NTRSPAVG* UTSDRIFT
CLPZMXP NPRQUAVG* NTRSPMAX* UTSNODE
LOADSCOP NPRQUMAX* TIMESYNC UTSTBCRV
MDMHWREV NPRSPAVG* TRATAVG UTSTIME
MODNUM NPRSPMAX* TRATMAX UTSTIMST
NMSGTXT

*These parameters are indexed. The index is either an odd number from 1 to 63 and represents either—
• the UCN node number of a peer node for peer-to-peer statistics with that node
• 0 for the sum of all peer-to-peer statistics
Example for case 2 is: NPRQUAVG(0) = NPRQUAVG(1) + NPRQUAVG(3) + ... + NPRQUAVG(63)

HPM Parameter Reference Dictionary 2-10 8/97


3

PARAMETERS PER ALGORITHM TYPE


Section 3
This section contains listings of parameters that are applicable to each PV and control algorithm in
the HPM. Refer to Sections $ - X for the definitions of the parameters.

3.1 Auto Manual (AutoMan)


The parameters of the Auto Manual contrrol algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) CTLALGID MODEPERM OPLAFL (F) PTORST
ALENBST (F) CTRLINIT MODNUM OPLOFL RARWSTS
ARWNET CV NAME OPLOLM RATE1
ARWOP CVEUHI NMODATTR OPLOPR (F) RCASOPT
ASSOCDSP CVEULO NMODE OPLOTP (F) RCASSHED
AUTMODFL ESWAUTO NOCINPTS OPMCHLM REDTAG (F)
B ESWCAS NOCOPTS OPRATRFL RINITREQ
B0 ESWENBST NODENUM OPROCLM RINITVAL
BADCTLFL ESWMAN NODETYP $OPTOL SAFEOP
BADCTLOP EUDESC NORMCYCL OVERVAL (F) SCHSTS
BADCTLPR (F) EXTSWOPT NRMATRFL PERIOD SHEDMODE
BCAMODFL HIGHAL (F) NRMMODFL PFDLYFL SHEDTIME
CASMODFL HIGHALPR (F) NTWKNUM PNTFORM SHUTDOWN
CASREQ INITMAN OP PNTMODTY SLOTNUM
CIDSTN K OPALDB (F) PNTNODTY STDBYMAN
CISRC KEYWORD OPEU PNTSTATE STSMSG
CNFMU LOCALMAN OPHAFL (F) PNTTYPE UNIT
CNFPU MANMODFL OPHIFL PRGATRFL USERID
CODSTN MODATTR OPHILM PRIMMOD (F) X1
CONTCUT (F) MODEAPPL OPHIPR (F) PSDLYFL X2
CTLEQN MODE OPHITP (F) PTDESC XEUHI
PTEXECST XEULO
PTINAL

HPM Parameter Reference Dictionary 3-1 8/97


3.2
3.2 Calculator (Calcultr)
The parameters of the Calculator PV algorithm are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) NAME PFDLYFL PVCLAMP PVLOTP (F)
ALENBST (F) P3 PIDSTN PVEUHI PVP
ASSOCDSP NODENUM PISRC PVEULO PVROCNFL
BADPVFL (F) NODETYP PNTFORM PVEXEUHI PVROCNPR (F)
BADPVPR (F) NOPINPTS PNTMODTY PVEXEULO PVROCNTP (F)
C1 NORMCYCL PNTNODTY PVEXHIFL PVROCPFL
C2 NTWKNUM PNTSTATE PVEXLOFL PVROCPPR (F)
C3 OVERVAL (F) PNTTYPE PVFORMAT PVROCPTP (F)
C4 P1 PRIMMOD (F) PVHHFL PVSGCHTP (F)
CALCEXP P1STS PSDLYFL PVHHPR (F) PVSOURCE (F)
CNFMU P2 PTDESC PVHHTP (F) PVSRCOPT (F)
CNFPU P2STS PTEXECST PVHIFL PVSTS
CONTCUT (F) P3STS PTINAL PVHIPR (F) PVTV (F)
EUDESC P4 PV PVHITP (F) PVTVP (F)
HIGHAL (F) P4STS PVALDB (F) PVINIT SCHSTS
HIGHALPR (F) P5 PVALDBEU (F) PVLLFL SLOTNUM
KEYWORD P5STS PVALGID PVLLPR (F) STSMSG
LASTPV P6 PVAUTO PVLLTP (F) TF
MODNUM P6STS PVAUTOST PVLOFL UNIT
N PERIOD PVCALC PVLOPR (F) USERID

HPM Parameter Reference Dictionary 3-2 8/97


3.3
3.3 Data Acquisition (DataAcq)

The parameters of the Data Acquisition PV algorithm are listed below in alphabetical order.
(F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) NOPINPTS PTEXECST PVHHFL PVROCNPR (F)
ALENBST (F) NORMCYCL PTINAL PVHHPR (F) PVROCNTP (F)
ASSOCDSP NTWKNUM PV PVHHTP (F) PVROCPVFL
BADPVFL (F) OVERVAL (F) PVALDB (F) PVHIFL PVROCPPR (F)
BADPVPR (F) P1 PVALDBEU (F) PVHIPR (F) PVROVPTP (F)
CONCUT (F) P1STS PVALGID PVHITP (F) PVSGCHTP (F)
CNFMU PERIOD PVAUTO PVINIT PVSOURCE (F)
CNFPU PFDLYFL PVAUTOST PVLLFL PVSRCOPT (F)
EUDESC PIDSTN PVCALC PVLLPR (F) PVSTS
HIGHAL (F) PISRC PVCLAMP PVLLTP (F) PVTV (F)
HIGHALPR (F) PNTFORM PVEUHI PVLOFL PVTVP (F)
KEYWORD PNTMODTY PVEULO PVLOPR (F) SCHSTS
LASTPV PNTNODTY PVEXEUHI PVLOTP (F) SLOTNUM
MODNUM PNTSTATE PVEXEULO PVP STSMSG
NAME PNTTYPE PVEXHIFL PVROCNFL TF
NODENUM PRIMMOD (F) PVEXLOFL UNIT
NODETYP PSDLYFL PVFORMAT USERID
PTDESC

3.4 Flow Compensation (FlowComp)

The parameters of the Flow Compensation PV algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) LASTPV PSDLYFL PVHHFL PVSRCOPT (F)
ALENBST (F) MODNUM PTDESC PVHHPR (F) PVSTS
ASSOCDSP NAME PTEXECST PVHHTP (F) PVTV (F)
BADPVFL (F) NODENUM PTINAL PVHIFL PVTVP (F)
BADPVPR (F) NODETYP PV PVHIPR (F) Q
C NOPINPTS PVALDB (F) PVHITP QSTS
C1 NORMCYCL PVALDBEU (F) PVINIT RG
C2 NTWKNUM PVALGID PVLLFL RP
CNFMU OVERVAL (F) PVAUTO PVLLPR (F) RQ
CNFPU P PVAUTOST PVLLTP (F) RT
COMPHILM PERIOD PVCALC PVOFL RX
COMPLOLM PFDLYFL PVCHAR PVLOPR (F) SCHSTS
COMPTERM P0 PVCLAMP PVLOTP (F) SLOTNUM
CONTCUT (F) PIDSTN PVEQN PVP STSMSG
EUDESC PISRC PVEUHI PVROCNFL T
F PNTFORM PVEULO PVROCNPR (F) T0
FSTS PNTMODTY PVEXEUHI PVROCNTP (F) TF
G PNTNODTY PVEXEULO PVROCPFL TSTS
GSTS PNTSTATE PVEXHIFL PVROCPPR (F) UNIT
HIGHAL (F) PNTTYPE PVEXLOFL PVROCPTP (F) USERID
HIGHALPR (F) PRIMMOD (F) PVFORMAT PVSGCHTP (F) X
KEYWORD PSTS PVSOURCE (F) XSTS

HPM Parameter Reference Dictionary 3-3 8/97


3.5

3.5 General Linearization (GenLin)

The parameters of the General Linearization PV algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) IN11 OUT12 PVALDBEU (F) PVLOPR (F)
ALENBST (F) IN12 OVERVAL (F) PVALGID PVLOTP (F)
ASSOCDSP KEYWORD P1 PVAUTOST PVP
BADPVFL (F) LASTPV P1STS PVCALC PVROCNFL
BADVPR (F) MODNUM PERIOD PVCLAMP PVROCNPR (F)
CNFMU NAME PFDLYFL PVEUHI PVROCNTP (F)
CNFPU NODENUM PIDSTN PVEULO PVROCPFL
CONTCUT (F) NODETYP PISRC PVEXEUHI PVROCPPR (F)
EUDESC NOPINPTS PNTFORM PVEXEULO PVROCPTP (F)
HIGHAL (F) NORMCYCL PNTMODTY PVEXHIFL PVSGCHTP (F)
HIGHALPR (F) NTWKNUM PNTNODTY PVEXLOFL PVSOURCE (F)
IN0 OUT0 PNTSTATE PVFORMAT PVSRCOPT (F)
IN1 OUT1 PNTTYPE PVHHFL PVSTS
IN2 OUT2 PRIMMOD (F) PVHHPR (F) PVTV (F)
IN3 OUT3 PSDLYFL PVHHTP (F) PVTVP (F)
IN4 OUT4 PTDESC PVHIFL SCHSTS
IN5 OUT5 PTEXECST PVHIPR (F) SEGTOT
IN6 OUT6 PTINAL PVHITP (F) SLOTNUM
IN7 OUT7 PV PVINIT STSMSG
IN8 OUT8 PVAUTO PVLLFL TF
IN9 OUT9 PVALDB (F) PVLLPR (F) UNIT
IN10 OUT10 PVLLTP (F) USERID
OUT11 PVLOFL

3.6 High-Low Average (HiLoAvg)

The parameters of the High-Low Average PV algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) NODETYP PISRC PVEUHI PVP
ALENBST (F) NOPINPTS PNTFORM PVEULO PVROCNFL
ASSOCDSP NORMCYCL PNTMODTY PVEXEUHI PVROCNPR (F)
BADPVFL (F) NTWKNUM PNTNODTY PVEXEULO PVROCNTP (F)
BADPVPR (F) OVERVAL (F) PNTSTATE PVEXHIFL PVROCPFL
CNFMU P1 PNTTYPE PVEXLOFL PVROCPPR (F)
CNFPU P1STS PRIMMOD (F) PVFORMAT PVROCPTP (F)
CONTCUT (F) P2 PSDLYFL PVHHFL PVSGCHTP (F)
EUDESC P2STS PTDESC PVHHPR (F) PVSOURCE (F)
FORCE P3 PTEXECST PVHHTP (F) PVSRCOPT (F)
FRCPERM P3STS PTINAL PVHIFL PVSTS
FSELIN P4 PV PVHIPR (F) PVTV (F)
HIGHAL (F) P4STS PVALDB (F) PVHITP (F) PVTVP (F)
HIGHALPR (F) P5 PVALDBEU (F) PVINIT SCHSTS
KEYWORD P5STS PVALGID PVLLFL SELINP
LASTPV P6 PVAUTO PVLLPR (F) SLOTNUM
MODNUM P6STS PVAUTOST PVLLTP (F) STSMSG
N PERIOD PVCALC PVLOFL TF
NAME PFDLYFL PVCLAMP PVLOPR (F) UNIT
NMIN PIDSTN PVEQN PVLOTP (F) USERID
NODENUM

HPM Parameter Reference Dictionary 3-4 8/97


3.7

3.7 Incremental Summer (IncrSum)

The parameters of the Incremental Summer control algorithm are listed below in
alphabetical order. (F) indicates that the parameter is applicable when the PNTFORM =
Full.
$AUXUNIT (F) CVEULO MODEPERM OPLOFL RARWSTS
ALENBST (F) DELCV MODNUM OPLOLM RCASOPT
ARWNET ESWAUTO NAME OPLOPR (F) RCASSHED
ARWOP ESWCAS NMODATTR OPLOTP (F) REDTAG (F)
ASSOCDSP ESWENBST NMODE OPMCHLM RINITREQ
AUTMODFL ESWMAN NOCINPTS OPRATRFL RINITVAL
BADCTLFL EUDESC NOCOPTS OPROCLM SAFEOP
BADCTLPR (F) EXTSWOPT NODENUM $OPTOL SCHSTS
BCAMODFL HIGHAL (F) NODETYP OVERVAL (F) SHEDMODE
CASMODFL HIGHALPR (F) NORMCYCL PERIOD SHEDTIME
CASREQ INITMAN NRMATRFL PFDLYFL SHUTDOWN
CIDSTN K1 NRMMODFL PNTFORM SLOTNUM
CISRC K2 NTWKNUM PNTMODTY STDBYMAN
CNFMU K3 OP PNTNODTY STSMSG
CNFPU K4 OPALDB (F) PNTSTATE UNIT
CODSTN KEYWORD OPEU PNTTYPE USERID
CONTCUT (F) LOCALMAN OPHAFL (F) PRGATRFL X1
CTLALGID M OPHIFL PRIMMOD (F) X2
CTRLINIT MANMODFL OPHILM PSDLYFL X3
CV MODATTR OPHIPR (F) PTDESC X4
CVEUHI MODE OPHITP (F) PTEXECST XEUHI
MODEAPPL OPLAFL (F) PTINAL XEULO
PTORST

3.8 Middle-of-3 (MidOf3)

The parameters of the Middle-Of-3 PV algorithm are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) NORMCYCL PSDLYFL PVEXLOFL PVROCNPR (F)
ALENBST (F) NTWKNUM PTDESC PVFORMAT PVROCNTP (F)
ASSOCDSP OVERVAL (F) PTEXECST PVHHFL PVROCPFL
BADPVFL (F) P1 PTINAL PVHHPR (F) PVROCPPR (F)
BADPVPR (F) P1STS PV PVHHTP (F) PVROCPTP (F)
CNFMU P2 PVALDB (F) PVHIFL PVSGCHTP (F)
CNFPU P2STS PVALDBEU (F) PVHIPR (F) PVSOURCE (F)
CONTCUT (F) P3 PVALGID PVHITP (F) PVSRCOPT (F)
EUDES C P3STS PVAUTO PVINIT PVSTS
HIGHAL (F) PERIOD PVAUTOST PVLLFL PVTV (F)
HIGHALPR (F) PFDLYFL PVCALC PVLLPR (F) PVTVP (F)
KEYWORD PIDSTN PVCLAMP PVLLTP (F) SCHSTS
LASTPV PISRC PVEQN PVLOFL SELINP
MODNUM PNTFORM PVEUHI PVLOPR (F) SLOTNUM
NAME PNTMODTY PVEULO PVLOTP (F) STSMSG
NODENUM PNTNODTY PVEXEUHI PVP TF
NODETYP PNTSTATE PVEXEULO PVROCNFL UNIT
NOPINPTS PNTTYPE PVEXHIFL USERID
PRIMMOD (F)

HPM Parameter Reference Dictionary 3-5 8/97


3.9

3.9 Multiply/Divide (MulDiv)

The parameters of the Multiply/Divide control algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) CTLALGID MODE OPHITP (F) PTEXECST
ALENBST (F) CTLEQN MODEAPPL OPLAFL (F) PTINAL
ARWNET CTRLINIT MODEPERM OPLOFL PTORST
ARWOP CV MODNUM OPLOLM RARWSTS
ASSOCDSP CVEUHI NAME OPLOPR (F) RATE1
AUTMODFL CVEULO NMODATTR OPLOTP (F) RCASOPT
B ESWAUTO NMODE OPMCHLM REDTAG (F)
B1, B2, B3 ESWCAS NOCINPTS OPRATRFL RINITREQ
BADCTLFL ESWENBST NODENUM OPROCLM RINITVAL
BADCTLOP ESWMAN NODETYP $OPTOL SAFEOP
BADCTLPR (F) EUDESC NORMCYCL OVERVAL (F) SCHSTS
BCAMODFL EXTSWOPT NRMATRFL PERIOD SHEDMODE
CASMODFL HIGHAL (F) NRMMODFL PFDLYFL SHEDTIME
CASREQ HIGHALPR (F) NTWKNUM PNTFORM SHUTDOWN
CIDSTN INITMAN OP PNTMODTY SLOTNUM
CISRC K OPALDB (F) PNTNODTY STDBYMAN
CNFMU K1, K2, K3 OPEU PNTSTATE STSMSG
CNFPU KEYWORD OPHAFL (F) PNTTYPE UNIT
CODSTN LOCALMAN OPHIFL PRGATRFL USERID
CONTCUT (F) MANMODFL OPHILM PRIMMOD (F) X1, X2, X3
MODATTR OPHIPR (F) PSDLYFL
PTDESC

3.10 Override Selector (ORSel)

The parameters of the Override Selector control algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) CODSTN MODEPERM OPLOLM RARWSTS
ALENBST (F) CONTCUT (F) MODNUM OPLOPR (F) RCASOPT
ARWNET CTALGID NAME OPLOTP (F) RCASSHED
ARWOP CTLEQN NMODATTR OPMCHLM REDTAG (F)
ASSOCDSP CTRLINIT MODE OPRATRFL RINITREQ
AUTMODFL CV NOCINPTS OPROCLM RINITVAL
BADCTLFL CVEUHI NOCOPTS $OPTOL SAFEOP
BADCTLOP CVEULO NODENUM OROFFSET SCHSTS
BADCTLPR (F) ESWAUTO NODETYP OROPT SELXINP
BCAMODFL ESWCAS NORMCYCL OVERVAL (F) SHEDMODE
BYPASS ESWENBST NRMATRFL PERIOD SHEDTIME
BYPASSX1 ESWMAN NRMMODFL PFDLYFL SHUTDOWN
BYPASSX2 EUDESC NTWKNUM PNTFORM SLOTNUM
BYPASSX3 EXTSWOPT OP PNTMODTY STDBYMAN
BYPASSX4 HIGHAL (F) OPALDB (F) PNTNODTY STSMSG
BCAMODFL HIGHALPR (F) OPEU PNTSTATE UNIT
CASMODFL INITMAN OPHAFL (F) PNTTYPE USERID
CASREQ KEYWORD OPHIFL PRGATRFL X1
CIDSTN LOCALMAN OPHILM PRIMMOD (F) X2
CISRC M OPHIPR (F) PSDLYFL X3
CNFMU MANMODFL OPHITP (F) PTDESC X4
CNFPU MODE OPLAFL (F) PTEXECST XEUHI
MODEAPPL OPLOFL PTINAL XEULO
PTORST

HPM Parameter Reference Dictionary 3-6 8/97


3.10

3.10 Pid

The parameters of the Pid control algorithm are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) DEV NLGAIN PNTTYPE PVTRACK
ADVDEVFL DEVHIFL NMODATTR PRGATRFL RAMPTIME
ADVDEVPR (F) DEVHITP (F) NMODE PSDLYFL RARWSTS
ADVDEVTP (F) DEVLOFL NOCINPTS PTDESC RATIO
ADVSP (F) DEVLOPR (F) NOCOPTS PTEXECST RBOPT
ADVSPP (F) DEVLOTP (F) NODENUM PTINAL RCASOPT
ALENBST (F) ESWAUTO NODETYP PTORST RCASSHED
ARWNET ESWCAS NORMCYCL PV REDTAG (F)
ARWOP ESWENBST NRMATRFL PVALDB (F) RINITREQ
ASPPROC (F) ESWMAN NRMMODFL PVALDBEU (F) RINITVAL
ASSOCDSP EUDESC NTWKNUM PVAUTO RTHILM
AUTMODFL EXTSWOPT OP PVAUTOST RTLOLM
BADCTLFL GAINOPT OPCMD PVEUHI SAFEOP
BADCTLOP GAPHI OPALDB (F) PVEULO SAFOPCMD
BADCTLPR (F) GAPLO OPEU PVFORMAT SCHSTS
BADPVFL (F) HIGHAL (F) OPHAFL (F) PVHHFL SHEDMODE
BADPVPR (F) HIGHALPR (F) OPHIFL PVHHPR (F) SHEDTIME
BCAMODFL INITMAN OPHILM PVHHTP (F) SHUTDOWN
BIAS K OPHIPR (F) PVHIFL SLOTNUM
BSHILM KEXT OPHISRC PVHIPR (F) SP
BSLOLM KEYWORD OPHITP (F) PVHITPID SPEUHI
CASMODFL KGAP OPLAFL (F) PVLLFL SPEULO
CASREQ KLIN OPLOFL PVLLPR (F) SPFORMAT
CIDSTN KNL OPLOLM PVLLTP (F) SPHIFL
CISRC LASTPV OPLOPR (F) PVLOFL SPHILM
CNFMU LMSRC OPLOSRC PVLOTP (F) SPLOFL
CNFPU LOCALMAN OPLOTP (F) PVLOPR (F) SPLOLM
CODSTN MANMODFL OPMCHLM PVP SPOPT
CONTCUT (F) MANOPCMD OPRATRFL PVROCNFL SPP
CTLACTN MANOPTIME OPROCLM PVROCNPR (F) $SPTOL
CTLALGID MAXPULSE $OPTOL PVROCNTP (F) SPTV
CTLEQN MODATTR OVERVAL (F) PVROCPFL SPTVP
CTRLINIT MODE PERIOD PVROCPPR (F) STDBYMAN
CV MODEAPPL PFDLYFL PVROCPTP (F) STSMSG
CVEUHI MODEPERM PIDFORM PVSGCHTP (F) T1
CVEULO MODNUM PNTFORM PVSOURCE (F) T2
DELCV NAME PNTMODTY PVSRCOPT (F) TVPROC
NLFM PNTNODTY PVSTS UNIT
PNTSTATE USERID

HPM Parameter Reference Dictionary 3-7 8/97


3.11

3.11 Pid with External Reset Feedback (PidErfb)

The parameters of the Pid with External Reset Feedback control algorithm are listed below
in alphabetical order. (F) indicates that the parameter is applicable when the PNTFORM =
Full.
$AUXUNIT (F) DEV NMODE PTEXECST RATIO
ADVDEVFL DEVHIFL NOCINPTS PTINAL RBOPT
ADVDEVPR (F) DEVHIPR (F) NOCOPTS PTORST RCASOPT
ADVDEVTP (F) DEVHITP (F) NODENUM PV RCASSHED
ADVSP (F) DEVLOFL NODETYP PVALDB (F) REDTAG (F)
ADVSPP (F) DEVLOPR (F) NORMCYCL PVALDBEU (F) RFB
ALENBST (F) DEVLOTP (F) NRMATRFL PVAUTO RINITREQ
ARWNET ESWAUTO NRMMODFL PVAUTOST RINITVAL
ARWOP ESWCAS NTWKNUM PVEUHI RTHILM
ASSOCDSP ESWENBST OP PVEULO RTLOLM
ASPPROC (F) ESWMAN OPALDB (F) PVFORMAT S1
AUTMODFL EUDESC OPEU PVHHFL SAFEOP
BADCTFL EXTSWOPT OPHAFL (F) PVHHTP (F) SCHSTS
BADCTLOP GAINOPT OPHIFL PVHHPR (F) SHEDMODE
BADCTLPR (F) GAPHI OPHILM PVHIFL SHEDTIME
BADPVFL (F) GAPLO OPHIPR (F) PVHIPR (F) SHUTDOWN
BADPVPR (F) HIGHAL (F) OPHITP (F) PVHITP (F) SLOTNUM
BCAMODFL HIGHALPR (F) OPLAFL (F) PVLLFL SP
BIAS INITMAN OPLOFL PVLLPR (F) SPEUHI
BSHILM K OPLOLM PVLLTP (F) SPEULO
BSLOLM K1 OPLOPR (F) PVLOFL SPFORMAT
CASMODFL KEXT OPLOTP (F) PVLOTP (F) SPHIFL
CASREQ KEYWORD OPMCHLM PVLOPR (F) SPHILM
CIDSTN KGAP OPRATRFL PVP SPLOFL
CISRC KLIN OPROCLM PVROCNFL SPLOLM
CNFMU KNL $OPTOL PVROCNPR (F) SPOPT
CNFPU LASTPV OVERVAL (F) PVROCNTP (F) SPP
CODSTN LOCALMAN PERIOD PVROCPFL $SPTOL
CONTCUT (F) MANMODFL PFDLYFL PVROCPPR (F) SPTV
CTLACTN MODATTR PIDFORM PVROCPTP (F) SPTVP
CTLALGID MODE PNTFORM PVSGCHTP (F) STSMSG
CTLEQN MODEAPPL PNTMODTY PVSOURCE (F) STDBYMAN
CTRLINIT MODEPERM PNTNODTY PVSRCOPT (F) T1
CV MODNUM PNTSTATE PVSTS T2
CVEUHI NAME PNTTYPE PVTRACK TRFB
CVEULO NLFM PRGATRFL RAMPTIME TVPROC
DELCV NLGAIN PSDLYFL RARWSTS UNIT
NMODATTR PTDESC USERID

HPM Parameter Reference Dictionary 3-8 8/97


3.12

3.12 Pid with Feed Forward (PidFf)

The parameters of the Pid with Feed Forward control algorithm are listed below in
alphabetical order. (F) indicates that the parameter is applicable when the PNTFORM =
Full.
$AUXUNIT (F) DELCV NAME PRGATRFL PVTRACK
ADVDEVFL DEV NLFM PSDLYFL RAMPTIME
ADVDEVPR (F) DEVHIFL NLGAIN PTDESC RARWSTS
ADVDEVTP DEVHIPR (F) NMODATTR PTEXECST RATIO
ADVSP (F) DEVHITP (F) NMODE PTINAL RBOPT
ADVSPP (F) DEVLOFL NOCINPTS PTORST RCASOPT
ALENBST (F) DEVLOPR (F) NOCOPTS PV RCASSHED
ARWNET DEVLOTP (F) NODENUM PVALDB (F) REDTAG (F)
ARWOP ESWAUTO NODETYP PVALDBEU (F) RINITREQ
ASPPROC (F) ESWCAS NORMCYCL PVAUTO RINITVAL
ASSOCDSP ESWENBST NRMATRFL PVAUTOST RTHILM
AUTMODFL ESWMAN NRMMODFL PVEUHI RTLOLM
BADCTLFL EUDESC NTWKNUM PVEULO SAFEOP
BADCTLOP EXTSWOPT OP PVFORMAT SCHSTS
BADCTLPR (F) FF OPALDB (F) PVHHFL SHEDMODE
BADPVFL (F) FFOPT OPEU PVHHPR (F) SHEDTIME
BADPVPR (F) GAINOPT OPHAFL (F) PVHHTP (F) SHUTDOWN
BCAMODFL GAPHI OPHIFL PVHIFL SLOTNUM
BFF GAPLO OPHILM PVHIPR (F) SP
BIAS HIGHAL (F) OPHIPR (F) PVHITP (F) SPEUHI
BSHILM HIGHALPR (F) OPHITP (F) PVLLFL SPEULO
BSLOLM INITMAN OPLAFL (F) PVLLPR (F) SPFORMAT
CASMODFL K OPLOFL PVLLTP (F) SPHIFL
CASREQ KEXT OPLOLM PVLOFL SPHILM
CIDSTN KEYWORD OPLOPR (F) PVLOTP (F) SPLOFL
CISRC KFF OPLOTP (F) PVLOPR (F) SPLOLM
CNFMU KGAP OPMCHLM PVP SPOPT
CNFPU KLIN OPRATRFL PVROCNFL SPP
CODSTN KNL OPROCLM PVROCNPR (F) SPTV
CONTCUT (F) LASTPV $OPTOL PVROCNTP (F) $SPTOL
CTLACTN LOCALMAN OVERVAL (F) PVROCPFL SPTVP
CTLALGID MANMODFL PERIOD PVROCPPR (F) STDBYMAN
CTLEQN MODATTR PFDLYFL PVROCPTP (F) STSMSG
CTRLINIT MODE PIDFORM PVSGCHTP (F) T1
CV MODEAPPL PNTFORM PVSOURCE (F) T2
CVEUHI MODEPERM PNTMODTY PVSRCOPT (F) TVPROC
CVEULO MODNUM PNTNODTY PVSTS UNIT
PNTSTATE USERID
PNTTYPE

HPM Parameter Reference Dictionary 3-9 8/97


3.13

3.13 PID Position Proportional (PidPosPr)

The parameters of the PID Position Proportional control algorithm are listed below in
alphabetical order.
$AUXUNIT (F) DELCV MINPULSE PTEXECST RAMPTIME
ADVDEVFL DEV MODATTR PTINAL RARWSTS
ADVDEVPR (F) DEVHIFL MODE PTORST RATIO
ADVDEVTP (F) DEVHIPR (F) MODEAPPL PV RBOPT
ADVSP (F) DEVHITP (F) MODEPERM PVALDB (F) RCASOPT
ADVSPP (F) DEVLOFL MODNUM PVALDBEU (F) RCASSHED
ALENBST (F) DEVLOPR (F) NAME PVAUTO REDTAG (F)
ARWNET DEVLOTP (F) NLFM PVAUTOST RINITREQ
ARWOP ESWAUTO NLGAIN PVEUHI RINITVAL
ASPPROC (F) ESWCAS NMODATTR PVEULO RP
ASSOCDSP ESWENBST NMODE PVFORMAT RT
AUTMODFL ESWMAN NOCINPTS PVHHFL RTHILM
BADCTLFL EUDESC NOCOPTS PVHHPR (F) RTLOLM
BADCTLOP EXTSWOPT NODENUM PVHHTP (F) SAFEOPCMD
BADCTLPR (F) GAINOPT NODETYP PVHIFL SCHSTS
BADPVFL (F) GAPHI NORMCYCL PVHIPR (F) SHEDMODE
BADPVPR (F) GAPLO NRMATRFL PVHITP (F) SHEDTIME
BADPVR (F) HIGHAL (F) NRMMODFL PVLLFL SHUTDOWN
BCAMODFL HIGHALPR (F) NTWKNUM PVLLPR (F) SLOTNUM
BIAS INITMAN OPCMD PVLLTP (F) SP
BSHILM K OPHIFL PVLOFL SPEUHI
BSLOLM K1 OPHISRC PVLOPR (F) SPEULO
CASMODFL KEXT OPLOFL PVLOTP (F) SPFORMAT
CASREQ KEYWORD OPLOSRC PVP SPHIFL
CIDSTN KGAP OVERVAL (F) PVROCNFL SPHILM
CISRC KLIN PERIOD PVROCNPR (F) SPLOFL
CNFMU KNL PFDLYFL PVROCNTP (F) SPLOLM
CNFPU LASTPV PIDFORM PVROCPFL SPOPT
CODSTN LMSRC PNTFORM PVROCPPR (F) SPP
CONTCUT (F) LOCALMAN PNTMODTY PVROCPTP (F) $SPTOL
CTLACTN LOWERTIM PNTNODTY PVSGCHTP (F) SPTV
CTLALGID LOWRDSTN PNTSTATE PVSOURCE (F) SPTVP
CTLEQN LOWRRATE PNTTYPE PVSRCOPT (F) STDBYMAN
CTRLINIT MANMODFL PRGATRFL PVSTS STSMSG
CYCLETIM MANOPCMD PRIMMOD (F) PVTRACK T1
DEADBAND MANOPTIM PSDLYFL RAISDSTN T2
DEADTIME MAXPULSE PTDESC RAISETIM TVPROC
RAISRATE UNIT
USERID

HPM Parameter Reference Dictionary 3-10 8/97


3.14

3.14 Position Proportional (PosProp)

The parameters of the Position Proportional control algorithm are listed below in
alphabetical order. (F) indicates that the parameter is applicable when the PNTFORM =
Full.
$AUXUNIT (F) DEVHIPR (F) NMODATTR PVAUTO RCASOPT
ADVDEVFL DEVHITP (F) NMODE PVAUTOST RCASSHED
ADVDEVPR (F) DEVLOFL NOCINPTS PVEUHI REDTAG (F)
ADVDEVTP (F) DEVLOPR (F) NOCOPTS PVEULO RINITREQ
ADVSP (F) DEVLOTP (F) NODENUM PVFORMAT RINITVAL
ADVSPP (F) ESWAUTO NODETYP PVHHFL RP
ALENBST (F) ESWCAS NORMCYCL PVHHPR (F) RT
ARWNET ESWENBST NRMATRFL PVHHTP (F) SAFOPCMD
ARWOP ESWMAN NRMMODFL PVHIFL SCHSTS
ASPPROC (F) EUDESC NTWKNUM PVHIPR (F) SHEDMODE
ASSOCDSP EXTSWOPT OPCMD PVHITP (F) SHEDTIME
AUTMODFL HIGHAL (F) OPHIFL PVLLFL SHUTDOWN
BADCTLFL HIGHALPR (F) OPHISRC PVLLPR (F) SLOTNUM
BADCTLOP INITMAN OPLOFL PVLLTP (F) SP
BADCTLPR (F) KEYWORD OPLOSRC PVLOFL SPEUHI
BADPVFL (F) LASTPV OVERVAL (F) PVLOPR (F) SPEULO
BADPVR (F) LMSRC PERIOD PVLOTP (F) SPFORMAT
BCAMODFL LOCALMAN PFDLYFL PVP SPHIFL
CASMODFL LOWERTIM PNTFORM PVROCNFL SPHILM
CASREQ LOWRDSTN PNTMODTY PVROCNPR (F) SPLOFL
CIDSTN LOWRRATE PNTNODTY PVROCNTP (F) SPLOLM
CISRC LTIMHILM PNTSTATE PVROCPFL SPOPT
CNFMU MANMODFL PNTTYPE PVROCPPR (F) SPP
CNFPU MANOPCMD PRGATRFL PVROCPTP (F) $SPTOL
CODSTN MANOPTIM PSDLYFL PVSGCHTP (F) SPTV
CONTCUT (F) MAXPULSE PRIMMOD (F) PVSOURCE (F) SPTVP
CTLALGID MINPULSE PTDESC PVSRCOPT (F) STDBYMAN
CTRLINIT MODATTR PTEXECST PVSTS STSMSG
CYCLETIM MODE PTINAL RAISDSTN TVPROC
DEADBAND MODEAPPL PTORST RAISETIM UNIT
DEADTIME MODEPERM PV RAISRATE USERID
DEV MODNUM PVALDB (F) RAMPTIME
DEVHIFL NAME PVALDBEU (F) RARWSTS

HPM Parameter Reference Dictionary 3-11 8/97


3.15

3.15 Ramp Soak (RampSoak)

The parameters of the Ramp Soak control algorithm are listed below in alphabetical order.
(F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) DEVHITP (F) NORMCYCL PVFORMAT SLOTNUM
ADVDEVFL DEVLOFL NRMATRFL PVP SOAKT1
ADVDEVPR (F) DEVLOPR (F) NRMMODFL PVSTS SOAKT2
ADVDEVTP (F) DEVLOTP (F) NTWKNUM RAMPTIME SOAKT3
ADVSP (F) ESWAUTO NXTSOAKV RARWSTS SOAKT4
ADVSPP (F) ESWCAS OP RATE1 SOAKT5
ALENBST (F) ESWENBST OPEU RATE2 SOAKT6
ARWNET ESWMAN OPHIFL RATE3 SOAKT7
ARWOP EUDESC OPHILM RATE4 SOAKT8
ASPPROC (F) EXTSWOPT OPLOFL RATE5 SOAKT9
ASSOCDSP HIGHAL (F) OPLOLM RATE6 SOAKT10
AUTMODFL HIGHALPR (F) OPMCHLM RATE7 SOAKT11
BADCTLFL HOLDCMD OPRATRFL RATE8 SOAKT12
BADCTLPR (F) INITMAN OPROCLM RATE9 SOAKV1
BCAMODFL KEYWORD $OPTOL RATE10 SOAKV2
CASMODFL LASTPV OVERVAL (F) RATE11 SOAKV3
CASREQ LOCALMAN PERIOD RATE12 SOAKV4
CIDSTN MANMODFL PFDLYFL REDTAG (F) SOAKV5
CISRC MODATTR PNTFORM REMSOAKT SOAKV6
CNFMU MODE PNTMODTY RINITREQ SOAKV7
CNFPU MODEAPPL PNTNODTY RINITVAL SOAKV8
CODSTN MODEPERM PNTSTATE S1 SOAKV9
CONTCUT (F) MODNUM PNTTYPE S1BGNTIM SOAKV10
CTLALGID MXRMPDEV` PRGATRFL S1ENDTIM SOAKV11
CTRLINIT MXSOKDEV PRIMMOD S1SEGID SOAKV12
CURSEGID NAME PSDLYFL S2 SP
CV NMODATTR PTDESC S2BGNTIM SPP
CVEUHI NMODE PTEXECST S2ENDTIM STDBYMAN
CVEULO NOCINPTS PTINAL S2SEGID STSMSG
CYCLEOPT NOCOPTS PTORST SAFEOP TVPROC
DEV NODENUM PV SCHSTS UNIT
DEVHIPR (F) NODETYP PVEUHI SEGTYPE
DEVHIFL NORSSEQ PVEULO SHUTDOWN

HPM Parameter Reference Dictionary 3-12 8/97


3.16

3.16 Ratio Control (RatioCtl)

The parameters of the Ratio-Control control algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) DEVHIFL NORMCYCL PTORST RARWSTS
ADVDEVFL DEVHIPR NRMATRFL PRGATRFL RATE1
ADVDEVPR (F) DEVHITP (F) NRMMODFL PV RCASOPT
ADVDEVTP (F) DEVLOFL NTWKNUM PVALDB (F) RCASSHED
ADVSP (F) DEVLOPR (F) OP PVALDBEU (F) REDTAG (F)
ADVSPP (F) DEVLOTP (F) OPALDB (F) PVAUTO RINITREQ
ALENBST (F) ESWAUTO OPEU PVAUTOST RINITVAL
ARWNET ESWCAS OPHAFL (F) PVEUHI SAFEOP
ARWOP ESWENBST OPHIFL PVEULO SCHSTS
ASPPROC (F) ESWMAN OPHILM PVFORMAT SHEDMODE
ASSOCDSP EUDESC OPHIPR (F) PVHHFL SHEDTIME
AUTMODFL EXTSWOPT OPHITP (F) PVHHPR (F) SHUTDOWN
B1 HIGHAL (F) OPLAFL (F) PVHHTP (F) SLOTNUM
B2 HIGHALPR (F) OPLOFL PVHIFL SP
BADCTLFL INITMAN OPLOLM PVHIPR (F) SPEUHI
BADCTLPR (F) K1 OPLOPR (F) PVHITP (F) SPEULO
BADPVFL (F) K2 OPLOTP (F) PVLLFL SPFORMAT
BADPVPR (F) KEYWORD OPMCHLM PVLLPR (F) SPHIFL
BCAMODFL LASTPV OPRATRFL PVLLTP (F) SPHILM
CASMODFL LOCALMAN OPROCLM PVLOFL SPLOFL
CASREQ MANMODFL $OPTOL PVLOPR (F) SPLOLM
CIDSTN MODATTR OVERVAL (F) PVLOTP (F) SPOPT
CISRC MODE PERIOD PVP SPP
CNFMU MODEAPPL PFDLYFL PVROCNFL $SPTOL
CNFPU MODEPERM PNTFORM PVROCNPR (F) SPTV
CODSTN MODNUM PNTMODTY PVROCNTP (F) SPTVP
CONTCUT (F) NAME PNTNODTY PVROCPFL STDBYMAN
CTLALGID NMODATTR PNTSTATE PVROCPPR (F) STSMSG
CTRLINIT NMODE PNTTYPE PVROCPTP (F) TVPROC
CV NOCINPTS PRIMMOD (F) PVSGCHTP (F) UNIT
CVEUHI NOCOPTS PSDLYFL PVSOURCE (F) USERID
CVEULO NODENUM PTDESC PVSRCOPT (F) X2
DEV NODETYP PTEXECST PVSTS X2FILT
PTINAL RAMPTIME X2TF

HPM Parameter Reference Dictionary 3-13 8/97


3.17

3.17 Summer (RegCtl)

The parameters of the Reguatory Control Summer algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) CTRLINIT MODEAPPL OPLOFL PTEXECST
ALENBST (F) CV MODEPERM OPLOLM PTINAL
ARWNET CVEUHI MODNUM OPLOPR (F) PTORST
ARWOP CVEULO NAME OPLOTP (F) RARWSTS
ASSOCDSP ESWAUTO NMODATTR OPMCHLM RATE1
AUTMODFL ESWCAS NMODE OPRATRFL RCASOPT
B ESWENBST NOCINPTS OPROCLM REDTAG (F)
BADCTLFL ESWMAN NODENUM $OPTOL RINITREQ
BADCTLOP EUDESC NODETYP OVERVAL (F) RINITVAL
BADCTLPR (F) EXTSWOPT NORMCYCL PERIOD SAFEOP
BCAMODFL HIGHAL (F) NRMATRFL PFDLYFL SCHSTS
CASMODFL HIGHALPR (F) NRMMODFL PNTFORM SHEDMODE
CASREQ INITMAN NTWKNUM PNTMODTY SHEDTIME
CIDSTN K OP PNTNODTY SHUTDOWN
CISRC K1, K2, K3, K4 OPALDB (F) PNTSTATE SLOTNUM
CNFMU KEYWORD OPEU PNTTYPE STDBYMAN
CNFPU LOCALMAN OPHAFL (F) PRGATRFL STSMSG
CODSTN M OPHIFL PSDLYFL UNIT
CONTCUT (F) MANMODFL OPHILM PRIMMOD (F) USERID
CTLALGID MODATTR OPHIPR (F) PTDESC X1, X2, X3, X4
CTLEQN MODE OPHITP (F) XEUHI
OPLAFL (F) XEULO

3.18 Summer (RegPV)

The parameters of the Summer Reguatory PV algorithm are listed below in alphabetical
order. (F) indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) N PERIOD PVCLAMP PVLOPR (F)
ALENBST (F) MODNUM PFDLYFL PVEQN PVLOTP (F)
ASSOCDSP NAME PISRC PVEULO PVP
BADPVFL (F) NODENUM PIDSTN PVEUHI PVROCNFL
BADPVPR (F) NODETYP PNTFORM PVEXEUHI PVROCNPR (F)
C NOPINPTS PNTMODTY PVEXEULO PVROCNTP (F)
C1 NORMCYCL PNTNODTY PVEXHIFL PVROCPFL
C2 NTWKNUM PNTSTATE PVEXLOFL PVROCPPR (F)
C3 OVERVAL (F) PNTTYPE PVFORMAT PVROCPTP (F)
C4 P1 PRIMMOD (F) PVHHFL PVSGCHTP (F)
C5 P1STS PSDLYFL PVHHPR (F) PVSOURCE (F)
C6 P2 PTDESC PVHHTP (F) PVSRCOPT (F)
CNFMU P2STS PTEXECST PVHIFL PVSTS
CNFPU P3 PTINAL PVHIPR (F) PVTV (F)
CONTCUT P3STS PV PVHITP (F) PVTVP (F)
D P4 PVALDB (F) PVINIT SCHSTS
EUDESC P4STS PVALDBEU (F) PVLLFL SLOTNUM
HIGHAL (F) P5 PVALGID PVLLPR (F) STSMSG
HIGHALPR (F) P5STS PVAUTO PVLLTP (F) TF
KEYWORD P6 PVAUTOST PVLOFL UNIT
LASTPV P6STS PVCALC USERID

HPM Parameter Reference Dictionary 3-14 8/97


3.19

3.19 Switch

The parameters of the Switch control algorithm are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) CVEUHI NMODE OPROCLM S1
ALENBST (F) CVEULO NRMATRFL $OPTOL S2
ARWNET ESWAUTO NRMMODFL OVERVAL (F) S3
ARWOP ESWCAS NOCINPTS PERIOD S4
ASSOCDSP ESWENBST NOCOPTS PFDLYFL SAFEOP
AUTMODFL ESWMAN NODENUM PNTFORM SCHSTS
BADCTFL EUDESC NODETYP PNTMODTY SELXINP
BADCTLOP EXTSWOPT NTWKNUM PNTNODTY SHEDMODE
BADCTLPR (F) HIGHAL (F) OP PNTSTATE SHEDTIME
BCAMODFL HIGHALPR (F) OPALDB (F) PNTTYPE SHUTDOWN
CASMODFL INITMAN OPEU PRGATRFL SLOTNUM
CASREQ KEYWORD OPHAFL (F) PRIMMOD (F) STDBYMAN
CIDSTN LOCALMAN OPHIFL PSDLYFL STSMSG
CISRC M OPHILM PTDESC TRACKING
CNFMU MANMODFL OPHIPR (F) PTEXECST UNIT
CNFPU MODATTR OPHITP (F) PTINAL USERID
CODSTN MODE OPLAFL (F) PTORST X1
CONTCUT (F) MODEAPPL OPLOFL RARWSTS X2
CTLALGID MODEPERM OPLOLM RCASOPT X3
CTLEQN MODNUM OPLOPR (F) RCASSHED X4
CTRLINIT NAME OPLOTP (F) REDTAG (F) XEUHI
CV NMODATTR OPMCHLM RINITREQ XEULO
OPRATRFL RINITVAL

HPM Parameter Reference Dictionary 3-15 8/97


3.20

3.20 Totalizer (Totalizr)

The parameters of the Totalizer PV algorithm are listed below in alphabetical order. (F)
indicates that the parameter is applicable when the PNTFORM = Full.
$AUXUNIT (F) HIGHALPR (F) PNTMODTY PVEXEULO PVROCPFL
ACCTYPE KEYWORD PNTNODTY PVEXHIFL PVROCPPR (F)
ALENBST (F) LASTPV PNTSTATE PVEXLOFL PVROCPTP (F)
ASSOCDSP MODNUM PNTTYPE PVFORMAT PVSGCHTP (F)
AVDEV1FL NAME PRIMMOD (F) PVHHFL PVSOURCE (F)
AVDEV1TP NODENUM PSDLYFL PVHHPR (F) PVSRCOPT (F)
AVDEV2FL NODETYP PTDESC PVHHTP (F) PVSTS
AVDEV2TP NOPINPTS PTEXECST PVHIFL PVTV (F)
AVTV NORMCYCL PTINAL PVHIPR (F) PVTVP (F)
AVTVFL NTWKNUM PV PVHITP (F) RESETFL
BADPVFL (F) OLDAV PVALDB (F) PVINIT RESETVAL
BADPVPR (F) OVERVAL (F) PVALDBEU (F) PVLLFL SCHSTS
C P1 PVALGID PVLLPR (F) SLOTNUM
COMMAND P1STS PVAUTO PVLLTP (F) STARTFL
CONTCUT (F) P2 PVAUTOST PVLOFL STATE
CNFMU P2STS PVCALC PVLOPR (F) STOPFL
CNFPU PERIOD PVCLAMP PVLOTP (F) STSMSG
CUTOFFLM PFDLYFL PVEQN PVP TF
EUDESC PIDSTN PVEUHI PVROCNFL TIMEBASE
HIGHAL (F) PISRC PVEULO PVROCNPR (F) UNIT
PNTFORM PVEXEUHI PVROCNTP (F) USERID

3.21 Variable Dead Time with Lead/Lag (VdtLdLag)

The parameters of the Variable Dead Time with Lead/Lag PV algorithm are listed below in
alphabetical order. (F) indicates that the parameter is applicable when the PNTFORM =
Full.
$AUXUNIT (F) MODNUM PNTSTATE PVEXHIFL PVROCNTP (F)
ALENBST (F) NAME PNTTYPE PVEXLOFL PVROCPFL
ASSOCDSP NLOC PRIMMOD (F) PVFORMAT PVROCPPR (F)
BADPVFL (F) NODENUM PSDLYFL PVHHFL PVROCPTP (F)
BADPVPR (F) NODETYP PTDESC PVHHPR (F) PVSGCHTP (F)
C NOPINPTS PTEXECST PVHHTP (F) PVSOURCE (F)
C1 NORMCYCL PTINAL PVHIFL PVSRCOPT (F)
C2 NTWKNUM PV PVHIPR (F) PVSTS
CNFMU OVERVAL (F) PVALDB (F) PVHITP (F) PVTV (F)
CNFPU P1 PVALDBEU (F) PVINIT PVTVP (F)
CONTCUT (F) P1STS PVALGID PVLLFL SCHSTS
CUTOFFLM P2 PVAUTO PVLLPR (F) SLOTNUM
D P2STS PVAUTOST PVLLTP (F) STSMSG
D1 PERIOD PVCALC PVLOFL TD
D2 PFDLYFL PVCLAMP PVLOPR (F) TF
EUDESC PIDSTN PVEQN PVLOTP (F) TLD
HIGHAL (F) PISRC PVEUHI PVP TLG1
HIGHALPR (F) PNTFORM PVEULO PVROCNFL TLG2
KEYWORD PNTMODTY PVEXEUHI PVROCNPR (F) UNIT
LASTPV PNTNODTY PVEXEULO USERID

HPM Parameter Reference Dictionary 3-16 8/97


$ADD

-$-

$ADD (Array)
Type: Logical Add Point Last Parameter Indicator—The last parameter sent to the HPM during
Lock: PtBld point build of an array point.
Default: On
PtRes: HPM
Range: Off
On

Helpful Hint: Do not remove $ADD from an exception build file or the point will not load
properly.

$AUXUNIT
Type: E:UNIT Auxiliary Unit—The Auxiliary Unit of an alarmable process point. If an
Lock: Oper Auxiliary Unit ID is specified, alarms from this point go to the Auxiliary Unit
Default: Null instead of the Primary Unit. If the $AUXUNIT parameter is set to null (- -),
PtRes: NIM alarms go to the Primary Unit. Available in Release 520 and later software.

Range: A-Z, 0-9 and Null - (Any valid unit ID as configured in the NCF)

Helpful Hint: A Network configuration option sets the keylevel required to change $AUXUNIT.

$COMCFLM (HPM Box)


Type: Real Comm Processor CPU Free Low Limit in per cent —
Lock: Engineer
Default: 10
PtRes: HPM

Helpful Hint: This parameter cannot be reset.

Range: 0 - 100

HPM Parameter Reference Dictionary $-1 8/97


$COMCUOS

$COMCUOS (HPM Box)


Type: Real
Lock: View
Default: 0.0
PtRes: HPM
Comm Processor CPU Utilization (System)— Specifies the CPU Utilization (in per cent) for the Comm
Processor operating system, device drivers, and interrupt handlers.

Helpful Hint: This parameter cannot be reset.

Range: 0 - 100

$COMCUTS(0 - 99) (HPM Box)


Type: Real Comm Processor CPU Utilization (Task)— CPU Utilization (in per cent) for
Lock: View each Comm Processor Task.
Default: 0.0
PtRes: HPM

Helpful Hint: This parameter cannot be reset.

Range: 0 - 100

$CTLCFLM (HPM Box)


Type: Real Control Processor CPU Free Low Limit—
Lock: Engineer
Default: 10
PtRes: HPM

Helpful Hint: This parameter cannot be reset.

Range:

$CTLCUOS (HPM Box)


Type: Real Control Processor CPU Utilization (system) — specifies the CPU Utilization
Lock: View (in per cent) for the Control Processor operating system, device drivers, and
Default: 0.0 interrupt handlers
PtRes: HPM

Helpful Hint: This parameter cannot be reset.

Range: 0 - 100

HPM Parameter Reference Dictionary $-2 8/97


$CTLCUTS

$CTLCUTS(0 - 99) (HPM Box)


Type: Real Control Processor CPU Utilization (Task) — specifies the CPU Utilization (in
Lock: View per cent) for each Control Processor Task
Default: 0.0
PtRes: HPM

Helpful Hint: This parameter cannot be reset.

Range: 0 - 100

$DBVALID (HPM Box)


Type: E:$ACCSRC HPM Database Valid
Lock: Eng
Default: DB Invalid
PtRes: HPM
Range: 0-DB_Valid (An IOP database is valid and the IOP can be started)
1-DBInvalid (An IOP database is not valid and the IOP will not start)

$IOMPADD(1)–(168)
Type: Integer IOP Address—Returns the physical address of the IOP with (soft address)
Lock: View (File-1)*16 + card + 127
Default:
PtRes: HPM
Range: 0, 129 - 255

$OPTOL (RegCtl, AO)


Type: Real (in Output Tolerance Parameter Definition—Tolerance limit for a manually entered
Percent) OP. The difference between a new OP and a current OP is compared against
Lock: Engineer $OPTOL. If the tolerance is violated in either a positive or negative direction
Default: 0.0 from the current value of the OP, operator confirmation is required before the
PtRes: HPM value is stored. A value of 0.0 disables this check. An NaN or a negative value
is not allowed.
Range: 0.0 to 106.9

$SPTOL (RegCtl)
Type: Real (in Setpoint Tolerance Parameter Definition—Tolerance limit for a manually entered
Engineering SP. The difference between a new SP and a current SP is compared against
Units) $SPTOL. If the tolerance is violated in either a positive or negative direction
Lock: Engineer from the current value of the SP, operator confirmation is required before the
Default: 0.0 value is stored. A value of 0.0 disables this check. An NaN or a negative value
PtRes: HPM is not allowed.
Range: >= 0.0

HPM Parameter Reference Dictionary $-3 8/97


$UCNLSB

$UCNLSB(1)–(50)
Type: Real Local UCN Communications Statistics
Lock: View
Default:
PtRes: HPM
Range:

$UCNLSB(45) (NIM)
Type: Real Local Statistics Block—The number of auto reconnects.
Lock: View
Default: 0
PtRes: HPM, NIM
Range: ≤0

HPM Parameter Reference Dictionary $-4 8/97


AB_DATA1

-A-

AB_DATA1 (SI - Array)


Type: Real Auxiliary A-B Data 1—Specifies the Allen-Bradley PLC family type: 2.0, 3.0,
Lock: Eng or 5.0. Refer to the APM/HPM Serial Interface Options manual when
Default: NaN configuring for diagnostics.
PtRes: HPM
Range: N/A

Helpful Hint: Use of this parameter is only required to configure Serial Interface mapping
to/from an Allen-Bradley programmable logic controller device. This parameter
should be set to NAN if it is not being used.

AB_DATA2 (SI - Array)


Type: Real Auxiliary A-B Data 2—Specifies the Allen-Bradley PLC File Number (in
Lock: Eng decimal) from which data is read into the Array point for PLC-3 or PLC-5
Default: NaN controllers. Must be NaN for PLC-2.
PtRes: HPM
Range: 0 - 999, NaN

Helpful Hint: Use of this parameter is only required to configure Serial Interface mapping
to/from an Allen-Bradley programmable logic controller device. This parameter
should be set to NAN if it is not being used.

AB_DATA3 (SI - Array)


Type: Real Auxiliary A-B Data 3—Specifies the data type for Allen-Bradley PLC-2 or PLC-5
Lock: Eng controllers or section ID for PLC-3 controllers. Refer to the APM/HPM Serial
Default: NaN Interface Options manual for additional information.
PtRes: HPM
Range: 0 - 13

Helpful Hint: Use of this parameter is only required to configure Serial Interface mapping
to/from an Allen-Bradley programmable logic controller device. This parameter
should be set to NAN if it is not being used.

AB_DATA4 (SI - Array)


Type: Real Auxiliary A-B Data 4—Specifies the Allen-Bradley PLC scan frequency: 0
Lock: Eng indicates that the point is to be scanned as fast as possible. 1–255 indicates the
Default: NaN number of seconds for the polling period; 256 = scan once. Note that the report
PtRes: HPM by exception feature can work with any scan rate selection. Refer to the
APM/HPM Serial Interface Options manual for more information.
Range: 0 - 256

Helpful Hint: Use of this parameter is only required to configure Serial Interface mapping
to/from an Allen-Bradley programmable logic controller device. This parameter
should be set to NAN if it is not being used.

HPM Parameter Reference Dictionary A-1 8/97


ABHEMSD

ABHEMSD (ProcMod)
Type: Logical Abnormal Handler Emergency Shutdown Enable Flag—Indicates if the
Lock: View Emergency Shutdown abnormal handler sequence is currently enabled.
Default: Off
PtRes: HPM
Range: On (Emergency Shutdown abnormal handler is enabled)
Off (Emergency Shutdown abnormal handler not enabled)

ABHHOLD (ProcMod)
Type: Logical Abnormal Handler Hold Enable Flag—Indicates if the Hold abnormal handler
Lock: View sequence is currently enabled.
Default: Off
PtRes: HPM
Range: On (Hold abnormal handler is enabled)
Off (Hold abnormal handler not enabled)

ABHRSTR (ProcMod)
Type: Logical Abnormal Handler Restart Enable Flag—Indicates if the Restart abnormal handler
Lock: View sequence is currently enabled.
Default: Off
PtRes: HPM
Range: On (Restart abnormal handler is enabled)
Off (Restart abnormal handler not enabled)

ABHSHDN (ProcMod)
Type: Logical Abnormal Handler Shutdown Enable Flag—Indicates if the Shutdown abnormal
Lock: View handler sequence is currently enabled.
Default: Off
PtRes: HPM
Range: On (Shutdown abnormal handler is enabled)
Off (Shutdown abnormal handler not enabled)

ACCELTIM (DevCtl)
Type: Time Acceleration Time—The amount of time the SECVAR parameter exceeded the
(Duration) SVHITP parameter while not in State0. This parameter resets to zero each time
Lock: View the state transitions to State0.
Default: 0
PtRes: HPM
Range: 0 to 4000 days (With a resolution of 1 second)

HPM Parameter Reference Dictionary A-2 8/97


ACCTYPE

ACCTYPE (Totalizer)
Type: E:$ACCTYPE Accumulator Operation Mode—Specifies the type of input.
Lock: Eng/PB
Default: Analog
PtRes: HPM

Range: 0-Pulse Pulse input


1-Analog Analog input

ACP (ProcMod)
Type: Ent_Id Advanced Control Point ID—Defines the name of the point in the CG or CM to
Lock: PtBld which this process module is assigned. The NIM notifies the advanced control
Default: Null point when the process module sends a special sequence message.
PtRes: NIM
Range: Tag name can be up to 16 characters, and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character
or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.

ACTPRIM(1)–(40) (HPM Box)


Type: E:$ACTPRIM Acting Primary I/O module—Specifies the acting primary I/O module.
Lock: View nn = 1–40 corresponds to the 40 logical I/O modules.
Default: Applies to primary IOP only.
PtRes: HPM
Range: 0-IOM_A (The A module is the acting primary)
1-IOM_B (The B module is the acting primary)

ADVDEVFL
Type: Logical Advisory Deviation Alarm Flag—Indicates whether an advisory alarm has been
Lock: View detected.
Default: Off
PtRes: HPM
Range: Off (Alarm has not been detected)
On (Alarm has been detected. PV - ADVSP is greater than ADVDEVTP)

Helpful Hint: ADVDEVFL is never On unless SPOPT = Asp.

HPM Parameter Reference Dictionary A-3 8/97


ADVDEVPR

ADVDEVPR
Type: E:ALPRIOR Advisory Deviation Alarm Priority—Determines the priority of the advisory
Lock: Engr deviation alarm.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: ADVDEVPR configuration requires SPOPT = Asp.

ADVDEVTP
Type: Real Advisory Deviation Alarm Trip Point—An alarm will be generated when the
Lock: Supr difference between PV and ADVSP exceeds the value in this parameter.
Default: NaN
PtRes: HPM
Range: > 0.0
NaN

Helpful Hint: 1. ADVDEVTP change requires SPOPT = Asp .


2. Alarm generation requires ASPPROC = Enable and
abs(PV - ADVSP) > ADVDEVTP.
When abs(PV - ADVSP) < ADVDEVTP * .9 alarm returns to normal.

ADVSP
Type: Real Advisory Setpoint in Engineering Units
Lock: Supr
Default: N/A
PtRes: HPM
Range: SPLOLM to SPHILM

Helpful Hint: ADVSP change requires (SPOPT = Asp) + (ASPPROC = Enable).


Alarm generation requires ASPPROC = Enable and
abs(PV - ADVSP) > ADVDEVTP.
When abs(PV - ADVSP) < ADVDEVTP * .9 alarm returns to normal.

ADVSPP
Type: Real Advisory Setpoint in Percent
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

Helpful Hint: ADVSPP cannot be viewed unless SPOPT = Asp.

HPM Parameter Reference Dictionary A-4 8/97


ALENBST

ALENBST
Type: E:ALENBST Alarm Enable Status—Defines the alarm reporting function that is to be used
Lock: Oper when an alarm condition is detected in this data point. Note that even when
Default: Enable alarms are disabled, the alarm indicators still appear on the Group and Detail
PtRes: NIM displays. With Release 510 and later software, the word DIS appears in half
height text above the tag name on the Point Detail or Group Display for a point
with ALENBEST set to Disable.

Range: Displayed Logged Reported to EIP


Enable Yes Yes Yes
Disable No Yes Yes
Inhibit No No No

Helpful Hint: ALENBST should not be set to Disable or Inhibit for points critical to safe
operations. For Box Flag points, this parameter applies to only slots 1
through 128.

Reference: See Engineer’s Reference Manual in the Alarm Management section,


for more information on what should happen under different possible alarm
actions.

NOTE

The access lock for the ALENBST parameter is configurable through System-Wide Values.

ALMOPT (DigIn)
Type: E:$ALMOPT Alarming Option—Defines the alarming option for a digital input point whose
Lock: Eng/PB DITYPE is Status.
Default: None
PtRes: HPM
Range: 0-None (No alarms are to be detected.)
1-Offnorml (Off Normal; alarm if current PV state is not the PVNORMAL state. PVNORMAL
is defined by the STATETXT(0) or STATETXT(1) descriptor, as configured by the user.)
2-ChngofSt (An alarm is generated when the digital input changes state in either direction. Note
that IOP firmware must support Change of State Reporting.)

Helpful Hint: ALMOPT configuration requires DITYPE = Status.

HPM Parameter Reference Dictionary A-5 8/97


ALPRIOR

ALPRIOR (ProcMod)
Type: E:ALPRIOR Alarm Priority—Defines the alarm priority for Process Module points. Note that
Lock: Engr even when the alarm priority is Journal, the alarm indicators still appear on the
Default: Low Group and Detail displays.
PtRes: NIM
Range: Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: Access to ALPRIOR is by schematic or CL. ALPRIOR is retained in R500 for
compatibility with earlier software. Use SEQPR for new points.

Reference: See Engineer’s Reference Manual in the Alarm Management section,


for more information on what should happen under different possible alarm
actions.

ALPRIOR (DigComp, DigIn, FL)


Type: E:ALPRIOR Composite Alarm Priority—When read, returns a value equal to the highest
Lock: Engr configured priority among all alarm parameters for the point. When written, sets
Default: Low all of the point’s alarm priority parameters equal to the value being stored. Note
PtRes: NIM that individual parameters such as BADPVPR, etc. can be stored individually.
If a point’s separate alarm priorities are all set to the same priority, ALPRIOR is
compatible with R400 and earlier software.
Range: Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: Access to ALPRIOR is by schematic or CL. No value is actually read from
ALPRIOR on a read and no value is actually stored to ALPRIOR on a write. Values are copied
to and from the separate alarm priorities.

Reference: See Engineer’s Reference Manual in the Alarm Management section,


for more information on what should happen under different possible alarm
actions.

ANAME(1)–(3) (ProcMod)
Type: String_8 Abnormal Sequence Name—Indicates the name of the abnormal handler currently
Lock: View being executed by the process module. A value of " " means that an abnormal
Default: Spaces handler is not executing. ANAME(1) returns the abnormal handler name, while
PtRes: HPM both ANAME(2) and ANAME(3) return the names of the two abnormal
subroutine levels being executed.
Range: N/A

HPM Parameter Reference Dictionary A-6 8/97


AOCALIB

AOCALIB(1)–(168)
Type: Logical AO Calibration In Progress Flag—Shows which AO modules are in the process
Lock: Eng/PB of calibration.
Default:
PtRes: HPM
Range: Off (No calibration in progress)
On (Calibration in progress)

ARWNET (RegCtl)
Type: E:WINDUP Windup Status of the Input—Indicates the windup status for the SP or another
Lock: View initializable input.
Default: Normal
PtRes: HPM
Range: 0-Normal (Free to move in either direction)
1-Hi (Free to move in the lower direction)
2-Lo (Free to move in the higher direction)
3-HiLo (Not free to move in any direction)

ARWOP (RegCtl)
Type: E:WINDUP Windup Status of the Output—Indicates the output (OP) windup status.
Lock: View
Default: Normal
PtRes: HPM
Range: 0-Normal (Free to move in either direction)
1-Hi (Free to move in the lower direction)
2-Lo (Free to move in the higher direction)
3-HiLo (Not free to move in any direction)

ASSOCDSP
Type: String_8 Associated Display—Specifies a user configured schematic that is associated
Lock: Engr with this point. Available on Release 510 and later software.
Default: Blank
PtRes: NIM
Range: N/A

Helpful Hint: The specified associated display can be called from a Point Detail Display, or
from any summary display or the Group display when the point is selected.

ASPPROC (RegCtl)
Type: E:ASPPROC Advisory SP Processor State
Lock: Supr
Default: Disable
PtRes: HPM
Range: 0-Disable (Disallow advisory deviation alarming)
1-Enable (Allow advisory deviation alarming)

Helpful Hint: ASPPROC change requires SPOPT = Asp.

HPM Parameter Reference Dictionary A-7 8/97


ASTEP

ASTEP(1)–(3) (ProcMod)
Type: String_8 Abnormal Step Name—ASTEP(1) indicates the step name of the abnormal
Lock: View handler that is executing in this process module. A value of “ “ means no
Default: Spaces abnormal handler is presently executing. Both ASTEP(2) and ASTEP(3) indicate
PtRes: HPM the step names of the first and second level subroutines called from the abnormal
handler.
Range: N/A

ASTMT(1)–(3) (ProcMod)
Type: Integer Abnormal Statement Number—ASTMT(1) indicates the statement number of the
Lock: View abnormal handler that is presently executing in the process module. Both
Default: Blank ASTMT(2) and ASTMT(3) give statement numbers for first and second level
PtRes: HPM subroutines executing from an abnormal handler. A value of 0 indicates no
sequence is being executed.
Range: 0 to 255

AUTMODFL (RegCtl)
Type: Logical Automatic Mode Flag—Indicates whether the current mode of the point is
Lock: View Automatic.
Default: N/A
PtRes: HPM
Range: Off (Current mode is not Automatic)
On (Current mode is Automatic)

AUXDATA1 (SI-Array — Generic Modbus)


Type: Real FTA Driver Auxiliary Data 1—Keep Alive Address for Modbus devices.
Lock: Eng Specifies the address of a coil that is written to every 10 seconds (Force Single
Default: NaN Coil On function). NaN (dashes) = Keep Alive function is inactive.
PtRes: HPM
Range: 1 - 9999, NaN

Helpful Hint: AUXDATA1 can be configured separately for each Array point. No two Array
points should write to the same coil address. This parameter should be set to
NAN if it is not being used.

AUXDATA2 (SI-Array — Generic Modbus)


Type: Real FTA Driver Auxiliary Data 2— Specifies the time interval that the FTA waits
Lock: Eng before a message retry to the Modbus is attempted. NaN (dashes) indicates a 1.5
Default: NaN second timeout.
PtRes: HPM
Range: .25 - 5 Sec., NaN

Helpful Hint: After three retries, a message timeout error is displayed on the Point Detail
display. AUXDATA2 can be configured separately for each Array point. This
parameter should be set to NAN if it is not being used.

HPM Parameter Reference Dictionary A-8 8/97


AUXDATA

AUXDATA3 (SI-Array — Generic Modbus)


Type: Real FTA Driver Auxiliary Data 3—Signaling mode.Modem support (in
Lock: Eng integer/decimal format). Integer = 232 or 485.
Default: NaN (232 = EIA-232, 485 = EIA-485 Multidrop).
PtRes: HPM Decimal (EIA-232 only) = .0 or .1 (.0 = no modem control, .1 = modem control).
NaN (dashes) = 232.0 (EIA-232 without modem control).

Range: 232.0, 232.1, or 485.0

Helpful Hint: All array points that are loaded to the same FTA must have the same
AUXDATA3 settings. This parameter should be set to NAN if it is not being
used.

AUXDATA4 (SI-Array — Generic Modbus)


Type: Real FTA Driver Auxiliary Data 4—Baud Rate.Parity (in integer/decimal format).
Lock: Eng Baud Rates = 1200, 2400, 4800, 9600, or 19200.
Default: NaN Parity: .0 = no parity, .1 = odd parity, .2 = even parity.
PtRes: HPM NaN (dashes) = 9600.1 = (9600 baud, odd parity).

Range: integer = 1200, 2400, 4800, 9600, or 19200


decimal = .0, .1, or .2

Helpful Hint: All array points that are loaded to the same FTA must have the same
AUXDATA4 settings. This parameter should be set to NAN if it is not being
used.

AV (DigIn)
Type: Integer Accumulated Value in Engineering Units—Indicates the current value
Lock: Oper accumulated in the accumulator.
Default: 0
PtRes: HPM
Range: 0..32767

AV (RegCtl)
Type: Integer Accumulated Value in Engineering Units—Indicates the current value
Lock: Configurable accumulated in the accumulator.
Default: 0
PtRes: APM
Range: 0..32767

AVDELTHS (PI)
Type: Integer The Last Half-second’s AV
Lock: View
Default: 0
PtRes: HPM
Range: >0

HPM Parameter Reference Dictionary A-9 8/97


AVDEV1FL

AVDEV1FL (Totalizr)
Type: Logical Accumulated Value; 1st Deviation Flag—Indicates whether PVCALC is greater
Lock: View than AVTV minus AVDEV1TP. (PVCALC > AVTV - AVDEV1TP). This is
Default: N/A the first "slowdown" or "near-target" flag.
PtRes: HPM
Range: Off (PVCALC is not > AVTV - AVDEV1TP)
On (PVCALC is > AVTV - AVDEV1TP)

AVDEV1TP (Totalizr)
Type: Real Accumulated Value; 1st Deviation Trip Point (deviation from AVTV)
Lock: Supr
Default: NaN
PtRes: HPM
Range: > 0.0,
NaN

AVDEV2FL (Totalizr)
Type: Logical Accumulated Value; 2nd Deviation Flag—Indicates whether PVCALC is greater
Lock: View than AVTV minus AVDEV2TP. (PVCALC > AVTV - AVDEV2TP). This is
Default: N/A the second "slowdown" or "near-target" flag.
PtRes: HPM
Range: Off (PVCALC is not > AVTV - AVDEV2TP)
On (PVCALC is > AVTV - AVDEV2TP)

AVDEV2TP (Totalizr)
Type: Real Accumulated Value; 2nd Deviation Trip Point (deviation from AVTV)
Lock: Supr
Default: NaN
PtRes: HPM
Range: > 0.0,
NaN

AVGPU (ProcMod)
Type: Real Average PUs—Specifies the average PUs used for point processing
Lock: View
Default: 0
PtRes: HPM
Range: N/A

AVGTF (NIM, HPM Box)


Type: Real Average Statistics Single Lag Filter Time Constant—Defines the filter time in
Lock: Engineer the single lag filter used to calculate average values of the performance statistics.
Default: 1.00 Minutes
PtRes: HPM
Range: 0.0 - 1440.0 (0 = no filter)

HPM Parameter Reference Dictionary A-10 8/97


AVSTS

AVSTS (PI)
Type: E:PVVALST Value Status of AV
Lock: View
Default: Bad
PtRes: HPM
Range: 0-Bad
2-Normal

AVTV (DigIn)
Type: Integer Accumulator Target Value—Specifies the target value of the accumulator.
Lock: Oper AVTV appears on a group or detail display as the SP value.
Default: 0
PtRes: HPM
Range: 0 to 32767

Helpful Hint: AVTV change requires DITYPE = Accum.

AVTV (Totalizr)
Type: Real Accumulator Target Value—Specifies the target value of the totalizer. AVTV
Lock: Oper appears on a group or detail display as the SP value.
Default: NaN
PtRes: HPM
Range: N/A,
NaN

AVTVFL
Type: Logical Accumulated Value Target Reached Flag—AVTVFL is the accumulated value's
Lock: View "target value reached" flag. It is turned On whenever PVCALC ≥ AVTV.
Default: N/A Parameter AVTV contains the target value last entered by the operator.
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary A-11 8/97


HPM Parameter Reference Dictionary A-12 8/97
B

-B-

B (AutoMan)
Type: Real Overall Bias—Defines the overall bias which consists of BO plus BI. Refer to
Lock: Oper the HPM Control Functions and Algorithms manual for a detailed description.
Default: 0.0
PtRes: HPM
Range: N/A

B (MulDiv, RegCtl Summer)


Type: Real Overall Bias—Defines the overall bias which consists of BO plus BI. Refer to
Lock: Oper the HPM Control Functions and Algorithms manual for a detailed description.
Default: 0.0
PtRes: HPM
Range: N/A

B0 (AutoMan, MulDiv, RegCtl Summer)


Type: Real Last Operator-Entered Output Bias
Lock: View
Default: 0.0
PtRes: HPM
Range: N/A

B1 (RatioCtl)
Type: Real Output Bias Constant—If the Calcultr PV algorithm is being used in
Lock: Supr conjunction with this algorithm, the value of B1 should be the same as C3.
Default: 0.0
PtRes: HPM
Range: N/A

B2 (RatioCtl)
Type: Real Bias for Input X2—If the Calcultr PV algorithm is being used in conjunction
Lock: Supr with this algorithm, the value of B2 should be the same as C4.
Default: 0.0
PtRes: HPM
Range: N/A

B1, B2, B3 (MulDiv)


Type: Real Bias for Inputs for X1, X2, and X3—
Lock: Supr
Default: 0.0
PtRes: HPM
Range:

HPM Parameter Reference Dictionary B-1 8/97


BADCTLFL
BADCTLFL
Type: Logical Bad-Control Alarm Flag—Indicates whether a bad control alarm has been
Lock: View detected.
Default: Off
PtRes: HPM
Range: Off (Bad-control alarm not present)
On (Bad-control alarm present)

BADCTLOP
Type: E:$BADCTLO Bad Control Option—Indicates if the mode sheds to manual when bad PV or CV
Lock: Engr occurs for regulatory control points. It also shows the value of the output.
Default: No_Shed
PtRes: HPM
Range: 0-No_Shed (The point holds its output and mode, resuming control after initialization upon
recovery)
1-ShedHold (The mode sheds to manual, the mode attribute goes to operator, while the output is
held and external mode switching is disabled)
2-ShedLow (The mode sheds to manual, the mode attribute goes to operator, while the output
goes to -6.9% and external mode switching is disabled)
3-ShedHigh (The mode sheds to manual, the mode attribute goes to operator, while the output
goes to 106.9% and external mode switching is disabled)
4-ShedSafe (The mode sheds to manual, the mode attribute goes to operator, while the output
goes to SafeOP and external mode switching is disabled. If SafeOP is NaN, the
output is held as if the Bad Control Option is ShedHold.

BADCTLPR
Type: E:ALPRIOR Bad Control Alarm Priority—Defines the priority of the bad control alarm.
Lock: Engr
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

BADIOLPF (ProcMod)
Type: Logical Bad IOL Prefetch—Set to ON, by the system if any IOL prefetch value is bad.
Lock: View
Default: Off
PtRes: HPM
Range: Off ( )
On (IOL prefetch value is bad)

HPM Parameter Reference Dictionary B-2 8/97


BADOCFL

BADOCFL (RegCtl)
Type: Logical Bad Output Connection Flag (BADOC) Alarm—ON indicates that the RegCtl
Lock: View point cannot drive at least one Analog Output point (out of 4 possible). The
Default: OFF alarm appears on the Alarm Summary display and in the Real Time Journal as a
PtRes: HPM BADOC alarm. If it is the highest level alarm on the point, it appears on the
Point Detail or Group displays as BOC.

Range: Off (Point is not in alarm)


On (Point is in alarm)

BADOC1FL
Type: Logical Bad Output Connection Flag 1—ON indicates that the RegCtl point cannot drive
Lock: View Output 1 to an AO point (if configured).
Default: OFF
PtRes: HPM
Range: Off
On

BADOC2FL
Type: Logical Bad Output Connection Flag 2—ON indicates that the RegCtl point cannot drive
Lock: View Output 2 to an AO point (if configured).
Default: OFF
PtRes: HPM
Range: Off
On

BADOC3FL
Type: Logical Bad Output Connection Flag 3—ON indicates that the RegCtl point cannot drive
Lock: View Output 3 to an AO point (if configured).
Default: OFF
PtRes: HPM
Range: Off
On

BADOC4FL
Type: Logical Bad Output Connection Flag 4—ON indicates that the RegCtl point cannot drive
Lock: View Output 4 to an AO point (if configured).
Default: OFF
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary B-3 8/97


BADOCPR

BADOCPR (RegCtl)
Type: E:ALPRIOR Bad Output Connection (BADOC) Alarm Priority—Indicates the priority of the
Lock: Engr Bad Output Connection (BADOC) alarm
Default: Low
PtRes: NIM
Range: NoAction
JnlPrint
Printer
Journal
Low
High
Emergncy

Helpful Hint: The value of this parameter can be changed on the Point Detail display with
Engineering keylevel access.

BADOCOPT (RegCtl)
Type: Logical Bad Output Connection Alarm Option (BADOC)—ON indicates that the Bad
Lock: Eng/Pb Output Connection (BADOC) alarm can be generated (or is permitted).
Default: OFF
PtRes: HPM
Range: Off (BADOC alarms are suppressed)
On (BADOC alarms are permitted)

Helpful Hint: The value of this parameter can be changed on the Point Detail display with
Engineering keylevel access.

BADPVFL
Type: Logical Bad PV Flag—Indicates that a bad PV value has been detected at this data point.
Lock: View For an analog input, a bad PV is defined as a PV whose value is NaN (Not a
Default: Off Number).
PtRes: HPM
Range: Off (PV is not bad)
On (PV is bad)

HPM Parameter Reference Dictionary B-4 8/97


BADPVFL

BADPVFL (DI)
Type: Logical Bad PV Flag—Indicates that a bad PV value has been detected at this data point.
Lock: View BADPVFL is shown on the detailed display only when PNTFORM = Full.
Default: On
PtRes: HPM For a Digital Input, the Bad PV Flag is on when:
• The PV source is not equal to Manual and DITYPE is set to Accumulator.
• The PV source has just been switched to Substituted but the PV has not
yet been updated.
• The PV source = Substitute or Auto and PTEXECST = Inactive or the
module is not in the RUN state.
• PVSOURCE = Auto and there is no FTA connected or there is a Soft Fail
that is preventing this chanel from working.

Range: Off (PV is not bad)


On (PV is bad)

BADPVFL (DevCtl, DigComp)


Type: Logical Bad PV Flag—For a Digital Composite or Device Control point, the Bad PV
Lock: View Flag is is set to ON when the PV is bad.
Default: Off
PtRes: HPM
Range: Off (PV is not bad)
On (PV is bad)

BADPVPR
Type: E:ALPRIOR Bad PV Alarm Priority—Defines the priority of the bad PV alarm.
Lock: Engr
Default: Low
PtRes: NIM
Range: Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

HPM Parameter Reference Dictionary B-5 8/97


BADPVTXT

BADPVTXT (DevCtl, DigComp, NIM)


Type: String_8 Bad PV State Descriptor—Defines the state descriptor that is displayed when the
Lock: PtBld digital composite or device control point state is indeterminate or bad. The bad
Default: BAD state can result when the PV input signals from the process are in an
PtRes: NIM inconsistent state (e.g., for a valve, the limit switches indicating open and closed
are on at the same time). This state descriptor is configured on a per point basis
and is valid only when the PVTXTOPT parameter is On.

Range: The permissible character set for the up to eight character descriptor is as follows:
Alphabetics A-Z (upper case only)
Numerics 0-9,
Underscore (_)

BADSVFL (DevCtl)
Type: Logical Bad SV Alarm Flag—Indicates a bad secondary value alarm.
Lock: View
Default: Off
PtRes: HPM
Range: Off (Good data being read)
On (SV parameter = BAD or NaN)

BADSVPR (DevCtl)
Type: E:ALPRIOR Bad SV Alarm Priority—Indicates the alarm priority for the secondary value.
Lock: Engr
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

BCAMODFL (RegCtl)
Type: Logical Backup Cascade Mode Flag—Indicates if the mode of the point is Backup
Lock: View Cascade.
Default: N/A
PtRes: HPM
Range: Off - (point is not in Backup Cascade mode)
On - (point is in Backup Cascade mode)

HPM Parameter Reference Dictionary B-6 8/97


BCOMOPT

BCOMPOPT (FlowComp)
Type: Bad Compensation Input Option—
Lock:
Default:
PtRes: HPM

Range: Set_PVCALC_Bad
Use_Last_Goood_Comp_Term
Use_LastGood_Comp_Input

BFF (PidFf)
Type: Real Feed Forward Input Bias—Defines the bias value for multiplicative action.
Lock: Supr
Default: 0.0
PtRes: HPM
Range: N/A

BHALMFL1–BHALMFL7
Type: String_2 Alarm Flags
Lock: View
Default:
PtRes: NIM
Range: Hexadecimal characters 00 - FF

BIAS (Pid)
Type: Real Bias—Defines the value which is added to the SP.
Lock: Oper
Default: 0.0
PtRes: HPM
Range: BSLOLM to BSHILM

BLK_INFO
Type: Blind Record Function Block Summary Information—Provides Function Block summary
Lock: View information needed by the NIM for checkpointing
Default: N/A
PtRes: IOP
Range:

BNDRESET (NIM, HPM Box)


Type: Logical Bounds (Minimum/Maximum) Statistics Reset Flag—A write of ON resets
Lock: Operator the following maximum/minimum statistics to their default values: HPM
Default: Off CPU free percentage events, UCN transaction, UCN parameter statistics and
PtRes: HPM UCN average statistics.
Range: Off/On

Helpful Hint: A read of BNDRESET always returns OFF.

HPM Parameter Reference Dictionary B-7 8/97


BNDRSTIM

BNDRSTIM (NIM, HPM Box)


Type: Time Time of Last Bounds (Minimum/Maximum) Statistics Reset.
Lock: View
Default: Time of HPM Startup
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

BOXCLR(0)–(2) (DevCtl, DigComp)


Type: E:BOXCOLOR Box Color for Digital Displays—Defines the color of the upper, middle, and
Lock: Eng/PB lower boxes that are used to display the current state of the point on the
Group and Detail Displays. The lower box and its default (Red) do not apply
if NOSTATES = 2 for this point.
Default: Green [Upper-box default (State 1)]
Yellow [Middle-box default (State 0)]
Red [Lower-box default (State 2)]
PtRes: NIM
Range: Red
Green
White
Black
Cyan
Yellow
Blue
Magenta

Helpful Hint: BOXCLR has an access lock of View if PNTFORM = Component.

BOXCLR(0)–(1) (DigIn, Flag)


Type: E:BOXCOLOR Box Color for Digital Displays—Defines the color of the upper and lower
Lock: Eng/PB boxes that are used to display the current state of the point on the Group and
Detail Displays. Boxes are applicable when DITYPE is Latched or Status.

Default: Green [Upper box default color (State 1)]


Yellow [Lower-box default color(State 0)]
PtRes: NIM
Range: Red
Green
White
Black
Cyan
Yellow
Blue
Magenta

HPM Parameter Reference Dictionary B-8 8/97


BSHILM

BSHILM
Type: Real Bias High Limit—Defines the upper limit of the bias.
Lock: Supr
Default: 50.0
PtRes: HPM
Range: > BSLOLM,
NaN

Helpful Hint: Entering NaN disables the BSHILM function with NaN being stored in the
database.

BSLOLM
Type: Real Bias Low Limit—Defines the lower limit of the bias.
Lock: Supr
Default: -50.0
PtRes: HPM
Range: < BSHILM,
NaN

Helpful Hint: Entering NaN disables the BSLOLM function with NaN being stored in the
database.

BYPASS (DevCtl, DigComp)


Type: Logical Interlock Bypass—Allows bypassing the permissive and override interlocks
Lock: Oper when ON. The Safety Override Interlock (SI0) is not affected. Only applies if
Default: Off Override Option (OROPT) is selected.
PtRes: HPM
Range: Off (Interlocks not bypassed)
On (Interlocks bypassed)

BYPASS (ORSel)
Type: Logical Override Input Bypass Enable—Allows the operator to select the bypass function
Lock: Oper for the X1-X4 inputs.
Default: Off
PtRes: HPM
Range: Off (Bypass of inputs is not allowed)
On (Bypass of inputs is allowed)

BYPASSX1–BYPASSX4 (ORSel)
Type: Logical Bypass X1–X4 Input—Refer to the HPM Control Functions and Algorithms
Lock: Oper manual for a detailed description. BYPASSXn being On does not bypass
X1–X4 unless BYPASS = On.
Default: BYPASSX1 = Off
BYPASSX2–X4 = On
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary B-9 8/97


HPM Parameter Reference Dictionary B-10 8/97
C

-C-

C (FlowComp, Summer, Totalizer, and VdtLdLg)


Type: Real Scale Factor—Value in C is used in the calculation of PVCALC. Refer to the
Lock: Supr HPM Control Functions and Algorithms manual for the equation.
Default: 1.0
PtRes: HPM
Range: Anything except NaN

C1–C2 (FlowComp)
Type: Real Correction Constants—Values in C1 and C2 are used in the calculation of
Lock: Supr PVCALC, and serve as factors in compensating for assumed design conditions.
Default: 1.0 Refer to the HPM Control Functions and Algorithms manual for a detailed
PtRes: HPM description.
Range: C1 > 0.1
C2 > 0.1

C1–C2 (PI)
Type: Real Scaling Constants—Values in C1 and C2 are used in the calculation of
Lock: Supr PVCALC. Refer to the HPM Control Functions and Algorithms manual for a
Default: 1.0 detailed description.
PtRes: HPM
Range: C1 > 0
C2 > 0

C1–C2 (VdtLdLg)
Type: Real Scaling Constant For Input P1–P2—Values in C1 and C2 are used in the
Lock: Supr calculation of TD (fixed time delay) and TDNEW (calculated new delay time).
Default: 1.0
PtRes: HPM
Range: > 0.0

C1–C4 (Calcultr)
Type: Real Intermediate Results of Calculations
Lock: Supr
Default: N/A
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary C-1 8/97


C1–C6

C1–C6 (Summer)
Type: Real Scaling Constants 1-6—Defines the scaling constants to be used with the
Lock: Supr respective inputs P1-P6.
Default: 1.0
PtRes: HPM
Range: N/A

C1–C4DESC (Logic)
Type: String_8 Custom Alarm Descriptors—Defines the state for each of the four custom
Lock: Engr alarms.
Default: Blank
PtRes: HPM
Range: 8 Character String

C1–C4FL (Logic)
Type: Logical Custom Alarm Flags—Defines the state for each of the four custom alarms.
Lock: Program These flags can be written to if C1–C4SRC=None.
Default: Off
PtRes: HPM
Range: Off (A custom alarm is not active)
On (A custom alarm is active)

C1–C4PR (Logic)
Type: E:ALPRIOR Custom Alarm Priorities—Defines the alarm priorities for each of the four
Lock: Engr custom alarms.
Default: NoAction
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

C1–C4SRC (Logic)
Type: E:$LGALSRC Custom Alarm Source—Indicates the alarm source for each of the four custom
Lock: PtBld alarms.
Default: None
PtRes: HPM
Range: NONE (No source configured for alarms)
L1..L12 (Alarm source is the configured input connection; they can be either On or Off)
SO1..SO24 (Alarm source is the status output (SOn) from another logic block)
FL1..FL12 (Alarm source is a local flag; they can be either On or Off)

HPM Parameter Reference Dictionary C-2 8/97


CABLESTS

CABLESTS (NIM)
Type: Integer Overall Cable Status for a UCN Node
Lock: View
Default: N/A
PtRes: NIM
Range: 0-(Both cables are OK)
1-(Cable A has failed)
2-(Cable B has failed)
3-(Both cables have failed)

CALCEXP (Calcultr)
Type: String_40 Calculator Expression—Allows the user to set up an equation that can be up to
Lock: Eng/PB 40 characters in length, which is to be solved by the Calcultr algorithm. Input
Default: blank values P1-P6 and intermediate results values C1-C4 can be used in the equation.
PtRes: HPM
Range: N/A

CALIBALL (1)–(168)
Type: Logical Full Calibration Enable Flag
Lock: Engr
Default: Off
PtRes: HPM
Range: Off (Card calibration is disabled)
On (Card calibration is enabled)

CALIBRJ (1)–(168)
Type: Logical Reference Junction Calibration Enable Flag
Lock: Eng/PB
Default: Off
PtRes: HPM
Range: Off (Disable Reference Junction calibration)
On (Enable Reference Junction calibration)

CASMODFL (RegCtl)
Type: Logical Cascade Mode Flag—Indicates whether the current mode of the point is Cascade.
Lock: View
Default: N/A
PtRes: HPM
Range: On - (point is in cascade mode)
Off - (point is not in cascade mode)

HPM Parameter Reference Dictionary C-3 8/97


CASREQ

CASREQ (AnalgOut, RegCtl)


Type: E:CASREQ Remote Cascade Request Flag—Defines whether the remote cascade mode has
Lock: Prog been requested for the data point. The remote cascade mode exists when MODE
Default: NotReq is changed to Cas and RCASOPT is Ddc or DdcRsp. When a request to change
PtRes: HPM MODE to Cas is received from a US or a program, MODE does not immediately
change to Cas. Instead, CASREQ is set to Request and a -C appears to the right
of the mode indicator on the Group and Detail displays. When continuous
control in an AM determines that CASREQ contains Request, it requests the
mode to go to Cas, and changes CASREQ to NotReq.

Should the point shed while it is in the remote cascade mode, MODE goes to the
state defined in SHEDMODE, and CASREQ goes back to Request.

Range: 0-NotReq (Remote cascade mode request not made)


1-Request (Remote cascade mode request made; operator or program has requested the
cascade mode)

Helpful Hint: CASREQ does not apply for an AnalgOut point if RCASOPT = None.
CASREQ does not apply for a RegCtl point unless RCASOPT = Spc, Ddc,
or DdcRsp.
If Spc has been entered for the RCASOPT parameter, the AM writes to the
setpoint.
Ddc is the only remote cascade option for an analog output point.

CHPINHWY (UCN)
Type: E:CHPINDAC Automatic Checkpoint Inhibit
Lock: Supr
Default: Enable
PtRes: NIM
Range: 0-Enable (Enable automatic checkpointing of data bases on this UCN)
1-Inhibit (Inhibit automatic checkpointing)

CHPINOPR (HPM Box)


Type: E:CHPINDAC Automatic Checkpoint Inhibit Operation—Defines whether automatic
Lock: Supr database saves are to be performed for the devices connected to this NIM.
Default: Enable
PtRes: NIM
Range: Enable (Automatic database saves are enabled)
Inhibit (Automatic database saves are inhibited)

HPM Parameter Reference Dictionary C-4 8/97


CIDSTN

CIDSTN(1)–CIDSTN(4) (RegCtl)
Type: Prm_ID Control Input Connection Destination—Defines the parameter name (PV, SP,
Lock: PtBld etc.) in the RegCtl point that is to receive the value fetched using the
Default: Based on "Tagname.Parameter" or the hardware reference address specified in parameter
CTLALGID, CISRC, Control Input Connection Source.
CTLEQN, N
PtRes: HPM
Range: N/A

Helpful Hint: 1. CIDSTN must contain a legitimate parameter of one to eight characters.
2. Default to PV, SP, or some other parameter depends on parameters
CTLALGID, CTLEQN, and M.

CISRC(1)–CISRC(4) (RegCtl)
Type: Ent.Prm Control Input Connection Source—Defines the "Tagname.Parameter" of the
Lock: PtBld parameter whose value is to be obtained and then stored in one of up to four
Default: null.null RegCtl algorithm inputs. Refer to the HPM Control Functions and Algorithms
PtRes: HPM manual for a detailed description.
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters, and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

CLBACK (ProcMod)
Type: Integer Number of Backward Branches -- Specifies how many backward brances may
Lock: Engr occur when executing GOTO WHEN ERROR, & REPEAT, before preemption
Default: 0 occurs. 0 = preempt every backward branch.
PtRes HPM
Range: (0 - 240)

HPM Parameter Reference Dictionary C-5 8/97


CLPZMXC

CLPZMXC (UCN)
Type: Logical Overall Cable Status for UCN Cable A
Lock: View
Default: N/A
PtRes NIM
Range: Off (Cable A status is OK)
On (Cable A status is not OK)

CLPZMXP (UCN)
Type: Logical Overall Cable Status for UCN Cable B
Lock: View
Default: N/A
PtRes NIM
Range: Off (Cable B status is OK)
On (Cable B status is not OK)

CMD (RegCtl)
Type: Logical Command Fail Alarm Flag—Indicates if the PV failed to move after the output
Lock: Configurable command within the allowed command fail time. Command Fail Alarm priority
Default: Off is determined by CMDDISPR.
PtRes: APM
Range: Off (PV moved after the output command)
On (PV did not move after the output command)

CMDDISFL (DevCtl, DigComp)


Type: Logical Command Disagree Alarm Flag—Indicates whether a field device did not go to
Lock: View the commanded state within the allowed feedback time.
Default: Off
PtRes: HPM
Range: Off (No command disagree alarm)
On (Command disagree alarm has been detected by this point)

Helpful Hint: A slow-responding field device can cause a premature alarm. If so, adjust the
time in parameter FBTIME.

HPM Parameter Reference Dictionary C-6 8/97


CMDDISPR

CMDDISPR (DevCtl, DigComp)


Type: E:ALPRIOR Command Disagree Alarm Priority—Defines the alarm priority of command
Lock: Engr disagree, command fail, and uncommanded change alarms.
Default: Low
PtRes: NIM
Range Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

CMDFALFL (DevCtl, DigComp)


Type: Logical Command Fail Alarm Flag—Indicates if the PV failed to move after the output
Lock: View command within the allowed command fail time. Command Fail Alarm priority
Default: Off is determined by CMDDISPR.
PtRes: HPM
Range: Off (PV moved after the output command)
On (PV did not move after the output command)

CMDFALTM (DevCtl, DigComp)


Type: Integer Command Fail Timeout—Sets the amount of time (in seconds) that the
Lock: Supr if point should wait before generating a “command fail” alarm, if the PV has
CMDFALTM not changed after changing the output. Command Fail Alarm priority is
is changed from determined by CMDDISPR.
a non-zero value
to a zero value,
else Eng/PB
Default: 0
PtRes: HPM
Range: 0 to 999 seconds (0 indicates command fail alarming is disabled)

CMDHWREV
Type: String_2 HPMM Communications Daughter Card Revision
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal characters 00 - FF

HPM Parameter Reference Dictionary C-7 8/97


CMFLTIME

CMFLTIME (HPM BOX)


Type: Time HPMM Communications Failure Time—
Lock: View
Default: N/A
PtRes: HPM

Helpful Hint: If a value of 0 is returned for the time from the UCN, a parameter status of
Parameter Invalid is returned on the LCN.

Range:

CMIDTXT (HPM BOX)


Type: String_16 HPMM Communications Identification Text String
Lock: View
Default: Blank
PtRes: HPM
Range: Hexadecimal characters 00 - FF

CMPLTIME
Type: Time Compile Time—Specifies the sequence compile time (CL object header)
Lock: View
Default: 0
PtRes: HPM
Range:

CNFERRFL
Type: Logical Configuration Error Flag—This flag is set if any configuration requirement is
Lock: View violated.
Default: Off
PtRes: HPM
Range: Off
On

CNFERRPR
Type: E: ALPRIOR Configuration Error Priority—
Lock: Eng/PB
Default: Low
PtRes: HPM
Range: Low

HPM Parameter Reference Dictionary C-8 8/97


CNFLUA

CNFLUA(n)
Type: Real Configured Link Units on Link A—
Lock: View n = 1 - 64 for per cycle totals
Default: 0.0 n = 257 - 320 for per cycle non-SI IOP loading
PtRes: HPM n = 513 - 576 for per cycle SI array slot loading
Range:

CNFLUB(n)
Type: Real Configured Link Units on Link B—
Lock: View n = 1 - 64 for per cycle totals
Default: 0.0 n = 257 - 320 for per cycle non-SI IOP loading
PtRes: HPM n = 513 - 576 for per cycle SI array slot loading
Range:

CNFMU
Type: Integer Configured Memory Units—Configured size of slot in Memory units.
Lock: View
Default: N/A
PtRes: HPM
Range:

CNFPU(1 - 64) (HPM Box)


Type: Real Configured Process Units Per Cycle—
Lock: View
Default: 0
PtRes: HPM
Range:

HPM Parameter Reference Dictionary C-9 8/97


CNFPU

CNFPU
Type: Real Configured Process Units Per Cycle—Process Units Configured as being
Lock: PtBld required to execute point processing.
Default: 2.0
PtRes: HPM
Range:

Helpful Hint: Can only be written for ProcMod points.

CNFPUP (1 -64)
Type: Real Configured PUs Percent—Specifies the Configured Process Units in percent
Lock: View
Default: 0
PtRes: HPM
Range:

CNTLLOCK
Type: E:ACCLVL Control Lock—Attempts to write values in the following parameters are
Lock: Engr subject to the access-lock value contained in CNTLLOCK. The check is
Default: OPERATOR bypassed for the exceptions.
PtRes: HPM
Parameter Exceptions
PROCMOD New value = START
SEQEXEC None
SEQMODE None
OVERPHAS SEQEXEC = FAIL or ERROR
OVERSTEP SEQEXEC = FAIL or ERROR
OVERSTAT SEQEXEC = FAIL or ERROR

Range: 0-OPERATOR - Operator and higher keylock positions allow store access.
1-SUPERVIS - Supervisor and higher keylock positions allow store access.
2-ENGINEER - Engineer and higher keylock positions allow store access.
3-PROGRAM - Only the program has store access.

HPM Parameter Reference Dictionary C-10 8/97


CODSTN

CODSTN(1)–CODSTN(4) (RegCtl)
Type: Universal Control Output Connection Destination—Defines up to four different
Ent.Prm "Tagname.Parameter" or hardware reference address destinations to which the
Lock: PtBld output value from RegCtl point is to be written. Refer to the HPM Control
Default: null.null Functions and Algorithms manual for a detailed description.
PtRes: HPM
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters, and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as AO (analog output)
mm is the IOP Card number (1-40)
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

COMCFAVG (HPM Box)


Type: Real Average HPM Communication CPU Free Percentage—The average percent of
Lock: View time the Communications Processor is not busy.
Default: NaN
PtRes: HPM
Range: 0 - 100

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

COMCFMAX (HPM Box)


Type: Real Maximum HPM Communication CPU Free Percentage—The maximum
Lock: View percent of time the Communications Processor is not busy.
Default: NaN
PtRes: HPM
Range: 0 - 100

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

COMCFMIN (HPM Box)


Type: Real Minimum HPM Communication CPU Free Percentage—The minimum
Lock: View percent of time the Communications Processor is not busy.
Default: NaN
PtRes: HPM
Range: 0 - 100

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary C-11 8/97


COMDAUGH

COMDAUGH
Type: Logical HPMM Communications Daughter Card Present Flag.
Lock: View
Default:
PtRes: HPM
Range: Off (No daughter card present)
On (Daughter card present)

COMDAY
Type: Integer Creation Day of HPMM Communications Personality.
Lock: View
Default: N/A
PtRes: HPM
Range: 1 - 31

COMFWREV
Type: String_2 HPMM Communications Firmware Revision.
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal characters 00 - FF

COMDGAVG (HPM Box)


Type: Real Average Diagnostic cycle time (in minutes) in the Comm CPU—
Lock: View
Default: 0.0
PtRes: HPM
Range:

COMDGMAX (HPM Box)


Type: Real Maximum Diagnostic cycle time (in minutes) in the Comm CPU—
Lock: View
Default: 0.0
PtRes: HPM
Range:

HPM Parameter Reference Dictionary C-12 8/97


COMHOUR

COMHOUR (HPM BOX)


Type: Integer HPMM Communications Personality Creation Date-Hour
Lock: View
Default: 0
PtRes: HPM
Range:

COMHWREV
Type: String_2 HPMM Communications Hardware Revision.
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal characters 00 - FF

COMLUAVG (1) - (2) (HPM Box)


Type: Real Average HPM IOL Utilization (inPercent) by the Comm CPU, per I/O Link—
Lock: View
Default: 0.0
PtRes: HPM
Range: 0 - 100

COMLUMAX (1) - (2) (HPM Box)


Type: Real Maximum HPM IOL Utilization (inPercent) by the Comm CPU, per I/O
Lock: View Link—
Default: 0.0
PtRes: HPM
Range: 0 - 100

COMMAND (DigIn)
Type: E:COMMAND Accumulator Commands—Allow the operator to control the accumulator.
Lock: Oper
Default: None
PtRes: HPM
Range: 0-None (No effect on accumulator)
1-Start (Start the accumulator)
2-Stop (Stop the accumulator)
3-Reset (Reset the accumulation to zero)

Helpful Hint: COMMAND applies only when DITYPE = Accum.

HPM Parameter Reference Dictionary C-13 8/97


COMMAND

COMMAND (STI)
Type: E:COMMAND Command—Allows the user to do database transfers between the STI point and
Lock: Oper the smart transmitter, and to calibrate the transmitter.
Default: None
PtRes: HPM

NOTE

During an up-load operation, previously unseen data is read from the transmitter database
and stored in the STI database. If this data is not desired, the data can be restored by using
the checkpoint restore or load IDF functions.

Range: 0-None (A command has not been issued by the STI point)
1-DnLoadDb (Loads the transmitter parameters from the STI point data base into the transmitter)
2-UpLoadDb (Loads the transmitter data base from the transmitter into the STI point)
3-Set_LRV (Sets the Lower Range Value)
4-Set_URV (Sets the Upper Range Value)
5-Cor_LRV (Corrects the Lower Range Value)
6-Cor_URV (Corrects the Upper Range Value)
7-Cor_Inpt (Corrects the zero point for the PV value)
8-RstCor (Sets all input calibration parameters to their default values)

Helpful Hint: If PV or PV_SV has been entered for the DECONF parameter, the only
command supported is DnLoadDB.

HPM Parameter Reference Dictionary C-14 8/97


COMMAND

COMMAND (Timer)
Type: E:COMMAND Timer Commands—Allow the operator to control the operation of the timer
Lock: Oper data point.
Default: None
PtRes: HPM
Range: 0-None (No effect on the timer)
1-Start (Starts the timer)
2-Stop (Stops the timer)
3-Reset (Resets the timer to zero)
4-RestStrt (Resets the timer, then starts the timer)

COMMAND (Totalizr)
Type: E:COMMAND Totalizer Commands—Allow the operator to control the operation of the
Lock: Oper totalizer.
Default: None
PtRes: HPM
Range: 0-None (No effect on totalizer)
1-Start (Starts the totalizer)
2-Stop (Stops the totalizer)
3-Reset (Resets the totalizer to RESETVAL)

COMMIN (HPM BOX)


Type: Integer HPMM Communications Personality Creation Date-Minute
Lock: View
Default: 0
PtRes: HPM
Range:

COMMONTH
Type: Integer Creation Month of HPMM Communications Personality
Lock: View
Default: N/A
PtRes: HPM
Range: 1 - 12

COMNAME
Type: String_8 HPMM Communications Personality Name
Lock: View
Default:
PtRes: HPM
Range:

HPM Parameter Reference Dictionary C-15 8/97


COMPHILM

COMPHILM (FlowComp)
Type: Real Compensation Term High Limit—Defines the upper limit of the COMPTERM
Lock: Supr (compensation term) parameter.
Default: 1.25
PtRes: HPM
Range: COMPLOLM to 10.0,
NaN

Helpful Hint: Entering NaN disables high-limit checking by forcing its value to the extreme
(10.0).

COMPLOLM (FlowComp)
Type: Real Compensation Term Low Limit—Defines the lower limit of the COMPTERM
Lock: Supr (compensation term) parameter.
Default: 0.8
PtRes: HPM
Range: 0.0 to COMPHILM,
NaN

Helpful Hint: Entering NaN disables low-limit checking by forcing its value to the extreme
(0.0).

COMPTERM (FlowComp)
Type: Real Compensation Term—This term differs in each of the five flow compensation
Lock: View equations, A through E. Refer to the HPM Control Functions and Algorithms
Default: 1.0 manual for a detailed description.
PtRes: HPM
Range: COMPLOLM to COMPHILM

COMRDRRV
Type: Integer Rdr Revision
Lock: View
Default:
PtRes: HPM
Range:

COMRDRVS
Type: Integer Rdr Version
Lock: View
Default:
PtRes: HPM
Range:

HPM Parameter Reference Dictionary C-16 8/97


COMREV

COMREV
Type: Integer HPMM Communications Software Revision
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

COMVERS
Type: Integer HPMM Communications Software Version
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

COMYEAR
Type: Integer Creation Year of HPMM Communications Personality
Lock: View
Default: N/A
PtRes: HPM
Range: 0 - 99

CONTCUT
Type: Logical Contact Cut Out —Defines whether alarms detected at this data point are to be
Lock: Prog cut out to prevent this data point's alarms from being reported to the operator.
Default: Off The alarms continue to be reported to the AM or CM through the EIPPCODE
PtRes: HPM parameter.

CONTCUT can be used to cutout alarms on a point when the alarms are
generated because of specific conditions at other points which themselves have
alarms. As an example, the user could configure a logic point so that the logic
point would monitor the nuisance alarm conditions and then store the contact
cutout state of this point using an output connection. It can also be stored by
the sequence program in the HPM or the AM which could monitor the process
conditions to determine when the alarms have to be suppressed.

Range: Off (Alarms are not cut out)


On (Alarms are cut out)

Helpful Hint: Cutout alarms behave the same as inhibited alarms; that is, when a point's
contact cutout state is true—
• alarms are not distributed to the US or HM
• return to normal events are not distributed to the US or HM
• EIP events triggered by the alarm condetion are not distributed

For HPM Box Flag points, CUTOUT applies to only slots 1–128.

HPM Parameter Reference Dictionary C-17 8/97


COUNTDWN

COUNTDWN (DigIn)
Type: Logical Accumulator Count Down Flag—Determines whether the accumulator is to
Lock: Eng/PB count down or count up.
Default: Off
PtRes: HPM
Range: Off (Accumulator is to count up)
On (Accumulator is to count down)

Helpful Hint: COUNTDWN configuration requires DITYPE = Accum.

CPMSGSEC (NIM PSDP)


Type: Real Number of Checkpoint Messages—Specifies the Number of Checkpoint
Lock: View Messages per second.
Default: 0
PtRes: NIM
Range: N/A

CPTIMAVG (NIM PSDP)


Type: Real Average Time to Complete a Checkpoint Request—Specifies the Average Time
Lock: View (in msec.) to Complete a Checkpoint Request.
Default: 0
PtRes: NIM
Range: N/A

CPTIMMAX (NIM PSDP)


Type: Real Maximum Time to Complete a Checkpoint Request—Specifies the Maximum
Lock: View Time (in msec.) to Complete a Checkpoint Request.
Default: 0
PtRes: NIM
Range: N/A

HPM Parameter Reference Dictionary C-18 8/97


CRIOLORN

CRIOLORN (1) - (4) (HPM Box)


Type: Integer Current Hour IOL Fetch/Store Overrun Counter—A counter that accumulates
Lock: View and shows the number of I/O Link fetch/store time outs that have occurred
Default: 0 during the current hour.
PtRes: HPM
In arrays 1 through 4, the counter is indexed by the cycle.
In array 0, the counter is totaled for all cycles.

Range: >0

CRPPXORN (0 - 8) (HPM Box)


Type: Integer Current Period Point Processing Overruns Per Cycle—A counter that
Lock: View accumulates and shows the number of HPMM point processing overruns that
Default: 0 have occurred during the current hour.
PtRes: HPM
In arrays 1 through 8, the counter is indexed by the cycle
In array 0, the counter is totaled for all cycles.

Range: >0

CRUCNORN (HPM Box)


Type: Integer Current-Hour UCN Access Overruns —Indicates the number of UCN access
Lock: View overruns that have occurred in the current hour. Refer to the HPM Control
Default: 0 Functions and Algorithms manual for a detailed description of overrun handling.
PtRes: HPM
Range: >0

HPM Parameter Reference Dictionary C-19 8/97


CTFLTIME

CTFLTIME (HPM Box)


Type: Time HPMM Control Failure Time—defines
Lock: View
Default: N/A
PtRes: HPM

Helpful Hint: If a value of 0 is returned for the time from the UCN, a parameter status of
Parameter Invalid is returned on the LCN.

Range: N/A

CTIDTXT (HPM BOX)


Type: String_16 HPMM Control Functionality ID Text String—defines
Lock: View
Default: Blank
PtRes: HPM
Range: N/A

CTLACTN
Type: E:POLARITY Control Action—Defines the direct/reverse action of this algorithm's output.
Lock: Eng/PB
Default: Reverse
PtRes: HPM
Range: 0-Direct (As PV increases, output increases)
1-Reverse (As PV increases, output decreases)

CTLALGID (RegCtl)
Type: E:$PMMCTAL Control Algorithm Identifier—Defines the algorithm that is to be used for
Lock: PtBld this RegCtl point.
Default: Null
PtRes: HPM
Range: 0-Null (No algorithm selected)
1-Pid (Proportional, Integral, Derivative)
2-PidFf (PID with Feedforward)
3-PidErfb (PID with External Reset Feedback)
7-RatioCtl (Ratio Control)
8-RampSoak (Ramp Soak)
9-AutoMan (Auto Manual Station)
10-IncrSum (Incremental Summer)
11-Switch (Switch)
12-ORSel (Override Selector)
13-PosProp (Position Proportional)
14-PIDPosProp (PID with Position Proportional output)

HPM Parameter Reference Dictionary C-20 8/97


CTLCFAVG

CTLCFAVG (HPM Box)


Type: Real Average HPM Control Processor CPU Free Percentage—The average percent
Lock: View of time the HPM Control Processor is not busy.
Default: NaN
PtRes: HPM
Range: 0 - 100

Helpful Hint: This statistic can be viewed on the Toolkit Displays

CTLCFMAX (HPM Box)


Type: Real Maximum HPM Control Processor CPU Free Percentage—The maximum
Lock: View percent of time the HPM Control Processor is not busy.
Default: NaN
PtRes: HPM
Range: 0 - 100

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

CTLCFMIN (HPM Box)


Type: Real Minimum HPM Control Processor CPU Free Percentage—The minimum
Lock: View percent of time the HPM Control Processor is not busy.
Default: NaN
PtRes: HPM
Range: 0 - 100

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

CTLDAY
Type: Integer Creation Day of HPMM Control Personality
Lock: View
Default: N/A
PtRes: HPM
Range: 1 - 31

CTLDGAVG (1) - (2) (HPM Box)


Type: Real Average Diagnostic cycle time (in minutes) in the Control CPU—
Lock: View
Default: 0.0
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary C-21 8/97


CTLDGMAX

CTLDGMAX (1) - (2) (HPM Box)


Type: Real Maximum Diagnostic cycle time (in minutes) in the Control CPU—
Lock: View
Default: 0.0
PtRes: HPM
Range: N/A

CTLEQN (AutoMan)
Type: E:ALGOEQN Control Equation Type
Lock: Eng/PB
Default: EqA
PtRes: HPM
Range: 0-EqA (CV = X1 + B +BI)
1-EqB (CV = X1 + (K*X2) + BI)

CTLEQN (ORSel)
Type: E:ALGOEQN Control Equation Type—Defines whether the highest or the lowest input is
Lock: PtBld to be selected.
Default: EqA
PtRes: HPM
Range: 0-EqA (Selects the highest input)
1-EqB (Selects the lowest input)

CTLEQN (Pid)
Type: E:ALGOEQN Control Equation Type—Defines how Proportional (P) or gain, Integral (I)
Lock: PtBld or reset, and Derivative (D) action is applied to a PID-type algorithm's
Default: EqA calculated Error (PV - SP).
PtRes: HPM
Range: 0-EqA (P, I, and D act on Error)
1-EqB (P and I act on Error, D acts on PV)
2-EqC (I acts on Error, P and D act on PV)
3-EqD (Integral-only control)

CTLEQN (Switch)
Type: E:ALGOEQN Control Equation Type—Defines whether the operator, the user-written
Lock: Eng/PB program, or the logic slot controls the selection of one of the four inputs
Default: EqA (X1-X4) as the input to this algorithm.
PtRes: HPM
Range: 0-EqA (Operator controls switch position)
1-EqB (Program or logic point controls switch position)

HPM Parameter Reference Dictionary C-22 8/97


CTLHOUR

CTLHOUR (HPM Box)


Type: Integer HPMM Control Personality Creation Date-Hour
Lock: View
Default: 0
PtRes: HPM
Range: N/A

CTLMIN (HPM Box)


Type: Integer HPMM Control Personality Creation Date-Minute
Lock: View
Default: 0
PtRes: HPM
Range: N/A

CTLMONTH
Type: Integer Creation Month of HPMM Control Personality
Lock: View
Default: N/A
PtRes: HPM
Range: 1 - 12

CTLNAME
Type: String_8 HPMM Control Personality Name
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

CTLOPT (HPM Box)


Type: Logical HPMM Control Processor Option
Lock: PtBld
Default: On
PtRes: HPM
Range: On (All point types can be configured)
Off (DigComp, Logic, RegCtl, or RegPV points cannot be configured; only I/O points can be
configured. This usually means that the control processor hardware is missing from the
HPM).

HPM Parameter Reference Dictionary C-23 8/97


CTLREDUN

CTLREDUN
Type: Logical HPMM Control Redundancy Present Flag
Lock: View
Default: N/A
PtRes: HPM
Range: Off
On

CTLREV
Type: Integer HPMM Control Personality Revision
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

CTLVERS
Type: Integer HPMM Control Personality Version
Lock: View
Default:
PtRes: HPM
Range: N/A

CTLYEAR
Type: Integer Creation Year of HPMM Control Personality
Lock: View
Default: N/A
PtRes: HPM
Range: 0 - 99

CTRLINIT (RegCtl)
Type: Logical Control Initialization Request Flag—A user-written program or a logic slot can
Lock: Prog cause a data point to initialize by setting the point's control initialization-request
Default: Off flag to On.
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary C-24 8/97


CURCOMFL

CURCOMFL
Type: E:$PMMHFST Current HPMM Communications Board Failure
Lock: View
Default:
PtRes: HPM
Range: Null (Unknown Error)
Pwrdwn (Power Down )
Lr_Par (Parity Error)
Lr_Lram (Local Ram Error)
Lr_Ck (Local Ram Check)
Lr_Exc (Local Ram Exception)
Lr_Hrev (Local Ram Hardware Revision)
Mm_Hrev (Memory Board Hardware Revision)
Lr_Tmr (Local Ram Timer Error)
Lr_Ptrn (Local Ram Pattern Check Error)
Lr_Byte (Local Ram Byte Error)
Lr_Adcd (Local Ram Address Decode Test)
Lr_Addl (Local Ram Additional Check)
Lr_Clrr (Local Ram Scrub Incomplete)
Sr_Par (Shared Ram Parity)
Sr_Ptrn (Shared Ram Pattern Check Error)
Sr_Adcd (Shared Ram Address Decode Test)
Sr_Addl (Shared Ram Additional Checks)
Gr_Par (Global Ram Parity)
Gr_Ptrn (Global Ram Pattern Check Error)
Gr_Byte (Global Ram Byte Error)
Gr_Adcd (Global Ram Address Decode Test)
Gr_Addl (Global Ram Additional Checks)
Gr_Clrr (Global Ram Scrub Incomplete)
31_Nr (IOL Processor, No Response or Failure)
31_Aliv (IOL Processor, Transmitter Not Alive)
31_Iltn (IOL Processor, Illegal Transition)
Nmi_Unk (Unknown NMI Request)
Baducnn (UCN Address Parity or Duplicate Address)
Nr (No Response From Other Processor)
Mrft (Memory Reference Table (Pattern Build Fail)
Nomtos (No MTOS Readout)
Llc_Comm (LLC Communication Fatal Error)
Ucndrv (UCN Driver, Fatal Error)
Rd_Hrev (Redundancy Card Version/Revision Mismatch)
Sw_Error (Software Error)
Md_Hrev (Modem Card Version/Revision Mismatch)
Da_Ptrn (Daughter Card Pattern Test)
Da_Byte (Daughter Card Byte Write Test)
Da_Adcd (Daughter Card Address Decode)
Da_Addl (Daughter Card Additional Test)
Da_Clrr (Daughter Card Scrub Incomplete)
Rd_Snps (Redundancy Card 96 Kw Snapshot Error)
Rd_Bslk (Redundancy Card Bus Lock Fail)

HPM Parameter Reference Dictionary C-25 8/97


CURCTLFL

CURCTLFL
Type: E:$PMMHFST Current HPMM Control Failure
Lock: View
Default:
PtRes: HPM
Range: Null (Unknown Error)
Pwrdwn (Power Down )
Lr_Par (Parity Error)
Lr_Lram (Local Ram Error)
Lr_Ck (Local Ram Check)
Lr_Exc (Local Ram Exception )
Lr_Hrev (Local Ram Hardware Revision)
Mm_Hrev (Memory Board Hardware Revision)
Lr_Tmr (Local Ram Timer Error)
Lr_Ptrn (Local Ram Pattern Check Error)
Lr_Byte (Local Ram Byte Error)
Lr_Adcd (Local Ram Address Decode Test)
Lr_Addl (Local Ram Additional Checks)
Lr_Clrr (Local Ram Scrub Incomplete)
Sr_Par (Shared Ram Parity)
Sr_Ptrn (Shared Ram Pattern Check Error)
Sr_Adcd (Shared Ram Address Decode Test)
Sr_Addl (Shared Ram Additional Checks)
Gr_Par (Global Ram Parity)
Gr_Ptrn (Global Ram Pattern Check Error)
Gr_Byte (Global Ram Byte Error)
Gr_Adcd (Global Ram Address Decode Test)
Gr_Addl (Global Ram Additional Checks)
Gr_Clrr (Global Ram Scrub Incomplete)
31_Nr (IOL Processor, No Response or Failure)
31_Aliv (IOL Processor, Transmitter Not Alive)
31_Ilatn (IOL Processor, Illegal Transition)
Nmi_Unk (Unknown NMI Request)
Baducnn (UCN Address Parity or Duplicate Address)
Nr (No Response From Other Processor)
Mrft (Memory Reference Table - Pattern Build Fail)
Nomtos (No MTOS Readout)
Llc_Comm (LLC Communication Fatal Error)
Ucndrv (UCN Driver, Fatal Error)
Rd_Hrev (Redundancy Card Version/Revision Mismatch)
Sw_Error (Software Error)
Md_Hrev (Modem Card Version/Revision Mismatch)
Da_Ptrn (Daughter Card Pattern Test )
Da_Byte (Daughter Card Byte Write Test )
Da_Adcd (Daughter Card Address Decode)
Da_Addl (Daughter Card Additional Tests)
Da_Clrr (Daughter Card Scrub Incomplete)
Rd_Snps (Redundancy Card 96 Kw Snapshot Error)
Rd_Bslk (Redundancy Card Bus Lock Fail)

HPM Parameter Reference Dictionary C-26 8/97


CURIOLFL

CURIOLFL
Type: E:$IOMHF Current HPMM IOL Interface Failure
Lock: View
Default:
PtRes: HPM
Range: Unknown - (Unknown Error)
Powerdwn - (Power Is Off)
Invprgex (Invalid Program Execution)
Epromerr (EPROM Error)
Ramcnter (Ram Contents Error)
Ramadrer (Ram Address Error)
Dpaerror (Device Physical Address Error)
Dsaerror (Device Soft Address Error)
Rxbufofl (Receive Buffer Overflow Error)
Ioljaber (IOL Jabber Error; Module saw or talked too much on link)
Badpgjmp (Bad Program Jump)
Adcincmp (A/D Incompatible)
Adoutovf (A/D Overflow)
Adoutudf (A/D Underflow)
Adccaler (A/D Calibration Error)
Baddcltc (Bad DC LTC)
Dmt_tmot (Deadman Time Out)
Mltoutfl (Multiple Output Failure)
Datbusfl (Data Bus Failure)
Baddarng (Bad A/D Range)
Mstrtmot (Master Timeout)
Ctrcktfl (Counter Circuit Failure)

CURPINAM (n)
Type: String_8 Current PI Filename—Defines the personality Image filename that currently
Lock: View resides in this IOP where n is the IOP number 1 - 40.
Default: N/A
PtRes: IOP
Range: N/A

HPM Parameter Reference Dictionary C-27 8/97


CURSEGID

CURSEGID (RampSoak)
Type: E:CURSEGID Current Segment ID—Defines the current ramp or soak segment.
Lock: Oper
Default: Ramp1
PtRes: HPM
Range: 0-Ramp1 1-Soak1
2-Ramp2 3-Soak2
: and :
20-Ramp11 21-Soak11
22-Ramp12 23-Soak12

CUTOFFLM (Totalizr)
Type: Real Zero-Flow Cutoff Limit—Allows the user to specify a cutoff limit such that
Lock: Supr when the value of input parameter P1 falls below the limit specified, its value is
Default: 0.0 replaced by 0.0.
PtRes: HPM
Range: > 0.0,
NaN (Cutoff limit is not applicable)

CUTOFFLM (VdtLdLag)
Type: Real Zero-Flow/Belt-Speed Cutoff Limit—Allows the user to specify a cutoff limit
Lock: Supr for equations C and D.
Default: NaN
PtRes: HPM
Range: > 0.0,
NaN (Bypasses the limit check)

CV
Type: Real Calculated Variable—The result (calculated value) of the calculation of the
Lock: Prog control algorithm. The value can be in percent or in engineering units depending
Default: NaN on the control algorithm.
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary C-28 8/97


CVEUHI

CVEUHI
Type: Real Calculated Value's High Limit in Engineering Units
Lock: Engr
Default: 100.0
(GPM,
PPH, etc.)
PtRes: HPM
Range: > CVEULO

Helpful Hint: CV ranges track X-input ranges if CTLALGID = AutoMan, ORSel, IncrSum,
or Switch. For CTLALGID = PidErfb and RampSoak, CV ranges are
configurable. For CTLALGID = Pid, Pidff, and RatioCtl, if NOCOPTS = 0,
then the CV ranges are configurable, otherwise, the CV ranges track the ranges
of the secondary output connection.

CVEULO
Type: Real Calculated Value's Low Limit in Engineering Units
Lock: Engr
Default: 0.0 (GPM,
PPH, etc.)
PtRes: HPM
Range: < CVEUHI

Helpful Hint: Same as above for CVEUHI.

CYCLEOPT (RampSoak)
Type: E:$CYCLOPT Ramp/Soak Cycle Option—Defines whether the ramp/soak cycle stops after
Lock: Oper a single cycle, or is continuous. For detailed information, refer to the HPM
Default: Cyclic Control Functions and Algorithms manual.
PtRes: HPM
Range: 0-Single (Stop after completing one complete cycle)
1-Cyclic (Repeat complete cycles over and over)

Helpful Hint: If Cyclic is entered, repeats complete ramp/soak cycles after Mode is changed
from Man to Auto. If Single is entered, performs one ramp/soak cycle and then
stops.

HPM Parameter Reference Dictionary C-29 8/97


CYCLETIM

CYCLETIM
Type: Real PosProp Output Cycle Time in Seconds—Determines the rate at which raise or
Lock: Supr lower output pulses are going to be generated. PV - SP determines the width of
Default: 10.0 seconds the output pulse.
PtRes: HPM

Range: 0.25 to 1000.0 seconds

CYCOVRO (FBus)
Type: Real Times Write Buffer Not Empty During Cycle—
Lock: View
Default: 0
PtRes: IOP

Range: N/A

HPM Parameter Reference Dictionary C-30 8/97


D

-D-

D (Summer, VdtLdLag)
Type: Real Overall Bias—Defines the overall bias used in calculating PVCALC.
Lock: Supr
Default: 0.0
PtRes: HPM
Range: N/A

D1 (VdtLdLag)
Type: Real Fixed Deadtime in Minutes—Bias value for the variable time delay.
Lock: Supr
Default: 0.0 minutes
PtRes: HPM
Range: 0.0 to 400.0 minutes

D1, D2 (DigComp, DevCtl)


Type: Logical Digital Input 1 Status and Digital Input 2 Status—Separately indicates whether
Lock: View input 1 and input 2 are on or off.
Default: Off
PtRes: HPM
Range: Off (No input present)
On (Input is present)

D1_0 (DigComp, DevCtl)


Type: E:$PVSTATS Digital Input 1 Equal to A PV State of 0—Defines the PV state that
Lock: View corresponds to input D1 = Off. D1_0 = true only if INPTDIR = Direct and the
Default: PVState0 field contact feeding D1 is open, or INPTDIR = Reverse and contact is cleared.
PtRes: HPM
Range: 0-PVState0 (STATETXT(0) describes D1 = 0)
1-PVState1 (STATETXT(1) describes D1 = 0)

Helpful Hint: Applies only if NODINPTS = 1. D1_0 is always the opposite state of D1_1.

D1_1 (DigComp, DevCtl)


Type: E:$PVSTATS Digital Input 1 Equals A PV State of 1—D1_1 defines the PV state that
Lock: Eng/PB corresponds to D1 (Input 1 status) = On. D1_1 = true only if INPTDIR =
Default: PVState1 Direct and the field contact feeding D1 is closed, or INPDIR = Reverse and
PtRes: HPM contact is open.
Range: 0-PVState0 (STATETXT(0) describes D1 = 1)
1-PVState1 (STATETXT(1) describes D1 = 1)

Helpful Hint: D1_1, Digital Input 1 Equal To A PV State Of 1, applies only if NODINPTS =
1. D1_1 is always the opposite state of D1_0 and vice versa.

HPM Parameter Reference Dictionary D-1 8/97


D2

D2 (VdtLdLag)
Type: Real Bias for Input P2
Lock: Supr
Default: 0.0
PtRes: HPM
Range: > 0.0

D2D1_00 (DigComp, DevCtl)


Type: E:$PVSTATS D2_D1 Zero_Zero PV State—Defines the PV state descriptor that is to be
Lock: Eng/PB used and displayed when inputs D2 and D1 are both Off (00).
Default: MovPV
PtRes: HPM
Range: 0-PVState0 (STATETXT(0) descriptor)
1-PVState1 (STATETXT(1) descriptor)
2-BadPV (BADPVTXT descriptor)
3-MovPV (MOVPVTXT descriptor)
4-PVState2 (STATETXT(2) descriptor)

Helpful Hint: D2D1_00 configuration requires NODINPTS = 2. Option PVState2 cannot be


selected unless NOSTATES = 3. STATETXT(0–2) is configured for each
DigComp or DevCtl point; BADPVTXT and MOVPVTXT are configured
during Box Data Point configuration for all DigComp or DevCtl points in this
box.

D2D1_01 (DigComp, DevCtl)


Type: E:$PVSTATS D2D1 Zero_One PV State—Defines the PV state descriptor that is to be used
Lock: Eng/PB and displayed when input D2 is Off and input D1 is On (01).
Default: PVState1
PtRes: HPM
Range: 0-PVState0 (STATETXT(0) descriptor)
1-PVState1 (STATETXT(1) descriptor)
2-BadPV (BADPVTXT descriptor)
3-MovPV (MOVPVTXT descriptor)
4-PVState2 (STATETXT(2) descriptor)

Helpful Hint: D2D1_01 configuration requires NODINPTS = 2. Option PVState2 cannot be


specified unless NOSTATES =3. STATETXT(0–2) is configured for each
DigComp or DevCtl tag name; BADPVTXT and MOVPVTXT are configured
during Box Data Point configuration for all DigComp or DevCtl points in the
box.

HPM Parameter Reference Dictionary D-2 8/97


D2D1_10

D2D1_10 (DigComp, DevCtl)


Type: E:$PVSTATS D2D1 One_Zero PV State—Defines the PV state descriptor that is to be used
Lock: Eng/PB and displayed when input D2 is On and input D1 is Off (10).
Default: PVState0
PtRes: HPM
Range: 0-PVState0 (STATETXT(0) descriptor)
1-PVState1 (STATETXT(1) descriptor)
2-BadPV (BADPVTXT descriptor)
3-MovPV (MOVPVTXT descriptor)
4-PVState2 (STATETXT(2) descriptor)

Helpful Hint: D2D1_10 configuration requires NODINPTS = 2. Option PVState2 cannot be


specified unless NOSTATES = 3. STATETXT(0–2) is configured for each
DigComp or DevCtl point; BADPVTXT and MOVPVTXT are configured
during Box Data Point configuration for all DigComp or DevCtl points in the
box.

D2D1_11 (DigComp, DevCtl)


Type: E:$PVSTATS D2D1 One_One PV State—Defines the PV state descriptor that is to be used
Lock: Eng/PB and displayed when inputs D2 and D1 are both On (11).
Default: BadPV
PtRes: HPM
Range: 0-PVState0 (STATETXT(0) descriptor)
1-PVState1 (STATETXT(1) descriptor)
2-BadPV (BADPVTXT descriptor)
3-MovPV (MOVPVTXT descriptor)
4-PVState2 (STATETXT(2) descriptor)

Helpful Hint: D2D1_11 configuration requires NODINPTS = 2. Option PVState2 cannot be


specified unless NOSTATES = 3. STATETXT(0–2) is configured for each
DigComp or DevCtl point; BADPVTXT and MOVPVTXT are configured
during Box Data Point configuration for all DigComp or DevCtl points in the
box.

HPM Parameter Reference Dictionary D-3 8/97


DAMPING

DAMPING (STI)
Type: Real Damping—Defines the first-order PV filtering option for the smart transmitter.
Lock: Supr/View User can also implement PV filtering by using this parameter or the TF
Default: 0.0 parameter; however, DAMPING is the preferred parameter. If DAMPING has
PtRes: HPM been configured at the transmitter using the Universal Station, the STI IOP
adjusts the entered value to one of the values in the range shown below for the
appropriate transmitter type. For Multivariable transmitters with SENSRTYP =
SFM the IOP will not adjust the damping value.

Any real number in the range of damping specified by the transmitter user
manual can be used. It can be changed only when the STI point execution state
PTEXECST is Inactive.
Range:
Transmitter Type
Spt Stt Sfm

0.0 0.0 0.0


0.16 0.30 0.5
0.32 0.70 1.0
0.48 1.5 2.0
1.00 3.10 3.0
2.0 6.3 4.0
4.0 12.7 5.0
8.00 25.5 10.0
16.0 51.1 50.0
32.0 102.3 100
NaN NaN NaN

DATE (HPM Box)


Type: Time Current Date/Time—Value of the LCN date in the HPM.
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

DAY (HPM Box)


Type: Integer Current Day—Value of the LCN date in the HPM.
Lock: View
Default: N/A
PtRes: HPM
Range: 1 to 31

DB_VALID(1)–(40) (HPM Box)


Type: E:$DBVALID Database Valid—Indicates if the database is valid. The IOP cannot be set to
Lock: Engr RUN unless the database is valid.
Default: Invalid
PtRes: HPM
Range: Valid (Database is valid)
Invalid (Database is not valid)

HPM Parameter Reference Dictionary D-4 8/97


DEADBAND

DEADBAND(1)–(24) (Logic)
Type: Real Deadband Value—Defines the value of the deadband for the specified logic block
Lock: Supr within the logic slot.
Default: 1.0
PtRes: HPM
Range: > 0.0

Helpful Hint: DEADBAND requires LOGALGID = EQ, NE, GT, GE, LT, or LE.

DEADBAND (PosProp, PIDPosPr)


Type: Real Deadband in Percent of Full Scale—Defines the error deadband.
Lock: Supr
Default: 5.0 %
PtRes: HPM
Range: 0.0 to 100.0 %

DEADTIME (PosProp, PIDPosPr)


Type: Real Deadtime (in seconds)—Additional pulse time required to overcome the friction
Lock: Supr in the motor when it begins to move or change direction. It is added to the
Default: 0.0 calculated pulse time except when the pulse that was issued in the last cycle time
PtRes: HPM was in the same direction (as the pulse this time), and the pulse width was equal
to CYCLETIM.
Range: 0.0 to 60.0 seconds

DEBOUNCE (DigIn)
Type: Integer Contact Debounce Time in Milliseconds—The length of time an input must
Lock: Engr/PB remain in a new state for it to be declared as a valid event by the DISOE IOP.
Default: 10 milliseconds Refer to the Absolute Delay Across parameter located in the Digital Input
PtRes: HPM Processor table of the HPM Specification and Technical Data.
Range: 0 to 50 milliseconds

HPM Parameter Reference Dictionary D-5 8/97


DECONF

DECONF (STI)
Type: E:$DECONF Digitally Enhanced Configuration Mode—Defines the contents of the data that
Lock: Eng/View will be sent by the smart transmitter to the STI point.
Default: Pv_Sv_Db The use of Pv_Db and Pv_Sv_Db is recommended because they offer database
PtRes: HPM mismatch detection and on-process mismatch recovery.

This parameter can be changed only when the STI point execution state
PTEXECST is Inactive.

Range: 0-Analog (Not Supported)


1-Pv (Transmits only the PV; 4-byte format)
2-Pv_Sv (Transmits the PV and the secondary variable (SV); 4-byte format)
3-PV_Db (Transmits the PV and the transmitter database; 6-byte format)
4-Pv_Sv_Db (Transmits the PV, SV, and the transmitter database; 6-byte format)

Helpful Hint: For the PV_Db and Pv_Sv_Db selections, one byte of the transmitter database
is transmitted each time the PV is transmitted to the STI IOP.

DELCV (IncrSum)
Type: Real Delta CV in Engineering Units—Indicates the calculated change in the CV
Lock: View output value in engineering units.
Default: N/A
PtRes: HPM
Range: N/A

DELCV (Pid)
Type: Real Delta CV in Percent—Indicates the calculated change in the CV output value in
Lock: View percent.
Default: N/A
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary D-6 8/97


DEV

DEV (RegCtl)
Type: Real Deviation—Indicates the deviation (PV - SP) in engineering units.
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

DEVADDR (Array)
Type: Real Serial Link Device Address—Indicates the serial link address of the device
Lock: PtBld containing data.
Default: NaN
PtRes: HPM
Range: N/A

DEVHIFL (RegCtl)
Type: Logical Deviation High Alarm Flag—Indicates whether the DEVHITP has been
Lock: View exceeded.
Default: Off
PtRes: HPM
Range: Off (No DEVHI alarm)
On (DEVHITP has been exceeded)

DEVHIPR (RegCtl)
Type: E:ALPRIOR Deviation High Alarm Priority—Defines the priority of the deviation high
Lock: Engr alarm.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

DEVHITP (RegCtl)
Type: Real Deviation High Alarm Trip Point—Defines the upper limit for the deviation.
Lock: Supr
Default: NaN
PtRes: HPM
Range: > 0.0,
NaN

Helpful Hint: Alarm occurs when the PV is higher than SP + DEVHITP.

HPM Parameter Reference Dictionary D-7 8/97


DEVLOFL

DEVLOFL (RegCtl)
Type: Logical Deviation Low Alarm Flag—Indicates whether the DEVLOTP has been
Lock: View exceeded.
Default: Off
PtRes: HPM
Range: Off (DEVLOTP has not been exceeded)
On (DEVLOTP has been exceeded)

DEVLOPR (RegCtl)
Type: E:ALPRIOR Deviation Low Alarm Priority—Defines the priority of the deviation low alarm.
Lock: Engr
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

DEVLOTP (RegCtl)
Type: Real Deviation Low Alarm Trip Point—Defines the lower limit for the deviation.
Lock: Supr
Default: NaN
PtRes: HPM
Range: > 0.0,
NaN

Helpful Hint: Alarm occurs when the PV is lower than SP - DEVLOTP.

HPM Parameter Reference Dictionary D-8 8/97


DHTIMMAX

DHTIMMAX(1) - (5) (NIM PSDP)


Type: Real Maximum Time to Complete a Data Handler Request—Specifies the
Lock: View maximum time to complete a Data Handler request in msec.
Default: 0
PtRes: NIM
Range: N/A

DIAGCMD (ProcMod)
Type: E: DIAGCMD Diagnostic Command—
Lock: Oper
Default: N/A
PtRes: HPM
Range:

Helpful Hint: DIAGCMD resets the ProcMod overrun statistics and AVGPU and MAXPU
values.

DISP_SIM (HPM Box)


Type: Logical Simulation Indicator Display Switch—see also SIM_TXT
Lock: Prog
Default: On
PtRes: HPMM
Range: Off (Simulation indicator is not required to be displayed
On (Simulation indicator is required to be displayed

HPM Parameter Reference Dictionary D-9 8/97


DISRC(1)–(2)

DISRC(1)–(2) (DigComp, DevCtl)


Type: Universal Digital Composite and Device Control Input-Connection Source—Specify the
Ent.Prm sources whose values are to be fetched and delivered to Digital Composite data
Lock: PtBld point inputs D1 and D2. The source can be specified using the
Default: null.null "Tagname.Parameter" format or the hardware reference address format. Refer to
PtRes: HPM the HPM Control Functions and Algorithms manual for a detailed description.

Range: Use Tagname.Parameter format for tagged points where Tagname can be up to 16 characters and
the permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters, and must be a legitimate parameter name.

Some possible input-connection sources are


a."DigIn slot Tagname.PVFL"
b."DigOut slot Tagname.SO"
c."Logic slot Tagname.SO(nn)" where nn = 1–24
d."Logic slot Tagname.Fl(nn)" where nn = 1–12
e."ProcMod slot Tagname.Fl(nnn)" where nnn = 1–127
f."Box Flag slot Tagname.PVFL
g."!Box.FL(nnnn)" for a box flag that resides in the same box;
nnnn = 1–16,384
h."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the NIM UCN address, xx is the HPM box number, and
nnnn = 1–4095

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DI (Digital Input)
mm is the IOP Card number (1–40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up-to-eight characters and must be a legitimate parameter name.

DITYPE
Type: E:$DITYPE Digital Input Type—Defines the type of digital input point.
Lock: PtBld
Default: Status
PtRes: HPM
Range: 0-Status (Point is to be used for alarming and event reporting)
1-Latched (Point is to be used for event reporting)
2-Accum (Point is to be used for accumulating pulses)

HPM Parameter Reference Dictionary D-10 8/97


DLYTIME

DLYTIME (DigIn)
Type: Integer Delay Time—For an off-normal alarm, defines the time (in seconds) that a point
Lock: Supr with a previously detected alarm condition is guaranteed to remain in alarm, even
Default: 5 seconds if the condition clears. If an alarm condition exists when the delay timer expires,
PtRes: HPM the point is held in alarm.

For a change of state (COS) alarm, if the PV is in the same state when the delay
timer expires, future state changes are immediately alarmed. If the PV is in the
opposite state, a second COS alarm is produced and the delay timer is restarted.
Range: 0 to 60 seconds

DLYTIME(1)–(24) (Logic)
Type: Real Alarm Delay in Seconds for Logic Block
Lock: Supr
Default: 1 second
PtRes: HPM
Range: 1–8000 seconds

Helpful Hint: DLYTIME requires LOGALGID = Pulse, MinPulse, MaxPulse,


OnDelay, OffDelay, or Watchdog.

HPM Parameter Reference Dictionary D-11 8/97


DODSTN

DODSTN(1)–(3) (DigComp, DevCtl)


Type: Universal Digital Composite and Device Control Output-Connection Destination—
Ent.Prm Specifies up to three output connection destinations that are to receive the OP
Lock: PtBld output from this point. The destination can be specified using the
Default: null.null "Tagname.Parameter" format or the hardware reference address format. Refer to
PtRes: HPM the HPM Control Functions and Algorithms manual for a detailed description.
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters, and must be a legitimate parameter name.

Some possible output-connection destinations are


a."DigOut slot tagname.ONPULSE or OFFPULSE"
b."DigOut slot Tagname.SO"
c."Logic slot Tagname.Fl(nn)" where nn = 7–12
d."ProcMod Tagname.Fl(nnn)" where nnn = 1–127
e."Flag slot Tagname.PVFL
f."!Box.FL(nnnn)" for a box flag that resides in the same HPM box; nnnn = 1–16,384.
g."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the NIM UCN address, xx is the HPM box number, and
nnnn = 1–4095.

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DO (Digital Output)
mm is the IOP Card number (1–40)
The letter "S" is a constant.
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

DOTYPE (DigOut)
Type: E:$DOTYPE Digital Output Type—Determines the type of digital output point.
Lock: PtBld
Default: Status
PtRes: HPM
Range: 0-Status (Status output type)
1-Pwm (Pulse Width Modulated output type)

DSA
Type: Integer Device Soft Address—The logical address of an IOP: 1-40 for primary IOPs
Lock: View and 129 - 168 for secondary IOPs.
Default: N/A
PtRes: HPM
Range: 1 - 40 for primary IOPs
129 - 168 for secondary IOPs

HPM Parameter Reference Dictionary D-12 8/97


EIPPCODE

-E-

EIPPCODE
Type: Ent_Id Event-Initiated Processing Point Identifier—Defines the tag name of the point in
Lock: Engr the AM or CM that is to be notified when an event is detected by this point.
Default: Null
PtRes: NIM
Range: Tag name of the data point can be up to 16 characters and the permissible character set is as
follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.

Helpful Hint: EIPPCODE configuration requires PNTTYPE = DigIn, DigComp, Logic, Flag
or DevCtl and EVTOPT = Eip or Eip_Soe. For HPM Box Flag points, this
parameter applies only to slots 1 through 128.

EQUOBJNM
Type: String Equipment List Object Name—Specifies the Equipment List Object Name (CL
Lock: View object header)
Default: Blank
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary E-1 8/97


ERRCODE

ERRCODE (Array)
Type: String_8 Serial Interface/Serial Link Communication Error Code—When the BADPVFL
Lock: View parameter = ON, this parameter provides additional information if initialized by
Default: Spaces the serial interface FTA driver program.
PtRes: HPM
SI Array Point Error Code Values

HPM

HPM Idle—When the HPMM status is IDLE, Array point configuration may or
may not be loaded to the SI IOP.
Iop Comm—When the HPMM status is RUN, Array point configuration is
NOT loaded to the SI IOP.

SI IOP

No_FTA—Appears when the power adapter panel is not connected to the IOP.
FTA_Comm—Appears when the corresponding FTA is not connected to the
power adapter panel, or when communication between the IOP and FTA has
failed.
CFG_Load—Appears when configuration data is downloaded to the FTA.
Mod_Idle—Appears when configuration data is downloaded to the FTA and the
IOP is in IDLE mode, or when the IOP operating state is switched from RUN to
IDLE.

SI IOP FTA Common

Dev Addr—The device address has a configuration error


Data Type—The data type has a configuration error
Startidx—The start index has a configuration error
# Elemnt—A number of elements configuration error has occurred
Config—An application-specific configuration error has occurred
Inv Resp—An invalid field device response has occurred
Parity, Checksum, MsgTmout, ChrTmout—A field device communication error
has occurred
Ex or xx—An exception or other field device error has occurred. The “xx” error
code is specific to the field device
Fac Test—A factory test is in progress
OK—No errors exist

Range: N/A

HPM Parameter Reference Dictionary E-2 8/97


ESWATO

ESWAUTO (RegCtl)
Type: Logical External Switching Flag for Automatic Mode—When On, means that this
Lock: Prog point's operating mode has been switched from some mode other than automatic
Default: Off to the automatic mode by an external source.
PtRes: HPM
Range: Off
On

ESWCAS (RegCtl)
Type: Logical Eternal Switching Flag for Cascade Mode—When On, means that this point's
Lock: Prog operating mode has been switched from some mode other than cascade to cascade
Default: Off mode, by an external source.
PtRes: HPM
Range: Off
On

ESWENBST (RegCtl)
Type: E:ENBLSTAT External Mode Switching Enable State—Defines whether external mode
Lock: Oper switching is permitted for this point.
Default: Disable
PtRes: HPM
Range: 0-Disable (Does not allow external switching of point's mode)
1-Enable (Allows external switching of point's mode)

Helpful Hint: ESWENBST cannot be changed if parameter SHUTDOWN is On or if


parameter REDTAG is On.

ESWMAN (RegCtl)
Type: Logical External Switching Flag for Manual Mode—When On, means that this point's
Lock: Prog operating mode has been switched from some mode other than the manual mode
Default: Off to the manual mode by an external source.
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary E-3 8/97


EUDESC

EUDESC
Type: String_8 Engineering Units Descriptor—An eight-character descriptor that defines the
Lock: PtBld name of the engineering units (EU) that are displayed on the Group and Detail
Default: Blank Displays for this point as shown in Figure N-1 (see NAME). In this figure,
PtRes: NIM LBS/SEC is the engineering unit descriptor.

Range: Permissible character set consists of all characters on the Engineer' s Keyboard. Basically this set
consists of alphabetics A-Z, numerics 0-9, and the following special characters: space ! % & '
( ) * + - / : ; > < = ? _ , . $

EUNDESC (1)–(168)
Type: String_72 IOP Generic Descriptor—Used as additional display text to help the operator
Lock: View diagnose potential problems with the IOP. It is primarily used with diagnostic
Default: Blanks displays.
PtRes: HPM
Range: nn = 1-40 specifies one of the 40 acting primaries.
nn = 129-168 specifies one of the 40 acting secondaries.

EVRCINPG
Type: Logical NIM Event Recovery in Progress Flag
Lock: View
Default:
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary E-4 8/97


EVTOPT

EVTOPT (DigComp)
Type: E:$EVTOPT Event Reporting Option—If EVTOPT = Eip and the PV changes or a PV alarm
Lock: PtBld is generated, the AM or CM data point named EIPPCODE is notified and a
Default: None "process special" on that data point takes place.
PtRes: HPM
Range: 0-None (Event-Initiated Processing is not allowed)
1-Eip (Process special is triggered in AM/CM)

Helpful Hint: EVTOPT configuration requires NODINPTS > 0.

EVTOPT (DevCtl, DigIn)


Type: E:$EVTOPT Event Reporting Option—If EVTOPT = Eip and the PV changes, the AM or
Lock: PtBld CM data point named EIPPCODE is notified and a "process special" on that
Default: None data takes place. If EVTOPT = Soe and a PV change occurs, Sequence Of
PtRes: HPM Events Processing is notified. If EVTOPT = EipSoe, the actions in both
apply.

Range: 0-None (Neither Eip nor Soe is allowed)


1-Eip (Process special is triggered in AM/CM)
2-Eip_Soe (Eip and Soe are both allowed)
3-Soe (Point notifies Sequence of Events Processing)

Helpful Hint: EVTOPT configuration requires DITYPE = Status or Latched. If DITYPE =


Latched, EVTOPT cannot = EIPSOE or SOE.

EXTDATA (Array)
Type: E:$EXTDATA External Data Option—Indicates if either the Array point flags, numerics, or
Lock: PtBld strings are mapped from a serial interface.
Default: None
PtRes: HPM
Range: None (None of the flags, numerics, or strings are mapped from a serial interface)
IO_FL (IO flags are mapped from a serial interface)
IO_NN (IO numerics are mapped from a serial interface)
IO_STR (IO strings are mapped from a serial interface)
UCN_FL (Reserved for future use)
UCN_NN (Reserved for future use)
UCN_STR (Reserved for future use)

Helpful Hint: You can map either flags, numerics, or strings from the Serial
Interface to a single Array point.

HPM Parameter Reference Dictionary E-5 8/97


EXTSWOPT

EXTSWOPT
Type: E:EXTSWOPT External Mode Switching Option—External mode switching is typically used
Lock: Eng/PB to establish mode interlocks, or under certain process conditions, to restrict the
Default: None use of a mode that invokes a higher level of control. Refer to the HPM
PtRes: HPM Control Functions and Algorithms manual for a detailed description of external
mode switching.

Range: 0-None (No external mode switching is allowed)


1-Ems (External source can change point's mode)
2-Emp (Not implemented)

HPM Parameter Reference Dictionary E-6 8/97


F

-F-

F (FlowComp)
Type: Real Flow Input—Indicates the value of the uncompensated flow input. This input is
Lock: View a square-rooted, differential pressure input.
Default: NaN
PtRes: HPM
Range: N/A

FAILCODE
Type: E:$IOMHF I/O Processor Hard Fail Status—
Lock: View
Default: N/A
PtRes: IOP

Range: 0-Unknown (Unknown status)


1-PowerDwn(This IOP Powered Down)
2-InvPrgEx(Invalid Program Execution)
3-EpromErr(EPROM Checksum Error)
4-RamCntEr(RAM Contents Error)
5-RamAdrEr(RAM Addressing Error)
6-DpaError(Device Physical Address Error)
7-DsaError(Device Soft Address Error)
8-RxBufOfl(I/O Link Receive Buffer Overflow)
9-IOLJaber(I/O Link Jaber Circuit Failure)
10-
11-BadPgJmp(Illegal Value of Case Control)
12-AdCIncmp(A to D Conversion Incomplete)
13-AdOutOvf(A to D Output Value Overflow)
14-AdOutUdf(A to D Output is less than Zero)
15-AdCCalEr(A to D Calibration is incorrect)
16-BadDcLtc(Bad DC LTC)
17-Dmt_Tmot(Dead Man Timer Timeout)
18-MLtOutFl(Multiple Output Failure)
20-BadDaRng(Bad D to A Range)
21-MstrTmot(Master 68K Timeout)

FAILOPT(1)–(168) (IOP)
Type: E:FAILOPT Failure Option for Outputs—Defines the state which an AO or DO IOP goes
Lock: Eng/PB into if the IOP itself, or the HPMM fails. If the IOP failure is due to power
Default: Unpower loss, outputs go to unpowered regardless of the FAILOPT value. When power
PtRes: HPM is restored to the module, outputs are reset regardless of the FAILOPT values.

Range: 0-Hold (Hold output at last good value)


1-Unpower (Remove power from the output)

HPM Parameter Reference Dictionary F-1 8/97


FBTIME

FBTIME (DevCtl, DigComp)


Type: Integer Feedback Time—Sets the amount of time (in seconds) that the point should wait
Lock: Supr if before generating a "command disagree" alarm after the operator has issued a
CMDFALTM start/stop-type command to a field device.
is changed from
a non-zero value
to a zero value,
else Eng/PB
Default: 0
PtRes: HPM
Range: 0 to 1000 seconds (0 indicates that command disagree alarming is disabled)

Helpful Hint: FBTIME can be increased to compensate for a slow-responding field device
that does not respond to the operator’s command in time to prevent a
command-disagree alarm.

FF (PidFf)
Type: Real Feed Forward Algorithm Input—FF is the feedforward input signal value that is
Lock: View added to (FFOPT = Add) or multiplied by (FFOPT = Multiply) the PidFf
Default: N/A algorithm's incremental output, before the full-value output is accumulated. FF
PtRes: HPM is normally a parameter with a percentage value.
Range: N/A

FFOPT (PidFf)
Type: E:FFOPT Feed Forward Type—Determines whether a PidFf algorithm's feedforward input
Lock: Eng/PB signal (FF) is added to or multiplied by the incremental output, before the full-
Default: Multiply value output is accumulated.
PtRes: HPM
Range: 0-Add (Scaled Feedforward + Feedback)
1-Multiply (Feedback x Scaled, Biased Feedforward)

FL(i) (Array)
Type: Logical Array Point Flag Variables—The flags are mapped from either the HPM
Lock: Determined by box (defined by FLSTIX and NFLAG parameters), or from a serial interface
SPLOCK IOP-connected device (when EXTDATA=IO_FL, mapping is defined by
parameter IOPNUM, FTANUM, DEVADDR, FLSTIX, and NFLAG parameters).
Default: N/A
PtRes: HPM
Range: 1 £ i £ Array parameter NFLAG

HPM Parameter Reference Dictionary F-2 8/97


FL

FL(1)–(12) (DevCtl, Logic)


Type: Logical Logic Slot Flags—Twelve flags, FL(1) to FL(12), are provided for each logic
Lock: View; FL1-FL5 slot. The states of flags FL(1) to FL(6) are controlled by the HPM and cannot
Prog; FL6 be changed by the user. FL(7)-FL(12) are assigned by the user for controlling
Oper; FL7- the path of the logic in the respective logic slot. Refer to the HPM Control
FL12 Functions and Algorithms manual for a detailed description
Default: FL2 = On,
rest = Off These flags are local to the logic slot and are different than the 127 flags
PtRes: HPM provided with each process module, and the 1023 flags provided in each HPM
box.
Range: Off (Flag is off)
On (Flag is set)

FL(1)–(127) (ProcMod)
Type: Logical Local Flag Variables—Each process module in the HPM has 127 local flags that
Lock: Determined can be used for implementing batch operations. These flags are local to the
by SPLOCK process module and are different than the 12 logic-slot flags, and the 1023 flags
parameter provided in each HPM box.
Default: Off
PtRes: HPM
Range: Off (Flag is off)
On (Flag is set)

FL(1)–(16,384) (HPM Box)


Type: Logical Box Flag Variables—Each HPM box has a set of 16,384 local flag variables that
Lock: Oper can be used by process modules in this HPM to implement batch operations.
Default: Off The first 2047 box flags are taggable. These flags are local to the HPM box and
PtRes: HPM are different than the 12 logic-slot flags, and the 127 flags provided in each
process module. The LCN index limit is 4095; there is no index limit for the
UCN. Array points can be used to address flags with an index greater than 4095.
Range: Off (Flag is off)
On (Flag is set)

Helpful Hint: For the first 128 flags, the On state is alarmed.

FLDESC (Array)
Type: String_64 FL Array Descriptor—Describes FL data for the Array point.
Lock: PtBld
Default: Spaces
PtRes: HPM
Range: N/A

FLSTIX (Array)
Type: Real Flag Array Start Index—Defines the flag array start index in Box FL variables or
Lock: PtBld serial interface-connected devices.
Default: 0.0
PtRes: HPM
Range: 0 to 99,999 (When EXTDATA = IO_FL, 0 can be a valid device index)
0 to 16,384 (When EXTDATA ¹ IO_FL, 0 indicates that no flags are configured)

HPM Parameter Reference Dictionary F-3 8/97


FORCE

FORCE (HiLoAvg)
Type: Logical Forced Input Request Flag—Defines whether the operator, a user-written
Lock: Oper program, or an input connection has requested that an input be used as the forced
Default: Off input for this algorithm.
PtRes: HPM
Range: Off (No request to force an input)
On (Request has been made to force an input)

Helpful Hint: FORCE change requires FRCPERM = On.

FRCPERM (HiLoAvg)
Type: Logical Forced Input Permissive—Defines whether an operator or a user-written program
Lock: Eng/PB can force-select an input. FRCPERM must be On before the operator or a
Default: Off program can select an input to be used as a forced input to this algorithm.
PtRes: HPM
Range: Off (Forced-selection function is disabled)
On (Forced- selection function is enabled)

FREQ6050(1)–(168)
Type: E:FRQ6050 Frequency 60/50Hz—Defines the 60/50 Hz frequency configuration needed for a
Lock: Eng/PB Low Level AI Mux or STI Temperature Transmitter. For the STI, if a
Default: 60Hz mismatch occurs between this parameter and the transmitter's internal 60 Hz/50
PtRes: HPM Hz frequency parameter, a database download from the STI IOP to the transmitter
Range: 0-60 Hz will clear this condition.
1-50 Hz

FRQUTAVG (NIM, HPM Box)


Type: Real Average UCN Fetch Request Trip Time—The average time in milliseconds it
Lock: View takes to receive a response to this node’s UCN fetch requests.
Default: NaN
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

FRQUTMAX (NIM, HPM Box)


Type: Real Maximum UCN Fetch Request Trip Time—The maximum time in
Lock: View milliseconds it takes to receive a response to this node’s UCN fetch requests.
Default: NaN
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary F-4 8/97


FRSPTAVG

FRSPTAVG (NIM, HPM Box)


Type: Real Average UCN Fetch Response Trip Time—The average time in milliseconds
Lock: View for this node to respond to fetch requests from other UCN nodes.
Default: NaN
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

FRSPTMAX (NIM, HPM Box)


Type: Real Maximum UCN Fetch Response Trip Time—The maximum time in
Lock: View milliseconds for this node to respond to fetch requests from other UCN nodes.
Default: NaN
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

FSELIN (HiLoAvg)
Type: E:PINP Force Selected Input—Defines the one of six inputs to be used as the forced
Lock: Oper/PB input to this algorithm.
Default: SelectP1
PtRes: HPM
Range: 1-SelectP1 (Input P1 is the forced input)
2-SelectP2 (Input P2 is the forced input)
3-SelectP3 (Input P3 is the forced input)
4-SelectP4 (Input P4 is the forced input)
5-SelectP5 (Input P5 is the forced input)
6-SelectP6 (Input P6 is the forced input)

Helpful Hint: FSELIN change by an operator requires FRCPERM = On.

FSTS (FlowComp)
Type: E:PVVALST Flow Input Value Status—Indicates the current status of flow input F.
Lock: View
Default: Bad
PtRes: HPM
Range: 0-Bad (Value is bad and replaced with NaN)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

HPM Parameter Reference Dictionary F-5 8/97


FTA1TYPE

FTA1TYPE, FTA2TYPE (HPM Box)


Type: E:$FTATYPE Type of FTA Connected to the LLMUX IOP or RHMUX IOP—The FTA
Lock: View type applies to both FTA positions (1 and 2). The FTA supplies 16 points
Default: None per FTA for a total of 32 points.
PtRes: HPM
Range: 0-None
1-TC
2-RTD

FTACONN(1)–(168) (HPM Box)


Type: E:$FTACON FTA connection to I/O module file. Indicates which FTA connector is connected
Lock: View to this module. It is primarily used with the diagnostic displays.
Default: CONN_A nn = 1–40 specifies FTA connection for one of the 40 acting primaries. nn =
PtRes: HPM 129–168 specifies FTA connection for one of the 40 acting secondaries.
Range: 0-CONN_A (Module is connected to FTA connector A)
1-CONN_B (Module is connected to FTA connector B)

FTANUM (Array)
Type: Integer IOP FTA Number—Indicates the FTA number of the serial interface IOP.
Lock: PtBld
Default: 1
PtRes: HPM
Range: 1 to 10

Helpful Hint: Only FTA Numbers 1 and 2 are presently applicable.

FTAPRES(1)–(168)
Type: Logical IOP FTA Present Flag—For primary and secondary IOPs.
Lock: View
Default:
PtRes: HPM
Range: Off (FTA Missing)
On (FTA Present)

HPM Parameter Reference Dictionary F-6 8/97


G

-G-

G (FlowComp)
Type: Real Specific Gravity Input—Indicates the value of the measured or calculated specific
Lock: View gravity or molecular weight.
Default: 1.0
PtRes: HPM
Range: N/A

GAINOPT (Pid)
Type: E:GAINOPT Gain (K) Option
Lock: Eng/PB
Default: Lin
PtRes: HPM
Range: 0-Lin (Applies linear gain, with overall gain (K) = KLIN)

1-Gap (Reduces the sensitivity of control action when the PV is within a narrow band around the
setpoint. If the PV is outside the gap, overall gain (K) = KLIN. If (SP - GAPLO) < PV <
(SP + GAPHI), K = KLIN times KGAP)

2-Nonlin (Makes control action proportional to the error (PV - SP) squared with overall
gain (K) =KLIN times KNL, where KNL = NLFM plus (NLGAIN times PV - SP)/100)

3-Ext (Applies external gain. Overall gain (K) = KLIN times KEXT, where KEXT is the
positive external gain modifier)

GAPHI (Pid)
Type: Real Gap High Limit—Defines the upper limit of the gap in the same engineering
Lock: Supr units as the PV.
Default: 0.0
PtRes: HPM
Range: > 0.0

GAPLO (Pid)
Type: Real Gap Low Limit—Defines the bottom limit of the gap in the same engineering
Lock: Supr units as the PV.
Default: 0.0
PtRes: HPM
Range: > 0.0

HPM Parameter Reference Dictionary G-1 8/97


GENDESC

GENDESC (1)–(12)
Type: String_8 Generic Descriptors—Define up to 12 generic descriptors that can be assigned to
Lock: PtBld logic-slot parameters. As an example, six descriptors could be assigned to six
Default: Blanks logic-slot inputs, two descriptors to the logic block flags which will describe the
PtRes: NIM current state of the logic slot based on the inputs, and two descriptors to the SO
outputs from the logic slot. Refer to the description of the PRMDESC
parameter, and to the HPM Control Functions and Algorithms manual for a
detailed description.
Range: Permissible character set for the eight-character generic descriptors consists of all characters on the
Engineer' s Keyboard. Basically this set consists of alphabetics A-Z, numerics 0-9, and the
following special characters: space ! " % & ' ( ) * + - / : ; > < = ? _ , . $

Helpful Hint: Example: GENDESC(7) is the descriptor for parameter PRMDESC(7), etc.

GENDESC(nn)
Type: String_72 Generic Descriptor—Used as additional display text to help the operator
Lock: View diagnose potential problems with the IOP. It is primarily used with
Default: Blanks diagnostic displays.
PtRes: HPM nn = 1–40 specifies one of the 40 acting primaries.
nn = 129–168 specifies one of the 40 acting secondaries.

GISRC(1—4) (RegCtl, RegPV)


Type: General Input Source—Specifies the Tag.Parameter source of General Input
Lock: Connection.
Default:
PtRes: HPM
Range:

GIDSTN(1—4) (RegCtl, RegPV)


Type: Parameter Destination General Input Connection—Specifies the
Lock: RegPV/RegCtl parameter destination of the General Input Connection
Default:
PtRes: HPM
Range:

GIENBL(1—4) (RegCtl, RegPV)


Type: General Input Connection Enable Flag—
Lock:
Default:
PtRes: HPM
Range:

HPM Parameter Reference Dictionary G-2 8/97


GOSRC

GOSRC(1—4) (RegCtl, RegPV)


Type: Parameter Source of General Output Connection—Specifies the
Lock: RegPV/RegCtl parameter source of the General Output Connection
Default:
PtRes: HPM
Range:

GODSTN(1—4) (RegCtl, RegPV)


Type: Parameter Destination General Output Connection—Specifies the
Lock: Tag.parameter destination of the General Output Connection
Default:
PtRes: HPM
Range:

GOENBL(1—4) (RegCtl, RegPV)


Type: General Output Connection Enable Flag—
Lock:
Default:
PtRes: HPM
Range:

GSTS
Type: E:PVVALST Gravity Input Value Status—Indicates the status of the gravity input value.
Lock: View
Default: Normal
PtRes: HPM
Range: 0-Bad (Value is bad and replaced with NaN)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

HPM Parameter Reference Dictionary G-3 8/97


HPM Parameter Reference Dictionary G-4 8/97
HIGHAL

-H-

HIGHAL (AnalgIn, RegCtl, RegPV)


Type: E:ALMTYPE Highest Alarm Detected—Indicates the highest alarm currently detected at the
Lock: View data point. This parameter is used by the system to ensure that when two or
Default: NoAlarm more different types of alarms occur on a point at the same time, the most
PtRes: NIM important or highest level alarm appears on the point's Group, Detail, and
Alarm Summary displays. For example, if both the PV High High and PV
High alarm priorities are set to Emergency, and both are in alarm, HIGHAL
contains the PVHH value.
Range: NoAlarm (No alarm exists—lowest level alarm)
AdvDev (Advisory Deviation)
DevHi (Deviation High)
DevLo (Deviation Low)
PVRocN (PV Rate Of Change Negative)
PVRocP (PV Rate Of Change Positive)
PVHi (PV High)
PVHH (PV High High)
PVLo (PV Low)
PVLL (PV Low Low)
BadCtl (Bad Control)
BadPV (Bad PV—highest level alarm)
BOC (Bad Output alarm)

HIGHAL (DevCtl, DigComp, DigIn, Flag, Logic)


Type: E:ALMTYPE Highest Alarm Detected—Indicates the highest alarm currently detected at the
Lock: View data point. This parameter is used by the system to ensure that when two or
Default: NoAlarm more different types of alarms occur on a point at the same time, the most
PtRes: NIM important or highest level alarm appears on the point's Group, Detail, and
Alarm Summary displays.
Range: NoAlarm (No alarm has been detected)
OffNorm (Current PV state is not the configured PVNORMAL state. For a flag point, the
off-normal state (STATE1) is the alarmed state.)
UnCEvt (Uncertain event was detected. Does not apply to a flag point.)
CmdDis (Command Disagree; field device did not respond to commanded output state. Does not
apply to a flag point.)
BadPV (PV is bad)
C1 - C4ALM (1 to 4 custom logic alarms)
Chngofst (State has changed)
Cmdfail (PV failed to change after OP changed)
SVHI (SECVAR>SVHITP)
SVHH (SECVAR>SVHHTP)
BadSV (SECVAR is Bad)
OVRDI2 (Override Interlock I2)
OVRDI1 (Override Interlock I1)
OVRDI0 (Override Interlock I0)
OVRDSI0 (Safety Override Interlock)
BadCtl (Bad Control) (DevCtl and DigComp only)

HPM Parameter Reference Dictionary H-1 8/97


HIGHALPR

HIGHALPR (AnalgIn, RegCtl, RegPV)


Type: E:ALPRIOR Highest Level Alarm's Priority—Defines the priority of the highest alarm
Lock: View currently detected at the data point. Associated with HIGHAL.
Default: NoAction
PtRes: NIM
Range: Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

HISVPEAK (DevCtl)
Type: Real Highest Peak SECVAR Value—The highest peak value of the SECVAR
Lock: View parameter since the most recent reset of maintenance statistics.
Default: 0.0
PtRes: HPM
Range: ≥0

HLCALIB(1)–(168)
Type: Logical HLAI in Calibration Flag—Shows which HLAIs are presently in calibration
Lock: Eng/Pb
Default:
PtRes: HPM
Range: Off - Calibration is not in progress
On - Calibration is in progress

HOLDCMD (RampSoak)
Type: Logical Hold Command Flag—If On, allows users to hold the ramp or soak segment at
Lock: Prog its current position to customize the guaranteed ramp and soak function.
Default: Off
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary H-2 8/97


HOUR

HOUR (HPM Box)


Type: Integer Current Hour—The value of the LCN time in the HPM.
Lock: View
Default: N/A
PtRes: HPM
Range: 0 to 23

Only full array access is supported.

HWYCTLST (UCN)
Type: E:$NODFSTA UCN Network Functional State
Lock: Supr
Default: Basic
PtRes: NIM
Range: Full (All LCN devices can do read/write operations to this UCN)
Basic (AM and CM cannot write to this UCN)

HPM Parameter Reference Dictionary H-3 8/97


HPM Parameter Reference Dictionary H-4 8/97
I0–2

-I-

I0–2 (DevCtl, DigComp)


Type: Logical Override Interlocks for Output States 0-2—Override interlocks force the
Lock: Engr commanded output to a specific state regardless of the condition of the
Default: Off permissive interlocks or the previous point state. The operator and user program
PtRes: HPM cannot change the output state when any override interlock is On. An override
interlock is provided for each of the three states. Refer to the HPM Control
Functions and Algorithms manual for a detailed description.
Range: Off (Override interlock has no effect on the point state)
On (Override interlock sets the point to the respective state)

Helpful Hint: 1. When I0 is On, forces the output to STATE0, regardless of the permissives
or any other overrides.
2. When I1 is On and I0 is Off, forces the output to a STATE1, regardless
of the permissives or any other overrides.
3. When I2 is On and I0 and I1 are both Off, forces the output to STATE2
regardless of the permissives or any other overrides.
4. I0-I2 change by the engineer, requires PTEXECST = InActive
or PNTSTATE = Idle for each interlock.

I0CONF (DigComp,DevCtl)
Type: Logical Override Interlock 0 Alarm Confirmation Flag—Indicates that the Override
Lock: Oper Interlock 0 Alarm needs to be confirmed.
Default: Off
PtRes: HPM
Range: N/A

I0DESC-I2DESC (DigComp)
Type: String_8 I0-I2 Alarm Descriptor—The override Interlock for States 0, 1, or 2 indicating
Lock: Engr which text should be copied into the OVRDDESC parameter when an override
Default: Blank alarm occurs. The text appears in the Alarm Display and can be configured to
PtRes: HPM indicate the cause for the alarm.

Range: 8 Character String

I1CONF (DigComp,DevCtl)
Type: Logical Override Interlock 1 Alarm Confirmation Flag—Indicates that the Override
Lock: Oper Interlock 1 Alarm needs to be confirmed.
Default: Off
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary I-1 8/97


I2CONF

I2CONF (DigComp,DevCtl)
Type: Logical Override Interlock 2 Alarm Confirmation Flag—Indicates that the Override
Lock: Oper Interlock 2 Alarm needs to be confirmed.
Default: Off
PtRes: HPM
Range: N/A

IN0–12 (GenLin)
Type: Real Input Coordinates 0–12—Define the input value at the respective coordinate.
Lock: Supr IN0 <IN1 <IN2 ......., <IN12
Default: NaN
PtRes: HPM
Range: > prev. coord.
< next coord.

INITMAN
Type: Logical Initialization Manual Flag—When On, indicates that this point is in
Lock: View Initialization Manual. The mode of the point does not change; however, INIT
Default: Off appears on the point’s detail or group display to indicate that the point is in
PtRes: HPM Initialization Manual. While the point is in Initialization Manual, an operator,
supervisor, or engineer cannot change the point’s output. The output is
indisposable because initialization is being requested from downstream. Upon
leaving Initialization Manual, the point’s output is initialized from the point’s
secondary as determined by the point’s output connection.

Range: Off (Mode ≠ Initialization Manual)


On (Mode = Initialization Manual)

Helpful Hint: OP changes with Operator, Supervisor, or Engineer access level, requires MODE
= Man and INITMAN = Off. SP changes with Operator, Supervisor, or Engineer access level,
for non-PID algorithms requires MODE = Auto and INITMAN = Off, while for PID algorithms
requires that MODE = Auto, and also that INITMAN = Off and PTEXECST = Active if
PVTRACK = Track.

INITMAN (DigComp, DevCtl, RegCtl)


Type: Logical Initialization Manual Flag—On, indicates that an output is storing to a DO
Lock: View point that has its INITREQ flag set and the point is forced into initialization.
Default: On When the DO point becomes available, the initialization state is cleared.
PtRes: HPM
Range: Off (Mode ≠ Initialization Manual)
On (Mode = Initialization Manual)

HPM Parameter Reference Dictionary I-2 8/97


INITREQ

INITREQ(1)–(4) (RegCtl)
Type: Logical Initialization Request Flags (1–4)—Indicates whether an initialization request has
Lock: View been made. Each flag represents a request to the primary point pushing to the
Default: Off corresponding input to be initialized as follows:
PtRes: HPM Flag 1: SP or X1
Flag 2: RATIO or X2
Flag 3: X3
Flag 4: X4
Range: Off (No initialization request)
On (Initialization request)

INITREQ (Array)
Type: Logical Initialization Request Flag—Indicates whether a Serial Interface-connected device
Lock: View can be written to, where OFF = yes, or ON = no. The flag is always OFF if
EXTDATA = None.
Default: On when EXTDATA = IO_FL, IO_NN, or IO_STR
Off when EXTDATA = None
PtRes: HPM
Range: Off (EXTDATA=None, or Serial interface-connected device can be written to)
On (Serial interface-connected device cannot be written to)

INITREQ (AO, DO)


Type: Logical Initialization Request Flag—When On, indicates that control strategies in the
Lock: View HPM cannot manipulate the output to the field. It is set to ON when:
Default: On
PtRes: HPM • the PWM type output is configured
• the point is inactive
• the module is idle
• there is a soft failure such that the channel is not working
• The output is connected to standby-manual device

Range: Off (No initialization request)


On (Initialization request)

INITREQ(0)–(2) (DigComp, DevCtl)


Type: Logical Initialization Request Flag—When On, indicates that CL programs or logic can
Lock: View not change the output to State(i), where i = 0, 1, or 2.
Default: On
PtRes: HPM

Range: Off
On

INITVAL
Type: Real Initialization Value—Indicates the value to which the primary point is to be
Lock: View initialized.
Default: N/A
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary I-3 8/97


INPTDIR

STATE 1
BOX
(Upper)
STATETXT (1)

STATE 0
BOX
(Lower)
STATETXT (0)

PVRAW INPTDIR = INPTDIR =


State Direct Reverse

PV = ON. PV = OFF.
State 1 Box is State 0 Box is
ON lighted. lighted.
State 0 Box is State 1 Box is
extinguished. extinguished.

PV = OFF. PV = ON.
State 0 Box is State 1 Box is
OFF lighted. lighted.
State 1 Box is State 0 Box is
extinguished. extinguished.

Figure I -1 — INPTDIR vs. Display Indicators 2065

INPTDIR (DigIn)
Type: E:POLARITY Digital Input Direction—Defines the contact conditions required to light the
Lock: Eng/PB upper or lower boxes on a Group or Detail Display for a digital input point.
Default: Direct See Figure I-1.
PtRes: HPM

Range: 0-Direct
State 0 (lower) box lighted =>PVRAW = Off
State 1 (upper) box lighted =>PVRAW = On

1-Reverse
State 0 (lower) box lighted =>PVRAW = On
State 1 (upper) box lighted =>PVRAW = Off

HPM Parameter Reference Dictionary I-4 8/97


IOLASTS

IOLASTS (HPM Box)


Type: Logical I/O Link Cable A Status
Lock: View
Default: Off
PtRes: HPM
Range: Off (I/O Link cable A not in error)
On (I/O Link cable A in error)

IOLBSTS (HPM Box)


Type: Logical I/O Link Cable B Status
Lock: View
Default: Off
PtRes: HPM
Range: Off (I/O Link cable B not in error)
On (I/O Link cable B in error)

IOLCHAER (HPM Box)


Type: Integer I/O Link Channel A Error Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

IOLCHASL (HPM Box)


Type: Integer I/O Link Channel A Silence Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

IOLCHBER (HPM Box)


Type: Integer I/O Link Channel B Error Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

IOLCHBSL (HPM Box)


Type: Integer I/O Link Channel B Silence Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

HPM Parameter Reference Dictionary I-5 8/97


IOLCHERT

IOLCHERT (HPM Box)


Type: Integer I/O Link Channel Error Threshold—Defines the acceptable number of I/O Link
Lock: EngOnly channel errors per minute before disabling the periodic I/O Link channel swap.
Default: 10
PtRes: HPM
Range: >0

IOLCMD (HPM Box)


Type: E:$IOLCMD I/O Link Command
Lock: EngOnly
Default: None
PtRes: HPM
Range: 0-None (No effect)
1-SelChnA (Select I/O Link Channel A)
2-SelChnB (Select I/O Link Channel B)
3-EnbPerSw (Enable periodic swapping of IOL cables)
4-DisPerSw (Disable periodic swapping of IOL cables)
5-RsIoLCom (Reset IOL communication error count to 0)

IOLHWREV (HPM Box)


Type: String_2 HPMM I/O Link Interface Processor Card Hardware Revision—
Lock: View
Default: Blank
PtRes: HPM
Range:

IOLPERSW (HPM Box)


Type: E:ENBLSTAT I/O Link Periodic Cable Swap
Lock: View
Default: N/A
PtRes: HPM
Range: 0-Disable (Swapping of I/O Link cables A & B is disabled)
1-Enable (Swapping of I/O Link cables A & B is enabled)

IOLPSERR (ProcMod)
Type: E:Pastatus I/O Link Poststore Failure Option — Contains the IOL Poststore PA status
Lock: View failure code, or null.
Default: NoError
PtRes: HPM

Helpful Hint: This parameter sould be used with IOLPSOPT.

Range: NoError

HPM Parameter Reference Dictionary I-6 8/97


IOLPSOPT

IOLPSOPT (ProcMod)
Type: E:$IOLPSOPT I/O Link Poststore Failure Option —
Lock: Engr
Default: Fail
PtRes: HPM

Helpful Hint: The program should check the value of IOLPSERR if this parameter is
continue.

Range: Fail (program fails on a bad IOL store)


Continue (program continues on a bad IOL store)

IOLREV (HPM Box)


Type: Integer HPMM I/O Link Software Revision—
Lock: View
Default: Blank
PtRes: HPM

Range:

IOLVERS (HPM Box)


Type: Integer HPMM I/O Link Software Version—
Lock: View
Default: Blank
PtRes: HPM
Range:

IOMACTYP(1)–(168)
Type: E:$PMMDTY IOP Actual Type — Actual type of IOP at module address.
Lock: View This should match the configured type.
Default: None
PtRes: HPM
Range: None (Not Configured)
LLAI (Low Level Analog Input)
HLAI (High Level Analog Input)
DI (Digital Input)
DO (Digital Output)
AO (Analog Output
HPMM (HPM Module)
LLMUX (Low Level Analog Input Multiplexer) Also includes RHMUX (Remote Hardened
Analog Multiplexer)
STIM (Smart Transmitter Interface Module)
PI (Pulse Input)

HPM Parameter Reference Dictionary I-7 8/97


IOMCARD

IOMCARD(1)–(168) (HPM Box)


Type: Integer I/O module card position for the acting primary/secondary
Lock: View (used for diagnostic displays).
Default: N/A nn = 1 - 40 correspond to card positions of the 40 acting primaries
PtRes: HPM nn = 129 - 168 correspond to card positions of the 40 acting secondaries
Range: 1-15

IOMCARDA(1)–(40) (HPM Box)


Type: Integer I/O module A card position. 1–40 specifies one of the 40 logical I/O
Lock: PtBld modules. The corresponding IOP must be connected to FTA connector
Default: 0 in IOP database; A. Applies to the primary IOP only.
per PKGOPT on GDF
PtRes: HPM
Range: 0 - 15 (0 specifies Not Connected)

IOMCARDB(1)–(40) (HPM Box)


Type: Integer I/O module B card position. 1-40 specifies one of the 40 logical I/O
Lock: PtBld modules. The corresponding IOP must be connected to FTA connector
Default: 0 in IOP database; B. Applies to primary IOP only.
none on GDF
PtRes: HPM
Range: 0 - 15 (0 specifies Not Connected)

IOMCHAER(1)–(168)
Type: Integer IOP Channel A Error Count—for a specific IOP
Lock: View
Default: N/A
PtRes: HPM
Range: 0 - 255

IOMCHASL(1)–(168)
Type: Integer IOP Channel A Silence Count—for a specific IOP
Lock: View
Default: N/A
PtRes: HPM
Range: 0 - 255

IOMCHBER(1)–(168)
Type: Integer IOP Channel B Error Count—for a specific IOP
Lock: View
Default: N/A
PtRes: HPM
Range: 0 - 255

HPM Parameter Reference Dictionary I-8 8/97


IOMCHBSL

IOMCHBSL(1)–(168)
Type: Integer IOP Channel B Silence Count—for a specific IOP
Lock: View
Default: N/A
PtRes: HPM
Range: 0 - 255

IOMCMD (HPM Box)


Type: E:$IOMCMD IOP Module Command—Indicates IO module state, or whether to swap
Lock: Oper redundant pairs.
Default: None
PtRes: HPM
Range: None
Run
Idle
Swap

IOMCOMER(1)–(168)
Type: E$:IOMCOMMIOP IOP Communications Error Status—for a specific IOP
Lock: View
Default: N/A
PtRes: HPM

Range: None - No error


Invalert - Invalid alert; message bit problem
Invdest - Invalid destination
Invchcnt - Invalid character count; message corrupted
Invsourc - Invalid source
Invcmd - Invalid command
Checksum - Checksum error
No_resp - No response
Chtimout - Channel time out
Msgovrun- Message overrun
Gaperror - Gap error; message gap too long
Lpbckerr - Loopback error
Nth_0 - Next token holder equals zero
Tknrecov - Token recovery in progress
Rplbufov - Reply buffer overflow

IOMFILE(1)–(168) (HPM Box)


Type: Integer I/O Module File Position for the Acting Primary/Secondary
Lock: View (used for diagnostic displays).
Default: N/A nn = 1 - 40 are file positions of the 40 acting primaries.
PtRes: HPM nn = 129 - 168 are file positions of the 40 acting secondaries.

Range: 0 - 8 (0 specifies Not Connected)

HPM Parameter Reference Dictionary I-9 8/97


IOMFILEA

IOMFILEA(1)–(40) (HPM Box)


Type: Integer I/O Module A File Position—1-40 specifies one of the 40 logical I/O
Lock: PtBld modules. The corresponding IOP must be connected to FTA connector
Default: 0 in IOP data base; A. Applies to the primary IOP only.
per PKGOPT on GDF
PtRes: HPM
Range: 0 - 8 (0 specifies Not Connected)

IOMFILEB(1)–(40) (HPM Box)


Type: Integer I/O Module B File Position—1-40 specifies one of the 40 logical I/O
Lock: PtBld modules. The corresponding IOP must be connected to FTA connector
Default: 0 in IOP data base; B. Applies to the primary IOP only.
none on GDF
PtRes: HPM
Range: 0 - 8 (0 specifies Not Connected)

IOMFWREV(1)–(168)
Type: Ascii_2 IOP Card Firmware Revision Status
Lock: View (This is not the same as the external letter code on the card)
Default: N/A
PtRes: HPM
Range: X.Y X = Version, Y = Revision
(For Release 300, X = 3)

IOMHWREV(1)–(168)
Type: Ascii_2 IOP Card Hardware Revision Status
Lock: View The status of R300 boards appears as $2x, the status of R210
Default: N/A appears as $0x, where x is the version (0=A, 1=B, 2=C, etc.)
PtRes: HPM
Range: Hexadecimal characters 00–FF

HPM Parameter Reference Dictionary I-10 8/97


IOMLHFST

IOMLHFST(1)–(168)
Type: E:$IOMHF Input/Output Processor Last Hard Fail Status—Refer to the HPM Service
Lock: View Manual for a detailed description and the recommended corrective action.
Default: N/A
PtRes: HPM
Range: 0-Unknown (Unknown Status)
1-PowerDwn (This IOP Powered Down)
2-InvPrgEx (Invalid Program Execution)
3-EpromErr (EPROM Checksum Error)
4-RamCntEr (RAM Contents Error)
5-RamAdrEr (RAM Addressing Error)
6-DpaError (Device Physical Address Error)
7-DsaError (Device Soft Address Error)
8-RxBufOfl (I/O-Link Receive Buffer Overflow)
9-IOLJaber (I/O-Link Jabber Circuit Failure)
11-BadPgJmp (Illegal Value of Case Control)
12-AdCIncmp (A-to-D Conversion Incomplete)
13-AdOutOvf (A-to-D Output Value Overflow)
14-AdOutUdf (A-to-D Output is less than Zero)
15-AdCCalEr (A-to-D Calibration is incorrect)
16-BadDcLtc (Bad DC LTC)
17-Dmt_Tmot (Dead Man Timer Timeout)
18-MLtOutFl (Multiple Output Failures)
20-BadDaRng (Bad D-to-A Range)
21-MstrTmot (Master 68 k Timeout)

IOMNUM
Type: Integer IOP Number—IOMNUM specifies the IOP on the I/O Link that this point
Lock: PtBld references for its process data.
Default: N/A
PtRes: HPM
Range: 1 to 40

IOMOPER(1)–(168) (HPM Box, IOP)


Type: E:$PRIMSEC Input/Output Processor In Operation
Lock: View
Default: N/A
PtRes: HPM
Range: 0-Primary (Primary IOP is operating)
1- Secondry (Secondary IOP is operating)

HPM Parameter Reference Dictionary I-11 8/97


IOMREALT

IOMREALT (HPM Box)


Type: E:$PMMDTY Actual Input/Output Processor Type
Lock: View
Default: None
PtRes: HPM
Range: 0-None (Not Configured)
1-LLAI
2-HLAI (High-Level Analog Input)
3-DI (Digital Input)
4-DO (Digital Output)
5-AO (Analog Output)
7-LLMUX (Low-Level Analog Input Multiplexer) also includes RHMUX (Remote Hardened
Analog Multiplexer)
14-STIM (Smart Transmitter Interface Module)
17-PI (Pulse Input)

IOMRECHN(1)–(168) (HPM Box)


Type: E:$RECCHN IOP Receive Channel
Lock: View
Default: N/A
PtRes: HPM
Range: ChannelA
ChannelB

IOMSEVER(1)–(168) (HPM Box)


Type: E:$SEVERTY Error Severity Based on Input/Output Processor State
Lock: View nn = 1 - 40 specifies the severity of 1 of the 40 acting primaries
Default: nn = 129 - 168 specifies the severity of 1 of the 40 acting secondaries
PtRes: HPM
Range: Ok (I/O Processor has no errors and is OK)
Fail (I/O Processor has failed)
Inform (I/O Processor should be calibrated soon)
Warning (I/O Processor is on the verge of failing)

HPM Parameter Reference Dictionary I-12 8/97


IOMSTS

IOMSTS(1)–(168) (HPM Box)


Type: E:$IOMSTS Input/Output Module State
Lock: View nn = 1 - 40 specifies the status of 1 of the 40 acting primaries
Default: N/A nn = 129 - 168 specifies the status of 1 of the 40 acting secondaries
PtRes: HPM
Range: 0-PowerOn (Transient state when power is turned on)
1-Idle (In the Idle State)
2-OK (Running)
3-NoResp (No Response)
4-IdleSF (In the Idle State and has a Soft Failure)
5-SoftFail (Running and has a Soft Failure)
6-CommErr (Communication Error)
7-ConfgMis (Configuration Mismatch)
8-NotConfg (This IOP is Not Configured)
9-NonExist (This IOP does Not Exist)

UnAvail (Transient state during which status for this IOP is unavailable)

IOMTYPE(1)–(168) (IOP)
Type: E:$PMMDTY Input/Output Processor Type
Lock: View
Default: None
PtRes: HPM

Range: 0-None (Not Configured)


1-LLAI (Low Level Analog Input)
2-HLAI (High Level Analog Input, 16 slot)
3-DI (Digital Input, 32 slot)
4-DO (Digital Output, 32 slot)
5-AO (Analog Output, 8 slot)
7-LLMUX (Low Level Analog Input Multiplexer) also includes RHMUX (Remote Hardened
Analog Multiplexer)
10-SI (Serial Interface)
14-STIM (Smart Transmitter Interface Module)
16DISOE (Digital Input, Sequence of Events)
17-PI (Pulse Input)
24-AO16 (Analog Output, 16 slot)
25DO32 (Digital Output, 32 slot)

HPM Parameter Reference Dictionary I-13 8/97


IOMTYPE

IOMTYPE (HPM Box)


Type: E:$PMMDTY Configured Input/Output Processor Type
Lock: PtBld
Default: NotConfg
PtRes: HPM
Range: 0-NotConfg (Not Configured)
1-LLAI (Low-Level Analog Input)
2-HLAI (High-Level Analog Input)
3-DI (Digital Input)
4-DO (Digital Output)
5-AO (Analog Output)
7-LLMUX (Low Level Analog Input Multiplexer) also includes RHMUX (Remote Hardened
Analog Multiplexer)
14-STIM (Smart Transmitter Interface Module)
17-PI (Pulse Input)
-DISOE (Digital Input, Sequence of Events)
-SI (Serial Interface)
-AO-16 (Analog Output)
-DO-32 (Digital Output)

IONTOKEN (HPM Box)


Type: Integer IOP Next Token Holder
Lock: View
Default: N/A
PtRes: HPM

NOTE

This parameter is available to the nodes on the LCN, but cannot be accessed on the UCN,
either by HPM/CL programs or print connections.

Range: 0, or 128 to 255

IOPDESC(1 - 40)
Type: String_8 IOP Description—Provides an 8-character description of the IOP.
Lock: View
Default: Spaces
PtRes: HPM

Helpful Hint: An 8-character string is read from the IOP's EPROM and stored in the HPMM.
The text string appears on the IOP Detail Display. Even if the IOP fails, an operator can
identify the IOP/FTA for maintenance. Not all IOPs have this feature yet.

Range: 8 characters

HPM Parameter Reference Dictionary I-14 8/97


IOPIDAY

IOPIDAY (HPM Box)


Type: Integer HPMM I/O Link Personality Creation Date- Day
Lock: View
Default: 0
PtRes: HPM

Range:

IOPIMON (HPM Box)


Type: Integer HPMM I/O Link Personality Creation Date- Month
Lock: View
Default: 0
PtRes: HPM

Range: N/A

IOPIYEAR (HPM Box)


Type: Integer HPMM I/O Link Personality Creation Date- Year
Lock: View
Default: 0
PtRes: HPM
Range: N/A

IOPNUM (Array)
Type: Integer Serial Interface IOP Module Number—Defines the module number of the serial
Lock: PtBld interface IOP.
Default: N/A
PtRes: HPM
Range: 1 to 127

IOPSTR1(1)–(40) (HPM Box)


Type: String_64 IOP String for FTA #1—Contains user-defined string data shown in the Box
Lock: View Detail display such as the FTA application name, its revision number, and date.
Default: Spaces NN = 1-40 specifies the Serial Interface IOP module number.
PtRes: SI
Range: N/A

IOPSTR2 (1)–(40) (HPM Box)


Type: String_64 IOP String for FTA #2—Contains user-defined string data shown in the Box
Lock: View Detail display such as the FTA application name, its revision number, and date.
Default: Spaces NN = 1-40 specifies the Serial Interface IOP module number.
PtRes: SI
Range: N/A

HPM Parameter Reference Dictionary I-15 8/97


IORECCHN

IORECCHN (HPM Box)


Type: E:$RECCHN I/O Link Receive Cable—The cable the I/O module is currently listening on.
Lock: PtBld
Default: None
PtRes: HPM
Range: A (I/O module is listening on Cable A)
B (I/O module is listening on Cable B)

IOREDOPT(1)–(40) (HPM Box)


Type: E:$REDOPT IOP Redundancy Option—Indicates if an IOP is configured for redundancy
Lock: PtBld
Default: NonRedun
PtRes: HPM
Range: 0-Redun
1-NonRedun

IOSTKNDR
Type: Integer IOP Token Drop Count
Lock: View
Default: N/A
PtRes: HPM
Range: 0 to 32767

IOSCNCYC(1 – 40)
Type: Integer Control base cycle number—
Lock: PtBld The index to this parameter specifies the IOP number for which this information
Default: 0.0 is being accessed.
PtRes: HPM
Range: 0 - 16

IOSCNPER(1 – 40) (AnalgIn)


Type: Real IO data Scan Period— the I/O data scan period in seconds for IO processors that
Lock: PtBld support Analong Input point types. The index to this parameter specifies the
Default: 0.0 IOP number for which this information is being accessed.
PtRes: HPM
Range: 0.0, 0.0625, 0.125, 0.25, 0.5, 1.0

HPM Parameter Reference Dictionary I-16 8/97


K

-K-

K (AutoMan)
Type: Real Gain Constant for X2 Input—Refer to the HPM Control Functions and
Lock: Supr Algorithms manual for a detailed description.
Default: 1.0
PtRes: HPM
Range: N/A

K (MulDiv, RegCtl Summer)


Type: Real Overall Gain—
Lock: Supr
Default: 1.0
PtRes: HPM
Range:

K (Pid)
Type: Real Overall Gain—Value of K depends on the chosen gain option. Refer to the
Lock: Supr HPM Control Functions and Algorithms manual for a detailed description.
Default: 1.0
PtRes: HPM
Range: 0.0 to 240.0

K (PosProp)
Type: Real Gain Constant
Lock: Supr
Default: 1.0
PtRes: HPM
Range: 0.0 to 10.0

K1 (PidErfb)
Type: Real External Reset Feedback Gain
Lock: Supr
Default: 0.0
PtRes: HPM
Range: 0.0 to 1.0

K1 (PIDPosPr)
Type: Real Gain Constant
Lock: Supr
Default: 1.0
PtRes: HPM
Range: 0.0 to 10.0

HPM Parameter Reference Dictionary K-1 8/97


K1-K2

K1–K2 (RatioCtl)
Type: Real K1 = Ratio Scale Factor; K2 = Scale Factor for X2 Input—When used in
Lock: Supr conjunction with the Calcultr algorithm, K1 must be equal to C1, and K2 must
Default: 1.0 be equal to C2.
PtRes: HPM
Range: N/A

K1–K3 (MulDiv)
Type: Real Gain Constants for X1–X3 Inputs
Lock: Supr
Default: 1.0
PtRes: HPM
Range:

K1–K4 (RegCtl Summer)


Type: Real Gain Constants for X1–X4 Inputs
Lock: Supr
Default: 1.0
PtRes: HPM
Range:

K1–K4 (IncrSum)
Type: Real Gain Constants for X1–X4 Inputs
Lock: Supr
Default: 1.0
PtRes: HPM
Range: > 0.0

KEXT(Pid)
Type: Real External Gain Modifier—Defines the external gain modification factor. It can be
Lock: Prog entered by a user-written program, or it can be an input from another data point.
Default: 1.0
PtRes: HPM
Range: 0.0 to 240.0

KEYWORD
Type: String_8 Keyword Descriptor— An eight-character descriptor that is used to describe an
Lock: PtBld important aspect of this particular data point. For example, in Figure N-1 (see
Default: Blank NAME) the keyword for the data point is REFLUX.
PtRes: NIM
Range: Alphabetics A-Z (upper case only).
Numerics 0-9 (an all numeric keyword is not allowed).
Underscore (_) cannot be used as the first character or the last character in a keyword.
Consecutive underscores are not allowed. Do not use quote marks (").

HPM Parameter Reference Dictionary K-2 8/97


KFF

KFF (PidFf)
Type: Real Gain for Feed Forward Input—Scale factor which is used in converting the FF
Lock: Supr input value to percent.
Default: 1.0
PtRes: HPM
Range: > 0.0 to < 1.0

KGAP (Pid)
Type: Real Gap Gain Factor—Defines the gain-modification factor.
Lock: Supr
Default: 1.0
PtRes: HPM
Range: 00 to 1.0

KLIN (Pid)
Type: Real Linear Gain Factor—Defines the linear gain in percent per percent.
Lock: Supr
Default: 1.0
PtRes: HPM
Range: 0.0 to 240.0

KNL (Pid)
Type: Real Nonlinear Gain Modifier—Indicates the calculated value of the nonlinear gain
Lock: View modifier.
Default: N/A
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary K-3 8/97


HPM Parameter Reference Dictionary K-4 8/97
L(1)–(12)

-L-

L(1)–(12) (DevCtl, Logic)


Type: Logical, Real Value of the External Input—L(1)–L(12) are the 12 inputs to a logic slot fetched
Lock: View with input connections from other points. Each input can be a Boolean, an
Default: N/A Integer, or a Real number. Integer input values are converted to real numbers
PtRes: HPM before being stored into the database.
Range: Real

Helpful Hint: L, if accessed from the LCN, must be accessed as a Logical data type.

LCNRECHN (HPM Box)


Type: E:$RECCHN LCN Receive Channel—Indicates the LCN channel to which the NIM is
Lock: View listening.
Default: ChanneLA
PtRes: HPM
Range: 0-ChanneLA (NIM is listening to LCN channel A)
1-ChanneLB (NIM is listening to LCN channel B)

LDNGNODE (HPM Box)


Type: Integer UCN Node Performing Personality Image Load to This Node
Lock: View
Default:
PtRes: HPM
Range:

LIBADOPT (DevCtl, Logic)


Type: E:$LIBADOP Logic Bad Input Handling Option—If a Boolean input is not successfully
Lock: PtBld fetched for an input connection to the logic slot, its value is defaulted to one
Default: Hold of the values (Off, On, Hold) selected through this parameter. Refer to the
PtRes: HPM HPM Control Functions and Algorithms manual for a detailed description.
Range: 0-On (On state is substituted for bad input)
1-Off (Off state is substituted for bad input)
2-Hold (Last good value is substituted for bad input)

LIBRYNUM
Type: Integer NIM Library Number—Specifies the number of the NIM Library being
Lock: PtBld configured. For Parameter Entry Display use only.
Default: 1
PtRes: NIM
Range: 1-3

HPM Parameter Reference Dictionary L-1 8/97


LIBRYTXT

LIBRYTXT(1)–(1000)
Type: String_8 NIM Library Text
Lock: PtBld
Default: N/A
PtRes: NIM
Range: N/A

LIDESC(1)–(12) (DevCtl)
Type: String_8 Input Descriptor—External input descriptors.
in an Array
(1..12)
Lock: Engr
Default: Blank
PtRes: HPM
Range: 8 Character String

LINEPERD (1)–(168)
Type: Real Line Period in Microseconds
Lock: View
Default: N/A
PtRes: HPM
Range: 15616.0 to 21759.0

HPM Parameter Reference Dictionary L-2 8/97


LISRC(1)_(12)

LISRC(1)–(12) (DevCtl, Logic)


Type: Universal Logic Input Connection Source—Define the parameters whose current values are
Ent.Prm to be supplied to one or more of up-to-12 logic slot or Device Control inputs.
Lock: PtBld The parameters can be specified using the "Tagname.Parameter" format or the
Default: null.null hardware reference address format. Refer to the HPM Control Functions and
PtRes: HPM Algorithms manual for a detailed description.
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

Some possible input-connection sources are


a. “AnalgIn slot Tagname.PV”
b."DigIn slot Tagname.PVFL"
c."Logic slot Tagname.SO(nn)" where nn = 1–24
d."Logic slot Tagname.Fl(nn)" where nn = 1–12
e.”Logic slot Tagname.NN(nn)” where nn = 1-8
f."ProcMod slot Tagname.Fl(nnn)" where nnn = 1–127
g.”ProcMod slot Tagname.NN(nn)” where nn = 1–80
h.”RegCtl slot Tagname.PV”
i.”RegPV slot Tagname.PV”
j."Box Flag slot Tagname.PVFL
k.”Box Numerics slot Tagname.NN” where nnnnn = 1-16,384
l."!Box.FL(nnnn)" for a box flag that resides in the same box where nnnnn = 1–16,384
m."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the NIM UCN address, xx is the HPM box number, and
nnnn = 1–4095 (data access limit)

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DI (Digital Input)
mm is the IOP Card number (1–40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

LMREV (DevCtl)
Type: E:POLARITY Local Manual Polarity—Indicates whether point processing inverts the local
Lock: Engr/PB manual input value.
Default: Direct
PtRes: HPM
Range: Direct (Value is not inverted)
Reverse (Value is inverted)

HPM Parameter Reference Dictionary L-3 8/97


LMSRC

LMSRC (DevCtl, PosProp, PIDPosPr)


Type: Universal Local Manual Source—The input connection for the local manual input.
Ent.Prm Only inputs with logical data types are valid.
Lock: PtBld
Default: Null.null
PtRes: HPM
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

Some possible input-connection sources are


a."DigIn slot Tagname.PVFL"
b."Logic slot Tagname.SO(nn)" where nn = 1–24
c."Logic slot Tagname.Fl(nn)" where nn = 1–12
d."ProcMod slot Tagname.Fl(nnn)" where nnn = 1–127
e."Box Flag slot Tagname.PVFL
f."!Box.FL(nnnn)" for a box flag that resides in the same box where nnnn = 1–16,384
g."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the NIM UCN address, xx is the HPM box number, and
nnnn = 1–4095 (data access limit)

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DI (Digital Input)
mm is the IOP Card number (1–40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

LOADFAIL
Type: Integer Node Load Failure Information
Lock: View
Default:
PtRes: HPM
Range:

HPM Parameter Reference Dictionary L-4 8/97


LOADFLAG

LOADFLAG
Type: String_2 Load Flag
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal characters 00 to FF

LOADPCKT
Type: Integer Current Personality Image Packet Being Loaded to This Node
Lock: View
Default:
PtRes: HPM
Range:

LOADSCOP (NIM)
Type: E:$LOADSCP Load Scope—Defines the scope of the point-build procedure for NIM and
Lock: PtBld HPM configuration. The point information is loaded to both the NIM and
Default: NIMAndPm HPM or to the NIM only. A value of NIMONLY is typically used to
PtRes: NIM configure points into the NIM only during installation of a new system
without HPMs.

NOTE

When points are built to a NIM and the NIM is restarted with no database, the points need
to be reloaded from checkpoint or the points must be reconfigured. If the database is to
be reconfigured, the HPMM must be in Idle, and the point execution state must be Inactive.
This allows the point build operation to override the database that already exists there.

NOTE

To delete active entities from the HPM database, the point must be put to the inactive state.
An alternative is to delete the entity in the NIM only by changing the LOADSCOP parameter
for the NIM to NimOnly and deleting the point. Be sure to restore LOADSCOP to NimAndPM
after deleting points.

Range: NimOnly (Configured data is to be loaded into the NIM only)


NimAndPm (Configured data is to be loaded into the NIM and HPM)

HPM Parameter Reference Dictionary L-5 8/97


LOADSTAT

LOADSTAT
Type: E:LOADSTAT Load Status
Lock: View
Default:
PtRes: HPM
Range: Notload
Loaded
Loading
Unlding

LOCALMAN (AnalgOut, RegCtl)


Type: Logical Local Manual Flag—Indicates whether the associated hardware output of this
Lock: View point is being controlled by a manually-operated analog display.
Default: Off
PtRes: HPM
Range: Off (Output is not being controlled by an Analog Display)
On (Output is being controlled by an Analog Display)

LOCALMAN (DigComp, DevCtl)


Type: Logical Local Manual Flag—When On, indicates that the output(s) is being locally
Lock: Prog controlled and not by the HPM. When this flag is on, it usually indicates that
Default: Off the "hand/off/auto" switch is not in the "auto" position.
PtRes: HPM
Range: Off
On

LOCPRIM(1—4)
Type: Local Primary—Returns the tag name of a primary point in the same HPM that
Lock: View is storing to this point’s parameters.
Default:
PtRes: HPM The parameter index indicates the parameter being pushed to by the primary as
follows, depending on the algorithm configured in the Regulatory Control point:
1 = SP or X1
2 = Ratio or X2
3 = X3
4 = X4
Range:

Helpful Hint: LOCPRIM returns a null entitty ID if the connection is not configured or the
primary point is in a different node (such as, a peer-to-peer connection).

HPM Parameter Reference Dictionary L-6 8/97


LODSTN

LODSTN(1)–(12) (Logic)
Type: Blind Record Logic Output-Connection Destination—Specifies up to 12 destinations to which
in an Array the current values of the logic slot outputs are supplied. The destinations can be
(1..12) specified using the "Tagname.Parameter" format or the hardware reference address
Lock: PtBld format. Refer to the HPM Control Functions and Algorithms manual for a
Default: null.null detailed description.
PtRes: HPM
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters, and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters, and must be a legitimate parameter name.

Some possible output-connection destinations are


a."DigOut slot tagname.ONPULSE or OFFPULSE"
b."DigOut slot Tagname.SO"
c."Logic slot Tagname.Fl(nn)" where nn = 7–12
d."ProcMod Tagname.Fl(nnn)" where nnn = 1–127
e."Flag slot Tagname.PVFL
f."!Box.FL(nnnn)" for a box flag that resides in the same HPM box where
nnnn = 1-16,384.
g."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the UCN number, xx is the HPM box number of the destination
parameter, and nnnn = 1-4095 (data access limit).

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DO (Digital Output)
mm is the IOP Card number (1-40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

HPM Parameter Reference Dictionary L-7 8/97


LODSTN(1)–(2)

LODSTN(1)–(2) (DevCtl)
Type: Blind Record Device Control Output Connection Destination—Specifies up to 2 destinations
in an Array to which the current values of the Device Control slot outputs are supplied. The
(1..2) destinations can be specified using the "Tagname.Parameter" format or the
Lock: PtBld hardware reference address format Refer to the HPM Control Functions and
Default: Null Algorithms manual for a detailed description.
PtRes: HPM
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

Some possible output-connection destinations are


a."DigOut slot tagname.ONPULSE or OFFPULSE"
b."DigOut slot Tagname.SO"
c."Logic slot Tagname.Fl(nn)" where nn = 7–12
d."ProcMod Tagname.Fl(nnn)" where nnn = 1–127
e."Flag slot Tagname.PVFL
f."!Box.FL(nnnn)" for a box flag that resides in the same HPM box where
nnnn = 1-16,384.
g."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the UCN number, xx is the HPM box number of the destination
parameter, and nnnn = 1-4095 (data access limit).

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DI (Digital Input)
mm is the IOP Card number (1–40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

LOENBL(1)–(2) (DevCtl)
Type: E:$PMDVPRM Device Control Output Enable—Allows the respective output connection
in an Array defined by LODSTN to write the value of the specified Device Control
(1..2) parameter to the destination. The logic output is allowed when the enable
Lock: PtBld function, selected from the list below, is On. If the FL1 parameter is
Default: FL2 specified and the output data type is logical, output occurs only during
PtRes: HPM change (normally, it is continuous).

Range: FL1...FL12 [Local flag; either a 1 (On) or a 0 (Off)]


D1, D2 [Digital PV inputs, either a 1 (On) or a 0 (Off)]
SI0 [Safety interlocks, either a 1 (On) or a 0 (Off)]
I0, I1, I2 [Interlocks, either a 1 (On) or a 0 (Off)]
P0, P1, P2 [Permissives, either a 1 (On) or a 0 (Off)]
PISO1..PISO12 [Primary Input Gate Values (logical)]
SISO1..SISO12 [Secondary Input Gate Values (logical)]
PGSO1..PGSO4 [Primary Gate Output Values (logical)]
SGSO1, SGSO2 [Secondary Gate Output Values (logical])
L1..L12 [Logic input value to device control slot (logical)]

HPM Parameter Reference Dictionary L-8 8/97


LOENBL(1)–(12)

LOENBL(1)–(12) (Logic)
Type: E:$PMMLGPM Logic Output Enable—Allows the respective output connection defined by
Lock: PtBld LODSTN to write the value of the specified logic-slot parameter to the
Default: FL2 destination. The logic output is allowed when the enable function, selected
PtRes: HPM from the list below, is On. If the FL1 parameter is specified and the
output data type is logical, output occurs only during change (normally, it
is continuous).

Range: FL1...FL12 [Local flag; either a 1 (On) or a 0 (Off)]


SO1...SO24 [Logic-block output; either a 1 (On) or a 0 (Off]
L1...L12 [Logic input value to logic slot (logical)]

LOGALGID(1)–(24) (Logic)
Type: E:$PMMLGAL Logic Block Algorithm Identifier—Defines the logic algorithm to be used
Lock: PtBld for a particular logic block. A different logic algorithm can be specified for
Default: NULL each logic block within a logic slot. Refer to the HPM Control Functions
PtRes: HPM and Algorithms manual for a detailed description of each logic algorithm.
Range: Algorithm ID Description Input(s)
0-NULL No logic algorithm is executed ---
1-AND AND Gate *S1, S2, S3
2-OR OR Gate *S1, S2, S3
3-NOT NOT Gate S1
4-NAND NAND Gate *S1, S2, S3
5-NOR NOR Gate *S1, S2, S3
6-XOR XOR Gate S1, S2
7-QOR2 Qualified OR Gate with 2 Inputs On S1, S2, S3, S4
8-QOR3 Qualified OR Gate with 3 inputs On S1, S2, S3, S4
9-SWITCH Switch S1, S2, S3
10-EQ Compare equal with deadband R1, R2, DEADBAND
11-NE Compare not equal with deadband R1, R2, DEADBAND
12-GT Compare > than with deadband R1, R2, DEADBAND
13-GE Compare > than or = with deadband R1, R2, DEADBAND
14-LT Compare < than with deadband R1, R2, DEADBAND
15-LE Compare < than or = with deadband R1, R2, DEADBAND
16-CheckBad Check for Bad R1
17-Pulse Fixed-size Pulse S1, DLYTIME
18-MinPulse Pulse with minimum time limit S1, DLYTIME
19-MaxPulse Pulse with maximum time limit S1, DLYTIME
20-Delay Either Direction S1
21-OnDly Off-On Delay S1, DLYTIME
22-OffDly On-Off Delay S1, DLYTIME
23-WatchDog Watchdog Timer FL6
24-FlipFlop Flip Flop S1, S2, S3
25-ChDetect Change Detect S1, S2 , S3
26-DISCREP3 Discrepancy Gate with 3 inputs plus delay S1, S2, S3, DLYTIME

*Inputs S1–S3 can be inverted as required

HPM Parameter Reference Dictionary L-9 8/97


LOGICSRC

LOGICSRC (DigComp, DevCtl)


Type: Ent_Id Logic Source—Specifies the tag name of a point, usually a logic slot, that is
Lock: PtBld controlling the interlock signals.
Default: Null
PtRes: NIM
Range: Tag name can be up to sixteen characters and the permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.

LOGMIX (Logic)
Type: E:$LOGMIX Logic Mix—Defines the number of input connections, logic blocks, and output
Lock: PtBld connections this logic slot contains.
Default: 12_24_4
PtRes: HPM
Input Connections Number of Output Connections
Range: LISRC(1)-LISRC(12) Logic Blocks LOSRC(1)-LOSRC(12)
12_24_4 12 24 4
12_16_8 12 16 8
12_8_12 12 8 12

LOSRC(1)–(2) (DevCtl)
Type: E:$PMDVPRM Device Control Output Connection Source—Defines the Device Control
in an Array parameter that is to provide its value to the output connection specified by
(1..2) parameter LODSTN(n), Device Control Output Connection Destination.
Lock: PtBld
Default: FL1
PtRes: HPM
Range: FL1...FL12 [Local flag; either a 1 (On) or a 0 (Off])
D1, D2 [Digital PV inputs, either a 1 (On) or a 0 (Off)]
SI0 [Safety interlocks, either a 1 (On) or a 0 (Off)]
I0, I1, I2 [Interlocks, either a 1 (On) or a 0 (Off)]
P0, P1, P2 [Permissives, either a 1 (On) or a 0 (Off)]
PISO1..PISO12 [Primary Input Gate Values (logical)]
SISO1..SISO12 [Secondary Input Gate Values (logical)]
PGSO1..PGSO4 [Primary Gate Output Values (logical)]
SGSO1, SGSO2 [Secondary Gate Output Values (logical)]
L1..L12 [Logic input value to device control slot (either logical or real)]
NN1..NN8 [Local numerics (real)]
PINN1..PINN12 [Numeric constant for arithmetic comparisons (real)]
SECVAR [Secondary variable input value (real)]

HPM Parameter Reference Dictionary L-10 8/97


LOSRC(1)–(12)

LOSRC(1)–(12) (Logic)
Type: E:$PMMLGPM Logic Output Connection Source—Defines the logic-slot parameter that is
Lock: Eng/PB to provide its value to the output connection specified by parameter
Default: FL1 LODSTN(n), Logic Output Connection Destination.
PtRes: HPM
Range: FL1...FL12 [Local flag; either a 1 (On) or a 0 (Off)]
SO1...SO24 [Logic block output; logical 1 or 0)]
L1...L12 [Input to the logic slot (logical or real value)]
NN1...NN8 [Local numeric; data type of Real]

LOWERTIM
Type: Real Lower Output Pulse Time (In Seconds)—Indicates the lower output pulse time
Lock: View in seconds. This value is clamped to MAXPULSE or CYCLETIM, whichever
Default: N/A is lower. If LOWERTIM is smaller than RP*MINPULSE, no pulse is issued.
PtRes: HPM
Range: N/A

LOWRDSTN
Type: Universal Lower OP Pulse Destination—Defines the destination of the Lower output
Ent.Prm pulse. LOWRDSTN must point to parameter ONPULSE or parameter
Lock: PtBld OFFPULSE of a DigOut point.
Default: Null
PtRes: HPM
Range: ONPULSE
OFFPULSE

LOWRRATE
Type: Real Lower OP Stroke Rate in Percent/Second
Lock: Supr
Default: 100.0%/sec.
PtRes: HPM
Range: >0.0 percent/second

LRL (STI)
Type: Real Lower Range Limit—Indicates the lower range limit of the PV at the smart
Lock: View transmitter. This limit is fixed and cannot be changed. Refer to the description
Default: NaN of the STI_EU parameter for the LRL engineering units.
PtRes: HPM
Range: N/A, NAN

HPM Parameter Reference Dictionary L-11 8/97


LRV

LRV (STI)
Type: Real Lower Range Value—Defines the lower end of the operating range for the
Lock: Supr/View PVRAW value. User entry for PVEULO is the user-entered engineering-unit
Default: NaN value that corresponds to LRV. Refer to description of the STI_EU parameter
PtRes: HPM for the LRV engineering units.

This parameter can be changed only when the STI point execution state
PTEXECST is Inactive.

Range: N/A, NaN

LSEQNUMR
Type: Integer Last Sequence Number—Specifies the sequence number of the last personality
Lock: Eng image file packet received by the IOP.
Default: 0
PtRes: IOP
Range: ?

LSIOLORN(0) - (4) (HPM Box)


Type: Integer Last Hour's I/O Link Fetch/Store Overruns—Indicates the number of
Lock: View I/O Link access overruns that have been detected in the last hour.
Default: 0
PtRes: HPM LSIOLORN is set equal to the contents of CRIOLORN, every hour on the hour.
Range: >0

LSPPXORN(0 - 8) (HPM Box)


Type: Integer Last Hour's Point Processing Overruns Per Cycle—Indicates the number of
Lock: View point processing overruns that have been detected in the last hour.
Default: 0
PtRes: HPM LSPPXORN is set equal to the contents of parameter CRPPXORN, every hour
on the hour.

Range: >0

LSTWHNER (ProcMod)
Type: Integer Last When Error—The CL Fail/Error code masked by the “When Error” clause.
Lock: View
Default: 0
PtRes: HPM
Range: >0

LSUCNORN (HPM Box)


Type: Integer Last Hour's UCN Access Overruns—LSUCNORN is set equal to the contents of
Lock: View parameter CRUCNORN, the current hour's UCN Access Overruns, every hour
Default: 0 on the hour.
PtRes: HPM
Range: >0

HPM Parameter Reference Dictionary L-12 8/97


M

-M-

M (IncrSum, ORSel, Switch)


Type: Integer Number of Inputs
Lock: PtBld
Default: 2
PtRes: HPM
Range: 2 to 4

MAINDAT (DevCtl, DigComp)


Type: Time Maintenance Reset Statistics Date—The date and time of the reset of maintenance
Lock: Engr statistics that can also be written by the engineer. Statistics can be reset by the
Default: Time of Point operator only when the device is red tagged, while programs can reset them at any
Build time. Resetting is accomplished by setting the RESETFL to ON.
PtRes: HPM
Range: Time Stamp (DD MMM YY HH:MM:SS)

Helpful Hint: This parameter is reset when the RESETFL parameter = ON.

MAINTOPT (DevCtl, DigComp)


Type: Logical Maintenance Option—Indicates if the maintenance statistics option is used.
Lock: PtBld
Default: Off
PtRes: HPM
Range: Off (Maintenance statistics are not available)
On (Maintenance statistics are available)

MANMODFL (RegCtl)
Type: Logical Manual Mode Flag—Indicates whether the current mode of the slot is Manual.
Lock: View
Default: N/A
PtRes: HPM
Range: Off (Current mode is other than Manual)
On (Current mode is Manual)

MANOPCMD
Type: E:$MANOPCM Manual Output Pulse Command—Defines the output pulse command issued
Lock: Oper by the operator for raising and lowering the output. See also,
Default: None MANOPTIM.
PtRes: HPM
Range: 0-None (No change)
1-Raise_1 (Raise output by 1 MANOPTIM each keystroke)
2-Lower_1 (Lower output by 1 MANOPTIM each keystroke)
3-Raise_10 (Raise output by 10 MANOPTIMs each keystroke)
4-Lower_10 (Lower output by 10 MANOPTIMs each keystroke)

HPM Parameter Reference Dictionary M-1 8/97


MANOPTIM

MANOPTIM
Type: Real Manual Output Pulse Time (in seconds)—Defines the width of the raise or lower
Lock: Eng/PB output pulse that is issued by the operator.
Default: 1.0
PtRes: HPM
Range: 0.0 to 60.0 seconds

MASKTIM (DevCtl)
Type: Integer Masktime—The amount of time the SECVAR parameter alarms are masked after
Lock: Supr a change in the output state.
Default: 0
PtRes: HPM
Range: 0 to 1000 seconds

MAXCNFPU (HPM Box)


Type: Real Maximum Configurable PUs—Specifies
Lock: View
Default: N/A
PtRes: HPM
Range:

Helpful Hint:

MAXPU (ProcMod)
Type: Real Maximum PUs—Specifies the maximum PUs used for point processing.
Lock: View
Default: 0
PtRes: HPM
Range: 0 to

Helpful Hint:

MAXPULSE
Type: Real Maximum Pulse Time Limit—Defines the maximum pulse time limit. If the
Lock: Supr calculated pulse time is greater than this value then a pulse of length
Default: 60 MAXPULSE is issued.
PtRes: HPM
Range: MINPULSE to 60.0 seconds
NaN

HPM Parameter Reference Dictionary M-2 8/97


MAXSLOTS

MAXSLOTS
Type: Real Maximum Available Slots—Returns the maximum number of slots that can be
Lock: View configured in an IOP.
Default: 0
PtRes: IOP
Range: 0 - 127 slots

Helpful Hint: Applies to the following IOP types: AO16, DI32 and DO32.

MAXTIM0H (DevCtl, DigComp)


Type: Real Maximum Time Allowed in State 1—The maximum amount of time (based on
Lock: Supr the PV) in hours allowed for state 1.
Default: 0
PtRes: HPM
Range: N/A

MAXTIM1H (DevCtl, DigComp)


Type: Real Maximum Time Allowed in State 1—The maximum amount of time (based on
Lock: Supr the PV) in hours allowed for state 2.
Default: 0
PtRes: HPM
Range: N/A

MAXTIM2H (DevCtl, DigComp)


Type: Real Maximum Time Allowed in State 2—The maximum amount of time (based on
Lock: Supr the PV) in hours allowed for state 3.
Default: 0
PtRes: HPM
Range: N/A

MAXTRAN0–2 (DevCtl, DigComp)


Type: Time Maximum Number of Transitions into State—This is the maximum number of
Lock: Supr transitions allowed in each state, and is the target value for maintenance
Default: 0.0 statistics.
PtRes: HPM
Range: 0 (There is no limit)

MDMHWREV (HPM Box, NIM)


Type: String_2 Modem Hardware Revision
Lock: View
Default:
PtRes: HPM, NIM
Range: Hexadecimal Characters 00 to FF

HPM Parameter Reference Dictionary M-3 8/97


MEMFWREV

MEMFWREV
Type: String_2 Memory Firmware Revision
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal Characters 00 to FF

MEMHWREV
Type: String_2 Memory Hardware Revision
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal Characters 00 to FF

MINPULSE
Type: Real Minimum Pulse Time Limit—Defines the minimum pulse time limit for the
Lock: Supr Raise pulse. If the calculated pulse time value is smaller than this value, no
Default: 0.0 pulse is issued.
PtRes: HPM
Range: 0.0 seconds to MAXPULSE
NaN

MINUTE (HPM Box)


Type: Integer Current Minute—Value of the LCN time in the HPM.
Lock: View
Default: N/A
PtRes: HPM
Range: 0 to 59

MNFASIC (HPM Box)


Type: Integer HPMM Communications Control Card ASIC Revision—
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 31

MNFCCDAY (HPM Box)


Type: Integer HPMM Communications Control Card Manufacturing Date-Day—
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 31

HPM Parameter Reference Dictionary M-4 8/97


MNFCCINF

MNFCCINF (HPM Box)


Type: String_8 HPMM Communications Control Card Manufacturing Information—
Lock: View
Default: 0
PtRes: HPM
Range:

MNFCCMTH (HPM Box)


Type: Integer HPMM Communications Control Card Manufacturing Date-Month—
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 12

MNFCCSER (HPM Box)


Type: String_24 HPMM Communications Control Card Serial Number—
Lock: View
Default: 0
PtRes: HPM
Range:

MNFCCYR (HPM Box)


Type: Integer HPMM Communications Control Card Manufacturing Date-Year—
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 99

MNFFPGA (HPM Box)


Type: Integer HPMM I/O Link Card FPGA Revision—
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 31

MNFIODAY (HPM Box)


Type: Integer HPMM I/O Link Card Manufacturing Date- Day
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 31

HPM Parameter Reference Dictionary M-5 8/97


MNFIOINF

MNFIOINF (HPM Box)


Type: String_8 HPMM IO Link Processor Card Manufacturing Information
Lock: View
Default: Blank
PtRes: HPM
Range: 0 - 99

MNFIOMTH (HPM Box)


Type: Integer HPMM IO Link Card Manufacturing Date-Month
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 12

MNFIOSER (HPM Box)


Type: String_24 HPMM IO Link Card Serial Number
Lock: View
Default: 0
PtRes: HPM
Range:

MNFIOYR (HPM Box)


Type: Integer HPMM IO Link Card Manufacturing Date-Year
Lock: View
Default: 0
PtRes: HPM
Range: 0 - 99

MNFMDDAY (HPM Box)


Type: Integer HPMM UCN Interface Card Manufacturing Date-Day
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 31

MNFMDINF (HPM Box)


Type: String_8 HPMM UCN Interface Card Manufacturing Information
Lock: View
Default: Blank
PtRes: HPM
Range:

HPM Parameter Reference Dictionary M-6 8/97


MNFMDMTH

MNFMDMTH (HPM Box)


Type: Integer HPMM UCN Interface Card Manufacturing Date-Month
Lock: View
Default: 0
PtRes: HPM
Range: 1 - 12

MNFMDSER (HPM Box)


Type: String_24 HPMM UCN Interface Card Serial Number
Lock: View
Default: 0
PtRes: HPM
Range: N/A

MNFMDYR (HPM Box)


Type: Integer HPMM UCN Interface Card Manufacturing Date - Year
Lock: View
Default: 0
PtRes: HPM
Range: 0 - 99

MODATTR
Type: E:MODATTR Mode Attribute—Defines whether the operator or the sequence program has the
Lock: Oper authority to change certain parameters of this data point. At the Universal
Default: Operator Station, the mode attribute is displayed next to the mode of the data point. If
PtRes: HPM the mode attribute is Program, a -P appears to the left of MODE. If the
attribute is operator, blanks are displayed to the left of mode.

Range: 0-Operator (Operator can set Mode, OP, SP, Ratio, Bias)
1-Program (Program can set Mode, OP, SP, Ratio, Bias)
2-Normal
3-None (No mode attribute)

Helpful Hint: MODATTR change requires SHUTDOWN = Off and REDTAG = Off. When
the "normal mode" button on the Operator's keyboard is pressed, MODATTR =
NMODATTR unless NMODATTR = None.

HPM Parameter Reference Dictionary M-7 8/97


MODE

MODE (AnalgOut)
Type: E:MODE Mode—Defines the current mode of the data point. Parameter MODATTR
Lock: Oper determines whether operator or the sequence program provides the output value
Default: Man for this point. If PNTFORM is Component, then MODE parameter is not
PtRes: HPM applicable for this data point.
Range: 1-Man (Operator or Program provides the point's output value (OP))
2-Cas (Data point receives its output value from a primary data point.
If RCASOPT is DDC, data point receives its output value from an AM point.)
5-Normal (Parameter NMODE determines this point's mode)

Helpful Hint: 1. MODE change by a program requires MODATTR = Program and


REDTAG = Off.
2. MODE change by an operator requires MODATTR = Operator,
MODEPERM = Permit, and REDTAG = Off.

MODE (DigComp, DevCtl)


Type: E:MODE Mode of Digital Composite and Device Control Slot—Defines the current mode
Lock: Oper of the data point. Parameter MODATTR determines whether operator or the
Default: Man sequence program provides the output value for this point. If PNTFORM is
PtRes: HPM Component, then MODE parameter is not applicable for this data point.
Range: 1-Man (Operator or Program controls slot's output (OP))
5-Normal (Parameter NMODE contains slot's mode)

Helpful Hint: 1. MODE change by a program requires MODATTR = Program,


SHUTDOWN = Off, and REDTAG = Off.
2. MODE change by an operator requires MODATTR = Operator,
MODEPERM = Permit, SHUTDOWN = Off, and REDTAG = Off.

MODE (RegCtl)
Type: E:MODE Mode of Regulatory Control Slot—Defines the mode of the RegCtl point.
Lock: Oper
Default: Man
PtRes: HPM
Range: 1-Man (Operator or discontinuous program controls slot's output (OP), regardless of any
automatic control strategy)
2-Cas (Upstream slot's OP is this slot's SP)
3-Auto (OP value is computed by the configured RegCtl algorithm, and the setpoint (SP)
comes from the local setpoint (LSP) location in the RegCtl point. An operator or a
discontinuous program can change the setpoint value.
4-Bcas (Local cascade mode where the RegCtl point receives its setpoint from the OP of a
primary data point, even though the entry for the RCASOPT parameter is Spc,
DdcRsp, or Rsp (where the AM provides the setpoint). In this way, should the AM
or the NIM fail, the control strategy will shed to the local cascade mode.)
5-Normal (Parameter NMODE determines the normal mode of this slot)

Helpful Hint: 1. MODE change by a program requires MODATTR = Program


and REDTAG = Off.
2. MODE change by an operator requires MODATTR = Operator,
MODEPERM = Permit, and REDTAG = Off.

HPM Parameter Reference Dictionary M-8 8/97


MODEAPPL

MODEAPPL(1)–(4) (DevCtl, DigComp, RegCtl)


Type: Logical Mode Applicability—Defines changes for Regulatory Control
Lock: View points:
Default: Man=On MODEAPPL[1] = ON if MAN mode if valid, else it is OFF
MODEAPPL [Auto]=Off MODEAPPL[2] = ON if AUTO mode is valid, else it is OFF
MODEAPPL [Bcas]=Off MODEAPPL[3] = ON if CAS mode is valid, else it is OFF
MODEAPPL[Cas]=Off MODEAPPL[4] = ON if BCAS mode is valid, else it is OFF
Static for DevCtl
and Digcomp points
PtRes: HPM
Range: N/A

MODEPERM (AO)
Type: E:MODEPERM Mode Permissive—Determines whether the operator can change the mode of
Lock: Eng/PB this data point.
Default: Permit
PtRes: HPM
Range: 0-Permit (Operator can change this point's mode)
1-NotPerm (Operator cannot change this point's mode)

MODEPERM (DevCtl, DigComp, RegCtl)


Type: E:MODEPERM Mode Permissive—Determines whether the operator can change the mode of
Lock: Eng this data point.
Default: Permit
PtRes: HPM
Range: 0-Permit (Operator can change this point's mode)
1-NotPerm (Operator cannot change this point's mode)

MODNUM
Type: Integer HPMM/IOP Module Number—Defines the module number in the HPM. The
Lock: PtBld HPMM is module number 0; the IOP Cards are module numbers 1–40.
Default: N/A
PtRes: NIM
Range: 0 to 40 (0 is reserved for the HPMM)

MOMSTATE (DevCtl, DigComp)


Type: E:$MOMSTAT Momentary Output States—Defines which of the output states are
Lock: Eng/PB momentary. Refer to the HPM Control Functions and Algorithms manual
Default: None for a detailed description.
PtRes: HPM
Range: 0-None (No momentary output states)
1-Mom_1 (State 1 is momentary if NOSTATES = 2 or 3)
2-Mom_0 (State 0 is momentary if NOSTATES = 2)
3-Mom_2 (State 2 is momentary if NOSTATES = 3)
4-Mom_1_2 (State 1 and State 2 are momentary; valid if NOSTATES = 3)

HPM Parameter Reference Dictionary M-9 8/97


MONPER

MONPER (HPM Box)


Type: Integer Monitoring Period—Specifies the monitoring period in seconds
Lock: Eng
Default: 3600
PtRes: HPM
Range: 4 - 3600 (must be in multiples of 4 seconds)

MONTH (HPM Box)


Type: Integer Current Month—The value of the LCN date in the HPM.
Lock: View
Default: N/A
PtRes: HPM
Range: 1 to 12 (January to December)

MOVPVFL
Type: Logical Moving PV Flag—Indicates whether the PV is moving from one state to
Lock: View another state.
Default: Off
PtRes: HPM
Range: Off (PV is not moving)
On (PV is moving)

MOVPVTXT (HPM Box, DevCtl, DigComp)


Type: String_8 Moving PV Text Descriptor—Defines the state descriptor that is displayed when
Lock: PtBld the Digital Composite or Device Control point is changing states (moving from
Default: MOVING one state to another), or is in-between states. This descriptor, defined on the
PtRes: NIM HPM box point, is displayed for all digital composite or device control points in
this HPM box if PVTXTOP, defined on the Digital Composite or Device
Control point, = OFF. This parameter contains the text for a configured moving
PV on a per point basis if the PVTXTOPT is ON.

Range: The permissible character set for the up to eight character descriptor is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9,
Underscore (_)

MPCFWREV (HPM Box)


Type: String_2 HPMM Master Processor Card Firmware Revision—
Lock: View
Default: Blank
PtRes: HPM
Range:

MPCHWREV (HPM Box)


Type: String_2 HPMM Master Processor Card Hardware Revision—
Lock: View
Default: Blank
PtRes: HPM
Range:

HPM Parameter Reference Dictionary M-10 8/97


MSGPEND

MSGPEND (ProcMod)
Type: Logical Sequence Message Pending—Indicates that a confirmable sequence message
Lock: View requiring confirmation has been issued to the operator.
Default: None
PtRes: HPM
Range: N/A

MSGTXT(0)–(15) (NIM)
Type: String_8 Status Message Text—Indicates the text for the self-defined enumeration of
in an Array STSMSG. MSGTXT(0) is always NONE, and cannot be configured. Refer to
(0..15) “Status Messages” in the Control Functions and Algorithms Manual for more
Lock: PtBld information.
Default: Blank
PtRes: NIM
Range: 0 to 15

MXRMPDEV (RampSoak)
Type: Real Maximum Ramp Deviation Value—If the PV falls behind the SP during a ramp
Lock: Supr segment by more than the value of MXRMPDEV, the ramping action is stopped
Default: NaN until the PV reaches the SP.
PtRes: HPM
Range: > 0.0,
NaN

MXSOKDEV (RampSoak)
Type: Real Maximum Soak Deviation Value—If the PV falls behind the SP during a soak
Lock: Supr segment by more than the value of MXSOKDEV, the soak timer is stopped
Default: NaN until the PV reaches SP.
PtRes: HPM
Range: > 0.0,
NaN

HPM Parameter Reference Dictionary M-11 8/97


HPM Parameter Reference Dictionary M-12 8/97
N

-N-

N (Calcultr)
Type: Integer Number of Inputs—Defines the number of inputs to this algorithm.
Lock: PtBld
Default: 1
PtRes: HPM
Range: 1 to 6

N (HiLoAvg, Summer)
Type: Integer Number of Inputs—Defines the number of inputs to this algorithm.
Lock: PtBld
Default: 2
PtRes: HPM
Range: 2 to 6 inputs

NAME
Type: String_16 Point Name—Identifies this point to the system and on displays, reports, and
Lock: PtBld logs. Figure N-1 shows examples of the Group and Detail Displays on which
Default: N/A the point name appears.
PtRes: NIM
Digital Input, Digital Output, Analog Output, Flag, and Numeric-type data
points do not have to be configured by using the point builder (DEB). All other
types of data points have to be configured by using the DEB and require that a
point name be specified during the point build process.

Range: Point name can be up to 16 characters, and the permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric point name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.

HPM Parameter Reference Dictionary N-1 8/97


NAME

GROUP DISPLAY

POINT NAME
F 3HP
FC1ØØT1 E. U. DESCRIPTOR
LBS/SEC
REFLUX KEYWORD
5Ø.7
5Ø.9U
25.9

DETH REFLUX PUMP - A CONTR POINT DESCRIPTOR

DETAIL DISPLAY
POINT NAME POINT DESCRIPTOR UNIT ID

FC1ØØT1 DETH REFLUX PUMP A CONTR UNIT XX


.ØØ% -

75% -

5Ø% -

25% -

Ø% - POINT NAME
F 3HP
FC1ØØT1 E. U. DESCRIPTOR
LBS/SEC
REFLUX KEYWORD
SP 5Ø.7
PV 5Ø.9U
OUT % 25.9
MAN

Figure N-1 — Locations of Terms on Group and Detail Displays 1850

HPM Parameter Reference Dictionary N-2 8/97


NARRSLOT

NARRSLOT (HPM Box)


Type: Integer Number of Array Slots in an HPM
Lock: PtBld
Default: 0
PtRes: HPM
Range: 0 to 500

NCTLSLOT (HPM Box)


Type: Integer Number of Regulatory Control Slots in an HPM—Refer to the HPM Control
Lock: PtBld Functions and Algorithms manual for a detailed description of HPM processing
Default: 0 capacity.
PtRes: HPM
Range: 0 to 250

NDCSLOT (HPM Box)


Type: Integer Number of Digital Composite Slots in an HPM—Refer to the HPM Control
Lock: PtBld Functions and Algorithms manual for a detailed description of HPM processing
Default: 0 capacity.
PtRes: HPM
Range: 0 to 999

NDEVSLOT (HPM Box)


Type: Integer Number of Device Control Points Configured—The number of Device Control
Lock: PtBld points in an HPM Box point. Refer to the HPM Control Functions and
Default: 0 Algorithms manual for a detailed description of HPM processing capacity.
PtRes: HPM
Range: 0 to 400

NEIPRQU (NIM PSDP)


Type: Real Number of Event Initiated Processing Requests—The number of Event Initiated
Lock: View Processing requests sent in the last 15 seconds.
Default: 0
PtRes: NIM
Range: N/A

HPM Parameter Reference Dictionary N-3 8/97


NEVTAVTG

NEVTAVG (HPM Box)


Type: Real Average number of Events per Second—Average number of events generated
Lock: View by the HPM per second.
Default: 0
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NEVTMAX (HPM Box)


Type: Real Maximum number of Events per Second—Maximum number of events
Lock: View generated by the HPM per second.
Default: 0
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NFASTCTL (HPM Box)


Type: Integer Number of Fast Regulatory Control Slots—Fast slots are processed four times
Lock: PtBld per second.
Default: 0
PtRes: HPM
Range: 0 to 100, cannot exceed NCTLSLOT

NFASTDC (HPM Box)


Type: Integer Number of Fast Digital Composite Slots—Fast slots are processed four times
Lock: PtBld per second.
Default: 0
PtRes: HPM
Range: 0 to 999, cannot exceed NDCSLOT

NFASTDEV (HPM Box)


Type: Integer Number of Fast Device Control Points Configured—The number of fast device
Lock: PtBld control points in an HPM Box data point. Fast slots are processed four times
Default: 0 per second.
PtRes: HPM
Range: 0 to 100, cannot exceed NDEVSLOT

HPM Parameter Reference Dictionary N-4 8/97


NFASTLOG

NFASTLOG (HPM Box)


Type: Integer Number of Fast Logic Slots—Fast slots are processed four times per second.
Lock: PtBld
Default: 0
PtRes: HPM
Range: 0 to 100, cannot exceed NLOGSLOT

NFASTPV (HPM Box)


Type: Integer Number of Fast Regulatory PV slots—Fast slots are processed four times per
Lock: PtBld second.
Default: 0
PtRes: HPM
Range: 0 to 100, cannot exceed NPVSLOT

NFLAG (HPM Box)


Type: Integer Number of Flags in HPM Box Data Point—The HPM always provides 16, 384
Lock: View box flag variables.
Default: 16, 384
PtRes: HPM
Range: 16,384

NFLAG (Array)
Type: Integer Number of Flags in Array Point FL Array—Defines the number of mapped flags
Lock: PtBld from either the HPM box (EXTDATA≠ IO_FL) or a serial interface IOP-
Default: 0 connected device (EXTDATA=IO_FL).
PtRes: HPM
Range: 0 to 512 (When EXTDATA = IO_FL)
0 to 1023 (When EXTDATA ≠ IO_FL)

NI0–2 (DevCtl, DigComp)


Type: Logical Inverted Interlocks Value—The negative value of the corresponding interlock.
Lock: Engr
Default: On
PtRes: HPM
Range: On (Interlock inactive)
Off (Interlock active)

Helpful Hint: This parameter can be changed by the engineer only if the point is inactive
or if the HPM is idle.

HPM Parameter Reference Dictionary N-5 8/97


NIMDAY

NIMDAY (NIM)
Type: Integer Day in Which the NIM Personality was Created
Lock: View
Default: 1
PtRes: NIM
Range: 1 to 31

Helpful Hint: This parameter is accessed using $NTWRKuu.NIMDAY (where uu = UCN


Network number).

NIMMONTH (NIM)
Type: Integer Month in Which the NIM Personality was Created
Lock: View
Default: 1
PtRes: NIM
Range: 1 to 12
Helpful Hint: This parameter is accessed using $NTWRKuu.NIMMONTH (where uu = UCN
Network number).

NIMREV (NIM)
Type: Integer Revision Number of the NIM Personality
Lock: View
Default: 0
PtRes: NIM
Range: N/A

Helpful Hint: This parameter is accessed using $NTWRKuu.NIMREV (where uu = UCN


Network number).

NIMVERS (NIM)
Type: Integer Version Number of the NIM Personality
Lock: View
Default: 0
PtRes: NIM
Range: N/A

Helpful Hint: This parameter is accessed using $NTWRKuu.NIMVERS (where uu = UCN


Network number).

NIMYEAR (NIM)
Type: Integer Year in Which the NIM Personality was Created
Lock: View
Default: 0
PtRes: NIM
Range: 0 - 99

Helpful Hint: This parameter is accessed using $NTWRKuu.NIMYEAR (where uu = UCN


Network number).

HPM Parameter Reference Dictionary N-6 8/97


NLFM

NLFM
Type: Integer Nonlinearity Form—Defines the form of the nonlinear gain.
Lock: Supr
Default: 1
PtRes: HPM
Range: 0 or 1

NLGAIN (Pid)
Type: Real Nonlinear Gain—Defines the value of the nonlinear gain factor KNL.
Lock: Supr
Default: 0.0
PtRes: HPM
Range: 0.0 to 240.0

NLOC (VdtLdLag)
Type: Integer Number of Locations in Delay Table
Lock: Eng
Default: 30
PtRes: HPM
Range: 2 to 30

NLOGSLOT (HPM Box)


Type: Integer Number of Logic Slots in the HPM—Refer to the HPM Control Functions and
Lock: PtBld Algorithms manual for a detailed description of HPM processing capacity.
Default: 0
PtRes: HPM
Range: 0 to 400

NMIN (HiLoAvg)
Type: Integer Minimum Number of Good Inputs—Defines the minimum number of valid
Lock: Supr inputs (PV status is good or uncertain) to this algorithm.
Default: 1
PtRes: HPM
Range: 1 to N (N is the number of inputs selected by N parameter)

HPM Parameter Reference Dictionary N-7 8/97


NMODATTR

NMODATTR (RegCtl)
Type: E:MODATTR Normal Mode Attribute—Defines whether an operator or a program can change
Lock: Engr certain parameters such as the mode, SP, or OP of a data point when the
Default: None point is in the normal mode.
PtRes: HPM
Range: 0-Operator (MODATTR can be set equal to Operator)
1-Program (MODATTR can be set equal to Program)
2-Normal
3-None (MODATTR is not affected by this parameter)

Helpful Hint: If NMODATTR = Operator or Program and the "normal mode" button on the
Operator's keyboard is pressed, MODATTR = NMODATTR. If NMODATTR
is to be changed, the engineer must change it.

NMODE (AnalgOut)
Type: E:MODE Normal Mode—Allows user to define the normal mode for this data point.
Lock: Engr/PB
Default: None
PtRes: HPM
Range: 0-None (No configured "normal" operating mode)
1-Man (Manual is configured "normal" mode)
2-Cas (Cascade is configured "normal" mode)

Helpful Hint: NMODE configuration for the Cas option requires RCASOPT = Ddc.

NMODE (DevCtl, DigComp)


Type: E:MODE Normal Mode—Allows user to define the normal mode for this data point.
Lock: View
Default: Man
PtRes: HPM
Range: 1-Man (Manual is the "normal" operating mode)

NMODE (RegCtl)
Type: E:MODE Normal Mode—Allows user to define the normal mode for this data point.
Lock: Engr
Default: None
PtRes: HPM
Range: 0-None (No configured "normal" operating mode)
1-Man (Manual is the "normal" operating mode)
2-Cas (Cascade is the "normal" operating mode)
3-Auto (Automatic is the "normal" operating mode)
4-Bcas (Backup Cascade is the "normal" operating mode)

Helpful Hint: Mode. If NMODATTR = None and the "normal mode" button on the Operator's
keyboard is pressed, MODE is set to the contents of NMODE.

HPM Parameter Reference Dictionary N-8 8/97


NMODETRK

NMODETRK (HPM Box)


Type: E:$NMODETR Normal Mode Tracking Supression —Enable/disable Normal Mode and
Lock: PtBld Normal Mode attribute from tracking mode and mode attribute changes.
Default: Enable
PtRes: HPM
Range: Enable
Disable

NMSGTXT (NIM)
Type: Integer Number of Message Text Items—Defines the number of message text items that
Lock: PtBld you can enter. See MSGTXT.
Default: 0
PtRes: NIM
Range: 0 to 15

NN(i) (Array)
Type: Real Array Point Numeric Variables—Numerics are mapped from either the HPM box
Lock: Determined by (defined by NNUMERIC and NNSTIX parameters) or from a serial interface IOP-
SPLOCK connected device (when EXTDATA=IO_NN, mapping is defined by the
parameter IOPNUM, FTANUM, DEVADDR, NNSTIX, and NNUMERIC parameters).
Default: N/A
PtRes: HPM
Range: 1 ≤ i ≤ Array parameter NNUMERIC

NN(1)–(8) (DevCtl, Logic)


Type: Real Numerics 1-8—Eight numerics are provided with each device control and logic
Lock: Supr slot. The numerics can be used as reference values for the comparison logic
Default: NaN algorithms, or they can be used as source parameters for the output connections
PtRes: HPM when writing predefined analog constants to other points. The values of the
Range: N/A numerics can be changed from the Universal Station, by other device control
logic slots, or by user-written programs.

NN(1)–(80) (ProcMod)
Type: Real Numeric Variables—Each process module in the HPM has 80 numerics that can
Lock: Determined be used for implementing batch operations.
by SPLOCK
parameter
Default: NaN
PtRes: HPM
Range: N/A

NN(1)–(16,384) (HPM Box)


Type: Real Numeric Value—This is an array of up to 16,384 numeric variables. The upper
Lock: Oper bound of this array is determined by the NNUMERIC parameter. Numerics
Default: NaN NN(1) to NN (2047) are taggable. Numerics NN(1) to NN (4095) are accessible
PtRes: HPM from the LCN by using hardware form [!Box.NN( )]. Numerics 4096 through
16,384 are accessible only through Array points.
Range: N/A

HPM Parameter Reference Dictionary N-9 8/97


NNDESC

NNDESC (Array)
Type: String_64 NN Array Descriptor—Describes NN data for the Array point.
Lock: PtBld
Default: Spaces
PtRes: HPM
Range: N/A

NNINSET(1)–(10) (DevCtl)
Type: Integer Numeric 1 - 10—A set of 10 integers that are used by the primary input gate
in an Array IN_SET algorithm.
(1..10)
Lock: Supr
Default: 0
PtRes: HPM
Range: 0 to 32767

NNSTIX (Array)
Type: Real Numeric Array Start Index—Defines the start index in Box NN variables, or a
Lock: PtBld serial interface-connected device.
Default: 0
PtRes: HPM
Range: 0 to 99,999 (When EXTDATA=IO_NN, 0 can be valid device index)
0 to Box parameter NNUMERIC (When EXTDATA≠IO_NN, 0 indicates no numerics are
configured)

NNUMERIC (HPM Box)


Type: Integer Number of Numerics in HPM Box Data Point—The number of box numerics is
Lock: PtBld determined in intervals of 16 numerics.
Default: 0
PtRes: HPM
Range: 0 to 16,384

NNUMERIC (Array)
Type: Integer Number of Numerics in Array Point NN Array—Defines the number of
Lock: PtBld numerics mapped from either the HPM box (EXTDATA≠ IO_NN), or a serial
Default: 0 interface IOP-connected device (EXTDATA=IO_NN). For external data, the valid
PtRes: HPM range depeneds on how numeric data is organized in the device.

Range: 0 - 16 (Floats), 0 - 32 (Integers), 0 - 64 (Byte Integers) When EXTDATA = IO_NN


0 to 240 When EXTDATA ≠ IO_NN

HPM Parameter Reference Dictionary N-10 8/97


NOCINPTS

NOCINPTS (RegCtl)
Type: Integer Number of Control Input Connections—Defines the number of control input
Lock: PtBld connections for this algorithm.
Default: Based on
CTLALGID,
CTLEQN, M
PtRes: HPM
Range: 0 to 4

NOCOPTS (RegCtl)
Type: Integer Number of Control Output Connections—Defines the number of control output
Lock: PtBld connections from this RegCtl point.
Default: 1
PtRes: HPM
Range: 0 to 4

Helpful Hint: Control output engineering ranges (CVEULO, CVEUHI) must be entered
for CTLALGID = PidErfb and Rampsoak, and must be entered for
CTLALGID = Pid, PidFf, and RatioCtl when NOCOPTS = 0. For
CTLALGID = Pid, PidFf, and RatioCtl, with NOCOPTS > 0, the CV
ranges are obtained from a secondary output connection.

NODEASSN (HPM Box)


Type: E:$NODEASN Node Assignment—Defines whether the NIM on this logical UCN or a NIM
Lock: PtBld on another logical UCN is the primary NIM for this UCN node.
Default: ThisNIM
PtRes: NIM
Range: ThisNIM (The NIM on this logical UCN is responsible for parameter fetch/stores,
alarming, AM control strategy and checkpointing for this UCN node.)

RemotNIM (A NIM on another logical UCN is responsible for configuring, checkpointing, and
restoring the database through this UCN node.)

HPM Parameter Reference Dictionary N-11 8/97


NODECMD

NODECMD (HPM Box)


Type: E: $PMCMD Node Command—Defines the command issued to the HPM.
Lock: Eng
Default: None
PtRes: HPM

Range: 0-None (No request made to the HPM)


1-Run (HPM requested to go to the Run state)
2-Idle (HPM requested to go to an Idle state)
3-Warmstrt (Warm Start requested )
4-Coldstrt (Cold Start requested )
5-Pause (HPM requested to go to the Simul_Pause state)
6-Resume (HPM requested to go to the Simul_Run state)

NODECONF (HPM Box)


Type: E:$PMCONF Node Configuration for the HPM—Currently not used. This parameter must
Lock: View always be set to manual.
Default: Manual
PtRes: HPM
Range: Manual
Auto

NODENUM (NIM)
Type: Integer Node Number—Defines the address of the NIM on the UCN.
Lock: PtBld
Default: N/A
PtRes: NIM
Range: 1 to 64

NOTE

The node number assigned to the NIM should be the lowest node number on the UCN (see
Timesync).

NODENUM (HPM Box)


Type: Integer Node Number—Defines the address of the HPMs on the UCN. NODENUM
Lock: PtBld assigned for any HPM must be odd whether PKGOPT equals
Default: N/A Option 1 (nonredundant) or Option 2 (redundant). Because of this restriction
PtRes: NIM and because the NIM takes up one odd address and the next even address, the
Range: 1 to 64 maximum number of HPM's that can be on the UCN is 31. The primary
HPMM is assigned an odd address, the associated secondary (redundant) HPMM
is assigned the next (even) address.

HPM Parameter Reference Dictionary N-12 8/97


NODEOPER

NODEOPER
Type: E:$PRIMSEC Node Operating Mode
Lock: View
Default:
PtRes: NIM
Range: Primary (HPM/NIM is the acting primary node)
Secndry (HPM/NIM is the acting secondary)

NODESC (Logic)
Type: Integer Number of Generic Descriptors—Defines the number of user-defined generic
Lock: PTBLD descriptors that are to be used on this logic slot. For each descriptor, the
Default: 0 parameter in the logic slot to which the generic descriptor is attached is defined
PtRes: NIM by the PRMDESC(n) parameter, and the corresponding descriptors are defined by
Range: 0 to 12 the GENDESC(n) parameters. This allows the user to customize the descriptors
used for displaying the logic slot on the Universal Station displays.

NODESTAT (HPM Box)


Type: E:$NODESTA HPM Node Status
Lock: View
Default: N/A
PtRes: HPM
Range: OffNet (HPM is not running on UCN)
OK (HPM is configured and running)

NODESTAT (NIM)
Type: E:$NODESTA NIM's Node Status
Lock: View
Default: N/A
PtRes: NIM
Range: OffNet (NIM is not running on UCN)
OK (NIM is configured and running)

NODESTS (NIM)
Type: E:$DSPSTAT NIM Node Summary Status—Indicates the current overall status of the NIM.
Lock: View
Default: N/A
PtRes: NIM
Range: OffNet (NIM cannot communicate with HPMM)
OK (NIM is performing normally)

HPM Parameter Reference Dictionary N-13 8/97


NODESTS

NODESTS (HPM Box)


Type: E:$DSPSTAT HPM Node Summary Status—Indicates the current overall status of the HPM
Lock: View on the UCN.
Default: N/A
PtRes: HPM
Range: 0-OK (HPM is performing normally)
1-IOIDL (At least one IOP has entered the idle state)
2-IDLE (HPMM has entered the idle state)
3-PF_IOIDL (Partial failure in one or more idle IOPs)
4-PF_IDLE (Partial failure in HPMM that is in idle state)
5-PartFail (Partial failure in HPMM that is in run state)
6-Fail (HPMM has sent a "failed" message to the NIM)
7-Alive (No event reports or point processing)
8-Loading (HPMM's personality or database is loading)
9-PowerOn (Transitional state when power applied to HPMM)
10-OffNet (NIM cannot communicate with HPMM)
12-NotConf (HPMM cannot be found on the UCN)
13-ConfgMis (IOP mismatch in NIM Box point)
19-Standby
20-S_OK (OK in I/O simulation mode)
21-S_IOIDL (IOIDL in I/O simulation mode)
22-S_IDLE (IDLE in I/O simulation mode)
23-S_PFIOIL (PF_IOIDL in I/O simulation mode)
24-S_PFIDLE (PF_IDLE in I/O simulation mode)
25-S_PtFail (PartFail in I/O simulation mode)
26-S_Pause (HPM is in the simulation pause state)
27-StandbySF
28-Upgrade
29-UpgradeSF

Helpful Hint: Loading the HPMM's operating personality requires NODESTS = Alive.

NODETYP (NIM)
Type: E:$UCNNDTY UCN Node Type—Defines the node type of this UCN node.
Lock: PtBld
Default: NIM
PtRes: NIM
Range: NIM (Network Interface Module)

NODETYP (HPM Box)


Type: E:$UCNNDTY UCN Node Type—Defines the node type of this UCN node.
Lock: PtBld
Default: HPM
PtRes: NIM
Range: HPM (High-Performance Process Manager)

HPM Parameter Reference Dictionary N-14 8/97


NODETYP

NODETYP (HPM Points)


Type: E:$UCNNDTY UCN Node Type—Defines which node type supports this point.
Lock: PtBld
Default: HPM
PtRes: NIM
Range: HPM (High-Performance Process Manager)

NODFSTAT (HPM Box)


Type: E:$NODFSTA Node's Functional Status—Defines the status of the UCN node.
Lock: Supr
Default: Basic
PtRes: NIM
Range: Full (All LCN devices can read/write from/to this node)
Basic (AM and CM cannot write to this node)

NODINPTS (DevCtl, DigComp)


Type: Integer Number of Digital Inputs—Defines the number of digital input connections to
Lock: PtBld this data point.
Default: 1
PtRes: HPM
Range: 0 (No inputs)
1 (One input)
2 (Two inputs)

NODOPTS (DevCtl, DigComp)


Type: Integer Number of Digital Outputs—Defines the number of digital output connections
Lock: PtBld from this data point.
Default: 1
PtRes: HPM
Range: 0 (No outputs)
1 (One output)
2 (Two outputs)
3 (Three outputs)

HPM Parameter Reference Dictionary N-15 8/97


NOGINPTS

NOGINPTS (RegPV, RegCtl)


Type: Number of General Input Connections—
Lock:
Default:
PtRes: HPM
Range: 0 - 4

Helpful Hint: NOGINPTS + NOGOPTS cannot exceed four.

NOGOPTS (RegPV, RegCtl)


Type: Number of General Ouptut Connections—
Lock:
Default:
PtRes: HPM
Range: 0 - 4

Helpful Hint: NOGINPTS + NOGOPTS cannot exceed four.

NOLINPTS (DevCtl, Logic)


Type: Integer Number of Logic Inputs—Indicates the number of logic inputs to this logic or
Lock: View (Logic), Device Control slot.
PtBld (DevCtl)
Default: 12 (Logic)
0 (DevCtl)
PtRes: HPM
Range: 0 to 12

NOLOGBLK (Logic)
Type: Integer Number of Logic Blocks—Indicates the number of logic blocks that have been
Lock: View configured for a particular logic slot.
Default: N/A
PtRes: HPM
Range: 0 to 24

NOLOPTS (DevCtl, Logic)


Type: Integer Number of Logic Output Connections—Indicates the number of output
Lock: View (Logic) connections from this logic slot.
PtBld (DevCtl)
Default: N/A
PtRes: HPM
Range: 0 to 12 (Logic), 0 to 2 (DevCtl)

HPM Parameter Reference Dictionary N-16 8/97


NOOVRRUN

NOOVRRUN (ProcMOD)
Type: Integer Number of Overruns—Indicates the number of times the point has overrun its
Lock: View CNFPU allocation since the last reset.
Default: 0
PtRes: HPM
Range:

Helpful Hint: NOOVRRUN is reset along with AVGPU and MAXPU

NOOVRRUN (ProcMod)
Type: Integer Number of Overruns—Specifies the number of times the point has overrun its
Lock: View CNFPU allocation since the last reset
Default: 0
PtRes: HPM
Range: 0-4

NOPGATE (DevCtl)
Type: Integer Number of Primary Gates—Indicates the number of primary gates configured for
Lock: PtBld a particular Device Control slot.
Default: 0
PtRes: HPM
Range: 0 to 4

Helpful Hint: All configured primary gates must have at least one input.

NOPINPTS (RegPV)
Type: Integer Number of PV Input Connections—Defines the number of PV input
Lock: View connections to this algorithm.
Default: Based on
PVALGID,
PVEQN, N
PtRes: HPM
Range: 0 to 6

HPM Parameter Reference Dictionary N-17 8/97


NOPTS

NOPTS(0 - 64)
Type: Integer Number of Points Per Cycle—Defines ...
Lock: View
Default: 0 Index = 0 used for total count
PtRes: HPM Index = 1 - 64 used for per cycle count
Range:

Helpful Hint: The total count may not be equal to the sum of all cycles because most points
are in more than one cycle.

NORMCYCL
Type: Integer Normal Execution Cycle—Specifies the normal execution cycle.
Lock: PtBld
Default:
PtRes: HPM
Range: 1 - 64 for points with PERIOD = 4 seconds
1 - 32 for points with PERIOD = 2 seconds
1 - 16 for points with PERIOD = 1 seconds
1-8 for points with PERIOD = 0.5 seconds
1-4 for points with PERIOD = 0.25 seconds
1-2 for points with PERIOD = 0.125 seconds
1 for points with PERIOD = 0.625 seconds

NORQUAVG (NIM, HPM Box)


Type: Real Average number of Nodes to which UCN Requests are made—Indicates the
Lock: View average number of UCN nodes per second that this node is requesting
Default: 0 communications with.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NORQUMAX (NIM, HPM Box)


Type: Real Maximum number of Nodes to which UCN Requests are made—Indicates the
Lock: View maximum number of UCN nodes per second that this node is requesting
Default: 0 communications with.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary N-18 8/97


NORSPAVG

NORSPAVG (NIM, HPM Box)


Type: Real Average number of Nodes to which UCN Responses are made—Indicates the
Lock: View average number of UCN nodes per second that this node is responding to.
Default: 0
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NORSPMAX (NIM, HPM Box)


Type: Real Maximum number of Nodes to which UCN Responses are made—Indicates
Lock: View the maximum number of UCN nodes per second that this node is responding
Default: 0 to.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NORSSEQ (RampSoak)
Type: Integer Number of Ramp/Soak Pairs in the Sequence
Lock: Eng/PB
Default: 2
PtRes: HPM
Range: 2 to 12

NOSGATE (DevCtl)
Type: Integer Number of Secondary Gates—Indicates the number of secondary gates configured
Lock: PtBld for a particular Device Control slot.
Default: 0
PtRes: HPM
Range: 0 to 2

Helpful Hint: All configured secondary gates must have at least one input.

NOSIOVRD (DevCtl, DigComp)


Type: Real Number of Safety Interlock Overrides—The number of safety interlock overrides
Lock: View that have accumulated since the most recent reset of maintenance statistics.
Default: 0.0
PtRes: HPM
Range: 0 (No limit)

HPM Parameter Reference Dictionary N-19 8/97


NOSTATES

NOSTATES (DevCtl, DigComp)


Type: Integer Number of Digital States—Defines the number of states in this point.
Lock: PtBld • State 1 is the first active state
Default: 2 • State 0 is the inactive (middle) state
PtRes: HPM • State 2 is the second active state
Refer to the HPM Control Functions and Algorithms manual for a detailed
description.
Range: 2 (Two states can be configured: STATE 0 and STATE 1)
3 (Three states can be configured: STATE 0, STATE 1, and STATE 2)

NOTRAAVG (NIM, HPM Box)


Type: Real Average number of Nodes to which UCN Transactions are made. This value
Lock: View indicates the average number of UCN nodes (per second) that this node is
Default: 0 communicating with (both requests and responses).
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NOTRAMAX (NIM, HPM Box)


Type: Real Maximum number of Nodes to which UCN Transactions are made. This
Lock: View value indicates the maximum number of UCN nodes (per second) that this
Default: 0 node is communicating with (both requests and responses).
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NOTRANS0–2 (DevCtl, DigComp)


Type: Real Accumulated Transitions—The number of transitions to each state of the
Lock: View OPFINAL parameter since the most recent reset of maintenance statistics. The
Default: 0.0 MAXTRAN parameter does not limit the number of transactions unless the user
PtRes: HPM writes a program to read MAXTRAN, comparing it to NOTRANS, and thereby
causing it to stop.
Range: 0 (No limit)

NPARAVG (NIM, HPM Box)


Type: Real Average number of UCN Parameter Accesses per Second—Average number of
Lock: View UCN parameter accesses per second between this node and all other nodes,
Default: 0 including both requests and responses.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary N-20 8/97


NPARMAX

NPARMAX (NIM, HPM Box)


Type: Real Maximum number of UCN Parameter Accesses per Second—Maximum
Lock: View number of UCN parameter accesses per second between this node and all other
Default: 0 nodes, including both requests and responses.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NPMSLOT (HPM Box)


Type: Integer Number of Process Module Slots—Refer to the HPM Control Functions and
Lock: PtBld Algorithms manual for a detailed description of HPM processing capacity.
Default: 0
PtRes: HPM
Range: 0 to 250

NPRQUAVG(0-64) (NIM, HPM Box)


Type: Real Average number of UCN Parameter Requests—Average number of UCN
Lock: View parameter requests per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is an odd number (1, 3, 5,...63). Using an even number
results in a Parameter_Invalid error. Using n = 0 returns average total number of
parameter requests to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NPRQUMAX(0-64) (NIM, HPM Box)


Type: Real Maximum number of UCN Parameter Requests—Maximum number of UCN
Lock: View parameter requests per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is an odd number (1, 3, 5,...63). Using an even number
results in a Parameter_Invalid error. Using n = 0 returns maximum total number of
parameter requests to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary N-21 8/97


NPRSPAVG

NPRSPAVG(0-64) (NIM, HPM Box)


Type: Real Average number of UCN Parameter Responses—Average number of UCN
Lock: View parameter responses per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is an odd number (1, 3, 5,...63). Using an even number
results in a Parameter_Invalid error. Using n = 0 returns average total number of
parameter responses to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NPRSPMAX(0-64) (NIM, HPM Box)


Type: Real Maximum number of UCN Parameter Responses—Maximum number of
Lock: View UCN parameter responses per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is an odd number (1, 3, 5,...63). Using an even number
results in a Parameter_Invalid error. Using n = 0 returns maximum total number of
parameter responses to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NPVSLOT (HPM Box)


Type: Integer Number of Regulatory PV Slots—Refer to the HPM Control Functions and
Lock: PtBld Algorithms manual for a detailed description of HPM processing capacity.
Default: 0
PtRes: HPM
Range: 0 to 125

HPM Parameter Reference Dictionary N-22 8/97


NRMATRFL

NRMATRFL (DigComp, DevCtl, RegCtl)


Type: Logical Normal Mode Attribute Flag—indicates if this point is in the configured
Lock: View Normal Mode attribute.
Default: N/A
PtRes: HPM
Range: ON - (point is in the configrured Normal mode attribute )
Off - (point is not in the configured Normal Mode attribute or Normal Mode attribute is
not configured)

Helpful Hint: If Normal mode attribute is not configured then the value returns to OFF.

NRMMODFL (RegCtl)
Type: Logical Normal Mode Flag—indicates if the mode for this point is normal mode.
Lock: View
Default: N/A
PtRes: HPM
Range: On - (Point is in configured normal mode)
Off - (Point is not in the configured normal mode or normal mode is not configured)

NSCANITM (HPM Box)


Type: Integer Number of Scan Items in HPM Scan Table.
Lock: View
Default: 0
PtRes: HPM
Range: 0 - 50

HPM Parameter Reference Dictionary N-23 8/97


NSIO

NSI0 (DevCtl, DigComp)


Type: Logical Inverted Interlocks Value—The negative value of the corresponding interlock.
Lock: Engr
Default: On
PtRes: HPM
Range: On (Safety interlock inactive)
Off (Safety interlock active)

Helpful Hint: This parameter can be changed by the engineer only if the point is inactive, or if
the HPM is idle.

NSTRING (HPM Box)


Type: Integer Number of Strings in HPM Box Data Point
Lock: PtBld
Default: 0
PtRes: HPM
Range: 0 to 16,384

NSTRING (Array)
Type: Integer Number of Strings in Array Point String Array—Defines the number of strings
Lock: PtBld (length specified by the STRLEN parameter) mapped to the Array point from
Default: 0 either the HPM box (EXTDATA≠ IO_STR), or a serial interface IOP-connected
PtRes: HPM device (EXTDATA=IO_STR).
Range: 0 to 8 (When EXTDATA=IO_STR)
0 to 240 (When EXTDATA≠ IO_STR)

Helpful Hint: When EXTDATA≠ IO_STR, the range for this parameter applies regardless
of the value of the STRLEN parameter (up to 240 strings, either 8, 16, 32, or
64 characters in length can be mapped to the Array point from the HPM box).
When EXTDATA=IO_STR, only 64 characters of string data are available
(i.e., one 64-character string, two 32-character strings, four 16-character
strings, or eight 8-character strings).

NTIME (HPM Box)


Type: Integer Number of Times in HPM Box Data Point
Lock: PtBld
Default: 0
PtRes: HPM
Range: 0 to 4,096

HPM Parameter Reference Dictionary N-24 8/97


NTIME

NTIME (Array)
Type: Integer Number of Times in Array Point Time Array—Defines the number of Times the
Lock: PtBld Array point has mapped from the HPM box.
Default: 0
PtRes: HPM
Range: 0 to 240

NTIMER (HPM Box)


Type: Integer Number of Timer Points in the HPM Box Data Point
Lock: View
Default: 64
PtRes: HPM
Range: 64

NTRAAVG (NIM, HPM Box)


Type: Real Average number of UCN Transactions —Average number of UCN
Lock: View transactions (requests and responses) per second between this node and all other
Default: 0 nodes.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NTRAMAX (NIM, HPM Box)


Type: Real Maximum number of UCN Transactions —Maximum number of UCN
Lock: View transactions (requests and responses) per second between this node and all other
Default: 0 nodes.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary N-25 8/97


NTRQUAVG

NTRQUAVG(0-64) (NIM, HPM Box)


Type: Real Average number of UCN Transaction Requests—Average number of UCN
Lock: View transaction requests per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is typically an odd number (1, 3, 5,...63). Using an even
number results in a Parameter_Invalid error. Using n = 0 returns average total
number of transaction requests to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NTRQUMAX(0-64) (NIM, HPM Box)


Type: Real Maximum number of UCN Transaction Requests—Maximum number of
Lock: View UCN transaction requests per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is an odd number (1, 3, 5,...63). Using an even number
results in a Parameter_Invalid error. Using n = 0 returns maximum total number of
transaction requests to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NTRSPAVG(0-64) (NIM, HPM Box)


Type: Real Average number of UCN Transaction Responses—Average number of UCN
Lock: View transaction responses per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is an odd number (1, 3, 5,...63). Using an even number
results in a Parameter_Invalid error. Using n = 0 returns average total number of
transaction responses to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary N-26 8/97


NTRSPMAX

NTRSPMAX(0-64) (NIM, HPM Box)


Type: Real Maximum number of UCN Transaction Responses—Maximum number of
Lock: View UCN transaction responses per second issued from this node to node n.
Default: 0
PtRes: HPM
Range: N/A

NOTE

The node address (n) is an odd number (1, 3, 5,...63). Using an even number
results in a Parameter_Invalid error. Using n = 0 returns maximum total number of
transaction responses to all other nodes.

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

NTWKNUM
Type: Integer Network Number—Defines on which UCN the NIM and HPMs reside.
Lock: PtBld
Default: N/A`
PtRes: NIM
Range: 1 to 20

NXTPINAM
Type: String_8 Next Personality Image File—Defines the personality Image file that will be
Lock: Eng loaded on the next personallity load request for this IOP.
Default: N/A
PtRes: IOP
Range: ?

NXTSOAKV (RampSoak)
Type: Real Next Soak Value
Lock: View
Default: N/A
PtRes: HPM
Range: > 0.0

HPM Parameter Reference Dictionary N-27 8/97


HPM Parameter Reference Dictionary N-28 8/97
OFFNRMFL

-O-

OFFNRMFL
Type: Logical Off-Normal Alarm Flag—Indicates whether an off-normal alarm has been
Lock: View detected at this data point.
Default: Off
PtRes: HPM
Range: Off (No alarm)
On (Current PV state is not the same as the configured PVNORMAL state.)

OFFNRMPR
Type: E:ALPRIOR Offnormal Alarm Priority—Indicates priority of the off normal or change of state
Lock: ENGR alarms.
Default: Low
PtRes: NIM
Range: Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

OFFPULSE (DigOut)
Type: Real Off Pulse Command—Command that sets output SO to Off for the specified
Lock: Oper number of seconds. At the end of the pulse time, SO is set to On. If 0.0 is
Default: N/A entered for OFFPULSE, SO is immediately set to On.
PtRes: HPM
Range: 0.0 to 60.0 seconds

Helpful Hint: OFFPULSE can be written to by only those entities that possess the
HPMM Cont_Ctl (continuous control) access level. These are Digital
Composite points, Logic points, and Regulatory Control Position
Proportional points.

HPM Parameter Reference Dictionary O-1 8/97


OLDAV

OLDAV (DigIn)
Type: Integer Old Accumulated Value—The value of parameter AV (accumulated value) just
Lock: View before the accumulator was reset. This parameter makes the previous
Default: N/A accumulated value available for those functions that need it.
PtRes: HPM
Range: >0

OLDAV (Totalizr)
Type: Real Old Accumulated Value—The value of parameter PVCALC (calculated PV) just
Lock: View before it is reset. This parameter makes the previous total available to those
Default: N/A functions that need it.
PtRes: HPM
Range: > 0.0

ONPULSE (DigOut)
Type: Real On Pulse Command—Command that sets output SO to On for the specified
Lock: Oper number of seconds. At the end of the pulse time, SO is set to Off. If 0.0 is
Default: N/A entered for ONPULSE, SO is immediately set to Off.
PtRes: HPM
Range: 0.0 to 60.0 seconds

Helpful Hint: ONPULSE can be written to by only those entities that possess the HPMM
Cont_Ctl (continuous control) access level. These are Digital Composite
points, Logic points, and Regulatory Control Position Proportional points.

OP (AnalgOut)
Type: Real Output in Percent—Defines the output value from this point in percent.
Lock: Oper
Default: -6.9% of full scale
PtRes: HPM
Range: -6.9 to 106.9%

Helpful Hint: To manually change the output value requires MODE = Man and
REDTAG = Off.

HPM Parameter Reference Dictionary O-2 8/97


OP

OP (DevCtl, DigComp)
Type: E:SD-ENM:STATETXT Digital State Output—Indicates the last commanded output
Lock: Oper state. See also OPFINAL. For Status Outputs, use SO.
Default: STATETXT(0)
PtRes: HPM
Range: STATETXT(0) Descriptor
STATETXT(1) Descriptor
STATETXT(2) Descriptor (internally set to $NULL for two-state devices)
STATETXT(3) None (Not configurable)

Helpful Hint: OP indicates text for the last commanded output state (i.e., On, Run, etc.).
Output state change requires MODE = Man, SHUTDOWN = Off, and
REDTAG = Off.

OP (DigOut)
Type: Real Pulsed Digital Output—OP is the percent on-time for the pulsed output. It can
Lock: Prog be written to by only the controlling slot in the HPMM, such as from the
Default: 0.0% PosProp RegCtl algorithm. Output change requires DOTYPE = Pwm. OP
PtRes: HPM (DigOut) has the same access-level requirement as OFFPULSE and ONPULSE;
Range: 0.0 to 100.0% the writing entity must have an HPMM access level of Cont_Ctrl (continuous
control). For Status Outputs, use SO.

For direct action, pulse-on time is calculated as follows:

Pulse On-Time = OP% * PERIOD


100
For reverse action:

Pulse On-Time = 100% - OP% * PERIOD


100
Refer to PERIOD parameter for length of period.

OP (RegCtl)
Type: Real Regulatory Control Output—OP is derived from CV, the variable
Lock: Oper calculated by the control algorithm. OP is checked for minimum
Default: -6.9% of full scale output change, output rate-of-change, and output high and low limits.
PtRes: HPM If any of the limits is exceeded, OP is adjusted or clamped as applicable.
Range: -6.9 to 106.9% OP remains in percent of full scale if it is going to a final control
element through an IOP Card. If OP is going to a secondary data point,
its value is converted to the engineering units of the receiving data
point's setpoint (SP).

Helpful Hint: OP change requires MODE = Man, SHUTDOWN = Off, and REDTAG = Off.
If the OP is manually set above or below the OP limits and the mode is then
changed to automatic or cascade, a process bump may occur.

HPM Parameter Reference Dictionary O-3 8/97


OPALDB

OPALDB (RegCtl)
Type: Real Output Alarm Dead Band—The deadband for the Regulatory Control OP
Lock: EngPB alarm. It is used to prevent excessive recurrence of alarms by adjusting
Default: 5 Output Units the range of the output at which the alarm "returns to normal."
PtRes: HPM Available on Release 510 and later software.
Range: 0 to 25 Output Units

Helpful Hint: The value of OPALDB must be less than or equal to (OPHITP - OPLOTP)/2.

OPCHAR
Type: Logical Output Characterization Option—Defines whether the output
Lock: PtBld characterization option is to be used for this data point. If this option
Default: Off is to be implemented, the user must supply the values for the input
PtRes: HPM coordinates (OPIN 1–4) and output coordinates (OPOUT 1–4). Refer to
the HPM Control Functions and Algorithms manual for a detailed
description of output characterization.
Range: On (Output characterization is to be used)
Off (Output characterization is not to be used)

OPCMD (DevCtl, DigComp)


Type: Logical Output Command
Lock: Prog
Default: Off
PtRes: HPM
Range: Off (Commands the output state to State0)
On (Commands the output state to State1)

Helpful Hint: If state change did not occur, OPCMD has to be set to the current state,
and then to the desired state.

OPCMD
Type: E:$OPCMD Output Command—Indicates the current output command.
Lock: View
Default: NA
PtRes: HPM
Range: 0-Idle (Output is not being affected by Output Command)
1-Lower (Output is being lowered)
2-Raise (Output is being raised)

HPM Parameter Reference Dictionary O-4 8/97


OPEU

OPEU
Type: Real Output Value in Engineering Units
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

OPFINAL (AO)
Type: Real Final Percent Output Sent to Control Element—Output value after
Lock: View direct or reverse control action and output characterization have all been
Default: -6.9% of applied. If output has been configured for direct action (OPTDIR),
full scale 0.0% represents 4 mA to the control element and 100% represents 20
PtRes: HPM mA. If configured for reverse action, 0.0% represents 20 mA, and
Range: N/A 100% represents 4 mA.

OPFINAL (DevCtl, DigComp)


Type: E:SD_ENM:STATETXT
Lock: Oper
Default: Statetxt(0) Final Output Sent to Control Element—The output value that was last stored.
PtRes: HPM This value can differ from the OP parameter if a sealin has occurred, state change
is active, or the Array/SI read-back check evaluates OPFINAL to be NONE. If
LOCALMAN = ON, then OP and OPFINAL follow the PV.

Range: Statetxt(0) (Self-defining enumeration)


Statetxt(1) (Self-defining enumeration)
Statetxt(2) (Self-defining enumeration)—internally set to $NULL for two-state devices.
Statetxt(3) NONE (not configurable)

OPHAFL (RegCtl)
Type: Logical Output High Alarm Flag—Indicates when a Regulatory Control Output High
Lock: View alarm has been detected at this data point. This flag is set when the output value
Default: Off (OP) exceeds OPHITP and is reset when OP is below OPHITP minus the
PtRes: HPM deadband. Available on Release 510 and later software.

Range: Off (OP High alarm is off)


On (OP High alarm is on)

Helpful Hint: Refer to the diagram with OPLAFL.

HPM Parameter Reference Dictionary O-5 8/97


OPHIFL

OPHIFL (RegCtl)
Type: Logical Output High Limit Flag—Indicates whether the OP value has reached its upper
Lock: Prog limit specified by OPHILM. If this parameter is set by a program, it will
Default: Off inhibit “raise” commands.
PtRes: HPM
Range: Off
On (OP value has reached its upper limit)

OPHILM
Type: Real Output High Limit in Percent
Lock: Supr
Default: 105.0%
PtRes: HPM
Range: OPLOLM to 106.9%,
NaN

Helpful Hint: Entering NaN disables limit checking by forcing OPHILM to its extreme value
(106.9%).

OPHIPR (RegCtl)
Type: E:Alprior Output High Alarm Priority—Specifies the priority of the Regulatory Control
Lock: EngPB Output High alarm. Available on Release 510 and later software.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

HPM Parameter Reference Dictionary O-6 8/97


OPHISRC

OPHISRC
Type: Universal Output High Flag Input Source—Defines the input connection that fetches the
Ent.Prm OPHIFL parameter to determine windup state.
Lock: PtBld
Default: Null
PtRes: HPM
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

Some possible input-connection sources are


a."DigIn slot Tagname.PVFL"
b."Logic slot Tagname.SO(nn)" where nn = 1–24
c."Logic slot Tagname.Fl(nn)" where nn = 1–12
d."ProcMod slot Tagname.Fl(nnn)" where nnn = 1–127
e."Box Flag slot Tagname.PVFL
f."!Box.FL(nnnn)" for a box flag that resides in the same box where nnnn = 1–16, 384
g."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the NIM UCN address, xx is the HPM box number, and
nnnn = 1–4095 (Data access limit)

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DI (Digital Input)
mm is the IOP Card number (1–40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

OPHITP (RegCtl)
Type: Real Output High Alarm Trip Point—The Regulatory Control Output High alarm is
Lock: Supr set when the output value (OP) exceeds the high alarm limit specified by
Default: NaN OPHITP. The alarm is removed when OP returns to normal. A suitable dead
PtRes: HPM band is provided by OPALDB. See also OPHIPR and the drawing with
OPLAFL. Available on Release 510 and later software.

Range: OPLOTP to OPHILM, NaN

Helpful Hint: The Regulatory Control Output High alarm is only available for points
configured as full. The alarm is disabled if OPHITP is not configured.

OPIN0
Type: Real Input Coordinate Number 0 in Percent—Defines the OPIN0 coordinate when
Lock: View output characterization has been selected (OPCHAR is On). This coordinate is
Default: -6.9% fixed at -6.9%.
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary O-7 8/97


OPIN1-4

OPIN1–4
Type: Real Input Coordinate Number 1, 2, 3, or 4 in Percent—Define the OPIN1–OPIN4
Lock: Supr coordinates when output characterization has been selected (OPCHAR is On).
Default: N/A
PtRes: HPM
Range: ≥ previous coordinate
≤ next coordinate

OPIN5
Type: Real Input Coordinate Number 5 in Percent—Defines the OPIN5 coordinate when
Lock: View output characterization has been selected (OPCHAR is On). This coordinate is
Default: 106.9% fixed at 106.9%.
PtRes: HPM
Range: N/A

OPLAFL (RegCtl)
Type: Logical Output Low Alarm Flag—Indicates if a Regulatory Control Output Low alarm
Lock: View has been detected at this data point. This flag is set when the output value (OP)
Default: Off is less than OPLOTP and is reset when OP is above OPLOTP plus the
PtRes: HPM deadband. Available on Release 510 and later software.

Range: Off (OP Low alarm is off).


On (OP Low alarm is on).

The drawing below illustrates the relationship of the output high/low alarm flags, the low
alarm trip point OPLOTP, and the deadband OPALDB.

OP

OPHITP
OPHAFL is turned off
if OP is below this point
OPALDB

OPLAFL is turned off


if OP is above this point

OPHITP - OPALDB

OPLOTP + OPALDB OPALDB


OPLOTP
0

HPM Parameter Reference Dictionary O-8 8/97


OPLOFL

OPLOFL
Type: Logical Output Low Limit Flag—Indicates whether the output value OP has reached the
Lock: Prog low limit. This parameter must be set by a program or logic point. It will
Default: Off inhibit "raise" commands.
PtRes: HPM
Range: Off (OP is above the low limit)
On (OP has reached the low limit)

OPLOLM
Type: Real Output Low Limit in Percent
Lock: Supr
Default: -5.0%
PtRes: HPM
Range: -6.9% to OPHILM,
NaN

Helpful Hint: Entering NaN disables limit checking by forcing OPLOLM to its extreme
value (-6.9%).

OPLOPR (RegCtl)
Type: E:Alprior Output Low Alarm Priority—Specifies the priority of the Regulatory Control
Lock: EngPB Output Low alarm. Available on Release 510 and later software.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

HPM Parameter Reference Dictionary O-9 8/97


OPLOSRC

OPLOSRC
Type: Universal Output Low Flag Input Source—Indicates which input connection fetches the
Ent.Prm OPLOFL parameter to determine the windup state.
Lock: HPM
Default: PtBld
PtRes: Null
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

Some possible input-connection sources are


a."DigIn slot Tagname.PVFL"
b."Logic slot Tagname.SO(nn)" where nn = 1–24
c."Logic slot Tagname.Fl(nn)" where nn = 1–12
d."ProcMod slot Tagname.Fl(nnn)" where nnn = 1–127
e."Box Flag slot Tagname.PVFL
f."!Box.FL(nnnn)" for a box flag that resides in the same box where nnnn = 1–4095
g."$NMhhBxx.FL(nnnn)" for a box flag that resides in a different HPM box on the same
UCN; hh is the NIM UCN address, xx is the HPM box number, and
nnnn = 1–4095 (Data access limit)

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as DI (Digital Input)
mm is the IOP Card number (1–40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

OPLOTP (RegCtl)
Type: Real Output Low Alarm Trip Point—The Regulatory Control Output Low alarm is
Lock: Supr set when the output value (OP) drops below the low alarm limit specified by
Default: NaN OPLOTP. The alarm is removed when OP returns to normal. A suitable dead
PtRes: HPM band is provided by OPALDB. See also OPLOPR. Available on Release 510
and later software.

Range: OPLOLM to OPHITP, NaN

Helpful Hint: The Regulatory Control Output Low alarm is only available for points
configured as full. The alarm is disabled if OPLOTP is not configured.

HPM Parameter Reference Dictionary O-10 8/97


OPMCHLM

OPMCHLM
Type: Real Output Minimum Change in Percent
Lock: Supr
Default: 0.0
PtRes: HPM
Range: > 0.0,
NaN

Helpful Hint: OP changes only if new output % - old output % is greater than the percentage
in parameter OPMCHLM. Entering NaN disables limit checking by forcing
OPMCHLM to its extreme value (0.0).

OPOUT0
Type: Real Output Coordinate Number 0 in Percent—Defines the OPOUT0 coordinate when
Lock: View output characterization has been selected. (OPCHAR = On) This coordinate is
Default: -6.9% fixed at a value of -6.9%.
PtRes: HPM
Range: N/A

OPOUT1–4
Type: Real Output Coordinates Number 1, 2, 3, or 4 in Percent—Define the OPOUT1–
Lock: Supr OPOUT4 coordinates when output characterization has been selected (OPCHAR
Default: N/A is On).
PtRes: HPM
Range: ≥ previous coordinate
≤ next coordinate

OPOUT5
Type: Real Output Coordinate Number 5 in Percent—Defines the OPOUT5 coordinate when
Lock: View output characterization has been selected. (OPCHAR = On) This coordinate is
Default: 106.9% fixed at a value of 106.9%.
PtRes: HPM
Range: N/A

OPRATRFL (DevCtl, DigComp, RegCtl)


Type: Logical Operator Mode Attribute Flag—Indicates whether the current mode attribute is
Lock: View Operator.
Default: N/A
PtRes: HPM
Range: Off (Current mode attribute is Program or None)
On (Current mode attribute is Operator)

HPM Parameter Reference Dictionary O-11 8/97


OPRINPUT

OPRINPUT (ProcMod)
Type: Real Operator Input—Defines the value entered by the operator in response to the last
Lock: Oper sequence message.
Default: 0.0
PtRes: HPM
Range: N/A

OPROCLM
Type: Real Output Rate of Change Limit in Percent Per Minute
Lock: Supr
Default: NaN
PtRes: HPM
Range: > 0.1
NaN

Helpful Hint: Entering NaN disables limit checking.

OPTDIR (AO)
Type: E:POLARITY Analog Output Direct/Reverse Action—Defines the output action of the
Lock: Eng/PB OPFINAL value of the data point.
Default: Direct
PtRes: HPM
Range: 0-Direct (For final OP: 0% = 4 mA; 100% = 20 mA)
1-Reverse (For final OP: 0% = 20 mA; 100% = 4 mA)

OPTDIR (DigOut)
Type: E:POLARITY Output Direction—Defines the direct/reverse action of the PWM digital
Lock: Eng/PB output.
Default: Direct
PtRes: HPM
Range: 0-Direct (OP is the % On time)
1-Reverse (OP is the % Off time)

OROFFSET (ORSel)
Type: Logical Override Offset—When OROFFSET is On, override initialization of Pid-type
Lock: Eng/PB algorithm points connected to this ORSel algorithm applies an override offset
Default: On equal to Gain times Error (PV - SP).
PtRes: HPM
Range: Off (No override offset is applied)
On (Offset of Gain times Error is applied)

HPM Parameter Reference Dictionary O-12 8/97


OROPT

OROPT (DevCtl, DigComp)


Type: Logical Override Option—Allows the operator to bypass permissive and override
Lock: Eng/PB interlocks by setting BYPASS On.
Default: Off
PtRes: HPM
Range: On (Override option enabled)
Off (Override option disabled)

OROPT (ORSel)
Type: Logical Override Option—Defines whether the operator can put the point in a bypass
Lock: Eng/PB state where any of the X1-X4 inputs can be bypassed. Also, when on, the
Default: Off feedback value is propagated to nonselected primaries of the override selector
PtRes: HPM algorithm. Refer to the HPM Control Functions and Algorithms manual for a
detailed description.
Range: Off (No override)
On (Inputs can be overridden)

OUT0–12 (GenLin)
Type: Real Output Coordinates 0 -12—Define the output value at the respective coordinates.
Lock: Supr
Default: NaN
PtRes: HPM
Range: Any value but NaN

OVERFLOW
Type: Logical Accumulation Overflow Flag—Indicates whether the accumulated value has
Lock: View overflowed.
Default: Off
PtRes: HPM
Range: Off (No overflow)
On (Overflow)

HPM Parameter Reference Dictionary O-13 8/97


OVERLAP

OVERLAP (Array)
Type: Integer Overlapping Array Slot Number—Indicates the Array slot number containing the
Lock: View data being referenced by the slot currently being built.
Default: 0
PtRes: HPM
Range: 0 through the number of Array slots (NARRSLOT)

OVERPHAS (ProcMod)
Type: E:JUMPDIR Override Current Phase—Allows the operator to override the current phase of the
Lock: ONPROC and sequence by skipping forward to the next phase, or backward to the previous
CNTLLOCK phase. A phase can be overridden in this manner only when the sequence
parameters execution state is PAUSE, FAIL, or ERROR.
Default: Blank
PtRes: HPM
Range: 0-Forward (Skip to next phase)
1-Backward (Go back to previous phase)

OVERSTAT (ProcMod)
Type: E:JUMPDIR Override Current Statement—Allows the operator to override the current
Lock: ONPROC and statement of the sequence by skipping forward to the next statement, or backward
CNTLLOCK to the previous statement. A statement can be overridden in this manner only
parameters when the sequence execution state is PAUSE, FAIL, or ERROR.
Default: Blank
PtRes: HPM
Range: 0-Forward (Skip to next statement)
1-Backward (Go back to previous statement)

OVERSTEP (ProcMod)
Type: E:JUMPDIR Override Current Step—Allows the operator to override the current step of the
Lock: ONPROC sequence by skipping forward to the next step, or backward to the previous step.
Default: Blank A step can be overridden in this manner only when the sequence execution state
PtRes: HPM is PAUSE, FAIL, or ERROR.
Range: 0-Forward (Skip to next step)
1-Backward (Go back to previous step)

HPM Parameter Reference Dictionary O-14 8/97


OVERVAL

OVERVAL
Type: Integer Overview Value in Percent—Defines the amount of deviation (PV - SP, in
Lock: Eng/PB percent) that causes the PV to reach the overview limit. For digital points, the
Default: 25 display shows the current state of the point.
PtRes: NIM As shown in Figure O-1, The baseline shows the normal operating value for this
PV.
Range: 0 to 100 (Entering a 0 suppresses the value; value is not shown on the display)

OVERVIEW LIMIT

DEVIATION TO REACH
OVERVIEW LIMIT

BASELINE
(Normal Value)

Figure O-1 — Overview Limit 1302

OVRCTIM (DevCtl)
Type: Time Time Over High Trip Limit—The amount of time the SECVAR parameter is
Lock: View continuously greater than the SECVAR high trip limit.
Default: 0
PtRes: HPM
Range: Duration (0 to 9999 days, with a resolution to 1 second)

OVRDALOP (DevCtl, DigComp)


Type: E:$OVRALOP Override Alarm Option—The override alarm option for I0, I1, and I2
Lock: Eng/PB parameters.
Default: None
PtRes: HPM
Range: 0-None (No override alarming)
1-Auto_Rtn (Return to normal when override is cleared)
2-Cnfm_Rqd (Confirm to clear, after interlock is cleared)

HPM Parameter Reference Dictionary O-15 8/97


OVERDALPR

OVRDALPR (DevCtl, DigComp)


Type: E:ALPRIOR Override Alarm Priority—Defines the priority of an override alarm.
Lock: Engr
Default: Low
PtRes: HPM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

OVRDCONF (DevCtl, DigComp)


Type: Logical Override Confirmation Flag—Indicates one of the four override alarms
Lock: Oper SI0CONF or I0CONF-I2CONF has not yet been confirmed. This flag is also
Default: Off used to confirm the alarm.
PtRes: HPM
Range: Off (An alarm is not waiting for confirmation)
On (An alarm is waiting for confirmation)

OVRDDESC (DevCtl, DigComp)


Type: String_8 Override Alarm Descriptor—Input connections and logic gating are examined in
Lock: View order to determine which input was the source of change for the interlock. For
Default: Blank the Device Control point, descriptor text for this parameter is taken from
PtRes: HPM LIDESC (1-12). Descriptive text for the Digital Composite point is taken from
SI0 DESC or I0-I2 DESC parameters.

Range: SI0 Desc (Current interlock or input descriptor)


I0 - I2 Desc (Current interlock or input descriptor)
L1 - L12 Desc (Current interlock or input descriptor, Device Control only)

OVRDI0FL, OVRDI1FL, OVRDI2FL, OVRDSIFL


(DevCtl, DigComp)
Type: Logical Override and Safety Override Alarm Flag—Indicates that an override is active, or
Lock: View that a confirmable override was cleared, but not yet confirmed.
Default: Off
PtRes: HPM
Range: Off (Override flag is not active)
On (Override flag is active)

HPM Parameter Reference Dictionary O-16 8/97


P

-P-

P (FlowComp)
Type: Real Pressure Input—Indicates the measured actual gage pressure.
Lock: View
Default: 1.0
PtRes: HPM
Range: > 0.0

P0 (FlowComp)
Type: Real Zero Reference for Pressure—P0 is the zero reference pressure input and is in the
Lock: Supr same engineering units as the P input. P0 is typically 14.696 if P is in psig or
Default: 0.0 101.325 if P is in kiloPascals. Enter the absolute value of the number.
PtRes: HPM
Range: N/A

P0–P2 (DevCtl, DigComp)


Type: Logical Permissive Interlocks for Output States 0, 1, & 2—Permissive interlocks are
Lock: Engr controlled by logic slot outputs, and each interlock determines whether the
Default: On operator and user program are allowed to use the respective state, or are locked
PtRes: HPM out from that state. A permissive interlock (P0-P2) is provided for each state
(STATE0-STATE2). The permissive interlocks themselves never cause the
outputs to change. P0-P2 can be changed by a logic block or a program when
the point is active and the mode attribute is Program. Refer to the HPM
Control Functions and Algorithms manual for a detailed description.

Range: Off (Respective state is locked out)


On (Respective state is permitted to be used)

Helpful Hint: P0–P2 configuration requires PTEXECST = InActive or PNTSTATE = Idle.

P1–P6 (RegPV)
Type: Real PV Inputs 1-6—Indicates the current values at the inputs to the RegPV
Lock: View algorithm. For Totalizers, P2 is the floating point input of AV.
Default: NaN
PtRes: HPM
Range: N/A,
NaN

HPM Parameter Reference Dictionary P-1 8/97


P1STS

P1STS–P6STS
Type: E:PVVALST P1–P6 Status—Indicate the status of the up to six inputs at the RegPV
Lock: View algorithm.
Default: Bad
PtRes: HPM
Range: 0-Bad (Value is bad and replaced with NaN)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

PAUSETIM (DevCtl, DigComp)


Type: Integer State 0 Pause Time—The amount of time to pause in State 0 on an OP state
Lock: Supr change, if the STCHGOPT parameter equals STATE0.
Default: 0
PtRes: HPM
Range: 0 to 1000 seconds

PERIOD (ProcMod, Timer)


Type: Real Period—Defines the processing period in seconds.
Lock: View
Default: 1 seconds
PtRes: HPM
Range: 1 seconds

PERIOD (DevCtl, DigComp, Logic, RegCtl, RegPV)


Type: Real Period—Defines the processing period in seconds.
Lock: View
Default: 1 second
PtRes: HPM
Range: 0.25, 0.5, or 1.0 seconds

PERIOD
Type: Real Period—specifies the scan period in seconds.
Lock: PtBld
Default: .25 sec for Logic, DigComp, & DevCtl
.50 sec for RegPv and RegCtl
1.00 sec for ProcMod
PtRes: HPM
Range: 0.0625, 0.125, 0.25, 0.5, 1.0, 2.0, and 4.0 seconds

PERIOD (DigOut)
Type: Real Period—Defines length of period for an SO output from DigOut point that has
Lock: Eng/PB been configured for a PWM output.
Default: 10.0 seconds
PtRes: HPM
Range: 1.0 to 120.0 seconds

HPM Parameter Reference Dictionary P-2 8/97


PFDLYFL

PFDLYFL (RegCtl, RegPV, DevCtl, DigComp,


Logic, ProcMod)
Type: Logical PreFetch Delayed Flag—Set when prefetch data is not available for slot
Lock: View execution.
Default: Off
PtRes: HPM
Range: Off (prefetch data is available for slot execution.)
On (prefetch data is not available for slot execution.)

PGALGID(1)–(4) (DevCtl)
Type: E:$GTALGID Primary Gate Algorithm ID—Defines the algorithm IDs for primary gates. The
in an Array Boolean logic gates beginning with “P” have a user-defined pulse size.
(1..4)
Lock: PtBld
Default: Null
PtRes: HPM
Range: NULL (No algorithm)
AND (And Gate algorithm)
OR (Or Gate algorithm)
NAND (Nand Gate algorithm)
NOR (Nor Gate algorithm)
XOR (Exclusive Or Gate algorithm)
PAND (Pulse Nand Gate algorithm)
POR (Pulse Or Gate algorithm)
PNAND (Pulse Nand Gate algorithm)
PNOR (Pulse Nor Gate algorithm)
PXOR (Pulse Exclusive-Or Gate algorithm)

PGDSTN(1)–(4) (DevCtl)
Type: E:$GATDSTN Primary Gate Destination—Defines the output destination of the primary gate.
in an Array
(1..4)
Lock: PtBld
Default: None
PtRes: HPM
Range: None (No destination)
SI0 (Output goes to Safety Interlock)
I0, I1, I2 (Output goes to Interlock)
P0, P1, P2 (Output goes to Permissives)
SOCMD0, SOCMD1, SOCMD2 (Output is commanded to go to SOCMD0, 1 or 2)
OPCMD (Output is commanded to go to OPCMD parameter)
SG1, SG2 (Output goes to Secondary gates 1 or 2)

PGPLSWTH(1)–(4) (DevCtl)
Type: Integer Primary Gate Pulse Width—Indicates the pulse width for primary gates whose
in an Array algorithm starts with a “P”.
(1..4)
Lock: Supr
Default: 0
PtRes: HPM
Range: 0 to 8000 seconds

HPM Parameter Reference Dictionary P-3 8/97


PGSO

PGSO(1)–(4) (DevCtl)
Type: Logical Primary Gate Status Output—Indicates the output value of the primary gate.
in an Array
(1..4)
Lock: View
Default: Off
PtRes: HPM
Range: Off
On

PHASE (ProcMod)
Type: String_8 Phase Name—Indicates the current phase of the sequence executing in the
Lock: View process module.
Default: Spaces
PtRes: HPM
Range: N/A

PHASEAL (ProcMod)
Type: Logical Phase Alarm—Indicates whether the current phase of the sequence has been
Lock: View completed within the specified time.
Default: Off
PtRes: HPM
Range: On (Phase has not been completed in the specified time)
Off (No phase alarm)

PHASETIM (ProcMod)
Type: Integer Phase Time —Indicates the time remaining in minutes in the current phase
Lock: View before a phase alarm is generated. The maximum time allowed for the phase is
Default: 0 seconds defined by the phase statement.
PtRes: HPM
Range: 0 to 9999 minutes

PHREMTIM (ProcMod)
Type: Time Phase Time Remaining—Indicates the time remaining in time duration before a
Lock: View phase alarm is generated. This value is displayed in the HPM Detail display.
Default: 0 seconds
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary P-4 8/97


PIALGID

PIALGID (1)–(12) (DevCtl)


Type: E:$I1ALGID Primary Input Gate Algorithm ID—The XX algorithms compare this input to
in an Array the PINN (1)-(12) parameter, and the IN_SET algorithm compares it to the range
(1..12) of 10 values in the NNINSET (1)-(10) parameter. The XX2 algorithms compare
Lock: PtBld this input defined by the PISRC(1)-(12) parameter.
Default: Null
PtRes: HPM
Range: NULL (No algorithm)
INVERT (Invert Logical algorithm)
GT (Greater Than algorithm)
GE (Greater Than or Equal To algorithm)
LT (Less Than algorithm)
LE (Less Than or Equal To algorithm)
EQ (Equal To algorithm)
NE (Not Equal To algorithm)
GT2 (Greater Than algorithm)
GE2 (Greater Than or Equal To algorithm)
LT2 (Less Than algorithm)
LE2 (Less Than or Equal To algorithm)
EQ2 (Equal To algorithm)
NE2 (Not Equal To algorithm)
IN_SET (Compares the input to values in the INSET array)

PIDEADBD(1)–(12) (DevCtl)
Type: Real Primary Input Gate Deadband—The deadband for primary input gates that is
in an Array configured for an arithmetic algorithm.
(1..12)
Lock: Supr
Default: 1.0
PtRes: HPM
Range: >0

PIDFORM
Type: E:PIDFORM PID Controller Form—Defines the type of Pid controller form. Refer to the
Lock: Eng/PB HPM Control Functions and Algorithms manual for a detailed description.
Default: Interact
PtRes: HPM
Range: 0-Interact [(Proportional + Integral) x Derivative]
1-Ideal (Proportional + Integral + Derivative)

PIDSTN(1)-(6)
Type: Ent.Prm PV Input Connection Destination—Defines the parameter in the data point that
Lock: View is to receive the value provided by the respective input connection. There can be
Default: Based on up to six input-connection destinations for a RegPV point.
PVALGID,
PVEQN, & N
PtRes: HPM
Range: 1–8 character valid parameter name

HPM Parameter Reference Dictionary P-5 8/97


PINN

PINN (1)–(12) (DevCtl)


Type: Real Primary Input Constants Numeric—The numeric constant for arithmetic
Lock: Supr comparisons of primary input gates using XX algorithms.
Default: 0.0
PtRes: HPM
Range: <> NaN

PISO (1)–(12) (DevCtl)


Type: Logical Primary Input Gate Output Value—Indicates the output value of the primary
in an Array input gate.
(1..12)
Lock: View
Default: Off
PtRes: HPM
Range: Off
On

PISRC(1)–(12) (DevCtl)
Type: E:$GATESRC Primary Input Source—The source for the second input of primary input gates
in an Array for arithmetic comparison algorithms that use a second external input (i.e., XX2
(1..12) algorithms).
Lock: PtBld
Default: Null
PtRes: HPM
Range: NULL (No source for input)
L1..L12 (These values correspond with the LISRC(1)—(12) parameter)

PISRC(1)–PISRC(6)
Type: Ent.Prm PV Input Connection Source—Define the parameters whose current values are to
Lock: PtBld be fetched and then written to the up to six RegPV algorithm inputs. The
Default: null.null source parameter name can be specified using the "Tagname.Parameter" format.
PtRes: HPM Refer to the HPM Control Functions and Algorithms manual for a detailed
description.
Range: Use Tagname.Parameter for tagged points where Tag name can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters, and must be a legitimate parameter name.

HPM Parameter Reference Dictionary P-6 8/97


PIUOTDCF

PIUOTDCF (STI, LLMUX, RHMUX)


Type: Logical Open Thermocouple Detection Enable—Defines whether the point is to detect an
Lock: Eng/View open thermocouple condition. This parameter is configurable for each STI point
Default: On that is connected to a smart temperature transmitter and for each LLMUX point.
PtRes: HPM NOTE: There is no special point type for RHMUX. The LLMUX point type
also applies to the RHMUX IOP.

This parameter is a view-only parameter when the point execution state


PTEXECST is Active.

Range: On (Detect an open thermocouple condition)


Off (Do not detect an open thermocouple)

PIUOTDCF(1)–(168) (LLAI)
Type: Logical LLAI Open Sensor Detection Enable—Defines whether an
Lock: Supr open-sensor condition is to be detected for all eight LLAI points.
Default: On
PtRes: HPM
Range: On (Detect open-sensor conditions)
Off (Do not detect open-sensor conditions)

PKGOPT (HPM Box)


Type: E:$PKGOPT HPMM Hardware Packaging Option. The tables below show the default
Lock: PtBld hardware location for each choice.
Default: REDUN_2F
PtRes: HPM

Range: 1-REDUN (HPMMs in two 7-slot files/can have up to 40 IOPs)


2-REDUN_2F (HPMMs in two 15-slot files/can have up to 40 IOPs)
3-REDUN_IO (HPMMs/two separate 15-slot files/can have full redundant IOPs)
4-NODEFALT (Sets file/card positions of IOPs to 0. Used to bypass all defaults for IOP
File/Card positions).

Helpful Hints: Parameter NODENUM must be equal to an odd number no matter which option
is selected for PKGOPT.

During Node Specific configuration, if you choose Redun_IO, you must type in file and card
numbers for the IOP cards. Refer to the tables below or the HPM Node Specific Configuration
Form if necessary.

An HPMM can be operated as a non-redundant node independent of the PKGOPT selected.

The options are illustrated or discussed further in the following pages:

HPM Parameter Reference Dictionary P-7 8/97


PKGOPT

REDUN
Left File Right File
H H
P P
M IOP Cards M IOP Cards
M M
1&2 3 - 7 9&10 11 - 15

The Primary and Secondary HPMM Cards must be in Left File Card slots 1 & 2
and Right Card File, Card slots 9 & 10.

File 2 File 3

IOP Cards IOP Cards

1 - 15 1 - 15

The File and Card position of the IOPs are defaulted as follows:
Hardware File Card Slot Hardware File Card Slot
IOM-A 1-5 1 3-7 IOM-A 11- 25 2 1 - 15
IOM-A 6-10 1 11 - 15 IOM-A 26-40 3 1 - 15

NOTE
To operate the HPMM as non-redundant, configure PKGOPT = REDUN as above but install
only one of the HPMM card sets above. The backplane slot positions vacated by the second
HPMM cards can be used to house IOP cards if necessary.

HPM Parameter Reference Dictionary P-8 8/97


PKGOPT
REDUN_2F

File 1 File 2 File 3


H H
P P
IOP Cards IOP Cards IOP Cards
M M
M M

1&2 3 - 15 1&2 3 - 15 1 - 14

The Primary and Secondary HPMMs must be in File 1, Card slots 1 & 2 and in File 2,
Card Slots 1 & 2.

File and Card positions of the IOPs are defaulted as follows:


Hardware File Card Slot
IOM-A 1 - 13 1 3 - 15
IOM-A 14 - 26 2 14 - 26
IOM-A 27 - 40 3 1 - 14

NOTE
To operate the HPMM as non-redundant, configure PKGOPT = REDUN_2F as above but
install only one of the HPMM card sets above. The backplane slot positions vacated by the
second HPMM cards can be used to house IOP cards if necessary.

HPM Parameter Reference Dictionary P-9 8/97


PKGOPT
REDUN_IO

File 1 File 2 File 3


H H
P P IOP Cards
M IOP Cards M IOP Cards
M M

1&2 3 - 15 1&2 3 - 15 1 - 15

File 4 File 5 File 6

IOP Cards IOP Cards IOP Cards

1 - 15 1 - 12 1 - 12

The Primary and Secondary HPMMs must be in File 1, Card Slots 1 & 2 and in File 2,
Card Slots 1 & 2.

The File and Card position of the IOPs are defaulted as follows:
Hardware File Card Slot Hardware File Card Slot
IOM-A 1-13 1 3 - 15 IOM-B 1 - 13 2 3 - 15
IOM-A 14-28 3 1 - 15 IOM-B 14 - 28 4 1 - 15
IOM-A 29-40 5 1 - 12 IOM-B 29 - 40 6 1 - 12

Note that on download of this configuration to the HPM, the PKGOPT is changed back to
REDUN_2F.

NODEFALT
The HPMM File(s) may be like any of the previous three configurations and up to 40 IOPs
are allowed. The IOP file/Card positions must be configured by the user. Note that on
download to the HPM, PKGOPT changes to REDUN, or REDUN_2F based on the actual
hardware.

I/O Simulator Option


The optional I/O Simulator can be used to build points for this (the host) HPM or another
HPM. When using the I/O Simulator personality you may choose a packaging option
(PKGOPT) that is different from the physical backplane/hardware configuration of the host
HPMM. The intent is to let you choose a PKGOPT based on either the host's hardware
configuration or that of another HPMM. This allows you to create databases for other
HPMs using a single HPM I/O Simulator independent of its actual physical configuration.
The following rules apply:
Host HPM Other HPM PKGOPT
Configuration Configuration Selection
Any 7 - Slot REDUN or NODEFALT
Any 15 - Slot REDUN_2F, REDUN_IO, or NODEFALT

HPM Parameter Reference Dictionary P-10 8/97


PMEVOVFL

PMEVOVFL
Type: Logical HPMM Event Overflow Flag
Lock: View
Default:
PtRes: HPM
Range: Off (No overflow)
On (Overflow has occurred)

PMMCHAER (HPM Box)


Type: Integer HPMM I/O Link Channel A Error Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

PMMCHASL (HPM Box)


Type: Integer HPMM I/O Link Channel A Silence Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

PMMCHBER (HPM Box)


Type: Integer HPMM I/O Link Channel B Error Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

PMMCHBSL (HPM Box)


Type: Integer HPMM I/O Link Channel B Silence Count
Lock: View
Default: 0
PtRes: HPM
Range: >0

HPM Parameter Reference Dictionary P-11 8/97


PMMCMD

PMMCMD (HPM Box)


Type: E:$PMMCMD HPMM Command
Lock: OnProc
Default: None
PtRes: HPM

NOTE

When points are built to a NIM and the NIM is restarted with no database, the points need
to be reloaded from checkpoint or the points must be reconfigured. If the database is to
be reconfigured, the HPMM must be in Idle, and the point execution state must be Inactive.
This allows the point build operation to override the database that already exists there.

Range: 0-None (No command request has been issued)


1-Run (To "Run" state for processing points)
2-Idle (To "Idle" state for reloading the database)
3-RsIoLCom (Reset I/O Link communication error count = 0)
4-ShutDown (To "Alive" state for reloading personality)
5-RsUcnLsb (Reset the Local Statistics Block to zeroes)
6-SelChnA (Select Input/Output Link Channel A)
7-SelChnB (Select Input/Output Link Channel B)
8-Warmstrt (Warm Start)
9-Coldstrt (Cold Start)
10-SwapPri (Switchover to the redundant HPMM)

PMMCOMER (HPM Box)


Type: E:$IOMCOMM HPMM I/O Link Communication Error Status
Lock: View
Default: N/A
PtRes: HPM
Range: 0-None (No communication errors)
1-InvAlert (Invalid Alert—message bit problem)
2-InvDest (Invalid Destination)
3-InvChCnt (Invalid Character Count)
4-InvSourc (Invalid Source)
5-InvCmd (Invalid Command)
6-Checksum (Data record Checksum Error)
7-No_Resp (No Response)
8-ChTimOut (Channel Time Out)
9-MsgOvRun (Message Overrun)
10-GapError (Message gap is too long)
11-LpBckErr (Loop Back Error)
12-NTH_0 (Next Token Holder equals zero)
13-TknRecov (Token Recovery in progress)
14-RplBufOv (Reply Buffer Overflow)

HPM Parameter Reference Dictionary P-12 8/97


PMMCTLST

PMMCTLST (HPM Box)


Type: Logical HPMM Control Processor Status
Lock: View
Default: Off
PtRes: HPM
Range: Off (Control processor has not failed)
On (Control processor has failed)

PMMIOLST (HPM Box)


Type: E:$IOMSTS
Lock: View
Default:
PtRes: HPM
Range: Notconfg (IOP not configured)
Confgmis (Configuration mismatch detected)
OK (Module is running with no soft fail errors)
Idle (Module is idle with no soft fail errors)
Softfail (Module is running with soft fail error(s) present)
Idlesf (Module is idle with soft failure error(s) present)
Nonexist (Module does not exist at this address)
Noresp (No response from module)
Poweron (Module state is Power On)
Commerr (Communication error to IOP)
Unavail (Module is unavailable for communication)

PMMOPER (HPM Box)


Type: E:$OPERATE Process Manager Module Operation—Indicates the type of HPMM.
Lock: View
Default: N/A
PtRes: HPM
Range: 0-NonRedun (This HPMM has no redundant HPMM to back it up)
1-Primary (This HPMM is the primary point processor)
2-Secondry (This HPMM is the secondary HPMM that backs up the primary HPMM)

PMMRECCH (HPM Box)


Type: E:$RECCHN HPMM I/O Link Current Receive Channel
Lock: View
Default: N/A
PtRes: HPM
Range: 0-ChannelA (Channel A is channel currently receiving)
1-ChannelB (Channel B is channel currently receiving)

PMMRECHN
Type: E:$RECCHN HPMM Active Receive Channel
Lock: View
Default: N/A
PtRes: HPM
Range: ChannelA
ChannelB

HPM Parameter Reference Dictionary P-13 8/97


PMMSFST

PMMSFST(1)–(96)
Type: Logical HPMM Soft Failure
Lock: View
Default:
PtRes: HPM
Range: Off
On

PMMSTS (HPM Box)


Type: E:$NODESTA HPMM Primary Status
Lock: View
Default: N/A
PtRes: HPM
Range: 0-OffNet (NIM cannot communicate with the HPMM)
1-ConfgMs (Configuration mismatch detected)
2-Idle (Event reports but no point processing)
3-IdleSF (Soft failure occurred in Idle state)
4-OK (HPMM is operating normally)
5-SoftFail (Soft failure while HPMM is running)
6-Fail (HPMM can be accessed but CPU is halted; box hard failure has been detected )
10-Alive (No event reports or point processing)
11-AliveSF (Soft failure during Idle state)
12-Test (HPMM is in the test mode)
13-TestSF (Soft failure has been detected while the HPMM is in the test mode)
15-Loading (Personality or data base is loading)
16 S_Idle (Idle in Simulation Mode)
17 S_IdleSf (IdleSF in Simulation Mode)
18 S_OK (OK in Simulation Mode)
19 S_SFFail (SoftFail in Simulation Mode)
20 S_Pause (HPM is in the Simulation Pause state)
Standby
StandbySF
Upgrade
UpgradeSF

Helpful Hint: Loading the HPMM's operating personality software requires PMMSTS = Alive.
Loading the HPMM's database requires PMMSTS = Idle. Use parameter
PMMCMD's "Shutdown" and "Idle" command requests, respectively.

PNAMIOPA
Type: String_16 Physical Node Name Assigned to IOP A— Returns the Fieldbus physical
Lock: View node name assigned to IOPA.
Default: Parameter_Invalid
PtRes: IOP
Range:

HPM Parameter Reference Dictionary P-14 8/97


PNAMIOPB

PNAMIOPB
Type: String_16 Physical Node Name Assigned to IOP B— Returns the Fieldbus physical
Lock: View node name assigned to IOPB.
Default: Parameter_Invalid
PtRes: IOP
Range:

PNTFORM
Type: E:$PNTFORM Point Form—Defines the form of the data point that is implemented. Refer
Lock: View/PB to the HPM Control Functions and Algorithms manual for a detailed
Default: Full description of this function.
PtRes: HPM
Range: 0-Full (Point is fully displayed and alarmed)
1-Componnt (Point is partially displayed but not alarmed)

Helpful Hint: This parameter is not applicable to DigOut points.

PNTMODTY
Type: E:$PMMDTY Point's Module Type—Defines where the data point resides. Control points
Lock: View such as DigComp, RegPV, RegCtl, Logic, Process Module, Array, Box
Default: N/A Flags, Box Numerics, and Box Timers reside in the HPMM.
PTRes: NIM
Range: AO (Analog Output)
AO_16 (Analog Output/high density)
DI (Digital Input)
DO (Digital Output)
DO_32 (Digital Output/high density)
HLAI (High-Level Analog Input)
LLAI (Low-Level Analog Input)
STI8M(Smart Transmitter Interface)
NotConfg (Not Configured)
PI (Pulse Input)
HPMM (High-Performance Process Manager Module)
LLMUX (Low-Level Analog Input Multiplexer) All references to LLMUX also apply to
RHMUX, except that RHMUX does not support SENSRTYP of RTD.
DISOE (Sequence of Events)
SI (Serial Interface)
AO_16 (Analog Output 16)
DO_32 (Digital Output 32)

HPM Parameter Reference Dictionary P-15 8/97


PNTNODTY

PNTNODTY
Type: E:$UCNNDTY Point's Node Type—Defines the type of node on the UCN
Lock: View
Default: N/A
PtRes: NIM
Range: NIM (Network Interface Module)
HPM (High-Performance Process Manager)
NotConfg (Node not configured)

PNTSTATE
Type: E:PNTSTATE Point's Overall State—Defines the state of the data point, which is based on
Lock: View the state of the HPMM and the IOP Card in which it resides.
Default: N/A
PtRes: NIM
Range: Failed (NIM cannot communicate with point's HPMM/IOP)
Idle (Point's HPMM or IOP is in the Idle State)
OK (Point's HPMM or IOP is the Run State and is OK)
UNCERTN (Point's HPMM or IOP state is uncertain)

PNTTYPE
Type: E:PNTTYPE Point Type—Defines the type of point in the HPM.
Lock: PtBld
Default: Null
PtRes: HPM
Range: 0-Null (Not configured)
1-AnalgIn (Analog Input)
2-AnalgOut (Analog Output)
4-DigIn (Digital Input)
5-DigOut (Digital Output)
6-DigCom (Digital Composite)
8-RegPV (Regulatory PV)
9-RegCtl (Regulatory Control)
10-Logic (Logic)
11-Array (Array)
12-Flag (Flag)
13-Numeric (Numeric)
14-ProcModl (Process Module)
22-Timer (Timer)
28-DevCtl (Device Control)

Helpful Hint: PNTTYPE of DigOut has a restriction that PNTFORM cannot be = Full.

HPM Parameter Reference Dictionary P-16 8/97


POSITION

POSITION (HPM Box)


Type: E:$POSITIN HPMM File Position
Lock: View
Default: N/A
PtRes: HPM
Range: 0-Right (HPMM cards are in card file slots 6–10)
1-Left (HPMM cards are in card file slots 1–5)
2-File_1 (HPMM cards are in card file 1)
3-File_2 (HPMM cards are in card file 2)
4-Pref
5-Non_Pref
6-None
7-Unknown (Not able to determine file position from hardware)

PR2PREFF (HPM Box)


Type: Real Peer-to-Peer Communication Efficiency (in percent)—Indicates the rate of
Lock: View successful and on time UCN transactions from this node.
Default: 100
PtRes: HPM
Range: 0 - 100

Helpful Hint: This statistic is displayed on the Control Configuration page of the HPM
Diagnostic Display.

PRGATRFL (DigComp, DevCtl, RegCtl)


Type: Logical Program Mode Attribute Flag —indicates if the point is in Program Mode
Lock: View attribute.
Default: N/A
PtRes: HPM
Range: On - (point is in Program mode attribute)
Off - (point is not in Program mode attribute)

HPM Parameter Reference Dictionary P-17 8/97


PRIMMOD

PRIMMOD
Type: Ent_Id Primary Module Point Identifier—Typically used in Batch Processing, this
Lock: Engr parameter contains the tag name of an HPM point to which this data point is
Default: Null assigned. Other points that belong to the Batch equipment unit should have
PtRes: NIM their PRIMMOD set to this same point. Primmod is used to collect alarms and
events from this point along with others related to the specified Primary Module
point. Information is collected into a common file, accessible from the Event
History Menu.

Range: Tag name of the process module point can be up to 16 characters, and the permissible character
set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.

Helpful Hint: For Box Flag points, this parameter applies to only slots 1 through 128.
LCN entities that can be stored to PRIMMOD in NIM points are restricted to local NIM points.

PRMDESC(1)–(12) (Logic)
Type: E:$PMMLGPM Parameter Descriptor Assignment—Defines up to 12 logic-slot parameters
Lock: Eng/PB to which custom generic descriptors entered through parameters
Default: N/A GENDESC(1-12) are to be assigned.
PtRes: NIM
Range: L1...L12 (Logic-slot inputs)
FL1...FL12 (Logic-slot flags)
NN1...NN8 (Logic-slot numerics)
SO1...SO24 (Logic-slot outputs)

PROCMOD (ProcMod)
Type: E:PROCMOD Process Module Operating State—Represents the operational condition of a
Lock: Determined by process module. Refer to the HPM Control Functions and Algorithms
CNTLLOCK manual for a state diagram.
parameter
Default: Off
PtRes: HPM
Range: 0-Off (Off)
2-Norm (Normal)
4-Hold (Hold)
5-Shdn (Shutdown)
6-Emsd (Emergency Shutdown)
7-Strt (Start)
8-Stop (Stop)

HPM Parameter Reference Dictionary P-18 8/97


PRPMMSTS

PRPMMSTS
Type: E:$NODESTA Previous HPMM Status
Lock: View
Default:
PtRes: HPM

Range: Offnet (HPMM is offnet with no communications possible)


Confgmis (HPMM is in configuration mismatch)
Idle (HPMM is idle)
Idlesf (HPMM is idle with soft failure(s))
OK (HPMM is running with no errors)
Softfail (HPMM is running with soft failure(s))
Fail (HPMM has failed)
Poweron (HPMM is in Power On state-startup condition from power loss)
Alive (HPMM has passed self diagnostics and is ready to accept personality)
Alivesf (HPMM diagnostics have soft failure)
Loading (HPMM is loading personality)
Notconfg (HPMM is not configured on network)
Unavail (HPMM is unavailable on network for communications)
Test (HPMM is in Test mode)
Testsf (HPMM is in Test mode with a soft failure(s))
Standby
StandbySF
Upgrade
UpgradeSF

HPM Parameter Reference Dictionary P-19 8/97


PRVCOMFL

PRVCOMFL
Type: E:$PMMHFST Previous HPMM Communications Board Failure
Lock: View
Default:
PtRes: HPM
Range: NULL (Unknown Error)
PWRDWN (Power is Off)
LR_PAR (Local Ram Parity Error)
LR_LRAM (Local Ram Error)
LR_CK (Local Ram Check)
LR_EXC (Local Ram Exception )
LR_HREV (Local Ram Hardware Revision)
MM_HREV (Memory Board Hardware Revision)
LR_TMR (Local Ram Timer Error)
LR_PTRN (Local Ram Pattern Check Error)
LR_BYTE (Local Ram Byte Error)
LR_ADCD (Local Ram Address Decode Test)
LR_ADDL (Local Ram Additional Checks)
LR_CLRR (Local Ram Scrub Incomplete)
SR_PAR (Shared Ram Parity)
SR_PTRN (Shared Ram Pattern)
SR_ADCD (Shared Ram Address Decode Test)
SR_ADDL (Shared Ram Additional Checks)
GR_PAR (Global Ram Parity)
GR_PTRN (Global Ram Pattern Check Error)
GR_BYTE (Global Ram Byte Error)
GR_ADCD (Global Ram Address Decode Test)
GR_ADDL (Global Ram Additional Checks)
GR_CLRR (Global Ram Scrub Incomplete)
31_NR (IOL Processor, No Response or Failure)
31_ALIV (IOL Processor, Transmitter Not Alive)
31_ILTN (IOL Processor, Illegal Transition)
NMI_UNK (Unknown NMI Request)
BADUCNN (UCN Address Parity or Duplicate Address)
NR (No Response From Other Processor)
MRFT (Memory Reference Table - Pattern Build Fail)
NOMTOS (No MTOS Readout)
LLC_COMM (LLC Communication Fatal Error)
UCNDRV (UCN Driver, Fatal Error)
RD_HREV (Redundancy Card Version/Revision Mismatch)
SW_ERROR (Software Error)
MD_HREV (Modem Card Version/Revision Mismatch)
DA_PTRN (Daughter Card Pattern Test)
DA_BYTE (Daughter Card Byte Write Test)
DA_ADCD (Daughter Card Address Decode)
DA_ADDL (Daughter Card Additional Tests)
DA_CLRR (Daughter Card Scrub Incomplete)
RD_SNPS (Redundancy Card 96 Kw Snapshot Error)
RD_BSLK (Redundancy Card Bus Lock Fail)

HPM Parameter Reference Dictionary P-20 8/97


PRVCTLFL

PRVCTLFL
Type: E:$PMMHFST Previous HPMM Control Failure
Lock: View
Default:
PtRes: HPM

Range: NULL (Unknown Error)


PWRDWN (Power is Off)
LR_PAR (Local Ram Parity Error)
LR_LRAM (Local Ram Error)
LR_CK (Local Ram Check)
LR_EXC (Local Ram Exception )
LR_HREV (Local Ram Hardware Revision)
MM_HREV (Memory Board Hardware Revision)
LR_TMR (Local Ram Timer Error)
LR_PTRN (Local Ram Pattern Check Error)
LR_BYTE (Local Ram Byte Error)
LR_ADCD (Local Ram Address Decode Test)
LR_ADDL (Local Ram Additional Checks)
LR_CLRR (Local Ram Scrub Incomplete)
SR_PAR (Shared Ram Parity)
SR_PTRN (Shared Ram Pattern)
SR_ADCD (Shared Ram Address Decode Test)
SR_ADDL (Shared Ram Additional Checks)
GR_PAR (Global Ram Parity)
GR_PTRN (Global Ram Pattern Check Error)
GR_BYTE (Global Ram Byte Error)
GR_ADCD (Global Ram Address Decode Test)
GR_ADDL (Global Ram Additional Checks)
GR_CLRR (Global Ram Scrub Incomplete)
31_NR (IOL Processor, No Response or Failure)
31_ALIV (IOL Processor, Transmitter Not Alive)
31_ILTN (IOL Processor, Illegal Transition)
NMI_UNK (Unknown NMI Request)
BADUCNN (UCN Address Parity or Duplicate Address)
NR (No Response From Other Processor)
MRFT (Memory Reference Table - Pattern Build Fail)
NOMTOS (No MTOS Readout)
LLC_COMM (LLC Communication Fatal Error)
UCNDRV (UCN Driver, Fatal Error)
RD_HREV (Redundancy Card Version/Revision Mismatch)
SW_ERROR (Software Error)
MD_HREV (Modem Card Version/Revision Mismatch)
DA_PTRN (Daughter Card Pattern Test)
DA_BYTE (Daughter Card Byte Write Test)
DA_ADCD (Daughter Card Address Decode)
DA_ADDL (Daughter Card Additional Tests)
DA_CLRR (Daughter Card Scrub Incomplete)
RD_SNPS (Redundancy Card 96 Kw Snapshot Error)
RD_BSLK (Redundancy Card Bus Lock Fail)

HPM Parameter Reference Dictionary P-21 8/97


PRVIOLFL

PRVIOLFL
Type: E:$IOMHF Previous IOL Failure
Lock: View
Default:
PtRes: HPM
Range: UNKNOWN (Unknown Error)
POWERDWN (Power is Off)
INVPRGEX (Invalid Program Execution)
EPROMERR (EPROM Error)
RAMCNTER (Ram Contents Error)
RAMADRER (Ram Address Error)
DPAERROR (Physical Address Error)
DSAERROR (Soft Address Error)
RXBUFOFL (Receive Buffer Overflow)
IOLJABER (IOL Jabber Circuit - saw too much traffic)
BADPGJMP (Bad Program Jump)
ADCINCMP (A/D Incomplete)
ADOUTOVF (A/D Output Overflow)
ADOUTUDF (A/D Output Underflow)
ADCCALER (A/D Calibration Error)
BADDCLTC (Bad DC LTC)
DMT_TMOT (Dead Man Time Out)
MLTOUTFL (Multiple Output Failure)
DATBUSFL (Data Bus Failure)
BADDARNG (Bad D/A Range)
MSTRTMOT (Master Time Out 68 K)
CTRCKTFL (Counter Circuit Failure)

PSDLYFL
Type: Logical Poststore Delayed Flag—Set when poststore data is older than 1 second.
Lock: View
Default: Off
PtRes: HPM
Range: Off
On (poststore data is older than 1 second.)

PSTS (FlowComp)
Type: E:PVVALST Pressure Input Value Status—Status of the P input value.
Lock: View
Default: Normal
PtRes: HPM
Range: 0-Bad (Value is bad and replaced with NaN)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

HPM Parameter Reference Dictionary P-22 8/97


PTDESC

PTDESC
Type: String_24 Point Descriptor—A 24-character descriptor which is used to describe the point
Lock: PtBld and appears on the Group and Detail Displays for the point. Refer to
Default: Blank Figure N-1.
PtRes: NIM
Range: Permissible character set consists of all characters on the Engineer' s Keyboard. Basically this set
consists of alphabetics A-Z, numerics 0-9, and the following special characters: space ! % & '
( ) * + - / : ; > < = ? _ , . $

PTEXECST
Type: E:PTEXECST Point Execution State—Defines the current execution state of the point.
Lock: Supr
Default: Inactive
PtRes: HPM
Range: 0-Inactive (Point is not scanned or processed)
1-Active (Point is scanned and processed)

PTINAL (RegCtl, RegPV)


Type: Logical Point in Alarm Indicator—Indicates when an alarm condition has been detected at
Lock: View this point.
Default: Off
PtRes: HPM
Range: Off (Point is not in alarm)
On (Point is in alarm)

PTORST (RegCtl)
Type: E:ORSTATUS Point Override Status—Indicates the override status of the point.
Lock: Prog
Default: NotCon
PtRes: HPM
Range: 0-NotCon (Not connected to ORSel algorithm. Also indicates that point has been returned from
inactive to active status, or it is undergoing a cold restart, or it is being initialized.)
1-Sel (Selected as a part of ORSel strategy)
2-NotSel (Not selected as a part of ORSel strategy)

HPM Parameter Reference Dictionary P-23 8/97


PTSTSIOL

PTSTSIOL
Type: E:$NODESTA Redundant Partner Status as Seen From the IOL
Lock: View
Default:
PtRes: HPM
Range: OffNet (NIM cannot communicate with the HPMM)
ConfgMis (Configuration mismatch detected)
Idle (Event reports but no point processing)
Idlesf (Soft failure occurred in Idle state)
Ok (HPMM is operating normally)
SoftFail (Soft failure while HPMM is running)
Fail (HPMM can be accessed but CPU is halted; box hard failure has been detected)
Powron (Power is on)
Alive (No event reports or point processing)
Alivesf (Soft failure during Idle state)
Test (HPMM is in the Test mode)
TestSF (Soft failure has been detected while the HPMM is in the Test mode)
Loading (Personality or database is loading)
Notconfg
Nosynch
Unavail
Standby
StandbySF
Upgrade
UpgradeSF

PTSTSUCN
Type: E:$NODESTA Redundant Partner Status as Seen From the UCN
Lock: View
Default:
PtRes: HPM
Range: Offnet (NIM cannot communicate with the HPMM)
Confgms (Configuration mismatch detected)
Idle (Event reports but no point processing)
Idlesf (Soft failure occurred in Idle state)
Ok (HPMM is operating normally)
Softfail (Soft failure while HPMM is running)
Fail (HPMM can be accessed but CPU is halted; box hard failure has been detected)
Powron (Power is on)
Alive (No event reports or point processing)
Alivesf (Soft failure during Idle state)
Test (HPMM is in the Test mode)
Testsf (Soft failure has been detected while the HPMM is in the Test mode)
Loading (Personality or database is loading)
Notconfg
Nosynch
Unavail
Standby
StandbySF
Upgrade
UpgradeSF

HPM Parameter Reference Dictionary P-24 8/97


PULSEWTH

PULSEWTH (DevCtl, DigComp)


Type: Real Pulse Width for Point Outputs
Lock: Supr
Default: 1.0 second
PtRes: HPM
Range: 0.0 to 60.0 seconds

Helpful Hint: PULSEWTH change requires DODSTN= "Tagname.ONPULSE" or


OFFPULSE. When On is to be written to the DigOut module, a pulse of the
specified width is generated. When Off is to be written, no pulse is generated.

PV (AnalgIn, PI)
Type: Real Process Variable—PV is the PV's current value after the PV is selected from one
Lock: Oper of the following possible sources: a field device, an operator, or a program. See
Default: NaN PVSRCOPT and PVSOURCE.
PtRes: HPM
Range: PVEXEUHI to PVEXEULO,
NaN

Helpful Hint: PV change by a program requires PVSRCOPT = All and PVSOURCE = Sub.
PV change by an operator requires PVSRCOPT = All and PVSOURCE = Man.

PV (DevCtl, DigComp)
Type: E:SD_ENM:PVSTATES Current State—PV is the PV's current state after the PV is selected
Lock: Oper from one of the following possible sources: a field device, an
Default: BADPVTXT operator, a program, or the output of the PV's data point. See
PtRes: HPM PVSRCOPT and PVSOURCE.
Range: 0-PVSTATES (0) (Defined by STATETXT (0))
1-PVSTATES (1) (Defined by STATETXT (1))
2-PVSTATES (2) (Defined by BADPVTXT)
3-PVSTATES (3) (Defined by MOVPVTXT)
4-PVSTATES (4) (Defined by STATETXT(2))

Helpful Hint: PV change by a program requires PVSRCOPT = All and PVSOURCE = Sub.
PV change by an operator requires PVSRCOPT = All and PVSOURCE = Man.

PV (DigIn)
Type: E:SD_ENM:STATETXT Current State—Indicates the current state of the PV input to this
Lock: Oper data point. Not appropriate if DITYPE = ACCUM.
Default: Off
PtRes: HPM
Range: STATETXT(0) or STATETXT(1)

Helpful Hint: PV is derived from the open or closed state of field contacts and from the
configured direct or reverse input direction (INPTDIR).
PV change by a program requires DITYPE = Latched or status,
PVSRCOPT = All, and PVSOURCE = Sub.
PV change by an operator requires DITYPE = Latched or status,
PVSRCOPT = All, and PVSOURCE = Man.

HPM Parameter Reference Dictionary P-25 8/97


PV

PV (Flag)
Type: E:SD_ENM:STATETXT Current State—Indicates the current state of the flag data point, and
Lock: Oper it is derived from PVFL. STATETXT(1) is the alarmed state.
Default: Blank
PtRes: HPM
Range: STATETXT(0) or STATETXT(1)

PV (Numeric)
Type: Real Process Variable—Indicates the value of the numeric. This value maps into
Lock: Oper parameter NN(n) in the HPM box where n = SLOTNUM.
Default: NaN
PtRes: HPM
Range: N/A

PV (RegCtl, RegPV)
Type: Real Process Variable—Indicates the current value of the PV after the PV is selected
Lock: View for from one of the following possible sources: a field device, an operator, or a
RegCtl, program. See PVSRCOPT and PVSOURCE.
Oper for
RegPV
Default: NaN
PtRes: HPM
Range: N/A

Helpful Hint: PV change by a program requires PVSRCOPT = All and PVSOURCE = Sub.
PV change by an operator requires PVSRCOPT = All and PVSOURCE = Man.

PV (Timer)
Type: Integer Current Value—Indicates the current time in seconds or minutes. The timer
Lock: View starts at 0 and is incremented towards the preset time established by the SP
Default: 0 parameter.
PtRes: HPM
Range: 0 to 32000

PVALDB (RegCtl, RegPV)


Type: E:PVALDB PV Alarm Deadband—Alarm deadband is used to prevent excessive recurrence of
Lock: Eng/PB alarms by adjusting the percent of Engineering Unit range at which the alarm
Default: One "returns to normal."
PtRes: HPM
Range: 0-Half (1/2 of 1% of Engineering Unit range)
1-One (1% of Engineering Unit range)
2-Two (2% of Engineering Unit range)
3-Three (3% of Engineering Unit range)
4-Four (4% of Engineering Unit range)
5-Five (5% of Engineering Unit range)
6-EU (Specify deadband in Engineering Units)

HPM Parameter Reference Dictionary P-26 8/97


PVALDBEU

PVALDBEU (RegCtl, RegPV)


Type: Real EU value of alarm deadband
Lock: Eng/PB
Default: NaN
PtRes: HPM
Range: > 0.0

PVALGID
Type: E:$PMMPVAG PV Algorithm Identifier—Defines which PV algorithm is to be used for a
Lock: PtBld RegPV point.
Default: Null
PtRes: HPM
Range: 0-Null (No algorithm configured)
1-DataAcq (Data Acquisition)
2-FlowComp (Flow Compensation)
3-MidOf3 (Middle-Of-3 Selector)
4-HiLoAvg (High Low Average Selector)
5-Summer (Summer)
6-VdtLdLag (Variable Dead Time with Lead Lag)
7-TotaLizr (Totalizer)
8-GenLin (General Linearization)
9-Calcultr (Calculator)

PVAUTO (AnalgIn, PI)


Type: Real PV Auto Value—Value of the PV after PVCALC is range checked, filtered, and
Lock: View clamped.
Default: NaN
PtRes: HPM
Range: N/A

PVAUTO (DevCtl, DigComp)


Type: E:PVSTATES Current PV State—Indicates the current PV state, based on the states of the
Lock: View inputs to the point.
Default: BADPVTXT
PtRes: HPM
Range: 0-STATETXT(0)
1-STATETXT(1)
2-BADPVTXT
3-MOVPVTXT
4-STATETXT(2) (only if NOSTATES is 3)

PVAUTO (DigIn)
Type: E:STATETXT Current PV State—Indicates the current PV state that corresponds to the field
Lock: View contact input after direct/reverse correction.
Default: N/A
PtRes: HPM
Range: STATETXT(0) or STATETXT(1)

HPM Parameter Reference Dictionary P-27 8/97


PVAUTO

PVAUTO (RegCtl)
Type: Real PV Auto Value Fetched Using Control Input Connection—Indicates the current
Lock: View value of the PV when the RegCtl point is in the Auto mode.
Default: NaN
PtRes: HPM
Range: N/A

PVAUTO (RegCtl, RegPV)


Type: Real PV Auto Value—Indicates the current value of the PV after the algorithm
Lock: View calculation is performed, the range is checked, and the PV is filtered and clamped.
Default: NaN
PtRes: HPM
Range: N/A

PVAUTOST (RegCtl, RegPV)


Type: E:PVVALST PV Auto Value Status—Indicates the current status of the PVAUTO value.
Lock: View
Default: Bad
PtRes: HPM
Range: 0-Bad (All inputs, or result in PVCALC is bad)
1-Uncertn (Final result in PVCALC is an uncertain value)
2-Normal (Final result in PVCALC is a normal value)

PVCALC (AnalgIn, PI)


Type: Real Calculated PV—PVCALC is the PV value in Engineering Units after the raw
Lock: View PV (PVRAW) input to this data point has been characterized. The value of
Default: NaN PVRAW is the PV value provided by the Field Termination Assembly (FTA).
PtRes: HPM
Range: PVEXEUHI to PVEXEULO,
NaN

PVCALC (RegPV)
Type: Real Calculated PV—Indicates the value of the PV after the PV has been calculated by
Lock: View the PV algorithm.
Default: NaN
PtRes: HPM
Range: N/A,
NaN

HPM Parameter Reference Dictionary P-28 8/97


PVCHAR

PVCHAR
Type: E:VALCHAR PV Characterization Option—Defines the display characterization to be used
Lock: PtBld for characterizing the input PV value. Characterization is based on the field
Default: Linear sensor type.
PtRes: HPM

HLAI, LLMUX, RHMUX, & LLAI — PV Characterization


Valid normal Valid extended
range range
______________________________________________________ (PVEULO– (PVEXEULO–
X = Allowable Sensor Type PVEUHI) PVEXEUHI)
(SENSRTYP) in Degrees C in Degrees C
(when TCRNGOPT (when TCRNGOPT
Range PNT- pt4- 0- 1- 0-100 T Slide R = Normal for = Extended for
MODTY 2V 5V 5V mV C wire T SENSRTYP = SENSRTYP =
(NOTE 1) D Thermcpl) Thermcpl)
0-Jtherm HLAI X X X -200 to 1200 N/A
LLAI X -100 to 750 -200 to 1200
LLMUX X -100 to 750 -200 to 1200
1-Ktherm HLAI X X X 0 to 1100 -200 to 1370
LLAI X 0 to 1100 -200 to 1370
LLMUX X 0 to 1100 -200 to 1370
2-Etherm HLAI X X X -200 to 1000 N/A
LLAI X -150 to 500 -200 to 1000
LLMUX X -150 to 500 -200 to 1000
3-Ttherm HLAI X X X -230 to 400 N/A
LLAI X -200 to 300 -230 to 400
LLMUX X -200 to 300 -230 to 400
4-Btherm HLAI X X X 100 to 1820 N/A
LLAI X 600 to 1650 100 to 1820
LLMUX X 600 to 1650 100 to 1820
5-Stherm HLAI X X X 0 to 1700 N/A
LLAI X 550 to 1500 0 to 1700
LLMUX X 550 to 1500 0 to 1700
6-Rtherm HLAI X X X 0 to 1700 N/A
LLAI X 550 to 1500 0 to 1700
LLMUX X 550 to 1500 0 to 1700
7-RPtherm HLAI X X X 0 to 1700 N/A
LLAI X 550 to 1500 0 to 1700
LLMUX X 550 to 1500 0 to 1700
8-DinRtd HLAI X X X -180 to 800 N/A
LLAI X -200 to 850 N/A
LLMUX X -200 to 850 N/A
9-JisRtd HLAI X X X -180 to 650 N/A
LLAI X -200 to 650 N/A
LLMUX X -200 to 650 N/A
10-NicklRtd HLAI X X X -45 to 315 N/A
LLAI X -45 to 315 N/A
LLMUX X -45 to 315 N/A
11-CopprRtd HLAI X X X -20 to 250 N/A
LLAI X -20 to 250 N/A
LLMUX X -20 to 250 N/A
12-Linear HLAI X X X X N/A N/A
LLAI X X X N/A N/A
LLMUX X N/A N/A
13-Sqrroot HLAI X X X N/A N/A
LLAI X X N/A N/A
N/A = Not Applicable
NOTE 1: PNTMODTY LLMUX includes RHMUX for all thermocouple types except RTD; RTD type is not
supported by RHMUX IOP.

HPM Parameter Reference Dictionary P-29 8/97


PVCHAR

STI — PV Characterization
(Pressure and Magnetic Flow Transmitters)

Range Spt_Dp Spt_Gp Spt_Ap Sfm

Linear X X X X

Sqrroot X -- -- --

X = Allowable Sensor Type

STI — PV Characterization (Temperature Transmitters)

Normal Range Maximum Range


Range (PVEULO to PVEUHI) (PVEXEULO to PVEXEUHI)
in Degrees C (except in Degrees C (except
where noted) where noted)

Linear -50 to 220 mV -1000 to 1000 mV

Thermocouples

Btherm 400 to 1820 200 to 1820

Etherm -100 to 1000 -200 to 1000


Jtherm -180 to 1200 -200 to 1200
Ktherm -170 to 1250 -200 to 1370

NiNiMoTC 600 to 1300 600 to 1300


Ntherm -100 to 1300 -200 to 1300
Rtherm 0 to 1760 -50 to 1760
Stherm 0 to 1760 -50 to 1760
Ttherm -120 to 400 -250 to 400
W3W25TC 0 to 2300 0 to 2300
W5W26TC 0 to 2300 0 to 2300

RTDs

Cu10RTD -20 to 250 -20 to 250


Cu25RTD -20 to 250 -20 to 250
Pt100 DinRtd -200 to 450 -200 to 850
Pt100 JisRtd -200 to 450 -200 to 640
Pt200 RTD -200 to 450 -200 to 850
Pt500 RTD -200 to 450 -200 to 850
RH Rad 420 to 1800 700 to 1800

RTD Ohms 0 to 4KΩ 0 to 4KΩ

HPM Parameter Reference Dictionary P-30 8/97


PVCHAR

PVCHAR (FlowComp)
Type: E:VALCHAR PV Characterization Option—Defines the display characterization to be used
Lock: PtBld for characterizing the input PV value of Regulatory PV point configuring with
Default: SqRoot Flow Compensation.
PtRes: HPM
Range: 12-Linear (The COMPTERM compensation is not square rooted)
13 SqRoot (The COMPTERM compensation is square rooted)

PVCHGDLY
Type: Integer PV Change Delay time in Seconds—Defines the time(in seconds) that a point
Lock: Supr with a previously detected PV change event is guaranteed to remain at the new
Default: 0 seconds value even if the PV returns to its original value. If the point remains at its
PtRes: HPM new value when the delay timer expires, the point is held at the new value.
Range: 0 to 60 seconds

Helpful Hint: PVCHGDLY requires that EVTOPT = EIP, SOE, or EIPSOE.

PVCLAMP
Type: E:PVCLAMP PV Clamping Option—Defines whether PV clamping is to be used for this
Lock: Eng/PB data point. If PVCLAMP = Clamp and the PV extended range is exceeded, PV
Default: NoClamp value status PVSTS is marked Uncertain and the PV is set equal to the
PtRes: HPM extended limit that was violated.

Range: 0-NoClamp (No clamping of the PV value)


1-Clamp (Clamp PV value at range extension limit)

PVEQN (FlowComp)
Type: E:ALGOEQN PV Equation Type—Defines the equation type (EqA-EqE) to be used for this
Lock: PtBld PV algorithm. Refer to the HPM Control Functions and Algorithms manual
Default: EqA for more information.
PtRes: HPM
Range: Comp. Inputs Type of Compensation
0-EqA G Mass/Volumetric flow of liquid
1-EqB P and T Mass flow of gases and vapors
2-EqC G, P, and T Mass flow of gases and vapors w/specific gravity
3-EqD G, P, and T Volumetric flow of gases and vapors
4-EqE P, T, X, and Q Mass flow of steam

G = measured or calculated specific gravity or molecular weight, P = measured actual gage pressure, T =
measured actual temperature, X = measured actual steam compressibility and Q = measured actual steam
quality.

PVEQN (HiLoAvg)
Type: E:ALGOEQN PV Equation Type—Defines the equation type (EqA-EqC) to be used for this
Lock: Eng/PB PV algorithm. Refer to the HPM Control Functions and Algorithms manual
Default: EqA for more information.
PtRes: HPM
Range: 0-EqA (Select and identify highest of up to six inputs)
1-EqB (Select and identify lowest of up to six inputs)
2-EqC (Calculate the average of up to six inputs)

PVEQN

HPM Parameter Reference Dictionary P-31 8/97


PVEQN (MidOf3)
Type: E:ALGOEQN PV Equation Type—Defines the equation type (EqA-EqC) to be used for this
Lock: Eng/PB PV algorithm. Refer to the HPM Control Functions and Algorithms manual
Default: EqA for more information.
PtRes: HPM
Range: 0-EqA (Highest good input when one or two are bad)
1-EqB (Lowest good input when one or two are bad)
2-EqC (Average of all good inputs)

PVEQN (Summer)
Type: E:ALGOEQN PV Equation Type—Defines the equation type (EqA or EqB) to be used for
Lock: PtBld this PV algorithm. Refer to the HPM Control Functions and Algorithms
Default: EqA manual for more information.
PtRes: HPM
Range: 0-EqA (P1 input is scaled and biased)
1-EqB (Up to six inputs are scaled and summed with an overall bias applied)

PVEQN (Totalizr)
Type: E:ALGOEQN PV Equation Type—Defines the equation type (EqA-EqF) to be used for this
Lock: Eng/PB PV algorithm. Refer to the HPM Control Functions and Algorithms manual
Default: EqA for more information.
PtRes: HPM
Range: Option Warm Restart Action Bad Input Handling
0-EqA Continue Use zero
1-EqB Continue Use last good value
2-EqC Continue Set Bad and stop
3-EqD Set Bad, and stop Use zero
4-EqE Set Bad, and stop Use last good value
5-EqF Set Bad, and stop Set Bad and stop

PVEQN (VdtLdLag)
Type: E:ALGOEQN PV Equation Type—Defines the equation type (EqA-EqD) to be used for this
Lock: PtBld PV algorithm. Refer to the HPM Control Functions and Algorithms manual
Default: EqA for more information.
PtRes: HPM
Range: 0-EqA (Lead-Lag)
1-EqB (Fixed dead time)
2-EqC (Variable dead time)
3-EqD (Variable dead time with two lags)

Helpful Hint: For Equations C and D, the dead time is changed in steps of NLOC*NRATE*TS
where NLOC is configurable from 2 to 30, for better resolution of dead time.

HPM Parameter Reference Dictionary P-32 8/97


PVEUHI

PVEUHI
Type: Real PV High Range in Engineering Units—Note that PVEUHI cannot be written
Lock: Eng/PB with NaN. NaN is the default value only.
Default: NaN
PtRes: HPM
Range: PVEULO to PVEXEUHI, NaN

Helpful Hint: For Smartline transmitters, refer to Table A-3 in the PM/APM Smartline
Transmitter Integration Manual, PM12-410.

PVEULO
Type: Real PV Low Range in Engineering Units—Note that PVEULO cannot be written
Lock: Eng/PB with NaN. NaN is the default value only.
Default: NaN
PtRes: HPM
Range: PVEXEULO to PVEUHI, NaN

Helpful Hint: For Smartline transmitters, refer to Table A-3 in the PM/APM Smartline
Transmitter Integration Manual, PM12-410.

PVEXEUHI
Type: Real PV Extended Engineering Unit Range High—Both PVEXEUHI and
Lock: Engr PVEXEULO are used to clamp or detect a bad PV value. Refer to parameter
Default: NaN PVEXEULO. Note that PVEXEUHI cannot be written with NaN. NaN is the
PtRes: HPM default value only.
Range: > PVEUHI, NaN

PVEXEULO
Type: Real PV Extended Engineering Unit Low Range—For the LLAI IOP with
Lock: Engr Thermocouple and RTD sensor types, extended PV range parameters are VIEW
Default: NaN ONLY. Their values are defaulted based on the sensor types, the thermocouple
PtRes: HPM range option, and temperature scale. The tables below show the default values in
degrees C. For other engineering units, these values are appropriately converted.
Note that PVEXEULO cannot be written with NaN. NaN is the default value
only.
Range < PVEULO, NaN

Defaults for Extended Range PV Parameters When SENSRTYP = THERMCPL, PVTEMP = Degrees C
TCRNGOPT = NORMAL TCRNGOPT = EXTENDED
PVCHAR PVEXEULO PVEXEUHI PVEXEULO PVEXEUHI
Btherm 600 1650 100 1820
Etherm -150 500 -200 1000
Jtherm -100 750 -200 1200
Ktherm 0 1100 -100 1370
Rtherm 550 1500 0 1700
RPtherm 550 1500 0 1770
Stherm 550 1500 0 1700
Ttherm -200 300 -230 400

HPM Parameter Reference Dictionary P-33 8/97


PVEXEULO

PVEXEULO (continued)
Defaults for Extended Range PV Parameters When SENSRTYP = RTD, PVTEMP = Degrees C
PVCHAR PVEXEULO PVEXEUHI

PtDinRTD -180 800


PtJisRTD -180 650
NicklRTD -45 315
CopprRTD -20 250

PVEXHIFL
Type: Logical PV Extended High Range Violation—Indicates that the PV has exceeded the
Lock: View extended-high range alarm trip point.
Default: Off
PtRes: HPM
Range: Off (Extended high range not exceeded)
On (Extended high range exceeded)

PVEXLOFL
Type: Logical PV Extended Low Range Violation—Indicates that the PV has exceeded the
Lock: View extended-low range alarm trip point.
Default: Off
PtRes: HPM
Range: Off (Extended low range not exceeded)
On (Extended low range exceeded)

PVFL(0)–(2) (DevCtl, DigComp)


Type: Logical PV Flag—Indicates the current PV state as three separate Boolean parameters.
Lock: View PVFL(n) is On when the PV is in state "n" where n is 0, 1, or 2.
Default: Off
PtRes: HPM
Range: Off (PV is not in the respective state)
On (PV is in the respective state)

PVFL (DigIn, Flag)


Type: Logical PV Flag—Represents the current PV state as a Boolean value.
Lock: Oper
Default: Off
PtRes: HPM
Range: Off [PV = STATETXT(0)]
On [PV = STATETXT(1)]

HPM Parameter Reference Dictionary P-34 8/97


PVFORMAT

PVFORMAT (RegCtl, RegPV)


Type: E:VALFORMT PV Decimal Point Format—Defines the decimal format that is to be used to
Lock: Engr (/PB ) display the PV and SP values. It contains up to eight characters including
Default: D1 the minus sign and decimal point.
PtRes: HPM
Range: 0-D0 (-XXXXXX.)
1-D1 (-XXXXX.X)
2-D2 (-XXXX.XX)
3-D3 (-XXX.XXX)

PVHHFL (RegCtl, RegPV)


Type: Logical PV High High Alarm Flag—Indicates whether the PV has exceeded the alarm
Lock: View trip point established by the PVHHTP parameter.
Default: Off
PtRes: HPM
Range: Off (High High limit not exceeded)
On (High High limit exceeded)

PVHHPR (RegCtl, RegPV)


Type: E:ALPRIOR PV High High Alarm Priority—Defines the priority of the PV high high alarm.
Lock: Engr
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: PVHHPR configuration requires PVHHTP ≠ NaN.

PVHHTP (AnalgIn, RegPV)


Type: Real PV High High Alarm Trip Point—Defines the PV high high alarm trip point
Lock: Supr for this point.
Default: NaN
PtRes: HPM
Range: PVHITP to PVEXEUHI, NaN

Helpful Hint: PVHHTP configuration requires PVHITP ≠ NaN.

HPM Parameter Reference Dictionary P-35 8/97


PVHHTP

PVHHTP (RegCtl, RegPV)


Type: Real PV High High Alarm Trip Point—Defines the PV high high alarm trip point
Lock: Supr for this point.
Default: NaN
PtRes: HPM
Range: PVHITP to PVEUHI, NaN

Helpful Hint: PVHHTP configuration requires PVHITP≠ NaN.

PVHIFL (RegCtl, RegPV)


Type: Logical PV High Alarm Flag—Indicates that the PV has exceeded the alarm trip point
Lock: View established by parameter PVHITP.
Default: Off
PtRes: HPM
Range: Off (No PV High alarm)
On (High PV alarm)

PVHIPR (RegCtl, RegPV)


Type: E:ALPRIOR PV High Alarm Priority—Defines the priority of the PV high alarm for this
Lock: Engr point.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: PVHIPR configuration requires PVHITP ≠ NaN.

PVHITP
Type: Real PV High Alarm Trip Point—Defines the trip point for the PV high alarm for
Lock: Supr this point.
Default: NaN
PtRes: HPM
Range: PVLOTP to PVHHTP, NaN

PVINIT
Type: Logical PV Initialization Request Flag—Indicates that an initialization request has been
Lock: Prog made for this point.
Default: Off
PtRes: HPM
Range: Off (No 1-shot initialization)
On (Initializes the PV filter and the algorithm for a 1-shot single sample time).

HPM Parameter Reference Dictionary P-36 8/97


PVLLFL

PVLLFL (RegCtl, RegPV)


Type: Logical PV Low Low Alarm Flag—Indicates that the PV has exceeded the alarm trip
Lock: View point established by the PVLLTP parameter.
Default: Off
PtRes: HPM
Range: Off (PV > Low Low alarm trip point)
On (PV < Low Low alarm trip point)

PVLLPR (RegCtl, RegPV)


Type: E:ALPRIOR PV Low Low Alarm Priority—Determines the priority of the PV low low alarm
Lock: Engr for this data point.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: PVLLPR configuration requires PVLLTP ≠ NaN.

PVLLTP (AnalgIn, RegPV, PI)


Type: Real PV Low Low Alarm Trip Point—Defines the trip point for the PV low low
Lock: Supr alarm for this point.
Default: NaN
PtRes: HPM
Range: PVEXEULO to PVLOTP, NaN

Helpful Hint: PVLLTP configuration requires PVLOTP ≠ NaN.

PVLLTP (RegCtl)
Type: Real PV Low Low Alarm Trip Point—Defines the trip point for the PV low low
Lock: Supr alarm for this point.
Default: NaN
PtRes: HPM
Range: PVEULO to PVLOTP, NaN

Helpful Hint: PVLLTP configuration requires PVLOTP ≠ NaN.

PVLOFL (RegCtl, RegPV)


Type: Logical PV Low Alarm Flag—Indicates that the PV has exceeded the alarm trip point
Lock: View established by parameter PVLOTP.
Default: Off
PtRes: HPM
Range: Off (PV > Low alarm trip point)
On (PV < Low alarm trip point)

HPM Parameter Reference Dictionary P-37 8/97


PVLOPR

PVLOPR (RegCtl, RegPV)


Type: E:ALPRIOR PV Low Alarm Priority—Defines the priority of the PV low alarm for this
Lock: Engr point.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: PVLOPR configuration requires PVLOTP ≠ NaN.

PVLOTP (RegCtl, RegPV)


Type: Real PV Low Alarm Trip Point—Defines the trip point for the PV low alarm for this
Lock: Supr point.
Default: NaN
PtRes: HPM
Range: PVLLTP to PVHITP,
NaN

PVNORMAL (DevCtl, DigIn, DigComp)


Type: E:STATETXT PV Normal State—Defines the normal state of the PV using the appropriate
Lock: Supr STATETXT descriptor.
(Engr to change
to/from NONE)
Default: N/A
PtRes: HPM
Range: STATETXT(0) descriptor (Defaulted to Off for PV State 0)
STATETXT(1) descriptor (Defaulted to On for PV State 1)
STATETXT(2) descriptor (Defaulted to State2 for PV State 2; internally set to $NULL for two-
state devices; does not apply to DigIn point)
NONE (No off normal checking)

Helpful Hint: PV normal state text descriptor describes the normal (desired) state,
such as Run, Stop, Open, Closed.

HPM Parameter Reference Dictionary P-38 8/97


PVNORMFL

PVNORMFL (DevCtl, DigIn, DigComp)


Type: Logical PV Normal State Flag—Indicates whether the normal state of the PV is active.
Lock: Supr
Default: Off
PtRes: HPM
Range: Off (Point is in a state other than the normal state)
On (Normal state is active)

Helpful Hint: PVNORMFL change requires ALMOPT = Offnorm for Digital Input points,
or that PVNORMAL ≠ None for Digital Composite or Device Control points.
If set to On, causes text in STATETXT (1) to be used to describe the normal
state of the PV, otherwise text in STATETXT (0) is used.

PVP (RegCtl, RegPV)


Type: Real PV in Percent—Defines the PV as a percentage.
Lock: View
Default: NaN
PtRes: HPM
Range: N/A

PVRAW (AnalgIn)
Type: Real PV Raw Value—Indicates the raw input value of the PV from the Field
Lock: Operator Termination Assembly (FTA) before PV characterization is performed. The
Default: NaN units of value for the PV are determined by the field sensor type as described
PtRes: HPM below.
Range: N/A

Helpful Hint: If sensor type is 0.4–2 V, 1- 5 V, 0 - 5 V, PVRAW is in percent; if sensor type


is T/C, PVRAW is in microvolts; if sensor type is in RTD, PVRAW is in
milliohms; if sensor type is slidewire, PVRAW is in ratio; if sensor type is
0–100 mV, PVRAW is in millivolts.

PVRAW (DigIn)
Type: Logical Raw State of Field Contacts—Indicates the current state of the field contacts.
Lock: View
Default: Off
PtRes: HPM
Range:
Off Open contacts
On Closed contacts

HPM Parameter Reference Dictionary P-39 8/97


PVRAW

PVRAW (PI)
Type: Real PV Raw Value—Indicates the raw input value of the PV in pulses per second.
Lock: View
Default: NaN
PtRes: HPM
Range: N/A

PVRAW (STI)
Type: Real PV Raw Value—Indicates the raw input value of the PV in % of span based on
Lock: View the transmitter PV after PV characterization (PVCHAR) and DAMPING have
Default: NaN been performed. The span of the PV is determined by using LRV as a 0%-point
PtRes: HPM and URV as a 100%-point.
Range: N/A

PVRAWHI
Type: Real PV Raw High Range—Defines the high end of the normal operating range for
Lock: Eng/PB the raw PV value (PVRAW). For a slidewire input, the units are ratio, for a
Default: NaN 0_100_MV input, the units are in millivolts.
PtRes: HPM
Range: PVRAWLO to 100 for a 0_100_mv input (microvolts)
PVRAWLO to 1 for a slidewire input (ratio)

PVRAWLO
Type: Real PV Raw Low Range—Defines the low end of the normal operating range for the
Lock: Eng/PB raw PV value (PVRAW).
Default: NaN
PtRes: HPM
Range: 0–PVRAWHI (0 to 100 microvolts for a 0_100 mv input, or 0 to 1 ratio for a slidewire input)

PVROCNFL (RegCtl, RegPV)


Type: Logical PV Negative Rate-of-Change Alarm Flag—Indicates that the PV negative rate-
Lock: View of-change has exceeded the value established by the PVROCNTP parameter.
Default: Off
PtRes: HPM
Range: Off (No PV negative rate-of-change alarm)
On (PV negative rate-of-change alarm)

HPM Parameter Reference Dictionary P-40 8/97


PVROCNPR

PVROCNPR (RegCtl, RegPV)


Type: E:ALPRIOR PV Negative Rate-of-Change Alarm Priority—Defines the priority of the PV
Lock: Engr negative rate-of-change alarm for this point.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: PVROCNPR configuration requires PVROCNTP ≠ NaN.

PVROCNTP (RegCtl, RegPV)


Type: Real PV Negative Rate-of-Change Trip Point—Defines the trip point for the PV
Lock: Supr negative rate-of-change alarm for this point. Operation is the same as for
Default: NaN PVROCPTP except for the direction of change.
PtRes: HPM
The maximum rate of change value must be less than the absolute value of:
60
(PVEUHI-PVEULO) * .
8

Range: > 0.0,


NaN

Helpful Hint: For RegPV points, RegCtl points, and points in a HLAI or LLAI, the
maximum rate of change is one step away from PVEXEUHI to PVEXEULO
in eight seconds; therefore, the maximum rate of change is
(PVEXEUHI - PVEXEULO) * 7.5 units/minute. For SENSRTYP = RTD, the
maximum is [800 - (-180)] * 7.5, which is 7350.

PVROCPFL (RegCtl, RegPV)


Type: Logical PV Positive Rate-of-Change Alarm Flag—Indicates that the positive
Lock: View rate-of-change of the PV has exceeded the value established by the PVROCPTP
Default: Off parameter.
PtRes: HPM
Range: Off (No PV positive rate-of-change alarm)
On (PV positive rate-of-change alarm)

HPM Parameter Reference Dictionary P-41 8/97


PVROCPPR

PVROCPPR (RegCtl, RegPV)


Type: E:ALPRIOR PV Positive Rate-of-Change Alarm Priority—Defines the priority of the
Lock: Engr positive rate-of-change PV alarm for this point.
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

Helpful Hint: PVROCPPR configuration requires PVROCPTP ≠ NaN.

PVROCPTP (RegCtl, RegPV)


Type: Real
Lock: Supr PV Positive Rate-of-Change Trip Point—Defines the positive PV rate-of-change
Default: NaN limit in engineering units/minute for this point; for example 25 degrees per
PtRes: HPM minute. The PV value is checked every four seconds. The rate of change alarm
trips if the PV rate-of-change value is exceeded for two successive scans. The
alarm is reset if the PV rate-of-change falls below the rate of change value for
two successive scans.

The maximum rate of change value must be less than the absolute value of:
60
(PVEUHI-PVEULO) * .
8
Range: > 0.0,
NaN

Helpful Hint: For RegPV points, RegCtl points, and points in HLAI or LLAI, the maximum
rate of change is one step away from PVEXEUHI to PVEXEULO in eight
seconds; therefore, the maximum rate of change is:
(PVEXEUHI - PVEXEULO) * 7.5 units/minute.
Example: for SENSRTYP = RTD, the maximum is: [800 - (-180)] *7.5,
which = 7350.

PVSGCHTP (RegCtl, RegPV)


Type: Real PV Significant Change Alarm Trip Point—Defines the alarm trip point for an
Lock: Supr increment of change that occurs between configured PVHITP and PVHHTP or
Default: NaN PVLOTP and PVLLTP alarms. For example, consider a temperature point with
PtRes: HPM limits of PVHITP = 800 degrees, PVHHTP = 850, and PVSGCHTP = 10.
Range: > 0.0, When the temperature rises to 800 degrees, the PVHITP alarm is annunciated,
NaN and should the temperature continue to increase, the alarm is annunciated again
when the temperature reaches 810 degrees, 820 degrees, and so on. This allows
the alarm to be reannunciated to remind the operator of the existence of an alarm
condition.

HPM Parameter Reference Dictionary P-42 8/97


PVSOURCE

PVSOURCE (RegCtl, RegPV)


Type: E:PVSOURCE PV Source—Defines the source of the PV input to this data point. The PV
Lock: Oper goes to bad when PVSOURCE is switched from Man to Sub.
Default: Auto
PtRes: HPM
Range: 0-Sub (Value is provided by a sequence program)
1-Man (PV is supplied by operator or program)
2-Auto (Field wiring or memory fetch supplies PV)
3-Track (PV tracks OP (DigComp points only))

Helpful Hint: PVSOURCE change by an operator requires PVSRCOPT = All and DITYPE =
Latched if PNTTYPE = DigIn.

PVSRCOPT (RegCtl, RegPV)


Type: E:PVSRCOPT PV Source Option—Defines the PV source options available in this data
Lock: Eng/PB point.
Default: OnlyAuto
PtRes: HPM
Range: 0-OnlyAuto (PV source selection is not available and field wiring or memory fetch supplies PV)
1-All (PV is provided by an operator, by a sequence program, or by field wiring)

Helpful Hint: PVSRCOPT change by an operator requires DITYPE = Latched if


PNTTYPE= DigIn.

PVSTATES(0)–(4) (DevCtl, DigComp)


Type: String_8 PV State Descriptors—The PV state descriptors contain the text that describes
Lock: View the five (0-4) possible states of a DigComp or DevCtl PV. The descriptors are
Default: N/A set equal to whatever is configured in BADPVTXT and MOVPVTXT during
PtRes: NIM HPM Box configuration and in STATETXT(0), STATETXT(1), and
Range: N/A STATETXT(2) during point configuration (if PVTXTOPT = ON).

Helpful Hint: PVSTATES, if accessed by Control Language programs, obey the


following rules:
a. PVSTATES (0) = STATETXT (0)
b. PVSTATES (1) = STATETXT (1)
c. PVSTATES (2) = BADPVTXT
d. PVSTATES (3) = MOVPVTXT
e. PVSTATES (4) = STATETXT (2); does not apply unless
NOSTATES = 3

HPM Parameter Reference Dictionary P-43 8/97


PVSTS

PVSTS (RegCtl, RegPV)


Type: E:PVVALST Status Of PV Input Value—Defines the current status of the PV value.
Lock: View
Default: Bad
PtRes: HPM
Range: 0-Bad (Value is bad and replaced with NaN. For an STI point, value can be set to Bad based on
transmitter gross status.)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

PVTEMP
Type: E:TEMPTURE PV Temperature Scale—Defines the temperature scale to be used in
Lock: PtBld characterizing the PV input.
Default: Degrees C
PtRes: HPM
Range: 0-Degrees C (Celsius)
1-Degrees F (Fahrenheit)
2-Degrees R (Rankin)
3-Degrees K (Kelvin)

Helpful Hint: PVTEMP is to be configured when PVCHAR = TC or RTD.

PVTRACK (Pid)
Type: E:TRACKING PV Tracking Option—Defines whether SP is to be set equal to PV.
Lock: Eng/PB
Default: NoTrack
PtRes: HPM
Range: 0-NoTrack (SP is never set equal to PV)
1-Track (Man mode or initialization causes SP to track PV)

Helpful Hint: SP is set equal to PV if PVTRACK = Track and the point is:
a. in manual mode
b. being initialized from a secondary
c. undergoing 1-shot initialization during the first sample time after
becoming active.

HPM Parameter Reference Dictionary P-44 8/97


PVTV

PVTV
Type: Real PV Target Value in Engineering Units—Defines the target value of the PV in
Lock: Configurable engineering units.
Default: NaN
PtRes: HPM
Range: PVEXEULO to PVEXEUHI,

PVTVP
Type: Real PV Target Value in Percent—Indicates the target value of the PV in percent.
Lock: View
Default: NaN
PtRes: HPM
Range: > 0.0%, NaN

PVTXTOPT (DevCtl, DigComp)


Type: Logical PV Text Option—Indicates whether the BADPVTXT and MOVPVTXT
Lock: PtBld parameters are configured for this point, or if the default from the box data point
Default: Off should be used.
PtRes: NIM
Range: Off (The parameters are not configured for this point)
On (The parameters are configured for this point)

HPM Parameter Reference Dictionary P-45 8/97


HPM Parameter Reference Dictionary P-46 8/97
Q

-Q-

Q
Type: Real Steam Quality Factor Input—Indicates the measured actual steam quality factor.
Lock: View
Default: 1.0
PtRes: HPM
Range: > 0.0,
NaN

QSTS (FlowComp)
Type: E:PVVALST Q Input Value Status—Indicates the status of the steam quality-factor input.
Lock: View
Default: Normal
PtRes: HPM
Range: 0-Bad (Value is bad and replaced by NaN)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

HPM Parameter Reference Dictionary Q-1 8/97


HPM Parameter Reference Dictionary Q-2 8/97
R1

-R-

R1(1)–(24), R2(1)–(24) (Logic)


Type: E:$PMMLGPM Real Inputs 1 & 2—Defines the sources that provide the input values for the
Lock: PtBld R1 and R2 inputs of certain logic blocks.
Default: L1
PtRes: HPM
Range: 32..47-L1...L12 (Values from Input Connections)
48..51-NN1...NN8 (Local Numerics)

Helpful Hint: R1 configuration requires LOCALGID = EQ, NE, GT, GE, LT, LE, or
CHECKBAD.

RAISDSTN
Type: Universal Raise Output Pulse Destination—Defines the destination of the Raise output
Ent.Prm pulse. RAISDSTN must point to parameters ONPULSE or OFFPULSE of a
Lock: PtBld DigOut data point.
Default: Null
PtRes: HPM
Range: ONPULSE
OFFPULSE

RAISETIM
Type: Real Raise Output Pulse Time—Indicates the Raise output pulse time in seconds. It
Lock: View is clamped to MAXPULSE or CYCLETIM, whichever is lower. If the value of
Default: N/A RAISETIM is smaller than MINPULSE, no pulse is issued.
PtRes: HPM
Range: N/A,
NaN

RAISRATE
Type: Real Raise OP Stroke Rate in Percent/Second
Lock: Supr
Default: 100.0% per sec.
PtRes: HPM
Range: > 0.0% per second

RAMPTIME
Type: Real Ramp Time in Minutes
Lock: Oper
Default: 0.0
PtRes: HPM
Range: > 0.0

Helpful Hint: RAMPTIME change by an operator requires SPOPT = Tv. The minimum value
is clamped to TS, the point sample time in minutes, while the maximum value
is clamped to 32767*TS. To change the RAMPTIME from a logic point
requires Node=Auto and Mode Attribute=Program.

HPM Parameter Reference Dictionary R-1 8/97


RARWSTS

RARWSTS (RegCtl)
Type: E:WINDUP Remote Anti-Reset Windup Status
Lock: View
Default: Normal
PtRes: HPM
Range: 0-Normal (Free to move in either direction)
1-Hi (Free to move lower)
2-Lo (Free to move higher)
3-HiLo (Not free to move in any direction)

Helpful Hint: RARWSTS applies only if RCASOPT = Spc, Ddc, or DdcRsp.

RATE1 (AutoMan, MulDiv, RegCtl Summer)


Type: Real Rate at Which Bias Ramps Down—Rate at which the bias (B) ramps down from
Lock: Supr the initialization value to the last value entered by the operator. If a positive
Default: 0.0 value is entered, Rate1 determines the ramp down rate of the internal bias value
PtRes: HPM (BI). If 0 is entered, the ramp down of B is disabled. If NaN is entered, the
internal bias does not decay, but instantaneously changes to 0 and will cause a
bump in the output.

Range: > 0.0 EU’s per minute, NaN

RATE1 (RatioCtl)
Type: Real Internal Bias Ramps Down Rate—Rate in EUs per minute at which the internal
Lock: Supr bias (BI) ramps down from the initialization value to the last value entered by
Default: NaN the operator. If BIAS = NaN, initialization for the primary is determined
PtRes: HPM through back calculation. If 0 is entered, the ramp down of B is disabled.
Range: > 0.0, NaN

RATE1–12 (RampSoak)
Type: Real Ramp Rate for Ramp Soak Segments 1–12
Lock: Supr
Default: NaN
PtRes: HPM
Range: Negative values are accepted to allow ramping down.

RATIO (Pid)
Type: Real Ratio—Defines the ratio value by which the SP is multiplied.
Lock: Oper
Default: 1.0
PtRes: HPM
Range: RTLOLM to RTHILM

HPM Parameter Reference Dictionary R-2 8/97


RBOPT

RBOPT (Pid)
Type: E:RBOPT Ratio/Bias Option—Defines the type of ratio/bias option to be used for this
Lock: Eng/PB algorithm. Refer to the HPM Control Functions and Algorithms manual for a
Default: NoRatBi detailed description of bias and ratio options.
PtRes: HPM
Range: 0-NoRatBi (No ratio/bias is used to calculate the SP)
1-FixRatBi (Fixed ratio (R) and fixed bias (B) are used)
2-AutoRat (R is back-calculated during initialization)
3-AutoBi (B is back-calculated during initialization)

Helpful Hint: RBOPT applies to only PID-type RegCtl algorithms.

RCASOPT (AnalgOut)
Type: E:$RCASOPT Remote Cascade Option—Defines whether the AM is to provide the output
Lock: Eng/PB value for this data point. This option is available only when the point has
Default: None been configured as a Full point.
PtRes: HPM
Range: 0-None (No cascade mode of any type is allowed)
2-Ddc (Direct Digital Control; in cascade mode, AM point controls this point's OP)

RCASOPT (AutoMan, IncrSum, ORSel, Switch)


Type: E:$RCASOPT Remote Cascade Option—Defines the type of remote cascade mode to be used.
Lock: Eng/PB Refer to the HPM Control Functions and Algorithms manual for a detailed
Default: None description.
PtRes: HPM
Range: 0-None (Only local cascade mode is allowed)
2-Ddc (In cascade mode, AM point provides the output OP for this data point)

RCASOPT (Pid)
Type: E:$RCASOPT Remote Cascade Option—Defines the type of remote cascade mode to be used.
Lock: Eng/PB Refer to the HPM Control Functions and Algorithms manual for a detailed
Default: None description.
PtRes: HPM
Range: 0-None (Local cascade is the only valid cascade)
1-Spc (AM writes to SP within SP limits)
2-Ddc (AM writes to OP. No OP limits)
3-Rsp (AM writes to SP when this point is in Auto and is being initialized by its secondary. SP
limits are applied)
4-DdcRsp (AM does Ddc and Rsp functions)

Helpful Hint: MODE for a point cannot be changed to Cascade by the operator or program if
a. parameter RCASOPT is configured to Ddc, Spc, or DdcRsp
b. the AM strategy has not yet stored to MODE, SP, or OP.
Even if PVTRACK = Track, PV tracking is not performed in auto mode with
INITMAN = On if RCASOPT = Rsp.

HPM Parameter Reference Dictionary R-3 8/97


RCASOPT

RCASOPT (RegCtl)
Type: E:$RCASOPT Remote Cascade Option—Defines the type of remote cascade mode to be used.
Lock: Eng/PB Refer to the HPM Control Functions and Algorithms manual for a detailed
Default: None description.
PtRes: HPM
Range: 0-None (Only local cascade mode is allowed)
1-Spc (In cascade mode, AM point provides the SP for this point)
2-DDC (In cascade mode, AM point provides the OP for this point)
3-Rsp (In Auto mode with INITMAN = ON, the AM point provides the SP for this point)
4-DDCRsp (In cascade mode, AM point provides the OP for this point)

RCASSHED (RegCtl)
Type: Logical Remote Cascade Shed—Indicates whether the mode has shed from the Cas mode
Lock: View to the preconfigured backup mode.
Default: Off
PtRes: HPM
Range: Off (No mode shed)
On (Mode has shed to the preconfigured backup mode)

Helpful Hint: RCASSHED applies only if RCASOPT = Spc, Ddc, or DdcRsp.

RDNHWREV
Type: String_2 HPMM Control Daughter Card Revision
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal Characters 00 to FF

REDTAG (RegCtl)
Type: E:REDTAG Red Tag State—Allows the user to set the point as being "out of service,"
Lock: Sup/Eng indicating that this point or the associated control loop needs repair or is being
Default: Off repaired. Once this point is put in the red tag condition, the output OP is frozen
PtRes: HPM at the last value or state.
Range: 0-Off (Data point is in service. Point's OP is not frozen)
1-On (Data point is out of service = point's OP is frozen)

Helpful Hint: REDTAG change requires MODE = Man and MODATTR = Oper. Once a
point is red tagged, parameters MODE, MODATTR, and OP (output) cannot
be changed. In addition, for a RegCtl point, ESWENBST cannot be changed.

RELREV (HPM)
Type: String_1 Overall Software Release Revision Code —
Lock: View
Default: 00 (Hex.)
PtRes: HPM

Range: N/A

HPM Parameter Reference Dictionary R-4 8/97


RELVERS

RELVERS (HPM)
Type: String_1 Overall Software Release Version Code —
Lock: View
Default: 00 (Hex.)
PtRes: HPM

Range: N/A

REMSOAKT (RampSoak)
Type: Real Remaining Soak Time—Indicates the amount of time remaining in the current
Lock: Oper soak segment.
Default: 0.0
PtRes: HPM
Range: 0.0 to 120.0 minutes

RESETFL (DevCtl, DigComp)


Type: Logical Reset Maintenance Statistics Flag—Used to reset maintenance statistics.
Lock: Oper
Default: Off
PtRes: HPM
Range: Off
On (Storing to this parameter resets maintenance statistics)

Helpful Hint: This parameter can be reset by the operator only while it is red tagged. A
program may reset at anytime.

RESETFL (DigIn)
Type: Logical Reset Flag—Resets the accumulator to zero when the command flag transitions
Lock: Prog from the Off to the On state.
Default: Off
PtRes: HPM
Range: Off (No Reset command)
On (Reset command is issued to the accumulator)

Helpful Hint: RESETFL change requires DITYPE = Accum

RESETFL (Timer)
Type: Logical Reset Timer Command Flag—Resets the total when this flag changes from Off
Lock: Prog to On.
Default: Off
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary R-5 8/97


RESETFL

RESETFL (Totalizr)
Type: Logical Reset Totalizer Command Flag—Resets the total RESETVAL when this flag
Lock: Prog changes from Off to On.
Default: Off
PtRes: HPM
Range: Off
On

RESETVAL (DigIn)
Type: Integer Accumulator Reset Value—Value that is preset in the accumulator. Value can
Lock: Oper then be incremented or decremented depending on the COUNTDWN parameter.
Default: 0
PtRes: HPM
Range: 0–32767

RESETVAL (Totalizr)
Type: Real Reset Value—Value used for presetting the value to be totaled.
Lock: Oper
Default: 0.0
PtRes: HPM
Range: N/A

RESTART (ProcMod)
Type: E:RESTART Process Module Restart State—Indicates the type of restart last performed by
Lock: View the process module. This value will be set to a value other than “None” until
Default: None the first preemption point.
PtRes: HPM

Helpful Hint: RESTART can be used to determine if the startup was caused by failover.
Following failover, RESTART takes on the value “Failover.” This value
remains until the first preemption point after which it returns to “None.”

Range: 0-None (Has not been restarted)


1-Failover (Running for the first time after a failover)
3-Warm (Running for the first cycle after a warm start)
4-Cold (Running for the first cycle after a cold start, or a power up to Run)
5-PTACTVN (Running for the first cycle following the transition from Off state to Run
state)

RFB (PidErfb)
Type: Real Reset Feedback Input in Percent—Indicates the PV value of another data point
Lock: View that is receiving its setpoint from this data point.
Default: N/A
PtRes: HPM
Range: > 0.0

HPM Parameter Reference Dictionary R-6 8/97


RG

RG (FlowComp)
Type: Real Reference Specific Gravity—Defines the reference specific gravity or reference
Lock: Supr molecular weight, in the same engineering units as G (measured or calculated
Default: 1.0(molecular specific gravity or molecular weight).
weight)
PtRes: HPM
Range: N/A

RINITREQ (RegCtl)
Type: Logical Remote Initialization Request—Indicates whether an initialization request has
Lock: View been made.
Default: On for
AnalgOut,
Off for
RegCtl
PtRes: HPM
Range: Off (No request)
On (Request has been made)

Helpful Hint: RINITREQ does not apply if RCASOPT = None.

RINITVAL (RegCtl)
Type: Real Remote Initialization Value
Lock: View
Default: NaN
PtRes: HPM
Range: N/A,
NaN

Helpful Hint: RINITVAL does not apply if RCASOPT = None.

RJRAW(1)–(168)
Type: Real Reference Junction's Raw Count in µVolts
Lock: View
Default: NaN
PtRes: HPM
Range: N/A

RJTEMP (LLAI)
Type: Real Reference Junction Temperature—Displays the current temperatures (°C) of the
Lock: View reference junction sensor. This value is updated only if the thermocouple input
Default: NaN is configured.
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary R-7 8/97


RNGCODE3

RNGCODE3 (ProcMod)
Type: Blind Record RNGCODE3— .
Lock: Oper
Default: N/A
PtRes: HPM
Range:

RP (FlowComp)
Type: Real Reference Pressure—RP is the reference pressure input and it is in the same
Lock: Supr Engineering Unit as the P (measured or actual gage pressure) input.
Default: 1.0
PtRes: HPM
Range: N/A

RP
Type: Real Minimum Pulse Time Ratio
Lock: Supr
Default: 1.0
PtRes: HPM
Range: 0.01 to 100.0

RQ (FlowComp)
Type: Real Reference Steam Quality Factor—Defines the reference steam quality factor
Lock: Supr which is in the same units as the Q (measured actual steam quality) input.
Default: 1.0
PtRes: HPM
Range: N/A

RSPBGP$$ (RampSoak)
Type: Real Ramp/Soak Percent Bar Graph Parameter—If in a ramp sequence, the value of
Lock: View the next soak percent is displayed. If in a soak sequence, the value of parameter
Default: N/A REMSOAKT as a percent of total soak time is displayed.
PtRes: HPM
Range: > 0.0

RSTROPT (ProcMod)
Type: E:$RSTROPT Restart Option—Defines how the sequence program is to be started following
Lock: Eng an Idle to Run, or power up to Run transition or a warm restart.
Default: Off
PtRes: HPM
Range: 0-Off (Sequence is waiting for the operator command to start)
1-Restart (Sequence is to be restarted from the beginning)
2-Stop (Sequence positions to beginning of the last preemption following a Warm, Cold, or
Power Up Restart and waits for the operator to start

HPM Parameter Reference Dictionary R-8 8/97


RT

RT (FlowComp)
Type: Real Reference Temperature—RT is the reference temperature input and is in the same
Lock: Supr Engineering Unit as the T (measured actual temperature) input.
Default: 1.0
PtRes: HPM
Range: N/A

RT
Type: Real Deadtime Ratio
Lock: Supr
Default: 1.0
PtRes: HPM
Range: 0.01 to 100.0

RTHILM (Pid)
Type: Real Ratio High Limit
Lock: Supr
Default: 100.0
PtRes: HPM
Range: RTLOLM to 100.0,
NaN

Helpful Hint: Entering NaN forces RTHILM to its extreme value (100.0%).

RTLOLM (Pid)
Type: Real Ratio Low Limit
Lock: Supr
Default: 0.01
PtRes: HPM
Range: 0.01 to RTHILM,
NaN

Helpful Hint: Entering NaN forces RTLOLM to its extreme value (0.01).

RUNSTATE (ProcMod)
Type: Logical Run State—Indicates that the point is in the RUN sequence execution state.
Lock: View
Default: Off
PtRes: HPM
Range: Off (Process Module point is not in the RUN state)
On (Process Module point is in the RUN state)

HPM Parameter Reference Dictionary R-9 8/97


RV

RV (Timer)
Type: Integer Remaining Time—Indicates the amount of time remaining (in seconds or
Lock: View minutes) that the timer is to run.
Default: 0
PtRes: HPM
Range: >0

Helpful Hint: RV represents remaining time computed as SP - PV. If SP = 0, RV


is always 0.

RX (FlowComp)
Type: Real Reference Steam Compressibility—Defines the reference steam compressibility,
Lock: Supr and is in the same engineering units as the X (measured actual steam
Default: 1.0 compressibility).
PtRes: HPM
Range: Anything except NaN

HPM Parameter Reference Dictionary R-10 8/97


S0BOXCLR

-S-

S0BOXCLR, S1BOXCLR, S2BOXCLR


Type: E:BOXCOLOR State Box Color—Used only for US displays; corresponds to the box colors
Lock: View configured using S0BOXCLR - BOXCLR(0), S1BOXCLR - BOXCLR(1),
Default: N/A S2BOXCLR - BOXCLR(2).
PtRes: NIM
Range: Red
Green
White
Black
Cyan
Yellow
Blue
Magenta

S1 (PidErfb)
Type: Logical Tracking Switch—Determines whether the CV value of this data point is
Lock: Prog replaced by the tracking value.
Default: Off
PtRes: HPM
Range: Off (CV value is not replaced)
On (CV value is replaced by the tracking value)

S1 (STI)
Type: String_127 Transmitter Status—Indicates the current status of the smart transmitter
Lock: View associated with this STI point. Transmitter status consists of
Default: Blank - Transmitter scratch pads 1, 2, 3 & 4
PtRes: HPM - Detailed transmitter status
Range: N/A, Blank - List of parameters whose values are not the same in both the STI IOP database
and the transmitter's database. (Parameters are mismatched.)

S1, S2 (RampSoak)
Type: Logical Mark 1 and Mark 2 Flags—These flags are used to indicate to other data points
Lock: View that a specified time has elapsed from the beginning of a specified ramp or soak
Default: Off segment. Refer to the HPM Control Functions and Algorithms manual for
PtRes: HPM detailed information.
Range: Off
On

HPM Parameter Reference Dictionary S-1 8/97


S1–S4

S1(1)–(24) through S4(1)–(24) (Logic)


Type: E:$PMMLGPM Status Inputs 1-4—Defines the input source for each of the S1-S4 inputs to
Lock: PtBld the logic block.
Default: L1
PtRes: HPM
Range: FL1...FL12 (Input source is a local flag; they can be either On or Off)
SO1...SO24 (Input source is the status output (SOn) from another logic block.)
L1...L12 (Input source is the configured input connection; they can be either On or Off)

S1–S4 (Switch)
Type: Logical Select X1-X4 Request Flag—Indicate whether the respective input (X1-X4) has
Lock: Oper been selected as the input to this algorithm.
Default: On
PtRes: HPM
Range: Off
On (Respective input has been selected)

S1BGNTIM, S2BGNTIM (RampSoak)


Type: Real Mark 1 and Mark 2 Begin Times—Times at which Mark Function Flag S1 or
Lock: Supr S2 is turned on. Refer to the HPM Control Functions and Algorithms manual
Default: 0.0 for detailed information.
PtRes: HPM
Range: > 0.0 to 120 minutes

S1ENDTIM, S2ENDTIM (RampSoak)


Type: Real Mark 1 and Mark 2 End Time—Times at which Mark Function Flags S1 and S2
Lock: Supr are turned Off. Refer to the HPM Control Functions and Algorithms manual for
Default: 0.0 detailed information.
PtRes: HPM
Range: > 0.0 to 120 minutes

S1REV(1)–(24) through S3REV(1)–(24) (Logic)


Type: Logical S1, S2, S3 Inputs Reversed—Allows the user to selectively reverse (invert) any
Lock: PtBld of the inputs to a logic block.
Default: Off
PtRes: HPM
Range: Off (Input is direct)
On (Input is reversed)

Helpful Hint: Reversed (inverted) inputs apply only to LOGALGID = And, Or, Nand, and Nor.

HPM Parameter Reference Dictionary S-2 8/97


S1SEGID, S2SEGID

S1SEGID, S2SEGID (RampSoak)


Type: E:CURSEGID Mark 1 and Mark 2 Segment Identifiers—Refer to the HPM Control
Lock: Supr Functions and Algorithms manual for detailed information.
Default: Ramp1
PtRes: HPM
Range: 0-Ramp1 1-Soak1
2-Ramp2 3-Soak2
: and :
20-Ramp11 21-Soak11
22-Ramp12 23-Soak12

SAFEOP
Type: Real Safe Operation For Safety Shutdown—Defines the safe output value (OP) for a
Lock: Engr point when the SHUTDOWN parameter is set to On.
Default: N/A
PtRes: HPM
Range: -6.9 to 106.9%,
NaN

SAFOPCMD (PosProp, PIDPosPr)


Type: E:$SFOPCMD Safe OP Command—Defines the Safe OP state for position proportional and
Lock: Engr PID position proportional.
Default: Idle
PtRes: HPM
Range: 0-IDLE (Output does not change)
1-RAISE (Output is raised)
2-LOWER (Output is lowered)

SCANPER (HPM Box)


Type: Real SI Data Scan Period—Defines the period that the HPMM Control Processor
Lock: PtBld scans serial interface data that is mapped to the Array point.
Default: 1.0
PtRes: HPM
Range: .25 seconds
.5 seconds
1.0 seconds

SCANPRI (Array)
Type: E:$SCANPRI SI Data FTA Scan Priority—Indicates which scan priority the serial interface
Lock: PtBld FTA is using when reading data from the serial link.
Default: Low
PtRes: HPM
Range: Low (Scan at low priority)
High (Scan at high priority)

HPM Parameter Reference Dictionary S-3 8/97


SCANRATE

SCANRATE (HPM Box)


Type: E:$PMMSNRT Scan Rate—Defines the number of times that all slots of a particular type are
Lock: PtBld scanned and processed. Refer to the HPM Control Functions and Algorithms
Default: Reg1Log1 manual for information on how to determine the processing capacity of the
PtRes: HPM HPM. During the load of the HPM Box Data point, the point mix (number
of points and box variables) and the scan rate are written to the HPMM by
the store of the SCANRATE parameter.

Range: RegCtl & RegPV Logic, DigComp & DevCtl ProcMod


Scan Freq Scan Freq Scan Freq
0-Null ---- ---- ----
1-Reg1Log1 1 second 1 second 1 second
2-Reg1Log2 1 second 1/2 second 1 second
3-Reg1Log4 1 second 1/4 second 1 second
5-Reg2Log2 1/2 second 1/2 second 1 second
6-Reg2Log4 1/2 second 1/4 second 1 second
8-Reg4Log4 1/4 second 1/4 second 1 second

CAUTION
If a new point mix or a new SCANRATE is loaded from the DEB, the following items should be noted:

a. Before making changes to the point mix or SCANRATE, any configured points being removed due
to a reduction in the point mix should first be deleted from the system.
b. Any other currently configured points are preserved in the new point mix (the point database is not
defaulted).
c . If the SCANRATE or any part of the point mix is rejected by the HPMM then the HPMM database
remains unchanged; the SCANRATE and the point mix also remain unchanged.
d. If the SCANRATE and the point mix are equivalent to the previous values, then the HPMM
database remains unchanged.

SCHSTS
Type: Logical Schedule Status—Indicates the status of the schedule configuration option
Lock: View processing (for example, before/after relationship).
Default: OK
PtRes: HPM
Range: OK (the point is correctly assigned to the desired scan cycle or before/after another point with the
same status)
Incomplete (the point did not complete loading to the point where the proper scan cycle or
before/after point could be determined. )
error (the point could not be placed on the desired scan cycle or before/after the desired point)
Alarm (the schedule configuration of the point was violated after the configuration of the point
was complete and its status was Ok.)

Helpful Hint: The point cannot be made active if SCHSTS = Incomplete or Error.

HPM Parameter Reference Dictionary S-4 8/97


SEALOPT

SEALOPT (DevCtl, DigComp)


Type: E:$SEALOPT Seal-in Circuit Option—Configures the seal-in circuit option.
Lock: Eng/PB
Default: None
PtRes: HPM
Range: 0-None (Sealin is not configured)
1-Sealin (Sealin is configured)

SECOND (HPM Box)


Type: Integer Current Second
Lock: View
Default: N/A
PtRes: HPM
Range: 0 to 59

SECSYNC
Type: E:$SECSYNC Secondary Synchronization Status
Lock: View
Default:
PtRes: HPM
Range: Synched (Modules are synchronized)
NoSynch (Modules are out of synchronization)

SECVAR (DevCtl)
Type: Real Secondary Variable—The analog feedback, normally the motor current or flow.
Lock: View
Default: 0.0
PtRes: HPM
Range: Real Numbers including NaN

SECVAR (STI)
Type: Real Secondary Variable—Displays the value of the secondary variable of the smart
Lock: View transmitter as follows:
Default: NaN Pressure transmitter—temperature of the transmitter
PtRes: HPM Temperature transmitter—cold junction temperature
Flow transmitter—totalized value.
Range: N/A, NaN

SEGTOT (GenLin)
Type: Integer Total Number of Segments—Defines the total number of segments in the curve.
Lock: Supr
Default: 1
PtRes: HPM
Range: 1 to 12

HPM Parameter Reference Dictionary S-5 8/97


SEGTYPE

SEGTYPE (RampSoak)
Type: E:SEGTYPE Segment Type—Indicates the current segment being executed by the RegCtl
Lock: View point.
Default: N/A
PtRes: HPM
Range: 0-Ramp (Ramp segment)
1-Soak (Soak segment)

SELINP (HiLoAvg, MidOf3)


Type: E:PINP Selected Input—Indicates the selected input for the algorithm.
Lock: View
Default: SelectP1
PtRes: HPM
Range: 1-SelectP1 (HiLoAvg and MidOf3 algorithms)
2-SelectP2 (HiLoAvg and MidOf3 algorithms)
3-SelectP3 (HiLoAvg and MidOf3 algorithms)
4-SelectP4 (Only HiLoAvg algorithm)
5-SelectP5 (Only HiLoAvg algorithm)
6-SelectP6 (Only HiLoAvg algorithm)

SELXINP (ORSel, Switch)


Type: E:XINP Selected X Input—For the ORSel algorithm, this parameter indicates the
Lock: View inputs to the algorithm that have not been bypassed by the BYPASS1-
(for ORSel) BYPASS4 parameters. For the Switch algorithm, this parameter allows the
Oper operator to specify the input (X1-X4) to the algorithm. Refer to the HPM
(for Switch) Control Functions and Algorithms manual for a detailed description.
Default: SelectX1
PtRes: HPM
Range: 1-SelectX1
2-SelectX2
3-SelectX3
4-SelectX4

SENSRTYP (HLAI & LLAI)


Type: E:$SENSRTY Sensor Type—Defines the type of field sensor connected to the Field
Lock: PtBld Termination Assembly (FTA). 0_100_mV, Thermocouple, and RTD sensor
Default: 1_5_V types do not apply for HLAI. P4_2_V and slidewire sensor types do not apply
PtRes: HPM for LLAI. Refer to PVCHAR for more information.
Range: 0-1_5_V (1 to 5 volts)
1-0_5_V (0 to 5 volts)
2-0_100_mV (0 to 100 millivolts)
3-Thermcpl (Thermocouple)
4-RTD (Resistance Temperature Device)
5-P4_2_V (0.4 to 2 volts)
6-Slidwire (Slidewire Resistance Device)

HPM Parameter Reference Dictionary S-6 8/97


SENSRTYP

SENSRTYP (LLMUX, RHMUX)


Type: E:$SENSRTY Sensor Type—Defines the type of field sensor connected to the Field
Lock: PtBld Termination Assembly (FTA). Refer to PVCHAR for more information.
Default: 0 - 100 mV
PtRes: HPM
Range: 2-0_100_mV (0 to 100 millivolts)
3-Thermcpl (Thermocouple)
4-RTD (Resistance Temperature Device) NOTE: RTD is not supported by RHMUX.

SENSRTYP (STI)
Type: E:$SENSRTY Sensor Type—Defines the Smart Transmitter type. Refer to PVCHAR for
Lock: PtBld more information. Note that SENSRTYP must match the FTA. The point
Default: Spt_Dp status is set to SOFTFAIL if a mismatch occurs.
PtRes: HPM
Range: 8-SPT_DP (ST3000—differential pressure)
9-SPT_GP (ST3000—gauge pressure)
10-SPT_AP (ST3000—absolute pressure)
11-STT (STT3000—temperature)
12-SFM (MagneW 3000—magnetic flow and most Multivariable transmitters)

Helpful Hint: For multivariable transmitters, refer to the transmitter manual for the default
value of the specific device.

HPM Parameter Reference Dictionary S-7 8/97


SEQERR

SEQERR (ProcMod)
Type: Integer Sequence Error—Indicates that a sequence error or failure was detected. A code is
Lock: View displayed to indicate the nature of the error or failure. When an error is detected,
Default: 0 the sequence execution state is changed to ERROR; when a failure is detected,
PtRes: HPM the execution state is changed to FAIL.
Range: 0 (No error)
1-100 (Not used)
Error Codes
101 (Not used)
102 (Array index error)
103 (Illegal IMD code)
104 (Illegal variable/operator code)
105 (Interpreter stack overflow)
106 (GOTO destination error)
107 (Key level error)
108 (Configuration mismatch error)
109 (I/O Link prefetch overflow)
110 (Subroutine nesting level error)
111 (Illegal value error)
112 (Fail statement)
113 (IOL-Prefetch buffer full)
114 (IOL-Poststore buffer full)
115 (UCN-Prefetch buffer full)
116 ((UCN-Postore buffer full)
117-164 (Not used)
Failure Codes
165 (Sequence has been halted by the operator)
166 (Sequence jumped to an abnormal condition handler which was not enabled)
167 (Not used)
168 (Timeout condition occurred on WAIT statement)
169 (An attempt was made to start a sequence that has not been loaded)
170 (Communication error in READ/WRITE statement)
171 (Communication error detected during I/O Link access. This error is also generated for all
post-store problems)
172 (Range Error)
173 (An attempt was made to write to a point that was not in the proper mode)
174 (Interlock error)
175-255 (Not used)

SEQEXEC (ProcMod)
Type: E:SEQEXEC Sequence Execution State—Indicates the current execution state of the
Lock: View sequence program that is executing in the process module. Refer to the HPM
Default: NL Control Functions and Algorithms manual for a detailed description of the
PtRes: HPM execution states.
Range: 0-NL (Not Loaded)
1-DLL (Down-line loading is in progress)
2-Loaded (Sequence has been loaded into the process module)
3-End (Sequence has stopped because it has run to completion)
4-Pause (Sequence has stopped because of a PAUSE statement, or after each step is executed
while in the SnglStep sequence execution mode.)
5-Fail (Sequence has stopped because a sequence failure was detected)
6-Error (Sequence has stopped because a sequence error was detected)
7-Run (Sequence is running in the process module)

HPM Parameter Reference Dictionary S-8 8/97


SEQMODE

SEQMODE (ProcMod)
Type: E:SEQMODE Sequence Execution Mode—Defines the manner in which the sequence is
Lock: Determined by executed.
CNTLLOCK
parameter
Default: Auto
PtRes: HPM
Range: 0-Auto (Normal mode of sequence operation. Sequence runs from beginning to end without
operator intervention.)
1-SemiAuto (Sequence stops at all PAUSE statements in the sequence. Operator action is
required to restart the sequence.)
2-SnglStep (Sequence is executed one step at a time, and operator action is required to resume
execution. This mode is normally used for debugging.)

SEQNAME (ProcMod)
Type: String_8 Sequence Name—Defines the name of the CL sequence that currently resides in
Lock: View the process module.
Default: Blank
PtRes: HPM
Range: N/A

SEQOBJSZ (ProcMod)
Type: Integer Sequence Program Size—Indicates the number of memory blocks used by the
Lock: View sequence currently loaded in this process module.
Default: 0
PtRes: HPM
Range: >0

SEQPR (ProcMod)
Type: E:ALPRIOR Sequence Priority—Defines the alarm priority for Process Module points. Note
Lock: Engr that even when the Sequence priority is Journal, the alarm indicators still appear
Default: Low on the Group and Detail displays.
PtRes: NIM
Range: Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

SEQPRGSZ (HPM Box)


Type: Integer Sequence Program Size—Gives total HPM memory available for sequence
Lock: View program, in blocks.
Default: N/A
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary S-9 8/97


SEQPROC

SEQPROC (HPM Box)


Type: E:$SEQPROC Sequence Processing Rate—Specifies the number of processing units per Process
Lock: PtBld Module data points that can be processed each quarter second cycle.
Default: 1_PU
PtRes: HPM
Range: 1_PU One PU per Process Module point is allocated per scan (200 points can be processed
per scan)
2_PU Two PUs per Process Module point are allocated per scan (100 points can be processed
per scan)

SEQSLTSZ (ProcMod)
Type: Integer Sequence Slot Size—Defines the size of the program memory allocated for this
Lock: PtBld process module in terms of blocks. Each block is 32 words long. The actual
Default: 0 size is limited by the available memory.
PtRes: HPM
Range: >0

SERIALNO (STI)
Type: String_8 Serial Number/PROM Number of the Smart Transmitter
Lock: View
Default: Blank
PtRes: HPM
Range: N/A

SGALGID(1)–(2) (DevCtl)
Type: E:$GTALGID Secondary Gate ID—Defines the algorithm IDs for secondary gates.
in an Array
(1..2)
Lock: PtBld
Default: None
PtRes: HPM
Range: NULL (No algorithm)
AND (And Gate algorithm)
OR (Or Gate algorithm)
NAND (Nand Gate algorithm)
NOR (Nor Gate algorithm)
XOR (Exclusive Or Gate algorithm)
PAND (Pulse Nand Gate algorithm)
POR (Pulse or Gate algorithm)
PNAND (Pulse Nand Gate algorithm)
PNOR (Pulse Nor Gate algorithm)
PXOR (Pulse Exclusive or Gate algorithm)

HPM Parameter Reference Dictionary S-10 8/97


SGDSTN

SGDSTN(1)–(2) (DevCtl)
Type: E:$GATDSTN Secondary Gate Destination—Defines the output destination for the secondary
in an Array gates.
(1..2)
Lock: PtBld
Default: None
PtRes: HPM
Range: None (No destination)
SI0 (Output goes to Safety Interlock)
I0, I1, I2 (Output goes to Interlocks)
P0, P1, P2 (Output goes to Permissives)
SOCMD0, SOCMD1, SOCMD2 (Output is commanded to go to SOCMD0, 1 or 2)
OPCMD (Output is commanded to go to OPCMD parameter)

SGPLSWTH(1)–(2) (DevCtl)
Type: Integer Pulse Width for Secondary Gate—Indicates the pulse width for gates whose
in an Array algorithms begin with “P”.
(1..2)
Lock: Supr
Default: 0
PtRes: HPM
Range: 0 to 8000

SGSO(1)–(2) (DevCtl)
Type: Logical Status Output for Secondary Gates
in an Array
(1..2)
Lock: View
Default: Off
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary S-11 8/97


SHEDMODE

SHEDMODE (RegCtl)
Type: E:MODE Shedmode—Defines the mode to which this point sheds when it sheds from the
Lock: Engr Cas mode.
Default: Man
PtRes: HPM
Range: 1-Man (Manual)
3-Auto (Automatic; applies to only Pid, PosProp, and RatioCtl algorithms)
4-Bcas (Backup Cascade)

Helpful Hint: 1. SHEDMODE configuration requires RCASOPT = Spc or Ddc for Pid
algorithm.
2. SHEDMODE configuration requires RCASOPT = Ddc for the following
algorithms:
AutoMan
IncrSum
ORSel
Switch
3. SHEDMODE configuration requires RCASOPT = Spc for the following
algorithms:
PosProp
RatioCtl

SHEDTIME (RegCtl)
Type: Integer Remote Cascade Shed Time—Defines the amount of time between successive
Lock: Eng/PB updates of the SP or OP value from the AM. If the update is not received within
Default: 0 the specified time, the AM or the NIM is assumed to have failed, and the backup
PtRes: HPM control strategy is substituted by means of changing the mode to a preconfigured
backup mode.
Range: 0 to 1000 seconds

Helpful Hint: SHEDTIME configuration requires RCASOPT = Spc, Ddc, or DdcRsp, which
indicates that the SP or OP value is provided by the AM. To disable mode
shed, use the default value of 0 for this parameter.

SHUTDOWN (RegCtl)
Type: Logical Shutdown Command Flag—This optional parameter allows the user to
Lock: Prog implement safety interlocks that can effectively shutdown a single control loop.
Default: Off When the SHUTDOWN flag is set to On by a user-written program or logic
PtRes: HPM block, the mode and mode attribute are changed to Man and Oper, respectively,
Range: Off and the OP output is set equal to a predefined safe output value (SAFEOP). As
On long as the SHUTDOWN flag is On, the MODE, MODATTR, ESWENBST,
and OP parameter values cannot be changed. When the SHUTDOWN flag is set
to Off, the control loop must be manually restarted.

Helpful Hint: Before a program sets this flag to the On state, it should write into parameter
SAFEOP a safe shutdown value of 0%, 100%, or NaN (which causes the
last good OP value to be used).
A Logic Point or CL program must be used to reset the Shutdown Flag.

HPM Parameter Reference Dictionary S-12 8/97


SI0

SI0 (DevCtl, DigComp)


Type: Logical Safety Override Interlock Flag
Lock: Engr
Default: Off
PtRes: HPM
Range: Off (Override is not active)
On (Override is active)

Helpful Hint: This parameter can be changed by the engineer only when the point is
inactive or when the HPM is idle.

SI0ALOPT (DevCtl, DigComp)


Type: E:$OVRALOP SI0 Safety Override Alarm—Indicates the required action to be performed when
Lock: Eng/PB a safety interlock occurs.
Default: None
PtRes: HPM
Range: None (No override alarming)
Auto_Rtn (Return to normal when override is cleared)
Cnfm_Rqd (Confirm to clear, after interlock is cleared)

SI0ALPR (DevCtl, DigComp)


Type: E:ALPIROR Override SI0 Alarm Priority—Indicates the alarm priority for the safety
Lock: Engr override.
Default: NoAction
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

SIALGID(1)–(12) (DevCtl)
Type: E:$I2ALGID Secondary Input Gate Algorithm ID—Indicates the algorithm IDs for secondary
in an Array input gates.
(1..12)
Lock: PtBld
Default: Null
PtRes: HPM
Range: NULL (No algorithm)
DLY (Input is Delayed algorithm)
ONDLY (On Delay algorithm, transition to ON is delayed)
OFFDLY (Off Delay algorithm, transition to OFF is delayed)
PULSE (Input is Pulsed algorithm)
MAXPULSE (Maximum Pulse Width algorithm)
MINPULSE (Minimum Pulse Width algorithm)

HPM Parameter Reference Dictionary S-13 8/97


SIDLYTIM(1)–(12)

SIDLYTIM(1)–(12) (DevCtl)
Type: Integer Secondary Input Gate Delay/Pulse Width—Indicates the delay or pulse width for
in an Array secondary input gates.
(1..12)
Lock: Supr
Default: 0
PtRes: HPM
Range: 0 to 8000 seconds

SIDSTN(1)–(12) (DevCtl)
Type: E:$GATDSTN Destination for Secondary Input Gates—Defines the output destination of the
in an Array secondary gate.
(1..12)
Lock: PtBld
Default: None
PtRes: HPM
Range: None (No destination)
SI0 (Output goes to Safety Interlock)
I0, I1, I2 (Output goes to Interlocks)
P0, P1, P2 (Output goes to Permissives)
SOCMD0, SOCMD1, SOCMD2 (Output is commanded to go to SOCMD0, 1 or 2)
OPCMD (Output is commanded to go to OPCMD)
SG1, SG2 (Output goes to Secondary gates 1 or 2)
PG1, PG2, PG3, PG4 (Output goes to Primary gates 1, 2, 3 or 4)

SIM_TXT (NIM)
Type: String_8 Simulation Indicator—see also DISP_SIM
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

SI0CONF (DigComp,DevCtl)
Type: Logical Safety Override Interlock Alarm Confirmation Flag—Indicates that the safety
Lock: Oper override interlock alarm needs to be confirmed.
Default: Off
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary S-14 8/97


SISO

SISO(1)–(12) (DevCtl)
Type: Logical Status Output for Secondary Input Gates—Indicates the output value of the
in an Array secondary input gate.
(1..12)
Lock: View
Default: Off
PtRes: HPM
Range: Off
On

SLOTNUM
Type: Integer Slot Number—Defines the slot number where this point resides. For IOP point
Lock: PtBld types (AnalgIn, AnalgOut, DigIn, DigOut), it defines the hardware subslot on
Default: N/A the module (IOP card) in which the point resides; refer to description of
PtRes: NIM MODNUM parameter. For control points (DigComp, DevCtl, Array, Logic,
RegPV, RegCtl, Flag, Numeric, Timer and ProcMod) it defines the software slot
in the PMM. The processing capacity of the HPM depends on the number and
mix of configured control points. Refer to the HPM Control Functions and
Algorithms manual for a detailed description of how to determine the processing
capacity of the HPM, based on the number of control points being used.

For multivariable Smartline transmitters, note that although the transmitter is


connected to only one slot, you must allocate adjacent slots for the other PVs.

Range: AnalgIn (1-16 for HLAI and STI; 1–32 for LLMUX and RHMUX)
AnalgIn (1-8 for LLAI)
Array (1-500, but ≤ the value of NARRSLOT)
DevCtl (1-400, but ≤ the value of NDEVSLOT)
DigComp (1-999, but ≤ the value of NDCSLOT)
DigIn (1-32)
DigOut (1-16 or 1-32)
Flag (HPM Box Flag 1-2047)
LLMUX (1-32)
Logic (1-400, but ≤ the value of NLOGSLOT)
Numeric (HPM Box Numeric 1-2047)
ProcMod (1-250, but ≤ the value of NPMSLOT)
PI (1-8)
RegCtl (1-250, but ≤ the value of NCTLSLOT)
RegPV (1-125, ≤ the value of NPVSLOT)
Timer (HPM box Timer 1-64)
AnalgOut (1-8 or 1-16)

Helpful Hint: SLOTNUM configuration for Digcomp, DevCtl, Array, Flag, Numeric, Timer,
ProcMod,Logic, RegCtl, and RegPV points require CTLOPT = On.

HPM Parameter Reference Dictionary S-15 8/97


SLOT0SF

SLOT0SF(1)–(168)
Type: String_96 Slot 0 Soft Failures—Returns blind record of box soft failures present at a
Lock: View module address.
Default:
PtRes: HPM
Range: Hexadecimal Characters 00 to FF

SLWSRCID (AnalgIn)
Type: Integer Slidewire Voltage Source Identifier—Defines the slot number of the voltage
Lock: Eng/PB source for the slidewire.
Default: 1
PtRes: HPM
Range: 1–16
Helpful Hint: SLWSRCID configuration requires SENSRTYP = Slidewire.

SNAME(1)–(2) (ProcMod)
Type: String_8 Subroutine Name—Indicates the name of the subroutine currently used by the
Lock: View process module. A value of “ “ means that no subroutine is executing.
Default: Spaces SNAME(1) and SNAME(2) display the name of the first and second level
PtRes: HPM subroutines called from the main sequence.
Range: N/A

SO (DigOut)
Type: Logical Status Output—The output from a DigOut point.
Lock: Oper
Default: Off
PtRes: HPM
Range: Off (Field contact is to be de-energized.)
On (Field contact is to be energized.)

Helpful Hint: Only the HPMM Cont_Ctl access level can write to this parameter.

SO (Timer)
Type: Logical Status Output of Timer—Indicates whether the PV (elapsed time) has reached
Lock: View the SP (preset time).
Default: Off
PtRes: HPM
Range: On (PV has reached the SP)
Off (PV has not reached the SP)

SO(1)–(24) (Logic)
Type: Logical Logic Block Status Output—Indicates the output state of the logic block.
Lock: View
Default: Off
PtRes: HPM
Range: Off (Output is false)
On (Output is true)

HPM Parameter Reference Dictionary S-16 8/97


SO(0)-(2)

SO(0)–(2) (DevCtl, DigComp)


Type: Logical Status output array—Indicates the current output state of the Digital Composite
Lock: View slot.
Default: Off s = (0) for state 0
PtRes: HPM s = (1) for state 1
Range: Off s = (2) for state 2
On

SOAKT1–12
Type: Real Soak Time for Soak Segments 1–12—Define the soak time in minutes for each
Lock: Supr soak segment.
Default: 0.0
PtRes: HPM
Range: 0.0 to 120.0 minutes

SOAKV1–12
Type: Real Soak Value for R/S Segments 1–12— Defines the soak values in engineering
Lock: Supr units for each soak segment.
Default: NaN
PtRes: HPM
Range: N/A

SOCMD(0)–(2) (DevCtl, DigComp)


Type: Logical Output Status Command—When commanding an OFF to ON write, the OP is
Lock: Prog commanded to the state corresponding to the array element written on an off-to-
Default: OFF on transition.
PtRes: HPM
Range: On (The OP is commanded to the state corresponding to ‘i’. 0=State 0, 1=State 1, 2=State 2 if
SOCMD (i) was previously OFF)
Off (No action)

SP (RegCtl)
Type: Real Setpoint of the PV in Engineering Units
Lock: Oper
Default: 0.0
PtRes: HPM
Range: SPLOLM to SPHILM

Helpful Hint: SP usually does not require a control input connection. If a cascade
connection to SP is required, it is typically configured by specifying a control
output connection on the primary point.

HPM Parameter Reference Dictionary S-17 8/97


SP

SP (Timer)
Type: Integer Preset Time—Defines the amount of time in seconds or minutes that the timer
Lock: Oper is to run.
Default: 0
PtRes: HPM
Range: 0 to 32000

SPEUHI (RegCtl)
Type: Real Setpoint Engineering Unit High Range
Lock: View
Default: N/A
PtRes: HPM
Range: > SPEULO

SPEULO (RegCtl)
Type: Real Setpoint Engineering Unit Low Range
Lock: View
Default: N/A
PtRes: HPM
Range: < SPEUHI

SPFORMAT (RegCtl)
Type: E:VALFORMT Setpoint Decimal Point Format—Indicates the format of the SP value.
Lock: View SPFORMAT tracks with the selected PVFORMAT.
Default: N/A
PtRes: HPM
Range: 0-D0 (XXXX.)
1-D1 (XXX.X)
2-D2 (XX.XX)
3-D3 (X.XXX)

SPHIFL (RegCtl)
Type: Logical Setpoint High Limit Violation Flag—Indicates the SP has exceeded the upper
Lock: View limit established by SPHILM.
Default: Off
PtRes: HPM
Range: Off (High limit not exceeded)
On (High limit exceeded)

HPM Parameter Reference Dictionary S-18 8/97


SPHILM

SPHILM (RegCtl)
Type: Real Setpoint High Limit—Defines the upper limit for the SP.
Lock: Supr
Default: NaN
PtRes: HPM
Range: SPLOLM to SPEUHI,
NaN

Helpful Hint: 1. Entering NaN disables limit checking by forcing SPHILM to its extreme
value (SPEUHI).
2. SPHILM does not apply for the RampSoak algorithm.

SPLOCK (ProcMod)
Type: E:ACCLVL Setpoint Lock—Stores to the process module point’s own flags, numeric,
Lock: Engr strings, and time parameters, and are checked against the access lock specified
Default: Operator by SPLOCK.
PtRes: HPM
Range: 0-Operator (Operator and higher keylock positions allow store access.)
1-Supervis (Supervisor and higher keylock positions allow store access.)
2-Engineer (Engineer and higher keylock positions allow store access.)
3-Program(Only the program has store access.)

SPLOCK (Array)
Type: E:ACCLVL Setpoint Lock—Indicates the access lock for array point parameters FL, NN,
Lock: Engr STRn and TIME.
Default: Operator
PtRes: HPM
Range: 0-Operator (Operator and higher keylock positions allow store access.)
1-Supervis (Supervisor and higher keylock positions allow store access.)
2-Engineer (Engineer and higher keylock positions allow store access.)
3-Program(Only the program has store access.)

SPLOCK (Totalizer)
Type: Setpoint Lock—Stores to AVTV/PVTV parameters, are checked against the
Lock: Engr access lock specified by SPLOCK.
Default:
PtRes: HPM
Range: 0-Operator (Operator and higher keylock positions allow store access.)
1-Supervis (Supervisor and higher keylock positions allow store access.)
2-Engineer (Engineer and higher keylock positions allow store access.)
3-Program(Only the program has store access.)

HPM Parameter Reference Dictionary S-19 8/97


SPLOFL

SPLOFL (RegCtl)
Type: Logical Setpoint Low Limit Violation Flag—Indicates that the SP has exceeded the
Lock: View lower limit established by SPLOLM.
Default: Off
PtRes: HPM
Range: Off (Low limit is not exceeded)
On (Low limit is exceeded)

SPLOLM (RegCtl)
Type: Real Setpoint Low Limit—Defines the lower limit for the SP.
Lock: Supr
Default: NaN
PtRes: HPM
Range: SPEULO to SPHILM,
NaN

Helpful Hint: 1. Entering NaN disableslimit checking by forcing SPLOLM to its extreme
value (SPEULO).
2. SPLOLM does not apply for the RampSoak algorithm.

SPOPT (RegCtl)
Type: E:SPOPT Setpoint Option
Lock: Eng/PB
Default: None
PtRes: HPM
Range: 0-None (No specialized options are available)
1-TV (Target Value processing; provides a smooth transition from an existing setpoint to a
desired setpoint)
2-Asp (Advisory setpoint processing for Advisory Deviation Alarming)

Helpful Hint: 1. If component has been entered for the PNTFORM parameter, the Asp option
cannot be configured.
2. SPOPT does not apply for the RampSoak algorithm.

SPP (RegCtl)
Type: Real Setpoint in Percent
Lock: View
Default: N/A
PtRes: HPM
Range: N/A

SPTV (RegCtl)
Type: Real Setpoint Target Value in Engineering Units
Lock: Oper
Default: N/A
PtRes: HPM
Range: SPLOLM to SPHILM,
NaN

Helpful Hint: SPTV change requires SPOPT = TV.

HPM Parameter Reference Dictionary S-20 8/97


SPTVP

SPTVP (RegCtl)
Type: Real Setpoint Target Value in Percent
Lock: View
Default: N/A
PtRes: HPM
Range: > 0.0

Helpful Hint: SPTVP change requires SPOPT = TV.

SRQUTAVG (NIM, HPM Box)


Type: Real Average UCN Store Request Trip Time—The average time in milliseconds
Lock: View that it takes to receive a response to this node’s UCN store request.
Default: NaN
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

SRQUTMAX (NIM, HPM Box)


Type: Real Maximum UCN Store Request Trip Time—The maximum time in
Lock: View milliseconds that it takes to receive a response to this node’s UCN store
Default: NaN request.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

SRSPTAVG (NIM, HPM Box)


Type: Real Average UCN Store Response Trip Time—The average time in milliseconds
Lock: View that it takes this node to respond to UCN store requests from other nodes.
Default: NaN
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

SRSPTMAX (NIM, HPM Box)


Type: Real Maximum UCN Store Response Trip Time—The maximum time in
Lock: View milliseconds that it takes this node to respond to UCN store requests from
Default: NaN other nodes.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

HPM Parameter Reference Dictionary S-21 8/97


SSTEP

SSTEP(1)–(2) (ProcMod)
Type: String_8 Subroutine Step Name—Indicates the current step of the subroutine executing in
Lock: View this Process Module. A value of “ “ means that no subroutine is executing.
Default: Spaces SSTEP(1) and SSTEP(2) display the step name of the first and second level
PtRes: HPM subroutines called from the main sequence.
Range: N/A

SSTMT(1)–(2) (ProcMod)
Type: Integer Subroutine Statement Number—This parameter points to the statement number
Lock: View (in the NIM sequence library) of the current subroutine. A value of 0 indicates
Default: 0 that no subroutine is executing. The array index indicates nesting level.
PtRes: HPM
Range: 0 to 255

ST0_OP1–3 (DevCtl, Digcomp)


Type: Logical State 0, Outputs 1 through 3—Defines the value (On or Off) that is to be
Lock: Eng/PB written to output number 1, 2, and 3 when the OP is in State 0.
Default: Off
PtRes: HPM
Range: Off
On

ST1_OP1–3 (DevCtl, Digcomp)


Type: Logical State 1, Outputs 1, 2, and 3—Defines the value (On or Off) that is to be written
Lock: Eng/PB to output number 1, 2, and 3 when the OP is in State 1.
Default: Off
PtRes: HPM
Range: Off
On

ST2_OP1–3 (DevCtl, Digcomp)


Type: Logical State 2–Outputs 1, 2, and 3—Defines the value (On or Off) that is to be written
Lock: Eng/PB to output number 1, 2, and 3 when the OP is in State 2.
Default: Off
PtRes: HPM
Range: Off
On

HPM Parameter Reference Dictionary S-22 8/97


STARTFL

STARTFL
Type: Logical Start Command Flag—Starts DigIn accumulator, RegPV totalizer, or Box
Lock: Prog Timer when flag transitions from Off to On.
Default: Off
PtRes: HPM
Range: Off (No effect on accumulator/totalizer)
On (Allows the accumulator/totalizer to begin counting up/down)

STATE (STI)
Type: E:STATE Current State—Indicates the current state of the STI point.
Lock: View
Default: N/A
PtRes: HPM
Range: 2-Loading (Indicates that database loading between the STI point and the transmitter is occurring.)
3-Loadcomp (Indicates that the database transfer between the STI point and the transmitter has
been successfully completed)
4-Loadfail (Indicates that the parameter transfer between the STI point and the transmitter has not
been successfully completed)
5-Calib (Indicates that certain parameters are being calibrated at the transmitter by the STI point)
6-Calcomp (Indicates that the calibration has been successfully completed)
7-Calfail (Indicates that the calibration has not been successfully completed)
8-OK (Normal state; indicates that the STI point and the transmitter are OK. Transmitter is
updating the PV value at the STI point. STATE remains OK when the point is made inactive.)
9-DBChange (Indicates that a database mismatch between the STI point and the transmitter has
been detected. Transmitter is not updating the PV value at the STI point. STATE remains
DBChange when the point is made inactive.)

STATE (Timer, DigIn)


Type: E:STATE Timer State—Indicates the current state of the timer data point.
Lock: View
Default: Stopped
PtRes: HPM
Range: 0-Stopped
1-Running

HPM Parameter Reference Dictionary S-23 8/97


STATE

STATE (Totalizr)
Type: E:STATE Accumulator State—Indicates the current state of the totalizer.
Lock: View
Default: Stopped
PtRes: HPM
Range: 0-Stopped (Stopped)
1-Running (Accumulating)

STATE0–2
Type: String_8 Current State—These parameters represent the state text (STATETXT)
Lock: View descriptors as follows:
Default: 1 = On STATE0 = STATETXT(0)
0 = Off STATE1 = STATETXT(1)
2 = State 2 STATE2 = STATETXT(2); Digital Composite and DevCtl points.
PtRes: NIM Refer to the HPM Control Functions and Algorithms manual for a detailed
description of the Digital Composite point states.
Range: N/A

STATETXT(0)–(3) (DevCtl, DigIn, DigComp, Flag)


Type: String_8 State Descriptor Text—Define the states of the point using descriptors which
Lock: PtBld can have up to eight characters.
Default: 1 = On
0 = Off STATETXT (1) corresponds to the first ACTIVE state, or the state
2 = State 2 corresponding to PVFL = On (direct acting) or PVFL = Off (reverse acting).
3 = None (State 3) On the Group or Detail Display, it is in the upper box.
PtRes: NIM
STATETXT (0) corresponds to the INACTIVE state, or the state
corresponding to PVFL = Off (direct acting) or On (reverse acting). On the
Group or Detail Display, it is the middle box for a Digital Composite or
DevCtl point. For a Digital Input point, it is the lower box.

STATETXT (2) corresponds to the second ACTIVE state. On the Group or


Detail Display for a Digital Composite or DevCtl point, it is in the lower
box. STATETXT(2) does not apply to Digital Input and Flag points.
When a two- state device is configured, STATETXT(2) is internally set to
$NULL.

STATETXT (3) “NONE” (not configurable).


STATETXT(3) does not apply to Digital Input and Flag points.

Range: N/A

Helpful Hint: STATETXT has an access lock of View if PNTFORM = Componnt.


STATETXT (2) for State 2 applies only if NOSTATES = 3 for digital
composite or device control points.

HPM Parameter Reference Dictionary S-24 8/97


STATMENT

STATMENT (ProcMod)
Type: Integer Statement—Indicates the current statement of the sequence executing in this
Lock: View process module. A statement number of 0 indicates that no statement is being
Default: 0 executed.
PtRes: HPM
Range: 1 to 255

STATTIM0–2 (DevCtl, DigComp)


Type: Time State Time—The amount of time based on the PV that has accumulated for
(Duration) States 0, 1, and 2 since the most recent reset of maintenance statistics.
Lock: View
Default: 0
PtRes: HPM
Range: 0 - 4000 Days (1 second resolution)

STDBYMAN (AnalgOut, DigOut, RegCtl)


Type: Logical Standby Manual Flag—Indicates whether the associated hardware output is
Lock: View connected to a standby manual device. It is not an indication of whether or not
Default: Off the output is isolated from the process.
PtRes: HPM
Range: Off (Output is not connected to standby-manual device)
On (Output is connected to standby-manual device)

STDBYSTS(1)–(168)
Type: Logical Standby Status Flag—Returns blind record of STDBYMAN status
Lock: View
Default:
PtRes: HPM
Range: Off (No Standby Manual present)
On (Standby Manual is activated)

STCHGOPT (DevCtl, DigComp)


Type: E:$STCHGOP State Change Option—State0 passed through before entering a new state. If
Lock: Engr/PB command disagree alarming is not configured, the point will wait for the
Default: 0-None number of seconds designated in the PAUSETIM parameter after State0 is
PtRes: 1-HPM commanded. If alarming is configured, the system will wait for the PV to go
to State0 (or when the feedback timer expires) before starting the pause timer.

Range: None (State change option is not configured)


State0 (State change option is configured)

STEP (ProcMod)
Type: String_8 Step Name—Indicates the step name of the sequence executing in this process
Lock: View module.
Default: Spaces
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary S-25 8/97


STI_EU

STI_EU (STI)
Type: E:STI_EU Smart Transmitter Engineering Units—Specifies the units of measurement for
Lock: Eng parameters LRL, LRV, URL, and URV. These units are used for display only.
Default: InH20
PtRes: HPM For multivariable Smart Transmitters with a SENSRTYP of SFM, choose
BLANK. For multivariable slots with a SENSRTYP of SPT_DP, SPT_AP,
SPT_GP, or STT, choose the preferred STI_EU (engineering units). When
BLANK is selected the limit values URL, LRL, URV and LRV are displayed in
the base engineering units specified in the transmitter user manual.

Helpful Hint: Loading an invalid STI_EU type causes an error. An attempt to correct it from
the Detail Display is rejected as CONFIG MISMATCH. To recover, load the correct STI_EU
parameter from the PED or perform an UPLOAD from the point Detail Display.

Range:
0-InH20 (Pressure transmitter—Inches of water)
1-MMHG (Pressure transmitter—Millimeters of mercury)
2-PSI (Pressure transmitter—Pounds per square inch)
3-KPA (Pressure flow transmitter—Kilopascals)
4-MPA (Pressure transmitter—Millipascals)
5-MBar (Pressure transmitter—Millibars)
6-Bar (Pressure transmitter—Bars)
7-G_SQCM (Pressure transmitter—Grams per square centimeter)
8-KG_SQCM (Pressure flow transmitter—Kilograms per square centimeter)
9-MMH20 (Pressure transmitter—Millimeters of water)
10-INHG (Pressure transmitter—Inches of mercury)
11-Deg_C (Temperature transmitter—Degrees Centigrade)
12-Deg_F (Temperature transmitter—Degrees Fahrenheit)
13-Deg_K (Temperature transmitter—Degrees Kelvin)
14-Deg_R (Temperature transmitter—Degrees Rankine)
15-MV (Temperature transmitter—Millivolts)
16-V (Temperature transmitter—Volts)
17-Ohms (Temperature transmitter—RTD Ohms)
18-CM_HR (Magnetic flow transmitter (volume)—Cubic Meters per hour)
19-Gal_HR (Magnetic flow transmitter (volume)—Gallons per hour)
20-LIT_HR (Magnetic flow transmitter (volume)—Liters per hour)
21-CC_HR (Magnetic flow transmitter (volume)—Cubic Centimeters per hour)
22-CM_Min (Magnetic flow transmitter (volume)—Cubic Meters per hour)
23-Gal_Min (Magnetic flow transmitter (volume)—Gallons per minute)
24-Lit_Min (Magnetic flow transmitter (volume)—Liters per minute)
25-CC_Min (Magnetic flow transmitter (volume)—Cubic centimeters per minute)
26-CM_Day (Magnetic flow transmitter (volume)—Cubic meters per day)
27-Gal_Day (Magnetic flow transmitter (volume)—Gallons per day)
28-KGal_Day (Magnetic flow transmitter (volume)—Thousands of gallons per day)
29-BRL_Day (Magnetic flow transmitter (volume)—Barrels per day)
30-CM_Sec (Magnetic flow transmitter (volume)—Centimeters per second)
31-KG_HR* (Magnetic flow transmitter (mass)—Kilograms per hour)
32-LBS_HR* (Magnetic flow transmitter (mass)—Pounds per hour)
33-Ft_Sec (Magnetic flow transmitter (velocity)—Feet per second)
34-M_Sec (Magnetic flow transmitter (velocity)—Meters per second)
35-KG_Min* (Magnetic flow transmitter (mass)—Kilograms per minute)
36-KG_Sec* (Magnetic flow transmitter (mass)—Kilograms per second)
37-LBS_Min* (Magnetic flow transmitter (mass)—Pounds per minute)
38-LBS_Sec* (Magnetic flow transmitter (mass)—Pounds per second)
39-PRCNT (Percent)
______________
*Not implemented

HPM Parameter Reference Dictionary S-26 8/97


STI_EU

STI_EU (STI) (continued)


40-BLANK (Blank) - Multivariable transmitter with SFM SENSRTYP
41-LBS (Pounds)
42-KG (Kilograms)
43-TONS (Tons)
44-GRAMS (Grams)
45-OZ (Ounces)
46-GAL (Gallons)
47-BRL (Barrels)
48-CUB_M (Cubic Meters)
49-LITERS (Liters)
50-MLITRES (Milliliters)
51-FL_OZ (Fluid ounce)
52-FEET (Feet)
53-METERS (Meters)
54-MM (Millimeters)
55-INCHES (Inches)
56-KG_CUM (Kilograms per cubic meter)
57-G_CUM (Grams per cubic Meter)
58-LBS_CUFT (Pounds per cubic foot)
59-LBS_CUIN (Pounds per cubic inch)

STISWVER (STI)
Type: String_8 Software Revision Level of the Smart Transmitter
Lock: View
Default: Blank
PtRes: HPM
Range: N/A

STITAG (STI)
Type: String_8 Transmitter Tag Name—Identifies the name of the Smart Transmitter to the
Lock: Eng/PB system and on displays, reports, and logs.
Default: All Spaces
PtRes: HPM

Helpful Hint: For multivariable transmitters, an identical STITAG must be entered for each
active slot related to that transmitter. The IOP uses the number of identical STITAG names to
calculate the number of PVs associated with with a given transmitter.

Range: Tag name can be up to 8 characters, and the permissible character set is as follows:
Alphabetics A-Z (uppercase or lowercase)
Numerics 0-9
Embedded space characters are allowed.

HPM Parameter Reference Dictionary S-27 8/97


STOPFL

STOPFL
Type: Logical Stop Command Flag—Stops the DigIn accumulator, RegPV totalizer, or Box
Lock: Prog Timer when flag transitions from Off to On.
Default: Off
PtRes: HPM
Range: Off (No effect on the accumulator/totalizer)
On (Stops the accumulator/totalizer from counting up/down)

STR8(1)–(16,384) (HPM Box)


Type: String_8 Box String Variables—The upper bound limit of this array is determined by the
Lock: Oper NSTRING Box parameter. The LCN index limit is 4095, while no limit exists
Default: Spaces for the UCN. Array points may be used to address strings with an index greater
PtRes: HPM than 4095.
Range: N/A

STR8(1)–(16) (ProcMod)
Type: String_8 Local String Variables—Each Process Module point has 16 local STR8
Lock: Determined by variables that are different from the HPM Box STR8 variables.
SPLOCK
parameter
Default: Spaces
PtRes: HPM
Range: N/A

STR16(1)–(8) (ProcMod)
Type: String_16 Local String Variables—Each Process Module point has 8 local STR16
Lock: Determined by variables that overlay the local STR8 variables [for example,
SPLOCK STR16(1)=STR8(1) concatenated with STR8(2)].
parameter
Default: Spaces
PtRes: HPM
Range: N/A

STR32(1)–(4) (ProcMod)
Type: String_32 Local String Variables—Each Process Module point has four local STR32
Lock: Determined by variables that overlay the local STR8 variables.
SPLOCK
parameter
Default: Spaces
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary S-28 8/97


STR64

STR64(1)–(2) (ProcMod)
Type: String_64 Local String Variables—Each Process Module point has two local STR64
Lock: Determined by variables that overlay the local STR8 variables [for example,
SPLOCK STR64(1)=STR8(1-8)].
parameter
Default: Spaces
PtRes: HPM
Range: N/A

STR8(i) (Array)
Type: String_8 Array Point String Variables—8-character string variables that are mapped to the
Lock: Determined by Array point. The number of variables is dependent on the NSTRING and
SPLOCK STRLEN variables.
parameter
Default: N/A
PtRes: HPM
Range: 1 ≤ i ≤ (Array parameter NSTRING)/(8/STRLEN)

STR16(i) (Array)
Type: String_16 Array Point String Array Variables—16-character string variables that are
Lock: Determined by mapped to the Array point. These variables overlay the STR8 variables.
SPLOCK
parameter
Default: N/A
PtRes: HPM
Range: 1 ≤ i ≤ (Array parameter NSTRING)/(16/STRLEN)

STR32(i) (Array)
Type: String_32 Array Point String Variables—32-character string variables mapped to the Array
Lock: Determined by point that overlay the STR8 variables.
SPLOCK
parameter
Default: N/A
PtRes: HPM
Range: 1 ≤ i ≤ (Array parameter NSTRING)/(32/STRLEN)

STR64(i) (Array)
Type: String_64 Array Point String Variables—64-character string variables mapped to the Array
Lock: Determined by point that overlay the STR8 variables.
SPLOCK
parameter
Default: N/A
PtRes: HPM
Range: 1 ≤ i ≤ (Array parameter NSTRING)/(64/STRLEN)

HPM Parameter Reference Dictionary S-29 8/97


STRDESC

STRDESC (Array)
Type: String_64 String Array Descriptor—64-character string describing the Array point string
Lock: PtBld data.
Default: Spaces
PtRes: HPM
Range: N/A

STRLEN (Array)
Type: Integer Array Point String Length—Indicates the length of the configured string (with
Lock: PtBld the STRSTIX and NSTRING parameters) displayed on the Array Point Detail
Default: 8 display. Strings can be accessed by STR8, STR16, STR32 or STR64 regardless
PtRes: HPM of this value.
Range: 8, 16, 32, 64

STRLEN (ProcMod)
Type: Integer Process Module String Length—Indicates the displayed string length on the
Lock: PtBld Process Module Detail display. Strings can still be accessed by STR8, STR16,
Default: 8 STR32, or STR64 regardless of this value.
PtRes: HPM
Range: 8, 16, 32, 64

STRSTIX (Array)
Type: Real String Array Start Index—Defines the string array start index in Box STR8
Lock: PtBld variables, or the Serial Interface-connected device.
Default: 0
PtRes: HPM
Range: 0 to Box parameter NSTRING (When EXTDATA≠IO_STR, 0 indicates no strings are configured)
0 to 99,999 (When EXTDATA=IO_STR, 0 can be a valid device index)

STRTFAIL(1)–(6)
Type: String_2 Startup/Failover Information
Lock: View
Default:
PtRes: HPM
Range: Hexadecimal characters 00 to FF

STSMSG
Type: E:MSGTXT Status Message—A self-defining enumeration of the MSGTXT parameter that
Lock: Oper provides additional descriptive information regarding the red tag, batch state, or
Default: MSGTXT(0) device state.
PtRes: HPM
Range: MSGTXT(0) to MSGTXT(15)

HPM Parameter Reference Dictionary S-30 8/97


SUMSLTSZ

SUMSLTSZ (HPM Box)


Type: Integer Total Configured Memory for Sequence Programs—This parameter equals the
Lock: View sum of all Process Module SEQSLTSZ parameters, and is shown on the
Default: 0 HPMM Control Configuration display.
PtRes: HPM
Range: >0

SUSPSTAT (ProcMod)
Type: E:$SUSPST Suspend State
Lock: View
Default: None
PtRes: HPM
Range: 0-None
2-Feedback
3-Wait
4-ConfMsg
5-InputMsg

SUSPTIME (ProcMod)
Type: Integer Suspension Timer—The remaining time (in minutes) before the sequence
Lock: View program resumes execution. This timer is started when a sequence program
Default: 0 executes a wait statement.
PtRes: HPM
Range: 0 to 32, 767 minutes

SVALDB (DevCtl)
Type: E:PVALDB SECVAR Alarm Deadband—The deadband for the SECVAR alarm.
Lock: Engr/PB
Default: One
PtRes: HPM
Range: 0-Half (1/2 of 1% of Engineering Unit range)
1-One (1% of Engineering Unit range)
2-Two (2% of Engineering Unit range)
3-Three (3% of Engineering Unit range)
4-Four (4% of Engineering Unit range)
5-Five (5% of Engineering Unit range)
6-EU (Value is defined by SVALDBEU parameter)

SVALDBEU (DevCtl)
Type: Real SECVAR Alarm Deadband in Engineering Units—Indicates the alarm deadband
Lock: Engr/PB in engineering units when the SVALDB parameter = EU.
Default: 0.0
PtRes: HPM
Range: Allowable Engineering Units

HPM Parameter Reference Dictionary S-31 8/97


SVDESC

SVDESC (DevCtl)
Type: String_8 SECVAR Descriptor—Defines the SECVAR parameter or secondary variable
Lock: PtBld descriptor.
Default: Blank
PtRes: HPM
Range: 8 Character String

SVEUDESC (DevCtl)
Type: String_8 SECVAR Engineering Unit Descriptor—Defines the engineering unit descriptor
Lock: PtBld for the SECVAR parameter or secondary variable descriptor.
Default: Blank
PtRes: HPM
Range: 8 Character String

SVEUHI (DevCtl)
Type: Real SECVAR Range High—Defines the high engineering unit range for the
Lock: Engr/PB SECVAR parameter.
Default: NaN
PtRes: HPM
Range: <> NaN

SVEULO (DevCtl)
Type: Real SECVAR Range Low—Defines the low engineering unit range for the
Lock: Engr/PB SECVAR parameter.
Default: NaN
PtRes: HPM
Range: <> NaN

SVHHFL (DevCtl)
Type: Logical SECVAR High-High Alarm Flag
Lock: View
Default: Off
PtRes: HPM
Range: Off (SECVAR parameter is below the SVHHTP parameter minus the deadband)
On (SECVAR parameter has exceeded the SVHHTP parameter)

SVHHPR (DevCtl)
Type: E:ALPIOR SECVAR High-High Alarm Priority
Lock: Engr
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized, reported to printer, but not annunciated)
Printer (Reported to printer only)
Emergncy (Reported to all alarm summary displays)
High (Reported to Area Alarm Summary Display and Unit Alarm Summary Display)
Low (Reported to Unit Alarm Summary Display)
Journal (Logged but not reported to Universal Stations)
NoAction (Alarm is not reported to the system)

HPM Parameter Reference Dictionary S-32 8/97


SVHHTP

SVHHTP (DevCtl)
Type: Real SECVAR High-High Alarm Trip Point—No alarms are generated when this
Lock: Supr parameter is set to NaN.
Default: NaN
PtRes: HPM
Range: ≥ SVHITP or NaN

SVHHTPP (DevCtl)
Type: Real SECVAR High-High Trip Point Percent—The SECVAR High-High Trip Point
Lock: Supr in terms of engineering units in percent.
Default: NaN
PtRes: HPM
Range: 0 to 100

SVHIFL (DevCtl)
Type: Logical SECVAR High Alarm Flag—This flag is set when the SECVAR exceeds
Lock: View SVHITP and is reset when SECVAR is below SVHIFL minus deadband.
Default: Off
PtRes: HPM
Range: Off (SECVAR parameter is below SVHIFL minus the deadband)
On (SECVAR parameter has exceeded SVHIFL)

SVHIPR (DevCtl)
Type: E:ALPRIOR SECVAR High Alarm Priority
Lock: Engr
Default: Low
PtRes: NIM
Range: JnlPrint (Alarm is historized and reported to the printer but not annunciated)
Printer (Alarm is reported to the printer but not historized and not annunciated)
Emergncy (Alarm is historized, annunciated, and reported to all alarm summary displays)
High (Alarm is historized, reported to Area Alarm Summary Display and Unit Alarm Summary
Display)
Low (Alarm is historized, reported to the Unit Alarm Summary Display, and annunciated)
Journal (Alarm is historized but not reported to Universal Stations and not annunciated)
NoAction (Alarm is not reported to the system and not annunciated)

SVHITP (DevCtl)
Type: Real SECVAR High Alarm Trip Point—When this parameter is set to NaN, no
Lock: Supr alarms are generated.
Default: NaN
PtRes: HPM
Range: ≥ SVEULO or NaN

HPM Parameter Reference Dictionary S-33 8/97


SVHITPP

SVHITPP (DevCtl)
Type: Real SECVAR High Alarm Trip Point Percent—The SECVAR High Trip Point in
Lock: Supr terms of engineering units percent.
Default: NaN
PtRes: HPM
Range: 0 to 100

SVP (DevCtl)
Type: Real SECVAR in Percent of Engineering Range—The percentage for this parameter is
Lock: View calculated from the SECVAR parameter, using both the SVEVHI and SVELVO
Default: NaN parameters.
PtRes: HPM
Range: 0 to 100

SVPEAK (DevCtl)
Type: Real Peak Value of SECVAR—Indicates the highest value of the SECVAR parameter
Lock: View since the device changed from state 0.
Default: NaN
PtRes: HPM
Range: Real or NaN

SVSRC (DevCtl)
Type: Universal SECVAR Input Connection—Specifies input connection to which the current
Ent.Prm values of Device Control inputs are supplied. The connection can be specified
Lock: PtBld using the "Tagname.Parameter" format or the hardware reference address format
Default: Null Refer to the HPM Control Functions and Algorithms manual for a detailed
PtRes: HPM description.
Range: Use Tagname.Parameter for tagged points where Tagname can be up to 16 characters and the
permissible character set is as follows:
Alphabetics A-Z (uppercase only)
Numerics 0-9 (an all numeric tag name is not allowed)
Underscore (_) cannot be used as the first character or the last character, and consecutive
underscores are not allowed.
Embedded space characters are not allowed.
An * is used to default to this point's tag name.
Parameter name can be up to eight characters and must be a legitimate parameter name.

Some possible input-connection sources are


a."Logic slot Tagname.NN(nn)" where nn = 1–8
b."ProcMod slot Tagname.NN(nnn)" where nnn = 1–80
c."Box Numerics slot Tagname.NN” where nnnnn = 1-16,384
d."!Box.FL(nnnn)" for a box flag that resides in the same box where nnnn = 1–16,384

Use the hardware reference address !MTmmSss.Parameter for untagged or tagged points where
MT is the IOP type, such as AI (Analog Input)
mm is the IOP Card number (1–40)
The letter "S" is a constant
ss is the slot number on the IOP Card (refer to SLOTNUM parameter)
Parameter name can be up to eight characters and must be a legitimate parameter name.

HPM Parameter Reference Dictionary S-34 8/97


SVTV

SVTV (DevCtl)
Type: Real Secondary Variable Target Value—Indicates the normal or operating setpoint for
Lock: Oper the SECVAR parameter.
Default: NaN
PtRes: HPM
Range: SVEULO to SVEUHI

SVTVP (DevCtl)
Type: Real Secondary Variable Target Value in Percent—Indicates the normal or operating
Lock: Oper setpoint for the SECVAR parameter as a percent.
Default: NaN
PtRes: HPM
Range: 0 to 100

SWTCHACT (1)–(40) (HPM Box)


Type: Logical IOP Synchronization—When this parameter is Off (inactive), the backup request
Lock: View line from the IOP's partner is not asserted. When this parameter is On (active),
Default: On the backup request line from the IOP's partner is asserted.
PtRes: HPM
Range: On-Active
Off-Inactive

SYNCHSTS(1)–(40) (HPM Box)


Type: E:$SYNCHST Primary/secondary Database Synchronization Status. It is set to WARNING
Lock: View when a database inconsistency is first detected, but the secondary appears
Default: None capable of providing backup. It changes to FAIL when the HPMM has tried
PtRes: HPM to resync but does not succeed or a secondary failure prevents synchronization.
nn = 1–40 corresponds to the 40 logical I/O modules.
Applies to primary IOP only.

Range: 0-OK - (the secondary is synchronized with the


primary and can provide backup if necessary.)
1-WARNING - (database inconsistency detected
but secondary can probably provide backup).
2-FAIL - (HPMM has tried to resynchronize but
has not succeeded or, secondary has also failed).

HPM Parameter Reference Dictionary S-35 8/97


HPM Parameter Reference Dictionary S-36 8/97
T

-T-

T (FlowComp)
Type: Real Temperature Input—Indicates the measured actual temperature.
Lock: View
Default: 1.0
PtRes: HPM
Range: > 0.0

T0 (FlowComp)
Type: Real Zero Reference for Temperature—T0 is the zero reference temperature input and
Lock: Supr it is in the same engineering units as the T (measured actual temperature) input.
Default: 0.0 T0 is typically -459.69 degrees F or -273.15 degrees C. Enter the absolute value
PtRes: HPM of the temperature.
Range: N/A

T1
Type: Real Integral Time in Minutes—Defines the integral time constant in
Lock: Supr minutes-per-repeat.
Default: 0.0 minutes
PtRes: HPM
Range: 0.0 to 1440.0 minutes

Helpful Hint: Integral action can be disabled by setting T1 equal to 0.0.

T2
Type: Real Derivative Time in Minutes—Defines the derivative time constant.
Lock: Supr
Default: 0.0 minutes
PtRes: HPM
Range: 0.0 to 1440.0 minutes

Helpful Hint: Derivative action can be disabled by setting T2 equal to 0.0

TCRNGOPT
Type: E:$TCRNGOP Thermocouple Range Option—Defines the thermocouple range option.
Lock: Eng/PB Applies only if a thermocouple (TC) sensor type is used for this data point.
Default: Normal
PtRes: HPM
Range: 0-Normal (Use PVEXEULO's normal range table)
1-Extended (Use PVEXEULO's extended range table)

Helpful Hint: TCRNGOPT configuration requires IOTYPE = LLAI, LLMUX, or RHMUX and
SENSRTYP = Thermcpl. Refer to parameter PVEXEULO.

HPM Parameter Reference Dictionary T-1 8/97


TD

TD (VdtLdLag)
Type: Real Total Dead Time in Minutes—Defines the fixed delay time in minutes for
Lock: Supr equation B, and the actual variable delay time in minutes for equations C and D.
Default: 0.0
PtRes: HPM
Range: > 0.0 minutes

TF
Type: Real PV Filter Lag Time in Minutes—Defines the filtering time lag to be used after
Lock: Supr the PV range has been checked. A value of 0.0 specifies that the PV is not
Default: 0.0 minutes delayed.
PtRes: HPM
Range: 0.0 to 60.0 minutes

TIERTYPE (HPM Box)


Type: E:$TIERTYP HPMM Tier Type
Lock: View
Default:
PtRes: HPM
Range:

TIME(1)–(4095) (HPM Box)


Type: Time Box Time Variables—The upper limit of this array is determined by the NTIME
Lock: Oper parameter. The LCN index limit is 4,095, while the limit on the UCN is 4096.
Default: 0 seconds Array points may be used to address Times with an index greater than 4095.
PtRes: HPM
Range: N/A

TIME(i) (Array)
Type: Time Array Point Time Variables—Times are mapped from the HPM Box defined by
Lock: Determined by the TIMESTIX and NTIME parameters.
SPLOCK
parameter
Default: N/A
PtRes: HPM
Range: 1 ≤ i ≤ Array parameter NTIME

TIME(1)–(4) (ProcMod)
Type: Time Local Time Variables—Four local Time variables are available in each Process
Lock: Determined by Module point. These variables are different than the HPM Box Time variables.
SPLOCK
parameter
Default: 0 seconds
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary T-2 8/97


TIMEBASE

TIMEBASE (Timer)
Type: E:TIMEBASE Time Base—Defines the time base to be used for the Timer data point.
Lock: Engr
Default: Seconds
PtRes: HPM
Range: 0-Seconds
1-Minutes

TIMEBASE (Totalizr, PI)


Type: E:TIMEBASE Totalizer Time Base—Defines whether time base is in seconds, minutes, or
Lock: Eng/PB hours.
Default: Minutes
PtRes: HPM
Range: 0-Seconds (PV and Setpoint engineering units (gallons, etc.) per second)
1-Minutes (PV and Setpoint engineering units (gallons, etc.) per minute)
2-Hours (PV and Setpoint engineering units (gallons, etc.) per hour)

TIMEDESC (Array)
Type: String_64 Time Array Descriptor—Sixty four-character string describing Time data.
Lock: PtBld
Default: Spaces
PtRes: HPM
Range: N/A

TIMESECS(1)–(240) (Array)
Type: Time Array Point Time Variables—Times mapped from the HPM box defined by
Lock: Determined TIMESTIX and NTIME parameters.
by SPLOCK
parameter
Default: N/A
PtRes: HPM
Range: 1 ≤ i ≤ NTIME Array parameter

TIMESTIX (Array)
Type: Real Time Array Start Index—Defines the Time data start index in the Box Time
Lock: PtBld variables.
Default: 0
PtRes: HPM
Range: 0 to Box parameter NTIME (0 indicates there are no Times configured for this point)

TIMESYNC (UCN)
Type: E:ENBLSTAT Timesynch Control—Defines whether SOE timesynch can be performed by
Lock: PtBld this NIM or NIM pair. Normally, the NIM with the lowest address is
Default: Disable configured for this function.
PtRes: NIM
Range: Enable (This NIM or NIM pair is able to perform SOE time synchronization)
Disable (This NIM or NIM pair does not perform SOE time synchronization, but can receive and
report SOE events)

HPM Parameter Reference Dictionary T-3 8/97


TLD

TLD (VdtLdLag)
Type: Real Lead Time Constant in Minutes—Defines the lead-compensation time constant
Lock: Supr in minutes. A 0 (zero) entry specifies no lead compensation.
Default: 0.0 minutes
PtRes: HPM
Range: -1440.0 to 1440.0 minutes

TLG1, TLG2 (VdtLdLag)


Type: Real Lag Time Constant
Lock: Supr
Default: 0.0 minutes
PtRes: HPM
Range: 0.0 to 1440.0 minutes (0 specifies no lag compensation)

TMCMD(1)–(64) (HPM Box)


Type: E:COMMAND Timer Command—An array of commands issued to the 64 Timer data points.
Lock: Oper
Default: N/A
PtRes: HPM
Range: 0-None (A command has not been issued to the timer)
1-Start (Starts the timer)
2-Stop (Stops the timer)
3-Reset (Resets the timer to 0)
4-RestStrt (Resets the timer to 0, and starts the timer)

TMPV(1)–(64) (Timer)
Type: Integer Timer PV—Indicates the current (elapsed) time of the Timer data point in
Lock: View seconds or minutes.
Default: 0
PtRes: HPM
Range: >0

TMRV(1)–(64) (Timer)
Type: Integer Timer RV—Indicates the remaining time (TMSP minus TMPV) for the Timer
Lock: View data point.
Default: 0
PtRes: HPM
Range: >0

TMSO(1)–(64) (Timer)
Type: Logical Timer Status Output—Indicates the current state of the timer output.
Lock: View
Default: Off
PtRes: HPM
Range: Off (TMPV ≠ TMSP; elapsed time has not reached the preset time)
On (TMPV = TMSP; elapsed time has reached the preset time)

HPM Parameter Reference Dictionary T-4 8/97


TMSP

TMSP(1)–(64) (Timer)
Type: Integer Timer Setpoint—Defines the preset time of the Timer data point, in seconds or
Lock: Oper minutes.
Default: 0
PtRes: HPM
Range: 0 to 32000

TMST(1)–(64) (Timer)
Type: E:STATE Timer State—Indicates the current state of the Timer data point.
Lock: View
Default: Stopped
PtRes: HPM
Range: 0-Stopped (Timer is currently stopped)
1-Running (Timer is currently running)

TMTB(1)–(64) (Timer)
Type: E:TIMEBASE Timer Time Base—Defines the time base of the timer.
Lock: Engr
Default: Seconds
PtRes: HPM
Range: 0-Seconds
1-Minutes

TOTLUAVG (1) - (2) (HPM Box)


Type: Real Average IOL Utilization (in per cent) by the HPM, per I/O Link— (total
Lock: View utilization by the Comm and Control CPUs)
Default: 0.0
PtRes: HPM
Range: 0 - 100

TOTLUMAX (1) - (2) (HPM Box)


Type: Real Maximum IOL Utilization (in per cent) by the HPM, per I/O Link— (total
Lock: View utilization by the Comm and Control CPUs)
Default: 0.0
PtRes: HPM
Range: 0 - 100

TRACKING
Type: Logical Selected Input Tracking—Allows the selected input to be changed without
Lock: Eng/PB bumping the output.
Default: Off
PtRes: HPM
Range: Off (Tracking disabled)
On (Tracking is to be used)

Helpful Hint: If On, causes nonselected inputs to track the selected input.

HPM Parameter Reference Dictionary T-5 8/97


TRANTIMO

TRANTIM0–2 (DevCtl, DigComp)


Type: Time Transition Time—The date and time of the most recent transition to each state
Lock: View based on the PV.
Default: 0
PtRes: HPM
Range: Time Stamp

TRATAVG (NIM, HPM Box)


Type: Real Average UCN Transaction Trip Time—The average UCN transaction trip time
Lock: View in milliseconds for both fetch and store responses from this node to other
Default: NaN UCN nodes.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays

TRATMAX (NIM, HPM Box)


Type: Real Maximum UCN Transaction Trip Time—The maximum UCN transaction trip
Lock: View time in milliseconds for both fetch and store responses from this node to other
Default: NaN UCN nodes.
PtRes: HPM
Range: N/A

Helpful Hint: This statistic can be viewed on the Toolkit Displays.

TRFB (PidErfb)
Type: Real Tracking Feedback Input in Engineering Units—Indicates the value of the PV or
Lock: View SP of another data point that is receiving its setpoint from this data point.
Default: NaN
PtRes: HPM
Range: N/A

TSCOMP
Type: Time Time Stamp, CL Source Compatibility —Specifies the CL Source
Lock: View compatibility time stamp (CL object header)
Default: 0
PtRes: HPM
Range: N/A

TSSRC
Type: Time Time Stamp, CL Source—Specifies the CL Source time stamp (CL object
Lock: View header)
Default: 0
PtRes: HPM
Range: N/A

HPM Parameter Reference Dictionary T-6 8/97


TSTS

TSTS (FlowComp)
Type: E:PVVALST Temperature Input Value Status—Status of the T input value.
Lock: View
Default: Normal
PtRes: HPM
Range: 0-Bad (Value is bad and replaced with NaN)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

TSUNICHG
Type: Time Time Stamp, Unit Change—Specifies the CL Unit Change time stamp (CL
Lock: View object header)
Default: 0
PtRes: HPM
Range: N/A

TVPROC (RegCtl)
Type: E:TVPROC Target Value Processor State
Lock: Oper
Default: Off
PtRes: HPM
Range: 0-Off (No target value processing)
1-Preset (Set up setpoint target value and ramp time)
2-Run (Perform ramping function)

Helpful Hint: TVPROC applies only if SPOPT = TV.

HPM Parameter Reference Dictionary T-7 8/97


HPM Parameter Reference Dictionary T-8 8/97
UCNRECHN

-U-
UCNRECHN (HPM Box, NIM)
Type: E:$RECCHN UCN Receive Channel—Indicates the channel to which the node is listening.
Lock: View
Default: ChannelA
PtRes HPM, NIM
Range: 0-ChannelA
1-ChannelB

UCNSCANT (HPM Box)


Type: Real Peer-to-Peer Scan Period in seconds
Lock: Eng/PB
Default: 0.5
PtRes: HPM
Range: 0.5, 1.0

UCNSFREV
Type: Integer UCN Software Revision
Lock: View
Default: N/A
PtRes HPM

UCNSFVER
Type: Integer UCN Software Version
Lock: View
Default: N/A
PtRes HPM

UCNWRTLK (HPM Box)


Type: E: UCNWRTL HPM Write Lockout—When HPM Write Lockout is set to On, all
Lock: Eng Writes to the HPM (except writes to UCNWRTLK and some IOL
Default: WrtLkOff parameters) are locked out including peer-to-peer writes. All parameter
PtRes: HPM reads are allowed as well as cable swaps, HPMM swaps and IOP
swaps.

Range: 0-WrtLkOff - (Write Lock Off, UCN node is read/write)


1-WrtLkOn - (Write Lock On, UCN node is read only)

Helpful Hint: Write Lockout must be set to Off before any changes are made to configuration,
modes, or setpoints. The state of UCNWRTLK can only be changed when the HPM is either in
RUN or RUNSOFTFAIL state.

UCNWRTL can be changed (under Engineer Key Level) from the HPM Write Lock Control
display. Refer to the HPM Implementation Guidelines for more information.

HPM Parameter Reference Dictionary U-1 8/97


UNCMDFL

UNCMDFL (DevCtl, DigComp)


Type: Logical Uncommanded Change Alarm Flag—Indicates whether an uncommanded change
Lock: View has been detected in the field device. (Field device has changed its state without
Default: Off a command.)
PtRes HPM
Range: Off (No uncommanded change alarm)
On (Uncommanded change alarm has been detected by this point)

UNIT
Type: String_2 Unit Identifier—Defines the process unit to which this point is assigned. The
Lock: PtBld unit identifier is originally assigned during network configuration, and it appears
Default: N/A in displays and listings throughout the system.
PtRes NIM
Restriction: Two characters are required; blanks are not allowed. For example,
unit 3 must be entered as 03.
CL and Picture Editor — An integer is returned. This number is equivalent to
the unit position in the Unit Names configuration list.

Range: A-Z, 0-9 (up to 100 unit IDs can be configured)

UPGRADE (UCN)
Type: E:UPGRADE NIM Upgrade Status
Lock: Oper
Default: OK
PtRes NIM
Range: OK (NIM has not been upgraded and is OK)
Upgrade (NIM is upgraded and is questionable)

HPM Parameter Reference Dictionary U-2 8/97


URL(STI)

URL (STI)
Type: Real Upper Range Limit—Indicates the upper range limit of the PV at the Smart
Lock: Eng/View Transmitter. This limit is a fixed limit and cannot be changed. Refer to the
Default: NaN description of the STI_EU parameter for the URL engineering units. During
PtRes: HPM configuration, the value entered for this parameter must agree with the URL
value of the transmitter. Although any value can be entered during
configuration, a database mismatch will occur when the point is put on-process
because the transmitter's URL value and the STI IOP's URL value are not the
same. If the values are not the same, the STATE parameter value becomes
DBChange and PVSTS becomes Bad. Refer to URL in the PM/APM Smartline
Transmitter Integration Manual for more information.
The corresponding LRL parameter is not a configurable parameter at the
Universal Station.
The upper range limits for the Smart Transmitters are as follows:
For the ST3000 Smart Pressure Transmitters (Spt_Dp, Spt_Gp and Spt_Ap):
Xmtr Range URL (In H2O)

400 inH2O 400.0


600 inH2O 600.0
780 mmHga 400.0
100 PSI 2768.0
200 PSI 5536.13
500 PSI/A 13840.34
1500 PSI 41521.0
2000 PSI 55361.35
3000 PSI 83042.02
6000 PSI 166084.0
10000 PSI 276806.7

For the STT3000 Smart Temperature Transmitter (STT):


Sensor Type URL
(PVCHAR) (in Degrees C except where noted)
Linear (mV) 1000 mV
Thermocouples:
B 1820
E 1000
J 1200
K 1370
NiNiMoTC 1300
N 1300
R 1760
S 1760
T 400
W5W26TC 2300
W3W25TC 2300

HPM Parameter Reference Dictionary U-3 8/97


URL(STI)
URL (STI) (continued)
RTDs:
Cu10RTD 250
Cu25RTD 250
DINRTD 850
JISRTD 640
NicklRTD 150
Pt200 850
Pt500 850
RHRad 1800
RTD (ohms) 4000 Ω

For the MagneW 3000 Magnetic Flowmeter (Sfm):

πD2
URL (in meters3/hour) = x 3600 x (N + 1)
4x106

where: D = the detector diameter in millimeters as follows: 2.5, 5, 10, 15, 25,
40, 50, 80, 100, 150, 200, 300, 350, 400, 500, 600, or 700
N = the number of dummy submerged detectors, from 0 to 9
Range: N/A, NaN

URV (STI)
Type: Real Upper Range Value—Defines the upper end of the operating range for the
Lock: Supr/View PVRAW value. Refer to the description of the STI_EU parameter for the URV
Default: NaN engineering units.
PtRes: HPM
Range: N/A, NaN Although the following maximum values can be entered, values greater than the
URL are not recommended and accuracy is not guranteed in such cases.

For a pressure transmitter (Spt): URVmax = 2.0 x URL


For a temperature transmitter (Stt): URVmax = 2.0 x URL
For a magnetic flow transmitter (Sfm): URVmax = 12.0 x URL

This parameter is a view-only parameter when the STI point execution state
PTEXECST is Active (indicating that changes cannot be made in this parameter
value from the Universal Station).

USERID (Array, DevCtl, DigComp, ProcMod,


RegCtl, RegPV)
Type: String_16 User ID Reservation—The user ID that currently has reserved this point. The
Lock: Oper User ID can be changed by either a point, program, or operator. The operator
Default: Dashes can overwrite the USERID parameter at anytime. A program can store a
PtRes HPM nonblank string in this parameter only if it is blank. If the USERID string
starts with three or more dashes (- - -), only the operator can overwrite the ID.
Range: 16 Character String

HPM Parameter Reference Dictionary U-4 8/97


UTSDRIFT

UTSDRIFT (HPM Box, NIM)


Type: Integer UCN Node Clock Drift—Indicates the current HPMM clock drift rate, calculated
Lock: View by averaging the LCN clock interval and SYNCH CLOCK interval over
Default: N/A multiple synchs. Averaging does not occur until UCN time synchronization is
PtRes HPM, NIM in a steady state.
Range:

UTSNODE (HPM Box, NIM)


Type: Integer Last UCN Syncher Node—Describes which node is the synch master or
Lock: View syncher. Normally, this is the primary NIM, even though the secondary NIM
Default: 0 can also be the syncher. The syncher function performs periodic time
PtRes HPM, NIM synchronization on the UCN.

Range: 0, 1 to 64 (0 specifies No Syncher Node)

UTSTBCRV (HPM Box, NIM)


Type: String_2 TBC Revision—The token bus controller revision number in hexidecimal
Lock: View format.
Default: N/A
PtRes HPM, NIM
Range: 5 to 15

UTSTIME (HPM Box, NIM)


Type: Time Current Time in LCN Node—Identifies the current time of day for this LCN
Lock: View node, and is useful if there are multiple LCNs or UCNs.
Default: N/A
PtRes HPM, NIM
Range: N/A

UTSTIMST (HPM Box, NIM)


Type: E:$UCNTMST Timesynch State of the UCN Node—The state of time synchronization
Lock: View for each UCN node.
Default: 0
PtRes HPM, NIM
Range: 0-Initial (Waiting for the first complete synch operation)
1-Failed (The maximum amount of time has elapsed and no synch operation has occurred,
or the NIM does not have a functioning EPNI board)
2-Degraded (In nonsyncher NIMs and HPMMs, an excessive amount of time has elapsed without
a complete synch operation. In HPMMs, the drift limit between the LCN and
HPMM clock has been exceeded)
3-LCN_Bad (Synch operations are taking place on a regular basis, but the NIM’s clock is not
synched with the LCN)
4-LCN_OK (Synch operations are occurring regularly and the NIM’s clock is properly synched
with the LCN)
5-OK (Synch operations are working in an optimal manner)

HPM Parameter Reference Dictionary U-5 8/97


HPM Parameter Reference Dictionary U-6 8/97
WARMSTRT(1)–(168)

-W-

WARMSTRT(1)–(168)
Type: Logical Warm Start Flag
Lock: View
Default: N/A
PtRes IOP
Range: On (Warm start executed)
Off (Cold start executed)

WEEKDAY (HPPM Box)


Type: Integer Current Weekday—The current weekday based on LCN wall clock time.
Lock: View
Default: N/A
PtRes HPM
Range: 1 to 7 (Sunday to Saturday)

WITHBIAS(1)–(40) (HPPM Box)


Type: Logical I/O Module Physical Bias State—ON Indicates that the preferred
Lock: View primary is really the acting primary; OFF indicates that it is not.
Default: ON For IOPs that do not have hardware bias (e.g., HLAI, DI, etc.),
PtRes HPM the status of ON is always returned. Applies to primary IOP only.

Range: On (The preferred primary is the acting primary)


Off (The preferred primary is not the acting primary)

HPM Parameter Reference Dictionary W-1 8/97


HPM Parameter Reference Dictionary W-2 8/97
X

-X-

X (FlowComp)
Type: Real Steam Compressibility Input—Indicates the measured actual steam
Lock: View compressibility.
Default: 1.0
PtRes HPM
Range: > 0.0

X1 (AutoMan)
Type: Real X1 Input Value to be Biased
Lock: Prog
Default: NaN
PtRes HPM
Range: NaN

X1–3 (MulDiv)
Type: Real Inputs 1-3—Current values of the inputs to this algorithm.
Lock: Prog
Default: NaN
PtRes HPM
Range: > 0.0,
NaN

X1–4 (IncrSum, ORSel, RegCtl Summer)


Type: Real Inputs 1-4—Current values of the inputs to this algorithm.
Lock: Prog
Default: NaN
PtRes HPM
Range: > 0.0,
NaN

X2 (AutoMan)
Type: Real Bias Adjustment Input
Lock: View
Default: N/A
PtRes HPM
Range: N/A

X2 (RatioCtl)
Type: Real Input Number 2—Indicates the value of the uncontrolled process variable.
Lock: View Source should be the same as for P2 of the Calcultr algorithm, if it is being used
Default: N/A in conjunction with the Calcultr algorithm.
PtRes HPM
Range: N/A

HPM Parameter Reference Dictionary X-1 8/97


X2FILT

X2FILT (RatioCtl)
Type: Real Filtered value of the X2 input
Lock: View
Default: N/A
PtRes HPM
Range: N/A

Helpful Hint: Filter time is determined by X2TF. This filter is only active if the point is in
the AUTO or CASC mode.

X2TF (RatioCtl)
Type: Real X2 input filter lag time in minutes
Lock: Supr
Default: 0.0
PtRes HPM
Range: 0 - 60 minutes

XEUHI (AutoMan, IncrSum, ORSel)


Type: Real X Input Engineering Unit High Range—Defines the upper limit of the value of
Lock: Engr the X input or inputs.
Default: 100.0
(equivalent
to 100%)
PtRes HPM
Range: > XEULO

XEULO (AutoMan, IncrSum, ORSel)


Type: Real X Input Engineering Unit Low Range—Defines the lower limit of the value of
Lock: Engr the X input or inputs.
Default: 0.0
(equivalent
to 0%)
PtRes HPM
Range: < XEUHI

XSTS (FlowComp)
Type: E:PVVALST X Input Value Status—Status of the steam compressibility input.
Lock: View
Default: Normal
PtRes HPM
Range: 0-Bad (Value is bad and replaced with NaN)
1-Uncertn (Status of the value is uncertain)
2-Normal (Value is good)

HPM Parameter Reference Dictionary X-2 8/97


YEAR

-Y-

YEAR (HPM Box)


Type: Integer Current Year—The value of the LCN date in the HPM.
Lock: View
Default: N/A
PtRes HPM
Range: 1979 to 2115

HPM Parameter Reference Dictionary Y-1 8/97


HPM Parameter Reference Dictionary Y-2 8/97
FAX Transmittal FAX No.: (602) 313-4842
TO: Andrea Simmons Total FAX pages:
(including this page)
Reader Comments
Title of Document: HPM Parameter Reference Dictionary
Document Number: HP09-540 Issue Date: 8/97

Comments:

Recommendations:

FROM:
Name: Date:
Title:
Company:
Address:
City: State: ZIP:
Telephone: FAX:

You may also call 800-822-7673 (available in the 48 contiguous states except Arizona; in Arizona dial
602-313-5558, or write to:
Honeywell Inc.
Industrial Automation and Control
Automation College
2820 West Kelton Lane
Phoenix, AZ 85023-3028
Industrial Automation and Control Helping You Control Your World
Automation College
2820 W. Kelton Lane
Phoenix, AZ 85023-3028