CSC-326

Transformer Protection IED


Technical Application Manual
CSC-326 数字式变压器保护装置
说明书
(英文)

编 制:

校 核:

标准化审查:说明书
审 定:
CSC-326
数字式变压器保护装置
版 本 号: V2.10
技术应用手册
文件代号:
(定制项目号(仅定制文档填写)+语种(英文/法文…))
出版日期: 2016.06
Version:V2.10
Doc. Code:0SF.450.085(E)
Issued Date:2016.06
Copyright owner: Beijing Sifang Automation Co., Ltd

Note: the company keeps the right to perfect the instruction. If equipment does not agree
with the instruction at anywhere, please contact our company in time. We will provide you
with corresponding service.

®
is registered trademark of Beijing Sifang Automation Co., Ltd.

We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and dis-
semination to third parties, is not permitted.

This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.

The data contained in this manual is intended solely for the product description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result; it is possible that there may be some differences between the hardware/software
product and this information product.

Manufacturer:
Beijing Sifang Automation Co., Ltd.
Email: support@sf-auto.com
Website: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085
Preface
Purpose of this manual

This manual describes the functions, operation, installation, and placing into
service of device CSC-326. In particular, one will find:

 Information on how to configure the device scope and a description of the


device functions and setting options;

 Instructions for mounting and commissioning;

 Compilation of the technical specifications;

 A compilation of the most significant data for experienced users in the


Appendix.

Target Audience

Protection engineers, commissioning engineers, personnel concerned with


adjustment, checking, and service of selective protective equipment, automatic
and control facilities, and personnel of electrical facilities and power plants.

Applicability of this Manual

This manual is valid for SIFANG Distance Protection IED CSC-326; firmware
version V1.00 and higher

Indication of Conformity
Additional Support

In case of further questions concerning IED CSC-326 system, please contact


SIFANG representative.

Safety information

Strictly follow the company and international safety regulations.


Working in a high voltage environment requires serious approch
to aviod human injuries and damage to equipment
Do not touch any circuitry during operation. Potentially lethal
voltages and currents are present

Avoid to touching the circuitry when covers are removed. The


IED contains electirc circuits which can be damaged if exposed
to static electricity. Lethal high voltage circuits are also exposed
when covers are removed

Using the isolated test pins when measuring signals in open


circuitry. Potentially lethal voltages and currents are present

Never connect or disconnect wire and/or connector to or from


IED during normal operation. Dangerous voltages and currents
are present. Operation may be interrupted and IED and
measuring circuitry may be damaged

Always connect the IED to protective earth regardless of the


operating conditions. Operating the IED without proper earthing
may damage both IED and measuring circuitry and may cause
injuries in case of an accident.

Do not disconnect the secondary connection of current


transformer without short-circuiting the transformer’s secondary
winding. Operating a current transformer with the secondary
winding open will cause a high voltage that may damage the
transformer and may cause injuries to humans.

Do not remove the screw from a powered IED or from an IED


connected to power circuitry. Potentially lethal voltages and
currents are present

Using the certified conductive bags to transport PCBs (modules).


Handling modules with a conductive wrist strap connected to
protective earth and on an antistatic surface. Electrostatic
discharge may cause damage to the module due to electronic
circuits are sensitive to this phenomenon
Do not connect live wires to the IED, internal circuitry may be
damaged

When replacing modules using a conductive wrist strap


connected to protective earth. Electrostatic discharge may
damage the modules and IED circuitry

When installing and commissioning, take care to avoid electrical


shock if accessing wiring and connection IEDs

Changing the setting value group will inevitably change the IEDs
operation. Be careful and check regulations before making the
change
Contents
Chapter 1 Introduction ........................................................................................................1
1 Overview ..........................................................................................................................2
2 Features ...........................................................................................................................3
Chapter 2 Basic protection elements .................................................................................9
1 Startup element ............................................................................................................. 10
1.1 Introduction ..................................................................................................... 10
1.2 Sudden-change current startup element ........................................................ 10
1.3 Differential current startup element ................................................................ 10
2 Input and output signals ................................................................................................. 11
3 Settings ......................................................................................................................... 13
4 Report............................................................................................................................ 17
Chapter 3 Differential protection ...................................................................................... 19
1 Introduction.................................................................................................................... 20
2 Applications ................................................................................................................... 20
3 Protection algorithm ...................................................................................................... 21
3.1 Differential and restraint current calculation ................................................... 22
3.2 Automatic Ratio compensation....................................................................... 24
3.3 Automatic Vector group and zero sequence current compensation .............. 28
4 Protection principle........................................................................................................ 34
4.1 Instantaneous differential protection characteristic ........................................ 34
4.2 Treble slope percent differential protection characteristic .............................. 36
4.3 Selective inrush stabilization schemes ........................................................... 39
4.3.1 2nd harmonic stabilization ....................................................................... 40
4.3.2 Fuzzy recognition of inrush based on the waveform .............................. 40
4.4 Overexcitation stabilization ............................................................................. 42
4.5 CT Failure supervision.................................................................................... 44
4.6 CT Saturation supervision .............................................................................. 45
4.7 Differential current supervision ....................................................................... 46
5 Input and output signals ................................................................................................ 48
6 Settings ......................................................................................................................... 50
7 Report............................................................................................................................ 52
8 Technical data ............................................................................................................... 53
Chapter 4 Stub differential protection .............................................................................. 55
1 Introduction.................................................................................................................... 56
2 Application ..................................................................................................................... 56
3 Protection algorithm ...................................................................................................... 56
3.1 Differential current and restraint current calculation ...................................... 56
3.2 Automatic ratio compensation ........................................................................ 58
4 Protection principle........................................................................................................ 59
4.1 Characteristic of differential instant tripping protection .................................. 59
4.2 Three-slope differential protection characteristic ........................................... 60
4.3 CT –secondary current supervision................................................................ 62
4.4 CT saturation detection................................................................................... 63
4.5 Differential supervision ................................................................................... 65
5 Input and output signals ................................................................................................ 66
6 Setting value.................................................................................................................. 68
7 Report ............................................................................................................................ 70
8 Technical data ............................................................................................................... 70
Chapter 5 Restricted earth fault protection ..................................................................... 73
1 Introduction .................................................................................................................... 74
2 Applications ................................................................................................................... 74
3 Protection principle........................................................................................................ 76
3.1 Differential and restraint current calculation ................................................... 77
3.2 Automatic Ratio compensation ....................................................................... 79
3.3 Positive sequence current blocking ................................................................ 81
3.4 Restricted earth fault current alarm ................................................................ 82
4 Input and output signals ................................................................................................ 83
5 Settings.......................................................................................................................... 84
6 Report ............................................................................................................................ 86
7 Technical data ............................................................................................................... 87
Chapter 6 Overexcitation protection ................................................................................ 89
1 Introduction .................................................................................................................... 90
2 Protection principle........................................................................................................ 90
2.1 Protection principle ......................................................................................... 90
2.2 Voltage channel configuration ........................................................................ 96
3 Input and output signals ................................................................................................ 97
4 Settings.......................................................................................................................... 97
5 Report ............................................................................................................................ 99
6 Technical data ............................................................................................................. 100
Chapter 7 Overcurrent protection .................................................................................. 101
1 Introduction .................................................................................................................. 102
2 Protection principle...................................................................................................... 102
2.1 Protection Elements...................................................................................... 102
2.2 Inrush Restraint Feature ............................................................................... 104
2.3 Direction Determination Feature .................................................................. 105
2.4 CBF initiation Feature ................................................................................... 108
3 Input and output signals .............................................................................................. 109
4 Setting ..........................................................................................................................110
5 Report ...........................................................................................................................117
6 Technical data ..............................................................................................................117
Chapter 8 Earth fault protection .....................................................................................119
1 Protection principle...................................................................................................... 120
1.1 Protection elements ...................................................................................... 120
1.2 Inrush Restraint Feature ............................................................................... 122
1.3 Direction Determination Feature .................................................................. 123
1.4 CBF initiation Feature ................................................................................... 125
2 Input and output signals .............................................................................................. 126
3 Setting ......................................................................................................................... 127
4 Report.......................................................................................................................... 133
5 Technical data ............................................................................................................. 134
Chapter 9 Neutral earth fault protection ........................................................................ 137
1 Protection principle...................................................................................................... 138
1.1 Protection Elements ..................................................................................... 138
1.2 Inrush Restraint Feature ............................................................................... 140
1.3 Direction Determination Feature .................................................................. 140
1.4 CBF initiation Feature ................................................................................... 142
2 Input and output signals .............................................................................................. 143
3 Setting ......................................................................................................................... 143
4 Report.......................................................................................................................... 150
5 Technical data ............................................................................................................. 151
Chapter 10 Thermal overload protection ......................................................................... 153
1 Introduction.................................................................................................................. 154
2 Protection principle...................................................................................................... 154
3 Input and output signals .............................................................................................. 156
4 Setting ......................................................................................................................... 156
5 Report.......................................................................................................................... 158
6 Technical data ............................................................................................................. 159
Chapter 11 Overload protection ...................................................................................... 161
1 Protection principle...................................................................................................... 162
2 Input and output signals .............................................................................................. 163
3 Setting ......................................................................................................................... 164
4 Report.......................................................................................................................... 166
Chapter 12 Overvoltage protection ................................................................................. 167
1 Introduction.................................................................................................................. 168
2 Protection principle...................................................................................................... 168
2.1 Phase to earth overvoltage protection.......................................................... 168
2.2 Phase to phase overvlotage protection ........................................................ 169
3 Logic diagram .............................................................................................................. 169
4 Input and output signals .............................................................................................. 169
5 Setting ......................................................................................................................... 170
6 Report.......................................................................................................................... 172
7 Technical data ............................................................................................................. 173
Chapter 13 Undervoltage protection ............................................................................... 175
1 Introduction.................................................................................................................. 176
2 Protection principle...................................................................................................... 176
2.1 Phase to phase underovltage protection ...................................................... 176
2.2 Phase to earth undervoltage protection ....................................................... 177
3 Logic diagram .............................................................................................................. 178
4 Input and output signals .............................................................................................. 179
5 Setting parameters ...................................................................................................... 179
6 Reports ........................................................................................................................ 180
7 Technical data ............................................................................................................. 181
Chapter 14 Zero-sequence voltage protection ................................................................ 183
1 Overview...................................................................................................................... 184
2 Protection principle...................................................................................................... 184
3 Logic diagram .............................................................................................................. 185
4 Input and output signals .............................................................................................. 185
5 Setting value................................................................................................................ 185
6 Report .......................................................................................................................... 186
7 Technical data ............................................................................................................. 187
Chapter 15 Circuit breaker failure protection .................................................................. 189
1 Introduction .................................................................................................................. 190
2 Protection principle...................................................................................................... 190
3 Logic diagram .............................................................................................................. 193
4 Input and output signals .............................................................................................. 195
5 Setting ......................................................................................................................... 196
6 Report .......................................................................................................................... 199
7 Technical data ............................................................................................................. 200
Chapter 16 Dead zone protection ................................................................................... 201
1 Introduction .................................................................................................................. 202
2 Protection principle...................................................................................................... 202
Function description .................................................................................................... 203
3 Logic diagram .............................................................................................................. 203
4 Input and output signals .............................................................................................. 203
5 Setting ......................................................................................................................... 204
6 Report .......................................................................................................................... 206
7 Technical data ............................................................................................................. 206
Chapter 17 Stub protection .............................................................................................. 207
1 Introduction .................................................................................................................. 208
2 Protection principle...................................................................................................... 208
2.1 Function description...................................................................................... 208
3 Logic diagram .............................................................................................................. 209
4 Input and output signals .............................................................................................. 209
5 Setting ......................................................................................................................... 210
6 Report .......................................................................................................................... 212
7 Technical data ............................................................................................................. 213
Chapter 18 Poles discordance protection ....................................................................... 215
1 Introdcution .................................................................................................................. 216
2 Protection principle...................................................................................................... 216
2.1 Function description...................................................................................... 216
3 Logic diagram .............................................................................................................. 217
4 Input and output signals .............................................................................................. 218
5 Setting ......................................................................................................................... 219
6 Report .......................................................................................................................... 220
7 Technical data ............................................................................................................. 220
Chapter 19 Distance protection ....................................................................................... 221
1 Introduction.................................................................................................................. 222
2 Protection principle...................................................................................................... 222
2.1 Frunction description .................................................................................... 222
2.2 Auxiliary startup element .............................................................................. 223
3 Logic diagram .............................................................................................................. 224
4 Input and output signals .............................................................................................. 224
5 Setting ......................................................................................................................... 225
6 Report.......................................................................................................................... 227
7 Technical data ............................................................................................................. 227
Chapter 20 Secondary system supervision..................................................................... 229
1 VT failure supervision function .................................................................................... 230
2 Function principle ........................................................................................................ 230
3 Input and output signals .............................................................................................. 233
4 Setting ......................................................................................................................... 234
5 Report.......................................................................................................................... 235
6 Technical data ............................................................................................................. 236
Chapter 21 External BIs to trip BOs ................................................................................ 237
1 Introduction.................................................................................................................. 238
2 Function principle ........................................................................................................ 238
3 BI Trigger Record ........................................................................................................ 239
4 BI Switch SetGroup ..................................................................................................... 239
5 BI “Blk Rem Access” and “RELAY TEST” ................................................................... 240
6 BI “BI_Config1~ BI_Config2” and “BI TRIGGER DR1~ 10” ....................................... 240
7 Setting ......................................................................................................................... 241
Chapter 22 Interturn protection ....................................................................................... 243
1 Overview ..................................................................................................................... 244
2 Protection principle...................................................................................................... 244
3 Logic diagram .............................................................................................................. 245
4 Input and output signals .............................................................................................. 246
5 Setting value................................................................................................................ 247
6 Report.......................................................................................................................... 247
7 Technical data ............................................................................................................. 247
Chapter 23 Station communication ................................................................................. 249
1 Overview ..................................................................................................................... 250
1.1 Protocol ......................................................................................................... 250
1.1.1 LON communication protocol ................................................................ 250
1.1.2 IEC61850-8 communication protocol .................................................... 250
1.1.3 IEC60870-5-103 communication protocol............................................. 251
1.2 Communication port ..................................................................................... 251
1.2.1 Front communication port ..................................................................... 251
1.2.2 RS485 communication ports ................................................................. 251
1.2.3 Ethernet communication ports .............................................................. 251
1.3 Technical data ............................................................................................... 251
1.3.1 Table Front communication port ............................................................ 252
1.3.2 RS485 communication port ................................................................... 252
1.3.3 Ethernet communication port ................................................................ 252
1.3.4 Time synchronization............................................................................. 253
2 Typical communication scheme .................................................................................. 253
2.1 Typical substation communication scheme .................................................. 253
2.2 Typical time synchronizing scheme .............................................................. 254
Chapter 24 Hardware ...................................................................................................... 255
1 Introduction .................................................................................................................. 256
1.1 IED structure ................................................................................................. 256
1.2 IED appearance ............................................................................................ 256
1.3 IED module arrangement ............................................................................. 257
1.4 The rear view of the protection IED .............................................................. 257
2 Local human-machine interface .................................................................................. 258
2.1 Human machine interface............................................................................. 258
2.2 LCD ............................................................................................................... 259
2.3 Keypad .......................................................................................................... 259
2.4 Shortcut keys and functional keys ................................................................ 260
2.5 LED ............................................................................................................... 260
2.6 Front communication port ............................................................................. 261
3 Analog input module ................................................................................................... 262
3.1 Introduction ................................................................................................... 262
3.2 Terminals of Analogue Input Module (AIM) .................................................. 262
3.3 Technical data ............................................................................................... 263
3.3.1 Internal current transformer ................................................................... 263
3.3.2 Internal voltage transformer .................................................................. 264
4 Communication module .............................................................................................. 264
4.1 Introduction ................................................................................................... 264
4.2 Substaion communication port ..................................................................... 264
4.2.1 RS232 communication ports ................................................................. 265
4.2.2 RS485 communication ports ................................................................. 265
4.2.3 Ethernet communication ports............................................................... 265
4.2.4 Time synchronization port ..................................................................... 265
4.3 Terminals of Communication Module ........................................................... 265
4.4 Operating reports .......................................................................................... 267
4.5 Technical data ............................................................................................... 267
4.5.1 Front communication port...................................................................... 267
4.5.2 RS485 communication port ................................................................... 267
4.5.3 Ethernet communication port ................................................................ 268
4.5.4 Time synchronization............................................................................. 268
5 Binary input module .................................................................................................... 269
5.1 Introduction ................................................................................................... 269
5.2 Terminals of Binary Input Module (BIM) ....................................................... 269
5.3 Technical data ............................................................................................... 271
6 Binary output module .................................................................................................. 272
6.1 Introduction ................................................................................................... 272
6.2 Terminals of Binary Output Module (BOM) .................................................. 272
6.2.1 Binary Output Module A ........................................................................ 272
6.2.2 Binary Output Module C ........................................................................ 275
6.3 Technical data ............................................................................................... 276
7 Power supply module .................................................................................................. 278
7.1 Introduction ................................................................................................... 278
7.2 Terminals of Power Supply Module (PSM)................................................... 278
7.3 Technical data ............................................................................................... 280
8 Terminal block ............................................................................................................. 280
9 Techinical data............................................................................................................. 281
9.1 Basic data ..................................................................................................... 281
9.1.1 Frequency.............................................................................................. 281
9.1.2 Internal current transformer................................................................... 281
9.1.3 Internal voltage transformer .................................................................. 282
9.1.4 Auxiliary voltage .................................................................................... 282
9.1.5 Binary inputs .......................................................................................... 282
9.1.6 Binary outputs........................................................................................ 283
9.2 Type tests ..................................................................................................... 283
9.2.1 Product safety-related Tests .................................................................. 284
9.2.2 Electromagnetic immunity tests ............................................................ 285
9.2.3 DC voltage interruption test ................................................................... 286
9.2.4 Electromagnetic emission test .............................................................. 287
9.2.5 Mechanical tests .................................................................................... 287
9.2.6 Climatic tests ......................................................................................... 288
9.2.7 CE Certificate ........................................................................................ 289
9.3 IED design .................................................................................................... 289
Chapter 25 Appendix ....................................................................................................... 291
1 General setting list ...................................................................................................... 292
1.1 Function setting list ....................................................................................... 292
1.2 Control word list ............................................................................................ 310
1.3 Table of setting values .................................................................................. 332
1.3.1 CSC-326 (M02) setting value ................................................................ 332
1.3.2 CSC-326 (M02) control word list ........................................................... 347
1.3.3 CSC-326 (M03) setting value list .......................................................... 367
1.3.4 CSC-326 (M03) control word list ........................................................... 382
1.3.5 CSC-326 (M11) setting value list........................................................... 399
1.3.6 CSC-326 (M11) control word list ........................................................... 400
1.3.7 CSC-326(M20) setting value list ........................................................... 401
1.3.8 CSC-326(M20) control word list ............................................................ 408
1 General report list........................................................................................................ 413
2 Time inverse characteristic ......................................................................................... 420
2.1 11 kinds of IEC and ANSI inverse time characteristic curves ...................... 420
2.2 User defined characteristic ........................................................................... 421
3 CT Requirement .......................................................................................................... 421
3.1 Overview ....................................................................................................... 421
3.2 Current transformer classification ................................................................. 422
3.3 Abbreviations (according to IEC 60044-1, -6, as defined) ........................... 423
3.4 General current transformer requirements ................................................... 424
3.4.1 Protective checking current ................................................................... 424
3.4.2 CT class ................................................................................................. 424
3.4.3 Accuracy class....................................................................................... 426
3.4.4 Ratio of CT ............................................................................................ 426
3.4.5 Rated secondary current ....................................................................... 427
3.4.6 Secondary burden ................................................................................. 427
3.5 Rated equivalent secondary e.m.f requirements.......................................... 428
Chapter 1 Introduction

Chapter 1 Introduction

About this chapter


This chapter gives an overview of SIFANG transformer pro-
tection IED.

1
Chapter 1 Introduction

1 Overview
It is selective, reliable and high speed IED (Intelligent Electronic Device)
for transformer protection with powerful capabilities to cover following
applications:

 For large and medium two- or three-winding transformers, and au-


totransformer

 Used in a wide range of voltage levels, up to 1000kV

 For single or multi-breaker arrangement

 Up to 7 three-phase sets of CTs input (special ordering)

 Work as main protection unit only or full functions unit for the
complicated application

 Communication with station automation system

The IED is able to provide all main protection functions and backup pro-
tection functions in one case, including differential protection, restricted
earth fault (REF), overexcitation, thermal overload, overcurrent, earth
fault protection, etc.

The integrated flexible logic make the IED suitable to be applied to (au-
to)transformers with all the possible vector groups, with/without earthing
connection inside the protected zone.

The wide application flexibility makes the IED an excellent choice for both
new installations and retrofitting of the existing stations.

2
Chapter 1 Introduction

2 Features
 Protection and monitoring IED with extensive functional library, user
configuration possibility and expandable hardware design to meet with
user’s special requirements

 Inter-lock between two CPU modules, avoiding mal-operation due to


internal severe fault of one module

 Transformer differential protection (87T)

 Treble slope percent differential protection

 Automatic CT ratio matching

 Automatic vector group and zero sequence current compensation

 Settable 2nd harmonic restraint function for transformer inrush

 Fuzzy waveform recognition restraint function for transformer


inrush

 3rd or 5th harmonic restraint for overexcitation

 CT saturation detection

 CT secondarycircuit supervison

 Differential current alarm

 Restricted earth fault protection (87N)

 Two slope percent REF protection

 Automatic CT ratio matching

 CT saturation recognition

 REF differential current supervision

 Positive sequence current blocking

 A complete protection functions library, include:

3
Chapter 1 Introduction

 Transformer differential protection (87T)

 Restricted earth fault protection (87N)

 Overcurrent protection (50, 51, 67)

 Earth fault protection (50N, 51N, 67N)

 Neutral earth fault protection (50G, 51G, 67G)

 Thermal overload protection (49)

 Overload protection (50OL)

 Delta winding overload protection (50OL)

 Overexcitation protection (24)

 Overvoltage protection (59)

 Circuit breaker failure protection (50BF)

 Poles discordance protection (50PD)

 Dead zone protection (50SH-Z)

 Voltage transformer secondary circuit supervision (97FF)

 Current transformer secondary circuit supervision

 2 sets external trip commands (BIs → BOs)

 Self-supervision to all modules in the IED

 Complete information recording: tripping reports, alarm reports,


startup reports and general operation reports. Any kinds of reports can
be stored up to 2000 and be memorized in case of power
disconnection

 Up to three electric /optical Ethernet ports can be selected to


communicate with substation automation system by IEC61850 or
IEC60870-5-103 protocols

 Up to two electric RS-485 ports can be selected to communicate with

4
Chapter 1 Introduction

substation automation system by IEC60870-5-103 protocol

 Time synchronization via network(SNTP), pulse and IRIG-B mode

 Configurable LEDs and output relays satisfied users’ requirement

 Versatile human-machine interface

 Multifunctional software tool CSmart/CSPC for setting, monitoring,


fault recording analysis, configuration, etc.

5
Chapter 1 Introduction

Table 1 Protection functions

IEC 61850
IEC 60617
Description ANSI Code Logical Node
graphical symbol
Name

Differential protection

Transformer differential protection 87T PDIF

Restricted earth fault protection 87N PDIF

Current protection

3IINV>
Overcurrent protection 50,51,67 PTOC 3I >>
3I >>>
I0INV>
Earth fault protection 50N, 51N, 67N PEFM I0>>
I0>>>

Neutral earth fault protection 50G, 51G, 67G

Thermal overload protection 49 PTTR Ith

Overload protection 50OL PTOC 3I >OL

Delta Winding Overload Protection 50OL

Voltage protection

Overexcitation protection 24 PVPH U/f>

3U>
Overvoltage protection 59 PTOV
3U>>

Breaker protection and control function

3I> BF
Breaker failure protection 50BF RBRF I0>BF
I2>BF

Dead zone protection 50SH-Z

3I< PD
Poles discordance protection 50PD RPLD1 I0>PD
I2>PD

Secondary system supervision

CT secondary circuit supervision

VT secondary circuit supervision

Other functions

2 sets external trip commands (BIs →


BOs)

6
Chapter 1 Introduction

Table 2 Monitoring functions

Description

Auxiliary contacts of circuit breaker supervision

Self-supervision

Fault recorder

Table 3 Station communication

Description

Front communication port

Isolated RS232 port

Rear communication port

0-2 isolated electrical RS485 communication ports

0-3 Ethernet electrical/optical communication ports

Time synchronization port

Communication protocols

IEC 61850 protocol

IEC 60870-5-103 protocol

Digital communication network through converter

Table 4 IED software tools

Functions

Reading measuring value

Reading IED report

Setting

IED testing

Disturbance recording analysis

IED configuration

Printing

7
Chapter 1 Introduction

8
Chapter 2 Basic protection elements

Chapter 2 Basic protection elements

About this chapter

This chapter describes basic protection elements including


startup elements, phase selectors and directional elements.

9
Chapter 2 Basic protection elements

1 Startup element

1.1 Introduction
Startup elements are designed to detect a faulty condition in the power
system and initiate all necessary procedures for selective clearance of
the fault. The main startup element of CSC-326 is current
sudden-change startup element(abrupt current), the backup startup
element is diffrential current startup elment.

Startup element includes:

 Current sudden-change startup element(abrupt current)

 differential current startup element

1.2 Sudden-change current startup element

Sudden-change current startup element is the main startup element that


can sensitively detect most of faults. Its criteria are as followings:

i  I _ startup


i  i (t )  2  i (t  T )  i (t  2T )

Equation 1

where

 I_startup is a fix threshold value(IQd =0.2A when the secondary


value of CT is 1A, and IQd =1A when secondary value of CT is 5A)

1.3 Differential current startup element

10
Chapter 2 Basic protection elements

 I d max  I _ diff startup




 I d max  Max I d ,  a, b, c

 I _ diff startup  0.8I _ percent diff

Equation 2

where

 I_diff startup is the startup threshold of differential protection,


I_Percent Diff is a setting value, and Idφis the phase differential current.

2 Input and output signals

Sudden-change current
startup element
IA1 Relay Startup

IB1

IC1

IA2

IB2

IC2

IA3

IB3

IC3

IA4

IB4

IC4

IA5

IB5

IC5

Figure 1 Sudden-change current startup element

11
Chapter 2 Basic protection elements

Differential current
startup element
IA1 Relay Startup

IB1

IC1

IA2

IB2

IC2

IA3

IB3

IC3

IA4

IB4

IC4

IA5

IB5

IC5

Figure 2 Differential current startup element

Table 5 Analog input list

Signal Description

IA1 Phase A current input of 1st CT set


IB1 Phase B current input of 1st CT set
IC1 Phase C current input of 1st CT set
IA2 Phase A current input of 2nd CT set
IB2 Phase B current input of 2nd CT set
IC2 Phase C current input of 2nd CT set
IA3 Phase A current input of 3th CT set
IB3 Phase B current input of 3th CT set
IC3 Phase C current input of 3th CT set
IA4 Phase A current input of 4th CT set
IB4 Phase B current input of 4th CT set
IC4 Phase C current input of 4th CT set
IA5 Phase A current input of 5th CT set
IB5 Phase B current input of 5th CT set

12
Chapter 2 Basic protection elements

Signal Description

IC5 Phase C current input of 5th CT set

Table 6 Binary output list

Signal Description

Relay Startup Relay Startup

3 Settings
Table 7 Settings of basic protection element

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
0 1 0 Connection for HV winding,
HV Wind Conn/Y-0
0:wye connection, 1:delta
D-1
connection
MV Wind Conn/Y-0 0 1 0 Connection for MV winding,
0:wye connection, 1:delta
D-1
connection
(Only for

three-winding

transformers)
0 1 1 Connection for LV winding,
LV Wind Conn/Y-0
0:wye connection, 1:delta
D-1
connection
Vet Grp Angle 0 12 11 Vector Group Angle( VET
GRP ANGLE)
SN MVA 1.000 3000. 120 Capacity of the transformer
HV VT Ratio 1.000 9999. 2200 Voltage transformer(VT) Ra-
tio in HV side
A 50.00 9999. 1200.0 CT Primary(PRI) current in
HV CT Pri
HV side
A 1.000 5.000 1.0 CT Secondary(SEC) current
HV CT Sec
in HV side

13
Chapter 2 Basic protection elements

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
HV Voltage Chan 1 3 1
HV voltage channel location
Sel
MV Voltage Chan 1 3 2 MV voltage channel loca-
Sel tion
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
HV NCT Pri(REF) ry(PRI) current in HV side
for REF
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
HV NCT Sec(REF) ary(SEC) current in HV side
for REF
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
HV NCT Pri(BU) ry(PRI) current in HV side
for backup protection
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
HV NCT Sec(BU) ary(PRI) current in HV side
for backup protection
kV 1.000 1000. 110.0 Nominal voltage (UN) in
MV UN
Middle voltage (MV)side
1.000 9999. 1100.0 Voltage transformer(VT) Ra-
MV VT Ratio
tio in MV side
A 50.00 9999. 1200.0 CT Primary(PRI) current in
MV CT Pri
MV side
A 1.000 5.000 1.0 CT Secondary(SEC) current
MV CT Sec
in MV side
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
MV NCT Pri(REF) ry(PRI) current in MV side
for REF
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
MV NCT Sec(REF) ary(SEC) current in MV
side for REF
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
MV NCT Pri(BU) ry(PRI) current in MV side
for backup protection
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
MV NCT Sec(BU) ary(PRI) current in MV side
for backup protection

14
Chapter 2 Basic protection elements

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
kV 1.000 1000. 10.50 Nominal voltage (UN) in Low
LV UN
voltage (LV)side
1.000 9999. 105.0 Voltage transformer(VT) Ra-
LV VT Ratio
tio in LV side
A 50.00 9999. 3000.0 CT Primary(PRI) current in
LV CT Pri
LV side
A 1.000 5.000 1.0 CT Secondary(SEC) current
LV CT Sec
in LV side
LV Sec Inside A 1.000 5.000 1.0 CT Secondary(SEC) cur-
Delta rent in LV inside delta
A 0 9999 Rated primary current for
HV Rated Cur Pri HV side (calculated value,
read only)
A 0 9999 Rated secondary current for
HV Rated Cur Sec HV side (calculated value,
read only)
0 9999 HV ratio factor for differen-
Ratio Factor KTAH tial protection (calculated
value, read only)
0 9999 MV ratio factor for differen-
Ratio Factor KTAM tial protection (calculated
value, read only)
0 9999 LV ratio factor for differential
Ratio Factor KTAL protection (calculated
value, read only)
0 9999 HV ratio factor, with ze-
ro-sequence current calcu-
Ratio REF KTAH lated, for REF protection
(calculated value, read
only)
0 9999 HV ratio factor with ze-
ro-sequence current directly
Ratio REF KNH measured, for REF protec-
tion (calculated value,
read only)
Ratio REF KTAM 0 9999 MV ratio factor, with ze-

15
Chapter 2 Basic protection elements

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
ro-sequence current calcu-
lated, for REF protection
(calculated value, read
only)
0 9999 MV ratio factor with ze-
ro-sequence current directly
Ratio REF KNM measured, for REF protec-
tion (calculated value,
read only)

Table 8 Control words of basic protection

Default
Setting Unit Min. Max. Description
setting
Autotransformer not comm
on transformer
Auto Trans 0 1 0
1-autotransformer ;
0- not autotransformer
Two-Wind Trans Two-winding(TWO WIND )
not three -winding trans-
0 1 0 former (TRANS)
1-two-winding trans;
0-three-winding trans
CT Fail Detect VT Failure Detection On/Off
0 1 0
1-On, 0-Off.

Table 9 Setting value of basic protection element

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
A 50.00 9999. 1200.0 Primary value of CT
I/II Side CT Pri
at I/II side
A 1.000 5.000 1.0 Secondary value of
I/II Side CT Sec
CT at I/II side
A 50.00 9999. 1200.0 Primary value of CT
III/IV Side CT Pri
at III/IV side
A 1.000 5.000 1.0 Secondary value of
III/IV Side CT Sec
CT at III/IV side

16
Chapter 2 Basic protection elements

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
A 50.00 9999. 3000.0 Primary value of CT
V Side CT Pri
at V side
A 1.000 5.000 1.0 Secondary value of
V Side CT Sec
CT at V side
0 9999 Ratio factor of dif-
ferential protection
Ratio Factor I/II
at I/II side (calculat-
ed value, read only)
0 9999 Ratio factor of differ-
ential protection at
Ratio Factor III/IV
III/IV side (calculated
value, read only)
0 9999 Ratio factor of differ-
ential protection at V
Ratio Factor V
side (calculated val-
ue, read only)

Table 10 Basic protection control word

Setting Unit Min. Max. Default Description


CT Fail Detect CT failure detection
0 1 0
1- enable, 0-disable

4 Report
Table 11 Event report list

Information Description

Relay startup The relay is initiated by startup elements

17
Chapter 2 Basic protection elements

18
Chapter 3 Differential protection

Chapter 3 Differential protection

About this chapter


This chapter describes the protection principle, input and
output signals, parameter, IED report and technical data for
differential protection function.

19
Chapter 3 Differential protection

1 Introduction
The numerical current differential protection represents the main protec-
tion function of the IED. It provides a fast short-circuit protection for
power transformers. The protected zone is selectively limited by the CTs
at its ends. The device is able to perform this function on 2 or 3 winding
transformers in a variety of voltage levels and protected object types.

2 Applications
The IED provides numerical differential protection function which can be
used to protect power transformers in various configurations. For exam-
ple, it is possible to use it for a two-winding transformer, three-winding
transformer as well as auto-transformer. Examples for some of applica-
tions are illustrated in the below figure.

HV LV
I A.1 Ia.2
A a
I B.1 Ib .2
B b
I C .1 Ic .2
C c

CSC-326

Figure 3 Application of differential protection on a two-winding Yd


transformer

I A.1
A Ia.2
a
IB.1
Ib .2
B
b
IC .1
C Ic .2
c

CSC-326

20
Chapter 3 Differential protection

Figure 4 Application of differential protection on an auto


transformer

HV LV
I A.1 Ia.2
A a
IB.1 Ib .2
B b
IC .1 Ic .2
C c

CSC-326

Figure 5 Application of differential protection on a two-winding Yd


transformer with earthing transformer inside the protected zone
MV
Ia.2
a
Ib .2
b
HV Ic .2
I A.1 c
A
I B.1
B
I C .1 LV
C Ia.3
a
Ib .3
b
Ic .3
c

CSC-326

Figure 6 Application of differential protection on a three-winding


Ydd transformer

3 Protection algorithm
This section describes basic principle of differential protection function.

21
Chapter 3 Differential protection

First, the case of a single phase transformer with two windings is con-
sidered. The basic principle is based on current comparison at two sides
of the protected object. Indeed, the differential protection function makes
use of the fact that a protected object carries always the same current at
its two sides in healthy operation condition. This current flows into one
side of the protected object and leaves it from the other side. A difference
in currents is an indication of a fault within this section. An example of this
condition is shown in below figure, when a fault inside the protected zone
causes a current I1prim. + I2prim. flowing in from both sides of the protected
object.

Protected Zone

I1-prim. I2-prim.

CT-1 CT-2
Protected
Transformer

I1 I2

CSC-326

Figure 7 Basic principle of differential protection for two ends


(single phase)

For protected objects with three or more sides, the basic principle is ex-
panded in that the total of all currents flowing into the protected object is
zero in healthy operation, whereas in case of a fault the total in-flowing
current is equal to the fault current.

When an external fault causes a heavy current to flow through the pro-
tected transformer, differences in the magnetic characteristics of the
current transformers CT-1 and CT-2 under saturation condition may
cause a significant difference in the secondary currents I1 + I2 connected
to IED. If the difference is greater than the pickup threshold, the differen-
tial protection function can trip even though no fault occurred in the pro-
tected zone. To prevent the protection function from such erroneous op-
eration, a restraint (stabilizing) current is brought in. For differential pro-
tection IED, the restraint current is normally derived from the I1 and I2.
The next subsection goes on to demonstrate how the differential and re-
straint currents are calculated.

3.1 Differential and restraint current calculation


22
Chapter 3 Differential protection

The differential current Idiff and the restraining current Ires are calculated
by the following equation. The following definitions apply for each phase
of the protected object.

 N 
 I diff 

 i 1
Ii
 N 1 
 1 


I res 
2
I j (max) i 1
I i (i  j )

Equation 3

Where I i is the current vector of side i, corresponding to HV, MV and LV

windings; N is total current inputs of the IED. In other words, it is number


of the protected object sides; I j (max) is the maximum current vector

N 1 
among the N current inputs of the IED, suppose it is side j;  I i (i j ) is
i 1
the sum of the other current inputs of the IED, not including side j. Idiff is
derived from the fundamental frequency current and produces the trip-
ping effect quantity, whereas Ires counteracts this effect. To clarify the
situation, three important operating conditions with ideal and matched
measurement qualities are examined.

(a) External fault under undisturbed conditions:

I1 flows into the protected zone, I2 leaves the protected zone, i.e. is
negative according to the definition of signs, therefore I2 = –I1.

Idiff = I1 + I2 = I1 – I1 = 0

Ires = 0.5×| I1 - (–I1) | = 0.5×|2I1| = |I1|

No tripping effect (Idiff = 0); the restraint (Ires) corresponds to the exter-
nal fault current flowing through the protected object.

(b) Internal fault, fed with equal currents from both sides:

The following applies I2 = I1

Idiff = I1 + I2 = I1 + I1 = 2 I1

Ires = 0.5×| I1 - I1| = 0

23
Chapter 3 Differential protection

Tripping effect (Idiff) corresponds to double the fault current, and restraint
value (Ires) are equal to zero.

(c) Internal fault, fed from one side only:

The following applies when assuming I2 = 0

Idiff = I1 + I2 = I1 + 0 = I1

Ires = 0.5×|I1 - I2| =0.5× |I1 - 0| = 0.5×|I1|=0.5 I1

Tripping quantity (Idiff) and restraint quantity (Ires) are equal and corre-
spond to the single-sided fault current.

The results show that the device is capable to properly discriminate in-
ternal and external faults by using the definitions proposed for differential
and restraint current. However, the device is still subjected to some in-
fluences that induce differential currents even during normal operation
condition. These influences should be compensated in appropriate
manners. The specific treatments designed to cope with these influences
includes automatic ratio compensation and automatic vector group
compensation which are explored in the next subsections.

3.2 Automatic Ratio compensation

Differential protection of power transformers represents some problems


in the application of current transformers. CTs should be matched to the
current rating of each transformer winding, so that normal current through
the power transformer is equal on the secondary side of the CT on dif-
ferent windings. However, because only standard CT ratios are available,
this matching may not be exact. As a result, the secondary currents of the
current transformers are not generally equal when a current flows
through the power transformer. The difference between the currents
flowing through CTs’ secondary circuit depends on the transformation ra-
tio of the protected power transformer, as well as the rated currents of the
current transformers. Therefore, the currents should be matched in order
to become comparable. To do so, the input currents of the IED are con-
verted in relation to the power transformer rated currents. This is
achieved by entering the characteristic values of the power transformer
(i.e. rated apparent power and rated voltages) and primary rated currents
of CTs into the IED by using user-entered settings. As a result, matching
to various power transformer and current transformer ratios is performed
purely mathematically inside the device. Therefore, no external matching

24
Chapter 3 Differential protection

transformer is required. In this context, the rated primary current of each


side, I1N, is calculated automatically according to below equation.

SN
I 1N 
3U 1N

Equation 4

Where SN is rated apparent power of the transformer and U1N is rated


voltage of the corresponding side.

The rated secondary current of each side, I2N, is then calculated.

I 1N
I 2N 
nCT

Equation 5

Rated secondary current of the high voltage side is then taken as the
reference current. The currents of the other sides are automatically
matched to the rated current of the high voltage side by calculation of
correction factor KCT for MV and LV side, according to below equations,
respectively:

I 2 N  HV I /n S / 3U 1N  HV nCT  MV U 1N  MV nCT  MV
K CT  MV   1N  HV CT  HV  N   
I 2 N  MV I1N  MV / nCT  MV S N / 3U 1N  MV nCT  HV U 1N  HV nCT  HV

Equation 6

I 2 N  HV I1N  HV / nCT  HV S N / 3U 1N  HV nCT  LV U 1N  LV nCT  LV


K CT  LV      
I 2 N  LV I1N  LV / nCT  LV S N / 3U 1N  LV nCT  HV U 1N  HV nCT  HV

Equation 7

Where KCT-MV is the correction factor for middle voltage side and
KCT-LV is the correction factor for Low voltage side,

25
Chapter 3 Differential protection

I1N is the primary rated current of the transformer (I1N-HV for high volt-
age side, I1N-MV for middle voltage side and I1N-LV for low voltage
side),

I2N is the secondary rated current of the transformer (I2N-HV for high
voltage side, I2N-MV for middle voltage side, I2N-LV for low voltage
side),

nCT is CT ratio of the transformer (nCT-HV for high voltage side, nCT-MV
for middle voltage side, nCT-LV for low voltage side),

U1N is rated voltage of the transformer (U1N-HV for high voltage side,
U1N-MV for middle voltage side, U1N-LV for low voltage side).

As mentioned previously, all of the calculations are automatically per-


formed inside the IED by its CPU. The related settings can be found
under the menu “Test Menu”.

Below figure shows an example of automatic ratio compensation in case


of a two-winding transformer. The primary nominal currents of the HV and
LV sides, (I1N = 402A, I2N= 1466A) are calculated from the rated ap-
parent power of the transformer (160MVA) and the nominal voltages of
each side (230kV and 63kV). Since the nominal currents of the current
transformers deviate from the nominal currents of the power transformer
sides, the secondary current of LV side is multiplied with the factor
KCT-LV. Subsequent to this matching, equal current magnitudes are
achieved at both sides under nominal conditions of the power transform-
er.

SN=160MVA
U1N-HV=230kV U1N-LV=63kV

CTRATIO=500/1A CTRATIO=2000/1A

Figure 8 Example of automatic ratio compensation in a two-winding


transformer

160MVA
I1N  HV   402 A
3  230
I 1N  HV 402
I 2 N  HV    0.804 A
nCT 500

26
Chapter 3 Differential protection

160MVA
I 1N  LV   1466 A
3  63
1466
I 2 N  LV   0.733 A
2000
0.804
K CT LV   1.097
0.733

Concerning three-winding power transformers, the windings may have


different power ratings. In order to compare secondary currents in an
appropriate manner, all currents are matched to the rated secondary
current of HV winding having highest power rating. This apparent power
is nominated as the rated apparent power of the transformer.

Below figure shows an example of a three-winding power transformer.


HV winding and MV winding are rated for 160MVA. The rated primary
and secondary currents of these windings are calculated as shown in
previous example. However, the LV winding has 25MVA rating (e.g. for
auxiliary supply). The rated current of this winding may result in 721A.
However, differential protection has to process comparable currents.
Therefore, the currents of LV winding should be referred to the rated
apparent power of the transformer, i.e. 160MVA. This results in a rated
current of 4619A. This is the base value for the LV winding, which should
be further multiplied by KCT-LV to be used in calculation process of dif-
ferential protection.

160MVA 160MVA
U1N-HV=230kV U1N-MV=63kV

CTRATIO=500/1A CTRATIO=2000/1A

U1N-LV=20kV 25MVA

CTRATIO=2500/1A

Figure 9 Example of automatic ratio compensation in a


three-winding transformer

160MVA
I 1N  LV   4619 A
3  20
I 1N  LV 4619
I 2 N  HV    1.848 A
nCT 2500
0.804
K CT LV   0.435
1.848

27
Chapter 3 Differential protection

If a three-winding transformer with a delta LV winding (with no CB in-


stalled) is used to supply substation LVAC loads, it may be desired that
LV current should not be integrated in differential protection. In this case,
Control word “Diff Includes LV Cur” is used to select whether LV current
should be included in differential protection calculation procedure or not.
By applying setting “Diff Includes LV Cur” to 0, only HV and MV currents
would be included in differential protection calculation. On the contrary,
when a three-winding transformer is equipped with three CBs in its sides,
it may be desired to include LV current in differential protection. This can
be achieved by applying setting “Diff Includes LV Cur” to 1 to respective
Control word.

3.3 Automatic Vector group and zero sequence


current compensation

Transformers have different vector groups, which cause a shift of the


phase angles between the primary and the secondary side. Without ad-
equate correction, this phase shift would cause a false differential current.
Furthermore, the conditioning of the starpoint(s) of the power transformer
has a great impact on the resulting differential current during through fault
currents.

The IED removes this problem. To do so, all CTs at the power trans-
former are connected Wye (polarity markings pointing away from the
transformer). User-entered settings in the relay are then used to char-
acterize the power transformer and allow the relay to automatically per-
form all necessary phase angles, and zero sequence compensation. This
section describes the procedures that perform this compensation inside
the relay and produce the required calculated quantities for transformer
differential protection. The phase angle compensation as well as zero
sequence current elimination procedure is performed by programmed
coefficient matrices which are capable to simulate the difference in phase
angle of currents flowing through transformer windings. Thus, compen-
sation is possible for the entire commonly used transformer vector
groups. This simplifies application of the IED in various configurations, if
the setting corresponding to vector Group Angle, “Vet Grp Angle”, is
properly entered into the device, together with the settings for connection
type of transformer windings in each side, “HV WIND CONN/Y-0 D-1”,
“MV WIND CONN/Y-0 D-1”, “LV WIND CONN/Y-0 D-1”, which could be
set to 1-delta or 0-wye. The basic principle of numerical vector group and
zero-sequence compensation is shown through some examples. A
through review of all possible connection groups as well as device

28
Chapter 3 Differential protection

treatment in each case is explored in Appendix.

(1). Take example for Yy0 connection, including similar ones of Yy0
(separate or auto-connected windings), YNy0, Yyn0, YNyn0 (separate or
auto-connected windings) and so on. Below figure shows an example in
case of Yy0 connection group with no earthed starpoint. The figure
shows the windings (left) and the vector diagrams of symmetrical cur-
rents (right).

A B C

Yy0 c b

C B

a b c

Figure 10 Vector Group and zero sequence compensation for Yy0


transformer

The equations including the coefficient matrix are as follow:

 I A  1 -1 0  IA 
  1   
 I B    0 1 -1   I B 
I   3
-1 0 1   I C 
 C  

Equation 8

 I a  1 -1 0   Ia 
  1   
 I b    0 1 -1   I b 
I   3
-1 0 1   I c 
 c  

Equation 9

 
According to these matrices, if we deduct side 1 currents I A  I B , the re-

29
Chapter 3 Differential protection

 
sulting current I A has the same direction as I A on side 2. Multiplying it

with 1 3 , matches the absolute value. The matrices describe the con-
version for all three phases. Using these matrices, the elimination of zero
sequence currents are warranted regardless of starpoint earth connec-
tion.

As mentioned previously, the two above equations can be used similarly


for auto-transformers, as the auto-connected windings in au-
to-transformers can only be connected Y(N)y(n)0. If the starpoint is
earthed, both the auto-connected HV and LV windings are affected. The
zero sequence components in current flowing through both sides of the
transformer are then coupled because of the common starpoint. These
zero sequence components are eliminated by the application of the ma-
trices presented in the above equations.

(2). Take example for Yd1 connection, including similar ones of Yd1 and
YNd1 without earthing transformer installed at delta side. Below figure
shows an example in case of Yd1 connection group with no earthed
starpoint.

A B C

A
a

Yd1 c

C b B

a b c

Figure 11 Vector Group compensation for Yd1 transformer

The equation including the coefficient matrix is as follows:

 I A  1 0 -1  I A 
  1   
 I B    -1 1 0    I B 
I   3
0 -1 1   I C 
 C  

30
Chapter 3 Differential protection

Equation 10

If an earthing transformer/reactor is installed inside the protected zone on


delta side, the IED should be informed about it by Control word “HV
D_side Eliminate I0”, “MV D_side Eliminate I0” or “LV D_side Eliminate
I0”. The Control word related to delta side with earthing connection
should be set to “1-eliminate” in such condition. By taking example for
Yd1 connection with earthing transformer installed at delta side, Control
word “LV D_side Eliminate I0” is set to “1-eliminate”, and thus, device
performs a zero sequence current elimination on delta side. In this case,
the equations including the coefficient matrices are as follow:

 I A  1 0 -1  I A 
  1   
 I B    -1 1 0    I B 
I   3 
0 -1 1   I C 
 C  

Equation 11

   
I
  I
a
 2  1  1  a 
  1

. I 
     
I b
3
. 1 2 1  b
   1  1 2    
 I c  I c 
   

Equation 12

(3). Take example for Ydd3 connection, including similar ones of Ydd3
and YNdd3 without earthing transformer installed at delta sides. Below
figure shows an example in case of Ydd3 connection group with no
earthed starpoint in Wye side.

31
Chapter 3 Differential protection

A B C

A
c(c’)

Ydd3 a(a’)

C b(b’) B

c a b c' a' b'

Figure 12 Vector Group compensation for Ydd3 transformer

The equation including the coefficient matrix is as follows:

 I A  0 1 -1  I A 
  1   
 I B    -1 0 1    I B 
I   3
1 -1 0   I C 
 C  

Equation 13

(4). Take example for Yd5 connection, including similar ones of Yd5 and
YNd5 with earthing transformer installed at delta side. Below figure
shows an example in case of Yd5 connection group with no earthed
starpoint.

A B C

A
c

Yd5 b

a
C B

c a b

Figure 13 Vector Group compensation for Yd5 transformer

32
Chapter 3 Differential protection

By setting control word “LV D_side Eliminate I0” to “1-eliminate”, the


equations including the coefficient matrices are as follow:

 I A  -1 1 0  I A 
  1   
 I B    0 -1 1    I B 
I   3 
1 0 -1  I C 
 C  

Equation 14

   
I
  I
a
 2  1  1  a 
  1

. I 
     
I b
3
. 1 2 1  b
   1  1 2    
 I c  I c 
   

Equation 15

(5). Take example for Dy1 connection, including similar ones of Dy1 and
Dyn1 without earthing transformer installed at delta side. Below figure
shows an example in case of Dy1 connection group with no earthed
starpoint.

A B C

Dy1 c

b
C B

a b c

Figure 14 Vector Group compensation for Dy1 transformer

The equation including the coefficient matrix is as follows:

33
Chapter 3 Differential protection

 I a  1 -1 0  I a 
  1   
 I b    0 1 -1   I b 
I   3
-1 0 1  I c 
 c  

Equation 16

If an earthing transformer/reactor is installed inside the protected zone on


delta side, control word “HV D_side Eliminate I0” is set to “1-eliminate”,
and thus, device performs a zero sequence current elimination on delta
side. In this case, the equations including the coefficient matrices are as
follow:

    
I
  I
A
 2  1  1  A 
  1    
 I  B   . 1 2  1. I B 
   3  1  1 2    
 I C    I C 
   

Equation 17

 I a  1 -1 0  I a 
  1   
 I b    0 1 -1   I b 
I   3 
-1 0 1  I c 
 c  

Equation 18

Subsequent to application of the magnitude, vector group and zero se-


quence compensation, the IED use the following calculated quantities
(per phase) to discriminate between internal and external faults: funda-
mental component of differential and restraint currents together with in-
stantaneous value, 2nd and 5th harmonic contents of differential current.
The following sections go on to demonstrate the fault recognition criteria
using these derived quantities.

4 Protection principle

4.1 Instantaneous differential protection


characteristic

34
Chapter 3 Differential protection

An instantaneous (unrestrained) differential characteristic which entails


an overcurrent protection is provided for fast tripping on heavy internal
faults. The characteristics can be enabled or disabled by using Control
word “Func_Inst Diff” (1-on, 0-off). If setting “1-on” is selected, a trip sig-
nal is issued regardless of the magnitude of the restraining current, as
soon as the differential current rises above the threshold ID>> (setting "
I_Inst Diff "). The generated trip signal is phase selective. it means that
the device issues event reports “Inst Diff Trip A”, “Inst Diff Trip B” or “Inst
Diff Trip C”, when the calculated differential current in phase A, B or C
exceeds the threshold ID>> (setting " I_Inst Diff "). The purpose of this
stage of differential protection is extremely fast operation in case of high
magnitude internal fault currents. This is always the case when the short
circuit current is higher than IN/Uk%, which indicates a fault inside the
power transformer. It should be noted that the magnitude of through fault
currents are always lower than IN/Uk%, when they are supplied via
power transformer. (In this equation, IN is nominal current and Uk% is
short circuit voltage of the power transformer.)

The logic diagram of instantaneous differential protection is shown in


below figure.

Ia>I_Inst Diff
AND INST DIFF TripA
Func_Inst Diff On

Ib>I_Inst Diff AND INST DIFF TripB

Ib>I_Inst Diff
AND INST DIFF TripC

Figure 15 Tripping logic of the instantaneous differential protection

As mentioned previously and can be seen from the figure, the stage op-
erates as an unrestrained protection function. In other words, it is not in-
hibited by any of harmonic stabilization features of the percent differential
element as well as the CT failure detection. This means that it can oper-
ate even when, for example, a considerable second harmonic is present
in the differential current, which is caused by current transformer satura-
tion by a DC component in the fault current, and which could be inter-
preted by the inrush inhibit function as an inrush current.

35
Chapter 3 Differential protection

This high current stage evaluates the fundamental component of the dif-
ferential current as well as the instantaneous values. Instantaneous value
processing ensures fast tripping even in case the fundamental compo-
nent of the current is strongly reduced by current transformer saturation.
Fast trip area is shown in Figure 16.

4.2 Treble slope percent differential protection


characteristic

The percent differential protection uses a treble-slope dual break-point


operating characteristic with magnetizing inrush and overexcitation and
CT failure detection inhibits integrated. The treble slope characteristics
can be enabled or disabled by using Control word “Func_Percent Diff”
(1-on, 0-off). If setting 1-on is selected, the stage calculates differential
and restraint current separately in each phase to obtain operating point in
each operation condition. The derived point is then mapped into Idiff-Ires
plane to examine whether it lies in trip or block area which is defined
according to predefined operating characteristic. The operation charac-
teristic is shown in below figure.

IDiff
Fast trip area
I_Inst Diff
Differential current

Slope 3
Trip area

Slope 2
block area
Slope 1
IRest
I_Percent Diff

I_ResPoint1 Diff I_ResPoint2 Diff Restraint current

Figure 16 Differential protection characteristics for transformers

In this characteristic, branch 1 represents the sensitivity threshold of the


differential protection. The setting of ID> (setting "I_Percent Diff") defines
the minimum differential current required for operation. The setting is
chosen based on the amount of differential current that might be seen
under normal operating conditions which corresponds to constant error
currents such as magnetizing currents and CT errors under no-load con-

36
Chapter 3 Differential protection

ditions. The setting for slope of branch 1 is applicable for restraint cur-
rents of zero to the first break-point indicated on restraint axis (setting
"I_ResPoint1 Diff"). The slope (setting “Slope1_Diff”) defines the ratio of
differential to restraint current above which the percent differential stage
will operate. The first break-point on restraint axis defines the end of the
slope 1 region and the start of the second branch region. This setting
should be set just above the maximum operating current level of the
transformer. This level is somewhere between the maximum
forced-cooled rated current of the transformer and the maximum emer-
gency overload current level.

Branch 2 considers current-proportional errors which may result from


transformation errors of the main CTs or the input CTs of the relay. This
may also contain the error caused by the influence of tap changers in
power transformers with voltage control. The setting for slope of branch 2
(setting “Slope2_Diff”) is applicable for restraint currents of the first
break-point to the second one on restraint axis, and defines the ratio of
differential to restraint current above which the element will operate. This
slope is set to ensure sensitivity to internal faults at normal operating
current levels. The second break-point on restraint axis (setting
“I_ResPoint2 Diff”) defines the end of the slope 2 region and the begin-
ning of the slope 3 region. This setting should be set to the level at which
any of the protection CTs is probable to saturate.

In the range of high through fault currents which may give rise to high
differential currents as a result of CT saturation, branch 3 is applicable to
provide additional stabilization. The setting for the slope of this branch
(setting “Slope3_Diff”) is applicable up to the point at which the branch
intersects the characteristic of instantaneous differential protection.

As a summary of the fault detection using operating characteristics of the


above figure, the calculated differential and restraint currents, IDiff and
IRest, are compared by the differential protection with the operating
characteristic according to the following formula ,

I diff  S1I res  I D I res  I R1 



I diff  S2 ( I res  I R1 )  S1  I R1  I D  I R1  I res  I R 2 

I diff  S3 ( I res  I R 2 )  S2 ( I R 2  I R1 )  S1  I R1  I D  I R 2  I res 

Equation 19

Where S1 is the slope of the branch 1 (setting “Slope1_Diff”),

37
Chapter 3 Differential protection

S2 is the slope of the branch 2, (setting “Slope2_Diff”),

S3 is the slope of the branch 3, (setting “Slope3_Diff”),

ID> is the setting for the sensitivity threshold of the differential protection,
(setting “I_Percent Diff”),

IR1 is the setting for the first breakpoint restraint current, (setting
“I_ResPoint1 Diff”),

IR2 is the setting for the second breakpoint restraint current, (setting
“I_ResPoint2 Diff”).

If the operating point calculated from the quantities of differential and re-
straint current falls into the trip area, a trip signal is issued by the percent
differential protection. The issued signals are phase selective. They can
be found in event report as “Per Diff Trip A”, “Per Diff Trip B” and “Per Diff
Trip C”.

This stage cannot operate when there is an inrush or overexcitation sta-


bilization or a restraint due to CT failure detection. This is illustrated in
below logic diagram.

Func_Percent Diff on

Phase-A
I diff  A , I rest  A A
ID>
N PER DIFF Trip A
D
PER DIFF BLK A

Phase-B
I diff  B , I rest  B
ID>
A
N PER DIFF Trip B
PER DIFF BLK B D

Phase-C
I diff C , I rest C
ID>
A
N PER DIFF Trip C
PER DIFF BLK C D

Block Diff at CT_Fail on


CT FAIL

Figure 17 Tripping logic of the percent differential protection

It should be noted that when the IED is delivered, both the instantaneous
and percent differential protection functions are switched off. Setting of
“0-off” is applied for Control words “Func_Inst Diff” and “Func_Percent

38
Chapter 3 Differential protection

Diff”. This is because the fact that these protection functions should not
be used before at least the vector group and other essential parameters
for each side is correctly set. Without these settings the equipment may
show unpredictable behavior. (E.g. tripping)

4.3 Selective inrush stabilization schemes

In power transformers, high short-time magnetizing currents may be


present during power-up (inrush currents). The inrush current can
amount to a multiple of the rated current. These currents enter the pro-
tected zone. However, it does not exit again. They thus produce differen-
tial quantities, as they seem like single-end fed fault currents. Therefore,
they should be recognized in an appropriate manner. By this way, it is
possible to prevent false operation of differential protection caused by
inrush current. This possibility is provided in the IED. Selective inrush
stabilization can be enabled or disabled by Control word “Block Diff at
Inrush”, (1-Block, 0-Not Block). If setting “1-Block” is applied, the function
monitors differential current to detect an inrush condition. If the condition
is detected, it is possible to block differential protection phase-selectively.
Furthermore, alarm report entitled “Diff 2har Blk” is issued whenever in-
rush detection impose a blocking condition to differential protection. It
should be noted that the latter, is generated when any condition (2nd
harmonic, 3rd/5th harmonic, CT fail) leads to blocking of differential pro-
tection.

The IED provides two schemes to detect inrush conditions. The first
scheme is 2nd harmonic stabilization; the second scheme is fuzzy
recognition of inrush conditions based on the waveform. The two
schemes are convenient for user to be selected by the setting “2nd HAR
NOT WAVE” (1-2nd harmonic on; 0-waveform on). The two implemented
algorithm work alternatively. As soon as an inrush condition is recognized
by each of them, a restraint condition is applied to the respective phase
evaluation of percent differential protection. Since the applied restraint by
2nd harmonic detection operates individually per phase, the protection is
fully operative even when the protected transformer is switched onto a
single-phase fault, whereas inrush currents may possibly be present in
one of the healthy phases. It is, however, possible to set the protection in
a way that when the 2nd harmonic recognition is fulfilled only in one sin-
gle phase, not only the phase with the inrush current, but also the re-
maining phases of the percent differential protection are blocked. This is
achieved by cross-blocking the differential protection for a certain period
to avoid spurious tripping. The setting corresponds to “T_2nd Harm
Block”. Within this time, all three phases are blocked as soon as an in-

39
Chapter 3 Differential protection

rush current is detected in any one phase. After the timer is expired, only
the phase with inrush current content is blocked.

4.3.1 2nd harmonic stabilization

By selecting “1-Block” for control-word “Block Diff at Inrush” and select-


ing“1-2nd harmonic” for Control word “2nd HAR NOT WAVE”, inrush
current is recognized if the second harmonic content in the differential
current exceeds a selectable threshold (setting “Ratio_2nd Harm”). The
ratio between the 2nd harmonic and the fundamental frequency compo-
nent is decisive to discriminate inrush conditions from the other operation
conditions. The ratio is calculated by the below equation. As soon as the
measured ratio exceeds the set thresholds, a restraint is applied to the
percent differential protection in respective phase.

I diff  2
 K 2
I diff 

Equation 20

Where Idiff-φ2 is 2nd harmonics magnitude of differential current, Kφ2 is


the setting for 2nd harmonics ratio, Idiff-φ is fundamental frequency
component of differential current.

4.3.2 Fuzzy recognition of inrush based on the


waveform

By selecting “1-block” in control-word “Block Diff at Inrush”, and selecting


“0-waveform on” for Control word “2nd HAR NOT WAVE”, inrush current
is detected by a fuzzy recognition method based on waveform. In this
context, differential current waveform is sampled in each phase by 2n
number of samples per cycle, each of the samples is nominated as I(k),
k=1, 2, …, 2n. Then the value of X(k) is calculated according to the below
equation.

I ( k )  I ( k  n)
X (k )  , k  1,2,...,n
I ( k )  I ( k  n)

40
Chapter 3 Differential protection

Equation 21

The smaller values of X(k) represent that the calculated point corre-
sponds to fault condition with higher confidence level. Alternatively, the
larger values of X(k) gives a picture that there is large content of inrush
current in the waveform. Assume that X(k) belongs to “inrush Fuzzy
class” with membership function of A[X(k)]. Then, the fuzzy similarity co-
efficient for the n calculated values of X(k) in one cycle is defined as be-
low equation.

n
N  A[ X (k )] / n
k 1

Equation 22

The derived value of N is used in the IED to assess the differential cur-
rent corresponds to inrush condition or not. To do so, the value of N is
compared with a threshold K, and inrush content is recognized in the
current waveform, if N>K.

Func_Percent Diff on

A
I diff  A 2 2nd Harm Not Wave on
N
 K 2 O Block Diff at Inrush on
I diff  A D T_2nd Harm Block PER DIFF BLK A
R

A
I diff  B  2 2nd Harm Not Wave on
N
 K 2 O Block Diff at Inrush on
I diff  B  D T_2nd Harm Block
PER DIFF BLK B
R

Block Diff at Inrush on


A O PER DIFF BLK C
I diff C  2 2nd Harm Not Wave on
N R
 K 2
I diff C  D T_2nd Harm Block

Figure 18 logic diagram of inrush stabilization schemes by 2nd harmonic

41
Chapter 3 Differential protection

Func_Percent Diff on

2nd Harm Not Wave off


A T_2nd Harm Block Block Diff at Inrush on
Fuzzy Inrush N PER DIFF BLK A
Recognition in
D
Ph-A

A T_2nd Harm Block Block Diff at Inrush on


Fuzzy Inrush 2nd Harm Not Wave off N PER DIFF BLK B
Recognition in
D
Ph-B

A T_2nd Harm Block Block Diff at Inrush on


2nd Harm Not Wave off
Fuzzy Inrush N PER DIFF BLK C
Recognition in D
Ph-C

Figure 19 logic diagram of inrush stabilization schemes by fuzzy


recognition

4.4 Overexcitation stabilization

Apart from the second harmonic, other harmonic contents can be se-
lected in the IED to cause stabilization of percent differential protection.
This is because the fact that unwanted differential currents caused by
transformer overexcitation may result in false tripping of the percent dif-
ferential protection. Since steady state overexcitation is characterized by
odd harmonics, the 3rd or the 5th harmonic can be selected in the IED to
judge for overexcitation stabilization. If it is desired to impose a blocking
condition to percent differential protection by these harmonics, Control
word “Block Diff at Overexcit” should be set to “1-on”. By applying this
setting, alarm report entitled “Diff 3/5har Blk” is issued whenever 3rd or
5th harmonic detection impose a blocking condition to differential protec-
tion. It should be noted that the latter, is generated when any condition
(2nd harmonic, 3rd/5th harmonic, CT fail) leads to blocking of differential
protection.

It is possible to use Control word “Overexcitation 3rd NOT 5th” to select


whether 3rd or 5th harmonic detection is utilized for detection of overex-
citation condition (1-3rd harmonic, 0-5th harmonic). Since the third har-
monic is often eliminated in delta winding of power transformers, the fifth
harmonic is more commonly used.

Similar to the 2nd harmonic stabilization, the applied restraint by 3rd or

42
Chapter 3 Differential protection

5th harmonic detection operates individually per phase. It is, however,


possible to set the protection in a way that when the 3rd or 5th harmonic
recognition is fulfilled only in one single phase, not only the phase with
the inrush current, but also the remaining phases of the percent differen-
tial protection are blocked. This is achieved by cross-blocking the differ-
ential protection for a certain period to avoid spurious tripping. The set-
ting corresponds to “T_3/5th Harm Block”. Within this time, all three
phases are blocked as soon as an 3rd or 5th harmonic is detected in any
one phase. After the timer is expired, only the phase with 3rd or 5th
harmonic content is blocked.

The detection method used for 3rd or 5th harmonic is similar to those
applied for 2nd harmonic. However, setting “Ratio_3/5th Harm” is deci-
sive in this case. It means that 3rd or 5th harmonic is recognized if the
ratio between third or fifth harmonic and the fundamental frequency
component of the differential current exceeds the setting threshold. The
ratio is calculated by the below equation.

I diff  3 / 5
 K 3 / 5
I diff 

Equation 23

Where Idiff-φ3/5 is 3rd/5th harmonic magnitude of differential current,


Kφ3/5 is the setting for 3rd/5th harmonic ratio, Idiff-φ is fundamental
frequency component of differential current. Below figure show logic di-
agram of overexcitation stabilization.

Block Diff at Overexcit on

I diff  A 3
 K  3 / 5
I diff  A Overexcit 3rd NOT 5th on A
A N
I diff  A 5 Overexcit 3rd NOT 5 th
off N D O
 K  3 / 5 D T_3/5th Harm Block R
PER DIFF BLK A
I diff  A

I diff  B  3
 K  3 / 5
I diff  B  Overexcit 3rd NOT 5th on A
A N
Overexcit 3rd NOT 5th off N D T_3/5th Harm Block
O
I diff  B  5 PER DIFF BLK B
 K  3 / 5 D R
I diff  B 

I diff C  3
 K  3 / 5 O
I diff C  Overexcit 3rd NOT 5th on A PER DIFF BLK C
A N R
I diff C  5 Overexcit 3rd NOT 5th off N D T_3/5th Harm Block
 K  3 / 5 D
I diff C 

Figure 20 logic diagram of overexcitation stabilization

43
Chapter 3 Differential protection

4.5 CT Failure supervision

During steady-state operation, the CT failure supervision monitors the


transient behavior of the currents flowing through secondary circuit of
each phase and thus registers failures in the secondary circuit of the
current transformers for each side of the power transformer. The function
can be enabled or disabled by using setting “CT Fail Detect” (1-On, 0-Off).
If setting “1-On” is applied, IED issues the alarm report “Ph_A CT Fail”,
“Ph_B CT Fail”, “Ph_C CT Fail”, whenever a CT failure is detected. It is
also possible to set differential protection to be blocked or not at CT fail-
ure detection through setting "Block Diff at CT_Fail" (1-Block, 0-Not
Block). By setting “1-Block”, the percent differential protection is blocked
immediately in all phases. Blocking condition is cancelled as soon as the
device is again supplied with a normal current in the relevant faulty
phase(s). It should be noted that the setting "Block Diff at CT_Fail" is not
useful if the differential current is very high (more than 1.2 Ie, Ie is the
rated current of high voltage side). In other words, blocking conditions
takes place only for treble slope percent differential protection. This
means that the instantaneous differential protection will issue trip if a dif-
ferential current greater than setting “I_Inst Diff” is present, even if " Block
Diff at CT_Fail " is set to 1-Block.

The criteria for CT failure detection are as follow:

The currents flowing through all three phases of CT secondary are nor-
mal at each side of the protected object. As a result, the differential cur-
rent is near to zero. When one or two phase current of one side is de-
creased to less than a threshold (half of the memory current), at the
same time all three phase currents in other side(s) are normal, and dif-
ferential current is more than a threshold (>0.3I_Percent Diff) at least in
one phase, the condition maybe an indication of CT failure in the muta-
tive phase(s). CT failure detection logic is illustrated in below figure.

44
Chapter 3 Differential protection

CT Fail Detect on

Max {Idiff_A, Idiff_B, Idiff_C}>0.3I_Percent Diff

Among {IHV_A, IHV_B, IHV_C} only 1


or 2 phase current decreased A
N
Among {IMV_A, IMV_B, IMV_C} D
and {ILV_A, ILV_B, ILV_C} all
currents without changing
A
N
Among {IMV_A, IMV_B, IMV_C} only 1 CT Fail
D
or 2 phase current decreased A O
N R
Among {IHV_A, IHV_B, IHV_C} and D
{ILV_A, ILV_B, ILV_C} all currents
without changing

Among {ILV_A, ILV_B, ILV_C} only 1


or 2 phase current decreased
A
N
Among {IHV_A, IHV_B, IHV_C} and D
{IMV_A, IMV_B, IMV_C} all currents
without changing

Figure 21 CT Fail detection logic

4.6 CT Saturation supervision

When Internal and external faults occurs, it is possible that transient and
steady fault currents induce the CT saturation. CT saturation may lead to
mal-operation of differential protection when an external fault occurs. In
order to avoid mal-operation of protection in such situations, CT satura-
tion supervision element is integrated in IED.

When transient saturation of CT occurs, the 2nd harmonic content in the


corresponding phase current is dominant. Also whenever steady satura-
tion of CT occurs, the 3rd harmonic content in the corresponding phase
current is dominant. Both 2nd and 3rd harmonic contents of all phase
currents of each side of the protected transformer are calculated to judge
whether CT saturation occurs or not. Comprehensive harmonic ratio is
calculated by below equation.

I 2 I 3
  K har
I I

Equation 24

45
Chapter 3 Differential protection

Where:

Iφ2 is 2nd harmonic magnitude of phase current at each side,

Iφ3 is 3rd harmonic magnitude of phase current at each side,

Khar is the setting for comprehensive harmonic ratio, fixed in the soft-
ware.

If the 2nd and 3rd harmonic contents of any phase current are more than
Khar, then CT satisfies the above formulas and it is saturated. Usually
before the CT saturation status, there is a short time period in which CT
still works in its linear characteristic. By very fast CT saturation detection
of IED, it needs only 4ms before any CT saturation happening to detect
the fault which is internal or external fault. In order to distinguish satura-
tion caused by internal faults and external faults effectively, percent dif-
ferential protection based on sample values is used. If CT saturation is
induced by external fault, differential protection will be blocked. However
if CT saturation is induced by internal fault, differential protection will
send its trip signal.

The typical saturation figure of phase A CT saturation is shown in below


figure.

Figure 22 Typical phase A current transformer Saturation waveform

4.7 Differential current supervision

In normal operation condition, zero differential current is assumed in


each phase. The differential current supervision monitors the differential

46
Chapter 3 Differential protection

currents and checks its value to be less than a threshold. An alarm report
is generated as “Diff Cur Alarm” after 5s, if the differential current ex-
ceeds the threshold value. The alarm is an indication of miss-connection
in CT secondary windings, and therefore is released to remind user to
detect the faulty connection in secondary circuit and remove it. The func-
tion can be enabled or disabled by using setting “Func_Diff Alarm” (1-On,
0-Off). The fixed threshold for releasing alarm is 0.3I_Percent Diff. How-
ever, to avoid incorrect alarm indications, the threshold value is increased
to 0.1A (in 1A nominal current inputs) and to 0.3A (in A nominal current
inputs), if 0.3I_Percent Diff<0.1A. This is shown in below equations.

 I D.alarm  max{0.3I _ Percent Diff , 0.1A} if I n  1A



 I D.alarm  max{0.3I _ Percent Diff , 0.3 A} if I n  5 A

Equation 25

Logic of differential current supervision is shown in below figure.

Func_Diff Alarm on

Idiff_A>ID.alarm
A
O N 5s DIFF Alarm
Idiff_B>ID.alarm
R D
Idiff_C>ID.alarm

Figure 23 CT Fail detection logic

DANGER: Before Differential protection is put into operation on site, po-


larity of current transformer must have been checked right by an energiz-
ing test of every side of the transformer or a test of simulating an external
fault of the side in primary system. Otherwise a mal-operation may occur
during an external fault.

47
Chapter 3 Differential protection

5 Input and output signals

Differential Protection

IA1 Diff Alarm

IB1 Diff Trip

IC1 Inst Diff A Trip

IA2 Inst Diff B Trip

IB2 Inst Diff C Trip

IC2 Per Diff A Trip

IA3 Per Diff B Trip

IB3 Per Diff C Trip

IC3 Relay Startup

IA4

IB4

IC4

IA5

IB5

IC5

Figure 24 Transformer differention protection module, with up to 15


current inputs

48
Chapter 3 Differential protection

Table 12 Analog input list

Signal Description

IA1 Phase A current input of 1st CT set


IB1 Phase B current input of 1st CT set
IC1 Phase C current input of 1st CT set
IA2 Phase A current input of 2nd CT set
IB2 Phase B current input of 2nd CT set
IC2 Phase C current input of 2nd CT set
IA3 Phase A current input of 3th CT set
IB3 Phase B current input of 3th CT set
IC3 Phase C current input of 3th CT set
IA4 Phase A current input of 4th CT set
IB4 Phase B current input of 4th CT set
IC4 Phase C current input of 4th CT set
IA5 Phase A current input of 5th CT set
IB5 Phase B current input of 5th CT set
IC5 Phase C current input of 5th CT set

Table 13 Binary output list

Signal Description

Diff Alarm Differential alarm


Diff Trip

Differential trip

Inst Diff A Trip Instantaneous differential phase A Trip


Inst Diff B Trip Instantaneous differential phase B Trip
Inst Diff C Trip Instantaneous differential phase C Trip
Per Diff A Trip Percent differential phase A Trip
Per Diff B Trip Percent differential phase B Trip
Per Diff C Trip Percent differential phase C Trip
Relay Startup Relay Startup

49
Chapter 3 Differential protection

6 Settings
Table 14 Instruction for Vector Group Angle setting

Control word Values

HV Wind Conn/Y-0 D-1 0 0 0 1 1 1

MV Wind Conn/Y-0 D-1

(Only for three-winding trans- 0 1 0 1 1 0

formers)

LV Wind Conn/Y-0 D-1 1 1 0 1 0 0

Vet Grp Angle odd odd even Even odd odd

Y-Y-D-1 Y-D-D-1 Y-Y-Y- D-D-D- D-D-Y- D-Y-Y-

Remarks /3/5/7/9/ /3/5/7/9/ 2/4/6/8 2/4/6/8/ 1/3/5/7 1/3/5/7

11 11 /10/12 10/12 /9/11 /9/11

Table 15 Settings of Differential protection

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
Instantaneous Differential
I_Inst Diff A 0.5Ir 20Ir 20
(ID>>) current setting
Percentage Differential (ID>)
I_Percent Diff A 0.08Ir 4Ir 2.1
current setting
The 1st breakpoint restraint
I_ResPoint1 Diff A 0.1Ir Ir 2
current (IR1)
The 2nd breakpoint restraint
I_ResPoint2 Diff A 0.1Ir 10Ir 2
current (IR2)
Slope1_Diff 0 0.2 0.2 the 1st slope

Slope2_Diff 0.2 0.7 0.5 the 2nd slope

Slope3_Diff 0.25 0.95 0.7 the 3rd slope

Ratio_2nd Harm 0.05 0.80 0.15 2nd harmonic(HAR) ratio

Ratio_3/5th Harm 0.05 0.80 0.35 3rd / 5th harmonic(HAR) ratio


Within the delay 2nd har-
T_2nd Harm Block s 0 20 20
monic block all three phas-

50
Chapter 3 Differential protection

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
es. After the delay, then
only the local phase is
blocked.
th
Within the delay 5 har-
monic block all three phas-
T_3/5th Harm
s 0 20 20 es. After the delay, then
Block
only the local phase is
blocked.

Table 16 Control words of Differential protection

Default
Setting Unit Min. Max. Description
setting
Instantaneous differential
Func_Inst Diff 0 1 0
protection ON 1-on; 0-off.
Func_Percent Diff Percentage differential pro-
0 1 0
tection ON 1-on; 0-off.
Block Diff at Inrush Inrush block differential pro-
0 1 0 tection
1-block; 0-not block.
2nd Harm Not 2nd harmonic (HAR) inhibit
Wave not the fuzzy recognition
based on the wave-
0 1 0
form(WAVE)
1-2nd harmonic on; 0-
waveform on
Block Diff at Overexcitation block differ-
Overexcit 0 1 0 ential protection
1-block; 0-not block.
Overexcitation stabilization
judgement
Overexcit 3rd NOT 3rd or 5th harmonic (HAR)
0 1 0
5th inhibit on
rd th
1-3 harmonic; 0-5 har-
monic.
Differential current (DIFF)
Func_Diff Alarm 0 1 0
Alarming on

51
Chapter 3 Differential protection

Default
Setting Unit Min. Max. Description
setting
1-on; 0-off.
Block differential protection
Block Diff at
0 1 0 when there is CT failure
CT_Fail
1-block; 0-not block.
Eliminate calculated 3I0
HV D_side Elimi- when HV side winding is
0 1 0
nate I0 connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0
MV D_side Elimi- when MV side winding is
0 1 0
nate I0 connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0
LV D_side Elimi- when LV side winding is
0 1 0
nate I0 connected in Delta mode
1- eliminate; 0-not eliminate
LV current is included in
calculation of the differential
Diff Includes LV
0 1 0 protection.
Cur
1- Diff Includes LV Cur;
0-Diff NOT Includes LV Cur

7 Report
Table 17 Event report list

Information Description

Per Diff Trip A

Per Diff Trip B Treble slope percent Differential protection (ID>) trip for phase A/B/C

Per Diff Trip C

Inst Diff Trip A

Inst Diff Trip B Instantaneous Differential protection (ID>>) trip for phase A/B/C

Inst Diff Trip C

52
Chapter 3 Differential protection

Table 18 Alarm report list

Information Description

Ph_A Ct Fail Phase A CT failure


Ph_B Ct Fail Phase B CT failure
Ph_C Ct Fail Phase C CT failure
Diff Cur Alarm Imbalance differential current alarm
Diff 2har Blk Differential protection is blocked by 2nd harmonic.
Diff 3/5har Blk Differential protection is blocked by 3rd or 5th harmonic.

Table 19 Operation report list

Information Description

Func_Diff On Differential protection is switched ON (by CW)


Func_Diff Off Differential protection is switched OFF (by CW)

8 Technical data
Table 20 Differential protection technical data

Item Range or value Tolerance

Instantaneous differential current 0.5 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir


Percentage differential current 0.08 Ir to 4.00 Ir ≤ ±3% setting or ±0.02Ir,
Restraint current 1 0.1 Ir to 1 Ir ≤ ±3% setting or ±0.02Ir
Restraint current 2 0.1 Ir to 10 Ir ≤ ±3% setting or ±0.02Ir
Slope 1 0.0 to 0.2
Slope 2 0.2 to 0.7
Slope 3 0.25 to 0.95
2nd harmonic restraint ratio 0.05 to 0.80 of fundamental
3rd / 5th harmonic restraint ratio 0.05 to 0.80
Reset ratio of restrained differ-
approx. 0.7
ential
Operating time of restraint dif- ≤ 30ms at 200% setting, and
ferential IDifferential>2IRestraint
Operating time of instantaneous
20ms typically at 200% setting
differential
Reset time approx. 40ms

53
Chapter 3 Differential protection

54
Chapter 4 Stub differential protection

Chapter 4 Stub differential


protection

About this chapter


This chapter describes the protection principle, input and
output signals, parameter, IED report and technical data for
Stub differential protection

55
Chapter 4 Stub differential protection

1 Introduction
Stub differential is mainly applicable for transformer and line T-zone pro-
tectioin, the protection area is restricted by CT quantity and polarity.

2 Application
5-side differential can be supported by stub differential protection. Some
application diagrams are shown below:

I busbar busbar II busbar


* CT1 *CT2

CT3

*
G1

element Differential

protection

Figure 25 Application in stub differential protection

3 Protection algorithm

3.1 Differential current and restraint current


calculation

The differential current Idiff and restraint current Ires are calculated via the
formula below, which is applicable to each phase of the protected object.

56
Chapter 4 Stub differential protection

 N 
 diff

I  
i 1
Ii
 N 1 
 1 
I 
 res 2

I j (max)  
i 1
I i (i  j )

Equation 26

in which, I i is the current vector at I side, corresponding to I/II side, III/IV

side and V side, N is the total channel of current input, viz. N is the
quantity at the protected object sice, I j (max) is the lagest current vector

N 1 
and supposed to be j side current,  I i (i j ) is the sum of other current
i 1

inputs, excluding j side current. Idiff is from the fundamental current and
is used to determine the action value, and Ires is used to determine the
restraint value.For the details, three important operating situations are
listed below.

(a) External fault:

I1 flows into protection area, I2 flows out of the protection area, viz. I2 =
–I1.

Idiff = I1 + I2 = I1 – I1 = 0

Ires = 0.5×| I1 - (–I1) | = 0.5×|2I1| = |I1|

The IED does not trip (Idiff = 0), the restraint current is protected when
external fault current flows through the protected object

(b) Internal fault:

The current at each side is equal, viz. I1= I2

Idiff = I1 + I2 = I1 + I1 = 2 I1

Ires = 0.5×| I1 - I1| = 0

The IED trips, the Idiff is two times of the fault current and the Ires is 0.

(c) Internal fault:

57
Chapter 4 Stub differential protection

The current is from one of the sides.

If I2 = 0

Idiff = I1 + I2 = I1 + 0 = I1

Ires = 0.5×|I1 - I2| =0.5× |I1 - 0| = 0.5×|I1|=0.5 I1

Idiff equals to Ires, then it is the single side fault current.

Based on the results above, the IED can distinguish the internal fault
and external fault via calculating the Idiff and Ires. However, the IED can
still be influenced by the differential in normal operation. This influence
should be compensated via automatic ratio compensation and auto-
matic phase compensation. For detailed introduction, please refer to
following sections.

3.2 Automatic ratio compensation

I/II side current is the reference current. III/IV side current and V side
current are matched with I/II side current automatically via the correction
coefficient of their calculations. The correction coefficient formulas are
as below.

nCT  III / IV
KCT  III / IV 
nCT  I / II

Equation 27

nCT V
KCT V 
nCT  I / II

Equation 28

In which, KCT-III/IV is III/IV side correction coefficient, KCT-V is V side


correction coefficient.

nCT is CT ratio,(nCT-I/II is I/II side CT ratio, nCTV is Vside CT ratio.

As sated above, all calculations are carried out in IED CPU.

58
Chapter 4 Stub differential protection

4 Protection principle

4.1 Characteristic of differential instant tripping


protection

Differential instant tripping protection (without restraint) characteristic is


similar to overcurrent protection. The instant tripping occurs in case of
internal fault. The function can be enabled or disabled via control word
"Func_Inst Diff " (1-On, 0-Off). If the setting value is 1, the split phase
triping order is given when Idiff ID>>(setting value “I_Inst Diff”) without
considering the value of Ires. The report of protection tripping is “Per Diff
Trip A”, “Per Diff Trip B” or “Per Diff Trip C” when the Idiff Idiff ID>>(setting
value “I_Inst Diff”). The IED trips when the internal fault current is rela-
tively large.

Logic diagram of differential instant tripping protection are shown in the


figure below.

Ia>ISD I_Inst Diff

and Per Diff Trip A


Func_Inst Diff

Ib>ISD I_Inst Diff and Per Diff Trip B

Ic>ISD I_Inst Diff


and Per Diff Trip C

Figure 26 Logic diagram of differential instant tripping protection

As shown in the figure above, there is no restricting to differential instant


tripping, viz. the differential instant tripping is not subjected to percentage
differential element harmonic characteristic and CT failure, which means
that the IED trips in case of CT saturation caused by DC offset charac-
teristic and 2nd harmonics caused by excitstion inrush.

The IED determines the fundmental current and setting value of differen-
tial instant tripping. The setting value of differential instant tripping should
make sure the IED trips instantly when the fundamental current de-
creases under the condition of CT saturation. For the instant tripping,
please refer to figure 16.

59
Chapter 4 Stub differential protection

4.2 Three-slope differential protection


characteristic

Three-slope double breaking points differential protection has excitation


inrush, overexcitation and CT failure blocking characteristics. The
three-slope characteristic can be enables or disabled by control word "
Func_Percent Diff " (1-On, 0-Off). If the setting value is 1, the Idiff and Ires
of each phase in each section are calculated to get the tripping point, and
then compare with the Idiff-Ires tripping characteristic to determine the
tripping point is in the tripping area or the restraint area. The tripping
characteristic is shown in the figure below.

Idiff

Differential instant tripping area


I_Inst Diff

Slope3
Tripping area
Idiff

Slope2 Restraint
Slope1 area
Ires
I_Percent Diff
I_ResPoint1 Diff I_ResPoint2 Diff Ires

Figure 27 Transformer differential protection characteristic

In the tripping characteristic, Slope 1 is the sensitive threshold of differ-


ential protection, the setting value of ID (ID>"I_Percent Diff ICD”) is the
minimum differential current required by differential protection tripping. In
normal operation, the unbalanced current caused by excitation inrush
and CT difference when there is no load should be considered in the set-
ting of differential setting value. The setting range of slope 1 is from zero
to the first breaking point ( setting value of IR1 “I_ResPoint1 Diff “)on the
horizontal restraint axis. Slope 1 (setting value of Slope1_Diff ) is the ratio
of Idiff to Ires. The percentage differential protection area is above the slope
1. The first breaking point on the restraint axis is the ending of slope 1
and the staring of slope 2. The slope 1 should be slightly larger than the
maximum operating current of transformer and between the maximum
rated current required cooling and the maximum emergent overload
current.

60
Chapter 4 Stub differential protection

Slope 2 should consider the current error caused by main CT of trans-


former and internal CT, including the error caused by transformer tap in
voltage regulating. The setting range of slope 2 (Slope2_Diff) is between
the first breaking point and second breaking point. The tripping order is
given when the ratio of Idiff to Ires is greater than this setting value. The
sebstivity of internal fault in normal operation should be ensured for the
value setting. At the same time, CT saturation should be considered. The
second breaking point is the ending of slope 2 and the starting of slope 3.

A very large differential current may occur when the over through fault
current causes CT saturation. The slope 3 may enure the stability of dif-
ferential protection. The setting value (Slope3_Diff) of slope 3 is set to
overlap with the differential instant tripping characteristic.

Fault detection is carried out through the tripping characteristic mentiond


in the figure above. The Idiff and Ires are compared with the following for-
mula of tripping characteristic.

I diff  S1I res  I D I res  I R1 



I diff  S2 ( I res  I R1 )  S1  I R1  I D  I R1  I res  I R 2 

I diff  S3 ( I res  I R 2 )  S2 ( I R 2  I R1 )  S1  I R1  I D  I R 2  I res 

Equation 29

in which, S1 means slope 1 (Slope1_Diff);

S2 means slope 2 (Slope2_Diff);

S3 means slope 3 (Slope3_Diff);

ID> differential protection sensitivity threshold (“ICD I_Percent Diff”);

IR1 is the first setting value at the restraint current breaking point
“I_ResPoint1 Diff”;

IR2 the second setting value at the restraint current breaking point
“I_ResPoint2 Diff”.

If the tripping point of Idiff and Ires are in the tripping area, the tripping order
will be given. The split-phase of tripping signal can be seen from the re-
port “Per Diff Trip A”, “Per Diff Trip B” and “Per Diff Trip C”.

When CT failure blocking conditions are met, the protection tripping


will be blocked, as shown in logic diagram.

61
Chapter 4 Stub differential protection

Figure 28 Percentage differential protection tripping logic

The differential instant tripping and percentage differential protection are


not enabled upon the delivery of IEDs. The control word “Func_Inst Diff
protection” and “Func_Percent Diff” are set as zero. Because enabling
differential function before the correct setting of parameters at each side
phase and other basic parameters will lead to unpredicatable actions (for
example, tripping).

4.3 CT –secondary current supervision

In steady operation, the CT-secondary current supervision supervises the


current transient processing of each phase in secondary circuit and de-
termine whether CT secondary circuit at each side of the transformer fails
or not. The CT transient supervision can be enabled or disabled via con-
trol word “CT Fail Detect” (1-On, 0-Off). If the control word is set as 1 and
the CT failure is detected, the alarm report is given by the IED. The dif-
ferential protection can be set to determine whether to be blocked by CT
failure via control word “Block Diff at CT_Fail”. If being blocked by CT
failure is set, percentage differential protection at each phase is blocked
immediately. When the phase current recovers, the blocking conditions
are disabled correspondingly. What should be noted is that when the
differential current is very lage (for example, greater than 1.2 In), the
control word doesn’t work. In other words, blocking conditions make a

62
Chapter 4 Stub differential protection

difference on three-slope percentage differential protection only, which


means that tripping occurs when the differential current is greater than
the setting value of differential instant tripping, even the differential pro-
tection is blocked through CT failure.

CT failure detection is based on following conditions.

In normal running status (without the startup of protection), the current


flows through each side of transformer is normal, therefore, the differen-
tial current is zero. CT failure may occur when the current of one phase
or two phases at one of the sides is reduced to the threshold value of
current (half of the memorizing current), meanwhile, three-phase current
at other sides is normal and at lwast one phase differential current is
greater than the threshold value (greater than 0.3 times of setting value
of differential protection current ICD).

The logic diagram of CT failure detection in case of abrupt variables is


shown in figure below.

CT Fail Detect

Max{Idiff_A , Idiff_B , Idiff_C}>0.3ICD I_Percent Diff

{I1/2_A , I1/2_B , I1/2_C } Only one or two phases decrease

and
{I 3/4_A , I 3/4_B , I 3/4_C }and{I 5 _A ,
I 5 _B , I 5 _C }No current change

and CT Fail
{I 3/4_A , I 3/4_B , I 3/4_C } Only one or two
phases decrease

and or
{I1/2_A , I1/2_B , I1/2_C } and{I 5 _A ,
I 5 _B , I 5 _C }No current change

{I 5 _A , I 5 _B , I 5 _C } Only one or two


phases decrease

and
{I1/2_A , I1/2_B , I1/2_C } and{I 3/4_A ,
I 3/4_B , I 3/4_C }No current change

Figure 29 CT logic diagram

4.4 CT saturation detection

63
Chapter 4 Stub differential protection

When the external or internal fault occur, the transient fault current and
load current may lead to CT saturation, which may cause differential
misoperation. To avoid the misoperation in case of saturation, CT
saturation detection is equipped within the IED.

When transient saturation of CT occurs, the 2 nd harmonics are very


large in corresponding phase. The 2nd and 3rd harmonics are calculated
at each phase of each side to determine whether CT is saturated or not.
The total harmonics ratio is calculated by using the formula below.

I 2 I 3
  K har
I I

Equation 30

In which

Iφ2 is the 2nd harmonics amplitude at each side current;

Iφ3 is the 3rd harmonics amplitude ar each side current;

Khar is the setting value of total harmonics ratio, fixed setting value in the
software.

If the 2nd harmonics and 3rd harmonics in any phase of current is larger
than Khar, meanwhile, CT meets the calculating formula listed above,
then it is CT saturation. Generally, CT still has liner characteristic before
saturation. 4 ms is needed only to determine interal or external fault be-
fore CT saturation. The differential protection adopts the sampling value
to determine rapidly CT saturation is caused by internal fault or external
fault. The differentional protection will be blocked if CT saturation is
caused by external fault. The tripping signal will be given if CT saturation
is casused by internal fault.

Typical A phase saturated wave is shown in the figure below.

64
Chapter 4 Stub differential protection

Figure 30 Typical A phase CT saturation and wave

4.5 Differential supervision

In normal running status, the differential current of each phase is con-


sidered as zero. The differential supervision supervises the differential
current and determine if the current is less than the threshold value. The
alarm report " Diff Cur Alarm" will be given in 5s if the differential current
is greater than the threshold value. The alarm is used to inform users to
check CT secondary winding connection error and clear the fault. This
function can be enabled or disabled via control word "Func_Diff Alarm"
(1-enable, 2-disable). The setting threshold value of alarm is 0.3 times of
"ICD I_Percent Diff". However, to avoid wrong alarm, the threshold value
will increase to 0.06A(1A CT) and 0.3A(5A CT) if the 0.3 times of "ICD
I_Percent Diff" is less than 0.06In. The formular is shown as below.

 I D.alarm  max{0.3I _ Percent Diff , 0.06 A} if I n  1A



 I D.alarm  max{0.3I _ Percent Diff , 0.3 A} if I n  5 A

Equation 31

The logic diagram of differential supervision is shown in the figure below.

65
Chapter 4 Stub differential protection

Func_Diff Alarm

Idiff_A>ID.alarm

Idiff_B>ID.alarm or or 5s Func_Diff

Idiff_C>ID.alarm

Figure 31 Logic diagram of differntial out-of-limits

Alarm: Before enabling differential protection, energizing test should be


conducted on CT polarity at each side of T area or the primary external
fault test should be correct, otherwise, protection misoperation may occur
in case of external fault.

5 Input and output signals

Differential protection

IA1 Diff Alm

IB1 Diff Trip

IC1 Inst Diff A Trip

IA2 Inst Diff B Trip

IB2 Inst Diff C Trip

IC2 Per Diff A Trip

IA3 Per Diff B Trip

IB3 Per Diff C Trip

IC3 Relay Startup

IA4

IB4

IC4

IA5

IB5

IC5

Figure 32 Sudden-change current startup element


Figure 32 Channels of current input stub differential protection module

66
Chapter 4 Stub differential protection

Table 21 Analog input list

Signal Description

IA1 A phase current input of the first set of CT


IB1 B phase current input of the first set of CT
IC1 C phase current input of the first set of CT
IA2 A phase current input of the second set of CT
IB2 B phase current input of the second set of CT
IC2 C phase current input of the second set of CT
IA3 A phase current input of the third set of CT
IB3 B phase current input of the third set of CT
IC3 C phase current input of the third set of CT
IA4 A phase current input of the fourth set of CT
IB4 B phase current input of the fourth set of CT
IC4 C phase current input of the fourth set of CT
IA5 A phase current input of the fifth set of CT
IB5 B phase current input of the fifth set of CT
IC5 C phase current input of the fifth set of CT

Table 22 Binary output list

Signal Description

Diff Alm Differential current alarm


Diff Trip Differential Protection trip
Inst Diff A Trip Phase A instantenous differential protection trip
Inst Diff B Trip Phase B instantenous differential protection trip
Inst Diff C Trip Phase C instantenous differential protection trip
Per Diff A Trip Percent differential phase A Trip
Per Diff B Trip Percent differential phaseB Trip
Per Diff C Trip Percent differential phase C Trip
Relay Startup Relay Startup

67
Chapter 4 Stub differential protection

6 Setting value
Table 23 Setting value of basic protection element

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
A 50.00 9999. 1200.0 Primary value of CT
I/II Side CT Pri
at I/II side
A 1.000 5.000 1.0 Secondary value of
I/II Side CT Sec
CT at I/II side
A 50.00 9999. 1200.0 Primary value of CT
III/IV Side CT Pri
at III/IV side
A 1.000 5.000 1.0 Secondary value of
III/IV Side CT Sec
CT at III/IV side
A 50.00 9999. 3000.0 Primary value of CT
V Side CT Pri
at V side
A 1.000 5.000 1.0 Secondary value of
V Side CT Sec
CT at V side
0 9999 Ratio factor of dif-
ferential protection
Ratio Factor I/II
at I/II side (calculat-
ed value, read only)
0 9999 Ratio factor of differ-
ential protection at
Ratio Factor III/IV
III/IV side (calculated
value, read only)
0 9999 Ratio factor of differ-
ential protection at V
Ratio Factor V
side (calculated val-
ue, read only)

Table 24 Basic protection control word

Setting Unit Min. Max. Default Description


CT Fail Detect CT failure detection
0 1 0
1- enable, 0-disable

68
Chapter 4 Stub differential protection

Table 25 Setting value of differential protection

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Setting value of dif-
I_Inst Diff A 0.5Ir 20Ir 20 ferential instant trip-
ping current (ID>>)
Setting value of per-
centage differential
I_Percent Diff A 0.08Ir 4Ir 2.1
protection circuit
(ID>)
The 1st breakpoint
I_ResPoint1 Diff A 0.1Ir Ir 2 restraint current
(IR1)
Setting value of cur-
I_ResPoint2 Diff A 0.1Ir 10Ir 2 rent at the second
breaking point (IR2)
The first ratio re-
Slope1_Diff 0 0.2 0.2
straint coefficient
The second ratio re-
Slope2_Diff 0.2 0.7 0.5
straint coefficient
The third ratio
Slope3_Diff 3 0.25 0.95 0.7 re-straint coeffi-
cient

Table 26 Control word of differential protection

Setting Value Unit Min. Max. Default Description


Differential instant tripping
Func_Inst Diff 0 1 0
protection 1-On, 0-Off
Func_Percent Diff Percentage differential pro-
0 1 0
tection 1-On, 0-Off
Differential current
Func_Diff Alarm 0 1 0 out-of-limits alarm 1-On,
0-Off
Block Diff at CT failure blocking differen-
0 1 0
CT_Fail tial 1-blocking, 2-unblocking

69
Chapter 4 Stub differential protection

7 Report
Table 27 Event report list

Report Description

Per Diff Trip A

Per Diff Trip B Three-slope percentage differential protection trip A/B/C phase

Per Diff Trip C

Inst Diff Trip A

Inst Diff Trip B Differential instant tripping protection trip A/B/C phase

Inst Diff Trip C

Table 28 Alarm report list

Alarm Report Description

Ph_A CT Fai A phase CT failure


Ph_B CT Fai B phase CT failure
Ph_C CT Fai C phase CT failure
Diff Cur Alarm Unbalanced differential alarm

Table 29 Operation report list

Report Description

Func_Diff On Enable differential protection


Func_Diff Off Disable differential protection

8 Technical data
Note:Ir is rated secondary current of CT, 1A or 5A.

70
Chapter 4 Stub differential protection

Table 30 Differential protection technical data

Content Range Error


Differential instant tripping cur- 0.5 Ir to 20.00 Ir ≤ ±3% of setting value or ±0.02Ir
rent
Percentage differential current 0.08 Ir to 4.00 Ir ≤ ±3% of setting value or ±0.02Ir,
I_ResPoint1 Diff 0.1 Ir to 1 Ir ≤ ±3% of setting value or ±0.02Ir
I_ResPoint2 Diff 0.1 Ir to 10Ir ≤ ±3% of setting value or ±0.02Ir
Slope1 0.0 to 0.2
Slope2 0.2 to 0.7
Slope3 0.25 to 0.95
Drop off value of percentage
About 0.7
differential
Tripping time of percentage dif- ≤ 30ms in case of 200% of set-
ferential ting value, and IDifferential>2IRestraint
The tripping time is 20ms in case
Differential instant tripping time
of 200% of setting value
Drop off time About 40ms

71
Chapter 4 Stub differential protection

72
Chapter 5 Restricted earth fault protection

Chapter 5 Restricted earth fault


protection

About this chapter


This chapter describes the protection principle, input and
output signals, parameter, IED report and technical data for
restricted earth fault protection function.

73
Chapter 5 Restricted earth fault protection

1 Introduction
The restricted earth fault protection detects earth faults in power trans-
formers with earthed starpoint or in non-earthed power transformers with
a starpoint former (earthing transformer/reactor) installed inside the pro-
tected zone. A precondition for using this function is that a CT should be
installed in the starpoint connection, i.e. between the starpoint and earth.
The starpoint CT and the phase CTs define the limits of the protected
zone by restricted earth fault protection.

2 Applications
The IED provides two restricted differential protection functions which
can be used independently at various locations. For example, it is possi-
ble to use them for both windings of YNyn transformer which is earthed at
both starpoints. Further, one of them can be implemented to protect an
earthed transformer winding and the other for an earthing transform-
er/reactor. In case of auto-transformers, one of them is sufficient to pro-
tect the auto-windings. Examples for some of applications are illustrated
in the below figure.

HV LV
I A.2
A a
IB.2
B b
IC .2
C c

3I02  IA.2  IB.2  IC .2


3I01
CSC-326

Figure 33 Application of restricted earth fault protection on an


earthed transformer winding

74
Chapter 5 Restricted earth fault protection

HV LV
Ia .2
A a
Ib .2
B b
Ic.2
C c

3I01

3I02
  Ia .2  Ib .2  Ic.2
CSC-326

Figure 34 Application of restricted earth fault protection on an


earthing transformer winding

HV LV
I A.2
Ia .2
A a
IB.2
Ib .2
B b
IC .2 Ic.2
C c

3I01 3I01

3I02  IA.2  IB.2  IC .2

CSC-326
3I02
  Ia .2  Ib .2  Ic.2

Figure 35 Application of restricted earth fault protection on both


sides of transformer

75
Chapter 5 Restricted earth fault protection

I A.2
A Ia.3
a
IB.2
Ib .3
B
b
IC .2
C Ic .3
c

3I01

3I02  IA.2  IB.2  IC .2


CSC-326
3I03  Ia.3  Ib.3  Ic.3

Figure 36 Application of restricted earth fault protection on an


auto-transformer

3 Protection principle
During healthy operation condition, no starpoint current 3I01 flows
through the starpoint CT. Furthermore, the sum of the phase currents 3I02
=IA.2 + IB.2 + IC.2 is almost zero. In case of auto-transformer, both the re-
sidual currents 3I02 =IA.2 + IB.2 + IC.2 and 3I03 =IA.3 + IB.3 + IC.3 are zero. With
an earth fault inside the protected zone, a starpoint current 3I01 flows.
Moreover, depending on the earthing conditions of the power system
outside the protected zone, a further earth current may be recognized in
the residual current path of the phase CTs (3I02 and 3I03). Since all the
currents flowing into the protected zone are defined positive, the residual
current from the system (3I02 and 3I03) is more or less in phase with the
starpoint current (3I01). With an earth fault outside the protected zone, a
starpoint current 3I01 flows into the protected zone, together with equal
residual current 3I02 and 3I03 which flows toward outside of the protected
zone, through the phase CTs. Keeping in mind positive direction current
flow, which is toward the protected zone, the starpoint current is in phase
opposition with 3I02 and 3I03.

With the described situations, it may seem to be simple to discriminate an


internal fault from an external one. However, there are some difficulties to
do so. For instance, when a strong fault without earth connection occurs
outside the protected zone, a residual current may appear in the residual
current path of the phase CTs. The residual current is caused by different
degrees of saturation in phase CTs and could simulate a fault in the
protected zone. Thus, additional measures should be taken to prevent
this current to cause false tripping. To achieve this objective, the re-
stricted earth fault protection provides a restraint quantity.

76
Chapter 5 Restricted earth fault protection

3.1 Differential and restraint current calculation

The differential current Idiff0 and the restraining current Irest0 are calculated
according to below figure.

 I diff 0  3I01  3I02  3I03




 I
 rest0

 max 3I01 , 3I02 , 3I03 

Equation 32

Idiff0 and Irest0 are compared by the restricted earth fault protection with
a dual-slope operating characteristic defined by below equation and
shown in below figure.

I diff 0  I 0 D if I res0  I 0 D / S 0 D



I diff 0  S 0 D  I res0 if I res0  I 0 D / S 0 D

Equation 33

Where I0D is the setting for sensitivity threshold of restricted earth fault
protection (setting “HV 3I0_REF”, “MV 3I0_REF” or “LV 3I0_REF”), and
S0D is slope of the branch (setting “HV Slope_REF”, “MV Slope_REF” or
“LV Slope_REF”).

This characteristic can be enabled or disabled by using Control word “HV


Func_REF Trip”, “MV Func_REF Trip” or “LV Func_REF Trip”). If setting
“1-on” is selected, a trip signal is issued by restricted earth fault protec-
tion when the operating point lies into tripping area (see below figure) and
the preset time delay is expired (setting “HV T_REF Trip”, “MV T_REF
Trip” or “LV T_REF Trip”).

The trip logic for restricted earth fault protection is shown in below figure.

77
Chapter 5 Restricted earth fault protection

I Diff0

Trip area
Slope _ REF

3 I 0 _ REF
block area

I Res0

Figure 37 Characteristic of restricted earth fault protection

Func_REF Trip on

A
T_REF Trip
N REF Trip
D

Func_REF Alarm on
A
T_REF Alarm
N REF Alarm
D
Idiff0>HV 3I0_REF Alarm

Figure 38 Tripping logic of the restricted earth fault protection

To clarify the proper operation during various situations, three important


operating conditions are examined.

External fault:

3I01 enters the protected zone, whereas 3I02 leaves the protected zone,
i.e. is negative according to the definition of signs, therefore 3I02 = –3I01.

Idiff0 = |3I01 + 3I02| = |3I01 – 3I02|= 0

Ires0 = max {|3I01|, |3I02|} = |3I01|

No tripping quantity (Idiff0 = 0); the restraint quantity (Irest0) corresponds


to the external fault current flowing through the starpoint connection.

Internal fault, fed only from the starpoint:

78
Chapter 5 Restricted earth fault protection

In this case, 3I02=0, thus,

Idiff0 = |3I01 + 3I02| = |3I01 + 0| = |3I01|

Ires0 = max {|3I01|, |3I02|} = |3I01|

Both the tripping (Idiff0) and the restraint (Irest0) quantities correspond to
the fault current flowing through the starpoint.

Internal fault, fed from the starpoint and from the system, e.g. with equal
earth current magnitude:

Both the 3I01 and 3I02 enter the protected zone, thus having positive sign.
The condition results in 3I02 = 3I01.

Idiff0 = |3I01 + 3I02| = |3I01 + 3I02|= 2×|3I01|

Ires0 = max {|3I01|, |3I02|} = |3I01|

Tripping quantity (Idiff0) corresponds to double the fault current flowing


through the starpoint connection, and restraint quantity (Irest0) is equal to
the fault current.

The results show that the device is capable to properly discriminate in-
ternal and external earth faults by using the definitions proposed for dif-
ferential and restraint current. However, the device is still subjected to
some influences that induce differential currents even during normal op-
eration condition. These influences should be compensated in appropri-
ate manner. The specific treatments designed to cope with these influ-
ences includes automatic ratio compensation which is explored as fol-
lows.

3.2 Automatic Ratio compensation

Restricted earth fault protection represents some problems in the appli-


cation of current transformers regarding to matching between phase and
starpoint CTs. The problem is originated from different ratio of phase and
starpoint CTs. The difference may result in a differential current in normal
operation condition. To remove this problem, the input currents of the
relay from starpoint CTs should be converted according to primary rated
currents of phase and starpoint CTs. In the IED, this objective is achieved
by taking a common reference value and converting all secondary cur-
rents of starpoint CTs into the same reference. The conversion is per-

79
Chapter 5 Restricted earth fault protection

formed by calculation of ratio compensation factor for starpoint CTs. The


compensation factors are then multiplied by the secondary current of
starpoint CTs to make them comparable with those current measured at
phase CTs. The conversion procedure is performed inside the device.
The ratio compensation factors are calculated as follow:

nStarpoint HV
K Starpoint HV 
nPhase HV

Equation 34

nStarpointMV
K StarpointMV 
nPhaseMV

Equation 35

nStarpoint LV
K Starpoint LV 
nPhase LV

Equation 36

K StarpointHV
Where is the ratio compensation factor for HV starpoint

K StarpointMV
CT; is the ratio compensation for MV starpoint CT

K Starpoint LV
and is the ratio compensation for LV starpoint CT;

For auto-transformer, in addition to the common winding starpoint CT, the


measured current from phase winding of MV winding should also be
converted to the common reference current. In this context, the ratio
compensation factors are calculated as follow:

nPhaseMV
K MV 
nPhase HV

Equation 37

nStarpoint
K Starpoint 
nPhase HV

80
Chapter 5 Restricted earth fault protection

Equation 38

Where K MV is the ratio compensation factor for MV phase CT, and

K Starpoint
is the ratio compensation factor for common winding starpoint
CT.

The reference current is selected as is shown in below figure.

Table 31 Reference side selection for REF functions

Type function HV REF MV REF LV REF

2 winding HV CT --- LV CT

3 winding HV CT MV CT ---

Auto-transformer HV CT --- ---

3.3 Positive sequence current blocking

CT2 HV LV
I A.2
A a
IB.2
B b
IC .2
C c

3I02  IA.2  IB.2  IC .2


3I01
CSC-326

Figure 39 Earth fault protection tripping logic

When an external fault causes a heavy current to flow through the pro-
tected transformer, differences in the magnetic characteristics of the
current transformer CT2 under saturation condition may cause a signifi-
cant difference in the secondary currents I02 connected to IED. If the
difference is greater than the pickup threshold, the REF protection func-
tion can trip even though no fault occurred in the protected zone. To
prevent the protection function from such erroneous operation, a restraint

81
Chapter 5 Restricted earth fault protection

(stabilizing) ratio, zero-sequence current divides positive-sequence cur-


rent, is brought in.

I0
15%
I1

Where I0 is zero-sequence current, I1 is positive-sequence current.

Only when the ratio is greater than 15% can the REF protection trip.

3.4 Restricted earth fault current alarm

In normal operation condition, zero differential current is expected for re-


stricted earth fault protection. The Restricted earth fault current supervi-
sion monitors Idiff0 and checks its value to be less than a threshold. An
alarm report is generated as “HV REF 3I0 Alarm”, “MV REF 3I0 Alarm” or
“LV REF 3I0 Alarm”, after the preset time of “HV T_REF Alarm”, “MV
T_REF Alarm” or “LV T_REF Alarm”, if the differential current exceeds
the threshold value “HV 3I0_REF”, “MV 3I0_REF” or “LV 3I0_REF”. The
alarm is an indication of miss-connection in phase or starpoint CT sec-
ondary windings, and therefore is released to remind user to detect the
faulty connection in secondary circuit and remove it. The function can be
enabled or disabled by using setting “HV Func_REF Alarm”, “MV
Func_REF Alarm” or “LV Func_REF Alarm”, (1-On, 0-Off). The setting
range of the threshold differential current to release restricted earth fault
current alarm is on [0.08-10A]. However, to avoid incorrect alarm indica-
tions, the threshold value is increased to 0.1A (in 1A nominal current in-
puts) and to 0.3A (in 5A nominal current inputs), if the set value is less
than 0.1A.

DANGER: Before Restricted Earth Fault protection is put into operation on

site, polarity of neutral current transformer for REF must have been

checked right by an energizing test of every side of the transformer or a


test of simulating an external fault of the side in primary system. Otherwise
a mal-operation may occur during an external earth fault.

82
Chapter 5 Restricted earth fault protection

4 Input and output signals

Restricted Earth
Fault Protection
IA1 REF Alarm

IB1 REF Trip

IC1 Relay Startup

IA2

IB2

IC2

IREF

Figure 40 Restricted earth fault protection module

Table 32 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker 1


IB1 Phase B current input of CT of circuit breaker 1
IC1 Phase C current input of CT of circuit breaker 1
IA2 Phase A current input of CT of circuit breaker 2
IB2 Phase B current input of CT of circuit breaker 2
IC2 Phase C current input of CT of circuit breaker 2
IREF Neutral point current for REF

Table 33 Binary output list

Signal Description

REF Alarm Restricted Earth Fault alarm


REF Trip Restricted Earth Fault trip
Relay Startup Relay Startup

83
Chapter 5 Restricted earth fault protection

5 Settings
Table 34 Settings of Restricted earth fault protection for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
Current setting for HV Restrict-
HV 3I0_REF A 0.08Ir 2Ir 2
ed Earth Fault protection
HV Slope setting for HV Restricted
0.2 0.95 0.5
Slope_REF Earth Fault protection
HV T_REF HV Restricted Earth Fault trip
s 0 60 0.03
Trip time setting
HV 3I0_REF HV Restricted Earth Fault alarm
A 0.08Ir 2Ir 2
Alarm current setting
HV T_REF HV Restricted Earth Fault alarm
s 0 60 0.03
Alarm time setting

Table 35 Control words of restricted earth fault protection for HV side of


transformer

De-
Setting Unit Min. Max. fault Description
setting
HV Restricted earth fault trip-stage
HV Func_REF
0 1 0 ON
Trip
1-on; 0-off.
HV Restricted earth fault
HV Func_REF
0 1 0 Alarm-stage ON
Alarm
1-on; 0-off.
Block HV REF Block HV REF when CT failure,
0 1 0
at HV CT_Fail 1-Block;0-unblock

Table 36 Settings of Restricted earth fault protection for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
Current setting for MV Restrict-
MV 3I0_REF A 0.08Ir 2Ir 2
ed Earth Fault protection

84
Chapter 5 Restricted earth fault protection

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
MV Slope setting for MV Restricted
0.2 0.95 0.5
Slope_REF Earth Fault protection
MV T_REF MV Restricted Earth Fault trip
s 0 60 0.03
Trip time setting
MV 3I0_REF MV Restricted Earth Fault alarm
A 0.08Ir 2Ir 2
Alarm current setting
MV T_REF MV Restricted Earth Fault alarm
s 0 60 0.03
Alarm time setting

Table 37 Control words of restricted earth fault protection for MV side of


transformer

De-
Setting Unit Min. Max. fault Description
setting
MV Func_REF MV Restricted earth fault trip-stage
0 1 0
Trip ON 1-on; 0-off.
MV Restricted earth fault
MV Func_REF
0 1 0 Alarm-stage ON
Alarm
1-on; 0-off.
Block MV REF Block MV REF when CT failure,
0 1 0
at MV CT_Fail 1-Block;0-unblock

Table 38 Settings of restricted earth fault protection for LV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
Current setting for LV Restricted
LV 3I0_REF A 0.08Ir 2Ir 2
Earth Fault protection
Slope setting for LV Restricted
LV Slope_REF 0.2 0.95 0.5
Earth Fault protection
LV Restricted Earth Fault trip
LV T_REF Trip s 0 60 0.03
time setting
LV 3I0_REF LV Restricted Earth Fault alarm
A 0.08Ir 2Ir 2
Alarm current setting

85
Chapter 5 Restricted earth fault protection

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
LV T_REF LV Restricted Earth Fault alarm
s 0 60 0.03
Alarm time setting

Table 39 Control words of restricted earth fault protection for LV side of


transformer

De-
Setting Unit Min. Max. fault Description
setting
LV Func_REF LV Restricted earth fault trip-stage
0 1 0
Trip ON 1-on; 0-off.
LV Restricted earth fault
LV Func_REF
0 1 0 Alarm-stage ON
Alarm
1-on; 0-off.
Block LV REF at Block LV REF when CT failure,
0 1 0
LV CT_Fail 1-Block;0-unblock

6 Report
Table 40 Event report list

Information Description

HV REF Trip HV Restricted Earth fault (REF) protection trip

MV REF Trip MV Restricted Earth fault (REF) protection trip

LV REF Trip LV Restricted Earth fault (REF) protection trip

Table 41 Alarm report list

Information Description

HV REF 3I0 Alarm HV Restricted Earth fault (REF) protection trip

MV REF 3I0 Alarm MV Restricted Earth fault (REF) protection trip

LV REF 3I0 Alarm LV Restricted Earth fault (REF) protection trip

86
Chapter 5 Restricted earth fault protection

Table 42 Operation report list

Information Description

HV Func_REF On HV REF protection is switched ON (by CW)


HV Func_REF Off HV REF protection is switched OFF (by CW)
MV Func_REF On MV REF protection is switched ON (by CW)
MV Func_REF Off MV REF protection is switched OFF (by CW)
LV Func_REF On LV REF protection is switched ON (by CW)
LV Func_REF Off LV REF protection is switched OFF (by CW)

7 Technical data
Table 43 Restricted earth fault protection technical data

Item Rang or Value Tolerance


Differential current 0.08 Ir to 2.00 Ir ±3% setting or ±0.02Ir
Slope 0.2 to 0.95

0.00 to 60.00s, step 0.01s ≤ ±1% setting or +40ms, at 200%


Time delay
operating setting
Reset ratio Approx. 0.7, at tripping
Operating time ≤ 30ms, at 200% setting
Reset time approx. 40ms

87
Chapter 5 Restricted earth fault protection

88
Chapter 6 Overexcitation protection

Chapter 6 Overexcitation protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for
overexciation protection function.

89
Chapter 6 Overexcitation protection

1 Introduction
The overexcitation protection is used to detect impermissible overexcitation
conditions which can endanger power transformers. An increase in trans-
former flux beyond the rated values leads to saturation of the iron core and to
large eddy current losses which cause impermissible temperature rise in
transformer core.

2 Protection principle

2.1 Protection principle

The overexcitation condition may occur in power plant transformers when a


load center is disconnected from the system, and the voltage regulator does
not operate sufficiently fast to control the associated voltage rise. Similarly,
the overexcitation condition may occur as result of a decrease in frequency,
e.g. in island system. To protect the power transformer in such conditions, the
overexcitation protection function should pick up when the permissible limit of
flux is exceeded in the transformer core. To do so, the overexcitation protec-
tion function measures the voltage/frequency (U/f) ratio which is proportional
to the flux density B in transformer core, and puts it in relation to the nominal
flux density BN. The decision is then made based on the calculated ratio as is
shown in below equation.

B U f
N 
BN U N f N

Equation 39

Where N is the ratio of volt/hertz calculated by the device.

U and f are the measured voltage and frequency, and UN and fN are the rated
voltage and frequency (50Hz or 60Hz) of the device. While the rated fre-
quency is fixed to 50Hz or 60Hz in software, device is informed about rated
voltage by setting “Reference Voltage” which corresponds to nominal
phase-neutral voltage of the protected transformer when is transferred to
secondary value, using the turn ratio of voltage transformer. Thus, the use of

90
Chapter 6 Overexcitation protection

the overexcitation protection presumes that measured voltage is connected to


the device. Calculation of voltage/hertz ratio above is performed based on the
maximum voltage of the three phase-neutral or phase-phase voltages. Con-
trol word “V/F Voltage(0-VPP,1-VPN)” determines whether phase-to-phase
voltage or phase-neutral voltage should be used for overexcitation protection,
by setting “0-VPP” or “1-VPN”, respectively.

It should be mentioned that the overexcitation protection can operate properly,


only if frequency is in range of 0.5 - 1.3 times the rated frequency and voltage
is greater than 0.7 times the rated voltage. If frequency or voltage is out of the
specified range, an alarm report “U or F EXCEED” is generated by the device,
after a fixed time delay of 150ms, and the overexcitation protection is blocked.
The logic is shown in below figure.

V<0.7Un
O 150ms U or F EXCEED
R
f<0.5fn or
f>1.3fn

Figure 41 Condition for generating “U or F EXCEED” alarm

The overexcitation protection includes two definite characteristics (alarm and


trip) and one thermal characteristic. The latter characteristic provides an ap-
proximate replica of the temperature rise caused by overexcitation in the
protected object. The definite alarm stage can be enabled or disabled by us-
ing Control word “Func_Overexcit Alarm Def ” on. Similarly, the definite trip
stage can be enabled or disabled by using Control word “Func_Overexcit Trip
Def” on. Furthermore, the thermal characteristic can be set by Control word
“Func_Overexcit Trip Inv” on. It should be mentioned that the overexcitation
protection can be applied at HV, MV or LV side of the protected transformer.
However, it is not recommended to apply the function on the transformer side
with variable winding turns such as the transformer side with an installed tap
changer. To enable the protection on a given side, setting of “HV
Func_Overexcit” on, “MV Func_Overexcit” on and “LV Func_Overexcit” on
should be applied to corresponding Control words. However, these settings
should be applied to 1 only on one side at the same time. If any two of “HV
Func_Overexcit”, “MV Func_Overexcit” and “HV Func_Overexcit” are set to 1
at the same time, alarm report “Setting Err” will be given by the device.

All the three available stages of the overexcitation protection use


phase-to-phase voltage or phase-neutral voltage of the corresponding side in
their calculations, based on the setting applied at Control word “V/F Volt-
age(0-VPP,1-VPN)”.

91
Chapter 6 Overexcitation protection

If the definite alarm stage is enabled in one side, and the calculated volt/hertz
ration exceeds the threshold defined by setting “Func_Overexcit Alarm Def”,
an alarm report “Def V/F Alarm ” is generated by the device, after the time
delay “T_Definite Alarm” elapsed. The logic for the definite alarm stage of
overexcitation protection is shown in below figure when it is applied to HV
side. The logic is the same when the protection function is applied to other
sides.

HV Func_Overexcit on

A
N
Func_Overexcit Alarm Def on D

NU AB_ Hv, f   DEF Alarm V / F

NUBC_ Hv, f   DEF Alarm V / F


O
R

NUAC_ Hv, f   DEF Alarm V / F

A
V/F Voltage(0-VPP,1-VPN) on N
D

O HV T_REF Alarm
DEF V/F Alarm
R

A
N
NUA_ Hv , f   DEF Alarm V / F D

NUB_ Hv , f   DEF Alarm V / F O


R

NUC_Hv , f   DEF AlarmV / F

U or F EXCEED

Figure 42 Logic of the definite alarm stage for overexcitation protection

Similarly, if the definite trip stage is enabled in one side, and the calculated
volt/hertz ration exceeds the threshold defined by setting “V/F_Definite Trip”,
an event report “Def V/F Trip” is generated by the device, subsequent to the
expiration of time delay “T_Definite Trip”. Tripping Logic of the definite trip
stage of overexcitation protection is shown in below figure.

92
Chapter 6 Overexcitation protection

HV Func_Overexcit on

A
N
Func_Overexcit Trip Def on D

NUAB_ Hv , f   DEF Trip V / F


`

NUBC_ Hv , f   DEF Trip V / F O


R

N U AC _ Hv , f   DEF Trip V / F

A
V/F Voltage(0-VPP,1-VPN) on N
D

O T_Definite Trip
DEF V/F Trip
R

A
N
N U A_ Hv , f   DEF Trip V / F D

N U B _ Hv , f   DEF Trip V / F O
R

N UC _ Hv , f   DEF Trip V / F

U or F EXCEED

Figure 43 Tripping logic of the definite trip stage for overexcitation protection

If thermal characteristic is set to “1-on” in one of transformer sides, it uses the


measured voltage and frequency of the corresponding side (depending on the
setting applied at Control word “V/F Voltage (0-VPP,1-VPN)”), together with
ten points derived from the manufacturer data. The points correspond to the
desired tripping times for a given volt/hertz ratios. Intermediate values are
determined by performing linear interpolation by the device. The ratios range
from N=1.05 to N=1.50. They are entered into the device by settings
“T1_Inverse V/F=1.05”, “T2_Inverse V/F=1.10”, “T3_Inverse V/F=1.15”,
“T4_Inverse V/F=1.20”, “T5_Inverse V/F=1.25”, “T6_Inverse V/F=1.30”,
“T7_Inverse V/F=1.35”, “T8_Inverse V/F=1.40”, “T9_Inverse V/F=1.45” and

93
Chapter 6 Overexcitation protection

“T10_Inverse V/F=1.50”. The device uses these points to form an inverse


characteristic such as those shown in below figure.

u/f

1.50
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05

T10 T9 T8 T7 T6 T5 T4 T3 T2 T1 t(s)

Figure 44 Thermal overexcitation characteristic

As can be seen from the above figure, N=1.05 works as a pickup threshold for
thermal stage. The thermal replica is implemented in IED by a counter which
is incremented from 0% to 100%, as soon as the calculated voltage/hertz ra-
tio of exceeds the pickup threshold (N=1.05). If the counter reaches to 100%
corresponding to expiration of trip time delay according to the trip character-
istic, the event report “Inv V/F Trip” is given. The trip signal is cancelled as
soon as the calculated voltage/hertz ratio falls below the pickup threshold
(N=1.05). However, the counter is decremented to zero according to cool
down time of the transformer (the time by which the thermal replica counter
reaches from 100% to 0%). The cool down time is informed to the device by
setting “T_Cool Down”.

Tripping Logic of the inverse thermal trip stage of overexcitation protection is


shown in below figure.

94
Chapter 6 Overexcitation protection

HV Func_Overexcit on

A
N
Func_Overexcit Trip Inv on D

u/f
1.50
1.45
1.40
1.35

N (U AB HV , f ) 1.30
1.25
1.20
1.15
1.10
1.05

T10T9 T8 T7 T6 T5 T4 T3 T2 T1 t(s)

u/f
1.50
1.45 O
1.40
1.35 R
N (U BC  HV , f ) 1.30
1.25
1.20
1.15
1.10
1.05

T10T9 T8 T7 T6 T5 T4 T3 T2 T1 t(s)

u/f
1.50
1.45
1.40
1.35
N (U AC  HV , f ) 1.30
1.25
1.20
1.15
1.10
1.05

T10T9 T8 T7 T6 T5 T4 T3 T2 T1 t(s)
A
V/F Voltage(0-VPP,1-VPN) on N
D

O Inv V/F Trip


u/f R
5
1.
0
4
1.
45
1.
0
3
1.
N (U A HV , f ) 1.
1.2
3
5
0
2 A
1.5
0
1
1.
1.
1
5
0
N
1.
5
T10T9 T8 T7 T6 T5 T4 T3 T2 T1 t(s)
D

u/f
5
1.
0
4
1.
1.
1.
45
0
3 O
3
5
N (U B HV , f ) 1.
1.2
1.5
0
2 R
0
1
1.
1
5
1.
0
1.
5
T10T9 T8 T7 T6 T5 T4 T3 T2 T1 t(s)

u/f
5
1.
0
4
1.
45
1.
0
3
1.
3
5
N (U C  HV , f ) 1.
1.2
1.5
0
2

0
1
1.
1
5
1.
0
1.
5
T10T9 T8 T7 T6 T5 T4 T3 T2 T1 t(s)

U or F EXCEED

Figure 45 Tripping logic of the thermal trip stage for overexcitation protection

NOTE: If it is possible for a given transformers to operate continuously under


the condition of N=1.05, corresponding time delay setting (“T1_Inverse

95
Chapter 6 Overexcitation protection

V/F=1.05”) should be set to 9999s. The same approach can be taken when, for

example, it is permissible for a transformer to operate continuously under the

condition N=1.10, N=1.15 and so on. It means that the thermal characteristic is
compound of 10 points at most, and it maybe contains less than 10 points. The

thermal characteristic would be disabled if all the delay time settings are set to

9999s.

2.2 Voltage channel configuration

UA/B/C voltage input channel of 1st Analog input module (hereinafter is ref-
ered as AIM) is provided with the high accurate frequency measurement
hardware circuit. In order to offer the high performance overexcitation function
for HV, MV or LV side, the applied voltage input of HV side, MV side or LV
side must be connected with the UA/B/C voltage input channel of 1st Analog
input module (AIM1).

Only one of HV overexcitation, MV overexcitation or LV overexcitation func-


tions could be enabled for one transformer, so settings of “HV Voltage Chan
Sel” and “MV Voltage Chan Sel” under “Comm Para” submenu are used to
select the voltage channel.

For example of HV side; the setting “HV Voltage Chan Sel” can be set as 1, 2
and 3 which means voltage channels are connected to the corresponding
analog input module (see below table).

Table 44 Voltage channel selection setting

“Voltage Chan Sel” Voltage input channels, connected with external

volage inputs

1 UA/B/C voltage input channel of AIM1, which channels can

provide the frequency measurement hardware circuit.

2 UA/B/C voltage input channel of AIM2

3 UA/B/C voltage input channel of AIM3

If Control word “HV Func_Overexcit” is set 1 and “HV Voltage Chan Sel” is set
2 or 3 (not 1), alarm report “Setting Err” will be given by the device. If Control
word “MV Func_Overexcit” is set 1 and “MV Voltage Chan Sel” is set 2 or 3
(not 1), alarm report “Setting Err” will be given by the device. If “LV
Func_Overexcit”, anyone of “HV Voltage Chan Sel” and “MV Voltage Chan
Sel” is set 1, alarm report “Setting Err” will be given by the device.

96
Chapter 6 Overexcitation protection

3 Input and output signals

Overexcitation
Protection
UA Def V/F Alarm

UB Def V/F Trip

UC Inv V/F Trip

Relay Startup

Figure 46 Overexcitation protection module

Table 45 Analog input list

Signal Description

UA Phase A voltage input


UB Phase B voltage input
UC Phase C voltage input

Table 46 Binary output list

Signal Description

Overexcitation protection(V/F) alarm with


Def V/F Alarm
definite (DEF) time characteristic
Overexcitation protection(V/F) tripping (Trip)
Def V/F Trip
with definite (DEF) time characteristic
Overexcitation protection(V/F) tripping (Trip)
Inv V/F Trip
with inverse(IVR) time characteristic
Relay Startup Relay Startup

4 Settings

97
Chapter 6 Overexcitation protection

Table 47 Settings of overexcitation protection

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
Reference Volt- Nominal phase voltage in HV
V 40 130 57.3
age side
V/F_Definite
1 1.5 1.1 Alarming setting of volt/hertz
Alarm
Timer setting for volt/hertz
T_Definite Alarm s 0.1 9999 10
alarming stage
V/F_Definite Tripping setting of definite
1 1.5 1.2
Trip volt/hertz stage
Timer setting for definite
T_Definite Trip s 0.1 9999 1
volt/hertz stage
T1_Inverse Timer setting for
s 0.1 9999 10
V/F=1.05 volt/hertz=1.05
T2_Inverse Timer setting for
s 0.1 9999 90
V/F=1.10 volt/hertz=1.10
T3_Inverse Timer setting for
s 0.1 9999 80
V/F=1.15 volt/hertz=1.15
T4_Inverse Timer setting for
s 0.1 9999 70
V/F=1.20 volt/hertz=1.20
T5_Inverse Timer setting for
s 0.1 9999 60
V/F=1.25 volt/hertz=1.25
T6_Inverse Timer setting for
s 0.1 9999 50
V/F=1.30 volt/hertz=1.30
T7_Inverse Timer setting for
s 0.1 9999 45
V/F=1.35 volt/hertz=1.35
T8_Inverse Timer setting for
s 0.1 9999 40
V/F=1.40 volt/hertz=1.40
T9_Inverse Timer setting for
s 0.1 9999 35
V/F=1.45 volt/hertz=1.45
T10_Inverse Timer setting for
s 0.1 9999 30
V/F=1.50 volt/hertz=1.50
Cool down time delay for
T_Cool Down s 0.1 9999 25
overexcitation protection

98
Chapter 6 Overexcitation protection

Table 48 Control words of overexcitation protection

De-
fault
Setting Unit Min. Max. Description
set-
ting
HV Overexcitation (V/F) on
HV Func_Overexcit 0 1 0
1-on; 0-off.
MV Overexcitation (V/F) on
MV Func_Overexcit 0 1 0
1-on; 0-off.
LV Overexcitation (V/F) on
LV Func_Overexcit 0 1 0
1-on; 0-off.
Definite Overexcitation (V/F)
Func_Overexcit
0 1 0 Alarming on
Alarm Def
1-on; 0-off.
Definite (DEF)Overexcitation
Func_Overexcit Trip
0 1 0 (V/F) on
Def
1-on; 0-off.
Inverse (IVR)Overexcitation
Func_Overexcit Trip
0 1 0 (V/F) on
Inv
1-on; 0-off.
Overexcitation protection uses
V/F Volt- phase-to-phase voltage (VPP)
0 1 0
age(0-VPP,1-VPN) or phase-to-earth voltage (VPN)
0-VPP; 1-VPN.

5 Report
Table 49 Event report list

Information Description

Def V/F Trip Overexcitation protection(V/F) tripping (Trip) with definite (DEF)

Inv V/F Trip and inverse(IVR) time characteristic

Table 50 Alarm report list

Information Description

Def V/F Alarm Overexcitation alarm

99
Chapter 6 Overexcitation protection

Information Description

Voltage or frequency is out of the permissible range


V or F Exceed
(25-65Hertz, >0.7 Un)

Table 51 Operation report list

Information Description

Func_Overexc On Overexcitation protection is switched ON (by CW)


Func_Overexc Off Overexcitation protection is switched OFF (by CW)

6 Technical data
Table 52 Overexcitation protection technical data

Item Rang or Value Tolerance


Reference voltage UN 40 to 130V, ≤ ±3 % setting or ±1 V
Inverse time characteristic
Ratio: 1.00 to 1.50 ≤ ±2.5% of the setting or 0.01
Time delay 0.1s to 9999s ≤±5% setting or ±70ms
Pair of Values for characteristic 1.05 /1.10 /1.15 /1.20 /1.25 /1.30
≤±5% setting or ± 70ms
of V/f /1.35 /1.40 /1.45 /1.50
Reset time, Approx. 70ms
Reset ratio ≥0.96
Definite time characteristic
≤±5% setting or ±70ms, at 200%
Time delay T 0.1s to 9999s
operating setting
Reset time, Approx. 70ms
Reset ratio ≥0.96

100
Chapter 7 Overcurrent protection

Chapter 7 Overcurrent protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for overcurrent
protection function.

101
Chapter 7 Overcurrent protection

1 Introduction
The non-directional overcurrent elements can be applied as backup protec-
tion functions for transformer as well as power system protection in networks
with radial nature and those which are supplied from a single source. The
directional overcurrent protection can also be applied in systems where pro-
tection coordination depends on both the magnitude of the fault current and
the direction of power flow to the fault location, for instance in case of par-
allel transformers supplied from a single source.

2 Protection principle

2.1 Protection Elements

Each voltage side of the protected transformer is provided with three over-
current protection elements from which two elements operate as definite
overcurrent stages and the other one operates with inverse time-current
characteristic. All the elements can operate in conjunction with the integrated
inrush restraint and directional functions.

Various stages of the elements are independent from each other and can be
combined as desired. They can be enabled or disabled in each side using
dedicated Control words. These Control words include “HV Func_OC1”, “HV
Func_OC2” and “HV Func_OC Inv”, for HV side overcurrent protection, “MV
Func_OC1”, “MV Func_OC2” and “MV Func_OC Inv”, for MV side overcur-
rent protection, “LV Func_OC1”, “LV Func_OC2” and “LV Func_OC Inv”, for
LV side overcurrent protection. For example by applying setting “1-on” to “HV
Func_OC1”, respective stage of overcurrent protection would be enabled in
HV side.

Individual pickup value for each definite stage can be defined by setting “HV
I_OC1” and “HV I_OC2” for HV side, “MV I_OC1” and “MV I_OC2” for MV
side, “LV I_OC1” and “LV I_OC2” for LV side. By applying these settings, each
phase current is compared separately with the setting value for each stage. If
the respective value is exceeded, a trip time delay timer is started. The con-
dition for start of the delay timer is expressed mathematically by below equa-
tion, in which a, b and c represent three phases.

I   I set   a, b, c
( )

Equation 40

The timer is set to count up to a user-defined time delay. The time delay can
be set for each definite stage individually through settings “HV T_OC1” and
“HV T_OC2” for HV side, “MV T_OC1” and “MV T_OC2” for MV side, “LV

102
Chapter 7 Overcurrent protection

T_OC1” and “LV T_OC2” for LV side. After the user-defined time delays have
been elapsed, a trip signal is issued if the inrush restraint feature is applied
and no inrush current is detected or if inrush restraint is disabled. However,
the overcurrent protection would be blocked and therefore, no tripping takes
place if the inrush restraint feature is enabled and an inrush condition exists.
Further, an alarm report is issued as “HV Inrush Blk BU”, “MV Inrush Blk BU”
or “LV Inrush Blk BU” indicating that a blocking condition is imposed to over-
current element by inrush condition detection.

The pickup value for the inverse time-current stage can be defined by setting
“HV I_OC Inv”, “MV I_OC Inv” and “LV I_OC Inv” for HV, MV and LV sides,
respectively. Each phase current is separately compared with corresponding
setting value. If a current exceeds 1.1 times the setting value, corresponding
stage picks up. If an inverse time-current stage picks up, the tripping time is
calculated from the actual fault current flowing, using the selected tripping
curve. Maximum tripping time is limited to 100s.

The time delay of time-inverse characteristic is calculated based on the type


of the characteristic, the magnitude of the current and a time multiplier. For
the time-inverse characteristic, both ANSI and IEC based standard curves are
available and any user-defined characteristic can be defined using the fol-
lowing equation:

 
 
 A _ OC Inv 
t  K _ OC Inv   P _ OC Inv
 B _ OC Inv 
 I  
  I S 
-1

 

Equation 41

Where I is the fault current;

Is is the current setting;

A_OC Inv: Time factor for inverse time stage

B_OC Inv: Time delay for inverse time stage

P_OC Inv: index for inverse time stage

K_OC Inv: Time multiplier Inrush restraint feature

(For detailed time inverse characteristic, refer to Appendix Time inverse


characteristic)

As mentioned previously, selection among the curves can be carried out by


settings “HV Func_OC Inv”, “MV Func_OC Inv” and “LV Func_OC Inv” for HV,
MV and LV sides, respectively. Furthermore, the time multiplier K_OC Inv can
be set by user to coordinate the integrated inverse time-current characteristic

103
Chapter 7 Overcurrent protection

of the device with other overcurrent relays installed for power system protec-
tion. This can be performed by settings “HV K_OC Inv”, “MV K_OC Inv” and
“LV K_OC Inv” in case of HV, MV and LV overcurrent elements, respectively.

By applying pickup current and time multiplier settings, the device calculates
the tripping time from the measured current in each phase separately, based
on the selected inverse curve. Once the calculated time has been elapsed, a
trip signal is issued provided that no inrush current is detected or inrush re-
straint is disabled. If the inrush restraint feature is enabled and an inrush
condition exists, the overcurrent protection would be blocked and therefore no
tripping takes place. However, an alarm report is generated as “HV Inrush Blk
BU”, “MV Inrush Blk BU” or “LV Inrush Blk BU”, indicating the blocking condi-
tion which is imposed to overcurrent element by detection of inrush condition.

The trip signals and corresponding event reports are available separately for
each stage. These include “HV OC1 Trip”, “HV OC2 Trip” and “HV OC Inv
Trip” for HV side, “MV OC1 Trip”, “MV OC2 Trip” and “MV OC Inv Trip” for MV
side, “LV OC1 Trip”, “LV OC2 Trip” and “LV OC Inv Trip” for LV side overcur-
rent elements.

2.2 Inrush Restraint Feature

The transformer overcurrent protection may detect large magnetizing inrush


currents flowing when transformer is energized. The inrush current may be
several times of the nominal current, and may last from several tens of milli-
seconds to several seconds. Inrush current comprises second harmonic as
well as considerable fundamental component. So it may affect the overcur-
rent protection which operates based on the fundamental component of the
measured current. Inrush blocking unit in overcurrent function is provided for
this purpose. It is possible to apply the inrush restraint feature separately to
each definite stage and inverse time-current stage of overcurrent element by
using Control words “HV OC1 Inrush Block”, “HV OC2 Inrush Block” and “HV
OC Inv Inrush Block” on for HV side, “MV OC1 Inrush Block”, “MV OC2 Inrush
Block” and “MV OC Inv Inrush Block” for MV side, “LV OC1 Inrush Block”, “LV
OC2 Inrush Block” and “LV OC Inv Inrush Block” for LV side. By applying set-
ting “1-on” to each of the mentioned Control words, no trip command would
be possible by corresponding stage, if an inrush condition is detected.

Since Inrush current contains a relatively large second harmonic component


which is nearly absent during a fault current, the inrush restraint feature op-
erates based on the evaluation of the second harmonic content which is
present in the measured current. The inrush condition is recognized if the ra-
tio of second harmonic current to fundamental component exceeds the set-
ting values “HV Ratio_I2/I1”, “MV Ratio_I2/I1” or “LV Ratio_I2/I1” in each
phase. The setting is applicable to both the definite stages of overcurrent
protection element as well as the inverse time-current stage for each voltage
side of the protected transformer. As soon as the measured ratio exceeds the
set threshold, a restraint is applied to those stages for which corresponding
setting is applied to make them blocked in inrush condition detection (“HV
OC1 Inrush Block”, “HV OC2 Inrush Block” and “HV OC Inv Inrush Block”
for HV side, “MV OC1 Inrush Block”, “MV OC2 Inrush Block” and “MV OC Inv
Inrush Block” for MV side, “LV OC1 Inrush Block”, “LV OC2 Inrush Block”

104
Chapter 7 Overcurrent protection

and “LV OC Inv Inrush Block” for LV side.).

Since the applied restraint by second harmonic detection operates individu-


ally per phase, the protection is fully operative even when the protected
transformer is switched onto a single-phase fault, whereas inrush currents
may possibly be present in one of the healthy phases. It is, however, possible
to set the protection in a way that when the second harmonic recognition is
fulfilled only in one single phase, not only the phase with the inrush current,
but also the remaining phases of the overcurrent protection are blocked. This
is achieved by cross-blocking the overcurrent protection for a certain period to
avoid spurious tripping. The setting corresponds to “HV T2h_Cross_Blk”, “MV
T2h_Cross_Blk”, “LV T2h_Cross_Blk”. Within this time, the overcurrent pro-
tection in all three phases is blocked as soon as an inrush current is detected
in any one phase. After the timer is expired, the overcurrent protection is
blocked only in the phase with inrush current content. To put it more simply,
cross blocking is reset if there is no more inrush in any phase, or the cross
blocking time interval is elapsed. It should be noted that inrush currents
flowing in the earth/ground path will not cross-block tripping by the phase
elements.

Furthermore, if the fundamental component of phase current exceeds the


upper limit value “HV Imax_2H_UnBlk”, “MV Imax_2H_UnBlk” or “LV
Imax_2H_UnBlk”, the inrush restraint will no longer be effective in respective
side, since a high-current fault is assumed in this case. The setting can be
applied for each overcurrent element in each side of the protected trans-
former.

2.3 Direction Determination Feature

The integrated directional function can be applied to each stage of overcur-


rent element via dedicated Control words. These Control words include “HV
OC1 Direction”, “HV OC2 Direction” and “HV OC Inv Direction” for HV side
overcurrent stages, “MV OC1 Direction”, “MV OC2 Direction” and “MV OC Inv
Direction” for MV side overcurrent stages and “LV OC1 Direction”, “LV OC2
Direction” and “LV OC Inv Direction” for LV side overcurrent stages. Fur-
thermore, the directional orientation can be set individually for each stage of
the overcurrent elements in various sides of the protected transformer. This
can be performed by using Control words “HV OC1 Dir To Sys, “HV OC2 Dir
To Sys” and “HV OC Inv Dir To Sys” for HV side, “MV OC1 Dir To Sys, “MV
OC2 Dir To Sys” and “MV OC Inv Dir To Sys” for MV side, “LV OC1 Dir To Sys,
“LV OC2 Dir To Sys” and “LV OC Inv Dir To Sys” for LV side. The possible
settings for these Control words comprise “0-toward transformer” and
“1-toward system”.

Basically, the direction determination is performed by determining the phase


angle between the fault current and a reference voltage. The direction of a
phase-directional element is detected by means of a cross-polarized voltage.
It means that the fault current of the corresponding phase is used together
with the healthy phase-to-phase voltage to determine direction of fault current.
This takes effect to all three phases. Below figure shows the assignment of
the measured values for the determination of fault direction for various types
of pickups in phase overcurrent elements.

105
Chapter 7 Overcurrent protection

NOTE: The direction mentioned above is based on that the positive polarity is
at the side of the busbar and the negative polarity is at the side the trans-
former.

Table 53 Voltage and current measurement used for direction determination

Phase Current Voltage

A Ia U bc

B Ib U ca

C Ic U ab

As can be seen, the healthy voltages are used in direction determination. This
allows for a correct direction determination even if the fault voltage has col-
lapsed entirely because of a single-phase short-line fault. With three-phase
short-line faults, memory voltage values are used to clearly determine the
direction if the measurement voltages are not sufficient. The directional ele-
ment of each side uses the voltage on itself side.

In a single-phase fault, the cross-polarized voltage (reference voltage) is 90°


out of phase with the fault voltage. With phase-to-phase faults, the position of
the reference voltage changes up to 30°, depending on the degree of collapse
in the fault voltages. In order to satisfy different network conditions and ap-
plications, the reference voltage can be rotated by an adjustable angle. For
each side of the protected transformer, the directional angle can be set in-
dependently. The settings include “HV Angle_OC”, “HV Angle_OC” and “LV
Angle_OC”, for HV, MV and LV sides, respectively.

Forward 90° IA

Bisector
Angle_Range
OC
Angle_OC

U BC_Ref

-IA

Figure 47 Overcurrent protection directional characteristic

where:

106
Chapter 7 Overcurrent protection

Angle_OC: The settable characteristic angle

Angle_Range OC: 85º

During direction decision by directional function, a VT Fail condition (a short


circuit or broken wire in the voltage transformer's secondary circuit or opera-
tion of the voltage transformer fuse) may result in false or undesired tripping
by directional overcurrent elements. In such a situation, it is possible to select
operation status of the directional overcurrent protection elements in each
side by using a number of control worlds to block the overcurrent protection
elements or keep them in operational state with no direction decision (block
direction decision). The corresponding Control words include “Block HV OC
at HV VT_FAIL”, “Block MV OC at MV VT_FAIL” and “Block LV OC at LV
VT_FAIL”, for HV, MV and LV sides, respectively. When the Control words are
set as 0 to select “HV OC1 Direction”, corresponding overcurrent protection
elements will not judge direction at the local side VT failure. When they set as
1 to select “Block OC at VT Fail”, no operation is possible by the overcurrent
protection elements. It is noted that the Control words affect all the stages of
corresponding overcurrent elements at each side. For instance, by applying
setting “0- HV OC1 Direction”, all the three stages of the overcurrent element
will remain operative without direction determination in case of any fault in
secondary circuit of HV side voltage transformer. On the other hand, setting
“1- Blk HV OC at HV VT_Fail” makes them blocked.

The logic for Definite and Inverse time IDMTL overcurrent protection is shown
in below figure.

HV Func_OC on

A O
DIR Positive N Direction Unit OK
R
D
VT failure
A
N
Direct OK at VT FAIL D
HV Func_OC1 (2) on
A
N HV T_OC1(2)
I>HV I_OC1 (2) OC 1 (2)Trip
D
Direction Unit OK

Inrush BLK OC Direction Unit


OK
HV Func_OC Inv on
A
t
N OC Inv Trip
Inverse Curve>
D
Direction Unit
OK
Inrush BLK OC

Figure 48 Tripping logic for overcurrent protection

107
Chapter 7 Overcurrent protection

2.4 CBF initiation Feature

It is possible to set whether the overcurrent protection elements can initiate


the integrated CBF protection or not. The available choices depend on the
voltage side of the power transformer at which overcurrent protection is ap-
plied. In this context, HV side overcurrent protection element always initiates
HV side CBF function with no additional setting. However, it is possible to
select whether it can initiate MV and LV CBF protection functions via Control
words “HV OC Initiate LV CBF” and “HV OC Initiate MV CBF”, respectively.

MV side overcurrent protection element always initiates MV side CBF function


with no additional setting. However, it is possible to select whether it can ini-
tiate HV side CBF protection function via Control word “MV OC Initiate HV1
CBF”.

LV side overcurrent protection element always initiates LV side CBF function


with no additional setting. However, it is possible to select whether it can ini-
tiate HV side CBF protection function via Control word “LV OC Initiate HV1
CBF”.

More detail information about the initiation conditions and related Control
words can be found as below.

108
Chapter 7 Overcurrent protection

3 Input and output signals

Overcurrent
Protection
IA1 OC1 Trip

IB1 OC2 Trip

IC1 OC Inv Trip

IA2 Relay Startup

IB2

IC2

UA

UB

UC

Figure 49 Overcurrent protection module

Table 54 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker 1


IB1 Phase B current input of CT of circuit breaker 1
IC1 Phase C current input of CT of circuit breaker 1
IA2 Phase A current input of CT of circuit breaker 2
IB2 Phase B current input of CT of circuit breaker 2
IC2 Phase C current input of CT of circuit breaker 2
UA Phase A voltage input
UB Phase B voltage input
UC Phase C voltage input

Table 55 Binary output list

Signal Description

OC1 Trip Overcurrent stage 1 trip


OC2 Trip Overcurrent stage 2 trip
OC Inv Trip Overcurrent inverse stage trip

109
Chapter 7 Overcurrent protection

Signal Description

Relay Startup Relay Startup

4 Setting
Table 56 Settings of overcurrent protection for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
HV overcurrent (O/C) current
HV I_OC1 A 0.05Ir 20Ir 5
setting for Stage 1
Time setting for HV OC, Stage
HV T_OC1 s 0 60 60
1
HV overcurrent (O/C) current
HV I_OC2 A 0.05Ir 20Ir 5
setting for Stage 2
Time setting for HV OC, Stage
HV T_OC2 s 0 60 60
2
HV
Curve_OC
1 12 1 Ref to IEC and ANSI Curves
Inv

HV I_OC Inv A 0.05Ir 20Ir 5 Ref to IEC and ANSI Curves

HV K_OC Inv 0.05 999 1 Ref to IEC and ANSI Curves

HV A_OC Inv s 0 200 0.14 Ref to IEC and ANSI Curves


HV B_OC Inv s 0 60 0 Ref to IEC and ANSI Curves

HV P_OC Inv 0 10 0.02 Ref to IEC and ANSI Curves


HV An- The angle setting for voltage
° 0 90 45
gle_OC ahead of current.
st
The maximum 1 -harmonic
HV
current setting to remove the
Imax_2H_Un A 0.25Ir 20Ir 5
inrush block, in HV O/C pro-
Blk
tection
nd
Inrush 2 harmonic ratio set-
HV Ra-
0.07 0.5 0.2 ting for blocking HV O/C pro-
tio_I2/I1
tection
HV s 0 60 20 Inrush 2nd harmonic

110
Chapter 7 Overcurrent protection

T2h_Cross_B cross-block time for HV O/C


lk protection

Table 57 Control words of overcurrent protection for HV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
HV Func_OC1 The 1st stage of HV OC (OC_1)
0 1 0 protection is switched ON
1-on; 0-off.
HV OC1 Direc- Direction (DIR) detection of HV OC
tion 0 1 0 Stage 1 is switched ON
1-on; 0-off.
HV OC1 Dir To Direction unit of HV OC Stage 1
Sys points to system
0 1 0
0 - point to the protected transformer
1- point to system
HV OC1 Inrush Inrush 2nd harmonic detection HV
Block 0 1 0 OC Stage 1 is switched ON
1-on; 0-off.
HV Func_OC2 The 2nd stage of HV OC (OC_2)
0 1 0 protection is switched ON
1-on; 0-off.
HV OC2 Direc- Direction (DIR) detection of HV OC
tion 0 1 0 Stage 2 is switched ON
1-on; 0-off.
HV OC2 Dir To Direction unit of HV OC Stage 2
Sys points to system
0 1 0
0 - point to the protected transformer
1- point to system
HV OC2 Inrush Inrush 2nd harmonic detection HV
Block 0 1 0 OC Stage 2 is switched ON
1-on; 0-off.
HV Func_OC The IDMTL inverse time stage of HV
Inv 0 1 0 OC protection is switched ON
1-on; 0-off.
HV OC Inv Di- Direction (DIR) detection of HV OC
0 1 0
rection IDMTL inverse time is switched ON

111
Chapter 7 Overcurrent protection

1-on; 0-off.
HV OC Inv Dir Direction unit of HV OC IDMTL in-
To Sys verse time points to system
0 1 0
0 - point to the protected transformer
1- point to system
nd
HV OC Inv In- Inrush 2 harmonic detection HV
rush Block OC IDMTL inverse time is switched
0 1 0
ON
1-on; 0-off.
Block HV OC at Select to block HV OC protection or
HV VT_Fail exit direction unit, when HV VT fails
0 1 0
0- HV Direct OK at HV VT Fail
1- Blk HV OC at HV VT Fail
HV OC Initiate HV OC protection initiate LV side
LV CBF 0 1 0 CBF
0 - initiate, 1 – not initiate
HV OC Initiate HV OC protection initiate MV side
MV CBF 0 1 0 CBF
0 - initiate, 1 – not initiate

Table 58 Settings of overcurrent protection for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
MV overcurrent (O/C) current
MV I_OC1 A 0.05Ir 20Ir 5
setting for Stage 1
Time setting for MV OC, Stage
MV T_OC1 s 0 60 60
1
MV overcurrent (O/C) current
MV I_OC2 A 0.05Ir 20Ir 5
setting for Stage 2
Time setting for MV OC, Stage
MV T_OC2 s 0 60 60
2
MV
Curve_OC
1 12 1 Ref to IEC and ANSI Curves
Inv

MV I_OC Inv A 0.05Ir 20Ir 5 Ref to IEC and ANSI Curves


MV K_OC Inv 0.05 999 1 Ref to IEC and ANSI Curves

112
Chapter 7 Overcurrent protection

MV A_OC Inv s 0 200 0.14 Ref to IEC and ANSI Curves


MV B_OC Inv s 0 60 0 Ref to IEC and ANSI Curves

MV P_OC Inv 0 10 0.02 Ref to IEC and ANSI Curves


MV An- The angle setting for voltage
° 0 90 45
gle_OC ahead of current.
st
The maximum 1 -harmonic
MV
current setting to remove the
Imax_2H_Un A 0.25Ir 20Ir 5
inrush block, in MV O/C pro-
Blk
tection
Inrush 2nd harmonic ratio set-
MV Ra-
0.07 0.5 0.2 ting for blocking MV O/C pro-
tio_I2/I1
tection
nd
MV Inrush 2 harmonic
T2h_Cross_B s 0 60 20 cross-block time for MV O/C
lk protection

Table 59 Control words of overcurrent protection for MV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
MV Func_OC1 The 1st stage of MV OC (OC_1)
0 1 0 protection is switched ON
1-on; 0-off.
MV OC1 Direc- Direction (DIR) detection of MV OC
tion 0 1 0 Stage 1 is switched ON
1-on; 0-off.
MV OC1 Dir To Direction unit of MV OC Stage 1
Sys points to system
0 1 0
0 - point to the protected transformer
1- point to system
nd
MV OC1 Inrush Inrush 2 harmonic detection MV
Block 0 1 0 OC Stage 1 is switched ON
1-on; 0-off.
MV Func_OC2 The 2nd stage of MV OC (OC_2)
0 1 0 protection is switched ON
1-on; 0-off.
MV OC2 Direc- Direction (DIR) detection of MV OC
0 1 0
tion Stage 2 is switched ON

113
Chapter 7 Overcurrent protection

1-on; 0-off.
MV OC2 Dir To Direction unit of MV OC Stage 2
Sys points to system
0 1 0
0 - point to the protected transformer
1- point to system
nd
MV OC2 Inrush Inrush 2 harmonic detection MV
Block 0 1 0 OC Stage 2 is switched ON
1-on; 0-off.
MV Func_OC The IDMTL inverse time stage of MV
Inv 0 1 0 OC protection is switched ON
1-on; 0-off.
MV OC Inv Direction (DIR) detection of MV OC
Direction 0 1 0 IDMTL inverse time is switched ON
1-on; 0-off.
MV OC Inv Dir Direction unit of MV OC IDMTL in-
To Sys verse time points to system
0 1 0
0 - point to the protected transformer
1- point to system
MV OC Inv Inrush 2nd harmonic detection MV
Inrush Block OC IDMTL inverse time is switched
0 1 0
ON
1-on; 0-off.
Block MV OC Select to block MV OC protection or
at MV VT_Fail exit direction unit, when MV VT fails
0 1 0
0- MV Direct OK at MV VT Fail
1- Blk MV OC at MV VT Fail
MV OC Initiate MV OC protection initiate HV1 side
HV1 CBF 0 1 0 CBF
0 - initiate, 1 – not initiate

Table 60 Settings of overcurrent protection for LV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
LV overcurrent (O/C) current
LV I_OC1 A 0.05Ir 20Ir 5
setting for Stage 1
Time setting for LV OC, Stage
LV T_OC1 s 0 60 60
1

114
Chapter 7 Overcurrent protection

LV overcurrent (O/C) current


LV I_OC2 A 0.05Ir 20Ir 5
setting for Stage 2
Time setting for LV OC, Stage
LV T_OC2 s 0 60 60
2
MV
Curve_OC
1 12 1 Ref to IEC and ANSI Curves
Inv

LV I_OC Inv A 0.05Ir 20Ir 5 Ref to IEC and ANSI Curves

LV K_OC Inv 0.05 999 1 Ref to IEC and ANSI Curves


LV A_OC Inv s 0 200 0.14 Ref to IEC and ANSI Curves

LV B_OC Inv s 0 60 0 Ref to IEC and ANSI Curves


LV P_OC Inv 0 10 0.02 Ref to IEC and ANSI Curves
The angle setting for voltage
LV Angle_OC 0 90 45
ahead of current.
The maximum 1st -harmonic
LV
current setting to remove the
Imax_2H_Un 0.25Ir 20Ir 5
inrush block, in LV O/C protec-
Blk
tion
Inrush 2nd harmonic ratio set-
LV Ra-
0.07 0.5 0.2 ting for blocking LV O/C pro-
tio_I2/I1
tection
LV Inrush 2nd harmonic
T2h_Cross_B 0 60 20 cross-block time for LV O/C
lk protection

Table 61 Control words of overcurrent protection for LV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
LV Func_OC1 The 1st stage of LV OC (OC_1) pro-
0 1 0 tection is switched ON
1-on; 0-off.
LV OC1 Direc- Direction (DIR) detection of LV OC
tion 0 1 0 Stage 1 is switched ON
1-on; 0-off.
LV OC1 Dir To Direction unit of LV OC Stage 1
0 1 0
Sys points to system

115
Chapter 7 Overcurrent protection

0 - point to the protected transformer


1- point to system
nd
LV OC1 Inrush Inrush 2 harmonic detection LV
Block 0 1 0 OC Stage 1 is switched ON
1-on; 0-off.
LV Func_OC2 The 2nd stage of LV OC (OC_2)
0 1 0 protection is switched ON
1-on; 0-off.
LV OC2 Direc- Direction (DIR) detection of LV OC
tion 0 1 0 Stage 2 is switched ON
1-on; 0-off.
LV OC2 Dir To Direction unit of LV OC Stage 2
Sys points to system
0 1 0
0 - point to the protected transformer
1- point to system
LV OC2 Inrush Inrush 2nd harmonic detection LV
Block 0 1 0 OC Stage 2 is switched ON
1-on; 0-off.
LV Func_OC The IDMTL inverse time stage of LV
Inv 0 1 0 OC protection is switched ON
1-on; 0-off.
LV OC Inv Di- Direction (DIR) detection of LV OC
rection 0 1 0 IDMTL inverse time is switched ON
1-on; 0-off.
LV OC Inv Dir Direction unit of LV OC IDMTL in-
To Sys verse time points to system
0 1 0
0 - point to the protected transformer
1- point to system
nd
LV OC Inv In- Inrush 2 harmonic detection LV
rush Block OC IDMTL inverse time is switched
0 1 0
ON
1-on; 0-off.
Block LV OC at Select to block LV OC protection or
LV VT_Fail exit direction unit, when LV VT fails
0 1 0
0- LV Direct OK at LV VT Fail
1- Blk LV OC at LV VT Fail
LV OC Initiate LV OC protection initiate HV1 side
HV1 CBF 0 1 0 CBF
0 - initiate, 1 – not initiate

116
Chapter 7 Overcurrent protection

5 Report
Table 62 Event report list

Information Description

HV OC Inv Trip Inverse time stage of HV overcurrent protection trip


HV OC1 Trip HV overcurrent stage 1 trip
HV OC2 Trip HV overcurrent stage 2 trip
MV OC Inv Trip Inverse time stage of MV overcurrent protection trip
MV OC1 Trip MV overcurrent stage 1 trip
MV OC2 Trip MV overcurrent stage 2 trip
LV OC Inv Trip Inverse time stage of LV overcurrent protection trip
LV OC1 Trip LV overcurrent stage 1 trip
LV OC2 Trip LV overcurrent stage 2 trip

Table 63 Operation report list

Information Description

HV Func_OC On Overcurrent protection of HV side is switched ON (by CW)


HV Func_OC Off Overcurrent protection of HV side is switched OFF (by CW)
MV Func_OC On Overcurrent protection of MV side is switched ON (by CW)
MV Func_OC Off Overcurrent protection of MV side is switched OFF (by CW)
LV Func_OC On Overcurrent protection of LV side is switched ON (by CW)
LV Func_OC Off Overcurrent protection of LV side is switched OFF (by CW)

6 Technical data
Table 64 Overcurrent protection technical data

Item Rang or Value Tolerance


Definite time characteristics
Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
≤ ±1% setting or +40ms, at 200%
Time delay 0.00 to 60.00s, step 0.01s
operating setting
Reset time approx. 40ms
Reset ratio Approx. 0.95 at I/In ≥ 0.5
Inverse time characteristics

117
Chapter 7 Overcurrent protection

Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir


IEC standard Normal inverse; ≤ ±5% setting + 40ms, at 2
Very inverse; <I/ISETTING < 20, in accordance

Extremely inverse; with IEC60255-151

Long inverse
ANSI Inverse; ≤ ±5% setting + 40ms, at 2

Short inverse; <I/ISETTING < 20, in accord-

Long inverse; ance with ANSI/IEEE C37.112,

Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic ≤ ±5% setting + 40ms, at 2
T= <I/ISETTING < 20, in accordance
with IEC60255-151
Time factor of inverse time, A 0.005 to 200.0s, step 0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
Minimum operating time 20ms
Maximum operating time 100s
Reset mode instantaneous
Reset time approx. 40ms,
Directional element
Operating area range ≤ ±3°, at phase to phase volt-
Characteristic angle 0°to 90°, step 1° age >1V

118
Chapter 8 Earth fault protection

Chapter 8 Earth fault protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for earth fault
protection function.

119
Chapter 8 Earth fault protection

1 Protection principle

1.1 Protection elements

Each voltage side of the protected transformer is provided with three earth
fault protection elements from which two elements operate as definite earth
fault stages and the other one operates with inverse time-current characteris-
tic. All the elements can operate in conjunction with the integrated inrush re-
straint and directional functions.

Various stages of each element are independent from each other and can be
combined as desired. They can be enabled or disabled in each side using
dedicated Control words. These Control words include “HV Func_EF1”, “HV
Func_EF2” and “HV Func_EF Inv” on, for HV side earth fault protection, “MV
Func_EF1”, “MV Func_EF2” and “MV Func_EF Inv”, for MV side earth fault
protection, “LV Func_EF1”, “LV Func_EF2” and “LV Func_EF Inv”, for LV side
earth fault protection. For example by applying setting “1-on” to “HV
Func_EF1”, respective stage of earth fault protection would be enabled in HV
side.

Individual pickup value for each definite stage can be defined by setting “HV
3I0_EF1” and “HV 3I0_EF2” for HV side, “MV 3I0_EF1” and “MV 3I0_EF2” for
MV side, “LV 3I0_EF1” and “LV 3I0_EF2” for LV side. By applying these set-
tings, each earth current (quantity 3I0) calculated from the three phase cur-
rents is compared separately with the setting value for each stage. If the re-
spective value is exceeded, a trip time delay timer is started. The condition for
start of the delay timer is expressed mathematically:

3I 0  3I 0set

Equation 42

The timer is set to count up to a user-defined time delay. The time delay can
be set for each definite stage individually through settings “HV T_EF1” and
“HV T_EF2” for HV side, “MV T_EF1” and “MV T_EF2” for MV side, “LV
T_EF1” and “LV T_EF2” for LV side. After the user-defined time delay has
been elapsed, a trip signal is issued if the inrush restraint feature is applied
and no inrush current is detected or inrush restraint is disabled. The earth
fault protection would be blocked and therefore, no tripping takes place if the
inrush restraint feature is enabled and an inrush condition exists. However, an
alarm report is issued nominated as “HV EF1 Inrush Block”, “HV EF2 Inrush
Block” or “HV EF Inv Inrush Block”, indicating the blocking condition of earth
fault element caused by inrush condition detection.

Pickup value for the inverse time-current stage can be set by setting “HV
3I0_EF Inv”, “MV 3I0_EF Inv” and “LV 3I0_EF Inv” for HV, MV and LV sides,
respectively. Each earth current (quantity 3I0) calculated from the three phase
currents is separately compared with corresponding setting value. If a current

120
Chapter 8 Earth fault protection

exceeds 1.1 times the setting value, corresponding stage picks up. When an
inverse time-current stage picks up, the tripping time is calculated from the
calculated quantity 3I0, using the selected tripping curve. Maximum tripping
time is limited to 100s.

The time delay of time-inverse characteristic is calculated based on the type


of the characteristic, the magnitude of the current and a time multiplier. For
the time-inverse characteristic, both ANSI and IEC based standard curves are
available and any user-defined characteristic can be defined using the fol-
lowing equation:

 
 
 A _ EF Inv 
t  K _ EF Inv   HP _ EF Inv
 B _ EF Inv 
 I  
  I S 
-1

 

Equation 43

Where I is the calculated earth fault current;

Is is the current setting;

A_EF Inv: Time factor for inverse time stage

B_EF Inv: Time delay for inverse time stage

P_EF Inv: index for inverse time stage

K_EF Inv: Time multiplier

By applying the desired setting values, the device calculates the tripping time
from the zero sequence current. Once the calculated time elapsed, report “EF
Inv Trip” will be issued.

As mentioned previously, selection among the curves can be carried out by


settings “HV Curve_EF Inv”, “MV Curve_EF Inv” and “LV Curve_EF Inv” for
HV, MV and LV sides, respectively. Furthermore, the time multiplier K_EF Inv
can be applied by user to coordinate the integrated inverse time-current
characteristic of the device with other earth fault relays installed for power
system protection. This can be performed by settings “HV K_EF Inv”, “MV
K_EF Inv” and “LV K_EF Inv” in case of HV, MV and LV earth fault elements.

By applying pickup current and time multiplier settings, the device determines
the tripping time from the calculated earth current, based on the selected in-
verse curve. Once the calculated time has been elapsed, a trip signal is is-
sued provided that no inrush current is detected or inrush restraint is disabled.
If the inrush restraint feature is enabled and an inrush condition exists the
earth fault protection would be blocked and therefore no tripping takes place.
However, an alarm report is issued designated as “HV Inrush Blk BU”, “MV

121
Chapter 8 Earth fault protection

Inrush Blk BU” or “LV Inrush Blk BU”, indicating the blocking condition of
overcurrent element caused by inrush condition detection.

The trip signals and corresponding event reports are available separately for
each stage. They include “HV EF_1 Trip”, “HV EF_2 Trip” and “HV IDMTL EF
Trip” for HV side, “MV EF_1 Trip”, “MV EF_2 Trip” and “MV IDMTL EF Trip” for
MV side, “LV EF_1 Trip”, “LV EF_1 Trip” and “LV IDMTL EF Trip” for LV side
earth fault elements.

1.2 Inrush Restraint Feature

The transformer earth fault protection may detect large magnetizing inrush
currents flowing when transformer is energized. The inrush current may be
several times of the nominal current, and may last from several tens of milli-
seconds to several seconds.

Inrush current comprises second harmonic as well as a considerable funda-


mental component. So, it may affect earth fault protection which operates
based on the fundamental component of the measured current. Inrush
blocking unit in earth fault function is provided for this purpose.

It is possible to apply the inrush restraint feature separately to each definite


stage and inverse time-current stage of earth fault element by using Control
words “HV EF1 Inrush Block”, “HV EF2 Inrush Block” and “HV EF Inv Inrush
Block” for HV side, “MV EF1 Inrush Block”, “MV EF2 Inrush Block” and “MV
EF Inv Inrush Block” for MV side, “LV EF1 Inrush Block”, “LV EF2 Inrush
Block” and “LV EF Inv Inrush Block” on for LV side. By applying setting “1-on”
to each of the mentioned Control words, no trip command would be possible
by corresponding stage, if an inrush condition is detected.

Since the inrush current contains a relatively large second harmonic compo-
nent which is nearly absent during a fault current, the inrush restraint oper-
ates based on the evaluation of the second harmonic content which is present
in the phase currents. The inrush condition is recognized if the ratio of second
harmonic current to the fundamental component exceeds the setting value
“HV Ratio_I2/I1_EF”, “MV Ratio_I2/I1_EF” or “LV Ratio_I2/I1_EF” in each
phase current. The setting is applicable to both the definite stages of earth
fault protection element as well as the inverse time-current stage. As soon as
the measured ratio exceeds the set threshold, a restraint is applied to those
stages for which corresponding setting is applied to make them blocked in
inrush condition detection (“HV EF1 Inrush Block”, “HV EF2 Inrush Block” and
“HV EF Inv Inrush Block” on for HV side, “MV EF1 Inrush Block”, “MV EF2
Inrush Block” and “MV EF Inv Inrush Block” for MV side, “LV EF_1 Inrush
Detect ON”, “LV EF1 Inrush Block”, “LV EF2 Inrush Block” and “LV EF Inv
Inrush Block” for LV side).

Furthermore, if the fundamental component of each phase current exceeds


the upper limit value “HV Ratio_I2/I1”, “MV Ratio_I2/I1” or “LV Ratio_I2/I1”,
the inrush restraint will no longer effective in respective side, since a
high-current fault is assumed in this case.

122
Chapter 8 Earth fault protection

1.3 Direction Determination Feature

The integrated directional function can be applied to each stage of earth fault
elements via Control words. The Control words include “HV EF1 Direction”,
“HV EF2 Direction” and “HV EF Inv Direction” on for HV side earth fault
stages, “MV EF1 Direction”, “MV EF2 Direction” and “MV EF Inv Direction” for
MV side earth fault stages and “LV EF1 Direction”, “LV EF2 Direction” and “LV
EF Inv Direction” for LV side earth fault stages.

Furthermore, the directional orientation can be set individually for each stage
of earth fault elements in various sides of the protected transformer. This can
be performed by Control words “HV EF1 Dir To Sys”, “HV EF2 Dir To Sys” and
“HV EF Inv Dir To Sys” for HV side, “MV EF1 Dir To Sys”, “MV EF2 Dir To Sys”
and “MV EF Inv Dir To Sys” for MV side, “LV EF1 Dir To Sys”, “LV EF2 Dir To
Sys” and “LV EF Inv Dir To Sys” for LV side. The possible settings for these
Control word comprise “0-toward transformer” and “1-toward system”.

Basically, the direction determination is performed by comparing the zero


sequence system quantities. In the current path, 3I0 current is calculated from
the sum of the three phase currents. In the voltage path, the device calculates
the zero sequence voltage 3V0 from the sum of the three phase voltages.
Contrary to the directional phase elements, which work with the un-faulted
voltage as reference voltage, the fault voltage itself is the reference voltage
for the directional ground element. Depending on the connection of the volt-
age transformer, this is the voltage 3V0 or VN. The directional element at
each side operates with the residual/ neutral voltage of the same side.

In order to satisfy different network conditions and applications, the reference


voltage can be rotated by an adjustable angle. For each side of the protected
transformer, the directional angle can be set independently. The settings in-
clude “HV Angle_EF”, “MV Angle_EF” and “LV Angle_EF”, for HV, MV and LV
sides, respectively. It should be noted that the settings affect all the directional
stages of the corresponding earth fault element.

NOTE: The direction mentioned above is based on that the positive polarities of

three phases CT. The voltage used by directional element is calculated by

three phase voltage. Details are shown as below.

Below figure shows an example of direction determination for a fault in phase


A. As can be seen from the figure, fault current 3I0 lags from fault voltage Va.
Accordingly, fault current -3I0 lags residual sequence voltage 3U0 by this
angle. The reference voltage 3U0 is rotated to be as close as possible to -3I0
current. Furthermore, the forward area is depicted in the figure.

123
Chapter 8 Earth fault protection

90°
3I 0


3U 0_Ref
Angle_EF

Angle_Range
EF

Forward Bisector
-3 I 0

Figure 50 Characteristic of zero sequence directional element

where:

Angle_EF: The settable characteristic angle

Angle_Range EF: 80º

During direction decision by directional function, a VT Fail condition (a short


circuit or broken wire in the voltage transformer's secondary system or an
operation of the voltage transformer fuse) may result in false or undesired
tripping by directional earth fault elements. In such a situation, it is possible to
select operation status of the directional earth fault protection elements in
each side by using a number of Control words to block the earth fault protec-
tion elements or keep them in operational state with no direction decision
(block direction decision). The Control words are designated as “Block HV EF
at HV VT_Fail”, “Block MV EF at HV VT_Fail” and “Block LV EF at HV
VT_Fail”, for HV, MV and LV sides, respectively. When the Control words are
set as 0 to select “Direct OK at VT Fail”, corresponding earth fault protection
elements will not judge direction at the local side VT failure. When they set as
1 to select “Block EF at VT Fail”, no operation is possible by the earth fault
protection elements. It is noted that the Control words affect all the stages of
corresponding earth fault elements at each side. For instance, by applying
setting “Block HV EF at HV VT_Fail” off, all the three stages of the earth fault
element will remain operative without direction determination in case of any
fault in secondary circuit of HV side voltage transformer. On the other hand,
setting “Block HV EF at HV VT_Fail” on makes them blocked.

It is possible to block earth fault protection elements in each side of the pro-
tected transformer if a CT fail is detected in the same side. This can be per-
formed by Control words “Block HV EF at HV CT_Fail”, “Blk MV EF at MV
CT_FAIL” and “Blk LV EF at LV CT FAIL” in each voltage side. If setting 1 is
applied to these Control words, any CT fail detection in a given side of the
power transformer would bring blocking condition to all stages of the earth

124
Chapter 8 Earth fault protection

fault element which is applied in the same side.

The logic for definite and inverse time IDMTL earth fault protection is shown in
below figure.

HV EF Direction

A O
DIR Positive N R
E/F Direction Unit OK

VT failure D
A
Direct OK at VT FAIL N
D
HV Func_EF1 (2) on

A
HV T_EF1(2)
3I0>HV 3I0_EF1(2) N E/F Trip
D
Direction Unit OK

Inrush BLK EF
HV Func_EF1 (2) on

HV Func_EF Inv on

A
t
Inverse Curve> N IDMTL E/F Trip
D
E/F Direction OK

Inrush BLK EF

Figure 51 Tripping logic for earth fault protection

1.4 CBF initiation Feature

It is possible to set whether the earth fault protection elements can initiate the
integrated CBF protection or not. The available choices depend on the volt-
age side of the power transformer at which earth fault protection is applied. In
this context, HV side earth fault protection element always initiates HV side
CBF function with no additional setting. However, it is possible to select
whether it can initiate MV and LV CBF protection functions via Control words
“HV EF Initiate LV CBF” and “HV EF Initiate MV CBF” on, respectively.

MV side earth fault protection element always initiates MV side CBF function
with no additional setting. However, it is possible to select whether it can ini-
tiate HV side CBF protection function via Control word “MV EF Initiate HV1
CBF” on.

More detail information about the initiation conditions and related Control
words can be found in below table.

125
Chapter 8 Earth fault protection

2 Input and output signals

Earth Fault
Protection
IA1 EF1 Trip

IB1 EF2 Trip

IC1 EF Inv Trip

IA2 Relay Startup

IB2

IC2

UA

UB

UC

Figure 52 Earth fault protection module

Table 65 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker 1


IB1 Phase B current input of CT of circuit breaker 1
IC1 Phase C current input of CT of circuit breaker 1
IA2 Phase A current input of CT of circuit breaker 2
IB2 Phase B current input of CT of circuit breaker 2
IC2 Phase C current input of CT of circuit breaker 2
UA Phase A voltage input of VT of related winding of transformer
UB Phase B voltage input of VT of related winding of transformer
UC Phase C voltage input of VT of related winding of transformer

Table 66 Binary output list

Signal Description

EF1 Trip Earth Fault stage 1 trip


EF2 Trip Earth Fault stage 2 trip
EF Inv Trip Earth Fault inverse stage trip

126
Chapter 8 Earth fault protection

Signal Description

Relay Startup Relay Startup

3 Setting
Table 67 Settings of earth fault protection for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
HV earth fault (E/F) protection
HV 3I0_EF1 A 0.05Ir 20Ir 5
current setting for Stage 1
HV T_EF1 s 0 60 60 Time setting for HV E/F, Stage 1
HV earth fault (E/F) current set-
HV 3I0_EF2 A 0.05Ir 20Ir 5
ting for Stage 2
HV T_EF2 s 0 60 60 Time setting for HV E/F, Stage 2
HV
Curve_EF 1 12 1 Ref to IEC and ANSI Curves
Inv
HV 3I0_EF
A 0.05Ir 20Ir 1.2 Ref to IEC and ANSI Curves
Inv
HV K_EF
0.05 999 1 Ref to IEC and ANSI Curves
Inv
HV A_EF
s 0 200 0.14 Ref to IEC and ANSI Curves
Inv
HV B_EF
s 0 60 0 Ref to IEC and ANSI Curves
Inv
HV P_EF
0 10 0.02 Ref to IEC and ANSI Curves
Inv
HV An- The angle setting for voltage
° 0 90 45
gle_EF ahead of current.
HV The maximum 1st -harmonic cur-
Imax_2H_U A 0.25Ir 20Ir 5 rent setting to remove the inrush
nBlk_EF block, in HV EF protection
The maximum 1st -harmonic cur-
HV Ra-
0.07 0.5 0.2 rent setting to remove the inrush
tio_I2/I1_EF
block, in HV EF protection

127
Chapter 8 Earth fault protection

Table 68 Control words of earth fault protection for HV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
The 1st stage of HV earth fault
HV Func_EF1 0 1 0 (EF_1) protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV EF
HV EF1 Direction 0 1 0 Stage 1 is switched ON
1-on; 0-off.
Direction unit of HV EF Stage 1
HV EF1 Dir To points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection HV
HV EF1 Inrush
0 1 0 EF Stage 1 is switched ON
Block
1-on; 0-off.
The 2nd stage of HV earth fault
HV Func_EF2 0 1 0 (EF_2) protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV EF
HV EF2 Direction 0 1 0 Stage 2 is switched ON
1-on; 0-off.
Direction unit of HV EF Stage 2
HV EF2 Dir To points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system
nd
Inrush 2 harmonic detection HV
HV EF2 Inrush
0 1 0 EF Stage 2 is switched ON
Block
1-on; 0-off.
The IDMTL inverse time stage of HV
HV Func_EF Inv 0 1 0 EF protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV EF
HV EF Inv Direc-
0 1 0 IDMTL inverse time is switched ON
tion
1-on; 0-off.
HV EF Inv Dir To Direction unit of HV EF IDMTL in-
0 1 0
Sys verse time points to system

128
Chapter 8 Earth fault protection

0 - point to the protected transformer


1- point to system
nd
Inrush 2 harmonic detection HV
HV EF Inv Inrush EF IDMTL inverse time is switched
0 1 0
Block ON
1-on; 0-off.
Select to block HV EF protection or
Block HV EF at exit direction unit, when HV VT fails
0 1 0
HV VT_Fail 0 - HV Direct OK at HV VT Fail
1 - Blk HV EF at HV VT Fail
Block HV EF when there is HV CT
Block HV EF at
0 1 0 failure
HV CT_Fail
1-Block; 0-NOT block
HV EF protection initiate LV side
HV EF Initiate LV
0 1 0 CBF
CBF
0 - initiate, 1 – not initiate
HV EF protection initiate MV side
HV EF Initiate
0 1 0 CBF
MV CBF
0 - initiate, 1 – not initiate

Table 69 Settings of earth fault protection for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
MV MV earth fault (E/F) protection
A 0.05Ir 20Ir 5
3I0_EF1 current setting for Stage 1
MV T_EF1 s 0 60 60 Time setting for MV E/F, Stage 1
MV MV earth fault (E/F) current set-
A 0.05Ir 20Ir 5
3I0_EF2 ting for Stage 2
MV T_EF2 s 0 60 60 Time setting for MV E/F, Stage 2
MV
Curve_EF 1 12 1 Ref to IEC and ANSI Curves
Inv
MV 3I0_EF
A 0.05Ir 20Ir 5 Ref to IEC and ANSI Curves
Inv
MV K_EF
0.05 999 1 Ref to IEC and ANSI Curves
Inv
MV A_EF
s 0 200 0.14 Ref to IEC and ANSI Curves
Inv

129
Chapter 8 Earth fault protection

MV B_EF
s 0 60 0 Ref to IEC and ANSI Curves
Inv
MV P_EF
0 10 0.02 Ref to IEC and ANSI Curves
Inv
MV An- The angle setting for voltage
° 0 90 45
gle_EF ahead of current.
MV The maximum 1st -harmonic cur-
Imax_2H_U A 0.25Ir 20Ir 5 rent setting to remove the inrush
nBlk_EF block, in MV E/F protection
MV Ra- Inrush 2nd harmonic ratio setting
0.07 0.5 0.2
tio_I2/I1_EF for blocking MV E/F protection

Table 70 Control words of earth fault protection for MV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
The 1st stage of MV earth fault
MV Func_EF1 0 1 0 (EF_1) protection is switched ON
1-on; 0-off.
Direction (DIR) detection of MV EF
MV EF1 Direction 0 1 0 Stage 1 is switched ON
1-on; 0-off.
Direction unit of MV EF Stage 1
MV EF1 Dir To points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system
nd
Inrush 2 harmonic detection MV
MV EF1 Inrush
0 1 0 EF Stage 1 is switched ON
Block
1-on; 0-off.
nd
The 2 stage of MV earth fault
MV Func_EF2 0 1 0 (EF_2) protection is switched ON
1-on; 0-off.
Direction (DIR) detection of MV EF
MV EF2 Direction 0 1 0 Stage 2 is switched ON
1-on; 0-off.
Direction unit of MV EF Stage 2
MV EF2 Dir To points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system

130
Chapter 8 Earth fault protection

nd
Inrush 2 harmonic detection MV
MV EF2 Inrush
0 1 0 EF Stage 2 is switched ON
Block
1-on; 0-off.
The IDMTL inverse time stage of MV
MV Func_EF Inv 0 1 0 EF protection is switched ON
1-on; 0-off.
Direction (DIR) detection of MV EF
MV EF Inv Direc-
0 1 0 IDMTL inverse time is switched ON
tion
1-on; 0-off.
Direction unit of MV EF IDMTL in-
MV EF Inv Dir To verse time points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system
nd
Inrush 2 harmonic detection MV
MV EF Inv Inrush EF IDMTL inverse time is switched
0 1 0
Block ON
1-on; 0-off.
Select to block MV EF protection or
Block MV EF at exit direction unit, when MV VT fails
0 1 0
MV VT_Fail 0 - MV Direct OK at MV VT Fail
1 - Blk MV EF at MV VT Fail
Block MV EF when there is MV CT
Block MV EF at
0 1 0 failure
MV CT_Fail
1-Block; 0-NOT block
MV EF protection initiate HV1 side
MV EF Initiate
0 1 0 CBF
HV CBF
0 - initiate, 1 – not initiate

Table 71 Settings of earth fault protection for LV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
LV earth fault (E/F) protection
LV 3I0_EF1 A 0.05Ir 20Ir 5
current setting for Stage 1
LV T_EF1 s 0 60 60 Time setting for LV E/F, Stage 1
LV earth fault (E/F) current setting
LV 3I0_EF2 A 0.05Ir 20Ir 5
for Stage 2
LV T_EF2 s 0 60 60 Time setting for LV E/F, Stage 2

131
Chapter 8 Earth fault protection

LV
Curve_EF 1 12 1 Ref to IEC and ANSI Curves
Inv
LV 3I0_EF
A 0.05Ir 20Ir 5 Ref to IEC and ANSI Curves
Inv
LV K_EF Inv 0.05 999 1 Ref to IEC and ANSI Curves
LV A_EF Inv s 0 200 0.14 Ref to IEC and ANSI Curves

LV B_EF Inv s 0 60 0 Ref to IEC and ANSI Curves

LV P_EF Inv 0 10 0.02 Ref to IEC and ANSI Curves


LV An- The angle setting for voltage
° 0 90 45
gle_EF ahead of current.
st
LV The maximum 1 -harmonic cur-
Imax_2H_U A 0.25Ir 20Ir 5 rent setting to remove the inrush
nBlk_EF block, in LV E/F protection
LV Ra- Inrush 2nd harmonic ratio setting
0.07 0.5 0.2
tio_I2/I1_EF for blocking LV E/F protection

Table 72 Control words of earth fault protection for LV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
The 1st stage of LV earth fault
LV Func_EF1 0 1 0 (EF_1) protection is switched ON
1-on; 0-off.
Direction (DIR) detection of LV EF
LV EF1 Direction 0 1 0 Stage 1 is switched ON
1-on; 0-off.
Direction unit of LV EF Stage 1
LV EF1 Dir To points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection LV EF
LV EF1 Inrush
0 1 0 Stage 1 is switched ON
Block
1-on; 0-off.
nd
The 2 stage of LV earth fault
LV Func_EF2 0 1 0 (EF_2) protection is switched ON
1-on; 0-off.

132
Chapter 8 Earth fault protection

Direction (DIR) detection of LV EF


LV EF2 Direction 0 1 0 Stage 2 is switched ON
1-on; 0-off.
Direction unit of LV EF Stage 2
LV EF2 Dir To points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system
nd
Inrush 2 harmonic detection LV EF
LV EF2 Inrush
0 1 0 Stage 2 is switched ON
Block
1-on; 0-off.
The IDMTL inverse time stage of LV
LV Func_EF Inv 0 1 0 EF protection is switched ON
1-on; 0-off.
Direction (DIR) detection of LV EF
LV EF Inv Direc-
0 1 0 IDMTL inverse time is switched ON
tion
1-on; 0-off.
Direction unit of LV EF IDMTL in-
LV EF Inv Dir To verse time points to system
0 1 0
Sys 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection LV EF
LV EF Inv Inrush
0 1 0 IDMTL inverse time is switched ON
Block
1-on; 0-off.
Select to block LV EF protection or
Block LV EF at exit direction unit, when LV VT fails
0 1 0
LV VT_Fail 0 - LV Direct OK at LV VT Fail
1 - Blk LV EF at LV VT Fail
Block LV EF when there is LV CT
Block LV EF at
0 1 0 failure
LV CT_Fail
1-Block; 0-NOT block
LV EF protection initiate HV1 side
LV EF Initiate HV
0 1 0 CBF
CBF
0 - initiate, 1 – not initiate

4 Report

133
Chapter 8 Earth fault protection

Table 73 Event report list

Information Description

HV EF Inv Trip Inverse time stage of HV earth fault protection trip


HV EF1 Trip HV earth fault stage 1 trip
HV EF2 Trip HV earth fault stage 2 trip
MV EF Inv Trip Inverse time stage of MV earth fault protection trip
MV EF1 Trip MV earth fault stage 1 trip
MV EF2 Trip MV earth fault stage 2 trip
LV EF Inv Trip Inverse time stage of LV earth fault protection trip
LV EF1 Trip LV earth fault stage 1 trip
LV EF2 Trip LV earth fault stage 2 trip

Table 74 Operation report list

Information Description

HV Func_EF On Earth fault protection of HV side is switched ON (by CW)


HV Func_EF Off Earth fault protection of HV side is switched OFF (by CW)
MV Func_EF On Earth fault protection of MV side is switched ON (by CW)
MV Func_EF Off Earth fault protection of MV side is switched OFF (by CW)
LV Func_EF On Earth fault protection of LV side is switched ON (by CW)
LV Func_EF Off Earth fault protection of LV side is switched OFF (by CW)

5 Technical data
Table 75 Earth fault protection technical data

Item Rang or value Tolerance


Definite time characteristic
Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
≤ ±1% setting or +40ms, at 200%
Time delay 0.00 to 60.00s, step 0.01s
operating setting
Reset time approx. 40ms
Reset ratio Approx. 0.95 at I/Ir ≥ 0.5
Inverse time characteristics
Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
IEC standard Normal inverse; IEC60255-151
≤ ±5% setting + 40ms, at 2

134
Chapter 8 Earth fault protection

Very inverse; <I/ISETTING < 20


Extremely inverse;
Long inverse
ANSI Inverse; ANSI/IEEE C37.112,

Short inverse; ≤ ±5% setting + 40ms, at 2

Long inverse; <I/ISETTING < 20

Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic IEC60255-151
T= ≤ ±5% setting + 40ms, at 2
<I/ISETTING < 20
Time factor of inverse time, A 0.005 to 200.0s, step
0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
Minimum operating time 20ms
Maximum operating time 100s
Reset mode instantaneous
Reset time approx. 40ms
Directional element
Operating area range of zero ≤ ±3°, at 3U0≥1V
sequence directional element
Characteristic angle 0°to 90°, step 1°
Operating area range of negative ≤ ±3°, at 3U2≥2V
sequence directional element
Characteristic angle 50°to 90°, step 1°

135
Chapter 8 Earth fault protection

136
Chapter 9 Neutral earth fault protection

Chapter 9 Neutral earth fault


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for neutral earth
fault protection function.

137
Chapter 9 Neutral earth fault protection

1 Protection principle
1.1 Protection Elements
Each voltage side of the protected transformer is provided with three neutral
earth fault protection elements from which two elements operate as definite
earth fault stages and the other one operates with inverse time-current char-
acteristic. All the elements can operate in conjunction with the integrated in-
rush restraint and directional functions.

Various stages of each element are independent from each other and can be
combined as desired. They can be enabled or disabled in each side using
dedicated Control words. These Control words include “HV Func_Neu OC1”,
“HV Func_Neu OC2” and “HV Func_Neu OC Inv”, for HV side earth fault
protection, “MV Func_Neu OC1”, “MV Func_Neu OC2” and “MV Func_Neu
OC Inv”, for MV side earth fault protection, “LV Func_Neu OC1”, “LV
Func_Neu OC2” and “LV Func_Neu OC Inv”, for LV side earth fault protection.
For example by applying setting “1-on” to “HV Func_Neu OC1”, respective
stage of neutral earth fault protection would be enabled in HV side.

Individual pickup value for each definite stage can be defined by setting “HV
3I0_Neutral OC1” and “HV 3I0_Neutral OC2” for HV side, “MV 3I0_Neutral
OC1” and “MV 3I0_Neutral OC2” for MV side, “LV 3I0_Neutral OC1” and “LV
3I0_Neutral OC2” for LV side. By applying these settings, each neutral current
(quantity IN) measured from the installed neutral CT is compared separately
with the setting value for each stage. If the respective value is exceeded, a
trip time delay timer is started. The condition for start of the delay timer is ex-
pressed mathematically:

I N  I N _ set

Equation 44

The timer is set to count up to a user-defined time delay. The time delay can
be set for each definite stage individually through settings “HV T_Neutral
OC1” and “HV T_Neutral OC2” for HV side, “MV T_Neutral OC1” and “MV
T_Neutral OC2” for MV side, “LV T_Neutral OC1” and “LV T_Neutral OC2”
for LV side. After the user-defined time delay has been elapsed, a trip signal is
issued if the inrush restraint feature is applied and no inrush current is de-
tected or inrush restraint is disabled. The neutral earth fault protection would
be blocked and therefore, no tripping takes place if the inrush restraint feature
is enabled and an inrush condition exists. However, an alarm report is issued
nominated as “HV Inrush Blk BU”, “MV Inrush Blk BU” or “LV Inrush Blk BU”,
indicating the blocking condition of neutral earth fault element caused by in-
rush condition detection.

Pickup value for the inverse time-current stage can be set by setting “HV
3I0_NOC Inv”, “MV 3I0_NOC Inv” and “LV 3I0_NOC Inv” for HV, MV and LV
sides, respectively. Each neutral current (quantity IN) measured by installed
neutral CT is separately compared with corresponding setting value. If a cur-
rent exceeds 1.1 times the setting value, corresponding stage picks up. When
an inverse time-current stage picks up, the tripping time is calculated from the

138
Chapter 9 Neutral earth fault protection

measured quantity IN, using the selected tripping curve. Maximum tripping
time is limited to 100s.

For Time-inverse characteristic, the pickup value can be defined by setting


“3I0_NOC Inv”. The measured zero sequence current is compared with cor-
responding setting value. If it exceeds the setting, related signal will be re-
ported and the tripping time is calculated according to the pre-defined char-
acteristic. The tripping curve can be set as IEC or ANSI standard curves or
any user-defined characteristic by following tripping time equation.

 
 
 A _ NOC Inv 
t  K _ NOC Inv   P _ NOC Inv
 B _ NOC Inv 
 I  
  I S 
-1

 

Equation 45

Where I is the calculated neutral current;

Is is the current setting;

where:
A_NOC Inv: Time factor for inverse time stage
B_ NOC Inv: Time delay for inverse time stage
P_ NOC Inv: index for inverse time stage
K_ NOC Inv: Time multiplier

As mentioned previously, selection between the curves can be carried out by


settings “HV Curve_NOC Inv”, “MV Curve_NOC Inv” and “LV Curve_NOC
Inv” for HV, MV and LV sides, respectively. Furthermore, the time multiplier
K_NOC Inv can be applied by user to coordinate the integrated inverse
time-current characteristic of the device with other relays installed for power
system protection. This can be performed by settings “HV K_NOC Inv”, “MV
K_NOC Inv” and “LV K_NOC Inv” in case of HV, MV and LV neutral earth fault
elements.

By applying pickup current and time multiplier settings, the device determines
the tripping time from the measured neutral current, based on the selected
inverse curve. Once the calculated time has been elapsed, a trip signal is
issued provided that no inrush current is detected or inrush restraint is disa-
bled. If the inrush restraint feature is enabled and an inrush condition exists,
the neutral earth fault protection would be blocked and therefore no tripping
takes place. However, alarm report of “HV Inrush Blk BU”, “MV Inrush Blk BU”
or “LV Inrush Blk BU” is issued, indicating the blocking condition of neutral
earth fault element caused by inrush condition detection.

The trip signals and corresponding event reports are available separately for
each stage. They include “HV Neu OC_1 Trip”, “HV Neu OC_2 Trip” and “HV
Neu OC IDMTL” for HV side, “MV Neu OC_1 Trip”, “MV Neu OC_2 Trip” and
“MV Neu OC IDMTL” for MV side, “LV Neu OC_1 Trip”, “LV Neu OC_1 Trip”
and “LV Neu OC IDMTL” for LV side neutral earth fault elements.

139
Chapter 9 Neutral earth fault protection

1.2 Inrush Restraint Feature


The transformer neutral earth fault protection may detect large magnetizing
inrush currents flowing when transformer is energized. The inrush current
may be several times of the nominal current, and may last from several tens
of milliseconds to several seconds.

Inrush current comprises second harmonic as well as a considerable funda-


mental component. So, it may affect neutral earth fault protection which op-
erates based on the fundamental component of the measured current. Inrush
blocking unit in neutral earth fault function is provided for this purpose.

It is possible to apply the inrush restraint feature separately to each definite


stage and inverse time-current stage of earth fault element by using Control
words “HV Neu OC1 Inrush Block”, “HV Neu OC2 Inrush Block” and “HV Neu
OC Inv Inrush Block” on for HV side, “MV Neu OC1 Inrush Block”, “MV Neu
OC2 Inrush Block” and “MV Neu OC Inv Inrush Block” on for MV side, “LV
Neu OC1 Inrush Block”, “LV Neu OC2 Inrush Block” and “LV Neu OC Inv In-
rush Block” on for LV side. By applying setting “1-on” to each of the men-
tioned Control words, no trip command would be possible by corresponding
stage, if an inrush condition is detected.

Since the inrush current contains a relatively large second harmonic compo-
nent which is nearly absent during a fault current, the inrush restraint oper-
ates based on the evaluation of the second harmonic content which is present
in the measured neutral current (quantity IN), or in the phase currents, based
on setting. The inrush condition is recognized if the ratio of second harmonic
current to the fundamental component exceeds the setting value “HV Ra-
tio_I2/I1_NOC”, “MV Ratio_I2/I1_NOC” or “LV Ratio_I2/I1_NOC” in the
measured neutral current. The setting is applicable to both the definite stages
of neutral earth fault protection element as well as the inverse time-current
stage. As soon as the measured ratio exceeds the set threshold, a restraint is
applied to those stages for which corresponding setting is applied to make
them blocked in inrush condition detection (“HV Neu OC1 Inrush Block”, “HV
Neu OC2 Inrush Block” and “HV Neu OC Inv Inrush Block” for HV side, “MV
Neu OC1 Inrush Block”, “MV Neu OC2 Inrush Block” and “MV Neu OC Inv
Inrush Block” for MV side, “LV Neu OC1 Inrush Block”, “LV Neu OC2 Inrush
Block” and “LV Neu OC Inv Inrush Block” for LV side).

Furthermore, if the fundamental component of the measured neutral current


exceeds the upper limit value “HV Imax_2H_UnBlk_NOC”, “MV
Imax_2H_UnBlk_NOC” or “LV Imax_2H_UnBlk_NOC”, the inrush restraint
will no longer effective in respective side, since a high-current fault is as-
sumed in this case.

1.3 Direction Determination Feature


The integrated directional function can be applied to each stage of neutral
earth fault elements via Control words. The Control words include “HV Neu
OC1 Direction”, “HV Neu OC2 Direction” and “HV Neu OC Inv Direction” on
for HV side earth fault stages, “MV Neu OC1 Direction”, “MV Neu OC2 Direc-
tion” and “MV Neu OC Inv Direction” for MV side earth fault stages and “LV
Neu OC1 Direction”, “LV Neu OC2 Direction” and “LV Neu OC Inv Direction”
for LV side earth fault stages.

140
Chapter 9 Neutral earth fault protection

Furthermore, the directional orientation can be set individually for each stage
of neutral earth fault elements in various sides of the protected transformer.
This can be performed by Control words “HV Neu OC1 Dir To Sys”, “HV Neu
OC2 Dir To Sys” and “HV Neu OC Inv Dir To Sys” for HV side, “MV Neu OC1
Dir To Sys”, “MV Neu OC2 Dir To Sys” and “MV Neu OC Inv Dir To Sys” for
MV side, “LV Neu OC1 Dir To Sys”, “LV Neu OC2 Dir To Sys” and “LV Neu OC
Inv Dir To Sys” for LV side. The possible settings for these Control word
comprise “0-toward transformer” and “1-toward system”.

Basically, the direction determination is performed by comparing the zero


sequence system quantities. In the current path, 3I0 current is measured from
the neutral CT installed at the transformer starpoint. In the voltage path, the
device calculates the zero sequence voltage 3V0 from the sum of the three
phase voltages. Contrary to the directional phase elements, which work with
the un-faulted voltage as reference voltage, in this application, the fault volt-
age itself is the reference voltage. Depending on the connection of the volt-
age transformer, this is the voltage 3V0 or VN. The directional element at
each side operates with the residual/ neutral voltage of the same side.

In order to satisfy different network conditions and applications, the reference


voltage can be rotated by an adjustable angle. For each side of the protected
transformer, the directional angle can be set independently. The settings in-
clude “HV Angle_NOC”, “MV Angle_NOC” and “LV Angle_NOC”, for HV, MV
and LV sides, respectively. It should be noted that the settings affect all the
directional stages of the corresponding neutral earth fault element.

90°
3I 0


3U 0_Ref
Angle_EF

Angle_Range
EF

Forward Bisector
-3 I 0

Figure 53 Neutral directional element characteristic

where:

Angle_OC: The settable characteristic angle

Angle_Range OC: 80º

During direction decision by directional function, a VT Fail condition (a short


circuit or broken wire in the voltage transformer's secondary system or an
operation of the voltage transformer fuse) may result in false or undesired

141
Chapter 9 Neutral earth fault protection

tripping by directional neutral earth fault elements. In such a situation, it is


possible to select operation status of the directional neutral earth fault pro-
tection elements in each side by using a number of Control words to block the
neutral earth fault protection elements or keep them in operational state with
no direction decision (block direction decision). The Control words are des-
ignated as “Block HV NOC at HV VT_Fail”, “Block MV NOC at HV VT_Fail”
and “Block LV NOC at HV VT_Fail”, for HV, MV and LV sides, respectively.
When the Control words are set as 0 to select “Direct OK at VT Fail”, corre-
sponding neutral earth fault protection elements will not judge direction at the
local side VT failure. When they set as 1 to select “Blk NEU OC at VT Fail”, no
operation is possible by the neutral earth fault protection elements. It is noted
that the Control words affect all the stages of corresponding neutral earth fault
elements at each side. For instance, by applying setting “Block HV NOC at
HV VT_Fail” off, all the three stages of the neutral earth fault element will
remain operative without direction determination in case of any fault in sec-
ondary circuit of HV side voltage transformer. On the other hand, setting
“Block HV NOC at HV VT_Fail” on makes them blocked.

The logic for definite and inverse time IDMTL neutral earth fault protection is
shown in below figure.

Func_Neu OC1( 2( on

And
Dir_Forward
Or NEF Direction Unit OK

VT failure

And
Direct OK at VT FAIL

Func_Neu OC1( 2( on

3I0 > 3I0_Neutral OC1( 2(


1)
t
NEF Direction Unit OK And Neutral EF Trip

Inrush BLK NEF

Func_Neu OC Inv on

3I0>3I0_NOC Inv

t
And NEF Inv Trip
NEF Direction Unit OK

Inrush BLK NOC


1) t: T_Neutral OC1(2)

Figure 54 Tripping logic for neutral earth fault protection

1.4 CBF initiation Feature


It is possible to set whether the neutral earth fault protection elements can in-
itiate the integrated CBF protection or not. The available choices depend on
the voltage side of the power transformer at which neutral earth fault protec-

142
Chapter 9 Neutral earth fault protection

tion is applied. In this context, HV side neutral earth fault protection element
always initiates HV side CBF function with no additional setting. However, it is
possible to select whether it can initiate MV and LV CBF protection functions
via Control words “HV Neu OC Init LV CBF” and “HV Neu OC Init MV CBF”,
respectively.

MV side neutral earth fault protection element always initiates MV side CBF
function with no additional setting.

2 Input and output signals

Neutral Earth
Fault Protection
INBK NEF1 Trip

UA NEF2 Trip

UB NEF Inv Trip

UC Relay Startup

Figure 55 Neutral earth fault protection module

Table 76 Analog output list

Signal Description

INBK Neutral current input of HV side, MV side, or LV side of transformer


UA Phase A voltage input of HV side, MV side, or LV side of transformer
UB Phase B voltage input of HV side, MV side, or LV side of transformer
UC Phase C voltage input of HV side, MV side, or LV side of transformer

Table 77 Binary output list

Signal Description

NOC1 Trip Neutral Earth Fault stage 1 trip


NOC2 Trip Neutral Earth Fault stage 2 trip
NOC Inv Trip Neutral Earth Fault inverse stage trip
Relay Startup Relay Startup

3 Setting

143
Chapter 9 Neutral earth fault protection

Table 78 Settings of neutral earth fault protection for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
HV neutral over-current (NOC)
c A 0.05Ir 20Ir 5 protection current setting for Stage
1
HV Time setting for HV NOC, Stage
T_Neutral s 0 60 60
1
OC1
HV HV neutral over-current (NOC)
3I0_Neutral A 0.05Ir 20Ir 5 protection current setting for Stage
OC2 2
HV Time setting for HV NOC, Stage
T_Neutral s 0 60 60
1
OC2
HV
Curve_NOC 1 12 1 Ref to IEC and ANSI Curves
Inv
HV 3I0_NOC
A 0.05Ir 20Ir 5 Ref to IEC and ANSI Curves
Inv

HV K_NOC
0.05 999 1 Ref to IEC and ANSI Curves
Inv

HV A_NOC
s 0 200 0.14 Ref to IEC and ANSI Curves
Inv

HV B_NOC
s 0 60 0 Ref to IEC and ANSI Curves
Inv

HV P_NOC Ref to IEC and ANSI Curves


0 10 0.02
Inv

HV An- The angle setting for voltage


° 0 90 45
gle_NOC ahead of current.
The maximum 1st -harmonic
HV current setting to remove the
Imax_2H_Un A 0.25Ir 20Ir 5
inrush block, in HV NOC pro-
Blk_NOC
tection
HV Ra- nd
Inrush 2 harmonic ratio setting
tio_I2/I1_NO 0.07 0.5 0.2
for blocking HV NOC protection
C

Table 79 Control words of neutral earth fault protection for HV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
HV Func_Neu The 1st stage of HV neutral OC
0 1 0
OC1 (OC_1) protection is switched

144
Chapter 9 Neutral earth fault protection

ON
1-on; 0-off.
Direction (DIR) detection of HV
HV Neu OC1 Di- neutral OC Stage 1 is switched
0 1 0
rection ON
1-on; 0-off.
Direction unit of HV neutral OC
Stage 1 points to system
HV Neu OC1 Dir 0 1 0 0 - point to the protected trans-
To Sys
former
1- point to system
Inrush 2nd harmonic detection
HV Neu OC1 In- HV neutral OC Stage 1 is
0 1 0
rush Block switched ON
1-on; 0-off.
The 2nd stage of HV neutral OC
HV Func_Neu (OC_2) protection is switched
0 1 0
OC2 ON
1-on; 0-off.
Direction (DIR) detection of HV
HV Neu OC2 Di- neutral OC Stage 2 is switched
0 1 0
rection ON
1-on; 0-off.
Direction unit of HV neutral OC
Stage 2 points to system
HV Neu OC2 Dir 0 1 0 0 - point to the protected trans-
To Sys
former
1- point to system
Inrush 2nd harmonic detection
HV Neu OC2 In- HV neutral OC Stage 2 is
0 1 0
rush Block switched ON
1-on; 0-off.
The IDMTL inverse time stage
HV Func_Neu OC of HV neutral OC protection is
0 1 0
Inv switched ON
1-on; 0-off.
Direction (DIR) detection of HV
HV Neu OC Inv neutral OC IDMTL inverse time
0 1 0
Direction stage is switched ON
1-on; 0-off.
Direction unit of HV neutral OC
IDMTL inverse time stage points
HV Neu OC Inv Dir to system
0 1 0
To Sys 0 - point to the protected trans-
former
1- point to system
Inrush 2nd harmonic detection
HV Neu OC Inv 0 1 0 HV neutral OC IDMTL inverse
Inrush Block
time stage is switched ON

145
Chapter 9 Neutral earth fault protection

1-on; 0-off.
Select to block HV neutral OC
Block HV NOC at protection or exit direction unit,
0 1 0 when HV VT fails
HV VT_Fail 0 - HV Direct OK at HV VT Fail
1 - Blk HV NOC at HV VT Fail
HV neutral OC protection initi-
HV Neu OC Init 0 1 0 ate LV side CBF
MV CBF
0 - initiate, 1 – not initiate

Table 80 Settings of neutral earth fault protection for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
MV MV neutral over-current (NOC)
3I0_Neutral A 0.05Ir 20Ir 5 protection current setting for
OC1 Stage 1
MV Time setting for MV NOC, Stage
T_Neutral s 0 60 60
1
OC1
MV MV neutral over-current (NOC)
3I0_Neutral A 0.05Ir 20Ir 5 protection current setting for
OC2 Stage 2
MV Time setting for MV NOC, Stage
T_Neutral s 0 60 60
1
OC2
MV
Curve_NOC 1 12 1 Ref to IEC and ANSI Curves
Inv
MV Ref to IEC and ANSI Curves
A 0.05Ir 20Ir 5
3I0_NOC Inv

MV K_NOC
0.05 999 1 Ref to IEC and ANSI Curves
Inv

MV A_NOC Ref to IEC and ANSI Curves


s 0 200 0.14
Inv

MV B_NOC
s 0 60 0 Ref to IEC and ANSI Curves
Inv

MV P_NOC
0 10 0.02 Ref to IEC and ANSI Curves
Inv

MV An- The angle setting for voltage


° 0 90 45
gle_NOC ahead of current.
The maximum 1st -harmonic
MV current setting to remove the
Imax_2H_Un A 0.25Ir 20Ir 5
inrush block, in MV NOC pro-
Blk_NOC
tection
MV Ra- Inrush 2nd harmonic ratio setting
tio_I2/I1_NO 0.07 0.5 0.2
for blocking MV NOC protection
C

146
Chapter 9 Neutral earth fault protection

Table 81 Control words of neutral earth fault protection for MV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
The 1st stage of MV neutral OC
MV Func_Neu 0 1 0
(OC_1) protection is switched
OC1 ON
1-on; 0-off.
Direction (DIR) detection of MV
MV Neu OC1 Di- neutral OC Stage 1 is switched
0 1 0
rection ON
1-on; 0-off.
Direction unit of MV neutral OC
Stage 1 points to system
MV Neu OC1 Dir 0 1 0 0 - point to the protected trans-
To Sys
former
1- point to system
Inrush 2nd harmonic detection
MV Neu OC1 In- MV neutral OC Stage 1 is
0 1 0
rush Block switched ON
1-on; 0-off.
The 2nd stage of MV neutral OC
MV Func_Neu 0 1 0
(OC_2) protection is switched
OC2 ON
1-on; 0-off.
Direction (DIR) detection of MV
MV Neu OC2 Di- neutral OC Stage 2 is switched
0 1 0
rection ON
1-on; 0-off.
Direction unit of MV neutral OC
Stage 2 points to system
MV Neu OC2 Dir 0 1 0 0 - point to the protected trans-
To Sys
former
1- point to system
Inrush 2nd harmonic detection
MV Neu OC2 In- MV neutral OC Stage 2 is
0 1 0
rush Block switched ON
1-on; 0-off.
The IDMTL inverse time stage
MV Func_Neu OC of MV neutral OC protection is
0 1 0
Inv switched ON
1-on; 0-off.
Direction (DIR) detection of MV
MV Neu OC Inv neutral OC IDMTL inverse time
0 1 0
Direction stage is switched ON
1-on; 0-off.
MV Neu OC Inv Direction unit of MV neutral OC
0 1 0
Dir To Sys IDMTL inverse time stage points

147
Chapter 9 Neutral earth fault protection

to system
0 - point to the protected trans-
former
1- point to system
Inrush 2nd harmonic detection
MV Neu OC Inv MV neutral OC IDMTL inverse
0 1 0
Inrush Block time stage is switched ON
1-on; 0-off.
Select to block MV neutral OC
protection or exit direction unit,
Block MV NOC at 0 1 0 when MV VT fails
MV VT_Fail 0 - MV Direct OK at MV VT Fail
1 - Blk MV NOC at MV VT Fail
MV neutral OC protection initi-
MV Neu OC Init 0 1 0 ate LV side CBF
MV CBF
0 - initiate, 1 – not initiate

Table 82 Settings of neutral earth fault protection for LV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
LV LV neutral over-current (NOC)
3I0_Neutral A 0.05Ir 20Ir 5 protection current setting for
OC1 Stage 1
LV T_Neutral
s 0 60 60 Time setting for LV NOC, Stage 1
OC1
LV LV neutral over-current (NOC)
3I0_Neutral A 0.05Ir 20Ir 5 protection current setting for
OC2 Stage 2
LV T_Neutral
s 0 60 60 Time setting for LV NOC, Stage 1
OC2
LV
Curve_NOC 1 12 1 Ref to IEC and ANSI Curves
Inv
LV 3I0_NOC
A 0.05Ir 20Ir 5 Ref to IEC and ANSI Curves
Inv

LV K_NOC Ref to IEC and ANSI Curves


0.05 999 1
Inv

LV A_NOC
s 0 200 0.14 Ref to IEC and ANSI Curves
Inv

LV B_NOC
s 0 60 0 Ref to IEC and ANSI Curves
Inv

LV P_NOC
0 10 0.02 Ref to IEC and ANSI Curves
Inv

148
Chapter 9 Neutral earth fault protection

LV An- The angle setting for voltage


° 0 90 45
gle_NOC ahead of current.
The maximum 1st -harmonic
LV current setting to remove the
Imax_2H_Un A 0.25Ir 20Ir 5
inrush block, in LV NOC protec-
Blk_NOC
tion
LV Ra- Inrush 2nd harmonic ratio setting
tio_I2/I1_NO 0.07 0.5 0.2
for blocking LV NOC protection
C

Table 83 Control words of neutral earth fault protection for LV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
The 1st stage of LV neutral OC
(OC_1) protection is switched
LV Func_Neu OC1 0 1 0
ON
1-on; 0-off.
Direction (DIR) detection of LV
LV Neu OC1 Di- neutral OC Stage 1 is switched
0 1 0
rection ON
1-on; 0-off.
Direction unit of LV neutral OC
Stage 1 points to system
LV Neu OC1 Dir 0 1 0 0 - point to the protected trans-
To Sys
former
1- point to system
Inrush 2nd harmonic detection
LV Neu OC1 In- LV neutral OC Stage 1 is
0 1 0
rush Block switched ON
1-on; 0-off.
The 2nd stage of LV neutral OC
(OC_2) protection is switched
LV Func_Neu OC2 0 1 0
ON
1-on; 0-off.
Direction (DIR) detection of LV
LV Neu OC2 Di- neutral OC Stage 2 is switched
0 1 0
rection ON
1-on; 0-off.
Direction unit of LV neutral OC
Stage 2 points to system
LV Neu OC2 Dir 0 1 0 0 - point to the protected trans-
To Sys
former
1- point to system
Inrush 2nd harmonic detection
LV Neu OC2 In- LV neutral OC Stage 2 is
0 1 0
rush Block switched ON
1-on; 0-off.

149
Chapter 9 Neutral earth fault protection

The IDMTL inverse time stage


LV Func_Neu OC of LV neutral OC protection is
0 1 0
Inv switched ON
1-on; 0-off.
Direction (DIR) detection of LV
LV Neu OC Inv neutral OC IDMTL inverse time
0 1 0
Direction stage is switched ON
1-on; 0-off.
Direction unit of LV neutral OC
IDMTL inverse time stage points
LV Neu OC Inv Dir to system
0 1 0
To Sys 0 - point to the protected trans-
former
1- point to system
Inrush 2nd harmonic detection
LV Neu OC Inv LV neutral OC IDMTL inverse
0 1 0
Inrush Block time stage is switched ON
1-on; 0-off.
Select to block LV neutral OC
protection or exit direction unit,
Block LV NOC at 0 1 0 when LV VT fails
LV VT_Fail 0 - LV Direct OK at LV VT Fail
1 - Blk LV NOC at LV VT Fail
LV neutral OC protection initiate
LV Neu OC Init LV 0 1 0 LV side CBF
CBF
0 - initiate, 1 – not initiate

4 Report
Table 84 Event report list

Information Description

HV NOC Inv Trip Inverse time stage of neutral OC protection trip


HV NOC1 Trip HV neutral OC stage 1 trip
HV NOC2 Trip HV neutral OC stage 2 trip
MV EF Inv Trip Inverse time stage of MV neutral OC protection trip
MV EF1 Trip MV neutral OC stage 1 trip
MV EF2 Trip MV neutral OC stage 2 trip
LV EF Inv Trip Inverse time stage of LV neutral OC protection trip
LV EF1 Trip LV neutral OC stage 1 trip
LV EF2 Trip LV neutral OC stage 2 trip

150
Chapter 9 Neutral earth fault protection

Table 85 Operation report list

Information Description

HV Func_NOC On NOC protection of HV side is switched ON (by CW)


HV Func_NOC Off NOC protection of HV side is switched OFF (by CW)
MV Func_NOC On NOC protection of MV side is switched ON (by CW)
MV Func_NOC Off NOC protection of MV side is switched OFF (by CW)
LV Func_NOC On NOC protection of LV side is switched ON (by CW)
LV Func_NOC Off NOC protection of LV side is switched OFF (by CW)

5 Technical data
Table 86 Neutral earth fault protection technical data

Item Rang or value Tolerance


Definite time characteristic
Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
≤ ±1% setting or +40ms, at 200%
Time delay 0.00 to 60.00s, step 0.01s
operating setting
Reset time approx. 40ms
Reset ratio Approx. 0.95 at I/Ir ≥ 0.5
Inverse time characteristics
Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
IEC standard Normal inverse; ≤ ±5% setting + 40ms, at 2
Very inverse; <I/ISETTING < 20, in accordance with
Extremely inverse; IEC60255-151
Long inverse
ANSI Inverse; ≤ ±5% setting + 40ms, at 2
Short inverse; <I/ISETTING < 20, in accordance
Long inverse; with ANSI/IEEE C37.112,
Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic ≤ ±5% setting + 40ms, at 2
T= <I/ISETTING < 20, in accordance with
IEC60255-151
Time factor of inverse time, A 0.005 to 200.0s, step
0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
Minimum operating time 20ms
Maximum operating time 100s
Reset mode instantaneous
Reset time approx. 40ms
Directional element
Operating area range ≤ ±3°, at 3U0≥1V

151
Chapter 9 Neutral earth fault protection

Characteristic angle 0°to 90°, step 1°


Operating area range ≤ ±3°, at 3U2≥2V
Characteristic angle 0°to 90°, step 1°

152
Chapter 10 Thermal overload protection

Chapter 10 Thermal overload


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for thermal
overload protection function.

153
Chapter 10 Thermal overload protection

1 Introduction
The insulating material surrounding the transformer windings ages rapidly if
the temperature exceeds the design limit value. Furthermore, by using less
and less metal per MVA of transformed power, the designed limit value is
reduced in modern power transformers. Hence, it represents an essential
requirement to provide thermal protection to supplement the winding temper-
ature device. The thermal overload protection estimates winding temperature
and therefore prevents damage to transformer caused by thermal overload-
ing.

2 Protection principle
The thermal overload protection includes two stages (alarm and trip). They
work by using an approximate replica of the temperature rise in the protected
object caused by overload. The thermal replica is implemented based on
thermal models (Cold / Hot Curve) of IEC60255-8 Std., without ambient
temperature influence.

Both of the alarm and trip stages can be enabled or disabled by using Control
word “HV Func_Thermal OvLd”, “MV Func_Thermal OvLd” or “LV
Func_Thermal OvLd” on. The thermal overload protection can be assigned to
any desired side (HV, MV or LV) of the protected object. However, for trans-
formers with tap changer, it is recommended to use the function on the
non-regulated side. To enable the protection on each side, setting of “1-on”
should be applied to corresponding Control word.

Both of the thermal overload stages can use cold curve or hot curve in their
calculations, based on the setting applied at Control word “HV Cold Curve”,
“MV Cold Curve” or “LV Cold Curve”. If the protection is enabled in one side,
and the measured current in each phase of the protected transformer in cor-
responding side exceeds the threshold defined by setting “HV I_Therm OL
Alarm”, “MV I_Therm OL Alarm” or “LV I_Therm OL Alarm”, a counter is in-
cremented from 0% to 100%. When the counter is accumulated to its alarm
setting which correspond to the expiration of alarm time delay according to
the selected cold/hot characteristic, the alarm report “HV Load Alarm”, “MV
Load Alarm” or “LV Load Alarm” is given to allow a preventive load reduction.
The alarm signal is cancelled as soon as the measured phase current falls
below the threshold defined by setting “HV I_Therm OL Alarm”, “MV I_Therm
OL Alarm” or “LV I_Therm OL Alarm”. However, the counter is decremented to
zero according to cool down time of the transformer (the time by which the
thermal replica counter reaches from 100% to 0%). The cool down time is
informed to the device by setting “HV T_Const Cool Down”, “MV T_Const
Cool Down” and “LV T_Const Cool Down”.

Similarly, if the measured current in each phase of the protected transformer


in corresponding side exceeds the threshold defined by setting “HV I_Therm
OL Trip”, “MV I_Therm OL Trip” or “LV I_Therm OL Trip”, a counter is incre-
mented from 0% to 100%. If the counter reaches to 100% corresponding to
expiration of trip time delay according to the selected cold/hot characteristic,
the event report “HV THERM Trip”, “MV THERM Trip” or “LV THERM Trip” is
given. The alarm signal is cancelled as soon as the measured phase current

154
Chapter 10 Thermal overload protection

falls below the threshold defined by setting “HV I_Therm OL Trip”, “MV
I_Therm OL Trip” or “LV I_Therm OL Trip”. However, the counter is decre-
mented to zero according to cool down time of the transformer which is en-
tered into the device by setting “HV T_Const Cool Down”, “MV T_Const Cool
Down” and “LV T_Const Cool Down”.

The cold and hot curves used in each thermal overload stages, is based on
thermal curves defined in IEC 60255-8 Std.

The curves provide an operating current/time characteristic that corresponds


to the current overload characteristic of the transformer windings. The for-
mulas corresponding to cold and hot curve is denoted by (1-46) and (1-47),
respectively. The cold curve provides no memory regarding to previous
thermal condition of the transformer, whereas, by using the hot curve, the
protection function is able to represent a memorized thermal profile of the
protected transformer.


 I ph 
2

t   ln  2 2
 I ph  I  
 

Equation 46


 I ph  I P 
2 2

t   ln  2 2 
 I ph  I  
 

Equation 47

Where,

t is alarm/trip time of thermal overload protection function in seconds,

τ is thermal time constant of heating for the power transformer, in seconds. It


is usually provided by the manufacturer. The device is informed about it by
settings “HV T_Const Therm”, “MV T_Const Therm” and “H\LV T_Const
Therm”.

Iph is the current flowing through corresponding side of the transformer, in


each phase. It means that the calculation is performed separately for each
phase, based on fundamental component measurement and also includes
the effect of harmonic contents up to 7th harmonic. Thus, the minimum cal-
culated alarm/ trip time is decisive for evaluation of the thresholds.

IΘ is the setting for alarm and trip stages of the thermal overload protection, in
rms. It should be set considering the maximum permissible thermal continu-
ous overload current of the transformer windings and insulations. The setting
is applied by using “HV I_Therm OL Alarm” and “HV I_Therm OL Trip” for HV
side, “MV I_Therm OL Alarm” and “HV I_Therm OL Trip” for MV side, and
“H\LV I_Therm OL Alarm” and “HV I_Therm OL Trip” for LV side of the power
transformer.

IP is the prior current to overload, assuming sufficient time to reach


steady-state temperature.

155
Chapter 10 Thermal overload protection

NOTE: When Control word “xx Curve/Hot Curve” is set to 0, and fundamental
current is less than the settings, and the heat accumulation is cleared and set
as “0” automatically.

3 Input and output signals

Thermal Overload
Protection
IA1 Therm OL Trip

IB1 Therm OL Alarm

IC1 Relay Startup

IA2

IB2

IC2

Figure 56 Thermal overload protection module

Table 87 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker 1


IB1 Phase B current input of CT of circuit breaker 1
IC1 Phase C current input of CT of circuit breaker 1
IA2 Phase A current input of CT of circuit breaker 2
IB2 Phase B current input of CT of circuit breaker 2
IC2 Phase C current input of CT of circuit breaker 2

Table 88 Binary output list

Signal Description

Therm OL Trip Thermal overload trip


Therm OL Alarm Thermal overload alarm
Relay Startup Relay Startup

4 Setting
Table 89 Settings of thermal overload protection for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/ (Ir:5A/ Description
(Ir:5A/
1A) 1A)
1A)

156
Chapter 10 Thermal overload protection

Setting for HV-side thermal


HV I_Therm OL Trip A 0.1Ir 5Ir 2 overload trip-stage current
Setting for HV-side thermal
HV I_Therm OL Alarm A 0.1Ir 5Ir 2 overload alarm-stage cur-
rent
Time const for HV-side
HV T_Const Therm s 1 9999 10 thermal overload protection

HV T_Const Cool Cool down time delay for


Down
s 1 9999 10 HV-side thermal overload

Table 90 Control words of thermal overload protection for HV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
Thermal overload in HV
HV Func_Thermal
0 1 0 side is switched on
OvLd
0 - OFF, 1 - ON
HV side using hot/cold
curve type
HV Cold Curve 0 1 0
0 – Hot curve, 1 – Cold
curve
HV thermal overload pro-
HV Thermal Init LV
0 1 0 tection initiate LV side CBF
CBF
0 - initiate, 1 – not initiate
HV thermal overload pro-
HV Thermal Init MV tection initiate MV side
0 1 0
CBF CBF
0 - initiate, 1 – not initiate

Table 91 Settings of thermal overload protection for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/ (Ir:5A/ Description
(Ir:5A/
1A) 1A)
1A)
Setting for MV-side thermal
MV I_Therm OL Trip A 0.1Ir 5Ir 2 overload trip-stage current
Setting for MV-side thermal
MV I_Therm OL
A 0.1Ir 5Ir 2 overload alarm-stage cur-
Alarm
rent
Time const for MV-side
MV T_Const Therm s 1 9999 10 thermal overload protection
MV T_Const Cool Cool down time delay for
Down
s 1 9999 10 MV-side thermal overload

157
Chapter 10 Thermal overload protection

Table 92 Control words of thermal overload protection for MV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
Thermal overload in MV
MV Func_Thermal
0 1 0 side is switched on
OvLd
0 - OFF, 1 - ON
MV side using hot/cold
0 1 0
curve type
MV Cold Curve
0 – Hot curve, 1 – Cold
curve
MV thermal overload pro-
MV Thermal Init HV1 tection initiate HV side
0 1 0
CBF CBF
0 - initiate, 1 – not initiate

5 Report
Table 93 Event report list

Information Description

HV Therm OL Trip HV Thermal (TEM) Overload(OVLD) tripping (Trip)

MV Therm OL Trip MV Thermal (TEM) Overload(OVLD) tripping (Trip)

Table 94 Alarm report list

Information Description

HV Therm OL Alm HV Thermal overload Alarm


MV Therm OL Alm MV Thermal overload Alarm

Table 95 Operation report list

Information Description

HV Func_Therm On HV thermal overload protection is switched ON (by CW)


HV Func_Therm Off HV thermal overload protection is switched OFF (by CW)
MV Func_Therm On MV thermal overload protection is switched ON (by CW)
MV Func_Therm Off MV thermal overload protection is switched OFF (by CW)

158
Chapter 10 Thermal overload protection

6 Technical data
Table 96 Thermal overload protection technical data

Item Rang or Value Tolerance


Current 0.1 Ir to 5.00 Ir ≤ ±3% setting or ±0.02Ir
Thermal heating time constant 1 to 9999 s
Thermal cooling time constant 1 to 9999 s

 I eq2 
IEC cold curve t   ln  2 2 
IEC 60255–8,
≤ ±5% setting or +40ms
 I eq  I  
 I eq2  I P2  IEC 60255–8,
IEC hot curve t   ln  2 2 ≤ ±5% setting or +40ms
 I eq  I  

159
Chapter 9 Thermal overload protection

160
Chapter 11 Overload protection

Chapter 11 Overload protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for overload
protection function.

161
Chapter 11 Overload protection

1 Protection principle
Overload protection is equipped for each voltage side and LV delta winding.
The function is to protect all sides of windings of transformer continuous
overload currents.

HV or MV or LV overload protection only comprises a definite time alarm


stage.

HV Func_OverLoad on HV T_OverLoad
A
Load Alarm
Max(IA,IB,IC)>HV N
I_OverLoad D

Figure 57 The logic for HV overload protection

The LV winding overload includes one alarm and two definite time tripping
stages, namely low-setting tripping stage and high-setting tripping stage. The
two tripping stage can be set respective to initiate each side CBF or not

The logic for overload protection is shown in below figure.

LW Func_OvLd Alarm on

& T_OverLo LW Load Alarm


Max(IA,IB,IC)> I_OverLoad ad

LW Func_OvLd Low Trip on

& LW Load Low_Stg


Max(IA,IB,IC)> LW I_OvLd LW T_OvLd
Low Trip Low Trip

LW Func_OvLd High Trip on

& LW T_OvLd High


LW Load High_Stg
Max(IA,IB,IC)>LW I_OvLd
Trip
High Trip

Figure 58 The logic for LV winding overload protection

162
Chapter 11 Overload protection

2 Input and output signals

Overload Protection

IA1 Overload Alarm

IB1 Relay Startup

IC1

IA2

IB2

IC2

Figure 59 Overload protection module for HV, MV, or LV side of


transformer

Delta Winding
Overload Protection
IA Overload high set trip

IB Overload low set trip

IC Overload Alarm

Relay Startup

Figure 60 Overload protection module for LV delta winding of


transformer

Table 97 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker 1


IB1 Phase B current input of CT of circuit breaker 1
IC1 Phase C current input of CT of circuit breaker 1
IA2 Phase A current input of CT of circuit breaker 2
IB2 Phase B current input of CT of circuit breaker 2
IC2 Phase C current input of CT of circuit breaker 2

Table 98 Binary output list

Signal Description

Overload Alarm Overload Alarm


Relay Startup Relay Startup

163
Chapter 11 Overload protection

3 Setting
Table 99 Setting of overload protection for HV side of transformer

De-
fault
Min. Max.
set-
Setting Unit (Ir:5A/ (Ir:5A/ Description
ting
1A) 1A)
(Ir:5A/
1A)
HV I_OverLoad A 0.1Ir 4Ir 2 Overcurrent Setting of overload

HV T_OverLoad s 0.1 3600 10 Time setting for overload

Table 100 Control words of overload protection for HV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
Overload (LOAD) protection in
HV Func_OverLoad 0 1 0 HV side is switched ON
1-on; 0-off.

Table 101 Setting of overload protection for MV side of transformer

De-
fault
Min. Max.
set-
Setting Unit (Ir:5A/ (Ir:5A/ Description
ting
1A) 1A)
(Ir:5A/
1A)
MV I_OverLoad A 0.1Ir 4Ir 2 Overcurrent Setting of overload

MV T_OverLoad s 0.1 3600 10 Time setting for overload

Table 102 Control words of overload protection for MV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
Overload (LOAD)in MV side
MV Func_OverLoad 0 1 0
on

Table 103 Setting of overload protection for LV side of transformer

De-
fault
Min. Max.
set-
Setting Unit (Ir:5A/ (Ir:5A/ Description
ting
1A) 1A)
(Ir:5A/
1A)
LV I_OverLoad A 0.1Ir 4Ir 2 Overcurrent Setting of overload

164
Chapter 11 Overload protection

LV T_OverLoad s 0.1 3600 10 Time setting for overload

Table 104 Control words of overload protection for LV side of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
LV Func_OverLoad 0 1 0 Overload (LOAD)in LV side on

Table 105 Setting of overload protection for LV delta winding of transformer

De-
fault
Min. Max.
set-
Setting Unit (Ir:5A/ (Ir:5A/ Description
ting
1A) 1A)
(Ir:5A/
1A)
Alarm current setting of LV delta
LW I_OvLd Alarm A 0.1Ir 4Ir 20 winding overload protection
Alarm time setting of LV delta
LW T_OvLd Alarm s 0.1 3600 10 winding overload protection
LW I_OvLd Low
A 0.1Ir 4Ir 20 Low stage tripping current setting
Trip
LW T_OvLd Low Low stage tripping time setting
Trip
s 0.1 3600 10
LW I_OvLd High
A 0.1Ir 4Ir 20 High stage tripping current setting
Trip
LW T_OvLd High High stage tripping time setting
Trip
s 0.1 3600 10

Table 106 Control words of overload protection for LV delta winding of transformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
Alarm stage of LV delta wind-
LW Func_OvLd ing (LWIND) overload (LOAD)
0 1 0
Alarm protection is switched ON.
1-on; 0-off.
Low-setting trip stage of LV
LW Func_OvLd Low delta winding overload protec-
0 1 0
Trip tion is switched ON.
1-on; 0-off.
High-setting trip stage of LV
LW Func_OvLd High delta winding overload protec-
0 1 0
Trip tion is switched ON.
1-on; 0-off.
Low-setting trip stage of LV
delta winding overload protec-
Low Trip Init HV1 CBF 0 1 0
tion initiate HV1 side CBF
0 - initiate, 1 – not initiate

165
Chapter 11 Overload protection

High-setting trip stage of LV


delta winding overload protec-
High Trip Init HV1 CBF 0 1 0
tion initiate HV1 side CBF
0 - initiate, 1 – not initiate
Low-setting trip stage of LV
delta winding overload protec-
Low Trip Init MV CBF 0 1 0
tion initiate MV side CBF
0 - initiate, 1 – not initiate
High-setting trip stage of LV
delta winding overload protec-
High Trip Init MV CBF 0 1 0
tion initiate MV side CBF
- initiate, 1 – not initiate

4 Report
Table 107 Event report list

Information Description

LW Load Low_Stg LV delta winding (LWIND) overload (LOAD) protection low setting
trip
LW Load High_Stg LV delta winding (LWIND) overload (LOAD) protection high setting
trip

Table 108 Alarm report list

Information Description

HV Load Alarm HV overload Alarm


MV Load Alarm MV overload Alarm
LV Load Alarm LV overload Alarm

Table 109 Operation report list

Information Description

HV Func_OL On HV overload protection is switched ON (by CW)


HV Func_OL Off HV overload protection is switched OFF (by CW)
MV Func_OL On MV overload protection is switched ON (by CW)
MV Func_OL Off MV overload protection is switched OFF (by CW)
LV Func_OL On LV overload protection is switched ON (by CW)
LV Func_OL Off LV overload protection is switched OFF (by CW)

166
Chapter 12 Overvoltage protection

Chapter 12 Overvoltage protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data used for over-
voltage protection.

167
Chapter 12 Overvoltage protection

1 Introduction
Voltage protection has the function to protect electrical equipment against
overvoltage condition. Abnormally high voltages often occur e.g. in low
loaded, long distance transmission lines, in islanded systems when generator
voltage regulation fails, or after full load shutdown of a generator from the
system. Even if compensation reactors are used to avoid line overvoltage by
compensation of the line capacitance and thus reduction of the overvoltage,
the overvoltage will endanger the insulation if the reactors fail (e.g. fault
clearance). The line must be disconnected within very short time.

The protection provides the following features:

 Two definite time stages

 Each stage can be set to alarm or trip

 Measuring voltage between phase-earth voltage and phase-phase (se-


lectable)

 Settable dropout ratio

2 Protection principle

2.1 Phase to earth overvoltage protection

All the three phase voltages are measured continuously, and compared with
the corresponding setting value. If a phase voltage exceeds the set thresh-
olds, “HV U_OV1” or “HV U_OV2” for HV said, “MV U_OV1” or “MV U_OV2”
for MV said, after expiry of the time delays, “HV T_OV1’ or “HV T_OV2”, and
“MV T_OV1’ or “MV T_OV2”, the protection IED will issue alarm signal or trip
command according to the user’s requirement.

There are two stages included in overvoltage protection, each stage can be
set to alarm or trip separately in control word, and the time delay for each
stage can be individually set. Thus, the alarming or tripping can be
time-coordinated based on how severe the voltage increase, e.g. in case of
high overvoltage, the trip command will be issued with a short time delay,
whereas for the less severe overvoltage, trip or alarm signal can be issued
with a longer time delay.

168
Chapter 12 Overvoltage protection

Additionaly, the dropout ratio of the overvoltage protection can be set in set-
ting “Dropout_OV”. Therefore, the trip command of overvoltage is reset if the
measured voltage comes bellow the ratio value mentioned in this setting.

2.2 Phase to phase overvlotage protection

The phase to earth overvoltage protection operates just like the phase to
phase protection except that it detects phase to earth voltages.

3 Logic diagram
Ua>HV U_OV1

O HV OV Chk PE on
Ub>HV U_OV1
R
Uc>HV U_OV1

HV OV1 Trip on
Trip
Uab>HV U_OV1
O
HV T_OV1
Ubc>HV U_OV1 O R
HV OV Chk PE off
R HV OV1 Trip off
Alarm
Uca>HV U_OV1

Figure 61 Logic diagram for overvoltage protection

4 Input and output signals

Overvoltage Protection

UA OV1 Trip

UB OV2 Trip

UC OV1 Alarm

OV2 Alarm

Relay Startup

Figure 62 Oervoltage protection module

169
Chapter 12 Overvoltage protection

Table 110 Analog input list

Signal Description

UA Phase A voltage input


UB Phase B voltage input
UC Phase C voltage input

Table 111 Binary output list

Signal Description

OV1 Trip OV stage 1trip


OV2 Trip OV stage 2trip
OV1 Alarm OV stage 1 alarm
OV2 Alarm OV stage 2 alarm
Relay Startup Relay Startup

5 Setting
Table 112 Function setting list for overvoltage protection for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
HV voltage setting for stage 1
HV U_OV1 V 40 200 200
of overvoltage protection
HV time setting for stage 1 of
HV T_OV1 s 0 60 60
overvoltage protection
HV voltage setting for stage 2
HV U_OV2 V 40 200 200
of overvoltage protection
HV time setting for stage 2 of
HV T_OV2 s 0 60 60
overvoltage protection
HV dropout ratio for overvolt-
HV Dropout_OV 0.9 0.99 0.95
age protection

170
Chapter 12 Overvoltage protection

Table 113 Control word list for overvoltage protection for HV side of transformer

Default
Setting Unit Min. Max. Description
setting
HV Func_OV1 HV overvoltage stage 1 enabled
0 1 0
or disabled
HV Func_OV2 HV overvoltage stage 1 trip or
0 1 0
alarm
HV Func_OV2 HV overvoltage stage 2 enabled
0 1 0
or disabled
HV OV2 Trip HV overvoltage stage 2 trip or
0 1 0
alarm
HV OV Chk PE HV phase to phase voltage or
0 1 0 phase to earth measured for
overvoltage protection

Table 114 Function setting list for overvoltage protection for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
MV voltage setting for stage 1
MV U_OV1 V 40 200 200
of overvoltage protection
MV time setting for stage 1 of
MV T_OV1 s 0 60 60
overvoltage protection
MV voltage setting for stage 2
MV U_OV2 V 40 200 200
of overvoltage protection
MV time setting for stage 2 of
MV T_OV2 s 0 60 60
overvoltage protection
MV dropout ratio for overvolt-
MV Dropout_OV 0.9 0.99 0.95
age protection

Table 115 Control word list for overvoltage protection for MV side of transformer

Default
Setting Unit Min. Max. Description
setting
MV Func_OV1 MV overvoltage stage 1 enabled
0 1 0
or disabled
MV Func_OV2 MV overvoltage stage 1 trip or
0 1 0
alarm
MV Func_OV2 MV overvoltage stage 2 enabled
0 1 0
or disabled

171
Chapter 12 Overvoltage protection

Default
Setting Unit Min. Max. Description
setting
MV OV2 Trip MV overvoltage stage 2 trip or
0 1 0
alarm
MV OV Chk PE MV phase to phase voltage or
0 1 0 phase to earth measured for
overvoltage protection

6 Report
Table 116 Event report list

Information Description

HV OV1 Trip HV overvoltage stage 1 trip


HV OV2 Trip HV overvoltage stage 2 trip
MV OV1 Trip MV overvoltage stage 1 trip
MV OV2 Trip MV overvoltage stage 2 trip

Table 117 Alarm report list

Information Description

HV OV1 Alarm HV overvoltage stage 1 alarm


HV OV2 Alarm HV overvoltage stage 2 alarm
MV OV1 Alarm MV overvoltage stage 1 alarm
MV OV2 Alarm MV overvoltage stage 2 alarm

Table 118 Operation report list

Description of event comment


HV Func_OV On HV overvoltage protection is switched ON (by CW)
HV Func_OV Off HV overvoltage protection is switched OFF (by CW)
MV Func_OV On MV overvoltage protection is switched ON (by CW)
MV Func_OV Off MV overvoltage protection is switched OFF (by CW)

172
Chapter 12 Overvoltage protection

7 Technical data
Table 119 Technical data for overvoltage protection

Item Rang or Value Tolerance


Voltage connection Phase-to-phase voltages or ≤ ±3 % setting or ±1 V
phase-to-earth voltages
Phase to earth voltage 40 to 100 V, step 1 V ≤ ±3 % setting or ±1 V
Phase to phase voltage 80 to 200 V, step 1 V ≤ ±3 % setting or ±1 V
Reset ratio 0.90 to 0.99, step 0.01 ≤ ±3 % setting
Time delay 0.00 to 60.00 s, step 0.01s ≤ ±1 % setting or +50 ms, at
120% energizing setting
Reset time <40ms

173
Chapter 12 Overvoltage protection

174
Chapter 13 Undervoltage protection

Chapter 13 Undervoltage protection

About this chapter

This chapter describes the protection principle, input and output


signals, parameter, IED report and technical data used for un-
dervoltage protection.

175
Chapter 13 Undervoltage protection

1 Introduction
Undervoltage protection has the function to protect electrical equipment
against undervoltage condition. It can detect voltage collapses on transmis-
sion lines, power transformer and electrical machines and prevents inadmis-
sible operation condition and a possible stability problem.

The protection provides following features:

 Two definite time stages

 Each stage can be set to alarm or trip

 Measuring voltage between phase-earth and phase-phase voltage se-


lectable

 Current criteria supervision

 Circuit breaker aux. contact supervision

 VT secondary circuit supervision, the undervoltage function will be


blocked when VT failure happens

 Settable dropout ratio

2 Protection principle

2.1 Phase to phase underovltage protection

All the three phase voltages are measured continuously, and compared with
the corresponding setting value. If phase to phase voltage falls below the set
threshold and after expiry of the time delay, the protection IED will issue
alarm signal or trip command according to the user’s requirement.

There are two stages included in undervoltage protection, each stage can be
set to alarm or trip separately in control word, and the time delay for each
stage can be individually set. Thus, the alarming or tripping can be
time-coordinated based on how severe the voltage collapse, e.g. in case of
severe undervoltage happens, the trip command will be issued with a short
time delay, whereas for the less severe undervoltage, trip or alarm signal can
be issued with a longer time delay.

176
Chapter 13 Undervoltage protection

Furthermore, for the undervoltage protection, it is possible to set the IED to


operate either when all the measured phase-to-earth or phase-to-phase
voltages falls below the setting or when at least one of the phase-to-earth or
phase-to-phase voltage falls below the respective setting, which can be set in
control word.

2.2 Phase to earth undervoltage protection

The phase to earth undervoltage protection operates just like the phase to
phase protection except that it detects phase to earth voltages.

177
Chapter 13 Undervoltage protection

3 Logic diagram
Ua<U_UV

UV Chk All Phase Off


Ub<U_UV OR

Uc<U_UV
UV Chk PE On

OR

Ua<U_UV

Ub<U_UV AND
UV Chk All Phase On

Uc<U_UV

OR

Uab<U_UV

UV Chk All Phase Off


Ubc<U_UV OR

Uca<U_UV
UV Chk PE Off

OR

Uab<U_UV

Ubc<U_UV AND
UV Chk All Phase On

Uca<U_UV

UV Chk CB status Off

OR
UV Trip On
CB 3 Poles Close
Trip
UV Chk CB status On
AND Func_UV

UV Chk Current Off T_UV

OR
Max(Ia,Ib,Ic)>I_Uv Alarm
UV Chk Current On UV Trip Off

VT fail

Figure 63 Logic diagram for undervoltage protection

178
Chapter 13 Undervoltage protection

4 Input and output signals

UA UV1 Trip
UB UV2 Trip
UC UV1 Alarm
IA UV2 Alarm
IB Relay Startup
IC
CB 3 Poles Close

Figure 64 Undervoltage protection module

5 Setting parameters
Table 120 Undervoltage protection function setting list

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (sIr:5A/ Description
(Ir:5A/1
A) 1A)
A)
Voltage setting for undervolt-
U_UV1 V 5.00 150.0 40
age protection stage 1
Time setting for undervoltage
T_UV1 s 0.00 120.00 0.3
protection stage 1
Voltage setting for undervolt-
U_UV2 V 5.00 150.0 45
age protection stage 2
Time setting for undervoltage
T_UV2 s 0.00 120.00 0.6
protection stage 2
Dropout ratio for undervoltage
Dropout_UV 1.01 2.00 1.05
protection
Current setting for undervolt-
I_UV_Chk A 0.05 10.00 0.1In
age

Table 121 Undervoltage protection control word list

Default
Setting Unit Min. Max. Description
setting
Func_UV1 0 1 1 Undervoltage stage 1 enabled or

179
Chapter 13 Undervoltage protection

Default
Setting Unit Min. Max. Description
setting
disabled
Undervotage stage 1 tripping
UV1 Trip 0 1 0
enabled or disabled
Undervoltage stage 2 enabled or
Func_UV2 0 1 1
disabled
Undervotage stage 2 tripping
UV2 Trip 0 1 0
enabled or disabled
Checking current for undervolt-
UV Chk Current 0 1 1
age protection
Checking CB aux. contact for
UV Chk CB Status 0 1 1
undervoltage protection
Phase to phase or phase to earth
UV Chk PE 0 1 1 measured for undervoltage pro-
tection
Checking three phase voltage for
UV Chk All Phase 0 1 0
undervoltage protection
UV protection initiate other side
UV Init CBF 0 1 0
CBF

6 Reports
Table 122 Event report list

Information Description
UV1 Trip Undervoltage stage 1 trip
UV2 Trip Undervoltage stage 2 trip

Table 123 Alarm report list

Information Description
UV1 Alarm Undervoltage stage 1 alarm
UV2 Alarm Undervoltage stage 2 alarm

Table 124 Operation report list

Description of event comment


HV Func_OV On HV Undervoltage protection is switched ON (by CW)

180
Chapter 13 Undervoltage protection

Description of event comment


HV Func_OV Off HV Undervoltage protection is switched OFF (by CW)
MV Func_OV On MV Undervoltage protection is switched ON (by CW)
MV Func_OV Off MV Undervoltage protection is switched OFF (by CW)
LV Func_OV On LV Undervoltage protection is switched ON (by CW)
LV Func_OV Off LV Undervoltage protection is switched OFF (by CW)

7 Technical data
Table 125 Technical data for undervoltage protection

Item Rang or Value Tolerance


Voltage connection Phase-to-phase voltages or ≤ ±3 % setting or ±1 V
phase-to-earth voltages
Phase to earth voltage 5 to 75 V , step 1 V ≤ ±3 % setting or ±1 V
Phase to phase voltage 10 to 150 V, step 1 V ≤ ±3 % setting or ±1 V
Reset ratio 1.01 to 2.00, step 0.01 ≤ ±3 % setting
Time delay 0.00 to 120.00 s, step 0.01 s ≤ ±1 % setting or +50 ms, at
80% operating setting
Current criteria 0.08 to 2.00 Ir ≤ ±3% setting or ±0.02Ir
Reset time ≤ 50 ms

181
Chapter 13 Undervoltage protection

182
Chapter 14 Zero-sequence voltage protection

Chapter 14 Zero-sequence voltage


protection

About this chapter


This chapter introduced the protection principle, input and output
of signals, logic diagrams, device report and technical data of
zero-sequence voltage protection.

183
Chapter 14 Zero-sequence voltage protection

1 Overview
The supervision of zero-sequence voltage is required to detect earth fault in
power system in some occasion. This function is generally spplied in the
system to restrict the zero-sequence current.

The function has following features.

 Two stages of definite time;

 Each stage can be set as alarm or tripping;

 Fault phase judgement;

 Zero-sequence voltage 3U0 is from internal calculation or external input.

2 Protection principle
Zero-sequence voltage protection is used in the earth fualt detection and di-
recrion discrimination. More details on zero-sequence voltage direction de-
scrimination are shown in other chapters. The stage one is included in the
zero-sequence voltage protection to detect earth fault. This stage can be set
as alarm or tripping and can be set via control word “3U0_Neu Disp Trip/
3U0_Neu Disp Alm”.

Compare the zero-sequence voltage from internal calculation and external


input with the corresponding setting value, the tripping or alarm time delay
counter starts if the zero-sequence voltage is greater than the setting value.
The time delay is set by users. The setting value of time delay can be set
separately by “LV T_Neu Disp Alm” and “LV T_Neu Disp Trip”. The tripping
order or alarming signal will be given by the protection device when reaching
time delay defined by user.

184
Chapter 14 Zero-sequence voltage protection

3 Logic diagram
Internal 3U0>Alarm

setting value
HV Func_3U0 Alarm
or Alarm
External 3U0>Alarm

setting value

Internal 3U0> Tripping

setting value
or HV Func_3U0 TRIP
External 3U0> Tripping
Tripping
setting value

Figure 65 Logic diagram of zero-sequence voltage protection

4 Input and output signals

Zero-sequence voltage protection

UA HV 3U0 Alarm
UB HV 3U0 Trip

UC Relay Startup

U0

Figure 66 Zero-sequence voltage protection module

5 Setting value
Table 126 Setting value of zero-sequence voltage protection

Setting Unit Min. Max. Default Description

3U0_Neu Neutral displacement voltage


V 2.00 100.0 10
Disp Alm alarm

185
Chapter 14 Zero-sequence voltage protection

Setting Unit Min. Max. Default Description

Setting value of ze-


T_Neu Disp
s 0.10 20.00 20.00 ro-sequence voltage protec-
Alm
tion alarm time

3U0_Neu Neutral displacement voltage


V 2.00 100.0 10
Disp Trip alarm

Setting value of ze-


T_Neu Disp
s 0.10 20.00 20.00 ro-sequence voltage protec-
Trip
tion tripping time

Table 127 Zero-sequence voltage protection control word

Setting Unit Min. Max. Default Description


Func_3U0 LV protection stage 1
0 1 1
Alarm 1-on,0-off

Func_3U0 LV protection stage 1 tripping


0 1 0
Trip 1-on,0-off

6 Report
Table 128 Event report list

Report Description

LV 3U0 Trip Zero sequence voltage protection output

Table 129 Alarm report list

Report Description

LV 3U0 Alarm Zero sequence voltage protection alarm

186
Chapter 14 Zero-sequence voltage protection

Table 130 Operating report list

Report Description

LV Func_3U0 Alarm Enable the zero-sequence voltage protection alarm at low voltage
side
LV Func_3U0 Trip Enable the zero-sequence voltage protection tripping at low
voltage side

7 Technical data
Table 131 Technical data of low voltage protection

Content Range or value Error


Phase voltage 40 to 100 V, step 1 V ≤ ±3 % of setting value or ±1 V
Drop-off factor 0.90 to 0.99, step 0.01 ≤ ±3 % of setting value
Time delay 0.00 to 60.00 s, step 0.01s ≤ ±1 % of setting value or +50
ms, when 120% of setting value
Drop-off time <40ms

187
Chapter 14 Zero-sequence voltage protection

188
Chapter 15 Circuite breaker failure protection

Chapter 15 Circuit breaker failure


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for circuit
breaker failure protection function.

189
Chapter 15 Circuit breaker failure protection

1 Introduction
The circuit breaker failure (CBF) protection function monitors proper tripping
of the relevant circuit breaker. There are two separate CBF protection inte-
grated in the IED. They are dedicated to HV and MV sides of the protected
transformer.

2 Protection principle
Normally, the circuit breaker should be tripped and therefore interrupt the fault
current whenever a short circuit protection function issues a trip command.
The circuit breaker failure protection provides rapid back-up fault clearance,
in the event of circuit breaker malfunction to respond to a trip command. This
feature can be enabled or disabled at each side of the protected transformer
via Control words “HV1 CBF ON”, “MV CBF ON”. If setting “1-On” is applied
at these Control words, respective CBF protection will be switched on. In this
case, by operation of a protection function, and subsequent CBF initiation by
respective protection function, a report nominated as “HV1 CBF INIT” or “MV
CBF INIT” is generated by the IED. Furthermore, CBF initiation causes a
programmed timer to run toward a preset time delay limit. This time delay is
set by user under the settings “HV1 T1_CBF” or “MV1 T1_CBF”. If the circuit
breaker has not been opened after expiration of the preset time limit, the cir-
cuit breaker failure protection issues a command to trip circuit breaker (e.g.
via a second trip coil). Furthermore, event report of “HV1 CBF T1” or “MV
CBF T1”is generated by the device. If the circuit breaker doesn’t respond to
the repeated trip command, until another preset delay time which is set at
“HV1 T2_CBF” or “MV1 T2_CBF”, the protection issues a trip command to
isolate the fault by tripping other surrounding backup circuit breakers (e.g. the
other CBs connected to the same bus section as the faulty CB). Furthermore,
event report of “HV1 CBF T2” or “MV CBF T2” is generated in this case.

Initiation of CBF protection can be carried out by both the internal and exter-
nal protection functions. If it is desired to initiate the CBF protection by means
of external protection functions, they should be marshaled to Binary input (BI)
of “HV1 CBF EXT. INT” or “MV CBF EXT. INT” for HV or MV CBF protection
respectively. Internal protection functions can initiate the CBF protection in-
tegrated in IED (HV and/or MV CBF), according to the mapping shown in
below table.

190
Chapter 15 Circuite breaker failure protection

Table 132 Internal functions mapping to initiate CBF protection

CBF INITIATION
PROTECTION FUNCTIONS
HV1 MV

Percent Differential Protection Trip [IDIFF>] ● ● ●

High-Set Differential Protection Trip [IDIFF>>] ● ● ●

HV Restricted Earth Fault Protection Trip ● ● ●

MV Restricted Earth Fault Protection Trip ● ● ●

LV Restricted Earth Fault Protection Trip ● - ●

Overexcitation Protection INV Trip ● ● ●

Overexcitation Protection DEF Trip [U/f >>] ● ● ●

CW CW
HV Thermal Overload Protection Trip ●
[0/1] [0/1]
CW
MV Thermal Overload Protection Trip ● -
[0/1]
CW
LV Thermal Overload Protection Trip - ●
[0/1]

CW CW
HV Overcurrent Protection Trip [INV / DEF (Stage-1,2)] ●
[0/1] [0/1]

MV Overcurrent Protection Trip [INV / DEF CW


● -
(Stage-1,2)] [0/1]

CW
LV Overcurrent Protection Trip [INV / DEF (Stage-1,2)] - ●
[0/1]
CW CW
HV Earth Fault Protection Trip [INV / DEF (Stage-1,2)] ●
[0/1] [0/1]
CW
MV Earth Fault Protection Trip [INV / DEF (Stage-1,2)] ● -
[0/1]
CW
LV Earth Fault Protection Trip [INV / DEF (Stage-1,2)] - ●
[0/1]

HV Neutral Current Protection Trip [INV / DEF CW CW



(Stage-1,2)] [0/1] [0/1]

MV Neutral Current Protection Trip [INV / DEF CW


● -
(Stage-1,2)] [0/1]

LV Neutral Current Protection Trip [INV / DEF CW


- ●
(Stage-1,2)] [0/1]

Overload Protection for LV Winding Low-Stage Trip CW CW


-
(Inside Delta) [0/1] [0/1]

191
Chapter 15 Circuit breaker failure protection

Over Load Protection for LV Winding High-Stage Trip CW CW


-
(Inside Delta) [0/1] [0/1]

CW CW CW
DI1 Trip
[0/1] [0/1] [0/1]

CW CW CW
DI2 Trip
[0/1] [0/1] [0/1]

In above table,

● :means that the protection function working at a given side of the protected
transformer always initiate the CBF protection applied in specified side of the
power transformer. As can be seen, differential, restricted earth fault and
overexcitation protection functions initiate CBF protection in each side of
protected transformer with no additional settings.

The statement CW [0/1] means that the protection function can initiate CBF
protection according to the setting which is applied at respective control word.
The setting includes “1: Initiate the CBF” and “0: Don’t initiate the CBF”. Re-
lated Control words are available for specific functions which include thermal
overload, overcurrent, earth fault and neutral earth fault protections. Fur-
thermore, the dash sign means that it is not possible to initiate CBF protection
of respective side by operation of a protection function working at a given side
of the protected transformer.

There are two criteria for breaker failure detection: the first one is to check
whether the actual current flow effectively disappeared after a tripping com-
mand had been issued. The second one is to evaluate the circuit breaker
auxiliary contact status. Since circuit breaker is supposed to be open when
current disappears from the circuit, the first criterion (current monitoring) is
the most reliable means for relay to be informed about proper operation of
circuit breaker. Therefore, current monitoring is applied to detect circuit
breaker failure condition. In this context, the monitored current of each phase
is compared with the pre-defined setting. The settings are applied at “HV1
I_CBF OC” or “MV I_CBF OC”, for HV or MV CBF protection.

Furthermore, it is possible to implement current checking in case of ze-


ro-sequence and negative-sequence currents via Control word “HV1 3I0/3I2
Check On”, “MV1 3I0/3I2 Check On”. If setting “1-On” is applied at these
Control words, zero-sequence and negative-sequence currents are calculat-

ed and compared with user-defined settings. Corresponding


settings include “HV 3I0_CBF ZS” and “MV 3I0_CBF ZS” for zero-sequence
current, and “HV 3I2_CBF NS” and “MV 3I2_CBF NS” for negative-sequence
current.

192
Chapter 15 Circuite breaker failure protection

For protection functions where the tripping criterion is not dependent on cur-
rent, current flow is not a suitable criterion for proper operation of the breaker.
In this case, the position of the circuit breaker auxiliary contact should be
used to determine if the circuit breaker properly operated. It is possible to
evaluate the circuit breaker operation from its auxiliary contact status. To do
so, Control words “HV1 CB Status Check On” or “MV CB Status Check On”
should be set to “1-On” to integrate circuit breaker auxiliary contacts into CBF
function..

It should be noted that evaluation of circuit breaker auxiliary contacts is car-


ried out in CBF function only when the current flow monitoring has not picked
up. Once the current flow criterion has picked up during the running time of
CBF timers, the circuit breaker is assumed to be open as soon as the current
disappears, even if the associated auxiliary contacts don’t indicate that the
circuit breaker has opened. This gives preference to the more reliable current
criterion and avoids over functioning due to a defect e.g. in the auxiliary con-
tact mechanism or circuit.

3 Logic diagram
BI_HV1 CB EXT.INT
O
Init HV CBF
Inter 3Ph Init CBF R

Figure 67 Internal and external initiation

193
Chapter 15 Circuit breaker failure protection

Ia > HV1 I_CBF


OC
HV 3I0/3I2 Check Off
3I0 > HV1
3I0_CBF ZS
O
3I2 > HV1
A
3I2_CBF NS
R
O N HV 3I0/3I2 Check On
Ib >HV1 I_CBF OC R D
Ic > HV1 I_CBF
OC

Ib >HV1 I_CBF
OC
HV 3I0/3I2 Check Off
3I0 > HV1
3I0_CBF ZS
A O
3I2 > HV1
3I2_CBF NS N R
O HV 3I0/3I2 Check On
Ic > HV1 I_CBF D
OC R
Ia >HV1 I_CBF OC

Ic >HV1 I_CBF
OC
HV 3I0/3I2 Check Off
3I0 > HV1
3I0_CBF ZS
A O
3I2 > HV1
3I2_CBF NS N R
O HV 3I0/3I2 Check On
Ib > HV1 I_CBF D
OC R
Ia > HV1 I_CBF
OC O
R Curr. Crit.

Figure 68 Circuit breaker auxiliary contact evaluation

BI_HV1 CB Open A
A A
BI_HV1 CB Open B N N CB is closed
D D
BI_HV1 CB Open C

Init HV CBF A
N
CBF Curr. Crit. 3P O D
R

Figure 69 The logic for CB close

194
Chapter 15 Circuite breaker failure protection

CB is closed
CB Status Check On O
A
Curr. crit. R Func_CBF on
N
D T1_CBF CBF stg1

Init HV CBF
T2_CBF CBF stg2

Figure 70 The logic for CBF protection

4 Input and output signals

Circuit Breaker
Failure Proteciton
IA CBF Stage 1 Trip

IB CBF Stage 2 Trip

IC Relay Startup

CB Pole A Open

CB Pole B Open

CB Pole C Open

EXT. INT CBF

Figure 71 Circuit breaker protection module

Table 133 Analog input list

Signal Description

IA Phase A current input


IB Phase B current input
IC Phase C current input

Table 134 Binary intput list

Signal Description

CB Pole A Open Circuit breaker(CB) pole A is open

195
Chapter 15 Circuit breaker failure protection

Signal Description

CB Pole B Open Circuit breaker(CB) pole A is open


CB Pole COpen Circuit breaker(CB) pole A is open
EXT.INT CBF initiate the CBF protection by external protection

Table 135 Binary output list

Signal Description

CBF Stage1 Trip CBF protection stage 1 trip


CBF Stage2 Trip CBF protection stage 1 trip
Relay Startup Relay Startup

5 Setting
Table 136 Settings of CBF protection for HV side of transformer

Default
Min. Max.
Setting Unit setting Description
(Ir:5A/1A) (Ir:5A/1A)
(Ir:5A/1A)
Phase current setting value for
HV I_CBF
A 0.05Ir 20Ir 5 HVcircuit breaker failure (CBF)
OC
protection
Negative sequence (NS) cur-
HV
3I2_CBF A 0.05Ir 20Ir 5 rent setting 3I 2 value for HV
NS
CBF protection
Zero sequence (ZS) current
HV
3I0_CBF A 0.05Ir 20Ir 5 setting 3I 0 value for HV1
ZS
CBF protection
Time setting value of Stage 1,
HV T1_CBF s 0 32 10
for HV CBF protection
Time setting value of Stage 2,
HV T2_CBF s 0.1 32 10
for HV CBF protection

196
Chapter 15 Circuite breaker failure protection

Table 137 Control words of CBF protection for HV side of transformer

De-
Setting Unit Min. Max. fault Description
setting
HV Circuit breaker failure (CBF)
HV Func_CBF 0 1 0 protection is switched ON
1-on; 0-off.
HV CBF protection detect nega-
HV 3I0/3I2 Check tive or zero sequence current
0 1 0
On 3I0 or 3I2.
1-Detect; 0- Not Detect
HV CBF protection detect HV1
HV CB Status
0 1 0 CB status
Check On
1-Detect; 0- Not Detect

Table 138 Settings of CBF protection for MV side of transformer

Default
Min. Max.
Setting Unit setting Description
(Ir:5A/1A) (Ir:5A/1A)
(Ir:5A/1A)
MVI_CBF Phase current setting value for
A 0.05Ir 20Ir 5
OC MV CBF protection
Negative sequence (NS) cur-
MV
3I2_CBF A 0.05Ir 20Ir 5 rent setting 3I 2 value for MV
NS
CBF protection
Zero sequence (ZS) current
MV
3I0_CBF A 0.05Ir 20Ir 5 setting 3I 0 value for MV CBF
ZS
protection
Time setting value of Stage 1,
MV T1_CBF s 0 32 10
for MV CBF protection
Time setting value of Stage 2,
MV T2_CBF s 0.1 32 10
for MV CBF protection

197
Chapter 15 Circuit breaker failure protection

Table 139 Control words of CBF protection for MV side of transformer

De-
Setting Unit Min. Max. fault Description
setting
MV Circuit breaker failure (CBF)
MV Func_CBF 0 1 0 protection is switched ON
1-on; 0-off.
MV CBF protection detect nega-
MV 3I0/3I2 Check tive or zero sequence current
0 1 0
On 3I0 or 3I2.
1-Detect; 0- Not Detect
MV CBF protection detect MV
MV CB Status
0 1 0 CB status
Check On
1-Detect; 0- Not Detect

Table 140 Settings of CBF protection for LV side of transformer

Default
Min. Max.
Setting Unit setting Description
(Ir:5A/1A) (Ir:5A/1A)
(Ir:5A/1A)
LV I_CBF Phase current setting value for
A 0.05Ir 20Ir 5
OC LV CBF protection
Negative sequence (NS) cur-
LV 3I2_CBF
A 0.05Ir 20Ir 5 rent setting 3I 2 value for LV
NS
CBF protection
Zero sequence (ZS) current
LV 3I0_CBF
A 0.05Ir 20Ir 5 setting 3I 0 value for LV CBF
ZS
protection
Time setting value of Stage 1,
LV T1_CBF s 0 32 10
for LV CBF protection
Time setting value of Stage 2,
LV T2_CBF s 0.1 32 10
for LV CBF protection

198
Chapter 15 Circuite breaker failure protection

Table 141 Control words of CBF protection for LV side of transformer

De-
Setting Unit Min. Max. fault Description
setting
LV Circuit breaker failure (CBF)
LV Func_CBF 0 1 0 protection is switched ON
1-on; 0-off.
LV CBF protection detect nega-
LV 3I0/3I2 Check tive or zero sequence current
0 1 0
On 3I0 or 3I2.
1-Detect; 0- Not Detect
LV CBF protection detect LV CB
LV CB Status
0 1 0 status
Check On
1-Detect; 0- Not Detect

6 Report
Table 142 Event report list

Information Description

HV CBF1 Trip HV circuit breaker failure protection stage 1 trip


HV CBF2 Trip HV circuit breaker failure protection stage 2 trip
HV CBF Init Internal or external initiate HV circuit breaker failure protection
MV CBF1 Trip MV circuit breaker failure protection stage 1 trip
MV CBF2 Trip MV circuit breaker failure protection stage 2 trip
MV CBF Init Internal or external initiate MV circuit breaker failure protection
LV CBF1 Trip LV circuit breaker failure protection stage 1 trip
LV CBF2 Trip LV circuit breaker failure protection stage 2 trip
LV CBF Init Internal or external initiate LV circuit breaker failure protection

Table 143 Alarm report list

Description of event comment


HV Func_CBF On HV circuit breaker failure protection is switched ON (by CW)
HV Func_CBF Off HV circuit breaker failure protection is switched OFF (by CW)
MV Func_CBF On MV circuit breaker failure protection is switched ON (by CW)
MV Func_CBF Off MV circuit breaker failure protection is switched OFF (by CW)
LV Func_CBF On LV circuit breaker failure protection is switched ON (by CW)

199
Chapter 15 Circuit breaker failure protection

Description of event comment


LV Func_CBF Off LV circuit breaker failure protection is switched OFF (by CW)

7 Technical data
Table 144 CBF protection technical data

Item Rang or Value Tolerance


phase current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
Negative sequence current
zero sequence current
Time delay of stage 1 0.00s to 32.00 s, step 0.01s ≤ ±1% setting or +25 ms, at
Time delay of stage 2 0.00s to 32.00 s, step 0.01s 200% energizing setting

Reset ratio >0.95


Reset time < 25ms

200
Chapter 16 Dead zone protection

Chapter 16 Dead zone protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data used for dead
zone (short zone) protection function.

201
Chapter 16 Dead zone protection

1 Introduction
The IED provides this protection function to protect dead zone, namely the
area between circuit breaker and CT in the case that CB is open. Therefore,
by occurrence of a fault in dead zone, the short circuit current is measured by
protection relay while CB auxiliary contacts indicate the CB is open.

 Internal/ external initiation

 Self-adaptive for bus side CT or line side CT

When one bus side CT of feeder is applied, once a fault occurs in the dead
zone, the IED trips the relevant busbar zone. Tripping logic is illustrated in
below figure.

2 Protection principle
In the case of feeders with bus side CTs, once a fault occurs in the dead zone,
the IED trips the relevant busbar zone CBs. Tripping concept is illustrated in
the below figure.

Trip trip

Bus1 Bus1

IFAULT

IFAULT

T1
Ln L1 Ln L1

Bus2 T1 Bus2

Bus3 Bus3
Legend: Legend:

Opened CB Opened CB
Closed CB Closed CB

Figure 72 Tripping logic for applying bus side CT and for applying line side CT

202
Chapter 16 Dead zone protection

Function description

 Internal/external initiation
 Self-adaptive for bus side CT or line side CT. For bus side CTs, the dead
zone protection will select to trip breakers on other lines connected to the
same busbar. For line side CTs, the dead zone protection will select trip op-
posite side breakers on the same line.

3 Logic diagram
Func_HV CBF
On
Init HV CBF

A Func_Dead Zone On
CBF.Curr. Crit. N T_Dead Zone Dead Zone Trip
D
BI_HV PhA CB Open A
BI_HV PhB CB Open N A
D N
BI_HV PhC CB Open D
BI_HV 3Ph CB Close

Figure 73 Dead zone protection logic

4 Input and output signals

Dear Zone
Protection

IA DZ Trip
IB Relay Startup

IC
CB Pole A Open

CB Pole B Open

CB Pole C Open

CB 3 Poles Close

Figure 74 Dead zone protection module

203
Chapter 16 Dead zone protection

Table 145 Analog input list

Signal Description

IA Phase A current input


IB Phase B current input
IC Phase C current input

Table 146 Binary input list

Signal Description

CB Pole A Open Circuit breaker(CB) pole A is open


CB Pole B Open Circuit breaker(CB) pole B is open
CB Pole C Open Circuit breaker(CB) pole C is open
CB 3 Poles Close 3 poles of circuit breaker(CB) is close

Table 147 Binary output list

Signal Description

DZ Trip dead zone protection trip


Relay Startup Relay Startup

5 Setting
Table 148 Dead zone protection function setting list for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1A (Ir:5A/1A Description
(Ir:5A/1A
) )
)
HV T_Dead Zone Time delay setting for HV
s 0 32 10
dead zone protection

204
Chapter 16 Dead zone protection

Table 149 Dead zone protection control word list for HV side of transformer

Uni Min Max Default set-


Setting Description
t . . ting
Dead zone protection is switched
HV Func_Dead
0 1 0 ON
Zone
1-on; 0-off.

Table 150 Dead zone protection function setting list for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1A (Ir:5A/1A Description
(Ir:5A/1A
) )
)
MV T_Dead Zone Time delay setting for MV
s 0 32 10
dead zone protection

Table 151 Dead zone protection control word list for MV side of transformer

Uni Min Max Default set-


Setting Description
t . . ting
Dead zone protection is switched
MV Func_Dead
0 1 0 ON
Zone
1-on; 0-off.

Table 152 Dead zone protection function setting list for LV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1A (Ir:5A/1A Description
(Ir:5A/1A
) )
)
LV T_Dead Zone Time delay setting for LV
s 0 32 10
dead zone protection

Table 153 Dead zone protection control word list for LV side of transformer

Uni Min Max Default set-


Setting Description
t . . ting
LV Func_Dead Dead zone protection is switched ON
0 1 0
Zone 1-on; 0-off.

205
Chapter 16 Dead zone protection

6 Report
Table 154 Event report list

Information Description
HV Dead Zone HV Dead zone trip
MV Dead Zone MV Dead zone trip
LV Dead Zone LV Dead zone trip

Table 155 Operation report list

Information Description
HV Func_DZ On HV DZ function on
HV Func_DZ Off HV DZ function off
MV Func_DZ On MV DZ function on
MV Func_DZ Off MV DZ function off
LV Func_DZ On LV DZ function on
LV Func_DZ Off LV DZ function off

7 Technical data
NOTE: Ir: CT rated secondary current, 1A or 5A;

Table 156 Technical data of dead zone protection

Item Rang or Value Tolerance


Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
Time delay 0.00s to 32.00s, step 0.01s ≤ ±1% setting or +40 ms, at
200% energizing setting
Reset ratio >0.95

206
Chapter 17 Stub protection

Chapter 17 Stub protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data used for stub
protection function.

207
Chapter 17 Stub protection

1 Introduction
The stub protection protects the zone between the CTs and the open dis-
connector. The stub protection is enabled when the open position of the dis-
connector is informed to the IED through connected binary input. The function
supports one definite stage with the logic shown inbelow figure.

2 Protection principle

2.1 Function description

Busbar A

CT1-1

CB1

CT1-2
Fault
Feeder1

Feeder 1 Disconnector
CT3-1

CB3
CT3-2
Feeder2

Feeder 2 Disconnector
CT2-1

CB2

CT2-2

Busbar B

Figure 75 Stub fault at circuit breaker arrangement

If IED detects short circuit current flowing while the line disconnector is open,
stub fault is detected for the short circuit in the area between the current
transformers and the line disconnector. Here, the summation of CT1 and CT3
presents the short circuit current.

208
Chapter 17 Stub protection

The stub protection is an overcurrent protection which is only in service if the


status of the line disconnector indicates the open condition. The binary input
must therefore be informed via an auxiliary contact of the disconnector. In the
case of a closed line disconnector, the stub protection is out of service. The
stub protection stage provides one definite time overcurrent stage with setta-
ble delay time. This protection function can be enabled or disabled via the
control word “Func_STUB”. Corresponding current setting value can be in-
serted in “I_STUB” setting. The IED generate trip command whenever the
time setting “T_STUB” is elapsed.

3 Logic diagram
Ia>I_STUB

Ib>I_STUB O
R
Ic>I_STUB

Func_STUB A
T_STUB
N Permanent trip

Output Disconnector Open


D

Figure 76 Logic diagram for stub protection

4 Input and output signals

STUB Protection

IA1 STUB Trip

IB1 Relay Startup

IC1

IA2

IB2

IC2

Figure 77 Stub protection module

209
Chapter 17 Stub protection

Table 157 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker 1


IB1 Phase B current input of CT of circuit breaker 1
IC1 Phase C current input of CT of circuit breaker 1
IA2 Phase A current input of CT of circuit breaker 2
IB2 Phase B current input of CT of circuit breaker 2
IC2 Phase C current input of CT of circuit breaker 2

Table 158 Binary input list

Signal Description

Transformer output feeder disconnector is


Output disconnector open
open, to enable the stub protection

Table 159 Binary output list

Signal Description

STUB Trip Stub Trip


Relay Startup Relay Startup

5 Setting
Table 160 Setting value list for stub protection for HV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
current threshold of stub protec-
HV I_STUB A 0.05Ir 20Ir 100
tion
HV T_STUB s 0 60 60 delay time of stub protection

210
Chapter 17 Stub protection

Table 161 Control word list for stub protection for HV side of transformer

Default
Setting Unit Min. Max. Description
setting
HV Func_STUB Enable or disable stub
0 1 0
protection
HV STUB Init LV Stub protection initiate
CBF 0 1 0 LV side CBF
0 - initiate, 1 – not initiate
HV STUB Init MV Stub protection initiate
CBF 0 1 0 HV side CBF
0 - initiate, 1 – not initiate

Table 162 Setting value list for stub protection for MV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
current threshold of stub protec-
MV I_STUB A 0.05Ir 20Ir 100
tion
MV T_STUB s 0 60 60 delay time of stub protection

Table 163 Control word list for stub protection for MV side of transformer

Default
Setting Unit Min. Max. Description
setting
MV Func_STUB Enable or disable stub
0 1 0
protection
MV STUB Init LV stub protection initiate
CBF 0 1 0 LV side CBF
0 - initiate, 1 – not initiate
MV STUB Init MV Stub protection initiate
CBF 0 1 0 MV side CBF
0 - initiate, 1 – not initiate

Table 164 Setting value list for stub protection for LV side of transformer

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
LV I_STUB A 0.05Ir 20Ir 100 current threshold of stub protec-

211
Chapter 17 Stub protection

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
tion
LV T_STUB s 0 60 60 delay time of stub protection

Table 165 Control word list for stub protection for LV side of transformer

Default
Setting Unit Min. Max. Description
setting
LV Func_STUB Enable or disable stub
0 1 0
protection
LV STUB Init LV stub protection initiate
CBF 0 1 0 LV side CBF
0 - initiate, 1 – not initiate
LV STUB Init MV Stub protection initiate
CBF 0 1 0 LV side CBF
0 - initiate, 1 – not initiate

6 Report
Table 166 Event report list

Information Description

HV STUB Trip HV stub protection trip


MV STUB Trip MV stub protection trip
LV STUB Trip LV stub protection trip

Table 167 Operation report list

Information Description
HV Func_STUB On HV stub function on
HV Func_STUB Off HV stub function Off
MV Func_STUB On MV stub function on
MV Func_STUB Off MV stub function Off
LV Func_STUB On LV stub function on
LV Func_STUB Off LV stub function Off

212
Chapter 17 Stub protection

7 Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;

Table 168 Technical data for stub protection

Item Rang or Value Tolerance


Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
Time delay 0.00s to 60.00s, step 0.01s ≤ ±1% setting or +40 ms, at
200% energizing setting
Reset ratio >0.95

213
Chapter 17 Stub protection

214
Chapter 18 Poles discordance protection

Chapter 18 Poles discordance


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for poles dis-
cordance protection.

215
Chapter 18 Poles discordance protection

1 Introdcution
Under normal operating condition, all three poles of the circuit breaker must
be closed or open at the same time. The phase separated operating circuit
breakers can be in different positions (close-open) due to electrical or me-
chanical failures. This can cause negative and zero sequence currents which
gives thermal stress on rotating machines and can cause unwanted operation
of zero sequence or negative sequence current functions.

Single pole opening of the circuit breaker is permitted only in the short period
related to single pole dead times, otherwise the breaker is tripped three pole
to resolve the problem. If the problem still remains, the remote end can be
intertripped via circuit breaker failure protection function to clear the unsym-
metrical load situation.

The pole discordance function operates based on information from auxiliary


contacts of the circuit breaker for the three phases with additional criteria from
unsymmetrical phase current.

2 Protection principle
2.1 Function description
The CB position signals are connected to IED via binary input in order to
monitor the CB status. Poles discordance condition is established when con-
trol word “HV Func_PD” for HV said, or “MV Func_PD” for MV said is set to
“1/on”, and at least one pole is open and at the same time not all three poles
are closed. The auxiliary contacts of the circuit breakers are checked with
corresponding phase currents for plausibility check. Error alarm “CB Err Blk
PD” is reported after 5 sec whenever CB auxiliary contacts indicate that one
pole is open but at the same time current is flowing through the pole.

Additionally the function can be informed via control word “HV PD Chk
3I0/3I2” and “MV PD Chk 3I0/3I2”for additionaly zero and negative sequence
current as well as current criteria involved in CBF protection. Pole discord-
ance can be detected when current is not flowing through all three poles.
When current is flowing through all three poles, all three poles must be closed
even if the breaker auxiliary contacts indicate a different status.

216
Chapter 18 Poles discordance protection

3 Logic diagram
BI_CB Open A A
N
Ia > 0.06Ir
D

BI_CB Open B A O
N R
Ib > 0.06Ir
D

BI_CB Open C A A
N N
5s
CB Err Blk PD
Ic > 0.06Ir
D D
BI_CB Open A
A
BI_CB Open B N
D
BI_CB Open C

BI_CB Open A A
N
Ia < 0.06Ir
D
Func_PD On T_PD
BI_CB Open B A
O A PD Trip
N
Ib < 0.06Ir R N
D
D
BI_CB Open C A
N
Ic< 0.06Ir
D

3I2 > 3I2_PD O


3I0 >3I0_PD
R
A PD Chk 3I0/3I2 on
CBF Curr. Crit. A N
A D PD Chk 3I0/3I2 off
CBF Curr. Crit. B N
D
CBF Curr. Crit. C

Figure 78 Logic diagram for poles discordance protection

217
Chapter 18 Poles discordance protection

4 Input and output signals

Pole Discordance
Protection
IA PD Trip

IB Relay Startup

IC

INBK

CB Pole A Open

CB Pole B Open

CB Pole C Open

Figure 79 Poles discordance protection module

Table 169 Analog input list

Signal Description

IA Phase A current input


IB Phase B current input
IC Phase C current input
INBK Neutral current input

Table 170 Binary input list

Signal Description

CB Pole A Open Circuit breaker(CB) pole A is open


CB Pole B Open Circuit breaker(CB) pole B is open
CB Pole C Open Circuit breaker(CB) pole C is open

Table 171 Binary output list

Signal Description

PD Trip PD Trip
Relay Startup Relay Startup

218
Chapter 18 Poles discordance protection

5 Setting
Table 172 Function setting list for poles discordance protection for HV side of
tranformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
zero sequence current threshold of
HV 3I0_PD A 0.05Ir 20Ir 5 pole discordance protection
negative sequence current thresh-
HV 3I2_PD A 0.05Ir 20Ir 5 old of pole discordance protection
delay time of pole discordance
HV T_PD s 0 60 10 protection

Table 173 Control word list for poles discordance protection for HV side of
tranformer

Default
Setting Unit Min. Max. Description
setting
0 1 0 Enable or disable MV poles
MV Func_PD
discordance protection
MV PD Chk 0 1 0 Enable or disable 3I0/3I2
3I0/3I2 criteria

Table 174 Function setting list for poles discordance protection for MV side of
tranformer

De-
fault
Setting Unit Min. Max. Description
set-
ting
zero sequence current threshold of
MV 3I0_PD A 0.05Ir 20Ir 5 pole discordance protection
negative sequence current thresh-
MV 3I2_PD A 0.05Ir 20Ir 5 old of pole discordance protection
delay time of pole discordance
MV T_PD s 0 60 10 protection

Table 175 Control word list for poles discordance protection for MV side of
tranformer

Default
Setting Unit Min. Max. Description
setting
0 1 0 Enable or disable MV poles
MV Func_PD
discordance protection
MV PD Chk 0 1 0 Enable or disable 3I0/3I2
3I0/3I2 criteria

219
Chapter 18 Poles discordance protection

6 Report
Table 176 Event report list

Information Description

HV PD Trip HV poles discordance protection trip


MV PD Trip MV poles discordance protection trip

Table 177 Alarm report list

Information Description

CB Err Blk PD Circuit breaker error block poles discordance protection

Table 178 Operation report list

Information Description
HV Func_PD On HV poles discordance function on
HV Func_PD Off HV poles discordance function off
MV Func_PD On MV poles discordance function on
MV Func_PD Off MV poles discordance function off

7 Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;

Table 179 Technical data for pole discordance

Item Rang or Value Tolerance


Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir
Time delay 0.00s to 60.00s, step 0.01s ≤ ±1% setting or +40 ms, at
200% energizing setting
Reset ratio >0.95

220
Chapter 19 Distance protection

Chapter 19 Distance protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data of distance
protection.

221
Chapter 19 Distance protection

1 Introduction
The sub-transmission lines are extended, including lots of branches and dif-
ferent distance lines, so the situations are complicated. This kind of system
has higher requirement for fault isolating, in order to sustain the stability and
safety of power system.

The configuration of distance protection can meet basic requirements of


transformer and transmission line.

2 Protection principle
2.1 Frunction description
Phase-to-phase distance protection has two stages. Each of them can be
enabled or disabled speartely and time delay of each stage are setable. The
calculation of phase-to-phase distance is on the bisis of three-phase current
and three-phase-voltage. The equation is shown below:

 U A  U B
Z AB  
 I A  I B
 U B  U C

Z BC  
 I B  IC
  
Z CA  U C  U A
 IC  I A

Equation 48

Where, ZAB, ZBC, ZCA: phase-to-phase impendance.

Phase-to-earth disace has one stage; setting and time delay are settable. The
calcuation of phase-to-earth is shown below:

U 
Z  
I  K  3I
 0

Equation 49

Where: U  :Phase-to-earth voltage(   A, B, C )


I :Phase current(   A, B, C )


K:Zero sequence current compensation factor.

When VT failure happens, the distance protection will be blocked, in order to


prevent misoperation.

222
Chapter 19 Distance protection

Direction to system Direction to transformer

Figure 80 Distance protection characteristic

The direction of distance can be selected by control word setting. For exam-
ple, if the control word ‘

For example, for phase-to-phase distance, if control word “DIS_1 DIR TO


SYS” is set 1, it means direction for 1st stage phase-to-phase distance is to
system; and setting is set 0, it means direction to transformer. It is same to
phase to earth distance.

2.2 Auxiliary startup element


In order to avoid unwanted operation of distance protection and to insure
correct operation when phase-to-phase fault and phase-to-earth fault occur.
Auxiliary startup elements including negative current element and abrupt
current element are adopted.

Auxiliary abrupt current startup element

When all kinds of faults occur in the protected section, current in HV or MV


side will be abrupt change. Abrupt current startup element is adopted in dis-
tance protection; the formula is as follows:

i   0.2 I N


i   i  (t )  i  (t  n)  2i  (t  2n)

Equation 50

Where i  - abrupt current startup element

● Auxiliary negative current startup element

When the imbalance fault occurs in the protected section, negative current

223
Chapter 19 Distance protection

occurs at the same time. Using negative current is helpful to detect the im-
balance faults. the formula is as follows:

I 2  0.2I ie ( i  h, m )

Equation 51

Where I ie - rated current of HV or MV side.

Phase-to-phase distance and phase-to-earth distance have same logic.

3 Logic diagram
The typical logic of 1 stage of distance protection is shown in below figure.

DIS ON
I2>0.2Ie
>=1 T DIS Trip
i  0.2 I N &
Distance Point
inside the Circle
VT failure

Figure 81 Tripping logic for distance protection

4 Input and output signals


Distance Protection
IA1
HV DIS(Ph-N)Trip
IB1
HV DIS_1 Trip
IC1
HV DIS_2 Trip
IA2
Relay Startup
IB2

IC2

UA

UB

UC

Figure 82 Distance protection module

Table 180 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker


1
IB1 Phase B current input of CT of circuit breaker
1

224
Chapter 19 Distance protection

Signal Description

IC1 Phase C current input of CT of circuit breaker


1
IA2 Phase A current input of CT of circuit breaker
2
IB2 Phase B current input of CT of circuit breaker
2
IC2 Phase C current input of CT of circuit breaker
2
UA Phase A voltage input of VT of related winding
of transformer
UB Phase B voltage input of VT of related wind-
ing of transformer
UC Phase C voltage input of VT of related wind-
ing of transformer

Table 181 Binary output list

Signal Description

Phase to Earth Distance (DIS Ph-N) tripping


HV DIS(Ph-N)Trip
in HV side
HV DIS_1 Trip Phase to phase Distance (DIS) prot. Stage
HV DIS_2 Trip 1(_1) or Stage 2 (_2) tripping in HV side with
time delay T
Relay Startup Relay Startup

5 Setting
Table 182 Function setting list for distance protection for HV side of tranformer

De-
Setting
Setting Title fault Comment
options
setting
Phase-to-earth distance(DIS PH-N) set-
1 1HV DIS PH-N X 0.1..125Ω 10
ting X
Phase-to-earth distance(DIS PH-N) set-
2 2HV DIS PH-N R 0.1..125Ω 1
ting R
HV DIS OFFSET
3 3 0.0..1.00 1 Offset ratio to setting
RATIO
4 4HV K FACTOR 0.0..99.0 1 zero sequence compensation coefficient

5 5T HV DIS PH-N 0.1..20.0s 5 Timer setting for DIS PH-N


1st stage Phase-to-phase distance(DIS1)
6 8HV DIS1 PH-PH X1 0.1..125Ω 10
setting X
1st stage Phase-to-phase distance(DIS1)
7 9HV DIS1 PH-PH R1 0.1..125Ω 1
setting
8 1HV DIS1 OFFSET
0.0..1.00 1 Offset ratio to setting of 1st stage DIS1
0 RATIO
9 1
T HV DIS1 PH-PH 0.1..20.0s 5 Timer setting for 1st stage DIS1
1
10 1HV DIS2 PH-PH X2 0.1..125Ω 10 2nd stage Phase-to-phase dis-

225
Chapter 19 Distance protection

2 tance(DIS2) setting X

11 1 2nd stage Phase-to-phase dis-


HV DIS2 PH-PH R2 0.1..125Ω 1
3 tance(DIS2) setting
12 1HV DIS2 OFFSET
0.0..1.00 1 Offset ratio to setting of 2nd stage DIS2
4 RATIO
13 1
T HV DIS2 PH-PH 0.1..20.0s 5 Timer setting for 2nd stage DIS2
5

Table 183 Control word list for distance protection for HV side of tranformer

De-
Setting
No Setting Title fault Comment
options
setting
Phase to earth distance(DIS PH-N) in HV
1 6HV DIS PH-N ON 0/1 0
side on.
HV DIS PH-N DIR Phase to earth Distance (DIS PH-N) di-
2 7 0/1 0
TO SYS rection(DIR) to system(SYS) in HV side
3 1HV DIS1 PH-PH 1st stage phase to phase distance (DIS1)
0/1 0
6 ON in HV side on
1st stage Phase to phase Distance
4 1HV DIS1 PH-PH
0/1 0 (DIS1) direction(DIR) to system(SYS) in
7 DIR TO SYS
HV side
5 1HV DIS2 PH-PH 2nd stage phase to phase distance
0/1 0
8 ON (DIS2) in HV side on
2nd stage Phase to phase Distance
6 1HV DIS2 PH-PH
0/1 0 (DIS2) direction(DIR) to system(SYS) in
9 DIR TO SYS
HV side

Table 184 Function setting list for distance protection for MV side of tranformer

De-
Setting
No. Setting Title fault Comment
options
setting
Phase-to-earth distance(DIS PH-N) set-
1 MV DIS PH-N X 0.1..125Ω 10
ting X
Phase-to-earth distance(DIS PH-N) set-
2 MV DIS PH-N R 0.1..125Ω 1
ting R
MV DIS OFFSET
3 0.0..1.00 1 Offset ratio to setting
RATIO
4 MV K FACTOR 0.0..99.0 1 zero sequence compensation coefficient

5 T MV DIS PH-N 0.1..20.0s 5 Timer setting for DIS PH-N


MV DIS1 PH-PH 1st stage Phase-to-phase distance(DIS)
6 0.1..125Ω 10
X1 setting X
MV DIS1 PH-PH 1st stage Phase-to-phase distance(DIS)
7 0.1..125Ω 1
R1 setting
MV DIS1 OFFSET
8 0.0..1.00 1 Offset ratio to setting of 1st stage DIS1
RATIO
9 T MV DIS1 PH-PH 0.1..20.0s 5 Timer setting for 1st stage DIS1
MV DIS2 PH-PH 2nd stage Phase-to-phase dis-
10 0.1..125Ω 10
X2 tance(DIS2) setting X

226
Chapter 19 Distance protection

MV DIS2 PH-PH 2nd stage Phase-to-phase dis-


11 0.1..125Ω 1
R2 tance(DIS2) setting R
MV DIS2 OFFSET
12 0.0..1.00 1 Offset ratio to setting of 2nd stage DIS2
RATIO
13 T MV DIS2 PH-PH 0.1..20.0s 5 Timer setting for 2nd stage DIS2

Table 185 Control word list for distance protection for MV side of tranformer

No. De-
Setting
Setting Title fault Comment
options
setting
Phase to earth distance(DIS PH-N) in MV
1 5 MV DIS PH-N ON 0/1 0
side on.
MV DIS PH-N DIR Phase to earth Distance (DIS PH-N) di-
2 6 0/1 0
TO SYS rection(DIR) to system(SYS) in MV side
MV DIS1 PH-PH 1st stage phase to phase distance (DIS1)
3 0/1 0
ON in MV side on
1st stage Phase to phase Distance
MV DIS1 PH-PH
4 0/1 0 (DIS1) direction(DIR) to system(SYS) in
DIR TO SYS
MV side
MV DIS2 PH-PH 2nd stage phase to phase distance
5 0/1 0
ON (DIS2) in MV side on
2nd stage Phase to phase Distance
MV DIS2 PH-PH
6 0/1 0 (DIS2) direction(DIR) to system(SYS) in
DIR TO SYS
MV side

6 Report
Table 186 Event report list

Information Description

HV DIS(Ph-N)Trip Phase to Earth Distance (DIS Ph-N) tripping in HV side


HV DIS_1 Trip Phase to phase Distance (DIS) prot. Stage 1(_1) or Stage 2 (_2)
HV DIS_2 Trip tripping in HV side with time delay T
Relay Startup Relay Startup

Table 187 Operation report list

Information Description
HV Func_Dis On HV distance protection on
MV Func_Dis On MV distance protection on
HV Func_Dis Off HV distance protection off
MV Func_Dis Off MV distance protection off

7 Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;

227
Chapter 19 Distance protection

Table 188 Technical data for distance protection

Item Rang or Value Tolerance


Resistance setting range 0. 1Ω~25Ω, step 0.01Ω, when ≤± 5.0% static accuracy
Ir=5A; Conditions:
0. 5Ω~125Ω, step 0.01Ω, when Voltage range: 0.01 Ur to 1.2 Ur
Ir=1A; Current range: 0.12 Ir to 20 Ir
Reactance setting range 0. 1Ω~25Ω, step 0.01Ω, when
Ir=5A;
0. 5Ω~125Ω, step 0.01Ω, when
Ir=1A;
Time delay of distance zones 0.1to 20.00s, step 0.01s ≤±1% or +20 ms
Operation time 40ms typically at 70% setting of
zone
Dynamic overreaching ≤±5%, at 0.5<SIR<30

228
Chapter 20 Secondary system supervision

Chapter 20 Secondary system


supervision

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for secondary
system supervision function.

229
Chapter 20 Secondary system supervision

1 VT failure supervision function


In the event of a measured voltage failure due to a broken conductor or a
short circuit fault in the secondary circuit of voltage transformer, those protec-
tion functions which work based on voltage criteria may mistakenly see a
voltage of zero. VT failure supervision function is provided to inform those
functions about a voltage failure.

2 Function principle
VT failure supervision function can be enabled or disabled in each side
through Control word “HV VT Fail Detect”, “MV VT Fail Detect” and “LV VT
Fail Detect”. By applying setting “1-On” to these Control words, respective VT
failure supervision function would monitor the voltage transformer circuit of
corresponding side. Each VT failure supervision function is able to detect
single-phase broken, two-phase broken or three-phase broken faults in re-
spective voltage transformer. There are three main criteria for VT failure de-
tection; from them the first one is dedicated to detect three-phase broken
faults. The second and third one is dedicated to detect single or two-phase
broken faults in solid earthed and isolated/resistance earthed systems, re-
spectively. A precondition to meet these three criteria is that the relay should
not be picked up and the calculated zero sequence and negative sequence
currents should be less than setting of “HV I_VT Fail”, “MV I_VT Fail” or “LV
I_VT Fail”. These criteria are as follows:

The calculated zero sequence voltage 3U0 as well as maximum of three


phase-to-earth voltages of respective side of the protected transformer are
less than the setting of “HV Upe_VT Fail”, “MV Upe_VT Fail” or “LV Upe_VT
Fail” and at the same time, maximum of three phase currents of respective
side is higher than setting of “HV I_VT Fail”, “MV I_VT Fail” or “LV I_VT Fail”.
This condition may correspond to three phase broken fault in secondary cir-
cuit of the voltage transformer in respective side of the protected transformer.

The calculated zero sequence voltage 3U0 of respective side of the protected
transformer is more than the setting of “HV Upe_VT Fail”, “MV Upe_VT Fail”
or “LV Upe_VT Fail”. This condition may correspond to single or two-phase
broken fault in secondary circuit of the voltage transformer in respective side
of the protected transformer, if the system starpoint is solidly earthed.

The calculated zero sequence voltage 3U0 of respective side of the protected
transformer is more than the setting of “HV Upe_VT Fail”, “MV Upe_VT Fail”
or “LV Upe_VT Fail”, and at the same time, the difference between the max-
imum and minimum phase-to-phase voltages of respective side is more than
the setting of “HV Upp_VT Fail”, “MV Upp_VT Fail” or “LV Upp_VT Fail”. This
condition may correspond to single or two-phase broken fault in secondary
circuit of the voltage transformer in respective side of the protected trans-
former, if the system starpoint is isolated or resistance earthed.

In addition to the mentioned conditions, the device has the capability to be


informed about the VT MCB failure through its binary inputs. These inputs in-

230
Chapter 20 Secondary system supervision

clude “HV MCB FAIL BI”, “MV MCB FAIL BI” and “LV MCB FAIL BI”. In this
context, VT fail is detected in corresponding side, if the respective binary in-
puts are active.

If VT failure supervision detects a failure in voltage transformer secondary


circuit, either by means of the above mentioned criteria or reception of a VT
MCB fail indication, all the protection functions which operate based on di-
rection determination would be blocked in corresponding side of the protected
transformer, depending on the setting. Furthermore, an alarm report of “HV
VT Fail”, “MV VT Fail” or “LV VT Fail”, is issued after 10s delay time. The
blocking condition would be removed if one of the following conditions is met
within the 10s delay time.

Minimum phase voltage of corresponding side of the protected transformer


becomes more than setting of “HV Upe_VT Normal”, “MV Upe_VT Normal” or
“LV Upe_VT Normal” for 500ms.

Minimum phase voltage of corresponding side becomes more than setting of


“HV Upe_VT Normal”, “MV Upe_VT Normal” or “LV Upe_VT Normal” and at
the same time, the calculated zero sequence and negative sequence current
of corresponding side becomes more than the setting of “HV 3I02_VT Fail”,
“MV 3I02_VT Fail” or “LV 3I02_VT Fail”.

Subsequent to reporting VT fail alarm, the blocking condition of respective


protection functions would be removed if the minimum phase voltage of cor-
responding side becomes more than the setting of “HV Upe_VT Normal”, “MV
Upe_VT Normal” or “LV Upe_VT Normal” for a duration more than 10s.

Below figure shows logic diagram of VT failure supervision as it is imple-


mented in the IED.

231
Chapter 20 Secondary system supervision

Max(Ia,Ib,Ic)>I_ VT Fail

A
Max{Ua,Ub,Uc}<Upe_VT Fail N
D

3U0 < ( Upe_VT Fail-1)

Solid Earth on
O
R
3U0 >= (Upe_VT Fail-1)

A
Solid Earth off N
D A
N
D
Max{Uab,Ubc,Uca}-
Min{Uab,Ubc,Uca}>
Upp_VT Fail

A
Relay Pickup N
D O
R
BI MCB Fail

A
VT Fail
N
Detected
10s Alarm report
D
HV VT Fail Detect on

VT Fail Detected

A
Min{Ua,Ub,Uc}>Upe_VT Normal A N 500ms
N D
D
A
O
3I0>3I0_VT Fail or
N No VT Fail
3I2>3I2_VT Fail
R
D

A
N A
min{Ua,Ub,Uc}>Upe_VT Normal N 10s
D
D

Figure 83 Logic of VT Failure supervision

232
Chapter 20 Secondary system supervision

3 Input and output signals

VT Secondary
Circuit Supervision
IA1 VT Failure

IB1 Relay Startup

IC1

IA2

IB2

IC2

UA

UB

UC

V3P MCB Fail

Figure 84 VT Failure supervision module

Table 189 Analog input list

Signal Description

IA1 Phase A current input of CT of circuit breaker


1
IB1 Phase B current input of CT of circuit breaker
1
IC1 Phase C current input of CT of circuit breaker
1
IA2 Phase A current input of CT of circuit breaker
2
IB2 Phase B current input of CT of circuit breaker
2
IC2 Phase C current input of CT of circuit breaker
2
UA Phase A voltage input
UB Phase B voltage input
UC Phase C voltage input

Table 190 Binary input list

Signal Description

V3P MCB Fail VT failure informed by BI

233
Chapter 20 Secondary system supervision

Table 191 Binary output list

Signal Description

VT Failure VT Failure
Relay Startup Relay Startup

4 Setting
Table 192 Settings of VT failure supervision for HV side of transformer

Default
Setting Title Unit Min. Max. Comment
setting
HV I_VT Fail Minimum Current of VT failure
A 0.05Ir 0.2Ir 0.05 for HV side
HV 3I02_ VT Fail Minimum zero or negative Cur-
A 0.05Ir 0.2Ir 0.5 rent of HV VT fail
HV Upe_VT Fail Maximum phase to earth voltage
V 7 20 8
of HV VT fail
HV Upp_VT Fail Maximum phase to phase volt-
V 10 30 16
age of HV VT fail
HV Upe_VT Minimum phase to phase volt-
Normal V 40 65 40
age of HV VT normal

Table 193 Control words of VT failure supervision for HV side of transformer

De-
Setting Title Unit Min. Max. Comment
fault
HV VT Failure Detection
HV VT FAIL Detect 0 0 1 On/Off
1-On, 0-Off.
HV Earthing mode:
HV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.

Table 194 Settings of VT failure supervision for MV side of transformer

Setting Title Default Comment


Unit Min. Max.
setting
Minimum Current of VT failure
MV I_VT Fail A 0.05Ir 0.2Ir 0.05 for MV side
Minimum zero or negative Cur-
MV 3I02_VT Fail A 0.05Ir 0.2Ir 0.5 rent of MV VT fail
Maximum phase to earth voltage
MV Upe_VT Fail V 7 20 8
of MV VT fail
Maximum phase to phase volt-
MV Upp_VT Fail V 10 30 16
age of MV VT fail
MV Upe_VT Minimum phase to phase volt-
V 40 65 40
Normal age of MV VT normal

234
Chapter 20 Secondary system supervision

Table 195 Control words of VT failure supervision for MV side of transformer

De-
Setting Title Unit Min. Max. Comment
fault
MV VT Failure Detection
MV VT FAIL Detect 0 0 1 On/Off
1-On, 0-Off.
MV Earthing mode:
MV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.

Table 196 Settings of VT failure supervision for LV side of transformer

Default
Setting Title Unit Min. Max. Comment
setting
Minimum Current of VT failure
LV I_VT Fail A 0.05Ir 0.2Ir 0.05
for LV side
Minimum zero or negative Cur-
LV 3I02_VT Fail A 0.05Ir 0.2Ir 0.5 rent of LV VT fail
Maximum phase to earth voltage
LV Upe_VT Fail V 7 20 8
of LV VT fail
Maximum phase to phase volt-
LV Upp_VT Fail V 10 30 16
age of LV VT fail
LV Upe_VT Minimum phase to phase volt-
V 40 65 40
Normal age of LV VT normal

Table 197 Control words of VT failure supervision for LV side of transformer

De-
Setting Title Unit Min. Max. Comment
fault
LV VT Failure Detection On/Off
LV VT FAIL Detect 0 0 1
1-On, 0-Off.
LV Earthing mode:
LV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.

5 Report
Table 198 Alarm report list

Information Description

HV VT Fail HV VT Fail alarm


MV VT Fail MV VT Fail alarm
LV VT Fail LV VT Fail alarm

Table 199 Operation report list

Information Description
HV Func_VT On HV VT failure supervision function on
HV Func_VT Off HV VT failure supervision function off
MV Func_VT On MV VT failure supervision function on

235
Chapter 20 Secondary system supervision

Information Description
MV Func_VT Off MV VT failure supervision function off
LV Func_VT On LV VT failure supervision function on
LV Func_VT Off LV VT failure supervision function off

6 Technical data
Note: Ir is secondary current of CT, 1A or 5A

Table 200 Technical data of secondary system supervision

Item Range or value Tolerances


Minimum current 0.08Ir to 0.20Ir, step 0.01A ≤ ±3% setting or ±0.02Ir
Minimum zero or negative se- 0.08Ir to 0.20Ir, step 0.01A ≤ ±5% setting or ±0.02Ir
quence current
Maximum phase to earth voltage 7.0V to 20.0V, step 0.01V ≤ ±3% setting or ±1 V
Maximum phase to phase volt- 10.0V to 30.0V, step 0.01V ≤ ±3% setting or ±1 V
age
Normal phase to earth voltage 40.0V to 65.0V, step 0.01V ≤ ±3% setting or ±1 V

236
Chapter 21 External BIs to trip BOs

Chapter 21 External BIs to trip BOs

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for external BIs
to trip BOs function.

237
Chapter 21 External BIs to trip BOs

1 Introduction
Two special binary inputs (BI_Config1, BI_Config2) are provided which can
be used to activate respective binary outputs (BO1 and BO2), according to
the setting applied at Control words “BI1 Enable BO1” and “BI2 Enable BO2”.
By applying setting “1-enable” to these Control words, BO1 will be activated if
BI1 is energized. Similarly, BO2 will be activated if BI2 is energized. Fur-
thermore, 7th LED in front plate of the device would be lighted when BO1 or
BO2 is activated.

2 Function principle
The external BIs can be used in conjunction with the mechanical protections
of the protected transformer (such as Buchholz, Winding temperature, and so
on). In this context, trip commands of the main and backup mechanical pro-
tections can be marshaled to BI1 and BI2, respectively. By doing so, the
output trip commands would be provided at BO1 and BO2 respectively.

Since the trip command of mechanical protection has latched nature, two
operating modes are provided for the Bos activation. The operating modes
include direct and pulse tripping modes. In direct tripping mode, each BO
contact is active as long as respective BI is energized, and after BI disap-
pearance 20ms the BO contacts are deactivated. Whereas in pulse tripping
mode, by each up-edge of BI, respective BO contacts remain active during a
settable pulse time, and after the settable time, the BO contacts are inactive.
The tripping modes can be selected for the BOs by Control words “BO1 Pulse
Tripping” and “BO2 Pulse Tripping”. Pulse tripping mode would be possible if
setting “1-Pulse Tripping” is applied to the Control words. Similarly, setting
“0-Direct Tripping” activates direct tripping mode for respective BOs. The
logic is shown in below figure.

BI Enable BO on
A
N
D
Pulse Tripping Time
1
BO Pulse Tripping 0
A
N BI trip BO
1 D
BIx up edge 0

1
0
A A
N N BI trip BO
D D

238
Chapter 21 External BIs to trip BOs

Figure 85 Logic of external BIs to trip BOs

Furthermore, it is possible to set BIs to initiate CBF protection in HV, MV or LV


sides of protected transformer via a number of Control words. The Control
words include “BI1 Init HV CBF”, “BI1 Init MV CBF” and “BI1 Init LV CBF” on
for the first BI. Similarly, Control words “BI2 Init HV CBF”, “BI2 Init MV CBF”
and “BI2 Init LV CBF” correspond to the second BI.

3 BI Trigger Record
In the IED, it is possible for Binary inputs (BIs) to trigger disturbance record
(DR). The exceptions are “Switch SetGroup”, “Blk Rem Access”, “Relay Test”
and “Reset”. In this context, each Binary input can be set independently
whether it can trigger DR or not. Further, it is possible to set whether BI trig-
gers DR in its up or down edge. Example logic of BI “HV CB Open Status”
triggering DR is given in below figure. The same logic is applied for the other
BIs.

BI “HV1 CB Open A”
Change from “1”to “0”
A
N
Equipment parameter D
“HV1 CB OPEN STATUS DOWN” = 1
O Trigger
R Record
BI “HV1 CB OPEN STATUS ENABLE”
=1

BI “HV1 CB Open Status”


Change from “0”to “1” A
N
Equipment parameter
D
“HV1 CB OPEN STATUS DOWN” = 0
(meaning UP edge)

Figure 86 Logic of BI trigger record

4 BI Switch SetGroup
BI “Switch SetGroup” is used to switch setting group of the device. Both “BI
SetGrp Switch”and “Normal Set Switch” are selected by making change in the
content of special Control word “BI SetGrp Switch” which can be set under
“Common Para” submenu. When the Control word is set to 1, BI setting group
switch mode is applied, on the contrary, Normal setting group switch mode
(shortcut key or operate through the menu) is applied. For “BI SetGrp Switch”
mode, When BI “Switch SetGroup” is deactivated, the content of Control word
“BI SetGrp Switch” is set to 0 and it means that no switching in setting groups

239
Chapter 21 External BIs to trip BOs

is desired. In this case, Group 1 is applied to the device. When the BI is ac-
tivated, the content of Control word “BI SetGrp Switch” is set to 1 and it
means that “BI SetGrp Switch” mode is applied. Thus, the current set-
ting-value would automatically be switched to Group 2. For the other switch
mode, whether the BI is activated or not, setting group change is valid for
shortcut key or operate through the menu.

5 BI “Blk Rem Access” and “RELAY


TEST”
There are two methods to block remote access to the device, BI “Blk Rem
Access” or making change in the content of special Control word “NOT Blk
Remote Access” which can be set under “Common Para” submenu.

When BI “Blk Rem Access” is activated, or the content of Control word “NOT
Blk Remote Access” is set to 0, SCADA remote access is blocked to the de-
vice and therefore, only local operation is permitted.

When BI “Blk Rem Access” is deactivated, and the content of Control word
“NOT Blk Remote Access” is set to 1, both SCADA commands and local op-
eration can be executed by the device.

Similarly, there are two methods to select test or normal operating mode of
the device, BI “Relay Test” or making change in the content of special Control
word “Relay Test Mode” which can be set under “Common Para” submenu.

When BI “Relay Test” is activated, or the content of Control word “Relay Test
Mode” is set to 1, the relay is in test mode.

When BI “Relay Test” is deactivated, and the content of Control word “Relay
Test Mode” is set to 0, the relay is in normal operation mode

6 BI “BI_Config1~ BI_Config2” and “BI


TRIGGER DR1~ 10”
Both “BI_Config1~ BI_Config2” and “BI Trigger DR1~ BI Trigger DR10” are
binary inputs which can be recorded. BI_Config1~ BI_Config2 can operate to
binary output X10 and X11. The names of these BIs can be modified by
CSPC tools according to actual situation.

240
Chapter 21 External BIs to trip BOs

7 Setting
Table 201 Setting of external BIs to trip BOs

Max. Default
Min.
Setting Unit (Ir:5A/1 setting Description
(Ir:5A/1A)
A) (Ir:5A/1A)
T_Pulse
s 0.2 5 5 delay time of stub protection
Tripping

Table 202 Control words of external DIs to trip DOs

Setting Default
Setting Title Comment
options setting
To select whether the 1st binary input (BI1) trip the
BI1 Enable BO1 1/0 0 1st binary output (BO1) or not.
1-On, 0-Off
To select BO1 tripping in pulse mode or in direct
BO1 Pulse Trip- mode
1/0 0
ping 0- BO1 Direct Tripping, without delay
1- BO1 Pulse Tripping, with preset delay time
To select whether the 2nd binary input (BI2) trip the
BI2 Enable BO2 1/0 0 2nd binary output (BO2) or not.
1-On, 0-Off

To select BO2 tripping in pulse mode or in direct


BO2 Pulse Trip- mode
1/0 0
ping 0- BO2 Direct Tripping, without delay
1- BO2 Pulse Tripping, with preset delay time

whether BI1 initiate HV side CBF or not


BI1 Init HV CBF 1/0 0
0 - initiate, 1 – not initiate
whether BI1 initiate MV side CBF or not
BI1 Init MV CBF 1/0 0
0 - initiate, 1 – not initiate
whether BI1 initiate LV side CBF or not
BI1 Init LV CBF 1/0 0
0 - initiate, 1 – not initiate
whether BI2 initiate HV side CBF or not
BI2 Init HV CBF 1/0 0
0 - initiate, 1 – not initiate
whether BI2 initiate MV side CBF or not
BI2 Init MV CBF 1/0 0
0 - initiate, 1 – not initiate
whether BI2 initiate LV side CBF or not
BI2 Init LV CBF 1/0 0
0 - initiate, 1 – not initiate

241
Chapter 21 External BIs to trip BOs

242
Chapter 22 Interturn protection

Chapter 22 Interturn protection

About this chapter

This chapter introduces the protection principle (applicable for


reactor), input and output signal, parameters of interturn protec-
tion and device report and technical data.

243
Chapter 22 Interturn protection

1 Overview
Interturn short circuit is a usually seen internal fault. The fault tolerant recheck
self-adaptive interturn protection principle is adopted by the IED.

2 Protection principle
The IED uses the self calculated zero sequence current at the terminal of
main reactor and the self calculated zero sequence voltage in the place
where the reactor is installed to calculate the zero sequence power direction.
The zero sequence current is always lagged behind zero sequence voltage,
when the interturn short circuit happens, meanwhile, the measured zero
sequence reactance is then system zero sequence reactance of system. The
zero sequence voltage is lagged behind zero sequence current when external
fault occurs, meanwhile, the measured zero sequence rectance is the then
the zero sequence reactance of the reactor. Therefore, the phase relationship
between zero sequence current at the terminal of main reactor and zero
sequence voltage in ther place where the reactor is installed to distinguish the
interturn short circuit, internal earth fault and external earth fault. The zero
sequence current and voltage amplitudes based on zero sequence
impedence (zero sequence impedence of system is much less than the zero
sequence impedance of reactor) relatively small because the zero sequence
voltage is small when the short circuit number of turns are few. Hence, the
zero sequence voltage compensation is required for better judgement of
interturn fault of few turns. In order to eliminate the influence of irrelevant zero
sequence to the interturn protection sensitivity, the impedance acts as the
auxillary criterion.

The connection of zero sequence voltage and zero sequence current is


shown in the figure below.

PT

System

*
Reactor CT

Figure 87 Definition of zero sequence voltage and current positive direction

Tripping formula of zero sequence power direction is:

244
Chapter 22 Interturn protection

(3U 0  K  Z  3I02 )
0  Arg  180
3I02

Equation 52

In which, 3U 0 and 3I02 are respectively the self calculated zero sequence

voltage at PT and self calculated zero sequence current at CT. Z represents


the the zero sequence impedance of reacotor (The zero sequence imped-
ance of neutral reacor will be included if there is a neutral reactor). K repre-
sents self adaptive compensation factor, ranges from 0 to 0.8.

Tripping formula of impedance element is:

Z  0.66 Z 2 n

Equation 53

In which, Z represents the secondary resistant value of main reactor, which is

calculated in real time and judged by phase. Z 2 n is the secondary rated

impedance of main reac tor.

In order to ensure the reliable operation of interturn protection, the CT failue


and PT failure detection element is provided. The main reactor interturn pro-
tection is disabled when CT or PT failure occur.

3 Logic diagram
Abrupt or steady electric analogs & KG: Inter Turn &
criteria meet conditions. Inter Turn Trip
(3U 0  K  Z  3I0 )
0  Arg  180 ≥1
3I
0

Z  0.66 Z 2 n

PT Failure ≥1

CT Failure

KG represents protection control word

Figure 88 Main reactor interturn protection logic

245
Chapter 22 Interturn protection

4 Input and output signals

Main reactor interturn


protection
IA1 Inter Turn Trip

IB1 Relay Startup

IC1

IA2

IB2

IC2

UA

UB

UC

Figure 89 Interturn protection module

Table 203 Analog input

Signal Description

IA1 Phase A current input of HV side CT


IB1 Phase B current input of HV side CT
IC1 Phase C current input of HV side CT
IA2 Phase A current input of LV side CT
IB2 Phase B current input of LV side CT
IC2 Phase C current input of LV side CT
UA Phase A voltage input
UB Phase B voltage input
UC Phase C voltage input

Table 204 Output list

Signal Description

Inter Turn Trip Interturn trip


Relay Startup Relay startup

246
Chapter 22 Interturn protection

5 Setting value
Table 205 Main reactor interturn protection setting value list

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Tripping setting value of
3I0_InterTurn A 0.05Ir 20Ir 0.2
interturn protection

Table 206 Binary Main reactor interturn protection control word list

Setting Unit Min. Max. Default Description


Interturn protection
Inter Turn 0 1 0
1-ON,0-OFF

6 Report
Table 207 Event report list

Report Description
Inter Turn Trip Interturn protection trip

Table 208 Operation report list

Report Description
Inter Turn Interturn protection on
Inter Turn Off Interturn protection off

7 Technical data
Table 209 Interturn protection technical data

Content Range or value Error


Zero sequence startup cur- ≤ ±5% of setting value or
0.05 Ir to 20 Ir
rent ±0.02Ir
Max. sensitive angle 90° ±5°
Tripping range 20°~160°
Setting time delay Adopt inverse time charac-
teristic. The tripping time is
not more than 100ms.

247
Chapter 22 Interturn protection

248
Chapter 23 Station communication

Chapter 23 Station communication

About this chapter


This chapter describes the communication possibilities in a
SA-system.

249
Chapter 23 Station communication

1 Overview
Each IED is provided with a communication interface, enabling it to connect to
one or many substation level systems or equipment.

The following communication protocols are available:

 LON communication protocol

 IEC 61850-8-1 communication protocol

 60870-5-103 communication protocol

The IED is able to connect to one or more substation level systems or


equipments simultaneously, through the communication ports and supported
protocols.

1.1 Protocol

1.1.1 LON communication protocol

The LON protocol is specified in the LonTalkProtocol Specification Version 3


from Echelon Corporation. This protocol is designed for communication in
control networks and is a peer-to-peer protocol where all the devices con-
nected to the network can communicate with each other directly.

1.1.2 IEC61850-8 communication protocol

IEC 61850-8-1 allows two or more intelligent electronic devices (IEDs) from
one or several vendors to exchange information and to use it in the perfor-
mance of their functions and for correct co-operation.

GOOSE (Generic Object Oriented Substation Event), which is a part of IEC


61850-8-1 standard, allows the IEDs to communicate state and control in-
formation amongst themselves, using a publish-subscribe mechanism. That
is, upon detecting an event, the IED(s) use a multi-cast transmission to notify
those devices that have registered to receive the data. An IED can, by pub-
lishing a GOOSE message, report its status. It can also request a control ac-
tion to be directed at any device in the network.

250
Chapter 23 Station communication

1.1.3 IEC60870-5-103 communication protocol

The IEC 60870-5-103 communication protocol is mainly used when a protec-


tion IED communicates with a third party control or monitoring system. This
system must have software that can interpret the IEC 60870-5-103 commu-
nication messages.

The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit


serial communication exchanging information with a control system. In IEC
terminology a primary station is a master and a secondary station is a slave.
The communication is based on a point-to-point principle. The master must
have software that can interpret the IEC 60870-5-103 communication mes-
sages. For detailed information about IEC 60870-5-103, refer to the
“IEC60870 standard” part 5: “Transmission protocols”, and to the section 103:
“Companion standard for the informative interface of protection equipment”.

1.2 Communication port

1.2.1 Front communication port

There is a serial RS232 port on the front plate of all IEDs. Through this port,
the IED can be connected to the personal computer for setting, testing, and
configuration using the dedicated Sifang software tool.

1.2.2 RS485 communication ports

Up to 2 isolated electrical RS485 communication ports are provided to con-


nect with substation automation system. These two ports can work in parallel
for IEC60870-5-103.

1.2.3 Ethernet communication ports

Up to 3 electrical or optical Ethernet communication ports are provided to


connect with substation automation system. These two out of three ports can
work in parallel for protocol, IEC61850 or IEC60870-5-103.

1.3 Technical data

251
Chapter 23 Station communication

1.3.1 Table Front communication port

Table 210 Front communication port

Item Data
Number 1
Connection Isolated, RS232; front panel
9-pin subminiature connector, for CSmart
Communication speed 9600 baud
Max. length of communication cable 15 m

1.3.2 RS485 communication port

Table 211 RS485 communication port

Item Data
Number 0~2
Connection 2-wire connector
Rear port in communication module
Max. length of communication cable 1.0 km
IEC 60870-5-103 protocol
Communication speed Factory setting 9600 baud
Min. 1200 baud, Max. 19200 baud

1.3.3 Ethernet communication port

Table 212 Ethernet communication port

Item Data
Electrical communication port
Number 0~3
Connection RJ45 connector
Rear port in communication module
Max. length of communication cable 100m
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol

252
Chapter 23 Station communication

Item Data
Communication speed 100 Mbit/s

Optical communication port ( optional )


Number 0~3
Connection SC connector
Rear port in communication module
Optical cable type Multi-mode
Max. length of communication cable 2.0km
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s

1.3.4 Time synchronization

Table 213 Time synchronization

Item Data
Mode Pulse mode
IRIG-B signal format IRIG-B000
Connection 2-wire connector
Rear port in communication module
Voltage levels differential input

2 Typical communication scheme

2.1 Typical substation communication scheme

253
Chapter 23 Station communication

Server or Server or
Work Station 1 Work Station 2

Switch
Work Station 3 Work Station 4

Net 1: IEC61850/IEC103,Ethernet Port A

Switch Net 2: IEC61850/IEC103,Ethernet Port B Switch


Switch
Switch

Gateway Switch Gateway


or or
converter converter

Net 4: IEC103, RS485 Port B


Net 3: IEC103, RS485 Port A

Figure 90 Connection example for multi-networks of station automation system

2.2 Typical time synchronizing scheme

All IEDs feature a permanently integrated electrical time synchronization port.


It can be used to feed timing telegrams in IRIG-B or pulse format into the
IEDs via time synchronization receivers. The IED can adapt the second or
minute pulse in the pulse mode automatically.

Meanwhile, SNTP network time synchronization can be applied.

Below figure illustrates the optional time synchronization modes.

SNTP IRIG-B Pulse

Ethernet port IRIG-B port Binary input

Figure 91 Time synchronizing modes

254
Chapter 24 Hardware

Chapter 24 Hardware

About this chapter


This chapter describes the IED hardware.

255
Chapter 24 Hardware

1 Introduction

1.1 IED structure

The enclosure for equipment is 19 inches in width and 4U in height according


to IEC 60297-3.

 The equipment is flush mounting with panel cutout and cabinet.

 Connection terminals to other system on the rear.

 The front panel of equipment is aluminium alloy by founding in integer


and overturn downwards. LCD, LED and setting keys are mounted on the
panel. There is a serial interface on the panel suitable for connecting to PC.

 Draw-out modules for serviceability are fixed by lock component.

 The modules can be combined through the bus on the rear board. Both
the equipment and the other system can be combined through the rear in-
terfaces.

1.2 IED appearance

Figure 92 Protection IED front view

256
Chapter 24 Hardware

1.3 IED module arrangement

X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13


AIM AIM AIM AIM COM BIM BOM1 BOM2 BOM3 BOM4 PSM
Analogue Input module

Analogue Input module

Analogue Input module

Binary output module 1

Binary output module 2

Binary output module 3

Binary output module 4

Power supply module


Communication mod-

Binary input module


Spare slot

Spare slot

Spare slot
ule

Figure 93 Module arrangement (front view, when open the front panel)

1.4 The rear view of the protection IED

Test port For BIM and BOM Ethernet ports

X13 X12 X11 X10 X9 X8 X7 X6 X5 X3 X2 X1


PSM COM AIM AIM AIM

Figure 94 Rear view of the protection IED

257
Chapter 24 Hardware

2 Local human-machine interface


Setting operation and interrogation of numerical protection systems can be
carried out via the integrated membrane keyboard and display panel located
on the front plate. All the necessary operating parameters can be entered and
all the information can be read out from here,e.g. display, main menu, de-
bugging menu. Operation is, additionally, possible via interface socket by
means of a personal computer or similar.

2.1 Human machine interface

Front panel adopts little arc streamline and beelines sculpt, and function keys
for MMI are reasonably distributed in faceplate. Panel layout are shown as
below figures.

1
5
4

CSC-326

6 7
3 8

Figure 95 Front panel layout for 8 LEDs

1
5
4

CSC-326

6 7
3 8

Figure 96 Front panel layout for 20 LEDs

258
Chapter 24 Hardware

2.2 LCD

The member of keyboard and display panel is externally arranged similar to a


pocked calculator.

2.3 Keypad

The keypad is used to monitor and operate the IED. The keypad has the
same look and feel in all IEDs in the CSC series. LCD screens and other
details may differ but the way the keys function is identical. The keys used to
operate the IED are described below.

Table 214 function of keys of the keypad

Key function
SET SET key:
Enters main menu or sub-menu, and confirms the setting changes
QUIT QUIT key:
 Navigates backward the upper menu.
 Cancels current operation and navigates backward the upper
menu.
 Returns normal rolling display mode
 Locks and unlocks current display in the normal scrolling display
mode; (the locked display mode is indicated by a key type icon
on the upright corner of LCD.)
Right arrow key:
 Moves right in menu.
Left arrow key:
 Moves left in menu.
Up arrow key:
 Moves up in menu
 Page up between screens
 Increases value of setting.
Down arrow key
 Moves down in menu
 Page down between screens
 Decreases the value of setting.
RESET key:
 Reset LEDs
 Return to normal scrolling display mode directly
RESET

259
Chapter 24 Hardware

2.4 Shortcut keys and functional keys

The shortcut keys and functional keys are below the LCD on the front panel. These
keys are designated to execute the frequent menu operations for user’s convenience.
The keys used to operate the IED are described below.

Table 215 function of Shortcut keys and functional keys

Key function
F1 Reserved
F2 Reserved
F3 Reserved
F4 Reserved
+ Plus key:
Switch next setting group forward as active setting group, meaning

the number of setting group plus one.


_ Minus key
Switch next setting group backward as active setting group , mean-

ing the number of setting group subtracted one.

2.5 LED

The definitions of the LEDs are fixed and descrbed below.

Table 216 Definition of 8 LEDs

No LED Color Description

Steady lighting: Operation normally


1 Run Green
Flashing: IED startup

Steady lighting: Alarm II, meaning abnormal situation,


only the faulty function is out of service. Power supply
for tripping output is not blocked.
8 Alarm Red
Flashing: Alarm I, meaning severe internal fault, all
protections are out of service. And power supply for
tripping outputs is blocked as well.

The definitions of the LEDs are fixed and described below for 20 LEDs.

260
Chapter 24 Hardware

Table 217 Definition of 20 LEDs

No LED Color Description

Steady lighting: Operation normally


1 Run Green
Flashing: IED startup

Steady lighting: Alarm II, meaning abnormal situation,


only the faulty function is out of service. Power supply
for tripping output is not blocked.
11 Alarm Red
Flashing: Alarm I, meaning severe internal fault, all
protections are out of service. And power supply for
tripping outputs is blocked as well.

The other LEDs which are not described above can be configured.

2.6 Front communication port

There is a serial RS232 port on the front plate of all the IEDs. Through this
port, the IED can be connected to the personal computer for setting, testing,
and configuration using the dedicated Sifang software tool.

261
Chapter 24 Hardware

3 Analog input module

3.1 Introduction

The analogue input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers.

There are two types of current transformer: Rated current 5A with linearity
range 50mA~150A and rated current 1A with linearity range 100mA~30A
(please indicate clearly when order the product).

3.2 Terminals of Analogue Input Module (AIM)

b a

b01 a01
b02 a02
b03 a03
b04 a04
b05 a05
b06 a06
b07 a07

b08 a08
b09 a09

b10 a10

b11 a11
b12 a12

Figure 97 Terminals arrangement of AIM E

Table 218 Description of terminals of AIM E

Analogue
Terminal Remark
Input
a01 IA Polarity end
b01 I’A
a02 IB Polarity end
b02 I’B

262
Chapter 24 Hardware

Analogue
Terminal Remark
Input
a03 IC Polarity end
b03 I’C
a04 I’N
b04 IN Polarity end
a05 I’NM
b05 INM Polarity end
a06 Null
b06 Null Polarity end
a07 Null
b07 Null Polarity end
a08 Null
b08 Null Polarity end
a09 Null
b09 Null
a10 U4 Polarity end
b10 U’4
a11 UB Polarity end
b11 UC Polarity end
a12 UA Polarity end
b12 UN

3.3 Technical data

3.3.1 Internal current transformer

Table 219 Internal current transformer

Item Standard Data


Rated current Ir IEC 60255-1 1 or 5 A
Nominal current range 0.05 Ir to 30 Ir
Nominal current range of sensitive 0.005 to 1 A
CT
Power consumption (per phase) ≤ 0.1 VA at Ir = 1 A;
≤ 0.5 VA at Ir = 5 A

263
Chapter 24 Hardware

≤ 0.5 VA for sensitive CT


Thermal overload capability IEC 60255-1 100 Ir for 1 s
IEC 60255-27 4 Ir continuous
Thermal overload capability for IEC 60255-27 100 A for 1 s
sensitive CT DL/T 478-2001 3 A continuous

3.3.2 Internal voltage transformer

Table 220 Internal voltage transformer

Item Standard Data


Rated voltage Vr (ph-ph) IEC 60255-1 100 V /110 V
Nominal range (ph-e) 0.4 V to 120 V
Power consumption at Vr = 110 V IEC 60255-27 ≤ 0.1 VA per phase
DL/T 478-2001
Thermal overload capability IEC 60255-27 2 Vr, for 10s
(phase-neutral voltage) DL/T 478-2001 1.5 Vr, continuous

4 Communication module

4.1 Introduction

The communication module performs communication between the internal


protection system and external equipments such as HMI, engineering work-
station, substation automation system, RTU, etc., to transmit remote metering,
remote signaling, SOE, event reports and record data.

Up to 3 channels isolated electrical or optical Ethernet ports and up to 2


channels RS485 serial communication ports can be provided in communica-
tion module to meet the communication demands of different substation au-
tomation system and RTU at the same time.

The time synchronization port is equipped, which can work in pulse mode or
IRIG-B mode. SNTP mode can be applied through communication port.

In addition, a series printer port is also reserved.

4.2 Substaion communication port

264
Chapter 24 Hardware

4.2.1 RS232 communication ports

There is a serial RS232 port on the front plate of all the IEDs. Through this
port, the IED can be connected to the personal computer for setting, testing,
and configuration using the dedicated Sifang software tool.

4.2.2 RS485 communication ports

Up to 2 isolated electrical RS485 communication ports are provided to con-


nect with substation automation system. These two ports can work in parallel
for IEC60870-5-103.

4.2.3 Ethernet communication ports

Up to 3 electrical or optical Ethernet communication ports are provided to


connect with substation automation system. Two out of these three ports can
work in parallel for protocol, IEC61850 or IEC60870-5-103.

4.2.4 Time synchronization port

All IEDs feature a permanently integrated electrical time synchronization port.


It can be used to feed timing telegrams in IRIG-B or pulse format into the
IEDs via time synchronization receivers. The IED can adapt the second or
minute pulse in the pulse mode automatically.

Meanwhile, SNTP network time synchronization can also be applied.

4.3 Terminals of Communication Module

265
Chapter 24 Hardware

01
02 Ethernet port A
03
04
05
06
07 Ethernet port B

08
09
10
11
Ethernet port C
12
13
14
15
16

Figure 98 Terminals arrangement of COM

Table 221 Definition of terminals of COM

Terminal Definition

01 Null

02 Null

03 Null

04 Null

05 Optional RS485 port - 2B

06 Optional RS485 port - 2A

07 Optional RS485 port - 1B

08 Optional RS485 port - 1A

09 Time synchronization

10 Time synchronization GND

11 Null

12 Null

13 Null

14 Null

15 Null

16 Null

Ethernet Optional optical fiber or RJ45 port for


Port A station automation system

Ethernet Optional optical fiber or RJ45 port for


Port B station automation system

Ethernet Optional optical fiber or RJ45 port for

266
Chapter 24 Hardware

Port C station automation system

4.4 Operating reports

Table 222 Definition of terminals of COM

Information Description
DI Comm Fail DI communication error
DO Comm Fail DO communication error

4.5 Technical data

4.5.1 Front communication port

Table 223 Front communication port

Item Data
Number 1
Connection Isolated, RS232; front panel,
9-pin subminiature connector, for software tools
Communication speed 9600 baud
Max. length of communication cable 15 m

4.5.2 RS485 communication port

Table 224 RS485 communication port

Item Data
Number 0 to 2
Connection 2-wire connector
Rear port in communication module
Max. length of communication cable 1.0 km
Test voltage 500 V AC against earth
For IEC 60870-5-103 protocol
Communication speed Factory setting 9600 baud,

267
Chapter 24 Hardware

Min. 1200 baud, Max. 19200 baud

4.5.3 Ethernet communication port

Table 225 RS485 communication port

Item Data
Electrical communication port
Number 0 to 3
Connection RJ45 connector
Rear port in communication module
Max. length of communication cable 100m
For IEC 61850 protocol
Communication speed 100 Mbit/s
For IEC 60870-5-103 protocol
Communication speed 100 Mbit/s

Optical communication port ( optional )


Number 0 to 2
Connection SC connector
Rear port in communication module
Optical cable type Multi-mode
Max. length of communication cable 2.0km
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s

4.5.4 Time synchronization

Table 226 Time synchronization

Item Data
Mode Pulse mode
IRIG-B signal format IRIG-B000
Connection 2-wire connector
Rear port in communication module
Voltage levels differential input

268
Chapter 24 Hardware

5 Binary input module

5.1 Introduction

The binary input module is used to connect the input signals and alarm sig-
nals such as the auxiliary contacts of the circuit breaker (CB), etc.

The negative terminal of power supply for BI module, 220V or 110V, should
be connected to the terminal.

5.2 Terminals of Binary Input Module (BIM)

c a
c02 a02

c04 a04
c06 a06
c08 a08
c10 a10
c12 a12
c14 a14

c16 a16
c18 a18
c20 a20
c22 a22
c24 a24
c26 a26
c28 a28
c30 a30
c32 DC - DC - a32

Figure 99: Terminals arrangement of BIM A

269
Chapter 24 Hardware

Table 227 Definition of terminals of BIM A

Terminal Definition Remark

a02 BI1 BI group 1

c02 BI2 BI group 2

a04 BI3 BI group 1

c04 BI4 BI group 2

a06 BI5 BI group 1

c06 BI6 BI group 2

a08 BI7 BI group 1

c08 BI8 BI group 2

a10 BI9 BI group 1

c10 BI10 BI group 2

a12 BI11 BI group 1

c12 BI12 BI group 2

a14 BI13 BI group 1

c14 BI14 BI group 2

a16 BI15 BI group 1

c16 BI16 BI group 2

a18 BI17 BI group 1

c18 BI18 BI group 2

a20 BI19 BI group 1

c20 BI20 BI group 2

a22 BI21 BI group 1

c22 BI22 BI group 2

a24 BI23 BI group 1

c24 BI24 BI group 2

a26 BI25 BI group 1

c26 BI26 BI group 2

a28 BI27 BI group 1

c28 BI28 BI group 2

a30 BI29 BI group 1

c30 BI30 BI group 2

a32 DC - Input Common terminal of BI group 1

c32 DC - Input Common terminal of BI group 2

270
Chapter 24 Hardware

5.3 Technical data

Table 228 Definition of terminals of BIM A

Item Standard Data


Input voltage range IEC60255-1 110/125 V DC
220/250 V DC
Threshold1: guarantee oper- IEC60255-1 154V, for 220/250V DC
ation 77V, for 110V/125V DC
Threshold2: uncertain opera- IEC60255-1 132V, for 220/250V DC;
tion 66V, for 110V/125V DC
Response time/reset time IEC60255-1 Software provides de-bounce
time
Power consumption, ener- IEC60255-1 Max. 0.2 W/input, 24V DC
gized Max. 0.5 W/input, 110V DC
Max. 1 W/input, 220V DC

271
Chapter 24 Hardware

6 Binary output module

6.1 Introduction

The binary output modules mainly provide tripping output contacts, initiating
output contacts and signaling output contacts. All the tripping output relays
have contacts with a high switching capacity and are blocked by protection
startup elements.

Each output relay can be configured to satisfy the demands of users.

6.2 Terminals of Binary Output Module (BOM)

6.2.1 Binary Output Module A

The module provides 16 output relays for tripping or initiating, with total 16
contacts.

272
Chapter 24 Hardware

R R R R R R R R
1 3 5 7 9 11 13 15

c a
c02 a02

c04 a04

c06 a06

c08 a08

c10 a10

c12 a12

c14 a14

c16 a16

c18 a18

c20 a20

c22 a22

c24 a24

c26 a26

c28 a28

c30 a30

c32 a32

R R R R R R R R
2 4 6 8 10 12 14 16

Figure 100 Terminals arrangement of BOM A

273
Chapter 24 Hardware

Table 229 Definition of terminals of BOM A

Terminal Definition Related relay

a02 Trip contact 1-0 Output relay 1

c02 Trip contact 1-1 Output relay 1

a04 Trip contact 2-0 Output relay 2

c04 Trip contact 2-1 Output relay 2

a06 Trip contact 3-0 Output relay 3

c06 Trip contact 3-1 Output relay 3

a08 Trip contact 4-0 Output relay 4

c08 Trip contact 4-1 Output relay 4

a10 Trip contact 5-0 Output relay 5

c10 Trip contact 5-1 Output relay 5

a12 Trip contact 6-0 Output relay 6

c12 Trip contact 6-1 Output relay 6

a14 Trip contact 7-0 Output relay 7

c14 Trip contact 7-1 Output relay 7

a16 Trip contact 8-0 Output relay 8

c16 Trip contact 8-1 Output relay 8

a18 Trip contact 9-0 Output relay 9

c18 Trip contact 9-1 Output relay 9

a20 Trip contact 10-0 Output relay 10

c20 Trip contact 10-1 Output relay 10

a22 Trip contact 11-0 Output relay 11

c22 Trip contact 11-1 Output relay 11

a24 Trip contact 12-0 Output relay 12

c24 Trip contact 12-1 Output relay 12

a26 Trip contact 13-0 Output relay 13

c26 Trip contact 13-1 Output relay 13

a28 Trip contact 14-0 Output relay 14

c28 Trip contact 14-1 Output relay 14

a30 Trip contact 15-0 Output relay 15

c30 Trip contact 15-1 Output relay 15

a32 Trip contact 16-0 Output relay 16

c32 Trip contact 16-1 Output relay 16

274
Chapter 24 Hardware

6.2.2 Binary Output Module C

The module provides 16 output relays for signal, with total 19 contacts.

R R R R R R R
4 5 1 2 3 6 7

c a
c02 a02

c04 a04

c06 a06

c08 a08

c10 a10

c12 a12

c14 a14

c16 a16

c18 a18

c20 a20

c22 a22

c24 a24

c26 a26

c28 a28

c30 a30

c32 a32

R R R R R R R R R
8 9 10 11 12 13 14 15 16

Figure 101 Terminals arrangement of BOM C

Table 230 Definition of terminals of BOM C

Terminal Definition Related relay

a02 Signal 1-0, Common terminal of signal contact group 1

c02 Signal 2-0, Common terminal of signal contact group 2

275
Chapter 24 Hardware

Terminal Definition Related relay

a04 Signal contact 1-1 Output relay 1

c04 Signal contact 2-1 Output relay 1

a06 Signal contact 1-2 Output relay 2

c06 Signal contact 2-2 Output relay 2

a08 Signal contact 1-3 Output relay 3

c08 Signal contact 2-3 Output relay 3

a10 Signal 3-0, Common terminal of signal contact group 3

c10 Signal 4-0, Common terminal of signal contact group 4

a12 Signal contact 3-1 Output relay 4

c12 Signal contact 4-1 Output relay 7

a14 Signal contact 3-2 Output relay 5

c14 Signal contact 4-2 Output relay 6

a16 Signal contact 5-0 Output relay 8

c16 Signal contact 5-1 Output relay 8

a18 Signal contact 6-0 Output relay 9

c18 Signal contact 6-1 Output relay 9

a20 Signal contact 7-0 Output relay 10

c20 Signal contact 7-1 Output relay 10

a22 Signal contact 8-0 Output relay 11

c22 Signal contact 8-1 Output relay 11

a24 Signal contact 9-0 Output relay 12

c24 Signal contact 9-1 Output relay 12

a26 Signal contact 10-0 Output relay 13

c26 Signal contact 10-1 Output relay 13

a28 Signal contact 11-0 Output relay 14

c28 Signal contact 11-1 Output relay 14

a30 Signal contact 12-0 Output relay 15

c30 Signal contact 12-1 Output relay 15

a32 Signal contact 13-0 Output relay 16

c32 Signal contact 13-1 Output relay 16

6.3 Technical data

276
Chapter 24 Hardware

Table 231 Technical data of BOM C

Item Standard Data


Max. system voltage IEC60255-1 250V DC/AC
Current carrying capacity IEC60255-1 5 A continuous,
42A,1s ON, 9s OFF
Making capacity IEC60255-1 1100 W(DC) at inductive load
with L/R>40 ms
1000 VA(AC)
Breaking capacity IEC60255-1 ≥1000 cycles ,
DC220V, 0.15A, t=L/R≤40 ms
DC110V, 0.30A, t=L/R≤40 ms
Unloaded mechanical endur- IEC60255-1 50,000,000 cycles (3 Hz
ance switching frequency)
Specification state verification IEC60255-1 UL/CSA、TŰV
IEC60255-23
IEC61810-1
Contact circuit resistance IEC60255-1 30mΩ
measurement IEC60255-23
IEC61810-1
Open Contact insulation test IEC60255-1 AC1000V 1min
(AC Dielectric strength) IEC60255-27
Maximum temperature of parts IEC60255-1 55℃
and materials

277
Chapter 24 Hardware

7 Power supply module

7.1 Introduction

The power supply module is used to provide the correct internal voltages and
full isolation between the terminal and the battery system. Its power input is
DC 220V or 110V (according to the order code), and its outputs are five
groups of power supply.

(1) +24V two groups provided: Power for inputs of the corresponding bi-
nary inputs of the CPU module

(2) ±12V: Power for A/D

(3) + 5V: Power for all micro-chips

7.2 Terminals of Power Supply Module (PSM)

c a
c02 DC 24V + a02
OUTPUTS
c04 a04
c06 a06

c08 a08
DC 24V -
c10 OUTPUTS
a10
c12 a12
c14 a14

c16 a16
c18 a18

c20 AUX.DC + a20


INPUT
c22 a22

c24 a24
c26 AUX. DC - a26
INPUT
c28 a28
c30 a30

c32 a32

Figure 102 Terminals arrangement of PSM

278
Chapter 24 Hardware

Table 232 Definition of terminals of PSM

Terminal Definition

a02 AUX.DC 24V+ output 1

c02 AUX.DC 24V+ output 2

a04 AUX.DC 24V+ output 3

c04 AUX.DC 24V+ output 4

a06 Isolated terminal, not wired

c06 Isolated terminal, not wired

a08 AUX.DC 24V- output 1

c08 AUX.DC 24V- output 2

a10 AUX.DC 24V- output 3

c10 AUX.DC 24V- output 4

a12 AUX.DC 24V- output 5

c12 AUX.DC 24V- output 6

a14 Alarm contact A1, for AUX.DC power input failure

c14 Alarm contact A0, for AUX.DC power input failure

a16 Alarm contact B1, for AUX.DC power input failure

c16 Alarm contact B0, for AUX.DC power input failure

a18 Isolated terminal, not wired

c18 Isolated terminal, not wired

a20 AUX. power input 1, DC +

c20 AUX. power input 2, DC +

a22 AUX. power input 3, DC +

c22 AUX. power input 4, DC +

a24 Isolated terminal, not wired

c24 Isolated terminal, not wired

a26 AUX. power input 1, DC -

c26 AUX. power input 2, DC -

a28 AUX. power input 3, DC -

c28 AUX. power input 4, DC -

a30 Isolated terminal, not wired

c30 Isolated terminal, not wired

a32 Terminal for earthing

c32 Terminal for earthing

279
Chapter 24 Hardware

7.3 Technical data

Table 233 Technical data

Item Data
Rated auxiliary voltage Vaux 110~250V DC
Permissible tolerance ±%20 Uaux
Power consumption
Normal operation ≤ 30 W
Tripping condition ≤ 50 W

8 Terminal block

2
4
6
8

Figure 103 Terminals of CSC-326(M02)

280
Chapter 24 Hardware

2
4
6
8

Figure 104 Terminals of CSC-326(M03)

9 Techinical data

9.1 Basic data

9.1.1 Frequency

Table 234 Technical data of frequency

Item Data
System rated frequency 50 Hz or 60Hz

9.1.2 Internal current transformer

Table 235 Technical data of internal current transformer

Item Data
Rated current Ir 1 or 5 A
Nominal current range (0.05 – 20)x Ir
Power consumption (per phase) ≤ 0.1 VA at Ir = 1 A;
≤ 0.5 VA at Ir = 5 A

281
Chapter 24 Hardware

Item Data
Thermal overload capability 100 x Ir for 1 s
4 x Ir continuous

9.1.3 Internal voltage transformer

Table 236 Technical data of internal voltage transformer

Item Data
Rated voltage Vr (ph-ph) 100-120
Nominal range (ph-e) 0.4 V to 120 V
Power consumption at Vr = 110 V ≤ 0.1 VA per phase

Thermal overload capability (phase-neutral 2Vr, for 10s


voltage) 1.5Vr, continuous

9.1.4 Auxiliary voltage

Table 237 Technical data of auxiliary voltage

Item Standard Data


Rated auxiliary voltage Vaux IEC60255-1 110 to 250V DC
Permissible tolerance IEC60255-1 ±%20 Uaux
Power consumption at quies- IEC60255-1 ≤ 50 W
cent state
Power consumption at maxi- IEC60255-1 ≤ 60 W
mum load
Inrush Current IEC60255-1 T ≤ 10 ms/I≤ 25 A

9.1.5 Binary inputs

Table 238 Technical data of binary inputs

Item Standard Data


Input voltage range IEC60255-1 110/125 V DC
220/250 V DC
Threshold1: guarantee oper- IEC60255-1 154V, for 220/250V DC
ation 77V, for 110V/125V DC

282
Chapter 24 Hardware

Item Standard Data


Threshold2: uncertain opera- IEC60255-1 132V, for 220/250V DC;
tion 66V, for 110V/125V DC
Response time/reset time IEC60255-1 Software provides de-bounce
time
Power consumption, ener- IEC60255-1 Max. 0.2 W/input, 24V DC
gized Max. 0.5 W/input, 110V DC
Max. 1 W/input, 220V DC

9.1.6 Binary outputs

Table 239 Technical data of binary inputs


Item Standard Data
Max. system voltage IEC60255-1 250V DC/AC
Current carrying capacity IEC60255-1 5 A continuous,
42A,1s ON, 9s OFF
Making capacity IEC60255-1 1100 W(DC) at inductive load
with L/R>40 ms
1000 VA(AC)
Breaking capacity IEC60255-1 ≥1000 cycles ,
DC220V, 0.15A, t=L/R≤40 ms
DC110V, 0.30A, t=L/R≤40 ms
Unloaded mechanical endur- IEC60255-1 50,000,000 cycles (3 Hz
ance switching frequency)
Specification state verification IEC60255-1 UL/CSA、TŰV
IEC60255-23
IEC61810-1
Contact circuit resistance IEC60255-1 30mΩ
measurement IEC60255-23
IEC61810-1
Open Contact insulation test IEC60255-1 AC1000V 1min
(AC Dielectric strength) IEC60255-27
Maximum temperature of parts IEC60255-1 55℃
and materials

9.2 Type tests

283
Chapter 24 Hardware

9.2.1 Product safety-related Tests

Table 240 Technical data of product safety-related tests

Item Standard Data


Over voltage category IEC60255-27 Category III
Pollution degree IEC60255-27 Degree 2
Insulation IEC60255-27 Basic insulation
Degree of protection (IP) IEC60255-27 Front plate: IP40
IEC 60529 Rear, side, top and bottom: IP
30
Power frequency high voltage IEC 60255-5 2KV, 50Hz
withstand test ANSI C37.90 2.8kV DC
GB/T 15145-2001 between the following circuits:
DL/T 478-2001  auxiliary power supply
 CT / VT inputs
 binary inputs
 binary outputs
 case earth
500V, 50Hz
between the following circuits:
 Communication ports to
case earth
 time synchronization ter-
minals to case earth
Impulse voltage test IEC60255-5 5kV (1.2/50μs, 0.5J)
IEC 60255-27 if Ui≥63V
ANSI C37.90 1kV if Ui<63V
GB/T 15145-2001 Tested between the following
DL/T 478-2001 circuits:
 auxiliary power supply
 CT / VT inputs
 binary inputs
 binary outputs
 case earth
Note: Ui: Rated voltage
Insulation resistance IEC60255-5 ≥ 100 MΩ at 500 VDC
IEC 60255-27
ANSI C37.90

284
Chapter 24 Hardware

Item Standard Data


GB/T 15145-2001
DL/T 478-2001
Protective bonding resistance IEC60255-27 ≤ 0.1Ω
Fire withstand/flammability IEC60255-27 Class V2

9.2.2 Electromagnetic immunity tests

Table 241 Technical data of electromagnetic immunity tests


Item Standard Data
1 MHz burst immunity test IEC60255-22-1 class III
IEC60255-26 2.5 kV CM ; 1 kV DM
IEC61000-4-18 Tested on the following circuits:
ANSI/IEEE C37.90.1  auxiliary power supply
 CT / VT inputs
 binary inputs
 binary outputs
1 kV CM ; 0 kV DM
Tested on the following circuits:
 communication ports
Electrostatic discharge IEC 60255-22-2 Level 4
IEC 61000-4-2 8 kV contact discharge;
15 kV air gap discharge;
both polarities; 150 pF; Ri = 330
Ω
Radiated electromagnetic field IEC 60255-22-3 frequency sweep:
disturbance test 80 MHz – 1 GHz; 1.4 GHz – 2.7 GHz
spot frequencies:
80 MHz; 160 MHz; 380 MHz;
450 MHz; 900 MHz; 1850 MHz;
2150 MHz
10 V/m
AM, 80%, 1 kHz
Radiated electromagnetic field IEC 60255-22-3 pulse-modulated
disturbance test 10 V/m, 900 MHz; repetition rate
200 Hz, on duration 50 %
Electric fast transient/burst im- IEC 60255-22-4, class A, 4KV
munity test IEC 61000-4-4 Tested on the following circuits:
ANSI/IEEE C37.90.1  auxiliary power supply

285
Chapter 24 Hardware

Item Standard Data


 CT / VT inputs
 binary inputs
 binary outputs
class A, 2KV
Tested on the following circuits:
 communication ports
Surge immunity test IEC 60255-22-5 4.0kV L-E
IEC 61000-4-5 2.0kV L-L
Tested on the following circuits:
 auxiliary power supply
 CT / VT inputs
 binary inputs
 binary outputs
2.0kV L-E
Tested on the following circuits:
 communication ports
Conduct immunity test IEC 60255-22-6 frequency sweep: 150 kHz – 80
IEC 61000-4-6 MHz
spot frequencies: 27 MHz and
68 MHz
10 V
AM, 80%, 1 kHz
Power frequency immunity test IEC60255-22-7 Class A
300 V CM
150 V DM
Power frequency magnetic field IEC 61000-4-8 level 4
test 30 A/m cont. / 300 A/m 1 s to 3 s
100 kHz burst immunity test IEC61000-4-18 2.5 kV CM ; 1 kV DM
Tested on the following circuits:
 auxiliary power supply
 CT / VT inputs
 binary inputs
 binary outputs
1 kV CM ; 0 kV DM
Tested on the following circuits:
 communication ports

9.2.3 DC voltage interruption test

286
Chapter 24 Hardware

Table 242 Technical data of DC voltage interruption test


Item Standard Data
DC voltage dips IEC 60255-11 100% reduction 80 ms
60% reduction 200 ms
30% reduction 500 ms
DC voltage interruptions IEC 60255-11 100% reduction 5 s
DC voltage ripple IEC 60255-11 15%, twice rated frequency
DC voltage gradual shut–down IEC 60255-11 60 s shut down ramp
/start-up 5 min power off
60 s start-up ramp
DC voltage reverse polarity IEC 60255-11 1 min

9.2.4 Electromagnetic emission test

Table 243 Technical data of electromagnetic emission test

Item Standard Data

Item Standard Data


Radiated emission IEC60255-25 30MHz to 1GHz ( IT device may
CISPR22 up to 5 GHz)
Conducted emission IEC60255-25 0.15MHz to 30MHz
CISPR22

9.2.5 Mechanical tests

Table 244 Technical data of mechanical tests


Item Standard Data
Sinusoidal Vibration response IEC60255-21-1 class 1
test 10 Hz to 60 Hz: 0.075 mm
60 Hz to 150 Hz: 1 g
1 sweep cycle in each axis
Relay energized
Sinusoidal Vibration endur- IEC60255-21-1 class 1
ance test 10 Hz to 150 Hz: 1 g
20 sweep cycle in each axis
Relay non-energized
Shock response test IEC60255-21-2 class 1

287
Chapter 24 Hardware

Item Standard Data


5 g, 11 ms duration
3 shocks in both directions of 3
axes
Relay energized
Shock withstand test IEC60255-21-2 class 1
15 g, 11 ms duration
3 shocks in both directions of 3
axes
Relay non-energized
Bump test IEC60255-21-2 class 1
10 g, 16 ms duration
1000 shocks in both directions of
3 axes
Relay non-energized
Seismic test IEC60255-21-3 class 1
X-axis 1 Hz to 8/9 Hz: 7.5 mm
X-axis 8/9 Hz to 35 Hz :2 g
Y-axis 1 Hz to 8/9 Hz: 3.75 mm
Y-axis 8/9 Hz to 35 Hz :1 g
1 sweep cycle in each axis,
Relay energized

9.2.6 Climatic tests

Table 245 Technical data of climatic tests


Item Standard Data
Cold test - Operation IEC60255-27 -10°C, 16 hours, rated load
IEC60068-2-1
Cold test – Storage IEC60255-27 -25°C, 16 hours
IEC60068-2-1
Dry heat test – Operation [IEC60255-27 +55°C, 16 hours, rated load
IEC60068-2-2
Dry heat test – Storage IEC60255-27 +70°C, 16 hours
IEC60068-2-2
Change of temperature IEC60255-27 Test Nb, figure 2, 5 cycles
IEC60068-2-14 -10°C / +55°C
Damp heat static test IEC60255-27 +40°C, 93% r.h. 10 days, rated
IEC60068-2-78 load
Damp heat cyclic test IEC60255-27 +55°C, 93% r.h. 6 cycles, rated

288
Chapter 24 Hardware

Item Standard Data


IEC60068-2-30 load

9.2.7 CE Certificate

Table 246 Technical data of CE Certificate


Item Data
EN 61000-6-2 and EN61000-6-4 (EMC
EMC Directive
Council Directive 2004/108/EC)
EN 60255-27 (Low-voltage directive 2006/95
Low voltage directive
EC).

9.3 IED design

Table 247 Technical data of IED design


Item Data
Case size 4U×19inch
Weight ≤ 8kg

289
Chapter 24 Hardware

290
Chapter 25 Appendix

Chapter 25 Appendix

291
Chapter 25 Appendix

1 General setting list

1.1 Function setting list

Table 248 Function setting list


Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
HV Wind Conn/Y 0 1 0 Connection for HV winding,
0:wye connection, 1:delta
connection
MV Wind Conn/Y 0 1 0 Connection for MV winding,
0:wye connection, 1:delta
connection
LV Wind Conn/Y 0 1 1 Connection for LV winding,
0:wye connection, 1:delta
connection
Vet Grp Angle MVA 1.000 3000. 120.0 Vector Group Angle( VET
GRP ANGLE)
SN kV 1.000 1000. 220.0 Capacity of the transformer
HV VT Ratio MVA 1.000 9999. 2200.0 Voltage transformer(VT) Ra-
tio in HV side
A 50.00 9999. 1200.0 CT Primary(PRI) current in
HV CT Pri
HV side
A 1.000 5.000 1.0 CT Secondary(SEC) current
HV CT Sec
in HV side
HV Voltage Chan 1 3 1
HV voltage channel location
Sel
MV Voltage Chan 1 3 2 MV voltage channel loca-
Sel tion
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
HV NCT Pri(REF) ry(PRI) current in HV side
for REF
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
HV NCT Sec(REF) ary(SEC) current in HV side
for REF
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
HV NCT Pri(BU)
ry(PRI) current in HV side

292
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
for backup protection
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
HV NCT Sec(BU) ary(PRI) current in HV side
for backup protection
kV 1.000 1000. 110.0 Nominal voltage (UN) in
MV UN
Middle voltage (MV)side
1.000 9999. 1100.0 Voltage transformer(VT) Ra-
MV VT Ratio
tio in MV side
A 50.00 9999. 1200.0 CT Primary(PRI) current in
MV CT Pri
MV side
A 1.000 5.000 1.0 CT Secondary(SEC) current
MV CT Sec
in MV side
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
MV NCT Pri(REF) ry(PRI) current in MV side
for REF
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
MV NCT Sec(REF) ary(SEC) current in MV
side for REF
A 50.00 9999. 1200.0 Neutral CT (NCT) Prima-
MV NCT Pri(BU) ry(PRI) current in MV side
for backup protection
A 1.000 5.000 1.0 Neutral CT (NCT) Second-
MV NCT Sec(BU) ary(PRI) current in MV side
for backup protection
kV 1.000 1000. 10.50 Nominal voltage (UN) in Low
LV UN
voltage (LV)side
1.000 9999. 105.0 Voltage transformer(VT) Ra-
LV VT Ratio
tio in LV side
A 50.00 9999. 3000.0 CT Primary(PRI) current in
LV CT Pri
LV side
A 1.000 5.000 1.0 CT Secondary(SEC) current
LV CT Sec
in LV side
LV Sec Inside A 1.000 5.000 1.0 CT Secondary(SEC) cur-
Delta rent in LV inside delta
A 0 9999 Rated primary current for
HV Rated Cur Pri
HV side (calculated value,

293
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
read only)
A 0 9999 Rated secondary current for
HV Rated Cur Sec HV side (calculated value,
read only)
0 9999 HV ratio factor for differen-
Ratio Factor KTAH tial protection (calculated
value, read only)
0 9999 MV ratio factor for differen-
Ratio Factor KTAM tial protection (calculated
value, read only)
0 9999 LV ratio factor for differential
Ratio Factor KTAL protection (calculated
value, read only)
0 9999 HV ratio factor, with ze-
ro-sequence current calcu-
Ratio REF KTAH lated, for REF protection
(calculated value, read
only)
0 9999 HV ratio factor with ze-
ro-sequence current directly
Ratio REF KNH measured, for REF protec-
tion (calculated value,
read only)
0 9999 MV ratio factor, with ze-
ro-sequence current calcu-
Ratio REF KTAM lated, for REF protection
(calculated value, read
only)
0 9999 MV ratio factor with ze-
ro-sequence current directly
Ratio REF KNM measured, for REF protec-
tion (calculated value,
read only)
A 0.5Ir 20Ir 20 Setting value of differential
I_Inst Diff instant tripping current
(ID>>)

294
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
A 0.08Ir 4Ir 2.1 Percentage Differential
I_Percent Diff
(ID>) current setting
A 0.1Ir Ir 2 The 1st breakpoint restraint
I_ResPoint1 Diff
current (IR1)
A 0.1Ir 10Ir 2 The 2nd breakpoint re-
I_ResPoint2 Diff
straint current (IR2)
Slope1_Diff 0 0.2 0.2 the 1st slope

Slope2_Diff 0.2 0.7 0.5 the 2nd slope

Slope3_Diff 0.25 0.95 0.7 the 3rd slope


Ratio_2nd Harm 0.05 0.80 0.15 2nd harmonic(HAR) ratio
0.05 0.80 0.35 3rd / 5th harmonic(HAR)
Ratio_3/5th Harm
ratio
s 0 20 20 Within the delay 2nd har-
monic block all three phas-
T_2nd Harm Block es. After the delay, then
only the local phase is
blocked.
s 0 20 20 Within the delay 5th har-
monic block all three phas-
T_3/5th Harm
es. After the delay, then
Block
only the local phase is
blocked.
A 0.08Ir 2Ir 2 Current setting for HV Re-
HV 3I0_REF stricted Earth Fault protec-
tion
0.2 0.95 0.5 Slope setting for HV Re-
HV Slope_REF stricted Earth Fault protec-
tion
s 0 60 0.03 HV Restricted Earth Fault
HV T_REF Trip
trip time setting
A 0.08Ir 2Ir 2 HV Restricted Earth Fault
HV 3I0_REF Alarm
alarm current setting
s 0 60 0.03 HV Restricted Earth Fault
HV T_REF Alarm
alarm time setting
MV 3I0_REF A 0.08Ir 2Ir 2 Current setting for MV Re-

295
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
stricted Earth Fault protec-
tion
0.2 0.95 0.5 Slope setting for MV Re-
MV Slope_REF stricted Earth Fault protec-
tion
s 0 60 0.03 MV Restricted Earth Fault
MV T_REF Trip
trip time setting
MV 3I0_REF A 0.08Ir 2Ir 2 MV Restricted Earth Fault
Alarm alarm current setting
s 0 60 0.03 MV Restricted Earth Fault
MV T_REF Alarm
alarm time setting
A 0.08Ir 2Ir 2 Current setting for LV Re-
LV 3I0_REF stricted Earth Fault protec-
tion
0.2 0.95 0.5 Slope setting for LV Re-
LV Slope_REF stricted Earth Fault protec-
tion
s 0 60 0.03 LV Restricted Earth Fault
LV T_REF Trip
trip time setting
A 0.08Ir 2Ir 2 LV Restricted Earth Fault
LV 3I0_REF Alarm
alarm current setting
s 0 60 0.03 LV Restricted Earth Fault
LV T_REF Alarm
alarm time setting
V 40 130 57.3 Nominal phase voltage in
Reference Voltage
HV side
1 1.5 1.1 Alarming setting of
V/F_Definite Alarm
volt/hertz
s 0.1 9999 10 Timer setting for volt/hertz
T_Definite Alarm
alarming stage
1 1.5 1.2 Tripping setting of definite
V/F_Definite Trip
volt/hertz stage
s 0.1 9999 1 Timer setting for definite
T_Definite Trip
volt/hertz stage
T1_Inverse s 0.1 9999 10 Timer setting for
V/F=1.05 volt/hertz=1.05
T2_Inverse s 0.1 9999 90 Timer setting for

296
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
V/F=1.10 volt/hertz=1.10

T3_Inverse s 0.1 9999 80 Timer setting for


V/F=1.15 volt/hertz=1.15
T4_Inverse s 0.1 9999 70 Timer setting for
V/F=1.20 volt/hertz=1.20
T5_Inverse s 0.1 9999 60 Timer setting for
V/F=1.25 volt/hertz=1.25
T6_Inverse s 0.1 9999 50 Timer setting for
V/F=1.30 volt/hertz=1.30
T7_Inverse s 0.1 9999 45 Timer setting for
V/F=1.35 volt/hertz=1.35
T8_Inverse s 0.1 9999 40 Timer setting for
V/F=1.40 volt/hertz=1.40
T9_Inverse s 0.1 9999 35 Timer setting for
V/F=1.45 volt/hertz=1.45
T10_Inverse s 0.1 9999 30 Timer setting for
V/F=1.50 volt/hertz=1.50
s 0.1 9999 25 Cool down time delay for
T_Cool Down
overexcitation protection
A 0.05Ir 20Ir 5 HV overcurrent (O/C) cur-
HV I_OC1
rent setting for Stage 1
s 0 60 60 Time setting for HV OC,
HV T_OC1
Stage 1
A 0.05Ir 20Ir 5 HV overcurrent (O/C) cur-
HV I_OC2
rent setting for Stage 2
s 0 60 60 Time setting for HV OC,
HV T_OC2
Stage 2
HV Curve_OC Inv 1 12 1 Ref to IEC and ANSI
Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
HV I_OC Inv
Curves
0.05 999 1 Ref to IEC and ANSI
HV K_OC Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
HV A_OC Inv
Curves

297
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
s 0 60 0 Ref to IEC and ANSI
HV B_OC Inv
Curves
0 10 0.02 Ref to IEC and ANSI
HV P_OC Inv
Curves
° 0 90 45 The angle setting for volt-
HV Angle_OC
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
HV -harmonic current setting to
Imax_2H_UnBlk remove the inrush block, in
HV O/C protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
HV Ratio_I2/I1 setting for blocking HV O/C
protection
s 0 60 20 Inrush 2nd harmonic
HV T2h_Cross_Blk cross-block time for HV O/C
protection
A 0.05Ir 20Ir 5 MV overcurrent (O/C) cur-
MV I_OC1
rent setting for Stage 1
s 0 60 60 Time setting for MV OC,
MV T_OC1
Stage 1
A 0.05Ir 20Ir 5 MV overcurrent (O/C) cur-
MV I_OC2
rent setting for Stage 2
s 0 60 60 Time setting for MV OC,
MV T_OC2
Stage 2
MV Curve_OC Inv 1 12 1 Ref to IEC and ANSI
Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
MV I_OC Inv
Curves
0.05 999 1 Ref to IEC and ANSI
MV K_OC Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
MV A_OC Inv
Curves
s 0 60 0 Ref to IEC and ANSI
MV B_OC Inv
Curves
0 10 0.02 Ref to IEC and ANSI
MV P_OC Inv
Curves

298
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
° 0 90 45 The angle setting for volt-
MV Angle_OC
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
MV -harmonic current setting to
Imax_2H_UnBlk remove the inrush block, in
MV O/C protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
MV Ratio_I2/I1 setting for blocking MV O/C
protection
s 0 60 20 Inrush 2nd harmonic
MV
cross-block time for MV O/C
T2h_Cross_Blk
protection
A 0.05Ir 20Ir 5 LV overcurrent (O/C) cur-
LV I_OC1
rent setting for Stage 1
s 0 60 60 Time setting for LV OC,
LV T_OC1
Stage 1
A 0.05Ir 20Ir 5 LV overcurrent (O/C) cur-
LV I_OC2
rent setting for Stage 2
s 0 60 60 Time setting for LV OC,
LV T_OC2
Stage 2
MV Curve_OC Inv 1 12 1 Ref to IEC and ANSI
Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
LV I_OC Inv
Curves
0.05 999 1 Ref to IEC and ANSI
LV K_OC Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
LV A_OC Inv
Curves
s 0 60 0 Ref to IEC and ANSI
LV B_OC Inv
Curves
0 10 0.02 Ref to IEC and ANSI
LV P_OC Inv
Curves
0 90 45 The angle setting for volt-
LV Angle_OC
age ahead of current.
LV 0.25Ir 20Ir 5 The maximum 1st
Imax_2H_UnBlk -harmonic current setting to

299
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
remove the inrush block, in
LV O/C protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
LV Ratio_I2/I1 setting for blocking LV O/C
protection
0 60 20 Inrush 2nd harmonic
LV T2h_Cross_Blk cross-block time for LV O/C
protection
A 0.05Ir 20Ir 5 HV earth fault (E/F) protec-
HV 3I0_EF1 tion current setting for Stage
1
s 0 60 60 Time setting for HV E/F,
HV T_EF1
Stage 1
A 0.05Ir 20Ir 5 HV earth fault (E/F) current
HV 3I0_EF2
setting for Stage 2
s 0 60 60 Time setting for HV E/F,
HV T_EF2
Stage 2
1 12 1 Ref to IEC and ANSI
HV Curve_EF Inv
Curves
A 0.05Ir 20Ir 1.2 Ref to IEC and ANSI
HV 3I0_EF Inv
Curves
0.05 999 1 Ref to IEC and ANSI
HV K_EF Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
HV A_EF Inv
Curves
s 0 60 0 Ref to IEC and ANSI
HV B_EF Inv
Curves
0 10 0.02 Ref to IEC and ANSI
HV P_EF Inv
Curves
° 0 90 45 The angle setting for volt-
HV Angle_EF
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
HV
-harmonic current setting to
Imax_2H_UnBlk_E
remove the inrush block, in
F
HV EF protection
HV Ratio_I2/I1_EF 0.07 0.5 0.2 The maximum 1st

300
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
-harmonic current setting to
remove the inrush block, in
HV EF protection
A 0.05Ir 20Ir 5 MV earth fault (E/F) protec-
MV 3I0_EF1 tion current setting for Stage
1
s 0 60 60 Time setting for MV E/F,
MV T_EF1
Stage 1
A 0.05Ir 20Ir 5 MV earth fault (E/F) current
MV 3I0_EF2
setting for Stage 2
s 0 60 60 Time setting for MV E/F,
MV T_EF2
Stage 2
1 12 1 Ref to IEC and ANSI
MV Curve_EF Inv
Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
MV 3I0_EF Inv
Curves
0.05 999 1 Ref to IEC and ANSI
MV K_EF Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
MV A_EF Inv
Curves
s 0 60 0 Ref to IEC and ANSI
MV B_EF Inv
Curves
0 10 0.02 Ref to IEC and ANSI
MV P_EF Inv
Curves
° 0 90 45 The angle setting for volt-
MV Angle_EF
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
MV
-harmonic current setting to
Imax_2H_UnBlk_E
remove the inrush block, in
F
MV E/F protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
MV Ratio_I2/I1_EF setting for blocking MV E/F
protection
A 0.05Ir 20Ir 5 LV earth fault (E/F) protec-
LV 3I0_EF1 tion current setting for Stage
1

301
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
s 0 60 60 Time setting for LV E/F,
LV T_EF1
Stage 1
A 0.05Ir 20Ir 5 LV earth fault (E/F) current
LV 3I0_EF2
setting for Stage 2
s 0 60 60 Time setting for LV E/F,
LV T_EF2
Stage 2
1 12 1 Ref to IEC and ANSI
LV Curve_EF Inv
Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
LV 3I0_EF Inv
Curves
0.05 999 1 Ref to IEC and ANSI
LV K_EF Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
LV A_EF Inv
Curves
s 0 60 0 Ref to IEC and ANSI
LV B_EF Inv
Curves
0 10 0.02 Ref to IEC and ANSI
LV P_EF Inv
Curves
° 0 90 45 The angle setting for volt-
LV Angle_EF
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
LV
-harmonic current setting to
Imax_2H_UnBlk_E
remove the inrush block, in
F
LV E/F protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
LV Ratio_I2/I1_EF setting for blocking LV E/F
protection
A 0.05Ir 20Ir 5 HV neutral over-current
HV 3I0_Neutral
(NOC) protection current
OC1
setting for Stage 1
s 0 60 60 Time setting for HV NOC,
HV T_Neutral OC1
Stage 1
A 0.05Ir 20Ir 5 HV neutral over-current
HV 3I0_Neutral
(NOC) protection current
OC2
setting for Stage 2
HV T_Neutral OC2 s 0 60 60 Time setting for HV NOC,

302
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
Stage 1

HV Curve_NOC 1 12 1 Ref to IEC and ANSI


Inv Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
HV 3I0_NOC Inv
Curves
0.05 999 1 Ref to IEC and ANSI
HV K_NOC Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
HV A_NOC Inv
Curves
s 0 60 0 Ref to IEC and ANSI
HV B_NOC Inv
Curves
0 10 0.02 Ref to IEC and ANSI
HV P_NOC Inv
Curves
° 0 90 45 The angle setting for volt-
HV Angle_NOC
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
HV
-harmonic current setting to
Imax_2H_UnBlk_
remove the inrush block, in
NOC
HV NOC protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
HV Ra-
setting for blocking HV NOC
tio_I2/I1_NOC
protection
A 0.05Ir 20Ir 5 MV neutral over-current
MV 3I0_Neutral
(NOC) protection current
OC1
setting for Stage 1
s 0 60 60 Time setting for MV NOC,
MV T_Neutral OC1
Stage 1
A 0.05Ir 20Ir 5 MV neutral over-current
MV 3I0_Neutral
(NOC) protection current
OC2
setting for Stage 2
s 0 60 60 Time setting for MV NOC,
MV T_Neutral OC2
Stage 1
MV Curve_NOC 1 12 1 Ref to IEC and ANSI
Inv Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
MV 3I0_NOC Inv
Curves

303
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
0.05 999 1 Ref to IEC and ANSI
MV K_NOC Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
MV A_NOC Inv
Curves
s 0 60 0 Ref to IEC and ANSI
MV B_NOC Inv
Curves
0 10 0.02 Ref to IEC and ANSI
MV P_NOC Inv
Curves
° 0 90 45 The angle setting for volt-
MV Angle_NOC
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
MV
-harmonic current setting to
Imax_2H_UnBlk_
remove the inrush block, in
NOC
MV NOC protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
MV Ra-
setting for blocking MV
tio_I2/I1_NOC
NOC protection
A 0.05Ir 20Ir 5 LV neutral over-current
LV 3I0_Neutral
(NOC) protection current
OC1
setting for Stage 1
s 0 60 60 Time setting for LV NOC,
LV T_Neutral OC1
Stage 1
A 0.05Ir 20Ir 5 LV neutral over-current
LV 3I0_Neutral
(NOC) protection current
OC2
setting for Stage 2
s 0 60 60 Time setting for LV NOC,
LV T_Neutral OC2
Stage 1
1 12 1 Ref to IEC and ANSI
LV Curve_NOC Inv
Curves
A 0.05Ir 20Ir 5 Ref to IEC and ANSI
LV 3I0_NOC Inv
Curves
0.05 999 1 Ref to IEC and ANSI
LV K_NOC Inv
Curves
s 0 200 0.14 Ref to IEC and ANSI
LV A_NOC Inv
Curves
LV B_NOC Inv s 0 60 0 Ref to IEC and ANSI

304
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
Curves
0 10 0.02 Ref to IEC and ANSI
LV P_NOC Inv
Curves
° 0 90 45 The angle setting for volt-
LV Angle_NOC
age ahead of current.
A 0.25Ir 20Ir 5 The maximum 1st
LV
-harmonic current setting to
Imax_2H_UnBlk_
remove the inrush block, in
NOC
LV NOC protection
0.07 0.5 0.2 Inrush 2nd harmonic ratio
LV Ra-
setting for blocking LV NOC
tio_I2/I1_NOC
protection
HV I_Therm OL A 0.1Ir 5Ir 2 Setting for HV-side thermal
Trip overload trip-stage current
A 0.1Ir 5Ir 2 Setting for HV-side thermal
HV I_Therm OL
overload alarm-stage cur-
Alarm
rent
HV T_Const s 1 9999 10 Time const for HV-side
Therm thermal overload protection
HV T_Const Cool s 1 9999 10 Cool down time delay for
Down HV-side thermal overload
MV I_Therm OL A 0.1Ir 5Ir 2 Setting for MV-side thermal
Trip overload trip-stage current
A 0.1Ir 5Ir 2 Setting for MV-side thermal
MV I_Therm OL
overload alarm-stage cur-
Alarm
rent
MV T_Const s 1 9999 10 Time const for MV-side
Therm thermal overload protection
MV T_Const Cool s 1 9999 10 Cool down time delay for
Down MV-side thermal overload
A 0.1Ir 4Ir 2 Overcurrent Setting of
HV I_OverLoad
overload
HV T_OverLoad s 0.1 3600 10 Time setting for overload
A 0.1Ir 4Ir 2 Overcurrent Setting of
MV I_OverLoad
overload

305
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
MV T_OverLoad s 0.1 3600 10 Time setting for overload
A 0.1Ir 4Ir 2 Overcurrent Setting of
LV I_OverLoad
overload
LV T_OverLoad s 0.1 3600 10 Time setting for overload
A 0.1Ir 4Ir 20 Alarm current setting of LV
LW I_OvLd Alarm delta winding overload pro-
tection
s 0.1 3600 10 Alarm time setting of LV
LW T_OvLd Alarm delta winding overload pro-
tection
LW I_OvLd Low A 0.1Ir 4Ir 20 Low stage tripping current
Trip setting
LW T_OvLd Low s 0.1 3600 10 Low stage tripping time set-
Trip ting
LW I_OvLd High A 0.1Ir 4Ir 20 High stage tripping current
Trip setting
LW T_OvLd High s 0.1 3600 10 High stage tripping time
Trip setting
V 40 200 200 HV voltage setting for stage
HV U_OV1
1 of overvoltage protection
s 0 60 60 HV time setting for stage 1
HV T_OV1
of overvoltage protection
V 40 200 200 HV voltage setting for stage
HV U_OV2
2 of overvoltage protection
s 0 60 60 HV time setting for stage 2
HV T_OV2
of overvoltage protection
0.9 0.99 0.95 HV dropout ratio for over-
HV Dropout_OV
voltage protection
V 40 200 200 MV voltage setting for stage
MV U_OV1
1 of overvoltage protection
s 0 60 60 MV time setting for stage 1
MV T_OV1
of overvoltage protection
V 40 200 200 MV voltage setting for stage
MV U_OV2
2 of overvoltage protection
s 0 60 60 MV time setting for stage 2
MV T_OV2
of overvoltage protection

306
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
0.9 0.99 0.95 MV dropout ratio for over-
MV Dropout_OV
voltage protection
A 0.05Ir 20Ir 5 Phase current setting value
HV I_CBF OC for HVcircuit breaker failure
(CBF) protection
A 0.05Ir 20Ir 5 Negative sequence (NS)

HV 3I2_CBF NS current setting 3I 2 value

for HV CBF protection


A 0.05Ir 20Ir 5 Zero sequence (ZS) current

HV 3I0_CBF ZS 3I 0
setting value for HV1
CBF protection
s 0 32 10 Time setting value of Stage
HV T1_CBF
1, for HV CBF protection
s 0.1 32 10 Time setting value of Stage
HV T2_CBF
2, for HV CBF protection
A 0.05Ir 20Ir 5 Phase current setting value
MVI_CBF OC
for MV CBF protection
A 0.05Ir 20Ir 5 Negative sequence (NS)

MV 3I2_CBF NS current setting 3I 2 value

for MV CBF protection


A 0.05Ir 20Ir 5 Zero sequence (ZS) current

MV 3I0_CBF ZS 3I 0
setting value for MV
CBF protection
s 0 32 10 Time setting value of Stage
MV T1_CBF
1, for MV CBF protection
s 0.1 32 10 Time setting value of Stage
MV T2_CBF
2, for MV CBF protection
A 0.05Ir 20Ir 5 Phase current setting value
LV I_CBF OC
for LV CBF protection
A 0.05Ir 20Ir 5 Negative sequence (NS)

LV 3I2_CBF NS current setting 3I 2 value

for LV CBF protection

307
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
A 0.05Ir 20Ir 5 Zero sequence (ZS) current

LV 3I0_CBF ZS setting
3I 0 value for LV

CBF protection
s 0 32 10 Time setting value of Stage
LV T1_CBF
1, for LV CBF protection
s 0.1 32 10 Time setting value of Stage
LV T2_CBF
2, for LV CBF protection
HV T_Dead Zone s 0 32 10 Time delay setting for HV
dead zone protection
MV T_Dead Zone s 0 32 10 Time delay setting for MV
dead zone protection
LV T_Dead Zone s 0 32 10 Time delay setting for LV
dead zone protection
A 0.05Ir 20Ir 100 current threshold of stub
HV I_STUB
protection
s 0 60 60 delay time of stub protec-
HV T_STUB
tion
A 0.05Ir 20Ir 100 current threshold of stub
MV I_STUB
protection
s 0 60 60 delay time of stub protec-
MV T_STUB
tion
A 0.05Ir 20Ir 100 current threshold of stub
LV I_STUB
protection
s 0 60 60 delay time of stub protec-
LV T_STUB
tion
A 0.05Ir 20Ir 5 zero sequence current
HV 3I0_PD threshold of pole discord-
ance protection
A 0.05Ir 20Ir 5 negative sequence current
HV 3I2_PD threshold of pole discord-
ance protection
s 0 60 10 delay time of pole discord-
HV T_PD
ance protection
A 0.05Ir 20Ir 5 zero sequence current
MV 3I0_PD
threshold of pole discord-

308
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
ance protection
A 0.05Ir 20Ir 5 negative sequence current
MV 3I2_PD threshold of pole discord-
ance protection
s 0 60 10 delay time of pole discord-
MV T_PD
ance protection
A 0.05Ir 0.2Ir 0.05 Minimum Current of VT
HV I_VT Fail
failure for HV side
A 0.05Ir 0.2Ir 0.5 Minimum zero or negative
HV 3I02_ VT Fail
Current of HV VT fail
V 7 20 8 Maximum phase to earth
HV Upe_VT Fail
voltage of HV VT fail
V 10 30 16 Maximum phase to phase
HV Upp_VT Fail
voltage of HV VT fail
HV Upe_VT Nor- V 40 65 40 Minimum phase to phase
mal voltage of HV VT normal
A 0.05Ir 0.2Ir 0.05 Minimum Current of VT
MV I_VT Fail
failure for MV side
A 0.05Ir 0.2Ir 0.5 Minimum zero or negative
MV 3I02_VT Fail
Current of MV VT fail
V 7 20 8 Maximum phase to earth
MV Upe_VT Fail
voltage of MV VT fail
V 10 30 16 Maximum phase to phase
MV Upp_VT Fail
voltage of MV VT fail
MV Upe_VT Nor- V 40 65 40 Minimum phase to phase
mal voltage of MV VT normal
A 0.05Ir 0.2Ir 0.05 Minimum Current of VT
LV I_VT Fail
failure for LV side
A 0.05Ir 0.2Ir 0.5 Minimum zero or negative
LV 3I02_VT Fail
Current of LV VT fail
V 7 20 8 Maximum phase to earth
LV Upe_VT Fail
voltage of LV VT fail
V 10 30 16 Maximum phase to phase
LV Upp_VT Fail
voltage of LV VT fail
LV Upe_VT Nor- V 40 65 40 Minimum phase to phase
mal voltage of LV VT normal

309
Chapter 25 Appendix

Default
Min. Max.
setting
Setting Unit (Ir:5A/1 (Ir:5A/1 Description
(Ir:5A/1
A) A)
A)
s 0.2 5 5 delay time of stub protec-
T_Pulse Tripping
tion

1.2 Control word list

Table 249 Control word list

Default
Setting Unit Min. Max. Description
setting
Autotransformer not comm
on transformer
Auto Trans 0 1 0
1-autotransformer ;
0- not autotransformer
Two-Wind Trans Two-winding(TWO WIND )
not three -winding trans-
0 1 0 former (TRANS)
1-two-winding trans;
0-three-winding trans
CT Fail Detect VT Failure Detection On/Off
0 1 0
1-On, 0-Off.
Setting Default
Unit Min. Max. Description
setting
Func_Inst Diff Instantaneous differential
0 1 0
protection ON 1-on; 0-off.
Func_Percent Diff Percentage differential pro-
0 1 0
tection ON 1-on; 0-off.
Block Diff at Inrush Inrush block differential pro-
0 1 0 tection
1-block; 0-not block.
2nd Harm Not 2nd harmonic (HAR) inhibit
Wave not the fuzzy recognition
based on the wave-
0 1 0
form(WAVE)
1-2nd harmonic on; 0-
waveform on
Block Diff at Overexcitation block differ-
Overexcit 0 1 0 ential protection
1-block; 0-not block.

310
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Overexcit 3rd NOT Overexcitation stabilization
5th judgement
3rd or 5th harmonic (HAR)
0 1 0
inhibit on
1-3rd harmonic; 0-5th har-
monic.
Func_Diff Alarm Differential current (DIFF)
0 1 0 Alarming on
1-on; 0-off.
Block Diff at Block differential protection
CT_Fail 0 1 0 when there is CT failure
1-block; 0-not block.
HV D_side Elimi- Eliminate calculated 3I0
nate I0 when HV side winding is
0 1 0
connected in Delta mode
1- eliminate; 0-not eliminate
MV D_side Elimi- Eliminate calculated 3I0
nate I0 when MV side winding is
0 1 0
connected in Delta mode
1- eliminate; 0-not eliminate
LV D_side Elimi- Eliminate calculated 3I0
nate I0 when LV side winding is
0 1 0
connected in Delta mode
1- eliminate; 0-not eliminate
Diff Includes LV LV current is included in
Cur calculation of the differential
0 1 0 protection.
1- Diff Includes LV Cur;
0-Diff NOT Includes LV Cur
HV Func_REF Trip HV Restricted earth fault
0 1 0 trip-stage ON
1-on; 0-off.
HV Func_REF HV Restricted earth fault
Alarm 0 1 0 Alarm-stage ON
1-on; 0-off.
Block HV REF at Block HV REF when CT
HV CT_Fail 0 1 0 failure,
1-Block;0-unblock
MV Func_REF Trip MV Restricted earth fault
0 1 0
trip-stage ON 1-on; 0-off.
MV Func_REF 0 1 0 MV Restricted earth fault

311
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Alarm Alarm-stage ON
1-on; 0-off.
Block MV REF at Block MV REF when CT
MV CT_Fail 0 1 0 failure,
1-Block;0-unblock
LV Func_REF Trip LV Restricted earth fault
0 1 0
trip-stage ON 1-on; 0-off.
LV Func_REF LV Restricted earth fault
Alarm 0 1 0 Alarm-stage ON
1-on; 0-off.
Block LV REF at Block LV REF when CT fail-
LV CT_Fail 0 1 0 ure,
1-Block;0-unblock
HV HV Overexcitation (V/F) on
0 1 0
Func_Overexcit 1-on; 0-off.
MV MV Overexcitation (V/F) on
0 1 0
Func_Overexcit 1-on; 0-off.
LV Func_Overexcit LV Overexcitation (V/F) on
0 1 0
1-on; 0-off.
Func_Overexcit Definite Overexcitation (V/F)
Alarm Def 0 1 0 Alarming on
1-on; 0-off.
Func_Overexcit Definite (DEF)Overexcitation
Trip Def 0 1 0 (V/F) on
1-on; 0-off.
Func_Overexcit Inverse (IVR)Overexcitation
Trip Inv 0 1 0 (V/F) on
1-on; 0-off.
V/F Volt- Overexcitation protection
age(0-VPP,1-VPN) uses phase-to-phase volt-
0 1 0 age (VPP) or phase-to-earth
voltage (VPN)
0-VPP; 1-VPN.
HV Func_OC1 The 1st stage of HV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
HV OC1 Direction Direction (DIR) detection of
HV OC Stage 1 is switched
0 1 0
ON
1-on; 0-off.

312
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
HV OC1 Dir To Sys Direction unit of HV OC
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV OC1 Inrush Inrush 2nd harmonic detec-
Block tion HV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
HV Func_OC2 The 2nd stage of HV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
HV OC2 Direction Direction (DIR) detection of
HV OC Stage 2 is switched
0 1 0
ON
1-on; 0-off.
HV OC2 Dir To Sys Direction unit of HV OC
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV OC2 Inrush Inrush 2nd harmonic detec-
Block tion HV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
HV Func_OC Inv The IDMTL inverse time
stage of HV OC protection is
0 1 0
switched ON
1-on; 0-off.
HV OC Inv Direc- Direction (DIR) detection of
tion HV OC IDMTL inverse time
0 1 0
is switched ON
1-on; 0-off.
HV OC Inv Dir To Direction unit of HV OC ID-
Sys MTL inverse time points to
system
0 1 0
0 - point to the protected
transformer
1- point to system
HV OC Inv Inrush 0 1 0 Inrush 2nd harmonic detec-

313
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Block tion HV OC IDMTL inverse
time is switched ON
1-on; 0-off.
Block HV OC at Select to block HV OC pro-
HV VT_Fail tection or exit direction unit,
when HV VT fails
0 1 0
0- HV Direct OK at HV VT
Fail
1- Blk HV OC at HV VT Fail
HV OC Initiate LV HV OC protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
HV OC Initiate MV HV OC protection initiate MV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
MV Func_OC1 The 1st stage of MV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
MV OC1 Direction Direction (DIR) detection of
MV OC Stage 1 is switched
0 1 0
ON
1-on; 0-off.
MV OC1 Dir To Direction unit of MV OC
Sys Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
MV OC1 Inrush Inrush 2nd harmonic detec-
Block tion MV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
MV Func_OC2 The 2nd stage of MV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
MV OC2 Direction Direction (DIR) detection of
MV OC Stage 2 is switched
0 1 0
ON
1-on; 0-off.
MV OC2 Dir To 0 1 0 Direction unit of MV OC

314
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Sys Stage 2 points to system
0 - point to the protected
transformer
1- point to system
MV OC2 Inrush Inrush 2nd harmonic detec-
Block tion MV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
MV Func_OC Inv The IDMTL inverse time
stage of MV OC protection is
0 1 0
switched ON
1-on; 0-off.
MV OC Inv Direc- Direction (DIR) detection of
tion MV OC IDMTL inverse time
0 1 0
is switched ON
1-on; 0-off.
MV OC Inv Dir To Direction unit of MV OC
Sys IDMTL inverse time points to
system
0 1 0
0 - point to the protected
transformer
1- point to system
MV OC Inv Inrush Inrush 2nd harmonic detec-
Block tion MV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block MV OC at Select to block MV OC pro-
MV VT_Fail tection or exit direction unit,
when MV VT fails
0 1 0
0- MV Direct OK at MV VT
Fail
1- Blk MV OC at MV VT Fail
MV OC Initiate MV OC protection initiate
HV1 CBF 0 1 0 HV1 side CBF
0 - initiate, 1 – not initiate
LV Func_OC1 The 1st stage of LV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
LV OC1 Direction Direction (DIR) detection of
0 1 0
LV OC Stage 1 is switched

315
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
ON
1-on; 0-off.
LV OC1 Dir To Sys Direction unit of LV OC
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
LV OC1 Inrush Inrush 2nd harmonic detec-
Block tion LV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
LV Func_OC2 The 2nd stage of LV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
LV OC2 Direction Direction (DIR) detection of
LV OC Stage 2 is switched
0 1 0
ON
1-on; 0-off.
LV OC2 Dir To Sys Direction unit of LV OC
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
LV OC2 Inrush Inrush 2nd harmonic detec-
Block tion LV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
LV Func_OC Inv The IDMTL inverse time
stage of LV OC protection is
0 1 0
switched ON
1-on; 0-off.
LV OC Inv Direc- Direction (DIR) detection of
tion LV OC IDMTL inverse time is
0 1 0
switched ON
1-on; 0-off.
LV OC Inv Dir To Direction unit of LV OC ID-
Sys MTL inverse time points to
0 1 0 system
0 - point to the protected
transformer

316
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1- point to system

LV OC Inv Inrush Inrush 2nd harmonic detec-


Block tion LV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block LV OC at LV Select to block LV OC pro-
VT_Fail tection or exit direction unit,
0 1 0 when LV VT fails
0- LV Direct OK at LV VT Fail
1- Blk LV OC at LV VT Fail
LV OC Initiate HV1 LV OC protection initiate
CBF 0 1 0 HV1 side CBF
0 - initiate, 1 – not initiate
HV Func_EF1 The 1st stage of HV earth
fault (EF_1) protection is
0 1 0
switched ON
1-on; 0-off.
HV EF1 Direction Direction (DIR) detection of
HV EF Stage 1 is switched
0 1 0
ON
1-on; 0-off.
HV EF1 Dir To Sys Direction unit of HV EF
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV EF1 Inrush Inrush 2nd harmonic detec-
Block tion HV EF Stage 1 is
0 1 0
switched ON
1-on; 0-off.
HV Func_EF2 The 2nd stage of HV earth
fault (EF_2) protection is
0 1 0
switched ON
1-on; 0-off.
HV EF2 Direction Direction (DIR) detection of
HV EF Stage 2 is switched
0 1 0
ON
1-on; 0-off.
HV EF2 Dir To Sys Direction unit of HV EF
0 1 0 Stage 2 points to system
0 - point to the protected

317
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
transformer
1- point to system
HV EF2 Inrush Inrush 2nd harmonic detec-
Block tion HV EF Stage 2 is
0 1 0
switched ON
1-on; 0-off.
HV Func_EF Inv The IDMTL inverse time
stage of HV EF protection is
0 1 0
switched ON
1-on; 0-off.
HV EF Inv Direc- Direction (DIR) detection of
tion HV EF IDMTL inverse time is
0 1 0
switched ON
1-on; 0-off.
HV EF Inv Dir To Direction unit of HV EF ID-
Sys MTL inverse time points to
system
0 1 0
0 - point to the protected
transformer
1- point to system
HV EF Inv Inrush Inrush 2nd harmonic detec-
Block tion HV EF IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block HV EF at HV Select to block HV EF pro-
VT_Fail tection or exit direction unit,
when HV VT fails
0 1 0
0 - HV Direct OK at HV VT
Fail
1 - Blk HV EF at HV VT Fail
Block HV EF at HV Block HV EF when there is
CT_Fail 0 1 0 HV CT failure
1-Block; 0-NOT block
HV EF Initiate LV HV EF protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
HV EF Initiate MV HV EF protection initiate MV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
MV Func_EF1 The 1st stage of MV earth
0 1 0
fault (EF_1) protection is

318
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
switched ON
1-on; 0-off.
MV EF1 Direction Direction (DIR) detection of
MV EF Stage 1 is switched
0 1 0
ON
1-on; 0-off.
MV EF1 Dir To Sys Direction unit of MV EF
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
MV EF1 Inrush Inrush 2nd harmonic detec-
Block tion MV EF Stage 1 is
0 1 0
switched ON
1-on; 0-off.
MV Func_EF2 The 2nd stage of MV earth
fault (EF_2) protection is
0 1 0
switched ON
1-on; 0-off.
MV EF2 Direction Direction (DIR) detection of
MV EF Stage 2 is switched
0 1 0
ON
1-on; 0-off.
MV EF2 Dir To Sys Direction unit of MV EF
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
MV EF2 Inrush Inrush 2nd harmonic detec-
Block tion MV EF Stage 2 is
0 1 0
switched ON
1-on; 0-off.
MV Func_EF Inv The IDMTL inverse time
stage of MV EF protection is
0 1 0
switched ON
1-on; 0-off.
MV EF Inv Direc- Direction (DIR) detection of
tion MV EF IDMTL inverse time
0 1 0
is switched ON
1-on; 0-off.
MV EF Inv Dir To 0 1 0 Direction unit of MV EF ID-

319
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Sys MTL inverse time points to
system
0 - point to the protected
transformer
1- point to system
MV EF Inv Inrush Inrush 2nd harmonic detec-
Block tion MV EF IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block MV EF at Select to block MV EF pro-
MV VT_Fail tection or exit direction unit,
when MV VT fails
0 1 0
0 - MV Direct OK at MV VT
Fail
1 - Blk MV EF at MV VT Fail
Block MV EF at Block MV EF when there is
MV CT_Fail 0 1 0 MV CT failure
1-Block; 0-NOT block
MV EF Initiate HV MV EF protection initiate
CBF 0 1 0 HV1 side CBF
0 - initiate, 1 – not initiate
LV Func_EF1 The 1st stage of LV earth
fault (EF_1) protection is
0 1 0
switched ON
1-on; 0-off.
LV EF1 Direction Direction (DIR) detection of
LV EF Stage 1 is switched
0 1 0
ON
1-on; 0-off.
LV EF1 Dir To Sys Direction unit of LV EF Stage
1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
LV EF1 Inrush Inrush 2nd harmonic detec-
Block tion LV EF Stage 1 is
0 1 0
switched ON
1-on; 0-off.
LV Func_EF2 The 2nd stage of LV earth
0 1 0 fault (EF_2) protection is
switched ON

320
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-on; 0-off.

LV EF2 Direction Direction (DIR) detection of


LV EF Stage 2 is switched
0 1 0
ON
1-on; 0-off.
LV EF2 Dir To Sys Direction unit of LV EF Stage
2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
LV EF2 Inrush Inrush 2nd harmonic detec-
Block tion LV EF Stage 2 is
0 1 0
switched ON
1-on; 0-off.
LV Func_EF Inv The IDMTL inverse time
stage of LV EF protection is
0 1 0
switched ON
1-on; 0-off.
LV EF Inv Direction Direction (DIR) detection of
LV EF IDMTL inverse time is
0 1 0
switched ON
1-on; 0-off.
LV EF Inv Dir To Direction unit of LV EF ID-
Sys MTL inverse time points to
system
0 1 0
0 - point to the protected
transformer
1- point to system
LV EF Inv Inrush Inrush 2nd harmonic detec-
Block tion LV EF IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block LV EF at LV Select to block LV EF pro-
VT_Fail tection or exit direction unit,
when LV VT fails
0 1 0
0 - LV Direct OK at LV VT
Fail
1 - Blk LV EF at LV VT Fail
Block LV EF at LV Block LV EF when there is
CT_Fail 0 1 0 LV CT failure
1-Block; 0-NOT block

321
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
LV EF Initiate HV LV EF protection initiate HV1
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
HV Func_Neu The 1st stage of HV neutral
OC1 OC (OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
HV Neu OC1 Di- Direction (DIR) detection of
rection HV neutral OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
HV Neu OC1 Dir Direction unit of HV neutral
To Sys OC Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV Neu OC1 In- Inrush 2nd harmonic detec-
rush Block tion HV neutral OC Stage 1
0 1 0
is switched ON
1-on; 0-off.
HV Func_Neu The 2nd stage of HV neutral
OC2 OC (OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
HV Neu OC2 Di- Direction (DIR) detection of
rection HV neutral OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
HV Neu OC2 Dir Direction unit of HV neutral
To Sys OC Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV Neu OC2 In- Inrush 2nd harmonic detec-
rush Block tion HV neutral OC Stage 2
0 1 0
is switched ON
1-on; 0-off.
HV Func_Neu OC The IDMTL inverse time
Inv stage of HV neutral OC pro-
0 1 0
tection is switched ON
1-on; 0-off.

322
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
HV Neu OC Inv Direction (DIR) detection of
Direction HV neutral OC IDMTL in-
0 1 0 verse time stage is switched
ON
1-on; 0-off.
HV Neu OC Inv Dir Direction unit of HV neutral
To Sys OC IDMTL inverse time
stage points to system
0 1 0
0 - point to the protected
transformer
1- point to system
HV Neu OC Inv Inrush 2nd harmonic detec-
Inrush Block tion HV neutral OC IDMTL
0 1 0 inverse time stage is
switched ON
1-on; 0-off.
Block HV NOC at Select to block HV neutral
HV VT_Fail OC protection or exit direc-
tion unit, when HV VT fails
0 1 0 0 - HV Direct OK at HV VT
Fail
1 - Blk HV NOC at HV VT
Fail
HV Neu OC Init HV neutral OC protection
MV CBF 0 1 0 initiate LV side CBF
0 - initiate, 1 – not initiate
MV Func_Neu The 1st stage of MV neutral
OC1 OC (OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
MV Neu OC1 Di- Direction (DIR) detection of
rection MV neutral OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
MV Neu OC1 Dir Direction unit of MV neutral
To Sys OC Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
MV Neu OC1 In- Inrush 2nd harmonic detec-
0 1 0
rush Block tion MV neutral OC Stage 1

323
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
is switched ON
1-on; 0-off.
MV Func_Neu The 2nd stage of MV neutral
OC2 OC (OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
MV Neu OC2 Di- Direction (DIR) detection of
rection MV neutral OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
MV Neu OC2 Dir Direction unit of MV neutral
To Sys OC Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
MV Neu OC2 In- Inrush 2nd harmonic detec-
rush Block tion MV neutral OC Stage 2
0 1 0
is switched ON
1-on; 0-off.
MV Func_Neu OC The IDMTL inverse time
Inv stage of MV neutral OC
0 1 0
protection is switched ON
1-on; 0-off.
MV Neu OC Inv Direction (DIR) detection of
Direction MV neutral OC IDMTL in-
0 1 0 verse time stage is switched
ON
1-on; 0-off.
MV Neu OC Inv Dir Direction unit of MV neutral
To Sys OC IDMTL inverse time
stage points to system
0 1 0
0 - point to the protected
transformer
1- point to system
MV Neu OC Inv Inrush 2nd harmonic detec-
Inrush Block tion MV neutral OC IDMTL
0 1 0 inverse time stage is
switched ON
1-on; 0-off.
Block MV NOC at Select to block MV neutral
0 1 0
MV VT_Fail OC protection or exit direc-

324
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
tion unit, when MV VT fails
0 - MV Direct OK at MV VT
Fail
1 - Blk MV NOC at MV VT
Fail
MV Neu OC Init MV neutral OC protection
MV CBF 0 1 0 initiate LV side CBF
0 - initiate, 1 – not initiate
LV Func_Neu OC1 The 1st stage of LV neutral
OC (OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
LV Neu OC1 Di- Direction (DIR) detection of
rection LV neutral OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
LV Neu OC1 Dir To Direction unit of LV neutral
Sys OC Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
LV Neu OC1 In- Inrush 2nd harmonic detec-
rush Block tion LV neutral OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
LV Func_Neu OC2 The 2nd stage of LV neutral
OC (OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
LV Neu OC2 Di- Direction (DIR) detection of
rection LV neutral OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
LV Neu OC2 Dir To Direction unit of LV neutral
Sys OC Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
LV Neu OC2 In- Inrush 2nd harmonic detec-
rush Block 0 1 0 tion LV neutral OC Stage 2 is
switched ON

325
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-on; 0-off.

LV Func_Neu OC The IDMTL inverse time


Inv stage of LV neutral OC pro-
0 1 0
tection is switched ON
1-on; 0-off.
LV Neu OC Inv Direction (DIR) detection of
Direction LV neutral OC IDMTL in-
0 1 0 verse time stage is switched
ON
1-on; 0-off.
LV Neu OC Inv Dir Direction unit of LV neutral
To Sys OC IDMTL inverse time
stage points to system
0 1 0
0 - point to the protected
transformer
1- point to system
LV Neu OC Inv Inrush 2nd harmonic detec-
Inrush Block tion LV neutral OC IDMTL
0 1 0 inverse time stage is
switched ON
1-on; 0-off.
Block LV NOC at Select to block LV neutral
LV VT_Fail OC protection or exit direc-
tion unit, when LV VT fails
0 1 0
0 - LV Direct OK at LV VT
Fail
1 - Blk LV NOC at LV VT Fail
LV Neu OC Init LV LV neutral OC protection
CBF 0 1 0 initiate LV side CBF
0 - initiate, 1 – not initiate
HV Func_Thermal Thermal overload in HV side
OvLd 0 1 0 is switched on
0 - OFF, 1 - ON
HV Cold Curve HV side using hot/cold curve
0 1 0 type
0 – Hot curve, 1 – Cold curve
HV Thermal Init LV HV thermal overload protec-
CBF 0 1 0 tion initiate LV side CBF
0 - initiate, 1 – not initiate
HV Thermal Init HV thermal overload protec-
0 1 0
MV CBF tion initiate MV side CBF

326
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
0 - initiate, 1 – not initiate

MV Func_Thermal Thermal overload in MV side


OvLd 0 1 0 is switched on
0 - OFF, 1 - ON
MV Cold Curve MV side using hot/cold curve
0 1 0 type
0 – Hot curve, 1 – Cold curve
MV Thermal Init MV thermal overload protec-
HV1 CBF 0 1 0 tion initiate HV side CBF
0 - initiate, 1 – not initiate
HV Overload (LOAD) protection
Func_OverLoad 0 1 0 in HV side is switched ON
1-on; 0-off.
MV Overload (LOAD)in MV side
0 1 0
Func_OverLoad on
LV Overload (LOAD)in LV side
0 1 0
Func_OverLoad on
LW Func_OvLd Alarm stage of LV delta
Alarm winding (LWIND) overload
0 1 0 (LOAD) protection is
switched ON.
1-on; 0-off.
LW Func_OvLd Low-setting trip stage of LV
Low Trip delta winding overload pro-
0 1 0
tection is switched ON.
1-on; 0-off.
LW Func_OvLd High-setting trip stage of LV
High Trip delta winding overload pro-
0 1 0
tection is switched ON.
1-on; 0-off.
Low Trip Init HV1 Low-setting trip stage of LV
CBF delta winding overload pro-
0 1 0
tection initiate HV1 side CBF
0 - initiate, 1 – not initiate
High Trip Init HV1 High-setting trip stage of LV
CBF delta winding overload pro-
0 1 0
tection initiate HV1 side CBF
0 - initiate, 1 – not initiate
Low Trip Init MV Low-setting trip stage of LV
CBF 0 1 0 delta winding overload pro-
tection initiate MV side CBF

327
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
0 - initiate, 1 – not initiate

High Trip Init MV High-setting trip stage of LV


CBF delta winding overload pro-
0 1 0
tection initiate MV side CBF
- initiate, 1 – not initiate
HV Func_OV1 HV overvoltage stage 1 en-
0 1 0
abled or disabled
HV Func_OV2 HV overvoltage stage 1 trip
0 1 0
or alarm
HV Func_OV2 HV overvoltage stage 2 en-
0 1 0
abled or disabled
HV OV2 Trip HV overvoltage stage 2 trip
0 1 0
or alarm
HV OV Chk PE HV phase to phase voltage
0 1 0 or phase to earth measured
for overvoltage protection
MV Func_OV1 MV overvoltage stage 1 en-
0 1 0
abled or disabled
MV Func_OV2 MV overvoltage stage 1 trip
0 1 0
or alarm
MV Func_OV2 MV overvoltage stage 2 en-
0 1 0
abled or disabled
MV OV2 Trip MV overvoltage stage 2 trip
0 1 0
or alarm
MV OV Chk PE MV phase to phase voltage
0 1 0 or phase to earth measured
for overvoltage protection
HV Func_CBF HV Circuit breaker failure
(CBF) protection is switched
0 1 0
ON
1-on; 0-off.
HV 3I0/3I2 Check HV CBF protection detect
On negative or zero sequence
0 1 0
current 3I0 or 3I2.
1-Detect; 0- Not Detect
HV CB Status HV CBF protection detect
Check On 0 1 0 HV1 CB status
1-Detect; 0- Not Detect
MV Func_CBF MV Circuit breaker failure
0 1 0
(CBF) protection is switched

328
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
ON
1-on; 0-off.
MV 3I0/3I2 Check MV CBF protection detect
On negative or zero sequence
0 1 0
current 3I0 or 3I2.
1-Detect; 0- Not Detect
MV CB Status MV CBF protection detect
Check On 0 1 0 MV CB status
1-Detect; 0- Not Detect
LV Func_CBF LV Circuit breaker failure
(CBF) protection is switched
0 1 0
ON
1-on; 0-off.
LV 3I0/3I2 Check LV CBF protection detect
On negative or zero sequence
0 1 0
current 3I0 or 3I2.
1-Detect; 0- Not Detect
LV CB Status LV CBF protection detect LV
Check On 0 1 0 CB status
1-Detect; 0- Not Detect
HV Func_Dead Dead zone protection is
Zone 0 1 0 switched ON
1-on; 0-off.
MV Func_Dead Dead zone protection is
Zone 0 1 0 switched ON
1-on; 0-off.
LV Func_Dead Dead zone protection is
Zone 0 1 0 switched ON
1-on; 0-off.
HV Func_STUB Enable or disable stub pro-
0 1 0
tection
HV STUB Init LV stub protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
HV STUB Init MV stub protection initiate HV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
MV Func_STUB Enable or disable stub pro-
0 1 0
tection
MV STUB Init LV stub protection initiate LV
0 1 0
CBF side CBF

329
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
0 - initiate, 1 – not initiate

MV STUB Init MV Stub protection initiate MV


CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
LV Func_STUB Enable or disable stub pro-
0 1 0
tection
LV STUB Init LV stub protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
LV STUB Init MV stub protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
MV Func_PD Enable or disable MV poles
0 1 0
discordance protection
MV PD Chk 3I0/3I2 Enable or disable 3I0/3I2
0 1 0
criteria
MV Func_PD Enable or disable MV poles
0 1 0
discordance protection
MV PD Chk 3I0/3I2 Enable or disable 3I0/3I2
0 1 0
criteria
HV VT FAIL Detect HV VT Failure Detection
0 0 1 On/Off
1-On, 0-Off.
HV Solid Earth HV Earthing mode:
1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
MV VT FAIL Detect MV VT Failure Detection
0 0 1 On/Off
1-On, 0-Off.
MV Solid Earth MV Earthing mode:
1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
LV VT FAIL Detect LV VT Failure Detection
0 0 1 On/Off
1-On, 0-Off.
LV Solid Earth LV Earthing mode:
0 0 1 1: Solid earthed system ;
0: isolated system or re-

330
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
sistance earthed.

To select whether the 1st


binary input (BI1) trip the 1st
BI1 Enable BO1 0 0 1
binary output (BO1) or not.
1-On, 0-Off
To select BO1 tripping in
pulse mode or in direct mode
BO1 Pulse Trip- 0- BO1 Direct Tripping,
0 0 1
ping without delay
1- BO1 Pulse Tripping, with
preset delay time
To select whether the 2nd
binary input (BI2) trip the 2nd
BI2 Enable BO2 0 0 1
binary output (BO2) or not.
1-On, 0-Off
To select BO2 tripping in
pulse mode or in direct mode
BO2 Pulse Trip- 0- BO2 Direct Tripping,
0 0 1
ping without delay
1- BO2 Pulse Tripping, with
preset delay time
whether BI1 initiate HV side
BI1 Init HV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI1 initiate MV side
BI1 Init MV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI1 initiate LV side
BI1 Init LV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate HV side
BI2 Init HV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate MV side
BI2 Init MV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate LV side
BI2 Init LV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate

331
Chapter 25 Appendix

1.3 Table of setting values

1.3.1 CSC-326 (M02) setting value

Table 250 CSC-326 M02 setting value

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
HV Wind Conn/Y-0 0 1 0 High voltage side
D-1 winding connection
0:star-type connec-
tion 1:delta-type
connection
MV Wind Conn/Y-0 0 1 0 Middle voltage side-
D-1 winding connection
0:star-type connec-
tion 1:delta-type
connection
LV Wind Conn/Y-0 0 1 1 Low voltage side-
D-1 winding connection
0:star-type connec-
tion 1:delta-type
connection
Vet Grp Angle 0 12. 11 Vector Group An-
gle( VET GRP AN-
GLE)
SN MVA 1.000 3000. 120 Rated capacity of
transformer
HV UN 1.000 9999. 2200.0 High voltage side
VTchange
A 50.00 9999. 1200.0 High voltage side CT
HV CT Pri
primary value
A 1.000 5.000 1.0 High voltage side CT
HV CT Sec
secondary value
HV Voltage Chan 1 3 1 High voltage side
Sel channel selection
MV Voltage Chan 1 3 2 Middle voltage side
Sel channel selection
A 50.00 9999. 1200.0 Neutral CT (NCT)
HV NCT Pri(REF) Primary(PRI) current
in HV side for REF

332
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
A 1.000 5.000 1.0 Neutral CT (NCT)
Secondary(SEC)
HV NCT Sec(REF)
current in HV side for
REF
A 50.00 9999. 1200.0 Neutral CT (NCT)
Primary(PRI) current
HV NCT Pri(BU)
in HV side for backup
protection
A 1.000 5.000 1.0 Neutral CT (NCT)
Secondary(PRI) cur-
HV NCT Sec(BU)
rent in HV side for
backup protection
kV 1.000 1000. 110.0 Middle voltage sider-
MV UN
ated voltage
1.000 9999. 1100.0 Middle voltage side
MV VT Ratio
VT ratio
A 50.00 9999. 1200.0 Middle voltage CT
MV CT Pri
primary value
A 1.000 5.000 1.0 Middle voltage CT
MV NCT Sec(REF)
secondary value
A 50.00 9999. 1200.0 Middle voltage re-
MV NCT Pri(REF) stricted earth fault
primary value
A 1.000 5.000 1.0 Middle voltage
MV NCT Sec(REF) re-stricted earth fault
secondary value
A 50.00 9999. 1200.0 Middle voltage
re-stricted earth
MV NCT Pri(BU)
fault(backup) primary
value
A 1.000 5.000 1.0 Neutral CT (NCT)
Secondary(PRI) cur-
MV NCT Sec(BU)
rent in MV side for
backup protection
kV 1.000 1000. 10.50 Nominal voltage (UN)
LV UN in Low voltage
(LV)side
1.000 9999. 105.0 Voltage transform-
LV VT Ratio er(VT) Ratio in LV
side
LV CT Pri A 50.00 9999. 3000.0 Low voltage side CT

333
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
primary value

A 1.000 5.000 1.0 Low voltage side CT


LV CT Sec
secondary value
A 1.000 5.000 1.0 CT Secondary(SEC)
LV Sec Inside
current in LV inside
Delta
delta
A 0 9999 Rated primary cur-
rent for HV side
HV Rated Cur Pri
(calculated value,
read only)
A 0 9999 Rated secondary
current for HV side
HV Rated Cur Sec
(calculated value,
read only)
0 9999 HV ratio factor for
differen-tial protec-
Ratio Factor KTAH
tion (calculated val-
ue, read only)
0 9999 MV ratio factor for
differential protection
Ratio Factor KTAM
(calculated value,
read only)
0 9999 LV ratio factor for
differential protection
Ratio Factor KTAL
(calculated value,
read only)
0 9999 HV ratio factor, with
zero-sequence cur-
rent calculated, for
Ratio REF KTAH
REF protection
(calculated value,
read only)
0 9999 HV ratio factor with
zero-sequence cur-
rent directly meas-
Ratio REF KNH
ured, for REF pro-
tection (calculated
value, read only)

334
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
0 9999 MV ratio factor, with
zero-sequence cur-
rent calculated, for
Ratio REF KTAM
REF protection
(calculated value,
read only)
0 9999 MV ratio factor with
zero-sequence cur-
rent directly meas-
Ratio REF KNM
ured, for REF pro-
tection (calculated
value, read only)
Setting value of dif-
I_Inst Diff A 0.5Ir 20Ir 20 ferential instant trip-
ping current (ID>>)
Setting value of per-
centage differential
I_Percent Diff A 0.08Ir 4Ir 2.1
protection circuit
(ID>)
The 1st breakpoint
I_ResPoint1 Diff A 0.1Ir Ir 2
restraint current (IR1)
The 2nd breakpoint
I_ResPoint2 Diff A 0.1Ir 10Ir 2
restraint current (IR2)
First ratio restraint
Slope1_Diff 0 0.2 0.2
coefficient
Second ratio restraint
Slope2_Diff 0.2 0.7 0.5
coefficient
Third ratio restraint
Slope3_Diff 0.25 0.95 0.7
coefficient
2nd harmonic(HAR)
Ratio_2nd Harm 0.05 0.80 0.15
ratio
rd th
3 / 5 harmon-
Ratio_3/5th Harm 0.05 0.80 0.35
ic(HAR) ratio
Within the delay 2nd
harmonic block all
three phases. After
T_2nd Harm Block 0 20 20
s the delay, then only
the local phase is
blocked.
th
T_3/5th Harm s 0 20 20 Within the delay 5

335
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Block harmonic block all
three phases. After
the delay, then only
the local phase is
blocked.
Current setting for
HV 3I0_REF A 0.08Ir 2Ir 2 HV Restricted Earth
Fault protection
Slope setting for HV
HV Slope_REF 0.2 0.95 0.5 Re-stricted Earth
Fault pro-tection
HV Restricted Earth
HV T_REF Trip s 0 60 0.03 Fault trip time set-
ting
HV Restricted Earth
HV 3I0_REF Alarm A 0.08Ir 2Ir 2 Fault alarm current
setting
HV Restricted Earth
HV T_REF Alarm s 0 60 0.03 Fault alarm time set-
ting
Current setting for
MV 3I0_REF A 0.08Ir 2Ir 2 MV Restricted Earth
Fault protection
Slope setting for MV
MV Slope_REF 0.2 0.95 0.5 Restricted Earth
Fault protection
MV Restricted Earth
MV T_REF Trip s 0 60 0.03 Fault trip time set-
ting
MV Restricted Earth
MV 3I0_REF
A 0.08Ir 2Ir 2 Fault alarm current
Alarm
setting
MV Restricted Earth
MV T_REF Alarm s 0 60 0.03 Fault alarm time
setting
Nominal phase volt-
Reference Voltage V 40 130 57.3
age in HV side
Alarming setting of
V/F_Definite Alarm 1 1.5 1.1
volt/hertz

336
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Timer setting for
T_Definite Alarm s 0.1 9999 10 volt/hertz alarming
stage
Tripping setting of
V/F_Definite Trip 1 1.5 1.2 definite volt/hertz
stage
Timer setting for def-
T_Definite Trip s 0.1 9999 1
inite volt/hertz stage
T1_Inverse Timer setting for
s 0.1 9999 10
V/F=1.05 volt/hertz=1.05
T2_Inverse Timer setting for
s 0.1 9999 90
V/F=1.10 volt/hertz=1.10
T3_Inverse Timer setting for
s 0.1 9999 80
V/F=1.15 volt/hertz=1.15
T4_Inverse Timer setting for
s 0.1 9999 70
V/F=1.20 volt/hertz=1.20
T5_Inverse Timer setting for
s 0.1 9999 60
V/F=1.25 volt/hertz=1.25
T6_Inverse Timer setting for
s 0.1 9999 50
V/F=1.30 volt/hertz=1.30
T7_Inverse Timer setting for
s 0.1 9999 45
V/F=1.35 volt/hertz=1.35
T8_Inverse Timer setting for
s 0.1 9999 40
V/F=1.40 volt/hertz=1.40
T9_Inverse Timer setting for
s 0.1 9999 35
V/F=1.45 volt/hertz=1.45
T10_Inverse Timer setting for
s 0.1 9999 30
V/F=1.50 volt/hertz=1.50
Cool down time delay
T_Cool Down s 0.1 9999 25 for overexcitation
protection
HV overcurrent (O/C)
HV I_OC1 A 0.05Ir 20Ir 5 current setting for
Stage 1
Time setting for HV
HV T_OC1 s 0 60 60
OC, Stage 1
HV overcurrent (O/C)
HV I_OC2 A 0.05Ir 20Ir 5
current setting for

337
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Stage 2

Time setting for HV


HV T_OC2 s 0 60 60
OC, Stage 2
HV Curve_OC Inv Ref to IEC and ANSI
1 12 1
Curves
Ref to IEC and ANSI
HV I_OC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
HV K_OC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
HV A_OC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
HV B_OC Inv s 0 60 0
Curves
Ref to IEC and ANSI
HV P_OC Inv 0 10 0.02
Curves
The angle setting for
HV Angle_OC ° 0 90 45 voltage ahead of
current.
The maximum 1st
-harmonic current
HV
A 0.25Ir 20Ir 5 setting to remove the
Imax_2H_UnBlk
inrush block, in HV
O/C protection
nd
Inrush 2 harmonic
ratio setting for
HV Ratio_I2/I1 0.07 0.5 0.2
blocking HV O/C
protection
Inrush 2nd harmonic
HV T2h_Cross_Blk s 0 60 20 cross-block time for
HV O/C protection
MV overcurrent
MV I_OC1 A 0.05Ir 20Ir 5 (O/C) current setting
for Stage 1
Time setting for MV
MV T_OC1 s 0 60 60
OC, Stage 1
MV overcurrent
MV I_OC2 A 0.05Ir 20Ir 5 (O/C) current setting
for Stage 2

338
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Time setting for MV
MV T_OC2 s 0 60 60
OC, Stage 2
MV Curve_OC Inv Ref to IEC and ANSI
1 12 1
Curves
Ref to IEC and ANSI
MV I_OC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
MV K_OC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
MV A_OC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
MV B_OC Inv s 0 60 0
Curves
Ref to IEC and ANSI
MV P_OC Inv 0 10 0.02
Curves
The angle setting for
MV Angle_OC ° 0 90 45 voltage ahead of
current.
The maximum 1st
-harmonic current
MV
A 0.25Ir 20Ir 5 setting to remove the
Imax_2H_UnBlk
inrush block, in MV
O/C protection
Inrush 2nd harmonic
ratio setting for
MV Ratio_I2/I1 0.07 0.5 0.2
blocking MV O/C
protection
nd
Inrush 2 harmonic
MV
s 0 60 20 cross-block time for
T2h_Cross_Blk
MV O/C protection
LV overcurrent (O/C)
LV I_OC1 A 0.05Ir 20Ir 5 current setting for
Stage 1
Time setting for LV
LV T_OC1 s 0 60 60
OC, Stage 1
LV overcurrent (O/C)
LV I_OC2 A 0.05Ir 20Ir 5 current setting for
Stage 2
LV T_OC2 s 0 60 60 Time setting for LV

339
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
OC, Stage 2

MV Curve_OC Inv Ref to IEC and ANSI


1 12 1
Curves
Ref to IEC and ANSI
LV I_OC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
LV K_OC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
LV A_OC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
LV B_OC Inv s 0 60 0
Curves
Ref to IEC and ANSI
LV P_OC Inv 0 10 0.02
Curves
The angle setting for
LV Angle_OC 0 90 45 voltage ahead of
current.
The maximum 1st
-harmonic current
LV
0.25Ir 20Ir 5 setting to remove the
Imax_2H_UnBlk
inrush block, in LV
O/C protection
Inrush 2nd harmonic
ratio setting for
LV Ratio_I2/I1 0.07 0.5 0.2
blocking LV O/C
protection
Inrush 2nd harmonic
LV T2h_Cross_Blk 0 60 20 cross-block time for
LV O/C protection
HV earth fault (E/F)
HV 3I0_EF1 A 0.05Ir 20Ir 5 protection current
setting for Stage 1
Time setting for HV
HV T_EF1 s 0 60 60
E/F, Stage 1
HV earth fault (E/F)
HV 3I0_EF2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for HV
HV T_EF2 s 0 60 60
E/F, Stage 2

340
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Ref to IEC and ANSI
HV Curve_EF Inv 1 12 1
Curves
Ref to IEC and ANSI
HV 3I0_EF Inv A 0.05Ir 20Ir 1.2
Curves
Ref to IEC and ANSI
HV K_EF Inv 0.05 999 1
Curves
Ref to IEC and ANSI
HV A_EF Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
HV B_EF Inv s 0 60 0
Curves
Ref to IEC and ANSI
HV P_EF Inv 0 10 0.02
Curves
The angle setting for
HV Angle_EF ° 0 90 45 voltage ahead of
current.
The maximum 1st
HV -harmonic current
Imax_2H_UnBlk_E A 0.25Ir 20Ir 5 setting to remove the
F inrush block, in HV
EF protection
The maximum 1st
-harmonic current
HV Ratio_I2/I1_EF 0.07 0.5 0.2 setting to remove the
inrush block, in HV
EF protection
MV earth fault (E/F)
MV 3I0_EF1 A 0.05Ir 20Ir 5 protection current
setting for Stage 1
Time setting for MV
MV T_EF1 s 0 60 60
E/F, Stage 1
MV earth fault (E/F)
MV 3I0_EF2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for MV
MV T_EF2 s 0 60 60
E/F, Stage 2
Ref to IEC and ANSI
MV Curve_EF Inv 1 12 1
Curves
MV 3I0_EF Inv A 0.05Ir 20Ir 5 Ref to IEC and ANSI

341
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Curves

Ref to IEC and ANSI


MV K_EF Inv 0.05 999 1
Curves
Ref to IEC and ANSI
MV A_EF Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
MV B_EF Inv s 0 60 0
Curves
Ref to IEC and ANSI
MV P_EF Inv 0 10 0.02
Curves
The angle setting for
MV Angle_EF ° 0 90 45 voltage ahead of
current.
The maximum 1st
MV -harmonic current
Imax_2H_UnBlk_E A 0.25Ir 20Ir 5 setting to remove the
F inrush block, in MV
E/F protection
Inrush 2nd harmonic
ratio setting for
MV Ratio_I2/I1_EF 0.07 0.5 0.2
blocking MV E/F
protection
LV earth fault (E/F)
LV 3I0_EF1 A 0.05Ir 20Ir 5 protection current
setting for Stage 1
Time setting for LV
LV T_EF1 s 0 60 60
E/F, Stage 1
LV earth fault (E/F)
LV 3I0_EF2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for LV
LV T_EF2 s 0 60 60
E/F, Stage 2
Ref to IEC and ANSI
LV Curve_EF Inv 1 12 1
Curves
Ref to IEC and ANSI
LV 3I0_EF Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
LV K_EF Inv 0.05 999 1
Curves

342
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Ref to IEC and ANSI
LV A_EF Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
LV B_EF Inv s 0 60 0
Curves
Ref to IEC and ANSI
LV P_EF Inv 0 10 0.02
Curves
The angle setting for
LV Angle_EF ° 0 90 45 voltage ahead of
current.
st
The maximum 1
LV -harmonic current
Imax_2H_UnBlk_E A 0.25Ir 20Ir 5 setting to remove the
F inrush block, in LV
E/F protection
nd
Inrush 2 harmonic
ratio setting for
LV Ratio_I2/I1_EF 0.07 0.5 0.2
blocking LV E/F pro-
tection
HV neutral
HV 3I0_Neutral over-current (NOC)
A 0.05Ir 20Ir 5
OC1 protection current set-
ting for Stage 1
Time setting for HV
HV T_Neutral OC1 s 0 60 60
NOC, Stage 1
HV neutral
HV 3I0_Neutral over-current (NOC)
A 0.05Ir 20Ir 5
OC2 protection current set-
ting for Stage 2
Time setting for HV
HV T_Neutral OC2 s 0 60 60
NOC, Stage 1
HV Curve_NOC Ref to IEC and ANSI
1 12 1
Inv Curves
Ref to IEC and ANSI
HV 3I0_NOC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
HV K_NOC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
HV A_NOC Inv s 0 200 0.14
Curves

343
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Ref to IEC and ANSI
HV B_NOC Inv s 0 60 0
Curves
Ref to IEC and ANSI
HV P_NOC Inv 0 10 0.02
Curves
The angle setting for
HV Angle_NOC ° 0 90 45 voltage ahead of
current.
st
The maximum 1
HV -harmonic current
Imax_2H_UnBlk_ A 0.25Ir 20Ir 5 setting to remove
NOC the inrush block, in
HV NOC protection
Inrush 2nd harmonic
HV Ra- ratio setting for
0.07 0.5 0.2
tio_I2/I1_NOC blocking HV NOC
protection
MV neutral
MV 3I0_Neutral over-current (NOC)
A 0.05Ir 20Ir 5
OC1 protection current
setting for Stage 1
Time setting for MV
MV T_Neutral OC1 s 0 60 60
NOC, Stage 1
MV neutral
MV 3I0_Neutral over-current (NOC)
A 0.05Ir 20Ir 5
OC2 protection current
setting for Stage 2
Time setting for MV
MV T_Neutral OC2 s 0 60 60
NOC, Stage 1
MV Curve_NOC Ref to IEC and ANSI
1 12 1
Inv Curves
Ref to IEC and ANSI
MV 3I0_NOC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
MV K_NOC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
MV A_NOC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
MV B_NOC Inv s 0 60 0
Curves

344
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Ref to IEC and ANSI
MV P_NOC Inv 0 10 0.02
Curves
The angle setting for
MV Angle_NOC ° 0 90 45 voltage ahead of
current.
st
The maximum 1
MV -harmonic current
Imax_2H_UnBlk_ A 0.25Ir 20Ir 5 setting to remove
NOC the inrush block, in
MV NOC protection
Inrush 2nd harmonic
MV Ra- ratio setting for
0.07 0.5 0.2
tio_I2/I1_NOC blocking MV NOC
protection
Setting for HV-side
HV I_Therm OL
A 0.1Ir 5Ir 2 thermal overload
Trip
trip-stage current
Setting for HV-side
HV I_Therm OL
A 0.1Ir 5Ir 2 thermal overload
Alarm
alarm-stage current
Time const for
HV T_Const
s 1 9999 10 HV-side thermal
Therm
overload protection
Cool down time delay
HV T_Const Cool
s 1 9999 10 for HV-side thermal
Down
overload
HV voltage setting for
HV U_OV1 V 40 200 200 stage 1 of overvolt-
age protection
HV time setting for
HV T_OV1 s 0 60 60 stage 1 of overvolt-
age protection
HV voltage setting for
HV U_OV2 V 40 200 200 stage 2 of overvolt-
age protection
HV time setting for
HV T_OV2 s 0 60 60 stage 2 of overvolt-
age protection
HV Dropout_OV 0.9 0.99 0.95 HV dropout ratio for

345
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
overvoltage protec-
tion
HV I_VT Fail Minimum Current of
A 0.05Ir 0.2Ir 0.05 VT failure for HV side
Minimum zero or
HV 3I02_ VT Fail A 0.05Ir 0.2Ir 0.5 negative Current of
HV VT fail
Maximum phase to
HV Upe_VT Fail V 7 20 8 earth voltage of HV
VT fail
Maximum phase to
HV Upp_VT Fail V 10 30 16 phase voltage of HV
VT fail
HV Upe_VT Minimum phase to
Normal V 40 65 40 phase voltage of HV
VT normal
Minimum Current of
MV I_VT Fail A 0.05Ir 0.2Ir 0.05 VT failure for MV side
Minimum zero or
MV 3I02_VT Fail A 0.05Ir 0.2Ir 0.5 negative Current of
MV VT fail
Maximum phase to
MV Upe_VT Fail V 7 20 8 earth voltage of MV
VT fail
Maximum phase to
MV Upp_VT Fail V 10 30 16 phase voltage of MV
VT fail
MV Upe_VT Nor- Minimum phase to
V 40 65 40 phase voltage of MV
mal VT normal
Minimum Current of
LV I_VT Fail A 0.05Ir 0.2Ir 0.05 VT failure for LV side
Minimum zero or
LV 3I02_VT Fail A 0.05Ir 0.2Ir 0.5 negative Current of
LV VT fail
Maximum phase to
LV Upe_VT Fail V 7 20 8 earth voltage of LV
VT fail
Maximum phase to
LV Upp_VT Fail V 10 30 16 phase voltage of LV
VT fail
LV Upe_VT Nor- Minimum phase to
V 40 65 40 phase voltage of LV
mal VT normal
delay time of STUB
T_Pulse Tripping s 0.2 5 5
protection
Voltage setting for
U_UV1 V 5.00 150.0 40 undervoltage protec-
tion stage 1
Time setting for un-
T_UV1 s 0.00 120.00 0.3 dervoltage protection
stage 1

346
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Voltage setting for
U_UV2 V 5.00 150.0 45 undervoltage protec-
tion stage 2
Time setting for un-
T_UV2 s 0.00 120.00 0.6 dervoltage protection
stage 2
Dropout ratio for un-
Dropout_UV 1.01 2.00 1.05
dervoltage protection
Current setting for
I_UV_Chk A 0.05 10.00 0.1In
undervoltage
Neutral displacement
3U0_Neu Disp Alm V 2.00 100.0 10
voltage alarm
Setting value of ze-
T_Neu Disp Alm s 0.10 20.00 20.00 ro-sequence voltage
protection alarm time
Neutral displacement
3U0_Neu Disp Trip V 2.00 100.0 10
voltage alarm
Setting value of ze-
ro-sequence voltage
T_Neu Disp Trip s 0.10 20.00 20.00
protection tripping
time

1.3.2 CSC-326 (M02) control word list

Table 251 CSC-326 (M02) control word list

Default
Setting Unit Min. Max. Description
setting
CT Fail Detect VT Failure Detection On/Off
0 1 0
1-On, 0-Off.
Two-Wind Trans Two-winding(TWO WIND )
not three -winding trans-
0 1 0 former (TRANS)
1-two-winding trans;
0-three-winding trans
Autotransformer not comm
on transformer
Auto Trans 0 1 0
1-autotransformer ;
0- not autotransformer

347
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
LV current is included in
calculation of the differential
Diff Includes LV Cur 0 1 0 protection.
1- Diff Includes LV Cur;
0-Diff NOT Includes LV Cur
Eliminate calculated 3I0
LV D_side Eliminate when LV side winding is
0 1 0
I0 connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0
MV D_side Eliminate when MV side winding is
0 1 0
I0 connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0
HV D_side Eliminate when HV side winding is
0 1 0
I0 connected in Delta mode
1- eliminate; 0-not eliminate
Block differential protection
Block Diff at CT_Fail 0 1 0 when there is CT failure
1-block; 0-not block.
Differential current (DIFF)
Func_Diff Alarm 0 1 0 Alarming on
1-on; 0-off.
Overexcitation stabilization
judgement
Overexcit 3rd NOT 3rd or 5th harmonic (HAR)
th 0 1 0
5 inhibit on
rd th
1-3 harmonic; 0-5 har-
monic.
Block Diff at Overex- Overexcitation block differ-
cit 0 1 0 ential protection
1-block; 0-not block.
Block Diff at Overex- Overexcitation block differ-
cit 0 1 0 ential protection
1-block; 0-not block.
Block Diff at Inrush Inrush block differential pro-
0 1 0 tection
1-block; 0-not block.
Func_Percent Diff Percentage differential pro-
0 1 0
tection ON 1-on; 0-off.

348
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Instantaneous differential
Func_Inst Diff 0 1 0
protection ON 1-on; 0-off.
Overexcitation stabilization
judgement
Overexcit 3rd NOT 3rd or 5th harmonic (HAR)
th 0 1 0
5 inhibit on
rd th
1-3 harmonic; 0-5 har-
monic.
Block Diff at Overex- Overexcitation block differ-
cit 0 1 0 ential protection
1-block; 0-not block.
2nd Harm Not Wave 2nd harmonic (HAR) inhibit
not the fuzzy recognition
based on the wave-
0 1 0
form(WAVE)
1-2nd harmonic on; 0-
waveform on
Block Diff at Inrush Inrush block differential pro-
0 1 0 tection
1-block; 0-not block.
Func_Percent Diff Percentage differential pro-
0 1 0
tection ON 1-on; 0-off.
Instantaneous differential
Func_Inst Diff 0 1 0
protection ON 1-on; 0-off.
Block HV REF when CT
Block HV REF at HV
0 1 0 failure,
CT_Fail
1-Block;0-unblock
HV Restricted earth fault
HV Func_REF Alarm 0 1 0 Alarm-stage ON
1-on; 0-off.
HV Restricted earth fault
HV Func_REF Trip 0 1 0 trip-stage ON
1-on; 0-off.
MV Restricted earth fault
MV Func_REF Trip 0 1 0
trip-stage ON 1-on; 0-off.
MV Restricted earth fault
MV Func_REF Alarm 0 1 0 Alarm-stage ON
1-on; 0-off.
Block MV REF at MV Block MV REF when CT
0 1 0
CT_Fail failure,

349
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-Block;0-unblock

HV Overexcitation (V/F) on
HV Func_Overexcit 0 1 0
1-on; 0-off.
MV Overexcitation (V/F) on
MV Func_Overexcit 0 1 0
1-on; 0-off.
LV Overexcitation (V/F) on
LV Func_Overexcit 0 1 0
1-on; 0-off.
Definite Overexcitation (V/F)
Func_Overexcit
0 1 0 Alarming on
Alarm Def
1-on; 0-off.
Definite (DEF)Overexcitation
Func_Overexcit Trip
0 1 0 (V/F) on
Def
1-on; 0-off.
Inverse (IVR)Overexcitation
Func_Overexcit Trip
0 1 0 (V/F) on
Inv
1-on; 0-off.
Overexcitation protection
uses phase-to-phase volt-
V/F Volt-
0 1 0 age (VPP) or phase-to-earth
age(0-VPP,1-VPN)
voltage (VPN)
0-VPP; 1-VPN.
HV Func_OC1 The 1st stage of HV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
HV OC1 Direction Direction (DIR) detection of
HV OC Stage 1 is switched
0 1 0
ON
1-on; 0-off.
HV OC1 Dir To Sys Direction unit of HV OC
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV OC1 Inrush Block Inrush 2nd harmonic detec-
tion HV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
HV Func_OC2 0 1 0 nd
The 2 stage of HV OC

350
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
(OC_2) protection is
switched ON
1-on; 0-off.
HV OC2 Direction Direction (DIR) detection of
HV OC Stage 2 is switched
0 1 0
ON
1-on; 0-off.
HV OC2 Dir To Sys Direction unit of HV OC
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV OC2 Inrush Block Inrush 2nd harmonic detec-
tion HV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
HV Func_OC Inv The IDMTL inverse time
stage of HV OC protection is
0 1 0
switched ON
1-on; 0-off.
HV OC Inv Direction Direction (DIR) detection of
HV OC IDMTL inverse time
0 1 0
is switched ON
1-on; 0-off.
HV OC Inv Dir To Sys Direction unit of HV OC ID-
MTL inverse time points to
system
0 1 0
0 - point to the protected
transformer
1- point to system
HV OC Inv Inrush Inrush 2nd harmonic detec-
Block tion HV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block HV OC at HV Select to block HV OC pro-
VT_Fail tection or exit direction unit,
0 1 0
when HV VT fails
0- HV Direct OK at HV VT

351
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Fail
1- Blk HV OC at HV VT Fail
HV OC Initiate LV HV OC protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
HV OC Initiate MV HV OC protection initiate MV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
MV Func_OC1 The 1st stage of MV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
MV OC1 Direction Direction (DIR) detection of
MV OC Stage 1 is switched
0 1 0
ON
1-on; 0-off.
MV OC1 Dir To Sys Direction unit of MV OC
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
MV OC1 Inrush Block Inrush 2nd harmonic detec-
tion MV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
MV Func_OC2 The 2nd stage of MV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
MV OC2 Direction Direction (DIR) detection of
MV OC Stage 2 is switched
0 1 0
ON
1-on; 0-off.
MV OC2 Dir To Sys Direction unit of MV OC
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system

352
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
MV OC2 Inrush Block Inrush 2nd harmonic detec-
tion MV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
MV Func_OC Inv The IDMTL inverse time
stage of MV OC protection is
0 1 0
switched ON
1-on; 0-off.
MV OC Inv Direction Direction (DIR) detection of
MV OC IDMTL inverse time
0 1 0
is switched ON
1-on; 0-off.
MV OC Inv Dir To Direction unit of MV OC
Sys IDMTL inverse time points to
system
0 1 0
0 - point to the protected
transformer
1- point to system
MV OC Inv Inrush Inrush 2nd harmonic detec-
Block tion MV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block MV OC at MV Select to block MV OC pro-
VT_Fail tection or exit direction unit,
when MV VT fails
0 1 0
0- MV Direct OK at MV VT
Fail
1- Blk MV OC at MV VT Fail
MV OC Initiate HV1 MV OC protection initiate
CBF 0 1 0 HV1 side CBF
0 - initiate, 1 – not initiate
st
LV Func_OC1 The 1 stage of LV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
LV OC1 Direction Direction (DIR) detection of
0 1 0 LV OC Stage 1 is switched
ON

353
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-on; 0-off.
LV OC1 Dir To Sys Direction unit of LV OC
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
nd
LV OC1 Inrush Block Inrush 2 harmonic detec-
tion LV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
nd
LV Func_OC2 The 2 stage of LV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
LV OC2 Direction Direction (DIR) detection of
LV OC Stage 2 is switched
0 1 0
ON
1-on; 0-off.
LV OC2 Dir To Sys Direction unit of LV OC
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
nd
LV OC2 Inrush Block Inrush 2 harmonic detec-
tion LV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
LV Func_OC Inv The IDMTL inverse time
stage of LV OC protection is
0 1 0
switched ON
1-on; 0-off.
LV OC Inv Direction Direction (DIR) detection of
LV OC IDMTL inverse time is
0 1 0
switched ON
1-on; 0-off.
LV OC Inv Dir To Sys Direction unit of LV OC ID-
0 1 0 MTL inverse time points to
system

354
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
0 - point to the protected
transformer
1- point to system
nd
LV OC Inv Inrush Inrush 2 harmonic detec-
Block tion LV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block LV OC at LV Select to block LV OC pro-
VT_Fail tection or exit direction unit,
0 1 0 when LV VT fails
0- LV Direct OK at LV VT Fail
1- Blk LV OC at LV VT Fail
LV OC Initiate HV1 LV OC protection initiate
CBF 0 1 0 HV1 side CBF
0 - initiate, 1 – not initiate
The 1st stage of HV earth
fault (EF_1) protection is
HV Func_EF1 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
HV EF Stage 1 is switched
HV EF1 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of HV EF
Stage 1 points to system
HV EF1 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
tion HV EF Stage 1 is
HV EF1 Inrush Block 0 1 0
switched ON
1-on; 0-off.
The 2nd stage of HV earth
fault (EF_2) protection is
HV Func_EF2 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
HV EF2 Direction 0 1 0
HV EF Stage 2 is switched

355
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
ON
1-on; 0-off.
Direction unit of HV EF
Stage 2 points to system
HV EF2 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
nd
Inrush 2 harmonic detec-
tion HV EF Stage 2 is
HV EF2 Inrush Block 0 1 0
switched ON
1-on; 0-off.
The IDMTL inverse time
stage of HV EF protection is
HV Func_EF Inv 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
HV EF IDMTL inverse time is
HV EF Inv Direction 0 1 0
switched ON
1-on; 0-off.
Direction unit of HV EF ID-
MTL inverse time points to
system
HV EF Inv Dir To Sys 0 1 0
0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
HV EF Inv Inrush tion HV EF IDMTL inverse
0 1 0
Block time is switched ON
1-on; 0-off.
Select to block HV EF pro-
tection or exit direction unit,
Block HV EF at HV when HV VT fails
0 1 0
VT_Fail 0 - HV Direct OK at HV VT
Fail
1 - Blk HV EF at HV VT Fail
Block HV EF when there is
Block HV EF at HV
0 1 0 HV CT failure
CT_Fail
1-Block; 0-NOT block

356
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
HV EF protection initiate LV
HV EF Initiate LV
0 1 0 side CBF
CBF
0 - initiate, 1 – not initiate
HV EF protection initiate MV
HV EF Initiate MV
0 1 0 side CBF
CBF
0 - initiate, 1 – not initiate
The 1st stage of MV earth
fault (EF_1) protection is
MV Func_EF1 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
MV EF Stage 1 is switched
MV EF1 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of MV EF
Stage 1 points to system
MV EF1 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
tion MV EF Stage 1 is
MV EF1 Inrush Block 0 1 0
switched ON
1-on; 0-off.
The 2nd stage of MV earth
fault (EF_2) protection is
MV Func_EF2 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
MV EF Stage 2 is switched
MV EF2 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of MV EF
Stage 2 points to system
MV EF2 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
MV EF2 Inrush Block 0 1 0
tion MV EF Stage 2 is

357
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
switched ON
1-on; 0-off.
The IDMTL inverse time
stage of MV EF protection is
MV Func_EF Inv 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
MV EF IDMTL inverse time
MV EF Inv Direction 0 1 0
is switched ON
1-on; 0-off.
Direction unit of MV EF ID-
MTL inverse time points to
system
MV EF Inv Dir To Sys 0 1 0
0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
MV EF Inv Inrush tion MV EF IDMTL inverse
0 1 0
Block time is switched ON
1-on; 0-off.
Select to block MV EF pro-
tection or exit direction unit,
Block MV EF at MV when MV VT fails
0 1 0
VT_Fail 0 - MV Direct OK at MV VT
Fail
1 - Blk MV EF at MV VT Fail
Block MV EF when there is
Block MV EF at MV
0 1 0 MV CT failure
CT_Fail
1-Block; 0-NOT block
MV EF protection initiate
MV EF Initiate HV
0 1 0 HV1 side CBF
CBF
0 - initiate, 1 – not initiate
st
The 1 stage of LV earth
fault (EF_1) protection is
LV Func_EF1 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
LV EF1 Direction 0 1 0 LV EF Stage 1 is switched
ON

358
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-on; 0-off.

Direction unit of LV EF Stage


1 points to system
LV EF1 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
nd
Inrush 2 harmonic detec-
tion LV EF Stage 1 is
LV EF1 Inrush Block 0 1 0
switched ON
1-on; 0-off.
nd
The 2 stage of LV earth
fault (EF_2) protection is
LV Func_EF2 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
LV EF Stage 2 is switched
LV EF2 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of LV EF Stage
2 points to system
LV EF2 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
nd
Inrush 2 harmonic detec-
tion LV EF Stage 2 is
LV EF2 Inrush Block 0 1 0
switched ON
1-on; 0-off.
The IDMTL inverse time
stage of LV EF protection is
LV Func_EF Inv 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
LV EF IDMTL inverse time is
LV EF Inv Direction 0 1 0
switched ON
1-on; 0-off.
Direction unit of LV EF ID-
LV EF Inv Dir To Sys 0 1 0 MTL inverse time points to
system

359
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
0 - point to the protected
transformer
1- point to system
nd
Inrush 2 harmonic detec-
LV EF Inv Inrush tion LV EF IDMTL inverse
0 1 0
Block time is switched ON
1-on; 0-off.
Select to block LV EF pro-
tection or exit direction unit,
Block LV EF at LV when LV VT fails
0 1 0
VT_Fail 0 - LV Direct OK at LV VT
Fail
1 - Blk LV EF at LV VT Fail
Block LV EF when there is
Block LV EF at LV
0 1 0 LV CT failure
CT_Fail
1-Block; 0-NOT block
LV EF protection initiate HV1
LV EF Initiate HV
0 1 0 side CBF
CBF
0 - initiate, 1 – not initiate
The 1st stage of HV neu-
tral OC (OC_1) protection
HV Func_Neu OC1 0 1 0
is switched ON
1-on; 0-off.
Direction (DIR) detection
HV Neu OC1 Di- of HV neutral OC Stage 1
0 1 0
rection is switched ON
1-on; 0-off.
Direction unit of HV neu-
tral OC Stage 1 points to
HV Neu OC1 Dir To system
0 1 0
Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
HV Neu OC1 In- tection HV neutral OC
0 1 0
rush Block Stage 1 is switched ON
1-on; 0-off.
HV Func_Neu OC2 0 1 0 The 2nd stage of HV neu-

360
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
tral OC (OC_2) protection
is switched ON
1-on; 0-off.
Direction (DIR) detection
HV Neu OC2 Di- of HV neutral OC Stage 2
0 1 0
rection is switched ON
1-on; 0-off.
Direction unit of HV neu-
tral OC Stage 2 points to
HV Neu OC2 Dir To system
0 1 0
Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
HV Neu OC2 In- tection HV neutral OC
0 1 0
rush Block Stage 2 is switched ON
1-on; 0-off.
The IDMTL inverse time
HV Func_Neu OC stage of HV neutral OC
0 1 0
Inv protection is switched ON
1-on; 0-off.
Direction (DIR) detection
of HV neutral OC IDMTL
HV Neu OC Inv
0 1 0 inverse time stage is
Direction
switched ON
1-on; 0-off.
Direction unit of HV neu-
tral OC IDMTL inverse
time stage points to sys-
HV Neu OC Inv Dir
0 1 0 tem
To Sys
0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
tection HV neutral OC
HV Neu OC Inv
0 1 0 IDMTL inverse time stage
Inrush Block
is switched ON
1-on; 0-off.

361
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Select to block HV neutral
OC protection or exit direc-
tion unit, when HV VT fails
Block HV NOC at
0 1 0 0 - HV Direct OK at HV VT
HV VT_Fail
Fail
1 - Blk HV NOC at HV VT
Fail
HV neutral OC protection
HV Neu OC Init MV
0 1 0 initiate LV side CBF
CBF
0 - initiate, 1 – not initiate
The 1st stage of HV neu-
tral OC (OC_1) protection
HV Func_Neu OC1 0 1 0
is switched ON
1-on; 0-off.
The 1st stage of MV neu-
tral OC (OC_1) protection
MV Func_Neu OC1 0 1 0
is switched ON
1-on; 0-off.
Direction (DIR) detection
MV Neu OC1 Di- of MV neutral OC Stage 1
0 1 0
rection is switched ON
1-on; 0-off.
Direction unit of MV neu-
tral OC Stage 1 points to
MV Neu OC1 Dir system
0 1 0
To Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
MV Neu OC1 In- tection MV neutral OC
0 1 0
rush Block Stage 1 is switched ON
1-on; 0-off.
The 2nd stage of MV neu-
tral OC (OC_2) protection
MV Func_Neu OC2 0 1 0
is switched ON
1-on; 0-off.
MV Neu OC2 Di- Direction (DIR) detection
0 1 0
rection of MV neutral OC Stage 2

362
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
is switched ON
1-on; 0-off.
Direction unit of MV neu-
tral OC Stage 2 points to
MV Neu OC2 Dir system
0 1 0
To Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
MV Neu OC2 In- tection MV neutral OC
0 1 0
rush Block Stage 2 is switched ON
1-on; 0-off.
The IDMTL inverse time
MV Func_Neu OC stage of MV neutral OC
0 1 0
Inv protection is switched ON
1-on; 0-off.
Direction (DIR) detection
of MV neutral OC IDMTL
MV Neu OC Inv
0 1 0 inverse time stage is
Direction
switched ON
1-on; 0-off.
Direction unit of MV neu-
tral OC IDMTL inverse
time stage points to sys-
MV Neu OC Inv Dir
0 1 0 tem
To Sys
0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
tection MV neutral OC
MV Neu OC Inv
0 1 0 IDMTL inverse time stage
Inrush Block
is switched ON
1-on; 0-off.
Select to block MV neutral
OC protection or exit direc-
Block MV NOC at
0 1 0 tion unit, when MV VT fails
MV VT_Fail
0 - MV Direct OK at MV VT
Fail

363
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1 - Blk MV NOC at MV VT
Fail
MV neutral OC protection
MV Neu OC Init HV
0 1 0 initiate HV side CBF
CBF
0 - initiate, 1 – not initiate
Thermal overload in HV
HV Func_Thermal
0 1 0 side is switched on
OvLd
0 - OFF, 1 - ON
HV side using hot/cold
curve type
HV Cold Curve 0 1 0
0 – Hot curve, 1 – Cold
curve
HV thermal overload pro-
HV Thermal Init LV tection initiate LV side
0 1 0
CBF CBF
0 - initiate, 1 – not initiate
HV thermal overload pro-
HV Thermal Init MV tection initiate MV side
0 1 0
CBF CBF
0 - initiate, 1 – not initiate
HV Func_OV1 HV overvoltage stage 1 en-
0 1 0
abled or disabled
HV OV1 Trip HV overvoltage stage 1 trip
0 1 0
or alarm
HV Func_OV2 HV overvoltage stage 2 en-
0 1 0
abled or disabled
HV OV2 Trip HV overvoltage stage 2 trip
0 1 0
or alarm
HV OV Chk PE HV phase to phase voltage
0 1 0 or phase to earth measured
for overvoltage protection
HV VT Failure Detection
HV VT FAIL Detect 0 0 1 On/Off
1-On, 0-Off.
HV Earthing mode:
HV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
MV VT FAIL Detect 0 0 1 MV VT Failure Detection

364
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
On/Off
1-On, 0-Off.
MV Earthing mode:
MV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
LV VT Failure Detection
LV VT FAIL Detect 0 0 1 On/Off
1-On, 0-Off.
LV Earthing mode:
LV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
st
To select whether the 1
binary input (BI1) trip the 1st
BI1 Enable BO1 0 0 1
binary output (BO1) or not.
1-On, 0-Off
To select BO1 tripping in
pulse mode or in direct mode
0- BO1 Direct Tripping,
BO1 Pulse Tripping 0 0 1
without delay
1- BO1 Pulse Tripping, with
preset delay time
To select whether the 2nd
binary input (BI2) trip the 2nd
BI2 Enable BO2 0 0 1
binary output (BO2) or not.
1-On, 0-Off
To select BO2 tripping in
pulse mode or in direct mode
0- BO2 Direct Tripping,
BO2 Pulse Tripping 0 0 1
without delay
1- BO2 Pulse Tripping, with
preset delay time
whether BI1 initiate HV side
BI1 Init HV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI1 initiate MV side
BI1 Init MV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI1 initiate LV side
BI1 Init LV CBF 0 0 1
CBF or not

365
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
0 - initiate, 1 – not initiate

whether BI2 initiate HV side


BI2 Init HV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate MV side
BI2 Init MV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate LV side
BI2 Init LV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
Undervoltage stage 1 ena-
Func_UV1 0 1 1
bled or disabled
Undervotage stage 1 tripping
UV1 Trip 0 1 0
enabled or disabled
Undervoltage stage 2 ena-
Func_UV2 0 1 1
bled or disabled
Undervotage stage 2 tripping
UV2 Trip 0 1 0
enabled or disabled
Checking current for un-
UV Chk Current 0 1 1
dervoltage protection
Checking CB aux. contact
UV Chk CB Status 0 1 1
for undervoltage protection
Phase to phase or phase to
UV Chk PE 0 1 1 earth measured for un-
dervoltage protection
Checking three phase volt-
UV Chk All Phase 0 1 0 age for undervoltage protec-
tion
LV protection stage 1
Func_3U0 Alarm 0 1 1
1-on,0-off
LV protection stage 1 trip-
Func_3U0 Trip 0 1 0 ping
1-on,0-off

366
Chapter 25 Appendix

1.3.3 CSC-326 (M03) setting value list

Table 252 CSC-326 (M03) setting value list

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
HV Wind Conn/Y-0 0 1 0 High voltage side
D-1 winding connection
0:star-type connec-
tion 1:delta-type
connection
LV Wind Conn/Y-0 0 1 1 Low voltage side-
D-1 winding connection
0:star-type connec-
tion 1:delta-type
connection
Vet Grp Angle 0 12. 11 Vector Group An-
gle( VET GRP AN-
GLE)
SN MVA 1.000 3000. 120 Rated capacity of
transformer
HV UN 1.000 9999. 2200.0 High voltage side
VTchange
A 50.00 9999. 1200.0 High voltage side CT
HV CT Pri
primary value
A 1.000 5.000 1.0 High voltage side CT
HV CT Sec
secondary value
HV Voltage Chan 1 3 1 High voltage side
Sel channel selection
A 50.00 9999. 1200.0 Neutral CT (NCT)
HV NCT Pri(REF) Primary(PRI) current
in HV side for REF
A 1.000 5.000 1.0 Neutral CT (NCT)
Secondary(SEC)
HV NCT Sec(REF)
current in HV side for
REF
A 50.00 9999. 1200.0 Neutral CT (NCT)
Primary(PRI) current
HV NCT Pri(BU)
in HV side for backup
protection
A 1.000 5.000 1.0 Neutral CT (NCT)
HV NCT Sec(BU)
Secondary(PRI) cur-

367
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
rent in HV side for
backup protection
kV 1.000 1000. 10.50 Nominal voltage (UN)
LV UN in Low voltage
(LV)side
1.000 9999. 105.0 Voltage transform-
LV VT Ratio er(VT) Ratio in LV
side
A 50.00 9999. 3000.0 Low voltage side CT
LV CT Pri
primary value
A 1.000 5.000 1.0 Low voltage side CT
LV CT Sec
secondary value
A 1.000 5.000 1.0 CT Secondary(SEC)
LV Sec Inside
current in LV inside
Delta
delta
A 50.00 9999. 1200.0 Neutral CT (NCT)
Primary(PRI) cur-
LV NCT Pri(REF)
rent in LV side for
REF
A 1.000 5.000 1.0 Neutral CT (NCT)
Secondary(SEC)
LV NCT Sec(REF)
current in LV side for
REF
A 50.00 9999. 1200.0 Neutral CT (NCT)
Primary(PRI) cur-
LV NCT Pri(BU)
rent in LV side for
backup protection
A 1.000 5.000 1.0 Neutral CT (NCT)
Secondary(PRI)
LV NCT Sec(BU)
current in LV side for
backup protection
A 0 9999 Rated primary cur-
rent for HV side
HV Rated Cur Pri
(calculated value,
read only)
A 0 9999 Rated secondary
current for HV side
HV Rated Cur Sec
(calculated value,
read only)

368
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
0 9999 HV ratio factor for
differen-tial protec-
Ratio Factor KTAH
tion (calculated val-
ue, read only)
0 9999 LV ratio factor for
differential protection
Ratio Factor KTAL
(calculated value,
read only)
0 9999 HV ratio factor, with
zero-sequence cur-
rent calculated, for
Ratio REF KTAH
REF protection
(calculated value,
read only)
0 9999 HV ratio factor with
zero-sequence cur-
rent directly meas-
Ratio REF KNH
ured, for REF pro-
tection (calculated
value, read only)
Setting value of dif-
I_Inst Diff A 0.5Ir 20Ir 20 ferential instant trip-
ping current (ID>>)
Setting value of per-
centage differential
I_Percent Diff A 0.08Ir 4Ir 2.1
protection circuit
(ID>)
The 1st breakpoint
I_ResPoint1 Diff A 0.1Ir Ir 2
restraint current (IR1)
The 2nd breakpoint
I_ResPoint2 Diff A 0.1Ir 10Ir 2
restraint current (IR2)
First ratio restraint
Slope1_Diff 0 0.2 0.2
coefficient
Second ratio restraint
Slope2_Diff 0.2 0.7 0.5
coefficient
Third ratio restraint
Slope3_Diff 0.25 0.95 0.7
coefficient
2nd harmonic(HAR)
Ratio_2nd Harm 0.05 0.80 0.15
ratio
rd th
Ratio_3/5th Harm 0.05 0.80 0.35 3 / 5 harmon-

369
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
ic(HAR) ratio

Within the delay 2nd


harmonic block all
three phases. After
T_2nd Harm Block 0 20 20
s the delay, then only
the local phase is
blocked.
th
Within the delay 5
harmonic block all
T_3/5th Harm three phases. After
s 0 20 20
Block the delay, then only
the local phase is
blocked.
Current setting for
HV 3I0_REF A 0.08Ir 2Ir 2 HV Restricted Earth
Fault protection
Slope setting for HV
HV Slope_REF 0.2 0.95 0.5 Re-stricted Earth
Fault pro-tection
HV Restricted Earth
HV T_REF Trip s 0 60 0.03 Fault trip time set-
ting
HV Restricted Earth
HV 3I0_REF Alarm A 0.08Ir 2Ir 2 Fault alarm current
setting
HV Restricted Earth
HV T_REF Alarm s 0 60 0.03 Fault alarm time set-
ting
Nominal phase volt-
Reference Voltage V 40 130 57.3
age in HV side
Alarming setting of
V/F_Definite Alarm 1 1.5 1.1
volt/hertz
Timer setting for
T_Definite Alarm s 0.1 9999 10 volt/hertz alarming
stage
Tripping setting of
V/F_Definite Trip 1 1.5 1.2 definite volt/hertz
stage
T_Definite Trip s 0.1 9999 1 Timer setting for def-

370
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
inite volt/hertz stage
T1_Inverse Timer setting for
s 0.1 9999 10
V/F=1.05 volt/hertz=1.05
T2_Inverse Timer setting for
s 0.1 9999 90
V/F=1.10 volt/hertz=1.10
T3_Inverse Timer setting for
s 0.1 9999 80
V/F=1.15 volt/hertz=1.15
T4_Inverse Timer setting for
s 0.1 9999 70
V/F=1.20 volt/hertz=1.20
T5_Inverse Timer setting for
s 0.1 9999 60
V/F=1.25 volt/hertz=1.25
T6_Inverse Timer setting for
s 0.1 9999 50
V/F=1.30 volt/hertz=1.30
T7_Inverse Timer setting for
s 0.1 9999 45
V/F=1.35 volt/hertz=1.35
T8_Inverse Timer setting for
s 0.1 9999 40
V/F=1.40 volt/hertz=1.40
T9_Inverse Timer setting for
s 0.1 9999 35
V/F=1.45 volt/hertz=1.45
T10_Inverse Timer setting for
s 0.1 9999 30
V/F=1.50 volt/hertz=1.50
Cool down time delay
T_Cool Down s 0.1 9999 25 for overexcitation
protection
HV overcurrent (O/C)
HV I_OC1 A 0.05Ir 20Ir 5 current setting for
Stage 1
Time setting for HV
HV T_OC1 s 0 60 60
OC, Stage 1
HV overcurrent (O/C)
HV I_OC2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for HV
HV T_OC2 s 0 60 60
OC, Stage 2
HV Curve_OC Inv Ref to IEC and ANSI
1 12 1
Curves
HV I_OC Inv A 0.05Ir 20Ir 5 Ref to IEC and ANSI

371
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Curves

Ref to IEC and ANSI


HV K_OC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
HV A_OC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
HV B_OC Inv s 0 60 0
Curves
Ref to IEC and ANSI
HV P_OC Inv 0 10 0.02
Curves
The angle setting for
HV Angle_OC ° 0 90 45 voltage ahead of
current.
The maximum 1st
-harmonic current
HV
A 0.25Ir 20Ir 5 setting to remove the
Imax_2H_UnBlk
inrush block, in HV
O/C protection
Inrush 2nd harmonic
ratio setting for
HV Ratio_I2/I1 0.07 0.5 0.2
blocking HV O/C
protection
Inrush 2nd harmonic
HV T2h_Cross_Blk s 0 60 20 cross-block time for
HV O/C protection
LV overcurrent (O/C)
LV I_OC1 A 0.05Ir 20Ir 5 current setting for
Stage 1
Time setting for LV
LV T_OC1 s 0 60 60
OC, Stage 1
LV overcurrent (O/C)
LV I_OC2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for LV
LV T_OC2 s 0 60 60
OC, Stage 2
MV Curve_OC Inv Ref to IEC and ANSI
1 12 1
Curves
Ref to IEC and ANSI
LV I_OC Inv A 0.05Ir 20Ir 5
Curves

372
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Ref to IEC and ANSI
LV K_OC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
LV A_OC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
LV B_OC Inv s 0 60 0
Curves
Ref to IEC and ANSI
LV P_OC Inv 0 10 0.02
Curves
The angle setting for
LV Angle_OC 0 90 45 voltage ahead of
current.
The maximum 1st
-harmonic current
LV
0.25Ir 20Ir 5 setting to remove the
Imax_2H_UnBlk
inrush block, in LV
O/C protection
Inrush 2nd harmonic
ratio setting for
LV Ratio_I2/I1 0.07 0.5 0.2
blocking LV O/C
protection
Inrush 2nd harmonic
LV T2h_Cross_Blk 0 60 20 cross-block time for
LV O/C protection
HV earth fault (E/F)
HV 3I0_EF1 A 0.05Ir 20Ir 5 protection current
setting for Stage 1
Time setting for HV
HV T_EF1 s 0 60 60
E/F, Stage 1
HV earth fault (E/F)
HV 3I0_EF2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for HV
HV T_EF2 s 0 60 60
E/F, Stage 2
Ref to IEC and ANSI
HV Curve_EF Inv 1 12 1
Curves
Ref to IEC and ANSI
HV 3I0_EF Inv A 0.05Ir 20Ir 1.2
Curves
HV K_EF Inv 0.05 999 1 Ref to IEC and ANSI

373
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Curves

Ref to IEC and ANSI


HV A_EF Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
HV B_EF Inv s 0 60 0
Curves
Ref to IEC and ANSI
HV P_EF Inv 0 10 0.02
Curves
The angle setting for
HV Angle_EF ° 0 90 45 voltage ahead of
current.
The maximum 1st
HV -harmonic current
Imax_2H_UnBlk_E A 0.25Ir 20Ir 5 setting to remove the
F inrush block, in HV
EF protection
The maximum 1st
-harmonic current
HV Ratio_I2/I1_EF 0.07 0.5 0.2 setting to remove the
inrush block, in HV
EF protection
LV earth fault (E/F)
LV 3I0_EF1 A 0.05Ir 20Ir 5 protection current
setting for Stage 1
Time setting for LV
LV T_EF1 s 0 60 60
E/F, Stage 1
LV earth fault (E/F)
LV 3I0_EF2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for LV
LV T_EF2 s 0 60 60
E/F, Stage 2
Ref to IEC and ANSI
LV Curve_EF Inv 1 12 1
Curves
Ref to IEC and ANSI
LV 3I0_EF Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
LV K_EF Inv 0.05 999 1
Curves
Ref to IEC and ANSI
LV A_EF Inv s 0 200 0.14
Curves

374
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Ref to IEC and ANSI
LV B_EF Inv s 0 60 0
Curves
Ref to IEC and ANSI
LV P_EF Inv 0 10 0.02
Curves
The angle setting for
LV Angle_EF ° 0 90 45 voltage ahead of
current.
st
The maximum 1
LV -harmonic current
Imax_2H_UnBlk_E A 0.25Ir 20Ir 5 setting to remove the
F inrush block, in LV
E/F protection
Inrush 2nd harmonic
ratio setting for
LV Ratio_I2/I1_EF 0.07 0.5 0.2
blocking LV E/F pro-
tection
HV neutral
HV 3I0_Neutral over-current (NOC)
A 0.05Ir 20Ir 5
OC1 protection current set-
ting for Stage 1
Time setting for HV
HV T_Neutral OC1 s 0 60 60
NOC, Stage 1
HV neutral
HV 3I0_Neutral over-current (NOC)
A 0.05Ir 20Ir 5
OC2 protection current set-
ting for Stage 2
Time setting for HV
HV T_Neutral OC2 s 0 60 60
NOC, Stage 1
HV Curve_NOC Ref to IEC and ANSI
1 12 1
Inv Curves
Ref to IEC and ANSI
HV 3I0_NOC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
HV K_NOC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
HV A_NOC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
HV B_NOC Inv s 0 60 0
Curves

375
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Ref to IEC and ANSI
HV P_NOC Inv 0 10 0.02
Curves
The angle setting for
HV Angle_NOC ° 0 90 45 voltage ahead of
current.
st
The maximum 1
HV -harmonic current
Imax_2H_UnBlk_ A 0.25Ir 20Ir 5 setting to remove
NOC the inrush block, in
HV NOC protection
Inrush 2nd harmonic
HV Ra- ratio setting for
0.07 0.5 0.2
tio_I2/I1_NOC blocking HV NOC
protection
LV neutral over-current
LV 3I0_Neutral (NOC) protection
A 0.05Ir 20Ir 5
OC1 current setting for
Stage 1
Time setting for LV
LV T_Neutral OC1 s 0 60 60
NOC, Stage 1
LV neutral over-current
LV 3I0_Neutral (NOC) protection
A 0.05Ir 20Ir 5
OC2 current setting for
Stage 2
Time setting for LV
LV T_Neutral OC2 s 0 60 60
NOC, Stage 1
Ref to IEC and ANSI
LV Curve_NOC Inv 1 12 1
Curves
Ref to IEC and ANSI
LV 3I0_NOC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
LV K_NOC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
LV A_NOC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
LV B_NOC Inv s 0 60 0
Curves
Ref to IEC and ANSI
LV P_NOC Inv 0 10 0.02
Curves

376
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
The angle setting for
LV Angle_NOC ° 0 90 45 voltage ahead of
current.
The maximum 1st
LV -harmonic current
Imax_2H_UnBlk_ A 0.25Ir 20Ir 5 setting to remove
NOC the inrush block, in
LV NOC protection
nd
Inrush 2 harmonic
LV Ra- ratio setting for
0.07 0.5 0.2
tio_I2/I1_NOC blocking LV NOC
protection
Setting for HV-side
HV I_Therm OL
A 0.1Ir 5Ir 2 thermal overload
Trip
trip-stage current
Setting for HV-side
HV I_Therm OL
A 0.1Ir 5Ir 2 thermal overload
Alarm
alarm-stage current
Time const for
HV T_Const
s 1 9999 10 HV-side thermal
Therm
overload protection
Cool down time delay
HV T_Const Cool
s 1 9999 10 for HV-side thermal
Down
overload
Setting for LV-side
LV I_Therm OL
A 0.1Ir 5Ir 2 thermal overload
Trip
trip-stage current
Setting for LV-side
LV I_Therm OL
A 0.1Ir 5Ir 2 thermal overload
Alarm
alarm-stage current
Time const for
LV T_Const Therm s 1 9999 10 LV-side thermal
overload protection
Cool down time delay
LV T_Const Cool
s 1 9999 10 for LV-side thermal
Down
overload
Overcurrent Setting
HV I_OverLoad A 0.1Ir 4Ir 2
of overload

377
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Time setting for
HV T_OverLoad s 0.1 3600 10
overload
Overcurrent Setting
LV I_OverLoad A 0.1Ir 4Ir 2
of overload
Time setting for
LV T_OverLoad s 0.1 3600 10
overload
HV voltage setting for
HV U_OV1 V 40 200 200 stage 1 of overvolt-
age protection
HV time setting for
HV T_OV1 s 0 60 60 stage 1 of overvolt-
age protection
HV voltage setting for
HV U_OV2 V 40 200 200 stage 2 of overvolt-
age protection
HV time setting for
HV T_OV2 s 0 60 60 stage 2 of overvolt-
age protection
HV dropout ratio for
HV Dropout_OV 0.9 0.99 0.95 overvoltage protec-
tion
LV voltage setting for
LV U_OV1 V 40 200 200 stage 1 of overvolt-
age protection
LV time setting for
LV T_OV1 s 0 60 60 stage 1 of overvolt-
age protection
LV voltage setting for
LV U_OV2 V 40 200 200 stage 2 of overvolt-
age protection
LV time setting for
LV T_OV2 s 0 60 60 stage 2 of overvolt-
age protection
LV dropout ratio for
LV Dropout_OV 0.9 0.99 0.95 overvoltage protec-
tion
Phase current setting
LV I_CBF OC A 0.05Ir 20Ir 5 value for LV CBF
protection
LV 3I2_CBF NS A 0.05Ir 20Ir 5 Negative sequence

378
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
(NS) current setting

3I 2 value for LV

CBF protection
Zero sequence (ZS)

current setting 3I 0
LV 3I0_CBF ZS A 0.05Ir 20Ir 5
value for LV CBF
protection
Time setting value of
LV T1_CBF s 0 32 10 Stage 1, for LV CBF
protection
Time setting value of
LV T2_CBF s 0.1 32 10 Stage 2, for LV CBF
protection
Time delay setting for
LV T_Dead Zone
s 0 32 10 LV dead zone pro-
tection
current threshold of
HV I_STUB A 0.05Ir 20Ir 100
stub protection
delay time of stub
HV T_STUB s 0 60 60
protection
zero sequence cur-
rent threshold of pole
LV 3I0_PD A 0.05Ir 20Ir 5
discordance protec-
tion
negative sequence
current threshold of
LV 3I2_PD A 0.05Ir 20Ir 5
pole discordance
protection
delay time of pole
LV T_PD s 0 60 10 discordance protec-
tion
HV I_VT Fail Minimum Current of
A 0.05Ir 0.2Ir 0.05 VT failure for HV side
Minimum zero or
HV 3I02_ VT Fail A 0.05Ir 0.2Ir 0.5 negative Current of
HV VT fail
Maximum phase to
HV Upe_VT Fail V 7 20 8 earth voltage of HV
VT fail
Maximum phase to
HV Upp_VT Fail V 10 30 16
phase voltage of HV

379
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
VT fail

HV Upe_VT Minimum phase to


Normal V 40 65 40 phase voltage of HV
VT normal
Minimum Current of
LV I_VT Fail A 0.05Ir 0.2Ir 0.05 VT failure for LV side
Minimum zero or
LV 3I02_VT Fail A 0.05Ir 0.2Ir 0.5 negative Current of
LV VT fail
Maximum phase to
LV Upe_VT Fail V 7 20 8 earth voltage of LV
VT fail
Maximum phase to
LV Upp_VT Fail V 10 30 16 phase voltage of LV
VT fail
LV Upe_VT Nor- Minimum phase to
V 40 65 40 phase voltage of LV
mal VT normal
delay time of stub
T_Pulse Tripping s 0.2 5 5
protection
Setting value of low
V 5.00 150.0 40 voltage protection
HV U_UV1 stage I at HV side
Tripping time of low
s 0.00 120.00 0.3 voltage protection
HV T_UV1 stage I at HV side
Setting value of low
V 5.00 150.0 45 voltage protection
HV U_UV2 stage II at HV side
Tripping time of low
s 0.00 120.00 0.6 voltage protection
HV T_UV2 stage II at HV side
Drop-off factor of low
1.01 2.00 1.05 voltage protection
HV Dropout_UV stage I at HV side
Current setting of low
A 0.05 10.00 0.1In voltage protection
HV I_UV Chk stage I at HV side
Setting value of low
V 5.00 150.0 40 voltage protection
LV U_UV1 stage I at LV side
Tripping time of low
s 0.00 120.00 0.3 voltage protection
LV T_UV1 stage I at LV side

LV U_UV2 V 5.00 150.0 45 Setting value of low

380
Chapter 25 Appendix

Min. Max. Default


Setting Value Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
voltage protection
stage II at LV side
Tripping time of low
s 0.00 120.00 0.6 voltage protection
LV T_UV2 stage II at LV side
Drop-off factor of low
1.01 2.00 1.05 voltage protection
LV Dropout_UV stage I at LV side
Current setting of low
A 0.05 10.00 0.1In voltage protection
LV I_UV Chk stage I at LV side
Alarm setting of ze-
LV 3U0_Neu Disp V 2.00 100.0 10 ro-sequence voltage
Alm protection at LV side
Alarm settingime set-
ting of ze-
s 0.10 20.00 20.00
LV T_Neu Disp ro-sequence voltage
Alm protection at LV side
Tripping setting of
zero-sequence volt-
V 2.00 100.0 10
LV 3U0_Neu Disp age protection at LV
Trip side
Tripping time setting
of zero-sequence
s 0.10 20.00 20.00
LV T_Neu Disp voltage protection at
Trip LV side
Negative sequence
A 0.10 20.00 20.00 current setting at HV
HV1 I2_Detect side I
Negative sequence
A 0.10 20.00 20.00 current setting at HV
HV2 I2_Detect side II
Negative sequence
A 0.10 20.00 20.00 current setting at LV
LV I2_Detect side
Time delay of nega-
s 0.10 20.00 20.00 tive sequence detec-
T_I2 Detect tion

381
Chapter 25 Appendix

1.3.4 CSC-326 (M03) control word list

Table 253 CSC-326 (M03) control word list

Default
Setting Unit Min. Max. Description
setting
CT Fail Detect VT Failure Detection On/Off
0 1 0
1-On, 0-Off.
Two-Wind Trans Two-winding(TWO WIND )
not three -winding trans-
0 1 0 former (TRANS)
1-two-winding trans;
0-three-winding trans
Autotransformer not comm
on transformer
Auto Trans 0 1 0
1-autotransformer ;
0- not autotransformer
LV current is included in
calculation of the differential
Diff Includes LV
0 1 0 protection.
Cur
1- Diff Includes LV Cur;
0-Diff NOT Includes LV Cur
Eliminate calculated 3I0
LV D_side Elimi- when LV side winding is
0 1 0
nate I0 connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0
HV D_side Elimi- when HV side winding is
0 1 0
nate I0 connected in Delta mode
1- eliminate; 0-not eliminate
Block differential protection
Block Diff at
0 1 0 when there is CT failure
CT_Fail
1-block; 0-not block.
Differential current (DIFF)
Func_Diff Alarm 0 1 0 Alarming on
1-on; 0-off.
Overexcitation stabilization
judgement
Overexcit 3rd NOT 3rd or 5th harmonic (HAR)
th 0 1 0
5 inhibit on
rd th
1-3 harmonic; 0-5 har-
monic.

382
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Block Diff at Overexcitation block differ-
Overexcit 0 1 0 ential protection
1-block; 0-not block.
Block Diff at Overexcitation block differ-
Overexcit 0 1 0 ential protection
1-block; 0-not block.
Block Diff at Inrush Inrush block differential pro-
0 1 0 tection
1-block; 0-not block.
Func_Percent Diff Percentage differential pro-
0 1 0
tection ON 1-on; 0-off.
Instantaneous differential
Func_Inst Diff 0 1 0
protection ON 1-on; 0-off.
Overexcitation stabilization
judgement
Overexcit 3rd NOT 3rd or 5th harmonic (HAR)
th 0 1 0
5 inhibit on
1-3rd harmonic; 0-5th har-
monic.
Block Diff at Overexcitation block differ-
Overexcit 0 1 0 ential protection
1-block; 0-not block.
2nd Harm Not 2nd harmonic (HAR) inhibit
Wave not the fuzzy recognition
based on the wave-
0 1 0
form(WAVE)
1-2nd harmonic on; 0-
waveform on
Block Diff at Inrush Inrush block differential pro-
0 1 0 tection
1-block; 0-not block.
Func_Percent Diff Percentage differential pro-
0 1 0
tection ON 1-on; 0-off.
Instantaneous differential
Func_Inst Diff 0 1 0
protection ON 1-on; 0-off.
Block HV REF when CT
Block HV REF at
0 1 0 failure,
HV CT_Fail
1-Block;0-unblock
HV Func_REF 0 1 0 HV Restricted earth fault

383
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Alarm Alarm-stage ON
1-on; 0-off.
HV Restricted earth fault
HV Func_REF Trip 0 1 0 trip-stage ON
1-on; 0-off.
LV Restricted earth fault
LV Func_REF Trip 0 1 0
trip-stage ON 1-on; 0-off.
LV Restricted earth fault
LV Func_REF
0 1 0 Alarm-stage ON
Alarm
1-on; 0-off.
Block LV REF when CT fail-
Block LV REF at
0 1 0 ure,
LV CT_Fail
1-Block;0-unblock
HV HV Overexcitation (V/F) on
0 1 0
Func_Overexcit 1-on; 0-off.
LV Overexcitation (V/F) on
LV Func_Overexcit 0 1 0
1-on; 0-off.
Definite Overexcitation (V/F)
Func_Overexcit
0 1 0 Alarming on
Alarm Def
1-on; 0-off.
Definite (DEF)Overexcitation
Func_Overexcit
0 1 0 (V/F) on
Trip Def
1-on; 0-off.
Inverse (IVR)Overexcitation
Func_Overexcit
0 1 0 (V/F) on
Trip Inv
1-on; 0-off.
Overexcitation protection
uses phase-to-phase volt-
V/F Volt-
0 1 0 age (VPP) or phase-to-earth
age(0-VPP,1-VPN)
voltage (VPN)
0-VPP; 1-VPN.
HV Func_OC1 The 1st stage of HV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
HV OC1 Direction Direction (DIR) detection of
HV OC Stage 1 is switched
0 1 0
ON
1-on; 0-off.
HV OC1 Dir To Sys 0 1 0 Direction unit of HV OC

384
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Stage 1 points to system
0 - point to the protected
transformer
1- point to system
nd
HV OC1 Inrush Inrush 2 harmonic detec-
Block tion HV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
HV Func_OC2 The 2nd stage of HV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
HV OC2 Direction Direction (DIR) detection of
HV OC Stage 2 is switched
0 1 0
ON
1-on; 0-off.
HV OC2 Dir To Sys Direction unit of HV OC
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
HV OC2 Inrush Inrush 2nd harmonic detec-
Block tion HV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
HV Func_OC Inv The IDMTL inverse time
stage of HV OC protection is
0 1 0
switched ON
1-on; 0-off.
HV OC Inv Direc- Direction (DIR) detection of
tion HV OC IDMTL inverse time
0 1 0
is switched ON
1-on; 0-off.
HV OC Inv Dir To Direction unit of HV OC ID-
Sys MTL inverse time points to
0 1 0 system
0 - point to the protected
transformer

385
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1- point to system
HV OC Inv Inrush Inrush 2nd harmonic detec-
Block tion HV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block HV OC at Select to block HV OC pro-
HV VT_Fail tection or exit direction unit,
when HV VT fails
0 1 0
0- HV Direct OK at HV VT
Fail
1- Blk HV OC at HV VT Fail
HV OC Initiate LV HV OC protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
LV Func_OC1 The 1st stage of LV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
LV OC1 Direction Direction (DIR) detection of
LV OC Stage 1 is switched
0 1 0
ON
1-on; 0-off.
LV OC1 Dir To Sys Direction unit of LV OC
Stage 1 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
LV OC1 Inrush Inrush 2nd harmonic detec-
Block tion LV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
LV Func_OC2 The 2nd stage of LV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
LV OC2 Direction Direction (DIR) detection of
0 1 0 LV OC Stage 2 is switched
ON

386
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-on; 0-off.
LV OC2 Dir To Sys Direction unit of LV OC
Stage 2 points to system
0 1 0 0 - point to the protected
transformer
1- point to system
nd
LV OC2 Inrush Inrush 2 harmonic detec-
Block tion LV OC Stage 2 is
0 1 0
switched ON
1-on; 0-off.
LV Func_OC Inv The IDMTL inverse time
stage of LV OC protection is
0 1 0
switched ON
1-on; 0-off.
LV OC Inv Direc- Direction (DIR) detection of
tion LV OC IDMTL inverse time is
0 1 0
switched ON
1-on; 0-off.
LV OC Inv Dir To Direction unit of LV OC ID-
Sys MTL inverse time points to
system
0 1 0
0 - point to the protected
transformer
1- point to system
LV OC Inv Inrush Inrush 2nd harmonic detec-
Block tion LV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block LV OC at LV Select to block LV OC pro-
VT_Fail tection or exit direction unit,
0 1 0 when LV VT fails
0- LV Direct OK at LV VT Fail
1- Blk LV OC at LV VT Fail
LV OC Initiate HV1 LV OC protection initiate
CBF 0 1 0 HV1 side CBF
0 - initiate, 1 – not initiate
The 1st stage of HV earth
HV Func_EF1 0 1 0
fault (EF_1) protection is

387
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
switched ON
1-on; 0-off.
Direction (DIR) detection of
HV EF Stage 1 is switched
HV EF1 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of HV EF
Stage 1 points to system
HV EF1 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
nd
Inrush 2 harmonic detec-
HV EF1 Inrush tion HV EF Stage 1 is
0 1 0
Block switched ON
1-on; 0-off.
The 2nd stage of HV earth
fault (EF_2) protection is
HV Func_EF2 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
HV EF Stage 2 is switched
HV EF2 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of HV EF
Stage 2 points to system
HV EF2 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
nd
Inrush 2 harmonic detec-
HV EF2 Inrush tion HV EF Stage 2 is
0 1 0
Block switched ON
1-on; 0-off.
The IDMTL inverse time
stage of HV EF protection is
HV Func_EF Inv 0 1 0
switched ON
1-on; 0-off.
HV EF Inv Direc- Direction (DIR) detection of
0 1 0
tion HV EF IDMTL inverse time is

388
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
switched ON
1-on; 0-off.
Direction unit of HV EF ID-
MTL inverse time points to
HV EF Inv Dir To system
0 1 0
Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
HV EF Inv Inrush tion HV EF IDMTL inverse
0 1 0
Block time is switched ON
1-on; 0-off.
Select to block HV EF pro-
tection or exit direction unit,
Block HV EF at HV when HV VT fails
0 1 0
VT_Fail 0 - HV Direct OK at HV VT
Fail
1 - Blk HV EF at HV VT Fail
Block HV EF when there is
Block HV EF at HV
0 1 0 HV CT failure
CT_Fail
1-Block; 0-NOT block
HV EF protection initiate LV
HV EF Initiate LV
0 1 0 side CBF
CBF
0 - initiate, 1 – not initiate
st
The 1 stage of LV earth
fault (EF_1) protection is
LV Func_EF1 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
LV EF Stage 1 is switched
LV EF1 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of LV EF Stage
1 points to system
LV EF1 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
LV EF1 Inrush Inrush 2nd harmonic detec-
0 1 0
Block tion LV EF Stage 1 is

389
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
switched ON
1-on; 0-off.
The 2nd stage of LV earth
fault (EF_2) protection is
LV Func_EF2 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
LV EF Stage 2 is switched
LV EF2 Direction 0 1 0
ON
1-on; 0-off.
Direction unit of LV EF Stage
2 points to system
LV EF2 Dir To Sys 0 1 0 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
LV EF2 Inrush tion LV EF Stage 2 is
0 1 0
Block switched ON
1-on; 0-off.
The IDMTL inverse time
stage of LV EF protection is
LV Func_EF Inv 0 1 0
switched ON
1-on; 0-off.
Direction (DIR) detection of
LV EF IDMTL inverse time is
LV EF Inv Direction 0 1 0
switched ON
1-on; 0-off.
Direction unit of LV EF ID-
MTL inverse time points to
LV EF Inv Dir To system
0 1 0
Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic detec-
LV EF Inv Inrush tion LV EF IDMTL inverse
0 1 0
Block time is switched ON
1-on; 0-off.
Block HV EF at LV 0 1 0 Select to block HV EF pro-

390
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
VT_Fail tection or exit direction unit,
when LV VT fails
0 - LV Direct OK at LV VT
Fail
1 - Blk LV EF at LV VT Fail
Block HV EF when there is
Block HV EF at LV
0 1 0 LV CT failure
CT_Fail
1-Block; 0-NOT block
LV EF protection initiate HV1
LV EF Initiate HV
0 1 0 side CBF
CBF
0 - initiate, 1 – not initiate
The 1st stage of HV neu-
HV Func_Neu tral OC (OC_1) protection
0 1 0
OC1 is switched ON
1-on; 0-off.
Direction (DIR) detection
HV Neu OC1 of HV neutral OC Stage 1
0 1 0
Direction is switched ON
1-on; 0-off.
Direction unit of HV neu-
tral OC Stage 1 points to
HV Neu OC1 Dir system
0 1 0
To Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
HV Neu OC1 tection HV neutral OC
0 1 0
Inrush Block Stage 1 is switched ON
1-on; 0-off.
The 2nd stage of HV neu-
HV Func_Neu tral OC (OC_2) protection
0 1 0
OC2 is switched ON
1-on; 0-off.
Direction (DIR) detection
HV Neu OC2 of HV neutral OC Stage 2
0 1 0
Direction is switched ON
1-on; 0-off.
HV Neu OC2 Dir 0 1 0 Direction unit of HV neu-

391
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
To Sys tral OC Stage 2 points to
system
0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
HV Neu OC2 tection HV neutral OC
0 1 0
Inrush Block Stage 2 is switched ON
1-on; 0-off.
The IDMTL inverse time
HV Func_Neu stage of HV neutral OC
0 1 0
OC Inv protection is switched ON
1-on; 0-off.
Direction (DIR) detection
of HV neutral OC IDMTL
HV Neu OC Inv
0 1 0 inverse time stage is
Direction
switched ON
1-on; 0-off.
Direction unit of HV neu-
tral OC IDMTL inverse
time stage points to sys-
HV Neu OC Inv
0 1 0 tem
Dir To Sys
0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
tection HV neutral OC
HV Neu OC Inv
0 1 0 IDMTL inverse time stage
Inrush Block
is switched ON
1-on; 0-off.
Select to block HV neutral
OC protection or exit direc-
tion unit, when HV VT fails
Block HV NOC at
0 1 0 0 - HV Direct OK at HV VT
HV VT_Fail
Fail
1 - Blk HV NOC at HV VT
Fail
HV Neu OC Init
0 1 0 HV neutral OC protection
LV CBF

392
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
initiate LV side CBF
0 - initiate, 1 – not initiate
The 1st stage of LV neutral
LV Func_Neu OC (OC_1) protection is
0 1 0
OC1 switched ON
1-on; 0-off.
Direction (DIR) detection
LV Neu OC1 Di- of LV neutral OC Stage 1
0 1 0
rection is switched ON
1-on; 0-off.
Direction unit of LV neutral
OC Stage 1 points to
LV Neu OC1 Dir system
0 1 0
To Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
LV Neu OC1 In- tection LV neutral OC
0 1 0
rush Block Stage 1 is switched ON
1-on; 0-off.
The 2nd stage of LV neu-
LV Func_Neu tral OC (OC_2) protection
0 1 0
OC2 is switched ON
1-on; 0-off.
Direction (DIR) detection
LV Neu OC2 Di- of LV neutral OC Stage 2
0 1 0
rection is switched ON
1-on; 0-off.
Direction unit of LV neutral
OC Stage 2 points to
LV Neu OC2 Dir system
0 1 0
To Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
LV Neu OC2 In- tection LV neutral OC
0 1 0
rush Block Stage 2 is switched ON
1-on; 0-off.

393
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
The IDMTL inverse time
LV Func_Neu stage of LV neutral OC
0 1 0
OC Inv protection is switched ON
1-on; 0-off.
Direction (DIR) detection
of LV neutral OC IDMTL
LV Neu OC Inv
0 1 0 inverse time stage is
Direction
switched ON
1-on; 0-off.
Direction unit of LV neutral
OC IDMTL inverse time
LV Neu OC Inv stage points to system
0 1 0
Dir To Sys 0 - point to the protected
transformer
1- point to system
Inrush 2nd harmonic de-
tection LV neutral OC
LV Neu OC Inv
0 1 0 IDMTL inverse time stage
Inrush Block
is switched ON
1-on; 0-off.
Select to block LV neutral
OC protection or exit direc-
Block LV NOC at tion unit, when LV VT fails
0 1 0
LV VT_Fail 0 - LV Direct OK at LV VT
Fail
1 - Blk LV NOC at LV VT Fail
HV Thermal overload in HV
Func_Thermal 0 1 0 side is switched on
OvLd 0 - OFF, 1 – ON
HV side using hot/cold
curve type
HV Cold Curve 0 1 0
0 – Hot curve, 1 – Cold
curve
HV thermal overload pro-
HV Thermal Init tection initiate LV side
0 1 0
LV CBF CBF
0 - initiate, 1 – not initiate
LV 0 1 0 Thermal overload in LV

394
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Func_Thermal side is switched on
OvLd 0 - OFF, 1 - ON
LV side using hot/cold
curve type
LV Cold Curve 0 1 0
0 – Hot curve, 1 – Cold
curve
LV OC Initiate LV thermal overload pro-
HV1 CBF tection initiate HV1 side
0 1 0
CBF
0 - initiate, 1 – not initiate
Func_OverLoad Overload at LV side
0 - OFF, 1 - ON
HV Func_OV1 HV overvoltage stage 1 en-
0 1 0
abled or disabled
HV OV1 Trip HV overvoltage stage 1 trip
0 1 0
or alarm
HV Func_OV2 HV overvoltage stage 2 en-
0 1 0
abled or disabled
HV OV2 Trip HV overvoltage stage 2 trip
0 1 0
or alarm
HV OV Chk PE HV phase to phase voltage
0 1 0 or phase to earth measured
for overvoltage protection
HV OC Initiate LV HV OC protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
LV Func_OV1 LV overvoltage stage 1 ena-
0 1 0
bled or disabled
LV OV1 Trip LV overvoltage stage 1 trip
0 1 0
or alarm
LV Func_OV2 LV overvoltage stage 2 ena-
0 1 0
bled or disabled
LV OV2 Trip LV overvoltage stage 2 trip
0 1 0
or alarm
LV OV Chk PE LV phase to phase voltage
0 1 0 or phase to earth measured
for overvoltage protection
LV Circuit breaker failure
LV Func_CBF 0 1 0 (CBF) protection is switched
ON

395
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-on; 0-off.

LV CBF protection detect


LV 3I0/3I2 Check negative or zero sequence
0 1 0
On current 3I0 or 3I2.
1-Detect; 0- Not Detect
LV CBF protection detect LV
LV CB Status
0 1 0 CB status
Check On
1-Detect; 0- Not Detect
Dead zone protection is
LV Func_Dead
0 1 0 switched ON
Zone
1-on; 0-off.
HV Func_STUB Enable or disable stub pro-
0 1 0
tection
HV STUB Init LV stub protection initiate LV
CBF 0 1 0 side CBF
0 - initiate, 1 – not initiate
Enable or disable LV poles
LV Func_PD 0 1 0
discordance protection
Enable or disable 3I0/3I2
LV PD Chk 3I0/3I2 0 1 0
criteria
HV VT Failure Detection
HV VT FAIL Detect 0 0 1 On/Off
1-On, 0-Off.
HV Earthing mode:
HV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
LV VT Failure Detection
LV VT FAIL Detect 0 0 1 On/Off
1-On, 0-Off.
LV VT Failure Detection
LV VT FAIL Detect 0 0 1 On/Off
1-On, 0-Off.
LV Earthing mode:
LV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
To select whether the 1st
binary input (BI1) trip the 1st
BI1 Enable BO1 0 0 1
binary output (BO1) or not.
1-On, 0-Off

396
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
To select BO1 tripping in
pulse mode or in direct mode
BO1 Pulse Trip- 0- BO1 Direct Tripping,
0 0 1
ping without delay
1- BO1 Pulse Tripping, with
preset delay time
nd
To select whether the 2
nd
binary input (BI2) trip the 2
BI2 Enable BO2 0 0 1
binary output (BO2) or not.
1-On, 0-Off
To select BO2 tripping in
pulse mode or in direct mode
BO2 Pulse Trip- 0- BO2 Direct Tripping,
0 0 1
ping without delay
1- BO2 Pulse Tripping, with
preset delay time
whether BI1 initiate HV side
BI1 Init HV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI1 initiate LV side
BI1 Init LV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate HV side
BI2 Init HV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate LV side
BI2 Init LV CBF 0 0 1 CBF or not
0 - initiate, 1 – not initiate
HV undervoltage stage 1
HV Func_UV1 0 1 1
1-On, 0-Off
HV undervoltage stage 1
HV UV1 Trip 0 1 0
tripping enabled or disabled
HV undervoltage stage 2
HV Func_UV2 0 1 1
enabled or disabled
HV undervoltage stage 2
HV UV2 Trip 0 1 0
tripping enabled or disabled
HV UV Chk Cur- Checking current for HV UV
0 1 1
rent protection
HV UV Chk CB Checking CB aux. contact
0 1 1
Status for HV UV protection

397
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
Phase to phase or phase to
HV UV Chk PE 0 1 1 earth measured for HV UV
protection
HV UV Chk All Checking three phase volt-
0 1 0
Phase age for HV UV protection
LV UV protection initiate LV
LV UV Initiate LV
0 1 0 side CBF
CBF
0 - initiate, 1 – not initiate
LV undervoltage stage 1
LV Func_UV1 0 1 1
enabled or disabled
LV undervoltage stage 1
LV UV1 Trip 0 1 0
tripping enabled or disabled
LV undervoltage stage 2
LV Func_UV2 0 1 1
enabled or disabled
LV undervoltage stage 2
LV UV2 Trip 0 1 0
tripping enabled or disabled
Checking current for LV UV
LV UV Chk Current 0 1 1
protection
LV UV Chk CB Checking CB aux. contact
0 1 1
Status for LV UV protection
Phase to phase or phase to
LV UV Chk PE 0 1 1 earth measured for LV UV
protection
LV UV Chk All Checking three phase volt-
0 1 0
Phase age for LV UV protection
Zero sequence voltage pro-
LV Func_3U0
0 1 1 tection for LV protection
Alarm
1-On, 0-Off
VT failure blocking zero se-
Block LV 3U0 at quence voltage protection
0 1 0
VT_Fail for LV protectio
1-On, 0-Off
Negative sequence supervi-
HV1 Func_I2 De-
0 1 0 sion at HV1 side
tect
1-On, 0-Off
Negative sequence supervi-
HV2 Func_I2 De-
0 1 0 sion for HV2 protection
tect
1-On, 0-Off
Negative sequence se-
LV Func_I2 Detect 0 1 0 quence supervision for LV
protection

398
Chapter 25 Appendix

Default
Setting Unit Min. Max. Description
setting
1-On, 0-Off

1.3.5 CSC-326 (M11) setting value list

Setting Unit Max. Min. Default Description


0 9999 Ratio factor of differential
Ratio Factor I/II protection at I/II side (cal-
culated value, read only)
0 9999 Ratio factor of differential
Ratio Factor III/IV protection at III/IV side (cal-
culated value, read only)
0 9999 Ratio factor of differential
Ratio Factor V protection at V side (calcu-
lated value, read only)
A 50.00 9999. 1200.0 Primary value of CT at I/II
I/II Side CT Pri
side
A 1.000 5.000 1.0 Secondary value of CT at I/II
I/II Side CT Sec
side
A 50.00 9999. 1200.0 Primary value of CT at III/IV
III/IV Side CT Pri
side
III/IV Side CT A 1.000 5.000 1.0 Secondary value of CT at
Sec III/IV side
A 50.00 9999. 3000.0 Primary value of CT at V
V Side CT Pri
side
A 1.000 5.000 1.0 Secondary value of CT at V
V Side CT Sec
side
100.0 20.0 Instantaneous Differential
I_Inst Diff A 0.50
(ID>>) current setting
20.00 0.5 Setting value of percentage
I_Percent Diff A 0.08 differential protection circuit
(ID>)
5.00 2.0 The 1st breakpoint restraint
I_ResPoint1 Diff A 0.10
current (IR1)
50.00 2.0 The 2nd breakpoint restraint
I_ResPoint2 Diff A 0.10
current (IR2)
0.20 0.2 The first percentage differ-
Slope1_Diff 0.00
ential factor
0.70 0.5 The second percentage dif-
Slope2_Diff 0.20
ferential factor

399
Chapter 25 Appendix

0.95 0.7 The third percentage differ-


Slope3_Diff 0.25
ential factor
T_Pulse Tripping s 0.20 5.00 5.0 Pulse tripping time delay

1.3.6 CSC-326 (M11) control word list

Setting Unit Min. Max. Default Description


Control 1 0 CT failure detection
CT Fail Detect 0
word 1-On, 0-Off
1 0 Differential instant tripping
Func_Inst Diff Control
0 protection
word
1-On, 0-Off
1 0 Percentage differential pro-
Func_Percent Control
0 tection
Diff word
1-On, 0-Off
1 1 Differential out-of limits
Control
Func_Diff Alarm 0 alarm
word
1-On, 0-Off
Block Diff at Control 1 0 CT failure detection
0
CT_Fail word 1-On, 0-Off
1 0 To select whether the 1st
st
Control binary input (BI1) trip the 1
BI1 Enable BO1 0
word binary output (BO1) or not.
1-On, 0-Off
1 0 To select BO1 tripping in
pulse mode or in direct
mode
BO1 Pulse Trip- Control
0 0- BO1 Direct Tripping,
ping word
without delay
1- BO1 Pulse Tripping, with
preset delay time
nd
1 0 To select whether the 2
nd
Control binary input (BI2) trip the 2
BI2 Enable BO2 0
word binary output (BO2) or not.
1-On, 0-Off
1 0 To select BO2 tripping in
pulse mode or in direct
BO2 Pulse Trip- mode
Control
ping 0 0- BO2 Direct Tripping,
word
without delay
1- BO2 Pulse Tripping, with
preset delay time

400
Chapter 25 Appendix

1.3.7 CSC-326(M20) setting value list

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
SN MVA 1.000 3000. 120.0 Rated capacity of
reactor
HV UN V 1.000 1000 220.0 Rated voltage of
HVside
HV VT Ratio 1.000 9999. 2200.0. VT ratio of HV side
A 50.00 9999. 1200.0 High voltage side CT
HV CT Pri
primary value
A 1.000 5.000 1.0 High voltage side CT
HV CT Sec
secondary value
HV Voltage Chan 1 3 1 High voltage side
Sel channel selection
A 50.00 9999. 1200.0 Neutral CT (NCT)
HV NCT Pri(REF) Primary(PRI) current
in HV side for REF
Neutral CT (NCT)
Secondary(SEC)
HV NCT Sec(REF) A 1.000 5.000 1.0
current in HV side for
REF
kV 1.000 1000. 10.50 Nominal voltage (UN)
LV UN in Low voltage
(LV)side
1.000 9999. 105.0 Voltage transform-
LV VT Ratio er(VT) Ratio in LV
side
A 50.00 9999. 3000.0 Low voltage side CT
LV CT Pri
primary value
A 1.000 5.000 1.0 Low voltage side CT
LV CT Sec
secondary value
Ω 0.000 9999. 0.0 Primary impedance
Prim.ZofNeu.Point
value of neutral
R
point reactance
A 50.00 9999. 1200.0 Neutral CT (NCT)
Primary(PRI) cur-
LV NCT Pri(BU)
rent in LV side for
backup protection
A 1.000 5.000 1.0 Neutral CT (NCT)
LV NCT Sec(BU)
Secondary(PRI)

401
Chapter 25 Appendix

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
current in LV side for
backup protection
A 0 9999 Rated primary cur-
rent for HV side
HV Rated Cur Pri
(calculated value,
read only)
A 0 9999 Rated primary cur-
rent for HV side
HV Rated Cur Sec
(calculated value,
read only)
0 9999 HV ratio factor for
differential protec-
Ratio Factor KTAH
tion (calculated
value, read only)
0 9999 LV ratio factor for
differential protection
Ratio Factor KTAL
(calculated value,
read only)
0 9999 HV ratio factor, with
zero-sequence cur-
rent calculated, for
Ratio REF KTAH
REF protection
(calculated value,
read only)
0 9999 HV ratio factor with
zero-sequence cur-
rent directly meas-
Ratio REF KNH
ured, for REF pro-
tection (calculated
value, read only)
Instantaneous Dif-
I_Inst Diff A 0.5Ir 20Ir 20 ferential (ID>>)
current setting
Setting value of per-
centage differential
I_Percent Diff A 0.08Ir 4Ir 2.1
protection circuit
(ID>)
I_ResPoint1 Diff A 0.1Ir Ir 2 The 1st breakpoint

402
Chapter 25 Appendix

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
restraint current
(IR1)
The 2nd breakpoint
I_ResPoint2 Diff A 0.1Ir 10Ir 2 restraint current
(IR2)
First ratio restraint
Slope1_Diff 0 0.2 0.2
coefficient
Second ratio restraint
Slope2_Diff 0.2 0.7 0.5
coefficient
Third ratio restraint
Slope3_Diff 0.25 0.95 0.7
coefficient
2nd harmonic(HAR)
Ratio_2nd Harm 0.05 0.80 0.15
ratio
3rd / 5th harmon-
Ratio_3/5th Harm 0.05 0.80 0.35
ic(HAR) ratio
Within the delay 2nd
harmonic block all
three phases. After
T_2nd Harm Block 0 20 20
s the delay, then only
the local phase is
blocked.
Within the delay 5th
harmonic block all
T_3/5th Harm three phases. After
s 0 20 20
Block the delay, then only
the local phase is
blocked.
Current setting for
HV 3I0_REF A 0.08Ir 2Ir 2 HV Restricted Earth
Fault protection
Slope setting for HV
HV Slope_REF 0.2 0.95 0.5 Re-stricted Earth
Fault pro-tection
高压侧零差保护跳
HV T_REF Trip s 0 60 0.03
闸延时定值
HV Restricted Earth
HV 3I0_REF Alarm A 0.08Ir 2Ir 2 Fault alarm current
setting

403
Chapter 25 Appendix

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
HV Restricted Earth
HV T_REF Alarm s 0 60 0.03 Fault alarm time set-
ting
HV overcurrent (O/C)
HV I_OC1 A 0.05Ir 20Ir 5 current setting for
Stage 1
Time setting for HV
HV T_OC1 s 0 60 60
OC, Stage 1
HV overcurrent (O/C)
HV I_OC2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for HV
HV T_OC2 s 0 60 60
OC, Stage 2
Ref to IEC and ANSI
HV Curve_OC Inv 1 12 1
Curves
Ref to IEC and ANSI
HV I_OC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
HV K_OC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
HV A_OC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
HV B_OC Inv s 0 60 0
Curves
Ref to IEC and ANSI
HV P_OC Inv 0 10 0.02
Curves
The angle setting for
HV Angle_OC ° 0 90 45 voltage ahead of
current.
st
The maximum 1
-harmonic current
HV
A 0.25Ir 20Ir 5 setting to remove the
Imax_2H_UnBlk
inrush block, in HV
O/C protection
nd
Inrush 2 harmonic
ratio setting for
HV Ratio_I2/I1 0.07 0.5 0.2
blocking HV O/C
protection
HV T2h_Cross_Blk s 0 60 20 Inrush 2nd harmonic

404
Chapter 25 Appendix

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
cross-block time for
HV O/C protection
HV earth fault (E/F)
HV 3I0_EF1 A 0.05Ir 20Ir 5 protection current
setting for Stage 1
Time setting for HV
HV T_EF1 s 0 60 60
E/F, Stage 1
HV earth fault (E/F)
HV 3I0_EF2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for HV
HV T_EF2 s 0 60 60
E/F, Stage 2
Ref to IEC and ANSI
HV Curve_EF Inv 1 12 1
Curves
Ref to IEC and ANSI
HV 3I0_EF Inv A 0.05Ir 20Ir 1.2
Curves
Ref to IEC and ANSI
HV K_EF Inv 0.05 999 1
Curves
Ref to IEC and ANSI
HV A_EF Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
HV B_EF Inv s 0 60 0
Curves
Ref to IEC and ANSI
HV P_EF Inv 0 10 0.02
Curves
The angle setting for
HV Angle_EF ° 0 90 45 voltage ahead of
current.
The maximum 1st
HV -harmonic current
Imax_2H_UnBlk_E A 0.25Ir 20Ir 5 setting to remove the
F inrush block, in HV
EF protection
The maximum 1st
-harmonic current
HV Ratio_I2/I1_EF 0.07 0.5 0.2 setting to remove the
inrush block, in HV
EF protection
LV 3I0_EF1 A 0.05Ir 20Ir 5 LV earth fault (E/F)

405
Chapter 25 Appendix

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
protection current
setting for Stage 1
Time setting for LV
LV T_EF1 s 0 60 60
E/F, Stage 1
LV earth fault (E/F)
LV 3I0_EF2 A 0.05Ir 20Ir 5 current setting for
Stage 2
Time setting for LV
LV T_EF2 s 0 60 60
E/F, Stage 2
Ref to IEC and ANSI
LV Curve_EF Inv 1 12 1
Curves
Ref to IEC and ANSI
LV 3I0_EF Inv A 0.05Ir 20Ir 1.2
Curves
Ref to IEC and ANSI
LV K_EF Inv 0.05 999 1
Curves
Ref to IEC and ANSI
LV A_EF Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
LV B_EF Inv s 0 60 0
Curves
Ref to IEC and ANSI
LV P_EF Inv 0 10 0.02
Curves
The angle setting for
LV Angle_EF ° 0 90 45 voltage ahead of
current.
The maximum 1st
LV -harmonic current
Imax_2H_UnBlk_E A 0.25Ir 20Ir 5 setting to remove the
F inrush block, in LV
EF protection
The maximum 1st
-harmonic current
LV Ratio_I2/I1_EF 0.07 0.5 0.2 setting to remove the
inrush block, in LV
EF protection
LV neutral over-current
LV 3I0_Neutral (NOC) protection
A 0.05Ir 20Ir 5
OC1 current setting for
Stage 1

406
Chapter 25 Appendix

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Time setting for LV
LV T_Neutral OC1 s 0 60 60
NOC, Stage 1
LV neutral over-current
LV 3I0_Neutral (NOC) protection
A 0.05Ir 20Ir 5
OC2 current setting for
Stage 2
Time setting for LV
LV T_Neutral OC2 s 0 60 60
NOC, Stage 1
Ref to IEC and ANSI
LV Curve_NOC Inv 1 12 1
Curves
Ref to IEC and ANSI
LV 3I0_NOC Inv A 0.05Ir 20Ir 5
Curves
Ref to IEC and ANSI
LV K_NOC Inv 0.05 999 1
Curves
Ref to IEC and ANSI
LV A_NOC Inv s 0 200 0.14
Curves
Ref to IEC and ANSI
LV B_NOC Inv s 0 60 0
Curves
Ref to IEC and ANSI
LV P_NOC Inv 0 10 0.02
Curves
The angle setting for
LV Angle_NOC ° 0 90 45 voltage ahead of
current.
The maximum 1st
LV -harmonic current
Imax_2H_UnBlk_ A 0.25Ir 20Ir 5 setting to remove
NOC the inrush block, in
LV NOC protection
nd
Inrush 2 harmonic
LV Ra- ratio setting for
0.07 0.5 0.2
tio_I2/I1_NOC blocking LV NOC
protection
Pulse Tripping delay
T_Pulse Tripping s 0.2 5 5
time
HV I_VT Fail Minimum Current of
A 0.05Ir 0.2Ir 0.05
VT failure for HV side
Minimum zero or
HV 3I02_ VT Fail A 0.05Ir 0.2Ir 0.5 negative Current of
HV VT fail

407
Chapter 25 Appendix

Min. Max. Default


Setting Unit Description
(Ir:5A/1A) (Ir:5A/1A) (Ir:5A/1A)
Maximum phase to
HV Upe_VT Fail V 7 20 8 earth voltage of HV
VT fail
Maximum phase to
HV Upp_VT Fail V 10 30 16 phase voltage of HV
VT fail
HV Upe_VT Minimum phase to
Normal V 40 65 40 phase voltage of HV
VT normal
Interturn protection
3I0_InterTurn A 0.050 100 100 zero sequence
strartup current

1.3.8 CSC-326(M20) control word list

Setting Unit Min. Max. Default Description

Control 1 0 CT failure detection


CT Fail Detect 0
word 1-On, 0-Off
1 0 Differential instant tripping
Func_Inst Diff Control
0 protection
word
1-On, 0-Off
1 0 Percentage differential pro-
Control
Func_Percent Diff 0 tection
word
1-On, 0-Off
Block Diff at Inrush Inrush block differential pro-
0 1 0 tection
1-block; 0-not block.
2nd Harm Not 2nd harmonic (HAR) inhibit
Wave not the fuzzy recognition
based on the wave-
0 1 0
form(WAVE)
1-2nd harmonic on; 0-
waveform on
Block Diff at Overexcitation block differ-
Overexcit 0 1 0 ential protection
1-block; 0-not block.
Overexcitation stabilization
judgement
Overexcit 3rd NOT 3rd or 5th harmonic (HAR)
0 1 0
5th inhibit on
1-3rd harmonic; 0-5th har-
monic.

408
Chapter 25 Appendix

Setting Unit Min. Max. Default Description


Differential current (DIFF)
Func_Diff Alarm 0 1 0 Alarming on
1-on; 0-off.
Block Diff at Control 1 0 CT failure detection
0
CT_Fail word 1-On, 0-Off
Eliminate calculated 3I0
HV D_side Elimi- when HV side winding is
0 1 0
nate I0 connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0
LV D_side Elimi- when LV side winding is
0 1 0
nate I0 connected in Delta mode
1- eliminate; 0-not eliminate
LV current is included in
calculation of the differential
Diff Includes LV
0 1 0 protection.
Cur
1- Diff Includes LV Cur;
0-Diff NOT Includes LV Cur
HV Restricted earth fault
HV Func_REF Trip 0 1 0 trip-stage ON
1-on; 0-off.
HV Restricted earth fault
HV Func_REF
0 1 0 Alarm-stage ON
Alarm
1-on; 0-off.
Block HV REF when CT
Block HV REF at
0 1 0 failure,
HV CT_Fail
1-Block;0-unblock
st
HV Func_OC1 The 1 stage of HV OC
(OC_1) protection is
0 1 0
switched ON
1-on; 0-off.
HV OC1 Inrush Inrush 2nd harmonic detec-
Block tion HV OC Stage 1 is
0 1 0
switched ON
1-on; 0-off.
HV Func_OC2 The 2nd stage of HV OC
(OC_2) protection is
0 1 0
switched ON
1-on; 0-off.
HV OC2 Inrush 0 1 0 Inrush 2nd harmonic detec-

409
Chapter 25 Appendix

Setting Unit Min. Max. Default Description


Block tion HV OC Stage 2 is
switched ON
1-on; 0-off.
HV Func_OC Inv The IDMTL inverse time
stage of HV OC protection is
0 1 0
switched ON
1-on; 0-off.
HV OC Inv Inrush Inrush 2nd harmonic detec-
Block tion HV OC IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
HV Func_EF1 The 1st stage of HV earth
fault (EF_1) protection is
0 1 0
switched ON
1-on; 0-off.
HV EF1 Direction Direction (DIR) detection of
HV EF Stage 1 is switched
0 1 0
ON
1-on; 0-off.
HV Func_EF2 The 2nd stage of HV earth
fault (EF_2) protection is
0 1 0
switched ON
1-on; 0-off.
HV EF2 Direction Direction (DIR) detection of
HV EF Stage 2 is switched
0 1 0
ON
1-on; 0-off.
HV Func_EF Inv The IDMTL inverse time
stage of HV EF protection is
0 1 0
switched ON
1-on; 0-off.
HV EF Inv Inrush Inrush 2nd harmonic detec-
Block tion HV EF IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block HV EF at HV Block HV EF when there is
CT_Fail 0 1 0 HV CT failure
1-Block; 0-NOT block
LV Func_EF1 The 1st stage of LV earth
0 1 0 fault (EF_1) protection is
switched ON

410
Chapter 25 Appendix

Setting Unit Min. Max. Default Description


1-on; 0-off.

LV EF1 Inrush Inrush 2nd harmonic detec-


Block tion LV EF Stage 1 is
0 1 0
switched ON
1-on; 0-off.
LV Func_EF2 The 2nd stage of LV earth
fault (EF_2) protection is
0 1 0
switched ON
1-on; 0-off.
LV EF2 Inrush Inrush 2nd harmonic detec-
Block tion LV EF Stage 2 is
0 1 0
switched ON
1-on; 0-off.
LV Func_EF Inv The IDMTL inverse time
stage of LV EF protection is
0 1 0
switched ON
1-on; 0-off.
LV EF Inv Inrush Inrush 2nd harmonic detec-
Block tion LV EF IDMTL inverse
0 1 0
time is switched ON
1-on; 0-off.
Block LV EF at LV Block LV EF when there is
CT_Fail 0 1 0 LV CT failure
1-Block; 0-NOT block
st
The 1 stage of LV neutral
LV Func_Neu OC (OC_1) protection is
0 1 0
OC1 switched ON
1-on; 0-off.
Inrush 2nd harmonic de-
LV Neu OC1 In- tection LV neutral OC
0 1 0
rush Block Stage 1 is switched ON
1-on; 0-off.
The 2nd stage of LV neu-
LV Func_Neu tral OC (OC_2) protection
0 1 0
OC2 is switched ON
1-on; 0-off.
Inrush 2nd harmonic de-
LV Neu OC2 In- tection LV neutral OC
0 1 0
rush Block Stage 2 is switched ON
1-on; 0-off.

411
Chapter 25 Appendix

Setting Unit Min. Max. Default Description

The IDMTL inverse time


LV Func_Neu stage of LV neutral OC
0 1 0
OC Inv protection is switched ON
1-on; 0-off.
Inrush 2nd harmonic de-
tection LV neutral OC
LV Neu OC Inv
0 1 0 IDMTL inverse time stage
Inrush Block
is switched ON
1-on; 0-off.
VT failuredetection of
HV VT Fail De-
0 0 0 HVside
tect
1-on; 0-off.
HV Earthing mode:
HV Solid Earth 1: Solid earthed system ;
0 0 1
0: isolated system or re-
sistance earthed.
1 0 To select whether the 1st
Control binary input (BI1) trip the 1st
BI1 Enable BO1 0
word binary output (BO1) or not.
1-On, 0-Off
1 0 To select BO1 tripping in
pulse mode or in direct mode
BO1 Pulse Trip- Control 0- BO1 Direct Tripping,
0
ping word without delay
1- BO1 Pulse Tripping, with
preset delay time
1 0 To select whether the 2nd
Control binary input (BI2) trip the 2nd
BI2 Enable BO2 0
word binary output (BO2) or not.
1-On, 0-Off
1 0 To select BO2 tripping in
pulse mode or in direct mode
BO2 Pulse Trip-
Control 0- BO2 Direct Tripping,
ping 0
word without delay
1- BO2 Pulse Tripping, with
preset delay time
whether BI1 initiate HV side
BI1 Init HV CBF 0 0 0 CBF or not
0 - initiate, 1 – not initiate
whether BI1 initiate LV side
BI1 Init LV CBF 0 0 0
CBF or not

412
Chapter 25 Appendix

Setting Unit Min. Max. Default Description

0 - initiate, 1 – not initiate

whether BI2 initiate HV side


BI2 Init HV CBF 0 0 0 CBF or not
0 - initiate, 1 – not initiate
whether BI2 initiate LV side
BI2 Init LV CBF 0 0 0 CBF or not
0 - initiate, 1 – not initiate
Interturn protection
Inter Turn 0 1 0
1-ON,0-OFF

1 General report list


Table 254 event report list

Information Description

Relay startup The relay is initiated by startup elements

Per Diff Trip A

Per Diff Trip B Treble slope percent Differential protection (ID>) trip for phase A/B/C

Per Diff Trip C

Inst Diff Trip A

Inst Diff Trip B Instantaneous Differential protection (ID>>) trip for phase A/B/C

Inst Diff Trip C

HV REF Trip HV Restricted Earth fault (REF) protection trip

MV REF Trip MV Restricted Earth fault (REF) protection trip

LV REF Trip LV Restricted Earth fault (REF) protection trip

Def V/F Trip Overexcitation protection(V/F) tripping (Trip) with definite (DEF) and
Inv V/F Trip inverse(IVR) time characteristic

HV OC Inv Trip Inverse time stage of HV overcurrent protection trip

HV OC1 Trip HV overcurrent stage 1 trip

HV OC2 Trip HV overcurrent stage 2 trip

MV OC Inv Trip Inverse time stage of MV overcurrent protection trip

MV OC1 Trip MV overcurrent stage 1 trip

MV OC2 Trip MV overcurrent stage 2 trip

413
Chapter 25 Appendix

Information Description

LV OC Inv Trip Inverse time stage of LV overcurrent protection trip

LV OC1 Trip LV overcurrent stage 1 trip

LV OC2 Trip LV overcurrent stage 2 trip

HV EF Inv Trip Inverse time stage of HV earth fault protection trip

HV EF1 Trip HV earth fault stage 1 trip

HV EF2 Trip HV earth fault stage 2 trip

MV EF Inv Trip Inverse time stage of MV earth fault protection trip

MV EF1 Trip MV earth fault stage 1 trip

MV EF2 Trip MV earth fault stage 2 trip

LV EF Inv Trip Inverse time stage of LV earth fault protection trip

LV EF1 Trip LV earth fault stage 1 trip

LV EF2 Trip LV earth fault stage 2 trip

HV NOC Inv Trip Inverse time stage of neutral OC protection trip

HV NOC1 Trip HV neutral OC stage 1 trip

HV NOC2 Trip HV neutral OC stage 2 trip

MV EF Inv Trip Inverse time stage of MV neutral OC protection trip

MV EF1 Trip MV neutral OC stage 1 trip

MV EF2 Trip MV neutral OC stage 2 trip

LV EF Inv Trip Inverse time stage of LV neutral OC protection trip

LV EF1 Trip LV neutral OC stage 1 trip

LV EF2 Trip LV neutral OC stage 2 trip

HV Therm OL Trip HV Thermal (TEM) Overload(OVLD) tripping (Trip)

MV Therm OL Trip MV Thermal (TEM) Overload(OVLD) tripping (Trip)

HV OV1 Trip HV overvoltage stage 1 trip

HV OV2 Trip HV overvoltage stage 2 trip

MV OV1 Trip MV overvoltage stage 1 trip

MV OV2 Trip MV overvoltage stage 2 trip

HV CBF1 Trip HV circuit breaker failure protection stage 1 trip

HV CBF2 Trip HV circuit breaker failure protection stage 2 trip

HV CBF Init Internal or external initiate HV circuit breaker failure protection

MV CBF1 Trip MV circuit breaker failure protection stage 1 trip

414
Chapter 25 Appendix

Information Description

MV CBF2 Trip MV circuit breaker failure protection stage 2 trip

MV CBF Init Internal or external initiate MV circuit breaker failure protection

LV CBF1 Trip LV circuit breaker failure protection stage 1 trip

LV CBF2 Trip LV circuit breaker failure protection stage 2 trip

LV CBF Init Internal or external initiate LV circuit breaker failure protection

HV Dead Zone HV Dead zone trip

MV Dead Zone MV Dead zone trip

LV Dead Zone LV Dead zone trip

HV STUB Trip HV stub protection trip

MV STUB Trip MV stub protection trip

LV STUB Trip LV stub protection trip

HV PD Trip HV poles discordance protection trip

MV PD Trip MV poles discordance protection trip

HV VT Fail HV VT Fail alarm

MV VT Fail MV VT Fail alarm

LV VT Fail LV VT Fail alarm

Table 255 Alarm report list

No Abbr. (LCD Display) Description


1 Battery Off Battery off
2 BI Breakdown Binary input breakdown
3
BI Check Err Binary input checking is error

4
BI Comm Fail Binary input communication fail

5
BI Config Err Binary input configuration is error

6
BI EEPROM Err The EEPROM of binary input is error

7 BI Input Err Binary input error


8 BI_CBF Err Binary input error of CBF
9 BO Breakdown Binary output breakdown
10
BO Comm Fail Binary output communication fail

11
BO EEPROM Err The EEPROM of binary output is error

415
Chapter 25 Appendix

12
BO No Response No response of binary output

13
BOConfig Err Binary output configuration is error

14
CB auxiliary contacts indicate that one
CB Err Blk PD pole is open but at the same time current is
flowing through the pole.

15
CB Open A Err Binary input error of CB Open A

16
CB Open B Err Binary input error of CB Open B

17
CB Open C Err Binary input error of CB Open C

18 CB Status Err CB Status Error


19 Def V/F Alarm Def V/F Alarm
20
Inrush detection impose a blocking condi-
Diff 2har Blk
tion to differential protection
21
3rd or 5th harmonic detection impose a
Diff 3/5har Blk
blocking condition to differential protection

22
Differential current exceeds the threshold
Diff Cur Alarm
value
23
EquipPara Err Equipment parameter is error

24 FLASH Check Err FLASH checking is error


25
H BI MCB VT Fail Binary input error of VT fail of MCB

26
H BI_V3P_MCB Err Binary input error of three phase MCB

27 HV 3U0 Alarm HV 3U0 Alarm


28
HV BLK VOL REGU Block tap changer control of transformer

29
a blocking condition is imposed to backup
HV Inrush Blk BU
protection by inrush condition detection

30 HV Load Alarm HV Load Alarm


31
HV OV1 Alarm Stage 1 of overvoltage protection alarm

32
HV OV2 Alarm Stage 2 of overvoltage protection alarm

33 HV REF 3I0 Alarm HV REF 3I0 Alarm


34
HV Therm OL Alm HV Thermal Overload Alarm

35 HV VT Fail HV VT Fail

416
Chapter 25 Appendix

36 Negative-sequence current exceeds a thresh-


HV1 I2 Alarm
old

37 Negative-sequence current exceeds a thresh-


HV2 I2 Alarm
old
38
L BI MCB VT Fail Binary input error of VT fail of MCB

39
L BI_V3P_MCB Err Binary input error of three phase MCB

40 LV 3U0 Alarm LV 3U0 Alarm


41 Negative-sequence current exceeds a thresh-
LV I2 Alarm
old

42
a blocking condition is imposed to backup
LV Inrush Blk BU
protection by inrush condition detection

43 LV Load Alarm LV Load Alarm


44 LV REF 3I0 Alarm LV REF 3I0 Alarm
45 LV Thermal Overload Alarm
LV Therm OL Alm

46 LV VT Fail LV VT Fail
47 LW Load Alarm LW Load Alarm
48
M BI MCB VT Fail Binary input error of VT fail of MCB

49
M BI_V3P_MCB Err Binary input error of three phase MCB

50 MV 3U0 Alarm MV 3U0 Alarm


51
MV BLK VOL REGU Block tap changer control of transformer

52 Negative-sequence current exceeds a thresh-


MV I2 Alarm
old
53
a blocking condition is imposed to backup
MV Inrush Blk BU
protection by inrush condition detection

54 MV Load Alarm MV Load Alarm


55
MV OV1 Alarm Stage 1 of overvoltage protection alarm

56
MV OV2 Alarm Stage 2 of overvoltage protection alarm

57 MV REF 3I0 Alarm MV REF 3I0 Alarm


58 MV Thermal Overload Alarm
MV Therm OL Alm

59 MV VT Fail MV VT Fail
60 NO/NC Discord NO/NC discord
61 Ph_A CT Fail Phase A CT Fail

417
Chapter 25 Appendix

62 Ph_B CT Fail Phase B CT Fail


63 Ph_C CT Fail Phase C CT Fail
64 ROM Verify Err ROM verifying is error
65 Sampling Err Sampling is error
66 Set Group Err Setting group is error
67 Setting Err Setting value is error
68 Soft Version Err Soft version is error
69 SRAM Check Err SRAM checking is error
70
Sys Config Err System configuration is error

71
Test BO Un_reset Do not reset after testing binary output

72 Voltage or frequency is out of the permissible


V or F Exceed
range

Table 256 operation report list

No Information Description

1 Func_Diff On Differential protection is switched ON (by CW)


2 Func_Diff Off Differential protection is switched OFF (by CW)
3 HV Func_REF On HV REF protection is switched ON (by CW)
4 HV Func_REF Off HV REF protection is switched OFF (by CW)
5 MV Func_REF On MV REF protection is switched ON (by CW)
6 MV Func_REF Off MV REF protection is switched OFF (by CW)
7 LV Func_REF On LV REF protection is switched ON (by CW)
8 LV Func_REF Off LV REF protection is switched OFF (by CW)
9 Func_Overexc On Overexcitation protection is switched ON (by CW)
10 Func_Overexc Off Overexcitation protection is switched OFF (by CW)
11 Overcurrent protection of HV side is switched ON
HV Func_OC On
(by CW)
12 Overcurrent protection of HV side is switched OFF
HV Func_OC Off
(by CW)
13 Overcurrent protection of MV side is switched ON
MV Func_OC On
(by CW)
14 Overcurrent protection of MV side is switched OFF
MV Func_OC Off
(by CW)
15 Overcurrent protection of LV side is switched ON (by
LV Func_OC On
CW)
16 Overcurrent protection of LV side is switched OFF
LV Func_OC Off
(by CW)

418
Chapter 25 Appendix

No Information Description

17 Earth fault protection of HV side is switched ON (by


HV Func_EF On
CW)
18 Earth fault protection of HV side is switched OFF (by
HV Func_EF Off
CW)
19 Earth fault protection of MV side is switched ON (by
MV Func_EF On
CW)
20 Earth fault protection of MV side is switched OFF
MV Func_EF Off
(by CW)
21 Earth fault protection of LV side is switched ON (by
LV Func_EF On
CW)
22 Earth fault protection of LV side is switched OFF (by
LV Func_EF Off
CW)
23 HV Func_NOC On NOC protection of HV side is switched ON (by CW)
24 HV Func_NOC Off NOC protection of HV side is switched OFF (by CW)
25 MV Func_NOC On NOC protection of MV side is switched ON (by CW)
26 MV Func_NOC Off NOC protection of MV side is switched OFF (by CW)
27 LV Func_NOC On NOC protection of LV side is switched ON (by CW)
28 LV Func_NOC Off NOC protection of LV side is switched OFF (by CW)
29 HV thermal overload protection is switched ON (by
HV Func_Therm On
CW)
30 HV thermal overload protection is switched OFF (by
HV Func_Therm Off
CW)
31 MV thermal overload protection is switched ON (by
MV Func_Therm On
CW)
32 MV thermal overload protection is switched OFF (by
MV Func_Therm Off
CW)
33 HV Func_OL On HV overload protection is switched ON (by CW)
34 HV Func_OL Off HV overload protection is switched OFF (by CW)
35 MV Func_OL On MV overload protection is switched ON (by CW)
36 MV Func_OL Off MV overload protection is switched OFF (by CW)
37 LV Func_OL On LV overload protection is switched ON (by CW)
38 LV Func_OL Off LV overload protection is switched OFF (by CW)
39 HV Func_OV On HV overvoltage protection is switched ON (by CW)
40 HV Func_OV Off HV overvoltage protection is switched OFF (by CW)
41 MV Func_OV On MV overvoltage protection is switched ON (by CW)
42 MV Func_OV Off MV overvoltage protection is switched OFF (by CW)
43 HV Func_DZ On HV DZ function on
44 HV Func_DZ Off HV DZ function off
45 MV Func_DZ On MV DZ function on

419
Chapter 25 Appendix

No Information Description

46 MV Func_DZ Off MV DZ function off


47 LV Func_DZ On LV DZ function on
48 LV Func_DZ Off LV DZ function off
49 HV Func_STUB On HV stub function on
50 HV Func_STUB Off HV stub function Off
51 MV Func_STUB On MV stub function on
52 MV Func_STUB Off MV stub function Off
53 LV Func_STUB On LV stub function on
54 LV Func_STUB Off LV stub function Off
55 HV Func_PD On HV poles discordance function on
56 HV Func_PD Off HV poles discordance function off
57 MV Func_PD On MV poles discordance function on
58 MV Func_PD Off MV poles discordance function off
59 HV Func_VT On HV VT failure supervision function on
60 HV Func_VT Off HV VT failure supervision function off
61 MV Func_VT On MV VT failure supervision function on
62 MV Func_VT Off MV VT failure supervision function off
63 LV Func_VT On LV VT failure supervision function on
64 LV Func_VT Off LV VT failure supervision function off

2 Time inverse characteristic


2.1 11 kinds of IEC and ANSI inverse time
characteristic curves
In the setting, if the curve number is set for inverse time characteristic, which
is corresponding to the characteristic curve in the following tabel. Both IEC
and ANSI based standard curves are available.

Table 257 11 kinds of IEC and ANSI inverse time characteristic

Curves No. IDMTL Curves Parameter A Parameter P Parameter B

1 IEC INV. 0.14 0.02 0

2 IEC VERY INV. 13.5 1.0 0

420
Chapter 25 Appendix

3 IEC EXTERMELY INV. 80.0 2.0 0

4 IEC LONG INV. 120.0 1.0 0

5 ANSI INV. 8.9341 2.0938 0.17966

6 ANSI SHORT INV. 0.2663 1.2969 0.03393

7 ANSI LONG INV. 5.6143 1 2.18592

8 ANSI MODERATELY
0.0103 0.02 0.0228
INV.

9 ANSI VERY INV. 3.922 2.0 0.0982

10 ANSI EXTERMELY INV. 5.64 2.0 0.02434

11 ANSI DEFINITE INV. 0.4797 1.5625 0.21359

2.2 User defined characteristic


For the inverse time characteristic, also can be set as user defined
characteristic if the setting is set to 12.

Equation 54

where:

A: Time factor for inverse time stage

B: Delay time for inverse time stage

P: index for inverse time stage

K: Set time multiplier for step n

3 CT Requirement
3.1 Overview
In practice, the conventional magnetic- core current transformer (hereinafter
as referred CT) is not able to transform the current signal accurately in whole
fault period of all possible faults because of manufactured cost and installa-

421
Chapter 25 Appendix

tion space limited. CT Saturation will cause distortion of the current signal
and can result in a failure to operate or cause unwanted operations of some
functions. Although more and more protection IEDs have been designed to
permit CT saturation with maintained correct operation, the performance of
protection IED is still depended on the correct selection of CT.

3.2 Current transformer classification


The conventional CTs are usually manufactured in accordance with the
standard, IEC 60044, ANSI / IEEE C57.13, ANSI / IEEE C37.110 or other
comparable standards, which CTs are specified in different protection class.

Currently, the CT for protection are classified according to functional per-


formance as follows:

 Class P CT

Accuracy limit defined by composite error with steady symmetric primary


current. No limit for remanent flux.

 Class PR CT

CT with limited remanence factor for which, in some cased, a value of the
secondary loop time constant and/or a limiting value of the winding re-
sistance may also be specified.

 Class PX CT

Low leakage reactance for which knowledge of the transformer second-


ary excitation characteristic, secondary winding resistance, secondary
burden resistance and turns ratio is sufficient to assess its performance
in relation to the protective relay system with which it is to be used.

 Class TPS CT

Low leakage flux current transient transformer for which performance is


defined by the secondary excitation characteristics and turns ratio error
limits. No limit for remanent flux

 Class TPX CT

Accuracy limit defined by peak instantaneous error during specified tran-


sient duty cycle. No limit for remanent flux.

 Class TPY CT

Accuracy limit defined by peak instantaneous error during specified tran-


sient duty cycle. Remanent flux not to exceed 10% of the saturation flux..

 Class TPZ CT

Accuracy limit defined by peak instantaneous alternating current com-

422
Chapter 25 Appendix

ponent error during single energization with maximum d.c. offset at


specified secondary loop time constant. No requirements for d.c. com-
ponent error limit. Remanent flux to be practically negligible.

 TPE class CT (TPE represents transient protection and electronic type


CT)

3.3 Abbreviations (according to IEC 60044-1, -6, as


defined)
Abbrev. Description
Esl Rated secondary limiting e.m.f
Eal Rated equivalent limiting secondary e.m.f
Ek Rated knee point e.m.f
Uk Knee point voltage (r.m.s.)
Kalf Accuracy limit factor
Kssc Rated symmetrical short-circuit current factor
K’ssc Effective symmetrical short-circuit current factor
K”ssc based on different Ipcf
Kpcf Protective checking factor
Ks Specified transient factor
Kx Dimensioning factor
Ktd Transient dimensioning factor
Ipn Rated primary current
Isn Rated secondary current
Ipsc Rated primary short-circuit current
Ipcf protective checking current
Isscmax Maximum symmetrical short-circuit current
Rct Secondary winding d.c. resistance at 75 °C /
167 °F (or other specified temperature)
Rb Rated resistive burden
R’b = Rlead + Rrelay = actual connected resistive
burden
Rs Total resistance of the secondary circuit, inclu-
sive of the secondary winding resistance cor-
rected to 75℃, unless otherwise specified, and
inclusive of all external burden connected.
Rlead Wire loop resistance
Zbn Rated relay burden
Zb Actual relay burden
Tp Specified primary time constant
Ts Secondary loop time constant

423
Chapter 25 Appendix

3.4 General current transformer requirements

3.4.1 Protective checking current

The current error of CT should be within the accuracy limit required at speci-
fied fault current.

To verify the CT accuracy performance, Ipcf, primary protective checking


current, should be chose properly and carefully.

For different protections, Ipcf is the selected fault current in proper fault po-
sition of the corresponding fault, which will flow through the verified CT.

To guarantee the reliability of protection relay, Ipcf should be the maximum


fault current at internal fault. E.g. maximum primary three phase short-circuit
fault current or single phase earth fault current depended on system se-
quence impedance, in different positions.

Moreover, to guarantee the security of protection relay, Ipcf should be the


maximum fault current at external fault.

Last but not least, Ipcf calculation should be based on the future possible
system power capacity

Kpcf, protective checking factor, is always used to verified the CT perfor-


mance

To reduce the influence of transient state, Kalf, Accuracy limit factor of CT,
should be larger than the following requirement

Ks, Specified transient factor, should be decided based on actual operation


state and operation experiences by user.

3.4.2 CT class

The selected CT should guarantee that the error is within the required ac-

424
Chapter 25 Appendix

curacy limit at steady symmetric short circuit current. The influence of short
circuit current DC component and remanence should be considered, based
on extent of system transient influence, protection function characteristic,
consequence of transient saturation and actual operating experience. To ful-
fill the requirement on a specified time to saturation, the rated equivalent
secondary e.m.f of CTs must higher than the required maximum equivalent
secondary e.m.f that is calculated based on actual application.

For the CTs applied to transmission line protection, transformer differential


protection with 330kV voltage level and above, and 300MW and above gen-
erator-transformer set differential protection, the power system time constant
is so large that the CT is easy to saturate severely due to system transient
state. To prevent the CT from saturation at actual duty cycle, TP class CT is
preferred.

For TPS class CT, Eal (rated equivalent secondary limiting e.m.f) is generally
determined as follows:

Where

Ks: Specified transient factor

Kssc: Rated symmetrical short-circuit current factor

For TPX, TPY and TPZ class CT, Eal (rated equivalent secondary limiting
e.m.f) is generally determined as follows:

Where

Ktd: Rated transient dimensioning factor

Considering at short circuit current with 100% offset

For C-t-O duty cycle,

t: duration of one duty cycle;

For C-t’-O-tfr-C-t”-O duty cycle,

425
Chapter 25 Appendix

t’: duration of first duty cycle;

t”: duration of second duty cycle;

tfr: duration between two duty cycle;

For the CTs applied to 110 - 220kV voltage level transmission line protection,
110 - 220kV voltage level transformer differential protection, 100-200MW
generator-transformer set differential protection, and large capacity motor
differential protection, the influence of system transient state to CT is so less
that the CT selection is based on system steady fault state mainly, and leave
proper margin to tolerate the negative effect of possible transient state.
Therefore, P, PR, PX class CT can be always applied.

For P class and PR class CT, Esl (the rated secondary limited e.m.f) is gen-
erally determined as follows:

Kalf: Accuracy limit factor

For PX class CT, Ek (rated knee point e.m.f) is generally determined as fol-
lows:

Kx: Demensioning factor

For the CTs applied to protection for110kV voltage level and below system,
the CT should be selected based on system steady fault state condition. P
class CT is always applied.

3.4.3 Accuracy class

The CT accuracy class should guarantee that the protection relay applied is
able to operate correctly even at a very sensitive setting, e.g. for a sensitive
residual overcurrent protection. Generally, the current transformer should
have an accuracy class, which have an current error at rated primary current,
that is less than ±1% (e.g. class 5P).

If current transformers with less accuracy are used it is advisable to check


the actual unwanted residual current during the commissioning.

3.4.4 Ratio of CT

The current transformer ratio is mainly selected based on power system data

426
Chapter 25 Appendix

like e.g. maximum load. However, it should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to
be detected with the selected CT ratio. The minimum operating current is
different for different functions and settable normally. So each function
should be checked separately.

3.4.5 Rated secondary current

There are 2 standard rated secondary currents, 1A or 5A. Generally, 1 A


should be preferred, particularly in HV and EHV stations, to reduce the bur-
den of the CT secondary circuit. Because 5A rated CTs, i.e. I2R is 25x com-
pared to only 1x for a 1A CT. However, in some cases to reduce the CT
secondary circuit open voltage, 5A can be applied.

3.4.6 Secondary burden

Too high flux will result in CT saturation. The secondary e.m.f is directly
proportional to linked flux. To feed rated secondary current, CT need to
generate enough secondary e.m.f to feed the secondary burden. Conse-
quently, Higher secondary burden, need Higher secondary e.m.f, and then
closer to saturation. So the actual secondary burden R’b must be less than
the rated secondary burden Rb of applied CT, presented

Rb > R’b

Equation 55

The CT actual secondary burden R’b consists of wiring loop resistance


Rlead and the actual relay burdens Zb in whole secondary circuit, which is
calculated by following equation

R’b = Rlead + Zb

Equation 56

The rated relay burden, Zbn, is calculated as below:

427
Chapter 25 Appendix

Equation 57

Where
Sr: the burden of IED current input channel per phase, in VA;

For earth faults, the loop includes both phase and neutral wire, normally
twice the resistance of the single secondary wire. For three-phase faults the
neutral current is zero and it is just necessary to consider the resistance up to
the point where the phase wires are connected to the common neutral wire.
The most common practice is to use four wires secondary cables so it nor-
mally is sufficient to consider just a single secondary wire for the three-phase
case.

In isolated or high impedance earthed systems the phase-to-earth fault is not


the considered dimensioning case and therefore the resistance of the single
secondary wire always can be used in the calculation, for this case.

3.5 Rated equivalent secondary e.m.f requirements


To guarantee correct operation, the current transformers (CTs) must be able
to correctly reproduce the current for a minimum time before the CT will
begin to saturate.

Transformer differential protection

It is recommended that the CT of each side could be same class and with
same characteristic to guarantee the protection sensitivity.

For the CTs applied to 330kV voltage level and above step-down transformer,
TPY class CT is preferred for each side.

For the CTs of high voltage side and middle voltage side, Eal should be ver-
ified at external fault C-O-C-O duty cycle.

For the CT of low voltage side in delta connection, Eal should be verified at
external three phase short circuit fault C-O duty cycle.

Eal must meet the requirement based on following equations:

Equation 58

Where

K’td: Recommended transient dimensioning factor for verification, 3


recommended

428
Chapter 25 Appendix

For 220kV voltage level and below transformer differential protection, P


Class, PR class and PX class is able to be used. Because the system time
constant is less relatively, and then DC component is less, the probability of
CT saturation due to through fault current at external fault is reduced more
and more.

For P Class, PR class CT, Esl can be verified as below:

Equation 59

Where

Ks: Specified transient factor, 2 recommended

For PX class CT, Ek can be verified as below:

Equation 60

Where

Ks: Specified transient factor, 2 recommended

429