Perator S Anual: RO RO TAR TAR
Perator S Anual: RO RO TAR TAR
P H O T O V O LTA I C S Y S T E M C O N T R O L L E R S
OPERATOR’S MANUAL
MODEL RATINGS
2
• Even though the system is only 12 or 24 volts, both the PV
array and battery can contain lethal amounts of electrical
power.
• Do not splash water on the controller, do not allow water to
enter the ventilation slots.
• Do not touch the heatsink. Under certain operating condi-
tions, the heatsink can become hot.
• Always install the controller in a vertical position. Ensure
adequate space for ventilation, and never block the ventila-
tion slots.
• Do not short-circuit the PV array while connected to the
controller. This will damage the controller.
• Do not exceed the current ratings of the controller.
3
3. Connect the BATTERY first. Observe that all LED’s flash in
sequence one time.
4. Connect battery SENSE leads (if utilized). This is recom-
mended if the controller is placed more than 2 to 3 meters
from the battery.
5. Connect the PV (solar array). With sunlight, the green
CHARGING LED will light in 2 minutes.
6. Connect the LOAD. If the LED indicators begin to flash, the
load is shorted. Refer to the detailed installation instructions.
7. The BATTERY TYPE at start-up is sealed (LED on). If the PV
system battery is a flooded type, use a piece of wire to touch
the SELECT PIN to the battery minus terminal to change to
flooded (LED goes off). This must be reset every time the
battery is disconnected.
8. The ProStar will automatically select for a 12 or 24 volt sys-
tem. If this is a 24 volt system, first check to confirm that the
battery is above 17 volts, and boost-charge the battery if
under 17 volts.
9. Observe the LED indicators. After a few minutes to clear
delays and resets, the LED’s should operate per system con-
ditions as described in the following chart (section 3.1).
10. For effective surge protection, it is recommended that the
negative system conductor be properly grounded.
3.0 INDICATORS
4
BATTERY CHARGE Green ON: Battery near full charge
BATTERY CHARGE Yellow ON: Battery at middle capacity
(about 35% to 80% SOC)
NOTE: does not indicate
a problem
BATTERY CHARGE Red FLASH: Battery at low charge,
warning
ON: Load has been disconnected
All LED’s SEQUENTIAL FLASH:
Load is short-circuited
High temperature shutdown
High voltage disconnect
Initial battery connection (startup)
(flashes one cycle only)
5
4.0 INSTALLATION INSTRUCTIONS
6
4.2 INSTALLATION PROCEDURE
GENERAL INSTALLATION NOTES:
• The ProStar prevents reverse current leakage at night, so
a blocking diode is not required in the system.
• The ProStar is designed to regulate ONLY PV power. Do
NOT connect to any other type of power generator.
• The ProStar automatically selects 12 or 24 volt setpoints at
battery connection. Do not connect a battery larger than 24
vdc (12 cells) or the controller will be damaged.
• The connector terminals will accept a maximum wire size
of AWG #6 (solid/multistrand) or AWG #8 (fine strand) or a
maximum wire diameter of 5.0 mm. Use a flathead insulated
screwdriver (up to 5 mm).
INSTALLATION STEPS:
1. Inspect the controller for shipping damage. Mount the
ProStar to a vertical surface (4 stainless steel #8 self-tapping
screws are included). Do not install directly over an easily
combustible surface since the heatsink may get hot under
certain operating conditions.
7
Multiple ProStar units can be paralleled at the system battery,
but be careful that no PV sub-array exceeds a controller’s
individual current rating.
3. BATTERY (+ and -) Before connecting the battery, check the
open-circuit voltage of the system battery. It must be at least
8 volts for the controller to operate. If your PV system is 24
volts, the battery MUST be over 17 volts, or the controller
will regulate at the 12 volt setpoints. Any battery starting at
less than 11 (or 22) volts should be fully charged before con-
nection to a PV system, or battery life will be significantly
reduced.
Connect the battery and observe that all 5 LED’s flash in se-
quence one time. If the LED indicators do not sequence or
the BATTERY TYPE LED does not light, check the battery
polarity.
The green, yellow or red BATTERY CHARGE LED will light
depending on the battery charge state.
4. SENSE (+ and -) Battery sense leads are recommended if the
controller is located more than 2 or 3 meters from the bat-
tery. This will avoid voltage drops and improve the control
accuracy. However, if the sense leads are not connected, the
controller will default to BATTERY connections for control.
A smaller wire size can be used for sense (draws less than 1
mA current). Note that the wire entry slots into the case for
SENSE are smaller than the other system power terminals to
prevent mixing the BATTERY and SENSE connections.
5. PV (+ and -) Use these terminals to connect the solar array.
First confirm that the PV modules are wired for the same
voltage as the battery (either 12 or 24 volts).
Use caution, since the PV array will generate power whenever
in sunlight. Also, be careful not to short-circuit the PV array
while connected to the controller, since this will damage the
controller.
There is a 2 minute delay after connection of the PV array
before the controller begins charging. Check that the
8
CHARGING indicator comes on after 2 minutes to confirm
that the PV array has been properly connected.
6. LOAD (+ and -) Turn the load off. Connect the load to
LOAD terminals, and then turn the load on. If the battery is
below the load disconnect voltage, the load will be discon-
nected (normal LVD). There may be a short delay.
If the load is short-circuited, the controller will instantly
disconnect the load and flash the LED’s in sequence. If this
occurs, remove the load and repair the short. It will then be
necessary to disconnect the BATTERY + wire and reconnect
the battery to reset the ProStar for normal operation (or press
the red DISCONNECT button twice if the LCD meter option
is supplied).
7. The BATTERY TYPE defaults to sealed, and the green LED
should be on. If your battery is a flooded type, use a piece of
wire to touch the SELECT PIN to the BATTERY - (negative)
terminal or to the negative battery post. This will change the
battery charging setpoints from a sealed to a flooded battery.
When the change has been made, the green BATTERY TYPE
LED will turn off.
Check the LED to confirm the change. This SELECT PIN can
be used repeatedly. No damage can occur from touching the
pin to other terminals or parts of the controller. The BAT-
TERY TYPE can be changed between sealed and flooded
any number of times.
9
5.0 OPERATION
10
Automatic Safety • Load Short-Circuit: Instant load
Disconnects disconnect. The LED’s flash in sequence.
Battery must be disconnected to clear
and reset (see section 4.2-6)
• High Temperature: At very high tempera-
tures, PV array first disconnected, then
the load. The LED’s flash in sequence.
Auto reconnect as temperature falls.
• Emergency: If battery is disconnected,
the PV and load are instantly discon-
nected for safety and to protect the load.
Temperature Battery charging, equalization, and high
Compensation voltage functions are corrected for ambient
temperature variations.
Equalization Battery charging is automatically boosted
based on low state-of-charge or elapsed
time.
11
6. Inspect for dirt, insects, nests, and corrosion.
7. Check that the controller functions and LED indicators are
correct for the system conditions at that time.
5.4 TROUBLESHOOTING
If something seems wrong with the PV system (for example,
the load is not working or the battery is not charging), then
it may be necessary to troubleshoot the controller. Some
basic troubleshooting procedures are listed below.
CAUTIONS:
• Troubleshooting should be attempted by qualified
personnel only.
• Remember that a battery can cause serious damage if
shorted.
• Do not disassemble the ProStar from its case. There are
no user serviceable parts inside the ProStar.
• Observe all normal precautions when working with
energized circuitry.
12
the battery. This will cause undercharging of the battery.
See section 4.2-4.
g. Check the condition of the battery. Determine if the battery
voltage declines at night with no load. If unable to maintain
its voltage, the battery may be failing.
h. If all the ProStar LED’s are flashing in sequence, see item
number 4 below.
i. Check that the controller is operating at the correct system
voltage (12 or 24 vdc), and that the battery has enough volt-
age (over 8 volts) to operate the controller. If there is any
question, reset the controller by removing the BATTERY +
wire from the terminal and reconnecting it to the controller.
j. If the battery, PV array and wire connections seem to be sat-
isfactory, and if the ProStar LED indications are not normal
(refer to section 3.1 “LED Indicators”), then the ProStar may
be defective.
14
6.0 TECHNICAL SPECIFICATIONS
MODEL RATINGS
ProStar-12 ProStar-20 ProStar-30
PV current (amps) 12 20 30 • All models both 12V
and 24V (automatic
Load current (amps) 8 16 30 selection)
Note: Current ratings can be exceeded by 25% for up to 5 minutes.
RELIABILITY MECHANICAL
5-year failure rates at a 90% confidence level • Dimensions: (inches) ........... 6.01 (W) x 4.14 (H) x 2.17 (D)
• ProStar-12 .................................... < 0.1% (mm) ............... 153 (W) x 105 (H) x 55 (D)
• ProStar-20 .................................... < 0.1% • Weight: (oz) ................. 12
• ProStar-30 .................................... 0.4% (kg) ................. 0.34
• Wire terminals ..................... Euro-style
Max wire size:
ENVIRONMENTAL (solid) .............. #6 AWG/16 mm2
• Operating temperature ................ -40 to +85°C (multistrand) ... #6 AWG/10 mm2
• Max ambient temperature ........... +60°C (fine strand) .... #8 AWG/10 mm2
• Storage temperature .................... -55 to +100°C Terminal diameter ........... 0.2 inch/5 mm
• Humidity ....................................... 100% (NC) • Mounting orientation ......... vertical
• Case:
Material ........................ VALOX #310 SEO
PERFORMANCE / ELECTRICAL Fungicidal resistance ....... ASTM G21-70
Moisture absorption ........ < 0.4%
• Accuracy 12V ........................... +/- 22 mV UL Thermal Index ............ 120°C/140°C
24V ........................... +/- 38 mV
• Maximum array voltage ................ 50 V
• Min voltage to operate ................ 8.0 V ELECTRONIC FUSE / SYSTEM SAFETY
• Ground ................................. negative
• Parallel capability ......................... yes • Load short-circuit ................ Short-circuit is > 10X load
• Self-consumption (tare): rating for > 5 msec
Night ................................. 11 mA ........................ Load disconnected < 50
Charging ................................. 12 mA microsec
Load disconnected ................... 10 mA • Emergency disconnect ....... If voltage < 2.4 V, PV/load
• Voltage drops: disconnected < 0.1 sec
Maximum: PV/Batt ..................... 0.7 V • Reverse polarity .................. All 4 system inputs fully
Batt/Load ................. 0.4 V protected
Typical: PV/Batt ..................... 0.5 V • High temp shutdown .......... 70°C disconnect PV input
Batt/Load ................. 0.1 V 80°C disconnect load
• Operating life ............................... 15 years 60°C reconnect load
• Noise: 50°C reconnect PV
µP protection ........................... all inputs
Output noise pulses ................. < 400 mV CONTROL SETPOINTS
Noise pulse width .................... < 500 nanosec
Radiated noise ......................... < 100 picowatts/Khz 12 Volt
• FET’s: Sealed Flooded
Rds (on resistance) ................... 0.018 ohm • Low volt load disconnect 11.4 11.5
Pulse rating .............................. 120 A • LVD reconnect 12.5 12.6
Junction temp rating ................ 175°C • Constant-voltage regulation 14.1 14.3
Operating junction temp ......... 110°C • Equalization 14.35 14.6
• µP memory ................................. 2k ROM • HVD 15.5 15.5
• µP clock speed ............................. 2 Mhz
• Transient surge suppressors: (24V setpoints are twice 12V values)
Pulse power rating ................... 1500 watts
Response ................................. < 5 nanosec CONTROL PARAMETERS
• LED’s:
Pulse rate ................................. 300 Hz • Charge algorithm ............... constant-voltage
Current consumption ............... < 1 mA/LED PWM pulse charging
series configuration
• Temp comp coefficient ...... - 5.0 mV/°C/cell (25°C ref)
METER DISPLAY • LVD current coefficient ....... - 20 mV/amp load
• Type ............................................. LCD • Auto equalize:
• Display .......................................... 3-digit x .5 inch Sealed ........................ 16 days or 11.9/23.8 V
• Temp rating .................................. -30 to +85°C Flooded ........................ 11 days or 12.0/24.0 V
• Voltage accuracy .......................... 0.5% • Temp comp setpoints ........ Regulation, Equalize, HVD
• Current accuracy .......................... 2.5% • Software delays .................. LVD = 55 sec; HVD = 7 sec
• Status LED’s ................................. 3 • Software filtering ................ average 2 inputs/50 µsec
• Self-consumption (tare) ................ 8.5 mA • Measurement rate .............. 37.5 samples/sec
• Manual disconnect ....................... < 100 microsec
Specifications subject to change without notice.
15
P.O. BOX 958
OLNEY, MARYLAND 20830 USA