AMF9
AMF9
AMF9
AMF9
Key features
Outstanding EFI engine support with diagnostic
messages in plain text via J1939
Running hours event and performance log
Plug-in extension modules capability
Supports prime power (MRS) applications
Automatic and manual GCB and MCB control
D+ preexcitation terminal
True RMS measurement
3 phase power measurement of gen-set and mains
| InteliLite NT Datasheet | Related HW ver: 1.6 | Related SW ver: 2.2 | Date of issue: 2019-02-04
Technical data
Power supply Max. measured
9A
current
Power supply
8-36 V DC Max. allowed
range 10 A continuous, 50 A/1 s
current
Power supply
100 ms (from min. 10 V) Current accuracy 2 % from nominal current
drop-out immunity
Power approx. 100 mA / 8 V; 40 mA / 36 Binary inputs
consumption V
Number 4 non-isolated
Peak power
approx. 0,33 A / 8 V; 0,18 A / 36 V Input resistance 4.2 kΩ
consumption (LT)
Common pole Positive, V = 8-36 V DC
Backup battery s
CR 1225
type Close/Open 0-0.8 V close contact
Frequency Frequency
0.05 Hz 0.2 %
accuracy measurement
tolerance
Current measurement
D+
Measurement
3 ph generator current 250 mA, during the engine start
inputs Excitation current
only
Measurement type True RMS
Charging fail
Current range 5A 80 % of Usupply
threshold
InteliLite NT Datasheet 2
Display
Type Build-in monochromatic
Resolution 128 × 64 px
InteliLite NT Datasheet 3
Dimensions, terminals and mounting
Note: The controller is to be mounted onto the switchboard door. The requested cut-out size is 175x115 mm.
Use the screw holders delivered with the controller to fix the controller into the door.
InteliLite NT Datasheet 4
Available extension modules
Product Description Order code
Related products
Product Description Order code
EN 61000-6-3:2006
EN 61000-6-3:2006
EN 61000-6-1:2005
EN 61000-6-2:1999
Manufacturer:
ComAp a.s.
Czech Republic E-mail: [email protected]
Phone: +420 246 012 111 Web: www.comap-control.com
© ComAp. Features and specification are subject to change without prior notice.