Manual ABB
Manual ABB
Hardware Manual
ACS800-37 Drives (55 to 2700 kW / 75 to 3000 HP)
ACS800-37 Drives
55 to 2700 kW (75 to 3000 HP)
Hardware Manual
3AFE68557925 REV B EN
EFFECTIVE: 01.11.2005
Update Notice
The notice concerns the following ACS800-37 Drives (55 Code: 3AUA0000059451 Rev A
to 2700 kW / 75 to 3000 HP) Hardware Manuals: Valid: from 01.02.2010 until the release of the next revision of
Code Revision Language the manual
3AFE68557925 B English EN Contents:
3AFE68643155 B German DE The headings in this update notice refer to the modified
subsections in the original English manual. Each heading also
3AFE68643163 B Spanish ES includes a page number and a classifier NEW, CHANGED, or
3AFE68576024 B French FR DELETED. The page number refers to the page number in the
original English manual. The classifier describes the type of
3AFE68643171 B Italian IT
the modification.
3AUA0000019310 C Russian RU
ASTO An optional board within drives used to implement the Safe torque off function
(option +Q968).
Update Notice
2
+Q951 Emergency stop, stop category 0 with opening the main contactor/breaker
+Q952 Emergency stop, stop category 1 with opening the main contactor/breaker
+Q963 Emergency stop, stop category 0 without opening the main contactor/breaker
+Q964 Emergency stop, stop category 1 without opening the main contactor/breaker SS1
Update Notice
3
Update Notice
4
WARNING! The Safe torque off function does not disconnect the voltage of the main
and auxiliary circuits from the drive. Therefore maintenance work on electrical parts
of the drive or the motor can only be carried out after isolating the drive system from
the main supply.
Note: The Safe torque off function can be used for stopping the drive in emergency
stop situations. In the normal operating mode, use the Stop command instead. If a
running drive is stopped by using the function, the drive will trip and stop by coasting.
If this is not acceptable, e.g. causes danger, the drive and machinery must be
stopped using the appropriate stopping mode before using this function.
Note concerning permanent magnet motor drives in case of a multiple IGBT
power semiconductor failure: In spite of the activation of the Safe torque off
function, the drive system can produce an alignment torque which maximally rotates
the motor shaft by 180/p degrees. p denotes the pole pair number.
Note: If you add or modify the wiring in the drive safety circuits, ensure that the
appropriate standards (e.g. IEC 61800-5-1, EN 62061, EN/ISO 13849-1 and -2) and
the ABB guidelines are met. After making the changes, verify the operation of the
safety function by testing it.
Check that the Safe torque off function (option Optional function. See delivery
+Q968, if installed) works: specific circuit diagrams.
Update Notice
5
V309 (red) Prevention of unexpected start (option +Q950) or Safe torque off (option +Q968) is
ON.
Update Notice
6
Update Notice
5
Safety instructions
Safety instructions
6
WARNING!
• Only qualified electricians are allowed to install and maintain the drive.
• The main switch on the cabinet door does not remove the voltage from the input
busbars of the drive. Before working on the drive, isolate the whole drive from
the supply.
• Never work on the drive, the motor cable or the motor when main power is
applied. After switching off the input power, always wait for 5 min to let the
intermediate circuit capacitors discharge before you start working on the drive,
the motor or the motor cable. Measure the voltage between terminals UDC+
and UDC- (L+ and L–) with a multimeter (impedance at least 1 Mohm) to
ensure that the drive is discharged before beginning work.
• Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages to exist inside the drive even when the main power of the
drive is switched off.
• Do not make any insulation or voltage withstand tests on the drive or drive
modules.
• When reconnecting the motor cable, always check that the phase order is
correct.
• When joining shipping splits (if any), check the cable connections at the joints
before switching on the supply voltage.
• Live parts on the inside of the doors are protected against direct contact.
Special attention shall be paid when handling metallic shrouds.
Note:
• The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
• The Prevention of Unexpected Start function does not remove the voltage from
the main and auxiliary circuits.
Safety instructions
7
WARNING!
• During the installation procedure, supply, filter or inverter modules may have to
be temporarily extracted from the cabinet. The modules have a high centre of
gravity. In order to minimise the danger of toppling over, keep the support legs
(if provided) of the modules extended whenever manoeuvring the modules
outside the cabinet. An overturning module can cause physical injury.
Do not tilt!
• Electrically conductive dust inside the unit may cause damage or lead to
malfunction. Make sure that dust from drilling does not enter the drive when
installing.
• Cooling fans may continue to rotate for a while after the disconnection of the
electrical supply.
Safety instructions
8
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive. Incorrect grounding can cause physical injury, death or equipment malfunction
and increase electromagnetic interference.
WARNING!
• Ground the drive, the motor and adjoining equipment to ensure personnel
safety in all circumstances, and to reduce electromagnetic emission and pick-
up.
• Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
WARNING!
• Handle the fibre optic cables with care. When unplugging optic cables, always
grab the connector, not the cable itself. Do not touch the ends of the fibres with
bare hands as the fibre is extremely sensitive to dirt. The minimum allowed
bend radius is 25 mm (1 in.).
Safety instructions
9
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive. Ignoring the instructions can cause physical injury or death or damage the
equipment.
WARNING!
• Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
• Do not control the motor with the disconnecting device (means); instead, use
the control panel keys and , or commands via the I/O board of the drive.
The maximum allowed number of charging cycles of the DC capacitors (i.e.
power-ups by applying power) is five in ten minutes.
• Do not use the Prevention of Unexpected Start feature for stopping the drive
when the inverter unit(s) is running. Give a Stop command instead.
Note:
• If an external source for start command is selected and it is ON, the drive (with
Standard Application Program) will start immediately after fault reset unless the
drive is configured for 3-wire (a pulse) start/stop.
• When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key .
Safety instructions
10
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also when the supply power is switched off, a rotating permanent magnet motor
feeds power to the intermediate circuit of the drive and also the supply connections
become live (even when the inverter is stopped!).
Operation
Do not run the motor above the rated speed. Motor overspeed leads to overvoltage
which may result in explosion of the capacitors in the intermediate circuit of the drive.
Application program
Controlling a permanent magnet motor is only allowed using the ACS800 Permanent
Magnet Synchronous Motor Drive Application Program, or using other application
programs in scalar control mode only.
Safety instructions
11
Table of contents
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Usage of warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Permanent magnet motor drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Application program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table of contents
The ACS800-37
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
The ACS800-37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Cabinet line-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Frame R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Frame R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Swing-out frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Cabling direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Single-line circuit diagram of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operation principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Line-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
AC voltage and current waveforms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Motor-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Reduced run capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Control interfaces of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table of contents
12
Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Required tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Moving the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
…by crane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
…by fork-lift or pallet truck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
…on rollers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Laying the unit on its back . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Final placement of the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Fastening the cabinet to the floor (Non-marine units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Clamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Holes inside the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Fastening the unit to the floor and wall (Marine units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Joining the shipping splits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Connecting the DC busbars and the PE busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
DC busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
PE busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Cable conduit in the floor below the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Cooling air intake through bottom of cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Electric welding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Table of contents
13
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Option coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Input power connection – Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Input power connection – Frame R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Input power connection – Frame size R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Input power connection – Frame size 2×R8i and up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Motor connection – Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Table of contents
14
Table of contents
15
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Reduced run capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Checking and replacing the air filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Quick connectors (Frame R8i and up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Cooling fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Supply/Inverter module cooling fan replacement (Frame R6) . . . . . . . . . . . . . . . . . . . . . . . 112
Supply/Inverter module cooling fan replacement (Frame R7i) . . . . . . . . . . . . . . . . . . . . . . . 113
LCL filter module cooling fan replacement (Frame R7i) . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Supply and inverter module cooling fan replacement (Frame R8i and up) . . . . . . . . . . . . . 115
Module fan replacement procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
LCL filter cooling fan replacement (Frame R8i and up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
LCL filter fan replacement procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Cabinet fan replacement (Frame R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Cabinet fan replacement (Frame R8i and up with IP21-42) . . . . . . . . . . . . . . . . . . . . . . . . . 117
Cabinet fan replacement (Frame R8i and up with IP54) . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Heatsinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Capacitor replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Other maintenance actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Power module replacement (Frame R8i and up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Fault Tracing
Faults and warnings displayed by the CDP-312R Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . 121
Warning/Fault message from unit not being monitored by control panel . . . . . . . . . . . . . . . 121
Conflicting ID numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
LEDs of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Table of contents
16
Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
IEC ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
NEMA ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
ACS800-37 frame sizes and power module types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128
AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131
Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Tightening torques for power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
Compliance with the EN 61800-3 (2004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
“C-tick” marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
Compliance with the EN 61800-3 (2004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .142
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .142
Equipment warranty and liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .143
Dimensions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .146
Frame R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150
Frame R8i (without option +E202) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .157
Frame size R8i (with option +E202) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165
Frame size 2×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170
Frame size 3×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183
Frame size 4×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189
Frame size 5×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195
Table of contents
17
Resistor braking
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Resistor braking options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Chopper/Resistor combinations – Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Brake choppers – Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Brake resistors – Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Verifying the capacity of the braking equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Custom resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Calculating the maximum braking power (Pbr) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Example 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
Custom resistor installation and wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Brake circuit commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Table of contents
18
Table of contents
19
Target audience
This manual is intended for people who plan the installation, install, commission, use
and service the drive. Read the manual before working on the drive. The reader is
expected to know the fundamentals of electricity, wiring, electrical components and
electrical schematic symbols.
The manual is written for readers worldwide. Both SI and imperial units are shown.
Special US instructions for installations within the United States that must be
installed per the National Electrical Code and local codes are marked with (US).
Contents
The chapters of this manual are briefly described below.
Safety instructions gives safety instructions for the installation, commissioning,
operation and maintenance of the drive.
About this manual introduces this manual.
The ACS800-37 describes the drive.
Mechanical installation instructs how to move, place and mount the drive.
Planning the electrical installation provides advice on motor and cable selection, the
protective functions of the drive, and cable routing.
Electrical installation describes the cabling and wiring of the drive.
Motor control and I/O board (RMIO) shows external control connections to the motor
control and I/O board and its specifications.
Installation checklist and start-up helps in checking the mechanical and electrical
installation of the drive.
Maintenance contains preventive maintenance instructions.
Fault Tracing contains troubleshooting instructions.
Technical data contains the technical specifications of the drive, e.g. ratings, frame
sizes and technical requirements, provisions for fulfilling the requirements for CE
and other markings and warranty policy.
Dimensions contains information on the dimensions of the drive.
Resistor braking describes how to select, protect and wire optional brake choppers
and resistors.
Task See
Check the insulation of the motor and the motor Electrical installation: Checking the insulation of
cable. the assembly
Task See
Connect the power cables. Connect the control and Mechanical installation, Planning the electrical
the auxiliary control cables. installation, Electrical installation
Inquiries
Address any inquiries about the product to the local ABB representative, quoting the
type code and serial number of the unit. If the local ABB representative cannot be
contacted, address inquiries to ABB Oy, AC Drives, PO Box 184, 00381 Helsinki,
Finland.
AGPS Gate driver power supply board. An optional board within drives, used to
implement the Prevention of Unexpected Start function.
Frame (size) Relates to the construction type of the component in question. For
example, several drive types with different power ratings may have the
same basic construction, and this term is used in reference to all those
drive types.
With the ACS800-37, the frame size of the drive indicates the quantity and
frame size of the inverter modules, e.g. “2×R8i”.
To determine the frame size of a drive type, see the rating tables in the
chapter Technical data.
Line-side converter A converter that is connected to the supply network and is capable of
transferring energy from the network to the DC link of the drive. With
ACS800-37 drives of frame size R7i and above, the line-side converter is
also called the (IGBT) supply unit or the ISU.
Motor-side converter A converter that is connected to the motor and controls the motor
operation. With ACS800-37 drives of frame size R7i and above, the
motor-side converter is also called the inverter unit or INU.
PPCS Power Plate Communication System; a protocol used in the optical fibre
link that controls the output semiconductors of an inverter module.
RDCU Drive control unit. The RDCU is a separate unit consisting of an RMIO
board built in a plastic housing.
RMIO Motor control and I/O board. Contains the principal inputs and outputs of
the drive. The RMIO is contained within the RDCU drive control unit.
The ACS800-37
The ACS800-37
The ACS800-37 is a cabinet-built, low-harmonic drive for controlling AC motors.
Cabinet line-up
The drive consists of one or more cubicles that contain the supply and motor
terminals, 1 to 6 IGBT supply module(s) forming the line-side converter, 1 to 6
inverter modules forming the motor-side converter, and optional equipment. (Frame
R6 drives employ an integrated supply/inverter module.) The actual arrangement of
the cubicles varies from type to type and the selected options. See also the chapter
Dimensions for the different line-up variations.
The ACS800-37
24
Frame R6
The picture below shows the main components of a frame R6 drive with the door
open, and with the swing-out frame closed (left) and open (right).
3 3
No. Description
1 Swing-out frame (see page 27)
12 12 2 Cable entries for power and control cables (bottom
cable entry/exit models)
3 Cable entries for power and control cables (top cable
8 10 8 10 entry/exit models)
4 Switch fuse
4 4
5 Auxiliary voltage transformer
6 Integrated line-side/motor-side converter module
7 Input terminals (bottom cable entry/exit models)
8 Input terminals (top cable entry/exit models)
9 Output terminals (bottom cable entry/exit models)
10 Output terminals (top cable entry/exit models)
6 11 Control unit (RDCU) for motor-side converter
12 Cabinet cooling fan
11
1
7 9
5 5
2 2
The ACS800-37
25
Frame R7i
The picture below shows the main components of a frame R7i drive with the door
and the swing-out frame open.
No. Description
1 Swing-out frame (see page 27) (not shown). The drive
control units for both converter modules are installed on
the swing-out frame.
2 Cable entries for power and control cables (bottom
cable entry/exit models)
11 8 6 1 3 Cable entries for power and control cables (top cable
entry/exit models)
4 Switch fuse
5 Auxiliary voltage transformer
10 6 Line-side converter module
7 LCL filter
8 Motor-side converter module
9 Input terminals
10 Output terminals (units without du/dt filtering +E205)
11 Output terminals (units with du/dt filtering +E205)
9 4
5 7
The ACS800-37
26
Frame R8i
The picture below shows the main components of a frame R8i drive with the doors
open.
No. Description
1 Swing-out frame (see picture on page 27)
2 Supply unit controller (RDCU)
4 3 Inverter unit controller (RDCU)
5 4 Switch-disconnector*
8 5 Input contactor*
6 LCL filter
7 IGBT supply module
2
8 Intermediate DC link
3
9 Inverter module
6 7 9 10 Cooling fan for LCL filter
11 Cooling fan for IGBT supply module
12 Cooling fan for inverter module
13 Auxiliary voltage transformer (accessible by opening
14 the swing-out frame)
1 14 Auxiliary voltage circuitry (relays etc.)
13 *In larger drives, an air circuit breaker is used instead of the
switch-disconnector/contactor combination.
10 11 12
The ACS800-37
27
Swing-out frame
The swing-out frame provides space for the control circuitry of the drive as well as
optional electrical equipment. The frame can be opened by removing the two locking
screws (arrowed in the picture below) and moving the swing-out frame aside.
Depending on the frame size of the drive, the actual equipment of the drive may
differ from what is depicted.
The ACS800-37
28
The following is a generic device layout diagram for the swing-out frame (drive frame
size R8i). The diagram is also attached to the inside of the cubicle door, with
installed devices marked. Refer to the circuit diagrams delivered with the drive for
device designations.
The ACS800-37
29
Cabling direction
The drawing below shows the available power cabling directions of the drive.
Frame size R6
6 3 Description
2 5 1 Input/Motor output – Bottom entry
IP21-42 IP54
2 Input/Motor output – Top entry (IP21-42)
3 Input/Motor output – Top entry (IP54)
4 Signal cable input/output – Bottom entry
5 Signal cable input/output – Top entry (IP21-42)
6 Signal cable input/output – Top entry (IP54)
1 4 1 4
Description
2 4 1 Input/Motor output – Bottom entry
2 Input/Motor output – Top entry
3 Signal cable input/output – Bottom entry
4 Signal cable input/output – Top entry
1 3
The ACS800-37
30
Description
2
10 11
4 6 8 A Input/output cubicle
B Supply and inverter unit cubicle
C Common motor terminal cubicle (optional)*
2
10 Description
4 6
A Auxiliary control cubicle
B Incoming cubicle
C Inverter unit cubicle
D Common motor terminal cubicle (optional)
The ACS800-37
Supply unit Inverter unit Brake unit
DC bus
terminal cubicle.
M M
M M M M
Single-line circuit diagram of the drive
230/400 VAC
230/115
VAC
M
Main
Supply M
3~
Charging
circuit
400 VAC
230/115 VAC
Note: This diagram represents a frame 2×R8i drive without a common motor
The ACS800-37
31
32
Operation principle
The line-side and motor-side converters have their own RDCU control units and
control programs. The parameters of each program can be viewed and changed
using one control panel. The converter to be controlled can be selected using the
control panel; see the section Controls below.
Line-side converter
The line-side converter rectifies three-phase AC current to direct current for the
intermediate DC link of the drive. The intermediate DC link is further supplying the
motor-side converter that runs the motor.
The line-side converter is an active unit that, together with an LCL (inductor-
capacitor-inductor) filter, enables low harmonic distortion at the input terminals of the
drive.
By default, the line-side converter controls the DC link voltage to the peak value of
the line-to-line voltage. The DC voltage reference can be set also higher by a
parameter. The control of the IGBT power semiconductors is based on the Direct
Torque Control (DTC) method also used in the motor control of the drive. Two line
currents and the DC link voltage are measured and used for the control.
AC input Intermediate
DC link
The ACS800-37
33
I,U
uU
iU
t [ms]
An example spectrum and THD value of the current at the input of the drive are
shown below. Each harmonic is presented in percent of nominal current. n denotes
the ordinal number of the harmonic.
I [%] 10
0
THD 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 n
The ACS800-37
34
Motor-side converter
The motor control is based on the Direct Torque Control (DTC) method. Two phase
currents and DC link voltage are measured and used for the control. The third phase
control is measured for earth fault (ground fault) protection.
The motor-side converter is controlled by an RDCU drive control unit located in the
swing-out frame of the cabinet. The RDCU is connected to the inverter module(s) by
a fibre optic link, distributed through an optical branching unit. In the inverter
modules, the optic link connects to the AINT board, the terminals of which are
accessible through a hole on the front panel of the module.
The ACS800-37
Parameter setting and diagnostics through
CDP 312R Control Panel (and related
accessories).
Controls
RDNA, RPBA)
E
Y
or pulse encoder interface
(RTAC)
S TO P
Input power
= ~ To motor
~ =
Supply unit Inverter unit
The following diagram shows the control interfaces and I/O options of the drive.
The ACS800-37
35
36
Door switches
Main switch-disconnector (Q1 in frame size R6 to R8i)
The switch-disconnector handle switches the main and auxiliary voltages to the drive
on and off.
Air circuit breaker (Q1 in frame size 2×R8i and up)
The air circuit breaker controls the main supply voltage (phases L1, L2 and L3). For
more information on using the breaker, refer to its manual.
WARNING! Opening the air circuit breaker will not switch off the auxiliary voltages of
the drive.
CY
STO P
Reset button RESET
Resets an emergency stop, after
which the supply unit can be started
using the start switch.
(Drive faults are reset via the drive
control panel or serial
communication)
The ACS800-37
37
Control panel
A control panel (type CDP-312R) is installed on the door of the drive. The CDP-312R
is the user interface of the supply unit (line-side converter) and the inverter unit
(motor-side converter) of the drive, providing the essential controls such as Start/
Stop/Direction/Reset/Reference, and the parameter settings for the units’ application
programs. More information on using the panel can be found in the Firmware Manual
delivered with the drive.
The control panel is wired to both the supply unit and the inverter unit using a
Y-splitter. The unit that is currently being controlled is indicated by the drive name on
the drive display; the suffix “MR” denotes inverter unit, “LR” denotes supply unit. The
control is switched between the units as follows:
To control the supply unit…
Step Action Press… Display (example)
IXXR7xxx
ID-NUMBER 2
3. To verify the change to the line-side converter and display 2 -> 380.0 V
the warning or fault text ACT ACS 800 0490_3LR
** FAULT **
DC OVERVOLT (3210)
WARNING! The drive does not stop by pressing the control panel Stop key in local
control mode.
ACXR7xxx
ID-NUMBER 1
The ACS800-37
38
AI3
FIELD BUS
The ACS800-37
39
Type code
The type code of the drive is indicated on the type designation label, attached on the
cabinet door. The type code contains information on the specifications and
configuration of the drive. The first digits from left express the basic configuration
(e.g. ACS800-37-0490-3). The optional selections are given thereafter, separated by
+ signs (e.g. +E202). The main selections are described below.
Note: The information below is for quick reference only and does not contain all
conditions and details. For more information, refer to ACS800 Ordering Information
(code: 64556568), available through ABB representatives.
Selection Alternatives
Product series ACS800 product series
Type 37 = cabinet-mounted
Default configuration: IP21 (UL Type 1); main switch/disconnector with aR-
type AC fuses; 50 Hz supply; 230 V AC auxiliary voltage; RDCO-03 DDCS
Communication Option; CDP-312R Control Panel; EMC/RFI filtering for 2nd
Environment (+E200) (except frame R6); common mode filtering; Standard
Application Program; bottom entry/exit of cables; coated circuit boards; set of
English manuals.
Size Refer to Technical data: IEC ratings.
Voltage range 3 = 380/400/415 V AC
(nominal rating in bold) 5 = 380/400/415/440/460/480/500 V AC
7 = 525/575/600/690 V AC
+ options
Supply frequency A013 = 60 Hz
I/O options Refer to ACS800 Ordering Information (code: 64556568 [English]).
Fieldbus adapter
Application program
Degree of protection B053 = IP22 (UL Type 1)
B054 = IP42 (UL Type 1)
B055 = IP54 (UL Type 12) – Not available with +C134
B059 = IP54R with connection to air outlet duct
Construction C121 = Marine construction (reinforced mechanical parts and fastening,
marking of conductors [A1], door handles, self-extinctive materials)
C129 = UL Listed – Includes +H358
C134 = CSA Approved – Includes +H358
Resistor braking D150 = Brake chopper(s).
D151 = Brake resistors. Not available in IP54 or IP54R. Not available with
+C129 or +C134.
Filters E200 = EMC/RFI filtering for 2nd Environment (frame R6 only; standard with
frame R7i and R8i)
E202 = EMC/RFI filtering for 1st Environment TN (grounded) system,
restricted (A-limits). Only available for certain types. Not available for 690 V.
E205 = du/dt filtering
E206 = Sine filter – Not available with +C121 or +C129.
The ACS800-37
40
Selection Alternatives
Cabling H351 = Top entry
H353 = Top exit
H358 = US/UK gland/conduit plate
H359 = Common motor terminal cubicle – Frame R8i with +E202 only
Auxiliary voltage G304 = 115 V AC – Standard with +C129 and +C134
Cabinet options G300 = Cabinet heaters (external supply) – Not available with +C129 or
+C134
G307 = Input terminals for external UPS-backed auxiliary voltage
G313 = Output for motor heater (external supply)
G330 = Halogen-free wiring and materials – Not available with +C129 or
+C134
Language of manuals Rxxx
Refer to ACS800 Ordering Information (code: 64556568 [English]).
Starter of auxiliary M600 = 1 … 1.6 A (1 pc)
motor fan M601 = 1.6 … 2.5 A (1 pc)
M602 = 2.5 … 4 A (1 pc)
M603 = 4 … 6.3 A (1 pc)
M604 = 6.3 … 10 A (1 pc) – Not for frame R6
M605 = 10 … 16 A (1 pc) – Not for frame R6
Safety features Q950 = Prevention of unexpected start (Category 3)
Q951 = Emergency Stop, Category 0
Q952 = Emergency Stop, Category 1
Q954 = Earth fault monitoring for IT (ungrounded) system
Special P902 = Customised (specified in Technical appendix on ordering)
P904 = Extended warranty
P913 = Special colour (specified in Technical appendix on ordering)
Selection Alternatives
Product series ACS800 product series
Type 37 = cabinet-mounted
Default configuration: IP21 (UL Type 1); main switch/disconnector with aR-
type AC fuses, or air circuit breaker; 50 Hz supply; 230 V AC auxiliary
voltage; RDCO-03 DDCS Communication Option; CDP-312R Control Panel;
EMC/RFI filtering for 2nd Environment (+E200); du/dt filtering; common
mode filtering; Standard Application Program; bottom entry/exit of cables;
coated circuit boards; set of English manuals.
Size Refer to Technical data: IEC ratings.
Voltage range 3 = 380/400/415 V AC
(nominal rating in bold) 5 = 380/400/415/440/460/480/500 V AC
7 = 525/575/600/690 V AC
+ options
Supply frequency A013 = 60 Hz
I/O options Refer to ACS800 Ordering Information (code: 64556568 [English]).
Fieldbus adapter
Application program
Degree of protection B053 = IP22 (UL Type 1)
B054 = IP42 (UL Type 1)
B055 = IP54 (UL Type 12) – Not available with +C134
B059 = IP54R with connection to air outlet duct
The ACS800-37
41
Selection Alternatives
Construction C121 = Marine construction (reinforced mechanical parts and fastening,
marking of conductors [A1], door handles, self-extinctive materials)
C129 = UL Listed – Includes +H358
C134 = CSA Approved – Includes +H358
Resistor braking D150 = Brake chopper(s).
D151 = Brake resistors. Not available in IP54 or IP54R. Not available with
+C129 or +C134.
Filters E202 = EMC/RFI filtering for 1st Environment TN (grounded) system,
restricted (A-limits). Only available for certain types. Not available for 690 V.
Note: EMC/RFI filtering for 2nd Environment (+E200) is standard equipment.
E206 = Sine filter – Not available with +C121 or +C129.
Line options F259 = Earthing switch – Not available with +C129
Cabling H351 = Top entry
H353 = Top exit
H358 = US/UK gland/conduit plate
H359 = Common motor terminal cubicle
Auxiliary voltage G304 = 115 V AC
Cabinet options G300 = Cabinet heaters (external supply) – Not available with +C129 or
+C134
G307 = Input terminals for external UPS-backed auxiliary voltage
G313 = Output for motor heater (external supply)
G317 = Busbar supply conductors
G330 = Halogen-free wiring and materials – Not available with +C129 or
+C134
Language of manuals Rxxx
Refer to ACS800 Ordering Information (code: 64556568 [English]).
Starter of auxiliary M602 = 2.5 … 4 A (1, 2 or 4 pcs)
motor fan M603 = 4 … 6.3 A (1, 2 or 4 pcs)
M604 = 6.3 … 10 A (1, 2 or 4 pcs)
M605 = 10 … 16 A (1 or 2 pcs)
M606 = 16 … 25 A (1 pc)
Safety features Q950 = Prevention of unexpected start (Category 3)
Q951 = Emergency Stop, Category 0
Q952 = Emergency Stop, Category 1
Q954 = Earth fault monitoring for IT (ungrounded) system
Q959 = Red-coloured trip pushbutton for external breaker
Special P902 = Customised (specified in Technical appendix on ordering)
P904 = Extended warranty
P913 = Special colour (specified in Technical appendix on ordering)
The ACS800-37
42
The ACS800-37
43
Mechanical installation
General
See chapter Technical data for allowable operating conditions and requirements for
free space around the unit.
The unit should be installed in an upright vertical position.
The floor that the unit is installed on should be of non-flammable material, as
smooth as possible, and strong enough to support the weight of the unit. The floor
flatness must be checked with a spirit level before the installation of the cabinets into
their final position. The maximum allowed deviation from the surface level is 5 mm in
every 3 metres. The installation site should be levelled, if necessary, as the cabinet
is not equipped with adjustable feet.
The wall behind the unit should be of non-flammable material.
Provide the drive with the amount of fresh cooling air given in Technical data.
Note: Very wide cabinet line-ups (> 4200 mm) are delivered as shipping splits.
Required tools
The tools required for moving the unit to its final position, fastening it to the floor and
tightening the connections are listed below.
• crane, fork-lift or pallet truck (check load capacity!); iron bar, jack and rollers
• Pozidrive and Torx (2.5–6 mm) screwdrivers for the tightening of the frame
screws
• torque wrench
• set of wrenches or sockets for joining shipping splits.
Mechanical installation
44
…by crane
Use the steel lifting lugs attached to the top of
the cabinet. Insert the lifting ropes or slings into
the holes of the lifting lugs.
The lifting lugs can be removed (not mandatory)
once the cabinet is in its final position. If the
lifting lugs are removed, the bolts must be
refastened to retain the degree of protection
of the cabinet.
IP54 units
Allowed minimum height of lifting ropes or slings
for IP54 units is 2 metres.
Mechanical installation
45
…on rollers
(Not allowed with Marine versions)
Cabinet back panel Support If the cabinet needs to be laid on its back, it
must be supported from below beside the
cubicle seams as shown.
Mechanical installation
46
Mechanical installation
47
Before installation
Delivery check
The drive delivery contains:
• drive cabinet line-up
• optional modules (if ordered) installed into the control rack at the factory
• ramp for extracting supply and inverter modules from the cabinet
• hardware manual
• appropriate firmware manuals and guides
• optional module manuals
• delivery documents.
Check that there are no signs of damage. Before attempting installation and
operation, check the information on the type designation label of the drive to verify
that the unit is of the correct type. The label includes an IEC and NEMA rating, C-UL
US, and CSA markings, a type code and a serial number, which allow individual
recognition of each unit. The first digit of the serial number refers to the
manufacturing plant. The next four digits refer to the unit’s manufacturing year and
week respectively. The remaining digits complete the serial number so that there are
no two units with the same serial number.
The type designation label is located on the supply unit door.
Each power module (i.e. supply and inverter module) is also individually labelled.
Mechanical installation
48
Installation procedure
1 See detailed instructions in the following few
pages.
(1) The cabinet can be installed with its back
against a wall, or back-to-back with another unit.
Fasten the unit (or first shipping split) to the floor
A with fastening clamps or through the holes inside
A
the cabinet. See section Fastening the cabinet to
the floor (Non-marine units).
With marine versions, fasten the unit (or first
shipping split) to the floor and wall/roof as
described in section Fastening the unit to the floor
and wall (Marine units).
Note: A clearance of 600 mm minimum above the
basic roof level of the cabinet (see inset on left) is
Top clearances required for cooling.
> 320 mm (12.3”)
for fan replace- Note: Leave some space at the left-hand and
ment
right-hand sides of the line-up (A) to allow the
> 400 mm > 400 mm
(15.75”) (15.75”) doors to open sufficiently.
IP22/42 IP54
Note: Any height adjustment must be done before
fastening the units or shipping splits together.
Height adjustment can be done by using metal
shims between the bottom frame and floor.
2
(2) Remove the lifting bars (if present). In marine
units, also replace the lifting lugs with L-profiles
(see below). Use the original bolts to block any
unused holes.
(3) If the line-up consists of shipping splits, fasten
the first split to the second. Each shipping split
includes a joining cubicle where the busbars
connect to the next split.
(4) Fasten the second shipping split to the floor.
(5) Join the DC busbars and the PE busbars.
(6) Repeat steps (2) to (5) for the remaining
3 shipping splits.
Mechanical installation
49
Clamping
Insert the clamps into the twin slots along the front and rear edges of the cabinet
frame body and fasten them to the floor with a bolt. The recommended maximum
distance between the clamps is 800 mm (31.5”).
If there is not enough working space behind the cabinet for mounting, replace the
lifting lugs at the top with L-brackets (not included) and fasten the top of the cabinet
to the wall.
L-bracket
M16 screw
Cabinet top
Mechanical installation
50
L-bracket
M16 screw
25 mm (0.985”)
Cabinet top
Mechanical installation
51
2 3
Rubber damper
L-bracket
Mechanical installation
52
Procedure
7 7
• Fasten the front post of the joining section with 7 screws to the front frame post of
the next cubicle.
Mechanical installation
53
• Remove any intermediate or partitioning plates covering the rear posts of the
joining cubicle.
Partitioning
plate
• Fasten the rear post of the joining section with seven screws (below the busbar
joining part) to the rear post of the next cubicle.
• Replace all partitioning plates in the upper part of it after connecting the DC
busbars (see section Connecting the DC busbars and the PE busbar).
Mechanical installation
54
DC busbars
The DC busbar connection is shown below.
1 1 Joint pieces
1
1
PE busbar
The PE busbar runs continuously through the line-up near the floor at the back. The
connection is shown below. No separate nuts are needed.
Mechanical installation
55
Miscellaneous
With heavy
cabinets support
the structural C-
sections from
below.
This area can be used for a
cable conduit
Mechanical installation
56
Input fuse cubicle Diode supply cubicle Inverter cubicle Common motor
Cubicle width: 400 mm Cubicle width: 700 mm Cubicle width: 600 mm terminal cubicle
Air inlet size: Air inlet size: Air inlet size: (No air inlet required)
350 × 400 mm 650 × 505 mm 550 × 400 mm
Notes:
• The plinth of the cabinet must be supported all round.
• The air duct must be able to supply a sufficient volume of cooling air. The
minimum air flow values are given in the Technical data section of the Hardware
Manual.
• The cubicles of diode supply units require a larger air inlet area than other
cubicles.
• Some cubicles (mainly those without active, heat-generating components) require
no air inlet.
Mechanical installation
57
Electric welding
It is not recommended to fasten the cabinet by welding.
Cabinets without flat bars at the base
• Connect the return conductor of the welding equipment to the cabinet frame at
the bottom within 0.5 metres of the welding point.
Cabinets with flat bars at the base
• Weld only the flat bar under the cabinet, never the cabinet frame itself.
• Clamp the welding electrode onto the flat bar about to be welded or onto the floor
within 0.5 metres of the welding point.
WARNING! If the welding return wire is connected improperly, the welding circuit
may damage electronic circuits in the cabinet. The thickness of the zinc coating of
the cabinet frame is 100 to 200 micrometres; on the flat bars the coating is
approximately 20 micrometres. Ensure that the welding fumes are not inhaled.
Mechanical installation
58
Mechanical installation
59
Note: The installation must always be designed and made according to applicable
local laws and regulations. ABB does not assume any liability whatsoever for any
installation which breaches the local laws and/or other regulations. Furthermore, if
the recommendations given by ABB are not followed, the drive may experience
problems that the warranty does not cover.
3. Check that the motor voltage rating meets the application requirements:
If the drive is equipped with … … and … … then the motor voltage
rating should be …
The stress on motor insulation can be avoided by using optional ABB du/dt filters.
du/dt filters also reduce bearing currents.
To avoid damage to motor bearings, the cables must be selected and installed
according to the instructions given in this manual. In addition, insulated N-end (non-
driven end) bearings and output filters from ABB must be used according to the
following table. Two types of filters are used individually or in combinations:
• du/dt filtering (protects motor insulation system and reduces bearing currents).
• common mode filtering (CMF) (mainly reduces bearing currents).
Requirements table
The following table shows how to select the motor insulation system and when an
optional ABB du/dt filter, insulated N-end (non-driven end) motor bearings and ABB
common mode filters are required. The motor manufacturer should be consulted
regarding the construction of the motor insulation and additional requirements for
explosion-safe (EX) motors. Failure of the motor to fulfil the following requirements
or improper installation may shorten motor life or damage the motor bearings.
Motor type Nominal mains Requirement for
voltage (AC line Motor insulation ABB du/dt filter, insulated N-end bearing and ABB common mode
voltage)
Manufacturer
system filter
PN < 100 kW 100 kW < PN < 350 kW PN > 350 kW
and or or
frame size < IEC 315 frame size > IEC 315 frame size > IEC 400
PN < 134 HP 134 HP < PN < 469 HP PN > 469 HP
and frame size or frame size or frame size
< NEMA 500 > NEMA 500 > NEMA 580
A Random- UN < 500 V Standard - +N + N + CMF
B wound M2_
500 V < UN < 600 V Standard + du/dt + du/dt + N + du/dt + N + CMF
and M3_
B or
Reinforced - +N + N + CMF
600 V < UN < 690 V Reinforced + du/dt + du/dt + N + du/dt + N + CMF
Form-wound 380 V < UN < 690 V Standard n.a. + N + CMF PN < 500 kW:
HX_ and AM_ + N + CMF
PN > 500 kW:
+ N + CMF + du/dt
Old* form- 380 V < UN < 690 V Check with the + du/dt with voltages over 500 V + N + CMF
wound HX_ motor
and modular manufacturer.
Random- 0 V < UN < 500 V Enamelled wire + N + CMF
wound HX_ with fibre glass
500 V < UN < 690 V + du/dt + N + CMF
and AM_ ** taping
system filter
PN < 100 kW 100 kW < PN < 350 kW PN > 350 kW
and or or
frame size < IEC 315 frame size > IEC 315 frame size > IEC 400
PN < 134 HP 134 HP < PN < 469 HP PN > 469 HP
and frame size or frame size or frame size
< NEMA 500 > NEMA 500 > NEMA 580
N Random- UN < 420 V Standard: ÛLL = - + N or CMF + N + CMF
O wound and 1300 V
form-wound
N 420 V < UN < 500 V Standard: ÛLL = + du/dt + du/dt + N + du/dt + N + CMF
- 1300 V or
A
+ du/dt + CMF
B
or
B
Reinforced: ÛLL = - + N or CMF + N + CMF
1600 V, 0.2 µs
rise time
500 V < UN < 600 V Reinforced: Û LL = + du/dt + du/dt + N + du/dt + N + CMF
1600 V
or
+ du/dt + CMF
or
Reinforced: ÛLL = - + N or CMF + N + CMF
1800 V
600 V < UN < 690 V Reinforced: ÛLL = + du/dt + du/dt + N + du/dt + N + CMF
1800 V
Reinforced: ÛLL = - N + CMF N + CMF
2000 V, 0.3 µs
rise time ***
Abbreviation Definition
UN nominal voltage of the supply network
ÛLL peak line-to-line voltage at motor terminals which the motor insulation must withstand
PN motor nominal power
du/dt du/dt filtering at the output of the drive (+E205)
CMF common mode filtering (+E208)
N N-end bearing: insulated motor non-driven end bearing
n.a. Motors of this power range are not available as standard units. Consult the motor manufacturer.
given below. For other motor types, see the Requirements table above. Apply the requirements of
range “100 kW < P N < 350 kW” to motors with PN < 100 kW. Apply the requirements of range PN >
350 kW to motors within the range “100 kW < PN < 350 kW”. In other cases, consult the motor
manufacturer.
Manufacturer
3.0 5.5
Û LL/UN 5.0
2.5 du/dt
------------- (1/µs)
4.5 UN
2.0 4.0
3.5
1.5
3.0
ÛLL/UN
1.0 2.5
du/dt
------------- (1/µs)
UN 2.0
0.5
1.5
0.0 1.0
100 200 300 100 200 300
The drive protects the motor cable and the motor in a short-circuit situation when the
motor cable is dimensioned according to the nominal current of the drive.
WARNING! The prevention of unexpected start function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive can only be carried out after isolating the drive system
from the main supply.
Note: The prevention of unexpected start function is not intended for stopping the
drive. If a running drive is stopped by using the prevention of unexpected start
function, the drive will cut off the motor supply voltage and the motor will coast to
stop.
General rules
Dimension the supply (input power) and motor cables according to local
regulations:
• The cable must be able to carry the drive load current. See chapter Technical
data for the rated currents.
• The cable must be rated for at least 70 °C maximum permissible temperature of
conductor in continuous use. For US, see Additional US requirements.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when an ground fault
occurs).
• 600 VAC cable is accepted for up to 500 VAC. For 690 VAC rated equipment, the
rated voltage between the conductors of the cable should be minimum 1 kV.
For drive frame size R5 and larger, or motors larger than 30 kW, symmetrical
shielded motor cable must be used (figure below). A four-conductor system can be
used up to frame size R4 with up to 30 kW motors, but shielded symmetrical motor
cable is recommended.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. To operate as a protective conductor, the shield conductivity must
be as follows when the protective conductor is made of the same metal as the phase
conductors:
Cross-sectional area of the phase Minimum cross-sectional area of the
conductors corresponding protective conductor
S (mm2) Sp (mm 2)
S < 16 S
16 < S < 35 16
35 < S S/2
Note: The cabinet configuration of the drive may require multiple supply and/or
motor cabling. Refer to the connection diagrams in Electrical installation.
The motor cable and its PE pigtail (twisted screen) should be kept as short as
possible in order to reduce electromagnetic emission as well as capacitive current.
Recommended
Symmetrical shielded cable: three phase conductors A separate PE conductor is required if the conductivity
and a concentric or otherwise symmetrically of the cable shield is < 50 % of the conductivity of the
constructed PE conductor, and a shield phase conductor.
PE conductor Shield
and shield Shield
PE
PE
PE Shield
A four-conductor system:
three phase conductors
and a protective
conductor.
Not allowed for motor cables Not allowed for motor cables with phase
conductor cross section larger than 10 mm2
(motors > 30 kW).
Cable core
Additional US requirements
Type MC continuous corrugated aluminum armor cable with symmetrical grounds or
shielded power cable must be used for the motor cables if metallic conduit is not
used. For the North American market, 600 VAC cable is accepted for up to 500 VAC.
1000 VAC cable is required above 500 VAC (below 600 VAC). For drives rated over
100 amperes, the power cables must be rated for 75 °C (167 °F).
Conduit
Where conduits must be coupled together, bridge the joint with a ground conductor
bonded to the conduit on each side of the joint. Bond the conduits also to the drive
enclosure. Use separate conduits for input power, motor, brake resistors, and control
wiring. When conduit is employed, type MC continuous corrugated aluminum armor
cable or shielded cable is not required. A dedicated ground cable is always required.
Note: Do not run motor wiring from more than one drive in the same conduit.
If there are power factor compensation capacitors in parallel with the 3-phase input
of the drive:
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2. If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line, ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
should typically be equipped with a blocking reactor or harmonic filter.
WARNING! Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to the output can result in permanent
damage to the unit.
Relay outputs
Varistor
RO (NC)
RO (C)
230 VAC
RO (NO)
RC filter
RO (NC)
230 VAC RO (C)
RO (NO)
Diode
RO (NC)
24 VDC RO (C)
RO (NO)
a b
Double-shielded twisted Single-shielded twisted
pair cable multipair cable
Relay cable
The cable type with braided metallic screen (e.g. ÖLFLEX LAPPKABEL, Germany)
has been tested and approved by ABB.
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, the connection of a thermistor (and other similar
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see the
Firmware Manual.
Motor cable
Drive
min 300 mm (12 in.)
Power cable
Control cables
Electrical installation
WARNING! Only qualified electricians are allowed to carry out the work described in
this chapter. Follow the Safety instructions on the first pages of this manual. Ignoring
the safety instructions can cause injury or death.
Option coding
Some instructions contained within this chapter are intended for drives equipped
with certain options, marked with “plus codes” (e.g. +H359). The options included in
a drive are listed on its type code label. An option code listing is included in this
manual on page 39.
Electrical installation
76
Before installation
WARNING! Check the insulation before connecting the drive to the supply. Make
sure that the drive is disconnected from the supply (input power).
1. Check that all motor cables are disconnected from the drive output terminals.
2. Measure the insulation resistances of the motor cable and the motor between
each phase and the Protective Earth by using a measuring voltage of 1 kV DC.
The insulation resistance must be higher than 1 Mohm.
M
ohm
PE
IT (ungrounded) systems
EMC filter +E202 is not suitable for use in an IT (ungrounded) system. If the drive is
equipped with EMC filter +E202, disconnect the filter before connecting the drive to
the supply network. For detailed instructions on how to do this, please contact your
local ABB representative.
Electrical installation
77
Connection diagram
Q1 K1 U1
L1
L2
L3
PE
Connection procedure
Note: Before making the cable connections, check that the input of the auxiliary
voltage transformer (T10) is selected correctly according to the supply voltage.
1. Open the door of the cabinet.
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
78
Connection diagram
Q1 K1 L1 U1
L1
L2
L3
PE
Connection procedure
Note: Before making the cable connections, check that the input of the auxiliary
voltage transformer (T10) is selected correctly according to the supply voltage.
1. Open the door of the cabinet.
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
79
Connection diagram
Q1 K1 L1 U1
L1
L2
L3
PE
Connection procedure
Note: Before making the cable connections, check that the tap settings of the
auxiliary voltage transformer (T10, located in the input/output cubicle) are correct in
regard to the supply voltage. See instructions on page 94.
1. Open the door of the input/output cubicle (see section Cabling direction starting on
page 29).
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
80
Connection diagram
U<
Q1
L1
L2
L3
PE
Connection procedure
1. Open the door of the incoming cubicle (see section Cabling direction starting on
page 29).
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
81
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
1. Open the cabinet door.
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
82
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
1. Open the cabinet door.
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
83
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
Note: Before making the cable connections, consider checking the tap settings of
the auxiliary voltage transformer located in the input/output cubicle. See instructions
on page 94.
1. Open the door of the input/output cubicle (see section Cabling direction starting on
page 29).
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
84
Motor connection – Frame R8i with option +E202 but without +H359
Output busbars
The motor cables are to be connected to the output busbars behind the inverter
module. For the location and dimensions of the busbars, see the chapter
Dimensions.
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
WARNING! The inverter module is heavy and has a high centre of gravity. Be careful when
manoeuvring the module. In order to minimise the danger of toppling over, keep the support legs
of the module extended whenever manoeuvring it outside the cabinet.
Extract the inverter module from the cubicle as follows (refer to the pictures below):
1. Open the door of the supply and inverter unit cubicle (see section Cabling direction starting on page 29).
2. Remove any shrouds that protect the busbars and cable entries.
3. Open the transparent cover on the front of the inverter module (the rightmost module) and disconnect
the fibre optic cables. Move the cables aside.
4. Remove the L-shaped DC busbars on top of the inverter module.
5. Disconnect the terminal block (X50) next to the DC busbars.
6. Remove the two module fastening screws (6a) at the top. At the base of the module, loosen the two
fastening screws (6b) but leave them in place; lift the bracket (6c) into the up position.
7. Insert the module pull-out ramp under the two screws at the base of the module and tighten.
8. Pull the module carefully out of the cubicle along the ramp. Make sure the wires do not catch.
9. Extend the support legs of the module. Keep the legs extended until the module is about to be inserted
back into the cubicle.
Electrical installation
85
6a
4 8
3
6c
9a 9b
6b
Electrical installation
86
Lead the cables into the cabinet at the inverter module. Make the 360° earthing arrangement at the cable
entry as shown.
Twist the cable screens into bundles and connect to cabinet PE (ground) busbar.
Connect any separate ground conductors/cables to cabinet PE (ground) busbar.
Connect the phase conductors to the output terminals (U2, V2, W2).
Use the tightening torques specified in the chapter Technical data.
Provide support for the cables whenever necessary.
Electrical installation
87
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
1. Open the door of the common motor terminal cubicle (see section Cabling
direction starting on page 29).
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
88
Output busbars
The motor cables are to be connected to the output busbars behind each inverter
module. For the location and dimensions of the busbars, see the chapter
Dimensions.
Connection diagram
PE
U2
V2
W2
U1
V1
M
W1 3~
U2 PE
V2
W2
WARNING! The cabling from all inverter modules to the motor must be physically
identical considering cable type, cross-sectional area, and length.
PE
U2
V2
W2
U1
V1
M
W1 3~
U2 PE
V2
W2
Electrical installation
89
Connection procedure
WARNING! The inverter modules are heavy and have a high centre of gravity. Be careful when
manoeuvring the modules. In order to minimise the danger of toppling over, keep the support legs
of the modules extended whenever manoeuvring the modules outside the cabinet.
Extract each inverter module from the cubicle as follows (refer to the pictures below):
1. Open the door of the inverter unit cubicle (see section Cabling direction starting on page 29).
2. Remove any shrouds that protect the busbars and cable entries.
3. Open the transparent cover on the front of the inverter module (the rightmost module) and disconnect
the fibre optic cables. Move the cables aside.
4. Remove the L-shaped DC busbars on top of the inverter module.
5. Disconnect the terminal block (X50) next to the DC busbars.
6. Remove the two module fastening screws (6a) at the top. At the base of the module, loosen the two
fastening screws (6b) but leave them in place; lift the bracket (6c) into the up position.
7. Insert the module pull-out ramp under the two screws at the base of the module and tighten.
8. Pull the module carefully out of the cubicle along the ramp. Make sure the wires do not catch.
9. Extend the support legs of the module. Keep the legs extended until the module is about to be inserted
back into the cubicle.
6a
4 8
3
6c
9a 9b
6b
Electrical installation
90
Lead the cables into the cabinet at the inverter module. Make the 360° earthing arrangement at the cable
entry as shown.
Twist the cable screens into bundles and connect to cabinet PE (ground) busbar.
Connect any separate ground conductors/cables to cabinet PE (ground) busbar.
Connect the phase conductors to the output terminals (U2, V2, W2).
Use the tightening torques specified in the chapter Technical data.
Provide support for the cables whenever necessary.
Electrical installation
91
Control connections
Connection procedure
Open the cabinet door(s).
Remove the locking screws at the edge of the swing-out frame and open the frame.
Remove any shrouds that limit access to the cable lead-throughs and cable trunking.
Run the cables into the inside of the cabinet through the grommets provided.
Top entry units only: If several cables need to be run through one grommet, use Loctite 5221 (cat. no.
25551) under the grommet to seal the cable entry.
Electrical installation
92
Side view
Strain relief EMI conductive
cushions
If the outer surface of a cable shield is non-conductive, turn the shield inside out as shown below and
apply copper foil to keep the shielding continuous. Do not cut the grounding wire (if present).
Copper foil
Grounding wire
On top entry units, sort the cables so that the thinnest and thickest cables are at opposite ends of the
opening.
Top view
Run the cables to the appropriate terminals. Wherever possible, use the existing cable trunking in the
cabinet. Use sleeving wherever the cables are laid against sharp edges. When running cables to the
swing-out frame, leave some slack in the cable at the hinge to allow the frame to open fully. Tie the cables
to the cable supports wherever necessary.
Cut the cables to suitable length. Strip the cables and conductors.
Twist the cable shields into bundles and connect them to the ground terminal nearest to the terminal block.
Keep the unshielded portion of the cables as short as possible.
Connect the conductors to appropriate terminals (see the chapter Motor control and I/O board (RMIO) and
the circuit diagrams delivered with the unit).
Refit any shrouds removed earlier. Close the swing-out frame, refasten, and close the cabinet door(s).
Electrical installation
93
Module
Keep unshielded portion as
short as possible
Shield
1
2
3
4
To nearest PE terminal
CHASSIS
RTAC-01
PULSE ENCODER INTERFACE
GND
Note 1: If the encoder is of unisolated
12345678 123456
SHLD
F01
type, ground the encoder cable at the
DE
23
SHLD
C
456
AB
789
CHA
CHA+
CHA-
X2
CHB
WD/
drive end only. If the encoder is
Keep unshielded portion as CHB+
CHB-
INIT
galvanically isolated from the motor
NODE ID
CHZ-
shaft and the stator frame, ground the
0V
0V
encoder cable shield at the drive and
the encoder end.
1
2
3
4
VOUT
+15V
X1
VIN
+24V
Note 2: Twist the pair cable wires.
Electrical installation
94
Tap settings of the auxiliary voltage transformer (Frame R8i and up)
3~ Input
Primary
Secondary
Output
Supply Tap settings Supply 230 V 115 V 400 V (50 Hz) 320 V (60 Hz)
Terminals
voltage A1 to... B1 to… C1 to… voltage Terminals Tap setting Terminals Tap setting Terminals Terminals
690 V A1, B1, C1 C2 A2 B2 690 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
660 V A1, B1, C1 C2 A2 B2 660 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
600 V A1, B1, C1 C3 A3 B3 600 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
575 V A1, B1, C1 C3 A3 B3 575 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
525 V A1, B1, C1 C4 A4 B4 525 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
500 V A1, B1, C1 C4 A4 B4 500 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
480 V A1, B1, C1 C5 A5 B5 480 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
460 V A1, B1, C1 C5 A5 B5 460 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
440 V A1, B1, C1 C6 A6 B6 440 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
415 V A1, B1, C1 C6 A6 B6 415 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
400 V A1, B1, C1 C7 A7 B7 400 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
380 V A1, B1, C1 C7 A7 B7 380 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
Electrical installation
95
Analogue outputs
Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution 0.1 % (10 bit)
Inaccuracy ± 1 % (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ± 200 ppm/°C
(± 111 ppm/°F) max.
Digital inputs
With Standard Application Program six programmable digital inputs (common ground:
24 VDC, -15 % to +20 %) and a start interlock input. Group isolated, can be divided in
two isolated groups (see Isolation and grounding diagram below).
Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0”
(high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 VDC): short circuit proof. An external 24 VDC
supply can be used instead of the internal supply.
Isolation test voltage 500 VAC, 1 min
Logical thresholds < 8 VDC “0”, > 12 VDC “1”
Input current DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant 1 ms
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC
Minimum continuous current 5 mA rms at 24 VDC
Maximum continuous current 2 A rms
Isolation test voltage 4 kVAC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements, and that the installation site is below 2000 m (6562 ft) in altitude. For installation at higher altitudes,
see page 73.
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND1
Installation checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person.
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Neglecting the
safety instructions can cause injury or death.
Check…
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. See Electrical installation, Technical data: IEC ratings or Ambient
conditions.
The motor and the driven equipment are ready for start.
The EMC filter (option +E202) is disconnected if the drive is connected to an IT (ungrounded) system.
The supply (input power) voltage matches the nominal input voltage of the drive.
The supply (input power) connection to the input terminals are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Supply (input power) voltage cannot be applied to the output of the drive (with a bypass connection).
Check…
For drives with Category 1 Emergency stop function: The time relay has been set to a suitable value (e.g.
somewhat longer than the stop ramp of the inverter units).
Start-up procedure
Action Additional information
WARNING! Ensure that the disconnector of the supply transformer is
locked to open position, i.e. no voltage is, or cannot be connected to
drive inadvertently. Check also by measuring that there is no voltage
connected.
Basic checks with no voltage connected
If the unit is equipped with an air circuit breaker, check the current trip Optional device. See the delivery-
limits of the breaker (preset at the factory). specific circuit diagrams.
General rule
Ensure the selectivity condition is fulfilled i.e. the breaker trips at a lower
current than the protection device of the supplying network, and that the
limit is high enough not to cause unnecessary trips during the
intermediate DC circuit load peak at start.
Long-term current limit
As a rule of thumb, this should be set to the rated AC current of the
module.
Peak current limit
As a rule of thumb, this should be set to a value 3-4 times the rated AC
current of the module.
Check the settings of the relays and breakers/switches of the auxiliary Optional devices. See delivery
circuits. specific circuit diagrams.
Disconnect any unfinished or unchecked 230/115 VAC cables that lead
from the terminal blocks to the outside of the equipment.
For drive types ACS800-37-0640-3/0780-5/0790-7 and up: Locate the These drive types have two PPCS
APBU-xx PPCS branching units. Enable memory backup battery on branching units, one for the supply
each branching unit by setting actuator 6 of switch S3 to ON. unit, one for the inverter unit. By
default, memory backup is switched
off to save the battery.
Connecting voltage to input terminals and auxiliary circuit
WARNING! When voltage is connected to the input terminals, voltage
may also be connected to the auxiliary circuits of the drive.
Make sure that it is safe to apply voltage. Ensure that:
• nobody is working on the unit or circuits that are wired from outside into
the cabinets
• cabinet doors are closed
• covers of motor terminal boxes are in place.
Open the earthing/grounding switch (Q9) if present. The earthing/grounding switch and
the main disconnecting device are
either mechanically or electrically
interlocked so that the earthing/
grounding switch can only be closed
when the main disconnecting switch
is open, and vice versa.
Close the main breaker of the supply transformer.
Parameters
No. Name/Value Description T./FbEq Def.
16 SYSTEM CTR Parameter lock, parameter back-up etc.
INPUTS
16.15 I/O START MODE Selects I/O control start mode when par. 98.01 COMMAND SEL is set B DI2 EDGE
to I/O.
Note: The recommended setting for drives with optional emergency
stop is DI2 LEVEL.
DI2 EDGE Starts the line converter by digital input DI2 rising edge. The line 0
converter starts to modulate and the charging resistors will be by-
passed when the motor-side converter is started.
DI2 LEVEL Starts the line converter by the level of digital input DI2. The line 1
converter starts to modulate and the charging resistors will be by-
passed when the line converter RMIO board is powered, its digital
input DI2 is ON and there are no faults.
Note: With the ACS800-37, this selection changes the value of par.
98.01 COMMAND SEL from the default setting MCW to I/O on the
next RMIO board power-up.
31 AUTOMATIC Automatic fault reset.
RESET Automatic resets are possible only for certain fault types and when the
automatic reset function is activated for that fault type.
The automatic reset function is not operational if the drive is in local
control (L visible on the first row of the control panel display).
WARNING! If the start command is selected and it is ON, the
line converter may restart immediately after automatic fault
reset. Ensure that the use of this feature will not cause
danger.
WARNING! Do not use these parameters when the drive is
connected to a common DC bus. The charging resistors may
be damaged in an automatic reset.
31.01 NUMBER OF TRIALS Defines the number of automatic fault resets the drive performs within I 0
the time defined by parameter 31.02.
0…5 Number of the automatic resets 0
Term Definition
Actual signal Signal measured or calculated by the drive. Can be monitored by the
user. No user setting possible.
FbEq Fieldbus equivalent: The scaling between the value shown on the control
panel and the integer used in serial communication.
09.12 LCU ACT SIGNAL 1 Line converter signal selected by par. 95.08 LCU PAR1 SEL. 1=1 106
09.13 LCU ACT SIGNAL 2 Line converter signal selected by par. 95.09 LCU PAR2 SEL. 1=1 110
95 HARDWARE SPECIF Line converter references and actual signal selections.
95.06 LCU Q POW REF Reactive power reference for the line converter i.e. the value for 0
par. 24.02 Q POWER REF2 in the IGBT Supply Control Program.
Scaling example 1: 10000 equals to a value of 10000 of parameter
24.02 Q POWER REF2 and 100% of par. 24.01 Q POWER REF
(i.e. 100% of the converter nominal power given in par. 04.06
CONV NOM POWER) when par. 24.03 Q POWER REF2 SEL is
set to PERCENT.
Scaling example 2: Par. 24.03 Q POWER REF2 SEL is set to kVAr.
A value of 1000 of par. 95.06 equals to 1000 kVAr of par. 24.02 Q
POWER REF2. Value of par. 24.01 Q POWER REF is then 100 ·
(1000 kVAr divided by converter nominal power in kVAr)%.
Scaling example 3: Par. 24.03 Q POWER REF2 SEL is set to PHI.
A value of 10000 of par. 95.06 equals to a value of 100 deg of
parameter 24.02 Q POWER REF2 which is limited to 30 deg. The
value of par. 24.01 Q POWER REF will be determined
approximately according to the following equation where P is read
from actual signal 1.09 POWER:
S
P P Q
cos 30 = --- = ------------------------
S 2 2 30 deg
P +Q
P
Positive reference 30 deg denotes capacitive load.
Negative reference 30 deg denotes inductive load.
Maintenance
Safety instructions
Only a qualified electrician is allowed to perform the maintenance.
Before starting work inside the cabinet,
• isolate the drive from the supply (note that any switch-disconnector installed in
the drive does not switch off the voltage from the input terminals)
• wait for 5 minutes to let the intermediate circuit capacitors discharge
• open the cabinet doors
• ensure there is no dangerous voltage present by measuring the voltage of the
input terminals and the intermediate circuit terminals.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Maintenance
110
Note: This function is only available if the drive is equipped with a PPCS branching
unit of type APBU-xx. (The function is not supported by type NPBU branching units.)
Maintenance
111
Maintenance
112
Cooling fans
2 2
5
4
Maintenance
113
Maintenance
114
2 2
Maintenance
115
Supply and inverter module cooling fan replacement (Frame R8i and up)
The lifespan of the cooling fans of the supply and inverter modules is about 50 000
hours. The actual lifespan depends on the running time of the fan, ambient
temperature and dust concentration. Each supply and inverter module has its own
cooling fan. Replacements are available from ABB. Do not use other than ABB
specified spare parts.
The supply and inverter application programs keep track of the running times of the
cooling fans of the supply and inverter modules respectively. See the Firmware
Manuals delivered with the drive for the actual signals which indicate the running
time.
Module fan replacement procedure
1. Read and repeat the steps in section Safety instructions above.
2. Disconnect the fan wiring plug (1).
3. Remove the locking screws (2).
4. Pull the fan out along its sliding rails (3).
5. Install a new fan in reverse order.
Maintenance
116
ALCL-1x ALCL-2x
2 2
1
3
Maintenance
117
Fan holder
1. Remove the eight screws attaching the fan holder to the cabinet roof.
2. Lift the fan holder until the fan cable can be disconnected.
3. Disconnect the fan cable.
4. Remove the fan from the fan holder.
5. Fasten a new fan to the fan holder.
6. Reconnect the fan cable.
7. Insert the fan holder into the aperture in the cabinet roof. Make sure the gasket
is not displaced while doing this.
8. Fasten the eight screws attaching the fan holder.
Maintenance
118
2 2 4
1
3
2
2
3
7
6
5
5
Maintenance
119
10
9
8
8
9
8 8
12
11 11
Heatsinks
The heatsink fins of the power modules pick up dust from the cooling air. The module
runs into overtemperature warnings and faults if the heatsinks are not clean. In a
“normal” environment (not especially dusty nor clean) the heatsinks should be
checked annually, in a dusty environment more often.
Whenever necessary, clean the heatsinks as follows:
1. Remove the cooling fan (see section Cooling fans).
2. Blow dry clean compressed air from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust. Note: Prevent the dust from
entering adjoining equipment.
3. Refit the cooling fan.
Capacitors
The inverter modules employ several electrolytic capacitors. Their lifespan is at least
90 000 hours depending on the operating time of the drive, loading and ambient
temperature. Capacitor life can be prolonged by lowering the ambient temperature.
It is not possible to predict capacitor failure. Capacitor failure is usually followed by
damage to the unit and an input cable fuse failure, or a fault trip. Contact ABB if
capacitor failure is suspected.
Reforming
Reform (re-age) spare part capacitors once a year according to ACS 600/800
Capacitor Reforming Guide (code: 64059629 [English], available through your local
ABB representative.
Capacitor replacement
Contact an ABB service representative.
Maintenance
120
Maintenance
121
Fault Tracing
To display the warning or fault identification text, switch the control panel to view the
line-side converter as described in section Control panel on page 37.
Conflicting ID numbers
If the ID numbers of the line-side and the motor-side converters are set equal, the
control panel stops functioning. To clear the situation:
• Disconnect the panel cable from the RMIO board of the motor-side converter.
• Set the ID number of the line-side converter RMIO board to 2. For the setting
procedure, see the application program (e.g. Standard Application Program)
Firmware Manual.
• Connect the disconnected cable to the RMIO board of the motor-side converter
again and set the ID number to 1.
Fault Tracing
122
Fault Tracing
123
Technical data
IEC ratings
The ratings for the ACS800-37 with a 50 Hz supply are given below. The symbols
are described below the table.
Nominal No-over- Light- Heavy-duty Heat dissi- Air Noise
ratings load use overload use use pation flow level
ACS800-37 type
Icont.max Imax Pcont.max I2N PN I2hd Phd
A A kW A kW A kW kW m3/h dBA
Three-phase supply voltage 380 V, 400 V or 415 V
ACS800-37-0060-3 120 168 55 114 55 88 45 1.8 500 73
ACS800-37-0070-3 150 234 75 142 75 117 55 2.4 500 73
ACS800-37-0100-3 165 264 90 157 75 132 75 2.8 500 73
ACS800-37-0140-3 202 293 110 194 90 151 75 6 1300 74
ACS800-37-0170-3 250 363 132 240 132 187 90 7 1300 74
ACS800-37-0210-3 292 400 160 280 160 218 110 8 3160 75
ACS800-37-0260-3 370 506 200 355 200 277 132 10 3160 75
ACS800-37-0320-3 469 642 250 450 250 351 200 13 3160 75
ACS800-37-0390-3 565 773 315 542 315 423 250 16 3160 75
ACS800-37-0510-3 730 1000 400 701 355 546 250 23 3160 75
ACS800-37-0640-3 919 1258 500 882 500 688 355 24 6400 77
ACS800-37-0770-3 1111 1521 630 1067 630 831 450 31 6400 77
ACS800-37-0960-3 1379 1888 800 1324 710 1031 560 43 6400 77
ACS800-37-1070-3 1535 2102 900 1474 800 1149 630 46 10240 78
ACS800-37-1430-3 2056 2814 1200 1973 1100 1538 800 63 10240 78
ACS800-37-1810-3 2610 3573 1600 2506 1400 1953 1100 83 12800 79
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACS800-37-0070-5 120 168 75 114 75 88 55 2.4 500 73
ACS800-37-0100-5 139 234 90 132 90 114 75 2.8 500 73
ACS800-37-0120-5 156 264 110 148 (1 90 125 75 3.4 500 73
ACS800-37-0170-5 200 291 132 192 132 150 90 6 1300 74
ACS800-37-0210-5 245 355 160 235 (2 160 183 110 8 1300 74
ACS800-37-0260-5 302 438 200 289 (3 200 226 132 9 3160 75
ACS800-37-0320-5 365 530 250 350 (4 250 273 160 11 3160 75
ACS800-37-0400-5 455 660 315 437 315 340 200 14 3160 75
ACS800-37-0460-5 525 762 355 504 355 393 250 16 3160 75
ACS800-37-0510-5 595 863 400 571 400 445 315 18 3160 75
ACS800-37-0610-5 700 1016 500 672 450 524 315 23 3160 75
ACS800-37-0780-5 892 1294 630 856 630 667 450 26 6400 77
ACS800-37-0870-5 1005 1458 710 965 630 752 500 32 6400 77
ACS800-37-1160-5 1338 1941 900 1284 900 1001 710 44 6400 77
ACS800-37-1330-5 1528 2217 1120 1467 1120 1143 800 46 10240 78
Technical data
124
Symbols
Nominal ratings
Icont.max Continuous RMS output current. No overloadability at 40 °C (104 °F).
Imax Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Typical ratings for no-overload use
Pcont.max Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for light-overload use (10% overloadability)
I2N Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
PN Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for heavy-duty use (50% overloadability)
I2hd Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
Phd Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Technical data
125
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3281 ft), or if the ambient temperature exceeds 40 °C (104 °F).
Temperature derating
In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F), the rated output current is decreased
by 1% for every additional 1 °C (1.8 °F). The output current is calculated by multiplying the current
given in the rating table by the derating factor.
Example If the ambient temperature is 50 °C (+122 °F), the derating factor is 100 % - 1 % · 10 °C =
90% or 0.90. The output current is then 0.90 × I or 0.90 × I . °C
2N cont.max
Altitude derating
At altitudes from 1000 to 4000 m (3281 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool. If the installation site is higher than
2000 m (6600 ft) above sea level, please contact your local ABB distributor or office for further
information.
Technical data
126
NEMA ratings
The ratings for the ACS800-37 with a 60 Hz supply are given below. The symbols
are described below the table.
Heavy-duty Heat dis- Noise
Nominal ratings Normal use Air flow
use sipation level
ACS800-37 type
Imax Pcont.max I2N PN I2hd Phd
A HP A HP A HP Btu/h ft3/min dBA
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
ACS800-37-0070-5 168 75 114 75 88 60 8200 295 73
ACS800-37-0100-5 234 100 132 100 114 75 9600 295 73
ACS800-37-0120-5 264 125 156 125 125 100 11600 295 73
ACS800-37-0170-5 291 150 192 150 156 125 20500 765 74
ACS800-37-0210-5 355 200 240 200 183 150 27300 765 74
ACS800-37-0260-5 438 250 302 250 226 150 30700 1860 75
ACS800-37-0320-5 530 300 361 300 273 200 37600 1860 75
ACS800-37-0400-5 660 350 437 350 340 250 47800 1860 75
ACS800-37-0460-5 762 450 504 400 393 300 54700 1860 75
ACS800-37-0510-5 863 500 571 450 445 350 61500 1860 75
ACS800-37-0610-5 1016 550 672 550 524 400 78600 1860 75
ACS800-37-0780-5 1294 750 856 700 667 550 88800 3770 77
ACS800-37-0870-5 1458 900 965 800 752 650 109000 3770 77
ACS800-37-1160-5 1941 1150 1284 1050 1001 850 150000 3770 77
ACS800-37-1330-5 2217 1300 1467 1250 1143 1000 157000 6030 78
ACS800-37-1820-5 2956 1650 1956 1650 1524 1250 229000 6030 78
ACS800-37-2200-5 3670 2150 2428 2050 1892 1600 277000 7530 79
Three-phase supply voltage 525 V, 575 V or 600 V
ACS800-37-0170-7 202 125 133 125 104 100 27300 765 74
ACS800-37-0210-7 235 150 156 150 121 100 30700 765 74
ACS800-37-0260-7 301 200 193 200 150 150 41000 1860 75
ACS800-37-0320-7 417 250 268 250 209 200 51200 1860 75
ACS800-37-0400-7 502 350 322 300 251 250 61500 1860 75
ACS800-37-0440-7 571 400 367 350 286 300 64900 1860 75
ACS800-37-0540-7 668 450 429 450 334 350 71700 1860 75
ACS800-37-0790-7 985 700 632 650 493 500 120000 3770 77
ACS800-37-0870-7 1091 800 700 750 545 600 126000 3770 77
ACS800-37-1160-7 1425 950 914 1000 713 750 157000 3770 77
ACS800-37-1330-7 1663 1250 1067 1150 831 900 185000 6030 78
ACS800-37-1510-7 1879 1350 1206 1300 940 1050 212000 6030 78
ACS800-37-2320-7 2791 1850 1791 2000 1396 1500 304000 7530 79
ACS800-37-2780-7 3472 2600 2228 2450 1736 1900 362000 10550 79
ACS800-37-3310-7 3987 3000 2559 2800 1999 2200 413000 11300 79
PDM-184674-G18
Technical data
127
Symbols
Nominal ratings
Imax Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Pcont.max Typical motor power. The power ratings apply to most 4-pole NEMA-rated motors at
nominal voltage (460 or 575 V).
Normal use (10% overloadability)
I2N Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
PN Typical motor power. The power ratings apply to most 4-pole NEMA-rated motors at
nominal voltage (460 or 575 V).
Heavy-duty use (50% overloadability)
I2hd Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
Phd Typical motor power. The power ratings apply to most 4-pole NEMA-rated motors at
nominal voltage (460 or 575 V).
Technical data
128
Technical data
129
AC fuses
Notes:
• Larger fuses must not be used.
• Fuses from other manufacturers can be used if they meet the ratings.
• The recommended fuses are for branch circuit protection per NEC as required for
UL approval.
AC fuse information
Drive type aR, IEC aR, UL Recognized
Qty In
Bussmann Ferraz Shawmut Bussmann Ferraz Shawmut
400 V
ACS800-37-0060-3 3 160 170M3814 – 170M3014 –
ACS800-37-0070-3 3 200 170M3815 – 170M3015 –
ACS800-37-0100-3 3 250 170M3816 – 170M3016 –
ACS800-37-0140-3 3 315 170M3817 – 170M3017 –
ACS800-37-0170-3 3 400 170M5808 – 170M5008 –
ACS800-37-0210-3 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-37-0260-3 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-37-0320-3 3 800 170M8545 6.9URD3PV0800 170M6212 –
ACS800-37-0390-3 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-37-0510-3 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-37-0640-3 3 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-37-0770-3 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-37-0960-3 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-37-1070-3 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-37-1430-3 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-37-1810-3 6 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
500 V
ACS800-37-0070-5 3 160 170M3814 – 170M3014 –
ACS800-37-0100-5 3 200 170M3815 – 170M3015 –
ACS800-37-0120-5 3 250 170M3816 – 170M3016 –
ACS800-37-0170-5 3 315 170M3817 – 170M3017 –
ACS800-37-0210-5 3 400 170M5808 – 170M5008 –
ACS800-37-0260-5 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-37-0320-5 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-37-0400-5 3 800 170M8545 6.9URD3PV0800 170M6212 –
ACS800-37-0460-5 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-37-0510-5 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-37-0610-5 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-37-0780-5 3 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-37-0870-5 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-37-1160-5 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-37-1330-5 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-37-1820-5 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-37-2200-5 6 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
690 V
ACS800-37-0170-7 3 250 170M3816 – 170M3016 –
ACS800-37-0210-7 3 315 170M3817 – 170M3017 –
ACS800-37-0260-7 3 315 170M3817 6.9URD1PV0315 170M3017 –
ACS800-37-0320-7 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-37-0400-7 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-37-0440-7 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-37-0540-7 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-37-0790-7 3 1000 170M6414 6.9URD32TTF1000 170M6414 6.9URD32TTF1000
ACS800-37-0870-7 3 1250 170M6416 – 170M6416 –
ACS800-37-1160-7 3 1250 170M6416 – 170M6416 –
ACS800-37-1330-7 6 1000 170M6414 6.9URD32TTF1000 170M6414 6.9URD32TTF1000
ACS800-37-1510-7 6 1000 170M6414 6.9URD32TTF1000 170M6414 6.9URD32TTF1000
ACS800-37-2320-7 6 1250 170M6416 – 170M6416 –
ACS800-37-2780-7 9 1250 170M6416 – 170M6416 –
ACS800-37-3310-7 9 1250 170M6416 – 170M6416 –
PDM-184674-G5
Technical data
130
DC fuses
Notes:
• Larger fuses must not be used.
• Fuses from other manufacturers can be used if they meet the ratings.
• The recommended fuses are for branch circuit protection per NEC as required for
UL approval.
DC fuse information
Drive type IEC UL Recognized
Qty
Bussmann Ferraz Shawmut In Bussmann In
400 V
ACS800-37-0060-3
… – – – – – –
ACS800-37-0510-3
ACS800-37-0640-3 8 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-37-0770-3 8 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-37-0960-3 8 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-37-1070-3 12 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-37-1430-3 12 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-37-1810-3 16 170M8547 6.9URD33PA1250 1250 170M6216 1250
500 V
ACS800-37-0070-5
… – – – – – –
ACS800-37-0610-5
ACS800-37-0780-5 8 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-37-0870-5 8 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-37-1160-5 8 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-37-1330-5 12 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-37-1820-5 12 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-37-2200-5 16 170M8547 6.9URD33PA1250 1250 170M6216 1250
690 V
ACS800-37-0170-7
… – – – – – –
ACS800-37-0540-7
ACS800-37-0790-7 8 170M8646 12URD73PA0700 700 170M8636 700
ACS800-37-0870-7 8 170M8647 11URD73PA0800 800 170M8637 800
ACS800-37-1160-7 8 170M8647 11URD73PA0800 800 170M8637 800
ACS800-37-1330-7 12 170M8647 11URD73PA0800 800 170M8637 800
ACS800-37-1510-7 12 170M8647 11URD73PA0800 800 170M8637 800
ACS800-37-2320-7 16 170M8647 11URD73PA0800 800 170M8637 800
ACS800-37-2780-7 24 170M8647 11URD73PA0800 800 170M8637 800
ACS800-37-3310-7 24 170M8647 11URD73PA0800 800 170M8637 800
PDM-184674-G5
Technical data
131
Harmonic distortion Harmonics are below the limits defined in IEEE519 for all Isc/IL. Each individual harmonic
current fulfils IEEE519 table 10-3 for Isc/IL > 20. Current THD and each individual current
harmonic fulfil IEC 61000-3-4 table 5.2 for R sce > 66. The values will be met if the supply
network voltage is not distorted by other loads.
Input power cable lead- Ø60 mm. For quantity and location, see the chapter Dimensions.
throughs
Technical data
132
Technical data
133
Motor connection
Voltage (U2) 0 to U1, 3-phase symmetrical, Umax at the field weakening point
U Nmains
fFWP = · fNmotor
UNmotor
where fFWP = frequency at field weakening point; UNmains = mains (input power) voltage;
U Nmotor = rated motor voltage; fNmotor = rated motor frequency
Power limit 2 × Phd. After approximately 2 minutes at 2 × Phd, the limit is set at Pcont.max.
Motor cable lead-throughs 3 × Ø60 mm at each inverter module (units without common motor terminal cubicle)
Units with common motor terminal cubicle: See the chapter Dimensions.
Technical data
134
Technical data
135
Cabling
direction
Cabling direction
68265631-B cabinet_400_generic.asm
Output terminals 8 × Ø13 mm per phase. Tightening torque: 70 Nm (52 lbf.ft). See the chapter Dimensions.
Units with option +H359
(common motor terminal
cubicle)
Technical data
136
Maximum recommended 100 m (328 ft). Motor cables up to 500 m (1640 ft) long are allowed but EMC filtering
motor cable length within the specified limits will not be realised.
Efficiency
> 97% (at rated current and nominal supply voltage)
Cooling
Method Internal fans, flow direction from bottom to top
Degrees of protection
IP21; IP22; IP42; IP54, IP54R (with air outlet duct)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation Storage Transportation
installed for stationary use in the protective package in the protective package
Installation site altitude 0 to 4000 m (13123 ft) above - -
sea level [above 1000 m
(3281 ft), see section
Derating]
Air temperature -15 to +50 °C (5 to 122 °F). -40 to +70 °C (-40 to +158°F) -40 to +70 °C (-40 to +158°F)
See section Derating.
Relative humidity 5 to 95% Max. 95% Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels No conductive dust allowed.
(IEC 60721-3-3, IEC 60721-3- Boards without coating: Boards without coating: Boards without coating:
2, IEC 60721-3-1) Chemical gases: Class 3C1 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Boards with coating: Boards with coating: Boards with coating:
Chemical gases: Class 3C2 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Atmospheric pressure 70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
0.7 to 1.05 atmospheres 0.7 to 1.05 atmospheres 0.6 to 1.05 atmospheres
Vibration (IEC 60068-2) Max. 1 mm (0.04 in.) Max. 1 mm (0.04 in.) Max. 3.5 mm (0.14 in.)
(5 to 13.2 Hz), (5 to 13.2 Hz), (2 to 9 Hz),
max. 7 m/s2 (23 ft/s2) max. 7 m/s2 (23 ft/s2) max. 15 m/s2 (49 ft/s2)
(13.2 to 100 Hz) sinusoidal (13.2 to 100 Hz) sinusoidal (9 to 200 Hz) sinusoidal
Technical data
137
Shock (IEC 60068-2-29) Not allowed Max. 100 m/s2 (330 ft./s2), Max. 100 m/s2 (330 ft./s2),
11 ms 11 ms
Free fall Not allowed 100 mm (4 in.) for weight 100 mm (4 in.) for weight
over 100 kg (220 lb) over 100 kg (220 lb)
Materials
Cabinet Hot-dip zinc-coated (thickness approx. 20 µm) steel sheet (thickness 1.5 mm) with
polyester thermosetting powder coating (thickness approx. 80 µm) on visible surfaces.
Colour: RAL 7035 (light grey, semigloss).
Fire safety of materials Insulating materials and non-metallic items: Mostly self-extinctive
(IEC 60332-1)
Disposal The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
printed circuit boards contain lead, both of which are classified as hazardous waste within
the EU. They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions,
please contact your local ABB distributor.
Applicable standards
The drive complies with the following standards. The compliance with the European Low
Voltage Directive is verified according to standards EN 50178 and EN 60204-1.
• EN 50178 (1997) Electronic equipment for use in power installations.
• EN 60204-1 (1997) Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance: The final assembler of the machine is responsible for installing
- an emergency-stop device
- a supply disconnecting device.
• EN 60529: 1991 (IEC 529) Degrees of protection provided by enclosures (IP code).
• IEC 60664-1 (1992) Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
requirements and tests.
Technical data
138
• EN 61800-3 (2004) Adjustable speed electrical power drive systems. Part 3: EMC requirements and specific
test methods
• UL 508C UL Standard for Safety, Power Conversion Equipment, second edition
• CSA C22.2 No. 14-95 Industrial control equipment
Technical data
139
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the European Low
Voltage and EMC Directives (Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/
EEC, as amended by 93/68/EEC).
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is a
person or organisation having necessary skills in installing and/or commissioning power drive systems,
including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
400 A, or intended for use in complex systems in the second environment.
Technical data
140
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
from the local ABB representative.
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
Machinery Directive
The drive complies with the European Union Machinery Directive (98/37/EC) requirements for an
equipment intended to be incorporated into machinery.
Technical data
141
“C-tick” marking
“C-tick” marking is required in Australia and New Zealand. A “C-tick” mark is attached to each drive in
order to verify compliance with the relevant standard (IEC 61800-3 (2004) – Adjustable speed electrical
power drive systems. Part 3: EMC product standard including specific test methods), mandated by the
Trans-Tasman Electromagnetic Compatibility Scheme.
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced by the Australian
Communication Authority (ACA) and the Radio Spectrum Management Group (RSM) of the New
Zealand Ministry of Economic Development (NZMED) in November 2001. The aim of the scheme is to
protect the radiofrequency spectrum by introducing technical limits for emission from electrical/
electronic products.
First environment includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is a
person or organisation having necessary skills in installing and/or commissioning power drive systems,
including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
400 A, or intended for use in complex systems in the second environment.
Technical data
142
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
from the local ABB representative.
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
Technical data
143
Technical data
144
Technical data
145
Dimensions
Weights
The following table shows the approximate weights of all ACS800-37 types (without
options).
Weight
ACS800-37-…
kg lb
0060-3 0070-5
0070-3 0100-5 250 550
0100-3 0120-5
0140-3 0170-5 0170-7
400 880
0170-3 0210-5 0210-7
0210-3 0260-5 0260-7
0260-3 0320-5 0320-7
0320-3 0400-5 0400-7
950 2090
0390-3 0460-5 0440-7
0510-3 0510-5 0540-7
0610-5
0640-3 0780-5 0790-7
0770-3 0870-5 0870-7 2000 4410
0960-3 1160-5 1160-7
1070-3 1330-5 1330-7
3060 6750
1430-3 1820-5 1510-7
1810-3 2200-5 2320-7 3600 7940
2780-7 4780 10540
3310-7 4930 10870
Dimensions
146
Frame R6
Dimensions
147
Dimensions
148
Dimensions
149
Dimensions
150
Frame R7i
Dimensions
151
Dimensions
152
Dimensions
153
Dimensions
154
Dimensions
155
Dimensions
156
Dimensions
157
Dimensions
158
Dimensions
159
Dimensions
160
Dimensions
161
Dimensions
162
Dimensions
163
Dimensions
164
Dimensions
165
Dimensions
166
Dimensions
167
Dimensions
168
Dimensions
169
Dimensions
170
Dimensions
171
Dimensions
172
Dimensions
173
Dimensions
174
Dimensions
175
Dimensions
176
Dimensions
177
Dimensions
178
Dimensions
179
Dimensions
180
Dimensions
181
Dimensions
182
Dimensions
183
Dimensions
184
Dimensions
185
Dimensions
186
Dimensions
187
Dimensions
188
Dimensions
189
Dimensions
190
Dimensions
191
Dimensions
192
Dimensions
193
Dimensions
194
Dimensions
195
Dimensions
196
Dimensions
197
Dimensions
198
Dimensions
199
Dimensions
200
Dimensions
201
Dimensions
202
Dimensions
203
Dimensions
204
Dimensions
205
Dimensions
206
Dimensions
207
Dimensions
208
Dimensions
209
Dimensions
210
Dimensions
211
Dimensions
212
Dimensions
213
Dimensions
214
Dimensions
215
Dimensions
216
Dimensions
217
Dimensions
218
Dimensions
219
Resistor braking
UN ACS800-37 type Brake chopper type (+D150) Brake resistor type (+D151)
ACS800-37-0060-3
••• NBRA-658 2 × SAFUR210F575
ACS800-37-0170-3
ACS800-37-0210-3
400 V ••• NBRA-659 2 × SAFUR180F460
ACS800-37-0510-3
ACS800-37-0640-3
2 × NBRA-659 2 × (2 × SAFUR180F460)
ACS800-37-0770-3
ACS800-37-0070-5
••• NBRA-658 2 ×SAFUR125F500
ACS800-37-0210-5
ACS800-37-0260-5
500 V ••• NBRA-659 2 × SAFUR200F500
ACS800-37-0610-5
ACS800-37-0780-5
2 × NBRA-659 2 × (2 × SAFUR200F500)
ACS800-37-0870-5
ACS800-37-0170-7
••• NBRA-669 2 × SAFUR200F500
ACS800-37-0540-7
690 V
ACS800-37-0790-7
2 × NBRA-669 2 × (2 × SAFUR200F500)
ACS800-37-0870-7
Resistor braking
220
1 × NBRA-658 2 × SAFUR210F575 1.7 230 42 384 224 345 130 200 2500
1 × NBRA-659 2 × SAFUR180F460 1.2 353 54 545 287 444 167 257 2500
400 V
2 × NBRA-659 2 × (2 × SAFUR180F460) 1.2 706 108 545 575 444 333 257 5000
3 × NBRA-659 3 × (2 × SAFUR180F460) 1.2 1058 162 545 862 444 500 257 7500
1 × NBRA-658 2 × SAFUR125F500 2.0 268 36 408 192 237 111 137 2500
1 × NBRA-659 2 × SAFUR200F500 1.35 403 54 605 287 355 167 206 2500
500 V
2 × NBRA-659 2 × (2 × SAFUR200F500) 1.35 806 108 605 575 355 333 206 5000
3 × NBRA-659 3 × (2 × SAFUR200F500) 1.35 1208 162 605 862 355 500 206 7500
1 × NBRA-669 2 × SAFUR200F500 1.35 404 54 835 287 355 167 206 2500
690 V 2 × NBRA-669 2 × (2 × SAFUR200F500) 1.35 807 108 835 287 355 333 206 5000
3 × NBRA-669 3 × (2 × SAFUR200F500) 1.35 1211 162 835 575 355 500 206 7500
UN = Nominal voltage
R = Resistance of specified resistors (per chopper)
Pbrmax = Maximum short-term (1 min every 10 mins) braking power
Pcont = Maximum continuous braking power
Imax = Maximum peak current (per chopper)
Pbr = Braking power for the specified duty cycle
Irms = Corresponding RMS current (per chopper)
Airflow = Airflow required for cooling of chopper(s) and resistors
Resistor braking
221
NBRA-658 268 81 380 101 2.15 268 331 268 331 660
500 V 811 795
NBRA-659 403 109 571 136 1.43 403 498 317 391
690 V NBRA-669 404 119 414 107 2.72 404 361 298 267 1120 1096
UN = Nominal voltage
Pbrmax = Maximum short-term (1 min every 10 mins) braking power
Pcont = Maximum continuous braking power
Imax = Maximum peak current
Irms = Corresponding RMS current
R = Recommended resistance
Pbr = Braking power for the specified duty cycle. Note: This value may be limited by Pbrmax.
Ubr_on = DC voltage at which chopper starts conducting
Ubr_off = DC voltage at which chopper stops conducting
Airflow = Airflow required for cooling of chopper
U N = Nominal voltage
R = Resistance
ER = Short energy pulse that the resistor assembly will withstand each 400 seconds
PRcont = Continuous power (heat) dissipation of the resistor when placed correctly. Energy ER
dissipates in 400 seconds.
Airflow = Airflow required for cooling of one resistor
Resistor braking
222
The Pbrmax values specified in the technical data table above are for the reference braking cycle
(1 minute of braking, 9 minutes of rest). If the actual duty cycle does not correspond to the reference
cycle, the maximum allowed braking power Pbr must be used instead. In the technical data table,
Pbr is given for two additional braking cycles. See below for directions for calculating Pbr for other
braking cycles.
3. Check the resistors selection. The energy generated by the motor during a 400-
second period must not exceed the heat dissipation capacity ER.
If the ER value is not sufficient, it is possible to use a four-resistor assembly in which two standard
resistors are connected in parallel, two in series. The ER value of the four-resistor assembly is four
times the value specified for the standard resistor.
Custom resistors
Resistors other than the standard resistors can be used provided that:
• the resistance is not lower than with the standard resistors
WARNING! Never use a brake resistor with a resistance below the value specified
for the particular drive / brake chopper / resistor combination. The drive and the
chopper are not able to handle the overcurrent caused by the low resistance.
• the resistance does not restrict the braking capacity needed, i.e.,
2
UDC
Pmax <
R
where
Pmax maximum power generated by the motor during braking
UDC voltage over the resistor during braking, e.g.,
1.35 · 1.2 · 415 VDC (when supply voltage is 380 to 415 VAC),
1.35 · 1.2 · 500 VDC. (when supply voltage is 440 to 500 VAC) or
1.35 · 1.2 · 690 VDC (when supply voltage is 525 to 690 VAC).
R resistor resistance (ohm)
• the heat dissipation capacity (ER) of the resistors is sufficient for the application
(see step 3 above).
Resistor braking
223
Example 1
Duration of a braking cycle is 30 minutes. The braking time is
15 minutes.
Result: If the braking time exceeds 10 minutes, the braking is considered
continuous. The allowed continuous braking power is 10% of the Maximum Braking
Power (Pbrmax).
Example 2
Duration of a braking cycle is three minutes. The braking time is
40 seconds.
Pbrmax × 60 s
1. Pbr < = 0.375 × Pbrmax
4 × 40 s
Pbr
Pbrmax
t
tbr 600 s
T = Duration of braking cycle
Result: The maximum allowed braking power for the cycle is 37 % of the rated value
given for the reference cycle.
Resistor braking
224
Example 3
Duration of a braking cycle is three minutes. The braking time is 10 seconds.
Pbrmax × 60 s
1. Pbr < = 1.5 · Pbrmax
4 × 10 s
Pbr
Pbrmax
t
tbr 600 s
T = Duration of the braking cycle
Result: The maximum allowed braking power for the cycle is equal to the Maximum
Braking Power (Pbrmax) given for the reference cycle.
Resistor braking
225
WARNING! All materials near the brake resistors must be non-flammable. The
surface temperature of the resistors is high. The temperature of the air rising from
the resistors is hundreds of degrees Celsius. Protect the resistors against contact.
For resistor cable, use the type specified for drive input cabling (specified under
chapter Technical Data) so the input fuses will protect the resistor cable also. Two-
conductor shielded cable with the same cross-sectional area can alternatively be
used. The maximum length of the resistor cable is 10 m.
For protection against overheating, resistors with thermal circuit breakers (standard
in ABB resistors) should be used. The circuit breakers should be wired to the
ENABLE inputs of the brake choppers.
WARNING! The ENABLE input terminal blocks of the choppers are at intermediate
circuit potential when the supply unit of the ACS800-37 is running. This voltage is
extremely dangerous and may cause serious damage or injuries if the isolation level
and protection conditions for the thermal circuit breakers are not sufficient. The
normally-closed breakers should always be properly isolated (over 2.5 kV) and
shrouded against contact.
Note: For the ENABLE input wiring, use cable rated as follows:
• twisted pair (screened type recommended)
• rated operating voltage between a core and earth (U0): ≥ 750 V
• insulation test voltage > 2.5 kV
Resistor braking
226
Brake chopper
X1
R+ R– 1 2
1 2 3
R+ R–
t°
Brake resistor
Resistor braking
3AFE68557925 REV B EN
EFFECTIVE: 01.11.2005