Transformer Testing PDF
Transformer Testing PDF
Srinivasan
TYPES OF TRANSFORMER
BY APPLICATION
• 1. DISTRIBUTION TRANSFORMER
• 2.POWER TRANSFORMER
• 3.CURRENT TRANSFORMER
• 4.POTENTIAL TRANSFORMER
• 5.FURNACE TRANSFORMER
• 6.BOOSTER TRANSFORMER
• 7.RECTIFIER TRANSFORMER
• 8.LOCOMOTIVE TRANSFORMER
• 9.MINING TRANSFORMER
• 10.PHASE SHIFTING TRANSFORMER
• 11.WELDING TRANSFORMER
• 12.HIGH VOLTAGE TESTING/SC TESTING TRF.
• 13.GROUNDING TRANSFORMERS
• 14.CONVERTER TRANSFORMER
Traceabllity
Accuracy
Precision
Probability
Std. deviation
Standards
Accreditation
•A MODERN TRANSFORMER IS A
COMPLEX ELECTROMAGNETIC
APPARATUS
•TRANSFORMERS SERVE FOR
TRANSMISSION AND DISTRIBUTION
OF ELECTRICAL ENERGY
•TRANSFORMERS (DISTRIBUTION)
ARE THE LAST MAJOR LINK
BETWEEN UTILITY & CONSUMER
•TRANSFORMERS ARE STATIC
ALTERNATING CURRENT MACHINES
•PRINCIPLE IS BASED ON MUTUAL
INDUCTION BETWEEN WINDINGS
THROUGH A COMMON CORE
•OIL-IMMERSED AND DRY TYPES
•POWER AND DISTRIBUTION TYPES
•SPECIAL TYPES
V1
I’2 I1
I0
I2
E2 E = - 4.44 φmf N
R1 + R’2 X1 + X’2
I0 I’2
V1 X0 E’2=E1
X1 + X’2
Iw Iµ
R0
IEC-76 , IS 2026 and IS 1180 specify the
routine, type & special tests for power
transformers
Measurement of winding resistance
Measurement of voltage ratio
Polarity test
Measurement of no-load loss & no-load current
Measurement of load-loss & short-circuit
impedance
Measurement of insulation resistance
Dielectric tests
Measurement of winding resistance
Measurement of voltage ratio
Polarity test
Measurement of no-load loss & no-load
current
Measurement of load-loss & short-circuit
impedance
Measurement of insulation resistance
Dielectric tests
Temperature-rise test
Dielectric test
Short-circuit test
Measurement of zero-sequence
impedance of three phase transformers
Measurement of acoustic noise level
Measurement of harmonics of the no-
load current
Measurement of power taken by the
fans & oil pumps
• Separate source voltage withstand test
Impulse generator
• Impulse wave is generated by
discharge of capacitors charged in
parallel into a wave shaping circuit.
Connection
Oscilograms
Oscilograms contd.
Oscilograms contd.
• MINOR INSULATION -conductor turns, layers
•enamel, paper
•oil ducts, paper cylinders
• MAJOR INSULATION- winding, core
•press board cylinders, oil ducts
•BUSHINGS - porcelain , condenser
Power & distribution transformers must be
constructed to withstand mechanical
stresses caused by external faults. These
stresses are produced due to
electromagnetic forces as a result of very
high current in the windings during short-
circuits.
• Prior to the short-circuit, transformer
is subjected to routine tests.
Asymmetrical current
• The peak current that transformer is
required to withstand = Isc(peak)=K
Isc
Value of K :
x/r 1 1.5 2 3 4 5 6 8 10 >14
K 1.51 1.64 1.76 1.95 2.09 2.19 2.27 2.38 2.46 2.55
Short-circuit may be
a) Preset or
b) Post set
Duration of each test
being 0.5 sec. ( > 5 MVA 0.25 sec)
For 1φ Transformers
No. of tests = Three
one test with tap at highest voltage ratio, one test
in principal taping & one test in
lowest voltage ratio
3φ Transformers
• No. of tests = Nine
• Three tests with tap at highest voltage
ratio, three tests in principal taping &
three tests in lowest voltage ratio
Tolerances on
• Asymmetrical current = ±5 %
• Symmetrical current = ±10 %
• Test duration = ±10 %
Oscillogram of dynamic short-circuit test on
3Phase 11/0.433kV 500kVA Distribution
transformer
SC Test contd.
Top oil 50 55
(temp.rise by thermometer method)
a) Direct loading
b) Back-to-Back method
c) Short-circuit method
Duration of test
Top oil temperature-rise does not vary more than
10C/hour during 4 consecutive hourly readings
Partial Discharge Tests
100pC
500pC
Noise Level
7.2 20 40
60
12 28 60
75
95
17.5 38 75
95
24 50 95
125
145
36 70 145
170
52 95 250
NOTES
1.Value of the impulse component of the relevant combined test.
The introduction of Um=550kV (instead of 525 kV), 800 kV (instead of 765 kV),