DVC and DAA Installation, Programming and Operations Manual (52411)
DVC and DAA Installation, Programming and Operations Manual (52411)
• Barriers such as closed or partially closed doors, walls, or A fire alarm system will not operate without any electrical
chimneys may inhibit particle or smoke flow. power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
• Smoke particles may become “cold,” stratify, and not reach been properly maintained and replaced regularly.
the ceiling or upper walls where detectors are located.
Equipment used in the system may not be technically com-
• Smoke particles may be blown away from detectors by air patible with the control panel. It is essential to use only equip-
outlets. ment listed for service with your control panel.
• Smoke particles may be drawn into air returns before Telephone lines needed to transmit alarm signals from a
reaching the detector. premise to a central monitoring station may be out of service
The amount of “smoke” present may be insufficient to alarm or temporarily disabled. For added protection against tele-
smoke detectors. Smoke detectors are designed to alarm at phone line failure, backup radio transmission systems are rec-
various levels of smoke density. If such density levels are not ommended.
created by a developing fire at the location of detectors, the The most common cause of fire alarm malfunction is inade-
detectors will not go into alarm. quate maintenance. To keep the entire fire alarm system in
Smoke detectors, even when working properly, have sensing excellent working order, ongoing maintenance is required per
limitations. Detectors that have photoelectronic sensing the manufacturer's recommendations, and UL and NFPA stan-
chambers tend to detect smoldering fires better than flaming dards. At a minimum, the requirements of NFPA 72 shall be
fires, which have little visible smoke. Detectors that have ion- followed. Environments with large amounts of dust, dirt or
izing-type sensing chambers tend to detect fast-flaming fires high air velocity require more frequent maintenance. A main-
better than smoldering fires. Because fires develop in different tenance agreement should be arranged through the local man-
ways and are often unpredictable in their growth, neither type ufacturer's representative. Maintenance should be scheduled
of detector is necessarily best and a given type of detector monthly or as required by National and/or local fire codes and
may not provide adequate warning of a fire. should be performed by authorized professional fire alarm
Smoke detectors cannot be expected to provide adequate installers only. Adequate written records of all inspections
warning of fires caused by arson, children playing with should be kept.
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of Limit-C1-2-2007
This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity 93% ± 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27º C/60-80º F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
HARSH™, NIS™, Notifier Integrated Systems™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®,
ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark
and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments
or suggestions about our online Help or printed manuals, you can email us.
Please note this email address is for documentation feedback only. If you have any technical issues,
please contact Technical Services.
Table of Contents
General Information................................................................................................................. 7
Section 1: DVC Overview ....................................................................................................... 10
1.1: Description...................................................................................................................................................10
1.1.1: Features..............................................................................................................................................12
1.1.2: Options ..............................................................................................................................................13
1.1.3: Specifications ................................................................................................................................13
1.2: DVC Board Layout......................................................................................................................................15
1.2.1: Wire Version......................................................................................................................................15
1.2.2: Fiber Versions....................................................................................................................................17
1.2.3: Switch Functions ...............................................................................................................................18
1.2.4: Indicators ...........................................................................................................................................19
1.3: Options.........................................................................................................................................................20
1.3.1: DVC-AO Analog Output Board Layout............................................................................................20
1.3.2: DVC-KD Keypad ..............................................................................................................................20
Section 2: DVC Installation .................................................................................................... 21
2.1: Overview......................................................................................................................................................21
2.1.1: Chassis ...............................................................................................................................................21
2.1.2: Doors and Dress Panels .....................................................................................................................21
2.2: Prepare for Installation ................................................................................................................................22
2.3: Installation Checklist ...................................................................................................................................23
2.4: Cabinet .........................................................................................................................................................23
2.5: Mount DVC Series Option Boards ..............................................................................................................24
2.5.1: DVC-AO Analog Output Board ........................................................................................................24
2.5.2: DVC-KD Keypad ..............................................................................................................................25
2.6: Mount a Network Communications Module in a CA-1 or CA-2 Chassis ...................................................26
2.7: Mount a DVC Series Board in a CA-1 or CA-2 Chassis.............................................................................26
2.8: Using a CFFT-1 with the CA-1 Chassis ......................................................................................................27
2.9: Move the Chassis for Wiring Access...........................................................................................................27
2.9.1: CA-1 ..................................................................................................................................................27
2.9.2: CA-2 ..................................................................................................................................................28
2.10: Wiring ........................................................................................................................................................28
2.10.1: DVC Series Board to 24V Power ...................................................................................................28
2.10.2: Alarm Bus .......................................................................................................................................29
2.10.3: Digital Audio Ports A and B on Wire Version Boards....................................................................30
2.10.4: RXA, RXB, TXA, TXB Fiber Version Board Connections ...........................................................31
2.10.5: FFT Connectivity.............................................................................................................................31
2.10.6: Auxiliary Inputs A and B.................................................................................................................33
2.10.7: Network Connection (NUP) Ports...................................................................................................34
2.10.8: USB Ports ........................................................................................................................................34
2.10.9: Push-to-Talk Indicator.....................................................................................................................35
2.10.10: RM-1 Remote Microphone Interface ............................................................................................35
2.10.11: MIC-1 Local Microphone Interface ..............................................................................................36
2.10.12: TELH-1 Local Phone Interface .....................................................................................................36
2.10.13: Analog Audio Outputs (DVC-AO)................................................................................................36
2.10.14: UL Power-limited Wiring Requirements ......................................................................................38
2.11: Replacement of NVRAM Memory-Backup Battery .................................................................................38
Section 3: DVC Configuration and Programming................................................................ 39
3.1: Setting the Configuration Switches .............................................................................................................39
3.1.1: Piezo (Switch 5).................................................................................................................................39
3.1.2: EFA and EFB (Switches 7 and 6)......................................................................................................39
3.1.3: 4WIRE (Switch 8) .............................................................................................................................40
3.2: Panel Programming .....................................................................................................................................40
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values
or not used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
IP downloads over a local area network (LAN) or No Yes No
the internet (Wide Area Network - WAN) No
Supplemental Documentation
The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices.
VeriFire Tools CD help file and CD pamphlet VERIFIRE-TCD, 51690
DAA2 and DAX Digital Audio Amplifier Manual 53265
Wire Guide Addendum for Digital Audio Loops 52916ADD
DVC-AO Audio Option Board Installation Document 52728
DVC-KD Keypad Product Installation Document 52709
Heat Dissipation Calculations Document for Cabinets with Digital Audio Products 53645
CA-1 Chassis Product Installation Document 52474
CA-2 Chassis Product Installation Document 52455
CMIC-1 Chassis Product Installation Document 52476
CFFT-1 Chassis for Firefighter’s Telephone Product Information Document 53289
NFS2-3030 Installation, Programming and Operations Manuals 52544, 52545, 52546
NFS2-640 Installation, Programming and Operations Manuals 52741, 52742, 52743
AMPS-24 Manual 51907
ACPS-610 Addressable Power Supply Manua 53018
NFS-640 Installation, Programming, Operations Manuals 51332, 51333, 51334
NFS-3030 Installation, Programming, Operations Manual 51330, 51345, 51344
NCA Network Control Annunciator Manual 51482
NCA-2 Network Control Annunciator Manual 52482
NCS Manual 51658
ONYXWorks Workstation Manual 52342
Noti-Fire-Net Manual 51584
High-Speed Noti-Fire-Net Manual 54013
NCM Installation Document 51533
HS-NCM High Speed Network Communications Module Installation Document 54014
SLC Wiring Manual 51253
DAA Series Product Information Sheet 52410
AA Series Audio Amplifier Manual 52526
XPIQ Manual 51013
ACS Annunciator Manual 15842
AFAWS Automatic Fire Alarm Warden Station 50705
FTM-1 Firephone Control Module 156-1391-02
ACT-4 Audio Coupling Transformer 53431
ACT-25 Audio Coupling Transformer 53432
ACT-70 Audio Coupling Transformer 53240
RM-1 Series Remote Microphones 51138
RPJ-1 Remote Paging Jack 15058
FPJ Firefighter’s Phone Jack 15510
CAB-4 Series Cabinets Installation Instructions 15330
EQ-CAB Series Installation Instructions 53412
Audio Fiber Links Document 52230
RSM-1A Residential Silence Module I56-006-000
AIM-1A Audible Isolation Module I56-006-002
CIM-2A/CSM-1A Isolator and Silencing Modules I56-2200-002
This manual contains cautions and warnings to alert the reader as follows:
CAUTION: Information about procedures that could cause programming errors, runtime errors, or
! equipment damage.
WARNING: Indicates information about procedures that could cause irreversible damage to the
! control panel, irreversible loss of programming data, or personal injury.
1.1 Description
Each DVC Series model is a multi-featured audio processor with digital audio functionality that operates
as an event-driven audio message generator and router. It is designed for use with the DAA, DAA2, and
DAX Series digital audio amplifiers in a single panel or networked environment. With the addition of
the optional DVC-AO board, the DVC may also be used as an analog audio source in retrofit analog
audio applications. (See Figure 1.1.)
The NFS2-640 and NFS2-3030 may be directly connected to the DVC for single panel applications. An
associated NCA-2 is required with the NFS2-640 when a DAL (Digital Audio Loop) is part of the
configuration. An associated NCA-2 is not required with the NFS2-640 when there is no DAL. Refer to
Figure 1.1 for illustrations of single panel configurations.
Network configurations require an associated NCA-2 or NFS2-3030, and will support all Network
Control-by-Event (CCBE) from the following ONYX® Series panels: NFS2-640, NFS-640, NFS2-
3030, and NFS-3030.
When used with the optional DVC-KD keypad and an NCA-2 or NFS2-3030, the Digital
Command Center serves as an audio command center, accepting live paging from several sources
and providing the ability to direct the paging to appropriate pre-programmed speaker zones in the
system.
NOTE: The DVC Series consists of all the model versions listed in the bullets below this note.
Individual part numbers are used in this manual only when it is necessary to distinguish features
or functions that differ. The term DVC is used in all other cases.
NOTE: The terms DAA, DAA2, DAX, and BDA are used in this manual to refer to all respective
wire and fiber models. Individual part numbers are used only when it is necessary to distinguish
features or functions that differ. Refer to the appropriate manual for individual model descriptions.
Figure 1.1 gives simplified overview illustrations of typical applications for the DVC Series and its
Digital Audio Loop (DAL).
NOTE: Wire and fiber versions of all DVC and DAL devices are compatible on a DAL. Fiber
option modules are required for fiber connections to new devices.
NFS2-3030 Single
Panel Applications
NFS2-3030 DAL
Optional Style 7 return
NUP
with DVC and DAL DAL
Digital Audio DAL
DVC Device Device Device
Loop (DAL). 1 2 32
DAL
Optional Style 7 return
NFS2-3030 DVC
with DVC, NUP DAL DAL DAL
Device Device Device
DAL, and
DVC-AO for 1 2 32
SLC
retrofits.
XPIQ Low DVC-AO
level
analog
audio
NFS2-640 Single
Panel Applications
loop) not
compatible with XPIQ Low DVC-AO
this application. level
analog
audio
DAL
Optional Style 7 return
NFS2-640 DVC DAL
NUP DAL DAL
with DVC, Device Device Device
NCA-2, DAL, 1 2
and DVC-AO 32
for retrofits.
DVC-AO AA Series Audio Amplifiers
NCA-2 NUP Low level analog
audio XPIQ, etc.
NCA-2 or DAL
NCM Optional Style 7 return
NFS2-3030 *
Networked
NFS2-640 DAL DAL DAL
System NCM Noti-Fire-Net NCM DVC Device Device Device
1 2 32
NCM NCM
NFS2-3030 NFS-320
NCA-2 or DAL
Networked NCM NFS2-3030 * Optional Style 7 return
System DAL DAL
Noti-Fire-Net DAL
with NFS2-640 NCM NCM DVC Device Device Device
Analog 1 2 32
Equipment NCM NCM
NOTE:
Speaker placement must be given careful consideration when planning an audio system.
• Place speakers from different DALs (Digital Audio Loops) so they are not within the audible
areas of other DALs.
• Carefully consider the audible range of speakers within a DAL; overlapping audio messages can
be confusing.
NOTE: A maximum of 54 nodes may be used on a standard Noti•Fire•Net when digital audio
messages will be broadcast over it. This limitation does not apply to a high-speed Noti•Fire•Net
network.
1.1.1 Features
• Programmable from NUP or USB port using VeriFire Tools with:
• Up to 32 minutes of standard quality or 4 minutes of high quality digital audio storage of
user-selected/created messages and tones.
• Up to 1000 audio sequences.
• Message prioritization.
• System configuration parameters.
• Equations for distribution of messages.
• Eight audio data and five Firefighters Telephone (FFT) channels on the DAL (Digital Audio
Loop).
• Audio data channels:
- 8 audio data channels when using standard quality audio.
- 1 audio data channel when using high quality audio.
• FFT channels:
- 5 FFT channels.
- Remote microphone uses one FFT channel.
• Distribution of one channel of audio data on a standard or high-speed Noti-Fire-Net.
• One Firefighters Telephone channel on Noti-Fire-Net.
• Digital audio ports for direct connection with up to 32 digital audio loop devices.
• Operates as a node on a standard or high-speed Noti-Fire-Net.
• Multiple audio command centers supported within a system.
• DCC (Display and Control Center) capabilities when used with DVC-KD and associated
NCA-2, NFS2-3030 or network workstation.
• Functional with NFS2-3030 or NFS2-640 as a standalone system (without Noti-Fire-Net).
• FireFighter’s Telephone (FFT) Riser, with local telephone handset option.
• Local paging microphone option.
• Remote microphone paging option with RM-1.
• Broad paging functionality when used with DVC-KD via microphone, TELH-1 or FFT, RM-1,
AUX A or AUX B inputs.
• All Call
• Page Active Evac Areas
• Page Active Alert Areas
• Page Inactive Areas
• Auxiliary input for 12Vp-p analog low-level audio sources.
• Auxiliary input for 1VRMS, to be used for background music input, an interface with a
telephone paging source, or other compatible audio sources. Includes user audio level
adjustment feature.
• Push-to-talk relay.
• Isolated alarm bus input, to be used for backup activation of alarm messages when normal
digital communication is lost.
• Meets UL THD Distortion requirements. Refer to the DAA2/DAX manual for individual
amplifier distortion specifications.
• Meets ULC THD Distortion requirements. Refer to the DAA2/DAX manual for individual
amplifier distortion specifications.
1.1.2 Options
DVC-AO
The DVC-AO audio output board has four low-level analog outputs. It mounts on the DVC and is
compatible with XPIQ, AA-30/E, AA-100/E, and AA-120/E amplifier products. Refer to Section
“Analog Audio Outputs (DVC-AO)” on page 36.
DVC-KD
The DVC-KD keypad is for local annunciation and controls. Refer to “Using the DVC-KD
Keypad” on page 68 and “DVC-KD Keypad” on page 25 for more information on the DVC-KD.
1.1.3 Specifications
24VDC Power - TB1
24VDC input, 440 mA, alarm or standby, non-resettable, power-limited by the source, non-
supervised.
• If a DVC-KD is attached, add: 60 mA
• If a DVC-AO is attached, add: 175 mA
• If an RM-1 is attached, add: 60 mA
For a possible total of: 735 mA alarm or standby
Recommended wiring: 14-18 AWG twisted-pair (max. 14 AWG.).
Digital Audio Ports A and B - TB2, TB3
Refer to the Wiring Guide, p/n 52916ADD, for acceptable wire types.
EIA-485 format.
Power-limited.
Single- and Multi-mode Fiber-Optic Digital Audio Ports - RXA,TXA, RXB and
TXB (J100, J101, J102, and J103)
ST® Style (ST is a registered trademark of AT&T).
Supervised.
Fiber optic cable, multi-mode:50/125 or 62.5/125 micrometers.
Fiber optic cable, single-mode:9/125 micrometers.
Attenuation of cabling between two nodes (fiber-optic circuits are point-to-point) must not
exceed the Maximum attenuation, specified below.
To determine attenuation:
1. Find the rated dB loss per foot within the cable manufacturer’s specifications. Determine
the total attenuation between the two nodes due to the cable.
Loss = (loss/ft.) x (length in feet)
2. Establish the dB loss for each connector and splice. Sum all the losses.
3. Total the attenuation factors obtained in steps 1 and 2. This will provide an approximate
attenuation total. The actual attenuation can be measured end-to-end with fiber-optic
industry standard equipment using a test wavelength of 850 nanometers (multi-
mode)/1300 nanometers (single-mode).
The Maximum attenuation:
4.2dB for multi-mode with 50/125 micrometer cable @ 850 nm.
8dB for multi-mode with 62.5/125 micrometer cable @ 850 nm.
5.0dB for single-mode with 9/125 micrometer cable @ 1300 nm.
Refer to the DS-RFM section of the DAA2/DAX manual for information on fiber connections to
the DAA2 and DAX.
Auxiliary Input A (AUX A) - TB 4
Signal strength from low-level analog audio input (such as background music or telephone
paging): 1Vp-p max. Optional supervision through programming.
Recommended wiring: 18AWG, twisted-pair (max. 14 AWG).
Supervision programmable.
Auxiliary input source must be within 20 feet (6.09 m) of the DVC, and in the same room.
Auxiliary Input B (AUX B) - TB14
Signal strength from low-level analog audio input (AMG-style audio): 12Vp-p nominal, 15Vp-p
max. Optional supervision through programming.
Recommended wiring: 14-18 AWG twisted-pair (max. 14 AWG).
Supervision programmable.
Remote Microphone Interface - TB9
Recommended wiring: 14-18 AWG twisted-pair (max. 14 AWG.).
Nominal AC signal strength 2.5VRMS (3VRMS max).
Power-limited.
Supervised.
Max distance between remote microphone and DVC: 1000 ft (300 m).
Push-to-talk Interface - TB10
Dry contact.
Common, non-supervised.
Recommended wiring: 14-18 AWG twisted-pair (max. 14 AWG.).
Alarm Bus - TB12
Power-limited by source.
Non-supervised.
Recommended wiring: 14-18 AWG twisted-pair (max. 14 AWG.).
Requires 16 VDC minimum @ 20mA across the terminals to activate. Nominal 24VDC.
FFT Riser - TB13
Power-limited output.
Max: 15V, 75 mA AC
Supervised.
Class A (Style Z) or Class B (Style Y) operation.
Style Y 2-wire connections require a 3.9k ohm 1/2 watt end-of-line resistor (P/N R-3.9k).
Max. wiring resistance (including individual telephone zone to last handset) permitted is 50
ohms, 10,000 ft. (3048 m) max. wiring distance at 14 AWG to last handset.
Optional DVC-AO Analog Audio Output Circuits - TB5, TB6, TB7 and TB8
Power-limited outputs.
TB12 ALM OUT - NUP Port A NUP Port B TELH-1 Local Phone
Alarm ALM OUT + Connector Connector J8
Refer to ALM IN - J1 J2 Refer to page 36
page 29 Refer to Refer to
ALM IN + page 34
page 34
USB B Connector
(Type B) J4
Refer to page 34 FFT Riser
TB 13
Refer to page 31
USB A Connector
(Mini AB) -J3 + RISER OUT
Refer to page 34 - RISER OUT
TB3 - Digital DAPA REF SHLD RISER OUT
Audio Port A + RISER RTN
Refer to DAPA - - RISER RTN
page 30 DAPA + SHLD RISER RTN
TB2 - Digital DAPB REF
Audio Port B + AUXB TB 14
DAPB - - AUXB Refer to
Refer to
page 30 DAPB + SHLD AUXB page 33
Remote Microphone
NO
Refer to page 35
TB10 - + RMI AUDIO
PUSH-TO-TALK NC - RMI AUDIO
Refer to page 35 COM SHLD RMI AUDIO
TB 9
+ RMI PWR
- RMI PWR
NVRAM lithium battery SHLD RMI PWR
Alignment Dot for + AUXA R
Replacement - AUXA R TB 4
Refer to
+ AUXA L page 33
- AUXA L
TB1 - Power 24V OUT -
Refer to 24V OUT +
page 28 24V IN - MIC-1 LOCAL MIC
24V IN + J5
Refer to page 36
DVC_Bbrd.w
LED 14 USB B
LED 5 PHONE ACT
LED 13 USB A
LED 17 RXA
LED 18 TXA
LED 1 EFA
SW 7 EFA
LED 2 EFB LED 7 AUX B
SW 8 EFB
LED 16 TXB
LED 15 RXB
LED 3 TRBL
LED 6 AUX A
LED 19 RESET
LED 20 PWR
LED 21 - for
DVC_Bbrd.wmf
diagnostics only
LED 8 OUT 1
LED 9 OUT 2
LED 10 OUT 3
LED 11 OUT 4
Figure 1.3 LED Indicator and Switch Locations on Wire Version Boards
TB12 ALM OUT - NUP Port A NUP Port B TELH-1 Local Phone
Alarm ALM OUT + Connector Connector J8
Refer to ALM IN - J1 J2 Refer to page 36
page 29 Refer to Refer to
ALM IN + page 34
page 34
USB B Connector
(Type B) J4 FFT Riser
Refer to page 34 TB 13
Refer to page 31
USB A Connector
(Mini AB) -J3 + RISER OUT
Refer to page 34
- RISER OUT
SHLD RISER OUT
+ RISER RTN
Refer to page 30 for fiber - RISER RTN
Digital Audio Ports A and B SHLD RISER RTN
Digital TXA
Audio + AUXB TB 14
RXA - AUXB Refer to
Port A SHLD AUXB page 33
Remote Microphone
Digital TXB
Refer to page 35
+ RMI AUDIO
Audio - RMI AUDIO
RXB SHLD RMI AUDIO
TB 9
Port B
+ RMI PWR
- RMI PWR
SHLD RMI PWR
TB10 - NO + AUXA R
NC - AUXA R TB 4
PUSH-TO-TALK Refer to
Refer to page 35 COM + AUXA L page 33
- AUXA L
TB1 - Power 24V OUT -
Refer to 24V OUT +
page 28 24V IN - MIC-1 LOCAL MIC
24V IN + J5
Refer to page 36
NVRAM lithium battery
DVC_fBbrd.wmf
Alignment Dot for
Replacement
LED 17 RXA
LED 18 TXA
LED 15 RXB
LED 16 TXB
LED 3 TRBL
LED 6 AUX A
LED 19 RESET
LED 20 PWR
LED 21 - for
diagnostics only
DVCfbrd.wmf
LED 8 OUT 1
LED 9 OUT 2
LED 10 OUT 3
LED 11 OUT 4
Figure 1.5 LED Indicator and Switch Locations on Fiber Version Boards
EFB SW6 Enable/disable Digital Audio Port B earth fault detection. DIS (Disable)
Switch is on wire versions only.
EFA SW7 Enable/disable Digital Audio Port A earth fault detection. DIS (Disable)
Switch is on wire versions only.
1.2.4 Indicators
There are 18 diagnostic LEDs indicating various conditions and troubles. All are located as
indicated in Figure 1.3 on page 16 or Figure 1.5 on page 18.
EFA Yellow Illuminates steadily when an earth fault has been detected at digital audio port DAP A. LED is 1
on wire versions only.
EFB Yellow Illuminates steadily when an earth fault has been detected at digital audio port DAP B. LED is 2
on wire versions only.
TRBL Yellow Illuminates when a trouble occurs. Blinks for an unacknowledged trouble, illuminates steadily 3
for an acknowledged trouble.
AL BUS Red Illuminates steadily while the DVC’s alarm bus input is active. 4
PHONE Green Illuminates steadily while at least one firefighter’s telephone is active on a DAL device riser. 5
ACT
MIC ACT Green Illuminates steadily while push-to-talk is activated on the MIC-1 microphone. 12
RXB Green Illuminated while data is received on Digital Audio Port (DAP) B (wire versions) or RXB (fiber 15
versions). Illumination will flicker, turning on when activity is detected and off when it is not.
TXB Green Illuminated while data is transmitted on Digital Audio Port (DAP) B (wire versions) or TXB (fiber 16
versions). Illumination will flicker, turning on when activity is detected and off when it is not.
RXA Green Illuminated while data is received on Digital Audio Port (DAP) A (wire versions) or RXA (fiber 17
versions). Illumination will flicker, turning on when activity is detected and off when it is not.
TXA Green Illuminated while data is transmitted on Digital Audio Port (DAP) A (wire versions) or TXA (fiber 18
versions). Illumination will flicker, turning on when activity is detected and off when it is not.
POWER Green Illuminates steadily while local 24V from power supply is present. 20
RXA OK Green Illuminates steadily when there is a successful single- or multi-mode fiber connection on the 100
RXA connector. LED is on fiber versions only.
RXB OK Green Illuminates steadily when there is a successful single- or multi-mode fiber connection on the 101
RXB connector. LED is on fiber versions only.
1.3 Options
1.3.1 DVC-AO Analog Output Board Layout
Refer to “Analog Audio Outputs (DVC-AO)” on page 36 for information on wiring these
connections. See Figure 2.3, “Mounting a DVC-AO” on page 24 for information on mounting it
onto a DVC.
DVCAOPCAboard.wmf
TB6 Analog 3 Ret - TB7
Analog 2 Ret -
Analog 2 Ret + Analog 3 Ret SHLD
2.1 Overview
2.1.1 Chassis
All the DVC Series boards will mount in a size B, C or D CAB-4 series cabinet, in either one of the
following chassis assemblies:
• CA-2 - This chassis assembly Half-chassis for Well for MIC-1
occupies two rows of a CAB-4 series NFS2-3030 or microphone
NCA-2. and TELH-1
enclosure. The left side accomodates telephone
a DVC Series board mounted on a handset.
half-chassis and one NFS2-3030 or
CA2chassisassembly.wmf
NCA-2 mounted on a half-chassis.
The right side houses a microphone
Half-chassis for
and handset well. (Refer to DVC board.
Figure 2.1.)
A MIC-1 microphone (not pictured)
is included with the chassis assembly.
A TELH-1 telephone handset may be Figure 2.1 CA-2 Chassis Assembly
ordered separately.
• CA-1 - This chassis occupies one
row of a CAB-4 series enclosure.
The left side accomodates one DVC
Series board, and the right side CA-1 Chassis
houses an optional CMIC-1, which
consists of a MIC-1 microphone and
well.
A CFFT-1 chassis for Firefighter’s
Telephone may be used with the
CA-1 to add an FFT. Refer to
Section 2.8 on page 27 for
CMIC-1
cmic1_in_well.wmf
information on this installation.
ca1_chassis.wmf
microphone
and well
assembly.
Mount the CA-1 or complete CA-2 chassis assembly into the CA-1 or CA-2 Chassis Product Installation Document.
backbox either at this point or after the components have been
installed on the chassis.
Slide chassis component(s) aside for wiring. CA-1 - Section 2.9.1 on page 27
CA-2 - Section 2.9.2 on page 28
Wire and configure the DVC. Sections 2.10, "Wiring" and 3.1, "Setting the Configuration
Switches" in this manual.
2.4 Cabinet
Locate the cabinet backbox on a surface that is in a clean, dry, vibration-free area. The top should
be located so that all operational buttons, switches, displays, etc. are easily accessible and/or
viewable to the operator - usually no more than 66 inches (1.7 m) above the floor. Allow sufficient
clearance around the cabinet for the door to swing freely, and for easy installation and maintenance
of equipment.
Use the four holes in the back surface of the backbox to provide secure mounting. Follow the
instructions below.
1. Mark and pre-drill two holes for the keyhole mounting bolts. Install bolts.
2. Select and punch open the appropriate cabinet knock-outs.
3. Using the keyholes, mount the backbox on the two bolts.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting
holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten
all fasteners securely.
6. Feed wires through appropriate knockouts.
7. Install the Digital Voice Command according to this section before installing the door per
the CAB-4 Series Cabinet Installation Document.
DVCwAOstndoffs.wmf
DVCandAO.wmf
3. Carefully attach the 4. Carefully plug
DVC-AO pin connector the DVC-AO onto
(included, P/N 08580) to the its connector pins.
DVC board at J10.
4. Fasten the
standoffs at the back
3. Carefully plug the of the DVC
DVC-KD onto its board with four
connector pins. The 4-40 KEPS
metal standoffs will nuts (included,
automatically fit into P/N 36045).
CA2dVC_kdstndffs.wmf
their standoff holes
DVCandKDpins.wmf
during this process.
DVC_ALL.wmf
Figure 2.4 Mounting a DVC-KD
Insert the slide-in labels that come with Two blank slide-in labels
the DVC-KD keypad. Install the pre- Pre-printed slide-in for other programmed
labels for functions functions (P/N 52469).
printed labels in the two left slots. There that automatically
are two labels with ALL CALL; one with activate when the
and one without text descriptions of the DVC-KD is installed - Alternate “ALL
P/N 52467 for the CALL” slide-in
bottom three buttons (See Figure 2.5). first (left) column, label (P/N
For single-channel systems where the P/N 52468 for the 52598) for
Digital Voice Command and digital second column. single-channel
audio amplifiers will always play the systems.
same audio message, the three buttons
have no function and the alternate label LAMP TEST POWER
POWER
TROUBLE
ALL
should be inserted. DVC OFF-LINE
MICROPHONE
ALL
CALL
CALL
TROUBLE
PHONE
TROUBLE
BUSY / WAIT PAGE
The two right slots provide for 24 PAGE
INHIBITED
ACTIVE
EVAC
PRE-
ANNOUNCE
AREAS
annunciator-type functions that can be PAGE
ACTIVE
programmed in VeriFire Tools. Once
DVC-KDa.wmf
ALERT
AREAS
CA1NCM_inst.wmf
CA1NCM.wmf
1. Align network communications module over four 2. Fasten with the four 4-40, 1/4” screws (P/N
PEM studs of the CA-1 chassis as indicated. 31834) provided with the module.
CA-2 installations may require that a second network communications module be mounted in the
cabinet; one for the DVC and another for the FACP or network annunciator. This will require
another cabinet row. The network communications module may be mounted on a DAA chassis if
one is installed in the cabinet (see the DAA appendix of the DAA2/DAX manual for details), or it
may be mounted in any chassis that will accommodate it in the cabinet.
of the DVC into the slots at the 2) Fasten with two 4-40, 1/4” screws
DVC_all.wmf
Figure 2.9 Moving the CMIC-1 Chassis Aside for Wiring Access
2.9.2 CA-2
To provide more space around the field-wiring connections, loosen hex nuts and move chassis
components to the side. Each half-chassis slides to the left; the double-well slides to the right.
Figure 2.10 Moving Aside the CA-2 Chassis Components for Wiring Access
2.10 Wiring
2.10.1 DVC Series Board to 24V Power
TB1 IN
+ -
- SLC
from
+ FACP
+
ELR-47K,
ALARM Bus to next DVC
1/2 watt
Alarm Bus requires resistor
16VDC minimum @
20mA across the
DVCALARMtb12.wmf
terminals to activate.
Nominal 24VDC.
DVC
FMM-1.wmf
TB12 TB12
NAC Circuit
A- LIsted compatible
A+ panel or power
supply with onboard
B- NAC circuits.
B+
14-18 AWG twisted-pair
recommended.
terminals to activate.
DVC Nominal 24VDC.
TB12 TB12
Refer to the SLC manual and specific panel or power supply manual for more information.
DAA DAA
REF B REF B
DAP B- DAP B- SHIELD SHIELD
TBgen3.wmf
DVC and
TB3
REF REF
TB3
TB2
DAPA DAPB
NOTE: Digital Audio Ports A and B must be wired in Style 4 or Style 7 configuration. Do not wire
them in bus configuration.
NOTE: Style 4 configuration must be installed in accordance with the requirements for
survivability from attack by fire in the National Fire Alarm Code, NFPA 72.
Refer to “EFA and EFB (Switches 7 and 6)” on page 39, as well as the DAL Devices manual, for
information on enabling earth fault detection on a wire Digital Audio Loop.
TXA DAP A
RXA
TXB
RXB
Fiber DAA DAP B
TXA
RXA
Consult manufacturer’s Fiber DVC
TXB
DVC_F_cx.wmf
guidelines for minimum
radius of bend for fiber RXB
optic media.
NOTE: A fiber DVC will work in a network with DAA2 and DAX amplifiers: it must be connected
to a DAA2 or DAX that has a DS-RFM fiber option module if it is multi-mode, or a DS-SFM fiber
option module if it is single-mode. Refer to the DAA2/DAX manual for information on this
application.
NOTE: Style 4 configuration must be installed in accordance with the requirements for
survivability from attack by fire in the National Fire Alarm Code, NFPA 72.
J5
J4
J7
Spkr1
TB1
XPIQ
1 2 3
Backup OUT Backup IN
J8
J6
J10
Low Level
TRBL SPKR1
P2
P3
P4
P1
P5
Spkr2
TB2
J11
+ OUT - SHLD
1 2 3
Remote Remote
Out
AUDIO IN
AMPLIFIER #4
AMPLIFIER #3
AMPLIFIER #2
AMPLIFIER #1
TRBL SPKR2
In
J12
TB3
Spkr3
+ OUT - SHLD
1 2 3
SW4
23
9 1
456
TB10
0
78
P6
TRBL SPKR3
BCKGND
MUSIC
CONTROL/COMM
12
Spkr4
TB4
+ OUT - SHLD
1 2 3
GEN TBL
Phone 1
PHONE/NAC RISER
SHLD - PH + SHLD - PH +
1 2 3 4 5 6
S - +
1 2 3
TB5
Phone1 TRBL
PHONE
1 AND 2
Phone 2 JP1
SW2
2 X 2W
JP2
S - +
1 2 3
1 X 4W
TB6
Phone 2 TRBL
J13
Phone 3 TB9
PHONE
S - +
1 2 3
3 AND 4
TB7
Phone 3 TRBL
2 X 2W
CHGTRBL
Phone 4 1 X 4W
S - +
1 2 3
SW3
BATTRBL EARTH FAULT
Phone 4 TRBL
TB8
DETECTION
EARTH
SW1
XPIQ-PS Power A.C.Fail EXT TRBL IN FAULT DISABLED
ENABLED
J9
NOTIFIER XPIQ-MBPCA REV.
J2
J1
XPIQ-PS Control Cable
FPJ/RPJ-1
Firefighter’s
Phone Jack
PHONE JACK
FHS Telephone
Control Module
Telephone
Control Module
AFAWS Fire
Alarm Warden
Station
phonehandsetrt.wmf
phonehandset.wmf
DVCFFTriser.wmf
DVC SHLD SHLD
RISER OUT TB13 RISER RTN
Figure 2.16 FFT Riser on DVC Series Board (4-Wire Example)
An FHS firefighter handset may be used with the phone jacks in Figure 2.16. For a description
of the firefighter’s telephone network operation, refer to “FFT Communication” on page 90.
An FFT on this riser may be used for paging locally or to a standard or high-speed Noti-Fire-
Net.
NOTE: Digital audio software Version 2.0 and above does not support FFT risers on first release
DAA boards, which are marked “PCA”. Refer to the DAA appendix of the DAA2/DAX manual for
information on how to determine board type. Check VeriFre or an appropriate network display to
determine the software version. This note does not apply to DAA2 and DAX amplifiers.
DVCAUXAtb4.wmf
DVC AUXA
TB4
Stereo input shown. Monophonic input may
connect to either AUXA R or AUXA L.
Auxiliary Input B
Auxiliary Input B (AUXB) is provided to accept low-level analog audio (AMG-style audio) input
at 12Vp-p nominal, 15Vp-p max. The messages are then transmitted out to speaker circuits as
designated by programming.VeriFire Tools programming determines if signal supervision of
AUXB is enabled.
DVC AUXB
TB 14
NUPcnctr.wmf
DVC at the same time. NUP Connections
NUP Port A or B
(J1 or J2) DVC
NUP cables are included with NCM and HS-NCM modules, with VeriFire Tools, and also with the
DVC.
USB Cable
(Type B)
USB Cable
J3 - USB A
(Mini AB)
Connector
-+
FMM-1*
DVCPTTtb10.wmf
ELR-47K
FMMtpHa.wmf
appropriate non-fire Type ID code
per the FACP manual.
*If the SLC device does not match the one in this figure, refer to
DVC PTT the SLC manual appendix, which contains wiring conversion charts
for type V and type H modules.
TB 10
R-47K ohm
resistor
DVCRMItb9.wmf
RM1board.wmf
DVC RMI
TB 9
RM-1 board
Figure 2.22 RM-1 to DVC Connections
See the RM-1 Series document for more information on this product. Refer only to single-
microphone applications: multiples (e.g. daisy-chaining) are not compatible with the DVC.
DVCtoCMICcxj5.wmf
MIC-1 microphone, which provides the
DVC with paging capabilities. The DVC MIC-1 Cable
microphone connection will be monitored Local Mic
for continuity when MIC-1 is enabled in J5
VeriFire Tools.
Figure 2.23 MIC-1 Microphone Interface
DVCLocalPhoneJ8.wmf
riser, and gives the DVC paging
capabilities (selectable from the DVC-KD DVC
and utilization of the phone’s push-to-talk Local
button). The TELH-1 will be supervised Phone
for short or open circuit conditions when J8
“Local FFT” is selected in VeriFire Tools.
Figure 2.24 TELH-1 Telephone Interface
TB1 CH2
TB2 TB3
CH1 CH3
XPIQ
AIB-4
Low-level analog audio to AA-Series audio amplifier
XPIQAIB4terminals.wmf
DVCAOapp.wmf
XPIQAIB4.wmf
DVC-AO Outputs 1 - 4
S+ - S+ -
AA-30.wmf
Low-level Low-level AA-Series
audio IN audio RET audio amplifier terminals
ACT-4 ACT-4
TB1 TB1
P1 P1
DVC_AOact4.wmf
P3 P3
DVC-AO
AA-100/AA-100E* AA-30/AA-30E
or AA-120/AA-120E
*The ACT-4 is not ULC approved for use with AA-100/E amplifiers.
DVCpiezoenabl.wmf
factory enabled. It will sound during a DVC trouble
event, and may be acknowledged at a network
workstation, NCA-2, or an NFS2-3030 or NFS2-640
that is not on Noti-Fire-Net. However, it will resound if
another trouble event occurs within the DVC.
To disable, push the switch towards DIS.
The piezo can be disabled or enabled using SW5.
Disabling the piezo causes a trouble to be sent to the Figure 3.1 Piezo Enable/Disable
panel or network annunciator.
DVCdfABenabl.wmf
require resetting if earth fault detection is desired. (Refer
to Figure 3.2).
Each DAP on a DVC wire board is electrically isolated
from the other DAP and all other circuitry on that board.
A DAP with its associated earth fault switch enabled must
To disable, push the switch towards DIS.
be connected to a DAP with its associated earth fault
switch disabled for detection to occur. Otherwise, either Figure 3.2 EFA/EFB EN/DIS
• no detection will occur (when two connected
DAPs have their associated switches disabled), or
• an earth fault will be generated (when two connected DAPs have their associated switches
enabled).
Refer to Figure 3.3.
Twisted-pair wire
EFA EN
EFA EN
EFA EN
EFB DIS
EFB DIS
EFB DIS
EFB DIS
DAPB
NOTE: Refer to Appendix A, “DAL Earth Fault Detection” for information on earth fault detection
when a DAA2 or DAX is present on a DAL. Only DAP A is isolated on these devices.
Figure 3.3 Earth Fault Switch Settings for a Wire DVC with DAAs
Following are general descriptions of VeriFire Tools programming required for DVC operation.
NOTE: The DVC node number is assigned at the beginning of the VeriFire Tools session when
the database is opened. The DVC must always be assigned a unique node address, even when
used with a standalone FACP. That is, when used with a standalone FACP, the DVC must be
assigned a node number different from that FACP.
General I
DVCprogGEN I.jpg
Figure 3.5 DVC System Programming Service – General I
DVC Label
Enter the network node label for this DVC. You may enter up to 40 characters.
Common Settings
LOCAL CONTROL - Select to enable local DVC control of the following DVC-KD keys: ALL CALL,
PAGE ACTIVE EVAC AREAS, PAGE ACTIVE ALERT AREAS, PAGE INACTIVE AREAS, and
ENABLE TELEPHONE PAGE.
ANALOG OUTPUTS - Describe the configuration (“Not Installed”, “Installed, Class A,” or “Installed,
Class B”) of DVC’s analog outputs. Requires DVC-AO. “Installed” analog outputs will be represented in the
PAM as output circuits for DVC-0. (PAM programming is described in “Prioritized Audio Matrix (PAM)
Programming” on page 61.)
LOCAL/REMOTE MICROPHONE - Select to install the local and/or remote microphone.
See the RM-1 Series document for more information on the remote microphone.
DVC MODEL - Choose from the drop-down menu to indicate if the DVC is the standard (DVC) or an
extended memory (DVC-EM) version. The DVC-EM Extended Memory versions contain up to 32
minutes of standard quality (11.025 kHz sampling rate, 8 bit µ-law, mono) audio storage, or 4 minutes of
high quality (44.1 kHz sampling rate, 16 bit PCM, mono).
FIDELITY SELECTION - Choose the desired audio quality (standard or high). A message saved as high
quality requires more storage space than the same message saved as standard quality.
NOTE: Enable automatic gain control only in applications where the input is a voice input, such
as from a telephone paging system. Do not enable automatic gain control when using background
music.
BACKGROUND MUSIC - Check if the input is to be used for background music. Background music
will be disabled during AC Fail and will not play out of a DAA or DAA-2 that has a battery charge
rate greater than 1 amp (Battery size is greater than 26 AH and batteries are in need of a charge).
NFN Media Interface Settings
Set Port A and Port B thresholds for HIGH or LOW to establish tolerable noise thresholds for
network communications. Not applicable for high-speed NotiFireNets.
WIRING STYLE - Select according to your network’s configuration (STYLE 4 or STYLE 7). Refer to
the standard or high-speed NotiFireNet manual for more information.
PROGRAM - This button will save your changes to the VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
General II
DVCprogGEN II.jpg
Program Settings
Check the node numbers to set up for ALL CALL or SPECIAL PAGING FUNCTIONS paging at
the selected nodes. Nodes should be other DVCs or a panel with an XPIQ or SLC speaker points.
SPECIAL PAGING FUNCTIONS is comprised of the settings for the DVC-KD buttons PAGE
ACTIVE EVAC AREAS, PAGE ACTIVE ALERT AREAS, and PAGE INACTIVE AREAS. In
multi-channel applications (where audio message sequences are saved in standard fidelity format),
these pages are designed to override the message sequence types they describe (EVAC or ALERT
messages that are active), or to page to areas where no messages are active. In single-channel
applications (where audio message sequences are saved in high fidelity format), these pages are not
operative and the column will be grayed out.
Starting with VeriFire Tools 6.0, alarm bus programming is performed using logic equations. The
“Alarm Bus Maps” column no longer appears on this screen. Refer to “Logic Equation Builder” on
page 59.
PROGRAM - This button will save your changes to the VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
General III
DVCprogGEN III.jpg
Defines whether the DVC will participate in DCC operation for paging functions, and if so, which network
control node it will be associated with. See Section 4.3, “Display and Control Center (DCC)”.
DCC OPERATION - Check to enable DCC participation.
DCC ASSOCIATED NODE NUMBER - Map a DCC-designated DVC to a network control node through
which it will be able to assert network control for network paging purposes.
Canadian Operations
Pre-Announce - To enable the Pre-Announce feature, click Pre-Announce, then select an audio
sequence. The selected sequence will play before all pages from the DVC’s MIC-1 local
microphone, the TELH-1 local telephone, and the RM-1. The “Pre-Announce” LED on the
DVC-KD will light for the duration of the pre-announce.
PAGE INHIBIT - The Page Inhibit selection applies to the ALL CALL, PAGE ACTIVE EVAC
AREAS, PAGE ACTIVE ALERT AREAS, and PAGE INACTIVE AREAS buttons on the
DVC-KD. To enable, check the box and select a logic equation that will inhibit the page while the
logic equation is active. The “Page Inhibit” LED on the DVC-KD will light for the duration of the
page inhibit.
DVC-KD INHIBIT - The DVC-KD Inhibit selection applies to the 24 buttons on the right half of the
DVC-KD. To enable, check the box and select a logic equation that inhibit the DVC-KD while the
logic equation is active.
COMMON SETTINGS
NFN AUDIO PAGING - Check this box if network paging from any of the DVC’s live inputs to
outputs on other DVCs is desired. Live inputs can include the DVC’s local microphone, an RM-1
remote microphone, a firefighter’s telephone, or a live input from an AUXA or AUXB connection.
A check here creates the “Network” column in the PAM. (See “Prioritized Audio Matrix (PAM)
Programming” on page 61.) If this box is not checked, network paging is disabled.
NOTE: For a standard Noti-Fire-Net, the number of nodes allowed is limited to 54 when NFN
Audio Paging is selected. This limitation does not apply to a high-speed Noti-Fire-Net.
NOTE: Use of the IP Accessibility feature is subject to the approval of the local AHJ.
PROGRAM - This button will save your changes to the VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
DAL Mapping
Map DAL devices to DAL addresses with this screen. Once mapping has been completed, click on
an amplifier’s button to call up the the associated DAL device screen (page 49). A DAL device
must be programmed into the system here before VeriFire Tools will allow configuration of its
individual speakers circuits.
AMP 1 THROUGH AMP 32 - Click on the AMP button to select the DAL device being addressed from
the pull-down menu.
PROGRAM - This button will save your changes to the VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
DVC-KD
Program the user-defined keys on the DVC-KD. Map a function to a node, module, detector, panel
circuit point, zone, or PAM point.
DVCprogsvc DVC-KD.jpg
Explanation of Fields:
KEY -There are 24 user-defined keys on a DVC-KD. Refer to Figure 4.1 on page 68 for the
numbering format.
FUNCTION - Select from Monitor, Control, Telephone, All Call, Page Evac, Page Alert, Page
Inactive, Enable Paging, FFT-NFN, Disable, or None.
• Select Telephone for the following:
• when mapping to a telephone control module.
• when mapping to a DAL device FFT riser that has no telephone control modules (Use
the address NxxxAyyT, where N = node number, yy = the DAL device address [1 - 32]).
• Select All Call to broadcast to entire nodes.
• When Enable Paging is selected, AUX A or AUX B will be selectable.
• Select FFT-NFN to broadcast from a firefighter telephone over Noti•FireNet.
• Enter the two DVC nodes plus telephone control module “Nxxx,Nxxx,NxxxLxxMxxx”).
• When mapping to a DAL device FFT that has no installed telephone control modules,
use the address Nxxx,Nxxx,NxxxAyyT, where N = node number, yy = the DAA addresss
(1-32). Refer to Appendix B.2.2, “Point-to-point FFT Communication over Noti-Fire-Net
(FFT-NFN)”, on page 78 for more explanation.
• Select Disable to create a button that will disable a single local or network DAL device
speaker circuit point, or all the speaker circuits on a DAL device. Use the following
addresses
AyySz for a single local speaker circuit point.
NxxxAyySz for a single network speaker circuit point.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
DVC General Zones
Customize a DVC general zone label using the following screen. See Section 3.4 on page 66 for
information on programming DVC general zones.
DVCprogGEN ZONES.jpg
General I
AMPLIFIER ADDRESS - Select the installed amplifier to be programmed. The DAL Device Type
chosen at the DAL Mapping screen ( “DAL Mapping” on page 46) will display next to the
amplifier address selected.
Amplifier Settings
AMPLIFIER MODE – Select PRIMARY or BACKUP from the pull-down menu.
BDA CARD MODE – Select NOT INSTALLED, DUAL CHANNEL, or BACKUP from the pull-down menu.
BACKUP AMPLIFIER ADDRESS – Select the backup amplifier address, or NO BACKUP, from the pull-
down menu. Only backup amplifiers with matching BDA, speaker, group and riser mode settings
will be available.
Firefighter Telephone Settings:
These fields do not display for DAA PCA boards or DAX boards.
FFT RISER WIRE SELECTION –
• For DAA amplifiers - Select the wiring style (INSTALLED 2 WIRE or INSTALLED 4 WIRE)
according to the configuration of the analog network. Select UNINSTALLED when the FFT
riser is not installed.
• For DAA2 - Select INSTALLED or UNINSTALLED to indicate if there is a riser or not.
INSTALL FTM MODULES – Check this box if there are FTMs installed on the FFT riser with its
firefighter telephones. When this box is not checked, the address NxxxAyyT - where N = node
number, yy = the DAL device address (1 - 32) - can be used for FFT for mapping.
Auxiliary Input Source
These fields do not display for DAX boards.
AUXILIARY A – Check to install the AUXA analog input into the database.
AGC – Check to enable automatic gain control. This feature will smooth an incoming signal to
produce a consistent sound.
NOTE: Enable automatic gain control only in applications where the input is a voice input, such as
from a telephone paging system. Do not enable automatic gain control when using background music.
AUXILIARY ACTIVATION – Check which speaker circuits on the amplifier will be activated when
amplifying data from the AUX input.
MODIFY - This button will save your changes to the VeriFire Tools database.
DEFAULT - This button will restore all programmable options on this worksheet to their defaults.
NEXT and PRIOR - These buttons allow you to step through the amplifiers programmed in the
VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved,
VeriFire Tools will prompt you to do so.
General II
AMPLIFIER ADDRESS - Select the installed amplifier to be programmed. The DAL Device Type
chosen at the DAL Mapping screen (“DAL Mapping” on page 46) will display next to the amplifier
address selected.
Speaker Settings
SPEAKER RISER MODE -A DAL device can have only one Riser Mode type: the riser mode type
chosen will be applied to all speaker circuits on the DAL device. Backup amplifiers must be
programmed with the same riser mode type as the primary amplifiers. Select from the following
DAL device Riser Mode types:
• NORMAL - Select NORMAL when the DAL device will not be used for riser or room isolator
applications.
• RISER TO ADDITIONAL AMPLIFIERS - Select when the DAL device’s output will be used with
one or more audio coupling transformers to drive additional amplifiers. (ACT-70 for 70V
amplifiers, ACT-25 for 25V Amps.) This selection provides a 200 Hz tone that is required
for additional analog amplifiers. Refer to the DAA2/DAX manual.
• RISER TO ADDITIONAL CONTROL MODULES - Select when the DAL device’s output will be
routed to multiple speaker circuits using control modules. In this mode, the DAL device will
provide speaker circuit supervision only when idle. Only one DAL device speaker circuit
may be installed when operating in this mode. Do not use background music on the DAL
device in this mode. Refer to the DAA2/DAX manual.
• RSM OR AIM SERIES ROOM ISOLATORS - Select when connecting these modules to the DAL
device’s speaker circuits. Only oneDAL device speaker circuit may be installed when
operating in this mode. Refer to the DAA2/DAX manual.
• CIM OR CSM SERIES ROOM ISOLATORS - Select when connecting these modules to the DAL
device’s speaker circuits. Only one DAL device speaker circuit may be installed when
operating in this mode. Do not use background music on the DAL device in this mode.
Refer to the DAA2/DAX manual.
Refer to the DAA2/DAX manual for wiring illustrations.
SPEAKER WIRING CONFIGURATION – Make selection to program speaker circuit pairs (1/2 and 3/4.)
Selection must reflect physical configuration (All Class A; All Class B; 1 and 2 = Class A, 3 and 4
= Class B; 1 and 2 = Class B, 3 and 4 = Class A).
DISABLE CHARGER - Check to disable the charger on this DAL device. The charger should be disabled if
this DAL device is sharing batteries with at least one other DAL device, and is not the DAL device that
will supply the battery charging. See the battery sharing section for the appropriate device.
MODIFY - This button will save your changes to the VeriFire Tools database.
DEFAULT - This button will restore all programmable options to their defaults.
NEXT and PRIOR - These buttons allow you to step through the amplifiers programmed in the
VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved,
VeriFire Tools will prompt you to do so.
Group Settings
Groups consist of a collection of speaker circuits on a DAA2 with one or more amplifiers assigned
to it. Refer to Appendix D, “Audio Groups”, on page 86 for more information.
AMPLIFIER GROUP - Select the group number for the digital amplifier.
BDA GROUP - Select the group number for the BDA amplifier.
RM-1 Settings
INSTALL RM-1 - Check this box to activate the circuit for supervision.
SEND RM-1 AUDIO TO DVC - Check this box to make the audio available as a source to the I1038
PAM row. The first DAA2 with an active push-to-talk (PTT) will be the source. Once the PTT is
released, the next active PTT will become the source of the audio. Any DAA2’s RM-1 audio takes
priority over the DVC RM-1 audio.
LOCAL RM-1 MODE - This setting will adjust the priority of the RM-1 to its own DAA2.
• Override DVC audio to all speakers - Select to make the local RM-1 the highest priority
audio source for that DAA2.
• Override DVC background music to all speakers - Select to give the RM-1 priority over
background music only.
• Let DVC control RM-1 routing - With this selection, the RM-1 will not perform any local
paging, and the DVC PAM is needed to control where the RM-1 audio is routed.
If the DAA2 loses communication with the DVC, the local RM-1 will take priority over the
non-emergency and emergency tones.
Speaker Circuits
Damp SpkrcktsS.jpg
EXTENDED – Enter up to an additional 12 characters for more specific identification of the speaker circuit.
The total number of installed speaker circuits on the selected DAL device is listed on the lower
right hand side of the service form.
Group Settings
Groups consist of a collection of speaker circuits on a DAA2 with one or more amplifiers assigned
to it. Refer to Appendix D, “Audio Groups”, on page 86 for more information
GROUP NUMBER – Select the group number for this speaker circuit.
MODIFY - This button will save your changes to the VeriFire Tools database.
UNINSTALL - This button will delete that speaker circuit from the VeriFire Tools database.
NEXT and PRIOR - These buttons allow you to step through the speaker circuits programmed in the
VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved ,
VeriFire Tools will prompt you to do so.
NOTE: The CD booklet included with the VeriFire Tools CD outlines the equipment requirements
for creating a sound library. Use the equipment recommended in this booklet.
VeriFire Tools uses a “drag and drop” interface to easily sequence the sounds.
Message Segments
Message segments are sound files that can be used as part of a message sequence. The number of
message segments that may be stored is relative to their size, fidelity, and the DVC board used
(DVC or DVC-EM/F/SF).
Use the Message Segment form illustrated in Figure 3.14 to select and catalog the sound files that
will be used.
NOTE: The digital audio system uses files in specific .wav formats as described below.
Mess_SegBW.jpg
• AUDIO TYPE - Fidelity and storage capacity based on the fidelity selection and board type at the
first DVC form (See “Common Settings” on page 41) is displayed as a reminder in the AUDIO
TYPE field at the top of the form.
• OPEN EXPLORER - Click this button to open the Windows Explorer. Import sound files into the
segment library by dragging and dropping them from your PC. When a file is entered into the
library it is assigned a segment number. The segment library may contain up to 1000 message
segments.
NOTE: Sound files used as message segments must be accessible when downloading to a
DVC.
• They must be consistently mapped - that is, the path must remain unchanged if a database is
exported onto another PC.
• When accessed from external devices such as a CD drive, copy audio files onto your PC’s hard
drive, or always ensure that external media containing these files is in the drive when
downloading to the DVC.
• Total duration time will display in the top right corner of the service form. Specific message
segment lengths are displayed in the Available Message Segments section of the Message
Sequences screen. (See Figure 3.15 on page 55)
Use the arrow keys to the right to re-assign a file’s segment number.
• Click the OPEN AUDIO EDITOR button to open the Goldwave sound editor. Create and/or edit
sound files with this software program.
• Listen to a selected .wav file by clicking on PLAY SELECTION button at the bottom of the
service.
PROGRAM - This button will save your changes to the VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
Message Sequences
Build audio message sequences by combining message segments and sequence commands.
The Sequence
(“1” in this
example) displays
in the # field in the
Audio Sequences
selection.
Mess_SequenceBW.jpg
NOTE: Only ALERT and EVAC may be used when a DVC with DVC-AO is directly connected to
an NFS2-640 panel.
2. Type a 20-character description of the audio sequence in the LABEL field, if desired.
3. Drag and drop message segments and sequence commands into the SEQUENCE: field.
Segments may be grouped together and the group or individual segment may be played up to
14 times. An individual segment or group may also be commanded to play forever.
NOTE: For public mode signaling, messages activated during fire events must repeat
indefinitely (the PLAY FOREVER command must be used).
For private mode signaling, fire alarm messages may be of finite length (the PLAY X TIMES
command may be used), but they must then be assigned the “OTHER” category.
Security, supervisory, trouble, all finite-length messages, and all messages not activated by fire
events must be assigned “OTHER” in VeriFire Tools.
Each PLAY... command (PLAY X TIMES, PLAY FOREVER) must be completed with an END PLAY
command. Segments without a PLAY.../END PLAY command will play only once. Note that the
PLAY... and END PLAY commands are comparable to open (PLAY X TIMES, PLAY FOREVER) and
closed (END PLAY) brackets of a logic equation.
Sequences may be nested, as shown in Figure 3.16.
1. Play Forever
The AbortOn.wav 2. Play 3 Times
Sequences A file will play 3 Sequence A 3. AbortON.wav
and B will times and stop. 4. End Play
play forever. The ACFail.wav 5. Play 3 Times
file will play 3 Sequence B 6. ACFail.wav
times and stop. 7. End Play
8. End Play
PLAY SEQUENCE - Click this button to listen to and review the sequence as a test. During this test,
the PLAY FOREVER command will only play 200 times. When this sequence is activated in a non-test
situation, PLAY FOREVER will play indefinitely.
PROGRAM - This button will save your changes to the VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
Inputs
Each input source, live or recorded, is assigned a fixed input number and a programmable priority
number. (See Table 3.1 on page 58.) Use the Inputs service to program each input’s priority. The
lower the priority number, the higher the priority.
DVC_AudioMsgFFT.jpg
This screen will also display a fixed input number column to the left of the Priority column. To
view this column, place the cursor on the column wall left of the priority column and pull it out.
RENUMBER - Click the button to sequentially reassign priorities to the all inputs.
RESTORE DEFAULTS - Click this button to re-apply default priorities to all inputs. See Table 3.1 on
page 58 for defaults.
PROGRAM - This button will save your changes to the VeriFire Tools database.
CLOSE - This button will close the current service. If there are changes that have not been saved (by
pressing the PROGRAM button), VeriFire Tools will prompt you to do so.
3 – 15 RESERVED —
18 – 30 RESERVED —
31 Message Sequence 1 31
32 Message Sequence 2 32
• • •
• • •
• • •
1034 RESERVED —
1036 RESERVED —
* Local Microphone Page will always take priority over Local Telephone Page.
DVC3logeq.wmf
The Logic Equation Builder is an easy way to enter logic equations for the audio system. Use the "point and
click" method to select all available operators and operands and view your work as you build the equation
in the window at the top of the screen. Use the Program Validation Service to check your work.
The Edit Section
UNDO - This button will undo the last function that was executed. You can press the UNDO button
until the entire entered equation is erased.
REDO - This button will reverse the action of the UNDO button. The REDO button can be pressed
until the entire function is recovered.
ERASE - This button will clear the current equation so that a new equation can be entered. Once the
ERASE button is pressed, both the UNDO and REDO button will become unavailable.
COPY and PASTE - These buttons can be used to copy an equation in whole or in part and paste it
into another logic zone.
LABEL - Use this field to enter a label (up to 100 characters) for the logic equation. Labels are
accessible by viewing the database using VeriFire Tools.
The Functions Section
The Functions section lists the available operators to use. For every step that can be performed, the
available choices will be left enabled, while unavailable options will be grayed out. Following is a
description of each function. Refer to the VeriFire Tools help file for more information.
AND - Requires that each argument be active.
NOT - Inverts the state of the argument (activated to deactivated OR deactivated to activated).
ONLY1 - Requires that only one argument be active.
ANYX - Requires that the amount of arguments specified by the number preceding the arguments be
active.
TBL - Requires the system trouble(s) listed to activate.
SDEL - A latched version of the DEL function. Once the equation evaluates true, it remains
activated until a reset, even if the internal equation becomes false.
TIM - The TIM function specifies activation on specific days of the week or year.
RANGE - Each argument within the range must conform to the requirements of the governing
function. The range limit is 20 consecutive arguments.
) - Closes a logic equation.
CLEAR - Clicking this button will delete the selected equation from the database.
NEXT and PRIOR - Clicking these buttons cycle through the equations.
REFRESH - Clicking this button will restore the current logic equation from the database.
SPREADSHEET - Clicking this button displays the Logic Equation Spreadsheet in a separate screen.
CLOSE - This button will close the current service. If there are changes that have not been saved,
VeriFire Tools will prompt you to do so.
Outputs are Example: Output circuit for DAA 4 S3 Column. The darkened cell in the column is a PAM point in the row
represented by designated Input 31, and has a PAM point address of I31A4S3. When Logic Equation 3 (the “3” that is in
columns. the darkened cell) is activated, Input 31 will broadcast Sequence 1 on this output. This output can also be
activated by other PAM points in its column.
NEW_PAM_PTsBW.jpg
Inputs are
represented
by rows.
Example: Input
31 Row. The
selected cell in
the row is a
PAM point.
When Logic
Equation 3 is
activated,
Speaker Circuit
3 on the DAA at
Address 4 will
broadcast
Sequence 1.
Control-by-event
1 Z103 3
2 4
PAM point
DVC General Zone Programming - activation
Refer to “Programming DVC General programming
Zones” on page 66. options
PAM point
address
Network Paging
When “NFN Audio Paging” is selected in the DVC System Programming Service (see page 45),
the DVC is configured to send live audio to a standard or high-speed Noti-Fire-Net for audible
output by other DVCs on the network. The live audio present on the network can be used as input
audio by another DVC on Noti-Fire-Net, and may be played on any output circuit on that DVC.
Inputs designated as “Local” in the PAM of the source DVC become “Network” inputs of the same
type in the PAM of all other network DVCs. (See Table 3.2.)
Input Name on Source DVC Input Name on Other Network DVC
Local Mic Network Mic
Local Tel Network Tel
Local RM-1 Network RM-1
Local Aux B Network Aux B
Local Aux A Network Aux A
The message will be sent to the target output(s) through the PAM’s Network RM-1 Input
(1039).
to ALL CALL outputs at this DVC node
Message Overrides
When a PAM point is activated, its input will broadcast on its output. If more than one PAM point
activates for a particular output, the PAM point with the highest priority input will play first, and it
will pre-empt active messages of lesser priority. The pre-empted message will be set to either
pending or turned off, as shown in Table 3.3 below.
Live - an input that was not created by Audio Sequence programming (that is, paging, telephone
communication).
Evac, Alert, Other - Message type assigned to an audio sequence through Audio Sequence
programming.
Pending - means the new input will pre-empt the active input, but will allow that input to resume
its broadcasting once the new input has completed its broadcast.
OFF - means the new input will pre-empt the active input, and will turn it off.
Example:
A live page with a priority of one (1) occurs while an “Evac” message, initiated by a logic equation,
is broadcasting. The live input has a higher priority than the “Evac” message. Table 3.3 shows that
the new live message will cause the “Evac” message to be placed in a pending state. (The table cell
where the “Live” row intersects with the “Evac, PAM point turned on by logic equation” column
says “Pending”.) The “Evac” message will resume once the live page is completed.
This field determines whether the user can manually silence a PAM point. Based on the value
chosen from the list below, a Signal Silence command at a network annunciator, or at a single-panel
NFS2-640 or NFS2-3030 directly connected to a DVC, will silence a PAM point, as described in
Table 3.4.
NO Not manually silenceable
YES w/RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES w/RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
YES w/RESOUND SECURITY Silenceable, resound on security event Network and Local Resound
YES w/RESOUND TROUBLE Silenceable, resound on local DVC trouble event Network and Local Resound
SWITCH INHIBIT – When this selection is enabled, the PAM point will disregard any ACS control.
3.3.6 Reports
Printed reports can be generated from VeriFire Tools. The selections can be viewed from the drop-
down Reports Menu on the menu bar. The reports include the following:
• SYSTEM - Includes the information entered in th DVC System Programming Service
screens.
• DAAS - Includes the information entered in the DAA/DAA2/DAX Amplifier Programming
screens.
• AUDIO MESSAGE - Includes the information entered in the Audio Message Programming
Service screens.
• PAM - Includes the information entered in the PAM Programming Service screens.
• LOGIC EQUATIONS - Lists all logic equations.
• Compare Nodes - Compares two DVC nodes with the same database version.
SAVE - Click this button to save the validation results to an HTML file.
LAMP TEST
POWER PAGE
FRONT DESK
TROUBLE PAGE 2nd
ALL FLOOR
DVC OFF-LINE
CALL MUSIC to
MICROPHONE AUDITORIUM
TROUBLE
PHONE REMOTE
TROUBLE MIC
BUSY / WAIT PAGE FFT
ACTIVE CAFETERIA
PRE-ANNOUNCE EVAC FFT
EAST WING
AREAS
PAGE
ACTIVE
ALERT
AREAS
ENABLE
TELEPHONE PAGE
PAGE
DVC-KDa.wmf
INACTIVE
AREAS
NOTE: The ALL CALL, PAGE ACTIVE EVAC AREAS, PAGE ACTIVE ALERT AREAS, and
PAGE INACTIVE AREAS buttons will function only when “Local Control” has been selected in
VeriFire Tools programming.
NOTE: A local microphone page, initiated at the DVC’s MIC-1, will pre-empt a local telephone
page from the DVC’s TELH-1 or an FFT on the DVC or a DAL device riser.
ALL CALL
Press this button to initiate ALL CALL paging. DVC nodes that will receive the ALL CALL
message are determined by VeriFire Tools programming. The green “active” LED will light if
any of the mapped nodes are online. When one or more nodes are off-line, the yellow “trouble”
LED will blink. If both the green and yellow LEDs are lit, paging can still proceed,
broadcasting to all mapped nodes that are online.
PAGE ACTIVE EVAC AREAS
Press this button to initiate paging to active evacuation areas. Nodes that will receive the PAGE
ACTIVE EVAC AREAS message are determined by VeriFire Tools programming. The green
“active” LED will light if any of the mapped nodes are online. When one or more nodes are
off-line, the yellow “trouble” LED will blink. If both the green and yellow LEDs are lit, paging
can still proceed, broadcasting to all mapped nodes that are online.
PAGE ACTIVE ALERT AREAS
Press this button to initiate paging to active alert areas. Nodes that will receive the PAGE
ACTIVE ALERT AREAS message are determined by VeriFire Tools programming. The green
“active” LED will light if any of the mapped nodes are online. When one or more nodes are
off-line, the yellow “trouble” LED will blink. If both the green and yellow LEDs are lit, paging
can still proceed, broadcasting to all mapped nodes that are online.
PAGE INACTIVE AREAS
Press this button to initiate paging to inactive areas. Nodes that will receive the PAGE
INACTIVE AREAS message are determined by VeriFire Tools programming. The green
“active” LED will light if any of the mapped nodes are online. When one or more nodes are
off-line, the yellow “trouble” LED will blink. If both the green and yellow LEDs are lit, paging
can still proceed, broadcasting to all mapped nodes that are online.
Page Inhibited - Another node has assumed paging control and locked out paging from this DVC.
This occurs when the DVC requests paging permission over a standard or high-speed Noti-
Fire-Net from the DCC node, and the DCC has not granted it. Also illuminates when the Page
Inhibit feature is active.
Pre-Announce - Illuminates while the pre-announce sequence is playing before paging from the
DVC’s MIC-1 local microphone.
4.2 Paging
The MIC-1 microphone, TELH-1 telephone handset, RM-1 remote microphone, and AUXA and
AUXB inputs can perform paging operations to their local DVC or across a standard or high-speed
Noti-Fire-Net to another DVC.
FFTs on the DVC/DAL device FFT risers can perform paging operations to the DVC node or the
network.
NOTE: The DVC-KD Microphone Trouble LED will illuminate if paging is initiated but there is no
activity for 28 seconds.
8. Press the ENABLE TELEPHONE PAGE button to disengage the ALL CALL function. The
green LEDs at the ALL CALL and ENABLE TELEPHONE PAGE buttons will turn off.
NOTE: The DVC-KD Telephone Trouble LED will illuminate if paging is initiated but there is no
activity for 28 seconds.
5. To end the page, release the push-to-talk button and press the paging function button (not the
ENABLE PAGING button) to deactivate. The annunciator LED(s) will turn off.
NOTE: A DAX-50 does not have general earth fault detection. The device charging the
DAX-50’s batteries must have earth fault detection enabled, to provide earth fault notification for
the DAX-50.
When devices are sharing batteries, only one device in the sharing set may have its earth fault
switch enabled or its JP2 jumper left intact. If an earth fault occurs anywhere on the DAL segments
in the set, an earth fault error will generate for the device with its switch enabled or its jumper
intact. Refer to the battery sharing sections of each device for more information on wiring this
configuration.
Refer to Figure A.1 on page 75 for an illustration.
EFS = Disable
DAP DAP DAP B This DAX shares
B DAP DAP
A A B batteries with two
DAP A other DAL devices.
Because the EFS is
set to disable, it does
DAA2 DAA2 DAA2 not monitor for earth
faults.
EFS = Enable EFS = Enable
This DAA2 monitors for • The DAX that checks
earth faults on DAL for earth faults in the
Section 9. It generates battery-sharing set
general earth fault monitors for earth faults
errors for its address. on DAL Section 7.
• DAL Section 8 is fiber
and does not generate
earth fault errors.
*DAX-50s do not have general earth fault detection. Earth fault detection must be provided by
what is charging the DAX-50’s batteries.
FFT handsets, so 35 handsets may be active within the network at the same time. If this number is
exceeded, a short circuit trouble will be generated by the DVC; however, FFT communications will
continue.
NOTE: The FFT riser on the DVC is always one of the five active risers. Four FFT risers can be
active on digital audio amplifiers at the same time.
NOTE: An active RM-1 remote microphone on a DAA2 will take up one of the five FFT riser
channels, and will take priority over local FFT communication. Refer to “RM-1 Settings” on
page 51 for more information.
NOTE: The DVC’s TELH-1 connection (J8) always counts as one of the seven active FFT
handsets on the DVC, whether there is a TELH-1 handset connected to it or not.
Figure B.1 and the text that follows gives an example of how activated analog FFT risers interact
with the DAL.
E D
A B
FFT analog riser
C
FFT analog riser
phonehandsetrt.wmf
phonehandset.wmf
Digital Audio Loop (DAL)
DVC
DAP A
Optional Style 7 return
DAP B
1. A firefighter at DAA2 1 activates a handset (A) on the analog FFT riser by lifting the receiver
or plugging in a phone jack. An operator at the DVC grants the firefighter a connection.
• (A) will be able to communicate with other phones that activate on the DAA2 1 analog FFT
riser.
• (A) will automatically be granted a Digital Audio Loop (DAL) connection.
[ 1 (DAA2 1) analog riser + 1 (DVC) analog riser = 2 risers interconnected on the DAL.]
2. Subsequently, firefighters at DAA2 14 (B), DAA2 24 (C), and DAA2 32 (D) activate handsets
and are granted connections by the operator.
• (B), (C), and (D) will be able to communicate with other phones on their respective FFT
analog risers.
• (B), (C), and (D) will automatically be granted DAL connections.
[4 (DAA2 1, 14, 24 and 32) analog risers +1 (DVC) analog riser = 5 risers - the maximum allowed -
interconnected on the DAL.]
3. A firefighter at DAA2 16 activates a handset (E) and is granted a connection by the operator.
• (E) will hear a ring tone on his handset.
• (E) will be placed in a queue for the next available connection, because the maximum of
five risers on the DAL has already been reached. (E) will hear the ring tone until either (A),
(B), (C), or (D) is disconnected by the operator.
Example 1
Refer to Figures B.2 and B.3 for this example.
A call initiated at an FFT (C) on a DVC node can be answered at another DVC (A). This will
require turning on two communication links:
1. the link between the FFT (C) and its DVC (B), and
2. the link between DVC (A) and DVC (B) (the FFT-NFN link on a standard or high-speed
Noti-Fire-Net).
FFT riser
C
N1L1M2
One DVC-KD or ACS annunciator point is required to establish and terminate this communication.
The point must be programmed with the ACS function/mode “FFT-NFN”. Figure B.3 shows the
point programming.
DVC-KD or
Annunciator at (A)
• The N1L1M2 portion of the point programming controls the telephone communication
between the field telephone and the DVC at node 3. (In this example, N1 would be the panel
controlling the telephone module.)
NOTE: The FFT-NFN link will accommodate communication between two DVCs at a time. If the
FFT-NFN link is in use by two other DVCs when the Point 2 button is pressed, the attempt to link (A)
and (B) will be denied.
3. When the FFT-NFN connection is no longer needed, the operator at (A) disconnects the call by
pressing the point button to disconnect. The FFT-NFN link will be automatically disconnected,
because no other points are active at the DVC-KD or annunciator on the (A) to (B) link. The
link will close once all the active FFT-NFN points mapped to the DVC-KD or annunciator
have been turned off.
Example 2
Refer to Figures B.4 and B.5 for this example.
Calls initiated at more than one FFT on a DVC node can be answered at another DVC. This
communication requires turning on the following communication links:
1. the links between the FFTs and their local DVC ( (B) to (C), (D), and (E), and
2. the link between DVC (A) and DVC (B) (the FFT-NFN link on a standard or high-speed
Noti-Fire-Net).
FFT riser
E
FFT riser
C
N1L1M5
N1L1M2
A standard or high-
speed Noti-Fire-Net B
FFT riser
D
DAL
Device
N7A2T
DVC-KD or ACS annunciator points are required to establish and terminate this communication.
These points must be programmed with the ACS function/mode “FFT-NFN”. Figure B.5 shows
the point programming.
DVC-KD or ACS programming:
ACS function/mode = FFT-NFN
Mapping: as indicated in
point label
Point 1 mapping - connects (A) to (B) to (C) Point 1 N3,N7,N1L1M2
DVC-KD or
Annunciator at Node 3
1. A firefighter jacks in at (C). Point 1 rings at (A). Both LEDs flash (green and yellow at the
DVC-KD, point active and yellow at the annunciator).
2. The operator presses Point 1, turning on the point. The point active LEDs will light steady on,
and the yellow LEDs will turn off. Communication is established between (C) and the local
telephone at (A).If pressing Point 1 activates (C) but does not open the FFT-NFN link, the (A)
and (C) point LEDs will continue to flash because the FFT-NFN link is not available.
3. Firefighters jack in at (D) and (E). Points 2 and 3 ring at (A), the point active LEDs light
steady and the yellow LEDs flash. The operator at (A) presses the Point 2 and 3 buttons (either
the Point 2 and 3 DVC-KD buttons or the Point 2 and 3 ACS annunciator buttons),
programmed as shown in Figure B.2, turning on the points. The yellow LEDs will turn off.
Communication is established between the field telephones at (C), (D) and (E) and the local
telephone at (A). (A) through (E) are now in communication.
NOTE: (D) is on a riser with no telephone control modules installed, so mapping is to the DAL
device in the format NxAxT, where A = device address on the DAL (digital audio loop).
4. (C) jacks out. The operator presses Point 1 to terminate the connection with (C). Points (D)
and (E) are still active, and continue to communicate over the FFT-NFN link.
5. (D) and (E) jack out. The operator presses Points 2 and 3 to terminate these connections. The
FFT-NFN link automatically terminates, because no FFT-NFN programmed points remain
active on it.
Example 3
Refer to Figures B.6 and B.7 for this example.
A call initiated at an FFT on a DVC node can be connected to an FFT on another DVC’s digital
audio riser. This communication requires turning on three communication links:
1. the link between the FFT (F) and its DVC (A).
2. the link between DVC (A) and DVC (B) (the FFT-NFN link on a standard or high-speed
Noti-Fire-Net)
3. the link between the FFT (C) and its DVC (B).
FFT riser
FFT riser
F E
FFT riser
C
N9L1M8 N1L1M5
N1L1M2
DVC NCM or NCM or DVC
N3 DAL
HS-NCM HS-NCM N7 DAL Device
FFT-NFN Link on
standard or high-
A B
FFT riser
speed Noti-Fire-Net D
DAL
Device
N7A2T
DVC-KD or annunciator points are required to establish and terminate this communication. These
points must be programmed with the ACS function/mode “FFT-NFN”. Figure B.7 shows the point
programming.
DVC-KD or
Annunciator at Node 3
Figure B.7 Point Programming for Figure B.6
Example 4
Refer to Figures B.8 and B.9 for this example.
A DVC can communicate directly with another DVC via the FFT-NFN connection. The local
phone at one DVC node can be connected to another: the link between DVC (A) and DVC (B) (the
FFT-NFN link on Noti-Fire-Net).
DVC DVC
N3 NCM or NCM or
HS-NCM HS-NCM N7
FFT-NFN Link on
standard or high-
A B
Local
speed Noti-Fire-Net Local
phone phone
DVC-KD or annunciator points are required to establish and terminate this communication. These
points must be programmed with the ACS function/mode “FFT-NFN”. Figure B.9 shows the point
programming. There must be a programmed point at each DVC for this link to function.
DVC-KD or DVC-KD or
Annunciator at Node 3 Annunciator at Node 7
NOTE: If the DVC is directly connected to an NFS2-3030 (that is, they are not connected
through a network control module), the NFS2-3030 will display specific troubles. An NFS2-640
will require a network annunciator to view DAL device troubles.
When the DVC is a node on a standard or high-speed Noti-Fire-Net, specific troubles will display
at the network annunciator or workstation.
D.1 Overview
An audio group consists of a collection of speaker circuits on a DAA2 with one or more amplifiers
assigned to it. A DAA2 can have up to two groups. Implementing groups eliminates the possibility
of overloading amplifiers while retaining flexibility that covers most applications. Group elements
are linked through VeriFire Tools programming.
The number of channels a group can play is limited by the number of amplifiers assigned to the
group. For example, a group that consists of a DAA2 and its four speaker circuits with no BDA
acting as a second channel will only be able to play one channel at a time. A group that consists of
a DAA2, BDA used as a second channel, and speaker circuits would be able to play two channels
simultaneously.
Refer to the programming section of the Digital Voice Command manual or the VeriFire Tools Help
file for programming instructions for groups.
D.2 Examples
D.2.1 One Amplifier Per Group
The group examples in this section are single-channel group configurations. Each group can use
only one of the digital audio system’s eight channels at a time.
1. Figure D.1 shows a group that consists of a DAA2 amplifier and all its speaker circuits. The
load on all four speaker circuits does not exceed the DAA2’s 50 watt capacity. This group is
capable of broadcasting one channel at a time.
3rd floor - 10 W
2nd floor - 15 W
1st floor - 15 W
Figure D.1 DAA2 - One Amplifier and All Speaker Circuits per Group, No BDA
2. Figure D.2 shows a DAA2 with a BDA used as a primary amplifier. Each amplifier is in a
separate group with two speaker circuits. Each amplifier supports a 50 watt load, and each
group can play one message at a time. The amplifier’s charger will be disabled automatically.
1st floor - 25 W
Figure D.2 DAA2 - One Amplifier, Two Speaker Circuits per Group, BDA
D.3 Rules
DAA2 amplifiers and speaker circuits must be assigned to groups in VeriFire Tools programming.
In order to assign them properly, apply the following rules.
• The sum of the load (in watts) of the group must be equal to or less than the wattage of a single
amplifier in that group.
An amplifier must be capable of supporting the entire group of speaker circuits. For example,
in Section D.2.2, a DAA2-50 (EVAC) with a BDA-25V(ALERT) in the same group, the group
is limited to 50W in the event all circuits are in EVAC and the full load is on the DAA2-50 and
none on the BDA-25V.
• Groups can not overlap. A speaker circuit can not be assigned to more than one group.
• A group may not be assigned to more than one DAA2. It can not bridge between DAA2s.
• At least one amplifier is required for each channel that will be played simultaneously with
another channel in the group.
For example, if ALERT and EVAC channels will be played at the same time in a group, at least
two amplifiers are necessary.
M
Message Segment A .wav file used to create an
audio message sequence for alert, evacuation,
or other messages. The .wav is either provided
by the sound library supplied with VeriFire
Tools or created by the user.
T
TELH-1 21, 36, 42
Trouble messages 72
U
UL 864 Ninth Edition Compliance 7
UL Power-limited Wiring Requirements 38
User-programmable Buttons 70
V
Validation, Program 66
VeriFire Tools Programming 40
See also, "Programming"
Volume Control, point programming 40
W
WARNING
Install the system components in the se-
quence listed .... 22
Wear a static discharge strap... 22
Wiring
24VDC Power, DVC 28
Warn-HL-08-2009.fm
www.notifier.com