Cable Calculation
Cable Calculation
λ1 I 2 R λ2 I 2 R
I 2R
Wd
I 2R Wsh
Gi Gb
P
dielectric
Qc pQd (1 − p ) Qd
TA (ambient)
conductor sheath
hT = hc + hr
we have H = hT A (T − TA ) = hT AΔT
1
thus Go =
hT A
hence:
hT = k [Ts − TA ]
1/ 4
and:
1 1
Go = =
hT A k (π D ) [Ts − TA ]1/ 4
Tc − TA = I 2 R [Gi + Gb + Gs + Go ]
⎡G ⎤
+ Wd ⎢ i + Gb + Gs + Go ⎥
⎣2 ⎦
+ λ1 I 2 R [Gb + Gs + Go ]
+ λ2 I 2 R [Gs + Go ]
Hence:
⎡ ⎛ Gi ⎞⎤
( T
⎢ c A − T ) − ( To − TA ) − Wd ⎜ + G b + G s ⎟⎥
⎣ ⎝ 2 ⎠⎦ [eq.1]
= I 2 R ⎡⎣Gi + Gb (1 + λ1 ) + Gs (1 + λ1 + λ2 ) ⎤⎦
I 2 R (1 + λ1 + λ2 ) + Wd = k (π D ) [To − TA ]
5/ 4
Thus:
k (π D ) [To − TA ] − Wd
5/ 4
I 2R =
1 + λ1 + λ2
A 3-core
2r0 belted-type
cable
t2
g ⎡ ⎛ t1 ⎞ ⎤ ⎡⎛ ⎛ t1 ⎞ ⎞ ⎛ t2 ⎞ ⎤
Gi = ⎢ 0.85 + 0.2 ⎜ ⎟ ⎥ × ln ⎢⎜ 8.3 − 2.2 ⎜ ⎟ ⎟ ⎜ ⎟ + 1⎥
2π ⎣ ⎝ t2 ⎠ ⎦ ⎢⎣⎝ ⎝ t2 ⎠ ⎠ ⎝ ro ⎠ ⎥⎦
where:
t1 = insulation belt thickness
t2 = conductor insulation thickness
ro = conductor radius
Gi Gb Gs
Gi
sheath
0.26
Then: Gcp =
1 + ( 0.0026 × 55 ) × 23.52
= 0.06 thermal Ω/m
TC − TA = 80 − 25 = 55 oC
Hence:
i.e.
37.46 = 10.44 × 10−5 I 2 ⇒ I = 599 A
This is too high. Thus try Tm =58oC next and repeat until
agreement is reached.
where:
δ= conductor mass density
c = insulation specific heat
ρ = conductor electrical resistivity
α = temperature coefficient of resistivity for ρ
I= short circuit current rating
tsc = short circuit duration (protection operating time)
To = cable surface temperature
T(0) = initial conductor temperature
T(tsc) = Tsc = maximum permissible temperature
Example:
(a) Al conductor:
δ c
I sc ⎡ 2.7 ×103 × 0.219 × 4.18 × 103 ⎛ 1 + α (120 − 20 ) ⎞ ⎤
12
=⎢ ln ⎜ ⎟⎥
A ⎣⎢ −8
2.83 × 10 × 0.00403 ⎝ 1 + α ( 70 − 20 ) ⎠ ⎦⎥
ρ α
12
⎡ 1.403 ⎤
i.e. I sc = ( 5 × 10 ) × 1.472 × 10 ⎢ ln
−4 8
⎣ 1.202 ⎥⎦
= 28.9 kA
Thus:
=⎢ ln ⎜ ⎟⎥
A ⎣⎢ −8
20.65 × 10 × 0.004 ⎝ 1 + α ( 66.2 − 20 ) ⎠ ⎥⎦
ρ α
12
⎡ 1.72 ⎤
i.e. I sc = ( 6.21× 10−4 ) × 4.18 × 107 ⎢ln
⎣ 1.18 ⎥⎦
= 15.8 kA
⎡ ⎛ 1 + α ( 200 − 20 ) ⎞ ⎤
12
I sc
= 1.472 × 10 × ⎢ln ⎜
8
⎟⎥
A ⎢⎣ ⎝ 1 + α ( 66.2 − 20 ) ⎠ ⎥⎦
i.e. I sc = ( 6.21× 10−4 ) × 1.472 × 108 × 0.612
= 56 kA
Tc Ts TA
Gi Go
Q1 Q2 Q3
where:
Q1 is the thermal capacitance of the conductor plus a
fraction (p) of the thermal capacitance of the electrical
insulation.
TA
G1 G2 G3 G4
Q1 Q2 Q3 Q4
where:
d = cable outer diameter
h = burial depth
WT = total losses per unit length
g = soil thermal resistivity [ = 1 k ]
αD = soil thermal diffusivity ⎡⎣ = 1 ( gcδ ) ⎤⎦
c = soil specific heat
δ = soil mass density
t = time