Estamat PFC Mounting Instructions Mv1161: Issue February 2002 Document Number: 13124
Estamat PFC Mounting Instructions Mv1161: Issue February 2002 Document Number: 13124
Mounting Instructions
MV1161
Version 1.2.1
Issue February 2002
Document Number: 13124
Front Panel Controls Digital display Step LEDs
The four-digit display indicates The LEDs indicate the energized
actual values, faults, capacitor steps.
and the set parameters. yellow lettering:
fundamental current I fund (LED1)
root-mean-square current I eff
Trend LEDs (LED 6)
"ind" and "cap": orange lettering:
switching steps in or out. display of harmonic current
green lettering:
Alternate display of step
current "Ic"
number of switching
operations "Σ"
(step LEDs 1 to 12)
LED indicators
Selected operating mode
or parameter
Keyboard
Connection diagram
(Rear view of the
controller)
Terminals Connection
1 C.T. connection k (S1), X/5 A or X/1 A In case of standard setting
2 C.T. connection l (S2), X/5 A or X/1 A as per item 1.1 above, the
4 Mains connection N, 230 VAC or 120VAC measuring voltage can be
5 Mains connection L1, 230 VAC or 120VAC connected to the mains
7, 8 Potential-free alarm contact, normally open supply, i.e. terminal 4 shall
10 Measuring voltage L or N be bridged to terminal 10,
12 Measuring voltage L and terminal 5 is to be
15-20 Control terminals for contactors 1-6 bridged to terminal 12.
21-26 Control terminals for contactors 7-12 (only PFC12)
Having identified the location of the current transformer, the current or output ratings of the capacitor
steps will be determined.
Display Function
AU2 Starting with step 1, the Controller switches in each individual step briefly, and
2.1 to 2.3 switches it out again immediately. (PFC6 : 6 steps, PFC12: 12 steps).
The procedure is repeated three times.
Normally, the ESTAmat PFC Controller terminates a successful initialization after approximately 5
minutes, and correctly determines the configuration of the plant, and indicates the actual power factor.
If one of the following symbols is on display, the following conditions may be the cause:
Display Condition Remedy
≡I The measuring current is less than 25 mA. Check C.T. electric circuit
≡0 The measuring current is in excess of 5.3A. C.T. transformation ratio is too
small
≡U The measuring voltage is missing. Check connection of Controller
≡AU1 AU1 could not be carried out correctly. Possible Set AU2. Refer to item 6.3.1.
causes: quick reversals of load, insufficient
compensation output, load too low.
≡AU2 AU2 could not be carried out correctly. Possible Set AU3. Refer to item 6.3.1.
causes: quick reversals of load, no switching of
capacitor steps.
SLE The faults ≡AU1 or ≡AU2 have appeared five Set AU3. Refer to item 6.3.1.
times in succession. This condition can be
modified only upon fundamental change of load.
A target factor of 1.00 is preset as standard.
The ESTAmat PFC Controller can be applied wherever automatic control of the power factor is
required. All functions of the ESTAmat PFC are controlled by a microprocessor. A protective gear
(watchdog) continously monitors the processor to guarantee its faultless operation. There are no
internal time or date functions.
The measurable variables current and voltage are conducted across a 50/60Hz band-pass filter.Thus
harmonics existing in the network cannot affect the measurement process. Both measurement entries
are potential-free. The measuring voltage shall be in the range of 58V-690V and may be connected, at
option, between phase to neutral or phase to phase. The current measuring range is 25mA to 5A, and
there is no need to differentiate between X/1A or X/5A current transformer.
A measuring cycle lasts 0.5 seconds and comprises the measurement of values, the calculation of all
required parameters, such as power factor, current, harmonic current, etc., and if necessary, the
initialization of certain actions, e.g. switching the steps, activating alarm, etc.
The ESTAmat PFC Controller is capable of determining by itself , during the start-up procedure, the
location of the current transformer as well as the output rating of the connected capacitor steps by
means of test switchings.
The C/k-value is the pick-up value of the ESTAmat PFC Controller. The value represents the
reactive current response threshold of the Controller in Ar (ampere reactive). In case the reactive
current portion of the load exceeds the set C/k value, one of the two LEDs "ind" or "cap" will indicate
the trend. The calculation of the C/k value is described under item 6.3.5.
Switching in circular sequence means that capacitors which have been switched in first, will also be
switched out again first. Switching follows the FIFO principle: First-IN-First-OUT. If the switching-in
follows the order 1-2-3-4-5, then also the switching-out of the capacitors will follow that same order .
1-2-3-4-5.
The ESTAmat PFC Controller measures continuously the demand for reactive power and the
variations of it and, due to the optimized switching performance, switches in or out the largest possible
capacitor step. In case of, for example, a power factor correction equipment of 25 : 25 : 50 : 50 : 50
kvar, the ESTAmat PFC Controller will immediately switch in a step of 50 kvar instead of gradually
switching in steps of 25kvar. This way, the number of switching operations is reduced, which results
in an increased life expectancy of both the capacitors and the contactors.
The increasing use of renewable energy sources (e.g. wind, solar, biogas) and thermal regeneration,
as also the application of emergency power supply systems, require that state-of-the-art power factor
controllers operate trouble-free in case of a feed-back of active power into the general supply mains
(generator operation). In both cases of energy supply and of energy feed-back, the ESTAmat PFC
Controller can identify correctly the inductive reactive power and compensate it.
The period between lighting-up of one of the light-emitting diodes (LED) ("ind","cap") and the
switching in or out of capacitor steps is defined as switching delay time. The switching delay time can
either be determined by the ESTAmat PFC Controller as a function of load, or preset by the
operator.
The period between switching out a certain capacitor step and the earliest possible re-switching in
of the same step is defined as re-switching blocking delay. With the ESTAmat PFC Controller, this
blocking delay for re-switching can be either 20, 60, 180 or 300 seconds. This period is necessary in
order to allow the voltage existing at the capacitor after the switching-out to reduce to an acceptable
level. The blocking delay for re-switching shall be selected in accordance with the existing
discharging device. Switching-in shall be effected only when the residual voltage is less than 10% of
the operating voltage.
Via an internal temperature sensor the ESTAmat PFC Controller can permanently measure the
ambient temperature. Although the sensor is installed within the device, the measuring can be carried
out with sufficient precision because of the existing venting slots which allow sufficient air circulation.
When the Controller is mounted into a switch cabinet, there is the possibility of monitoring the
cabinet's internal termperature. By setting limit values, an alarm function can be activated.
When several transformers supply one single L.V. bus bar, the individual currents shall be measured
by means of current transformers and then added together via a summation current transformer.
Special attention shall be given to the correct polarity because, otherwise, the current intensities of the
individual transformers will subtract.
The calculation of the C/k-value is described under item 6.3.5. It is important to remember that the
transformation ratios of the individual current transformers shall be added up.
In case two network sections, each with independent power factor control equipment, are
interconnected, the two power factor controllers influence each other, because the currents distribute
across the two transformers. In such a case, to avoid hunting of the two power factor controllers, the
C/k-values should be set differently. The result will be a so-called "lead-follow" - behavior because
both controllers react at a different speed. The power factor controller with the lower C/k value is
quicker in switching than the one with the higher C/k value.
The target cosϕ values of both power factor controllers should be the same. If this is not the case, the
power factor controller with the higher setting would try to switch in steps which the power factor
controller with the lower setting would again switch out immediately. This would also result in an
unacceptable hunting between the switch-in and switch-out operations.
2.13. Interface
The ESTAmat PFC is equipped with a serial interface RS232. By means of a computer, all relevant
measuring values and Power Factor Controller data can be requested. Furthermore, all Power Factor
Controller's parameters can be modified via a computer. The computer software and the connection
cable ESTAmat PFC to the computer are available at option.
The power factor controller is connected by means of a 20-terminal plug. The ESTAmat PFC12 is
provided with an additional 6-terminal plug for the steps 7 to 12. The connections are shown at the
rear of the power factor controller's casing.
Terminals Connection
1 C.T. connection k (S1), X/5 A or X/1 A
2 C.T. connection l (S2), X/5 A or X/1 A
4 supply connection N, 230 VAC
5 supply connection L1, 230 VAC
7, 8 potential-free fault alarm contact, normally open
10 measuring voltage L or N
12 measuring voltage L
15-20 control outputs for contactors 1-6
21-26 control outputs for contactors 7-12 (only PFC12)
1. The power factor controller is internally protected by means of a fine-wire fuse 100 mA (glass
tube fuse 5 x 20 mm). This fuse is not accessible from the outside.
2. The rating of the external fuse is a function of the current consumption of the connected
contactors. It should, however, be taken into account that an individual control contact may
certainly be loaded with a maximum of 5A, but the external fuse must not exceed the value of
10A.
3. Under normal circumstances, the measuring voltage is identical with the operating voltage, i.e. the
terminals 4-10 and 5-12 shall be connected by means of bridging links. If measuring voltage and
operating voltage are connected separately, the terminals 10 and 12 are each to be protected by a
quick-acting fuse of 2 A.
4. All control contacts, except for the fault alarm contact (7 and 8), are bridged by a spark-quenching
unit (RC element). The impedance of the RC element is 30 kΩ at 50 Hz.
5. When using capacitors with attached discharge resistors, the necessary time for discharging will
be 60 or 180 seconds, which has to be observed for any switching-in of steps. The re-switching
blocking delay time of the ESTAmat PFC must be set accordingly via parameter 7.
1. In case of an unbalanced load of the phases, the current transformer should be connected to the
phase which is most highly loaded.
3. The connecting cable to the current transformer, with a maximum length of 10 m, should have a
minimum conductor cross section of 2.5 mm². If the cable is longer than 10 m, a larger conductor
cross section or a current transformer of a higher rating shall be used.
4. When an already existing current transformer can be made use of, then all the current paths of the
individual devices shall be connected in series with the ESTAmat PFC Controller. Attention
should be paid that the rating of the current transformer be sufficient.
5. The primary current of the current transformer should coincide with the actual current
consumption of the factory. If the current transformer is overdimensioned, the ESTAmat PFC
Controller receives too small a measuring signal and, consequently, will work incorrectly or not at
all, and will signalize the fault "undercurrent ≡I ".
6. The C/k value is set automatically by the ESTAmat PFC Controller in the initialization modes
AU1 und AU2. Attention shall be paid, however, that the current of the smallest capacitor step at the
transformer secondary is in the range of 0.025 up to a maximum 1.5 A.
When working at the C.T. secondary circuit (e.g. removal of the ESTAmat PFC), attention
should always be paid that the C.T. secondary terminals be short-circuited and remain so until
the work is completed (e.g. re-installation of P.F. Controller).
Example: means that the key IN shall be pressed. The display - - - - symbolizes an
4.4. Initialization :
The P.F. Controller is supplied with the fully automatic initialization mode AU1 set, which is the normal
application. The fully automatic initialization may not be successful in case of strong oscillations in
the public mains. In such a case, the semi-automatic AU2 or the manual initialization AU3 can be
applied. The initialization mode is stored as parameter -1- (item 6.3.1).
How to change the initialization mode is described under items 6.2 and 6.3.1 .
With this mode of initialization, the current transformer may be connected to any phase. Connection of
both the current transformer k/l (S1/S2) and the measuring voltage is also at option. The mode of
measuring voltage will have to be set either phase to phase L-L or phase to neutral L-0 (=standard
setting). Refer to items 6.2 and 6.3.2.
When the supply voltage is applied, the setting values will be displayed as described under item 4.3.
First of all, the set re-switching blocking delay is effective. During this time, AU1 is being displayed
and a decimal point is flashing. When the display alternates between AU1 and NO, it means that there is
still stored a C.T. location of a previous application. Refer to item 4.4.1.3. If this is not the case, the
ESTAmat PFC Controller switches capacitor steps in and out several times after the re-switching
blocking delay has elapsed and subject to the mains conditions. The number of switching cycles
carried out will be displayed after the last step has been switched out. This number may range between
-0- and -5- . When the display shows the figure -5- , part 1 of the initialization is completed.
If wrong results are caused by load variations during the measuring period, the display will show ≡AU1
and the result of the measurement will be rejected. If due to special mains conditions, a clear
determination of the connection mode during initialization is impossible, then five further trial runs
will be made observing the re-switching blocking delay. After five abortive trial runs in succession
displaying ≡AU1, the power factor controller switches into a stand-by position and will resume
initialization only after the load conditions have fundamentally changed. The stand-by position is
indicated by the letters SLE (Sleep).
Again in this case, the semi-automatic initialization AU2 or the manual initialization AU3 is
recommended.
At first, the set re-switching blocking delay is effective. During this time, AU2 is displayed and a
decimal point is flashing. For the determination of the currents of the capacitor steps, 6 (or 12) steps
will be switched in and out, one after the other. This procedure will be repeated three times. The
respective switching cycle is displayed as 2.1, 2.2 and 2.3. The measured reactive current changes will
be stored as step currents. Upon completion of the initialization, the power factor controller changes
into automatic operation mode and the actual power factor is displayed.
In case of a fault, e.g.: measuring voltage missing ≡U, measuring current insufficient ≡I or measuring
current too large ≡0, the initialization will be interrupted. The elimination of the fault's cause will be
detected by the power factor controller, and the initialization will automatically be re-started.
When the set target power factor has been reached for the first time during the automatic operation
mode, the C.T. location will be stored permanently. If this is the case, there will appear in the display
of the ESTAmat PFC Controller, directly after application of the supply voltage, alternatively AU1
and NO during the period of the re-switching blocking delay. Thereafter, the ESTAmat PFC
Controller performs part 2 AU2 (item 4.4.1.2).
A stored C.T. location can be erased by changing the alternating display AU1 and NO into AU1 and YES.
YES : The ESTAmat PFC Controller erases the stored C.T. location and performs part 1 and part 2
of the initialization AU1
The semi-automatic initialization AU2 should be selected when the fully automatic initialization does
not produce a satisfying result due to strong load changes. Attention will have to be paid to the fact
that the phase connection of the measuring voltage has to be explicitly specified. Refer to items 6.2
and 6.3.2.
The initialization runs in accordance with part 2 of the initialization mode AU1 (item 4.4.1.2).
During the first start-up procedure, parameters -4- and -5- must be verified. For this, both parameters
must be called-in and, if necessary, be modified in the setting menu. If this is not done ≡PAR will be
displayed, and after a delay of 2 seconds, the controller will automatically change to the setting menu
of the parameter concerned.
The step outputs will be determined by means of the C/k value, the number of switching steps and the
switching program. No readjustment of the step outputs will occur while switching the capacitor steps
during operation.
During the start-up procedure of the controller, if the measuring current ≡I, or the measuring
voltage ≡U is missing, a test mode can be activated to switch steps in the manual operating mode.
During AU1 and AU2, the switching program of 1:1:1:1, the C/k value of 0.05 and the maximum
number of switching steps are automatically preset. Only during AU3, the already set parameters (4, 5
and 6) will remain. The test mode is activated by means of the key .
Thereafter, the selected menu is displayed alternately with TEST. For deactivation of the test mode, the
operating voltage of the controller must be disconnected. For example, this can be achieved by
temporarily removing the control fuse of the capacitor bank.
Example: means that the key IN shall be pressed. The display - - - - symbolizes an
On the front plate of the ESTAmat PFC Controller six main menu points are laid out. Important
control parameters, measuring values, and control characteristics can be enquired for or can be set by
means of this main menu.
If one of the following menu points current, target-cosϕ, switching delay, Ic/Σ switching
operations or harmonic current is called upon, and no key is being operated for a period of 30
seconds, the ESTAmat PFC Controller switches to the AUTO mode.
In the automatic operating mode, the capacitors are automatically switched in or out depending on the
demand for reactive power. The actual power factor is shown in the display. A minus in front of the
power factor means that the power factor is capacitive.
For the purpose of testing, capacitors can be switched in or out manually at any time in the automatic
operating mode.
As long as the decimal point flashes in the display, the re-switching blocking delay is still effective.
However, the operation of the key is stored and the capacitor step will be switched in after the re-
switching blocking delay has elapsed.
The manual operating mode can be called upon from any other mode. When the MAN mode is set, the
automatic operating mode is ineffective, i.e. no capacitor steps are switched.
In order to activate the MAN mode, one must keep pressing the key until
the display shows 8888 after about 5 seconds. Manual operation is manifested by the flashing of the
LED AUTO.
As long as the decimal point flashes in the display, a re-switching blocking delay is still effective.
However, the operation of the key is stored and the capacitor step will be switched in after the re-
switching blocking delay has elapsed.
The MAN mode remains active even after a voltage interruption has occurred. When the voltage has
returned, the P. F. Controller goes back to MAN mode by itself. Capacitors which had been switched
in before the voltage interruption occurred will be switched in again taking into account the re-
switching blocking delay.
by means of the key the fundamental frequency current can be called upon.
This is displayed by means of the step LEDs 1 and 6 . The lettering I fund defines the fundamental
frequency current, I eff the root-mean-square value of the current.
The portion of harmonics will increase as a function of the increased deviation between root-mean-
square current and fundamental frequency current.
set in the range of 0.85 inductive ( 0.85 ) up to 0.95 capacitive ( -0.95 ). A minus in front of the
power factor means that the power factor is capacitive.
When pressing simultaneously the keys the standard setting 1.00 for the
target cosϕ is produced. The value shown when the setting mode for the target cosϕ is left will be
stored.
The period between surpassing the hysteresis and starting the switching procedure is defined as
switching delay time. The condition of surpassing must be given permanently during the determined
switching delay time. The switching delay time can be determined by the ESTAmat PFC Controller
as a function of load, or it can be fixed by the operator.
The following fixed switching delay times are possible: 10 , 30 , 60 , 120 , 180, 300 and 500 seconds.
Determination of the switching delay time as a function of load is activated when the display indicates
LOAD . The switching delay time may range between 2 and 500 seconds.
The selected value is stored by means of the key and the menu indicator
changes to the next menu.
By means of the parameters 8 and 9 (items 6.3.8 and 6.3.9), fixed switching delay times can be set
separately for the switching-in and the switching-out of capacitors. In this case, the flashing LED IND
signalizes a fixed presetting for the switching-in delay time while the flashing LED CAP indicates a
fixed presetting for the switching-out delay time.
In this mode the capacitor steps are examined. The capacitor current and the number of switching
operations of the selected step are alternately displayed.
The step LEDs 1 to 12 show for which step the values are being displayed. By means of the LEDs "Σ"
and "Ic", the displayed value can be identified:
Ic = Current in Ampere of the selected capacitor step. The current is readjusted via the current
transformer's transformation ratio which is set under parameter -18- .
The capacitor contactors will have to be replaced after about 100,000 switching operations. A regular
check is strongly recommended.
In the step display one can see which harmonic has been selected.
Example: means that the key IN shall be pressed. The display - - - - symbolizes an
The target power factor and the switching delay time can be modified directly by means of the main
menu.
The values can be reduced by means of the key or can be increased by means of
the key
The keys must be kept pressed until the display shows the value 8888 after about 5 seconds.
Thereafter, the parameter - 1- and in alternation its actual occupancy, e.g.: AU1 , is shown.
If the parameter is to be modified, press key The set value flashes in the
display.
is to be modified until the display indicates DONE . This display will appear at the moment when the
number of the parameter changes from -1- to -19- or from -19- to -1- .
By pressing the key the selection will be confirmed. Thereafter, the Controller
runs a new start-up of the program or, in case no significant parameters have been modified, it returns
to the calling menu position.
A new start-up of the program without modification of the parameter will also be carried out if, after
activating the setting menu, no key operation takes place for a period of 2 minutes.
Number Implication
- 1- Modes of initialization AU1, AU2 or AU3
- 2- Type of measuring voltage L-N or L-L, only to be set in case of AU1
- 3- Connection of measuring voltage, to be set in case of AU2 and AU3
- 4- Switching program, to be set in case of AU3
- 5- C/k value, to be set in case of AU3
The type of measuring voltage determines whether the measuring voltage is connected between phase
to phase or phase to neutral. Since this information is required only for the initialization mode AU1, this
parameter will only be displayed in case AU1 has been selected.
The connection of the measuring voltage needs to be indicated only in case of semi-automatic (= AU2)
and manual initialization (= AU3). The table shows all the possible connection combinations to the
terminals 12 and 10 of the ESTAmat PFC Controller.
The identifiers L1-N, L2-N, etc. indicate the connection of the measuring voltage. The setting value
has to be read in the column which indicates the correct C.T. phase.
The switching program has to be set only in case of the manual initialization mode (= AU3) . The
figures indicate the relation between the various step outputs. For example, the switching program
1:2:4:4:4 reveals that step 2 is double the size of step 1. Step 3 and the following steps have four times
the output of step 1 (e.g.: 50kvar : 100kvar : 200kvar : 200kvar ... etc.). The steps with equal output are
regarded also as equal with regard to controlling (=circular steps) and can be switched in accordance
with the principle of circular switching.
The C/k value is the pick-up value of the ESTAmat PFC Controller. This value is the reactive
current responding threshold of the Controller in reactive Ampere. If the reactive current portion of the
load exceeds the set C/k value, this will be displayed by one of the two LEDs ("ind" or "cap").
The setting range of the C/k value is 0.025A up to a maximum 1.5A. The maximum value is a function
of the selected switching program. The C/k value has to be set only with the initialization mode AU3.
Conditional on the minimum C/kmin-value of 0.025A and a specified C.T. transformation ratio, the
smallest possible capacitor step Qmin can be calculated as follows:
The number of the connected steps can be set by means of the LED step display. The setting range
comprises 1-6 or12 steps respectively. The number of steps has to be set in case of initialization mode
AU3. The minimum number of steps is determind by the switching program. In case the number of set
steps is lower than the allowed minimum number of steps, the number of steps will be adjusted
respectively.
If RST is selected (see page 20), 6 (PFC6) or 12 (PFC12) is reset.
The time between switching out a certain capacitor step and the earliest moment of switching it in
again is defined as blocking delay time for re-switching. This time is required in order to reduce the
voltage existing at the capacitor to an acceptable level. The re-switching blocking delay time will have
to be selected in accordance with the existing discharge device. Switching-in must take place only
after the residual voltage has fallen below 10% of the operating voltage. The standard setting of the
blocking delay time is 20 seconds.
Re-switching blocking delay time Display
20 sec 20
60 sec 60
180 sec 180
300 sec 300
If RST is selected (see page 20), 20 is reset.
The time for switching-in and switching-out can be set either processor-controlled as a function of
load, or as fixed time presetting. It is also possible to set the switching-in time separately from the
switching-out time. The setting range for the fixed time presetting is 2 to 500 seconds. This option is
not effective in case of setting OFF , i.e. fixing of the switching delay time is carried out in accordance
with the setting in the main menu.
If RST is selected (see page 20), OFF is reset.
As already mentioned in 6.3.8., the switching-out delay time can be set independently of the
switching-in delay time. The setting range is likewise 2 to 500 seconds. This option is not effective in
case of setting OFF , i.e.. fixing of the switching delay time is carried out in accordance with the setting
in the main menu.
If RST is selected (see page 20), OFF is reset.
Steps of equal output can be switched in different sequence. In case of circular switching, the step
which had been switched out for the longest time will be switched in, and the step which had been
switched in for the longest time will be switched out. The advantage of this method is that there is
equal switching stress and operating time for all steps. The series switching mode is applied where the
compensation is assembled of filter circuits with different tuning frequencies and also when a certain
switching sequence has to be maintained.
A number of capacitor steps determined by the operator can be defined as fixed steps. These steps are
switched in permanently upon application of the supply voltage to the ESTAmat PFC Controller and
after the re-switching blocking delay time has elapsed. The desired number of fixed steps has to be set.
The ESTAmat PFC Controller switches in the respective number of steps starting with the highest
step digit. As a rule, all circular steps can be used as fixed steps. One cirular step, however, shall
remain for the control operation. In case of series connections, no fixed steps can be defined. If the
operating mode MAN is set, this parameter cannot be selected.
If RST is selected (see page 20), OFF is reset.
The parameters of the main menu, e.g.: target power factor, switching time, etc. and the manual
operating mode MAN, can be protected against unauthorized adjustment by locking the keyboard.
Locking is activated, when the display indicates ≡LO[ .
During normal and trouble-free operation, the alarm relay is operative. The contact is open. In case of
faults and of a breakdown of the supply voltage, the contact closes. The fault situation to which the
alarm relay shall react can be selected by means of parameter 13.
Alarm signals
≡T ≡HAR ≡IEF ≡[ ≡U ≡0 ≡I Display
X 0
X 1
X 2
X 3
X 4
X 5
X 6
X X X 7
X X 8
X X X 9
X X X X 10
X X X X X X X 11
X = Alarm relay reacts to this fault situation.
The different types of fault are described in the survey matrix under item 7.
If RST is selected (see page 20), 0 is reset.
6.3.14. Parameter -14- : Switching out the capacitor steps in case of alarm
Capacitor steps can be switched out when certain alarm signals are given. The fault alarm which shall
cause a switch-out can be selected by means of parameter 14. The specific kind of fault alarm
determines the switch-out behavior. The numbers 1- 3 indicate the priorities.
1 = the capacitor steps will be switched out immediately without time delay.
2 = the capacitor steps will be switched out after a time delay which can be modified (parameter 19)
3 = steps will continue being switched out until the fault alarm has disappeared.
Fault alarms
≡IEF ≡T ≡E ≡U ≡I Display
OFF
1 1
1 2 2
2 1 3
3 1 4
3 1 5
2 1 2 6
3 2 1 7
3 3 1 8
3 3 2 1 9
3 3 1 2 10
3 3 2 1 2 11
By means of an internal sensor, the ESTAmat PFC Controller can measure the ambient temperature.
When the preset maximum temperature is exceeded, the display of the fault alarm ≡T alternates with
the display of the actual power factor.
Advice: If for parameter -13- (function of the alarm relay) the value 6 has been selected, a cabinet
ventilator can be switched in via the alarm relay.
This factor indicates the relation between fundamental frequency current (50Hz or 60Hz) and root-
mean-square current. The higher this factor the greater is the portion of harmonic waves. This way, the
harmonic situation can be evaluated. Factors between 1.05 and 2.00 can be set. The step width is 0.05.
If the factor is exceeded, the fault alarm ≡IEF will be given after a time delay of 5 minutes. With the
setting OFF , this function is switched out.
For the harmonic portions of the 3rd; 5th; 7th; 11th; 13th; 17th and 19th harmonic, 10 maximum value
profiles in percentage can be set. When at least one harmonic wave exceeds its set maximum value for
a period of 5 minutes, the fault alarm ≡HAR is triggered.
The current transformer transformation ratio k can be set by means of parameter 18. The displayed
current values and C/k values will be respectively multiplied by the set factor. Factors between 1 and
8000 can be selected. This is possible in all the initialization modes.
If RST is selected (see page 20), 1 is reset.
6.3.19. Parameter -19- : Time delay for switching out steps in case of ≡I and ≡E
If fault alarm is given as a consequence of undercurrent ≡I and energy feed-back ≡E , capacitor steps
can be switched out after the set waiting delay has elapsed. The switch-out function has to be released
via parameter 14. Waiting delays between 30 and 500 seconds can be set.
Step width is 10 seconds (range of 30 – 200), 20 seconds (range of 200 – 300) and 50 seconds (range
of 300 – 500).
If RST is selected (see page 20), 500 is reset.
2.1 progress of the figures 2.1 to 2.3 indicate the - No fault display!
to none
AU2 progress of AU2
2.3
8.3. Monitoring
Operating voltage : 230VAC ±15%, 50Hz (60Hz and/or 120VAC upon request)
Power input : 8W maximum
Instrument fuse : 100mA tr. 5 x 20 mm, inside the device
Connection : via 20-poles (PFC12: an additional 6-poles) multipoint
connectors, 2.5 mm², rigid or flexible cable
Interface : RS232, 3-poles multipoint connector
-2-
Type of measuring
voltage
L-0 or L-L