Sotf Logic Schemes-Nerc Guidelines
Sotf Logic Schemes-Nerc Guidelines
A Technical Document
Prepared by the
System Protection and Control Task Force
Of the
North American Electric Reliability Council
June 7, 2006
Copyright © 2006 by the North American Electric Reliability Council. All rights reserved.
A New Jersey Nonprofit Corporation
Switch-On-To-Fault Technical Document
TABLE OF CONTENTS
SWITCH-ON-TO-FAULT SCHEMES IN THE CONTEXT OF LINE RELAY LOADABILITY I
PURPOSE 1
INTRODUCTION 1
CONCLUSION 9
This technical document was approved by the NERC Planning Committee on June 7, 2006.
Page i
Switch-On-To-Fault Technical Document
PURPOSE
The Protection System Review Program – Beyond Zone 3 document, issued in August 2005,
Appendix B stated:
“When determining the switch on to fault element settings, each utility
shall verify that the schemes will not operate for emergency loading
conditions.”
Unfortunately, this requirement was not accompanied by adequate guidance. This reference
document is intended to provide transmission protection system owners with guidance for the
review of existing switch-on-to-fault schemes to ensure that those schemes do not operate for
non-switch-on-to-fault conditions or under heavily stressed system conditions. This document
also provides recommended practices for application of new switch-on-to-fault schemes.
INTRODUCTION
1
Switch-on-to-fault (SOTF) schemes are protection functions intended to trip a transmission line
breaker when closed on to a faulted line. Dedicated SOTF schemes are available in various
designs, but since the fault-detecting elements tend to be more sensitive than conventional,
impedance-based line protection functions, they are generally designed to be “armed” only for a
brief period following breaker closure. Depending on the details of scheme design and element
settings, there may be implications for line relay loadability. This paper addresses those
implications in the context of scheme design.
Page 1
Switch-On-To-Fault Technical Document
SOTF current fault detector pickup settings must be low enough to allow positive
detection of close-in three-phase faults under what is considered to be the “worst case”
(highest) impedance to the source bus.
2. When an impedance protection scheme uses line-side voltage transformers, SOTF current
fault detectors may operate significantly faster than impedance units when a breaker is
closed into a fault anywhere on the line. The dynamic characteristics of typical
impedance units are such that their speed of operation is impaired if polarizing voltages
are not available prior to the fault.
Current fault detector pickup settings will generally be lower in this application than in
(1) above. The greater the coverage desired, and the higher the source impedance, the
lower the setting.
3. Regardless of voltage transformer location, SOTF schemes may allow high-speed
clearing of faults along the entire line without having to rely or wait on a
communications-aided tripping scheme. Current or impedance-based fault detectors must
be set to reach the remote line terminal to achieve that objective.
The cited objectives may not be fully compatible with NERC line loadability requirements
depending on the design of the SOTF scheme and on its attendant settings.
2 Note that the voltage at the local end of the line may be greater than or less than 0.85 per unit at
the remote end due to the effects of line capacitance or tapped load. Any such differences are
ignored for purposes of this document.
Page 2
Switch-On-To-Fault Technical Document
This goal may be achieved with a combination of techniques including but not limited to:
• Utilize a SOTF scheme design which is enabled only in the period
immediately following breaker closing.
• Set SOTF line voltage detectors (used to arm SOTF tripping) no higher than
required to override induced voltages on the line when open at all terminals.
• Set SOTF current fault detectors no lower than required to clear a close-in
three-phase fault under worst-case (highest source impedance) conditions.
Existing SOTF schemes may not have the requisite flexibility either as to scheme logic or
range of available settings to satisfy NERC line loadability requirements while meeting the
minimum fault protection requirements. In these cases, transmission system protection
owners must implement scheme upgrades.
Page 3
Switch-On-To-Fault Technical Document
In the case of modern relays, every manufacturer has its own design, in some cases with
user choices for scheme logic as well as element settings.
In some SOTF schemes the use of breaker auxiliary contacts and/or breaker “close”
signaling is included, which limits scheme exposure to actual breaker closing situations.
With others, the breaker-closing declaration is derived solely from the status of voltage
and current elements. This is regarded as marginally less secure from misoperation when
the line terminals are (and have been) closed, but can reduce scheme complexity when
the line terminates in multiple breakers, any of which can be used to energize the line.
A second feature included in many SOTF schemes is the requirement that the line voltage
be low enough to be considered dead as a precondition for arming SOTF tripping and in
many cases as a condition which must still exist when the SOTF trip is declared. This is
a security measure intended to prevent undesired SOTF tripping when the line is alive. A
primary consideration in the design and application of schemes with line voltage
supervision is the pickup setting of the voltage unit. Ideally, line voltage detector pickup
should be set below any credible system voltage, but above any line voltage which could
be induced by the proximity of lines on the same right-of-way. The higher the voltage
unit pickup setting, the greater the risk that the breaker may be closing into a line which
is alive but still indicates dead due to lower than normal voltage.
Under present NERC line loadability requirements, line voltage unit pickup settings
above 0.85 per unit (or when line voltage is not included as part of the scheme), require
that the current fault detectors be set above 1.5 times the four-hour emergency line rating,
3
subject to applicable technical exceptions.
Three individual criteria are suggested for the settings on the overcurrent units,
depending on the line voltage unit pickup settings:
• For voltage settings above 0.85 per unit (or no voltage supervision), the
overcurrent elements must be set for 1.5 times the four-hour emergency line
rating or higher.
• For voltage settings between 0.70 and 0.85 per unit, it is recommended that
the current (or other) fault detectors be set only low enough to detect a close-
in, three-phase fault under “worst case” (highest source impedance)
conditions assuming that they cannot be set above 1.5 times the four-hour
emergency line rating criteria.
• For voltage settings less than 0.70 per unit, there is no suggested relay
loadability criterion.
3 Other types of fault detectors (e.g., impedance units with or without offset to include the
origin) used in addition to or in lieu of current fault detectors are subject to the same requirement.
Page 4
Switch-On-To-Fault Technical Document
Page 5
Switch-On-To-Fault Technical Document
It should be noted that large voltage angles across the breaker being closed, either when closing
into an energized line or when simultaneously reclosing multiple terminals of a line, may result in
transient currents considerably exceeding 1.5 times the four-hour emergency line rating.
Depending on the specific type of SOTF elements used and their settings, they may operate under
these conditions.
Figure 1: Scheme A
Scheme A describes a typical application of electromechanical current and voltage relays where
the voltage relays are connected to line-side potentials. As is evident, tripping is only enabled for
250 milliseconds following breaker closing. The scheme is therefore secure from tripping under
conditions when both line terminals are already closed, regardless of the load current or line
voltage.
If the local breaker is being closed to energize an unfaulted line, the scheme is secure from
tripping provided that the current fault detector is set above line charging current as well as any
tapped load current, including transformer magnetizing inrush current. A short time-delay in the
current fault detector input would increase security by allowing the line voltage detector time to
block tripping. Such a feature might also be useful in simultaneous high-speed reclosing
applications.
If the line is already energized from the remote terminal when the local breaker is closed, the
scheme is secure from tripping on through-load provided that the voltage detector has picked up.
In this example, the design of the voltage relay was such that it could not be set to pick up at less
than 0.85 per unit voltage. A 0.85 per unit voltage setting is considered acceptable. However, as
noted earlier, with a voltage setting this high, the current fault detectors should be set only low
enough to guarantee clearing of a close-in three-phase fault assuming that they cannot be set
above 1.5 times the four-hour emergency line rating criteria.
Page 6
Switch-On-To-Fault Technical Document
Figure 2: Scheme B
Scheme B does not rely on breaker auxiliary contacts to indicate a breaker closing situation,
relying instead on a combination of line undervoltage and line undercurrent to arm SOTF
tripping. This may be an attractive feature for lines terminating in multiple breakers.
There is only one (very low-set) current level detector, used for both undercurrent and
overcurrent detection, which would seem to make this scheme susceptible to undesired operation.
However, the 20 millisecond time-delay and the overall scheme logic should provide immunity
against false tripping for high-charging current and tapped load situations, and also for
simultaneous high-speed reclosing applications, since the voltage level detector should pick up
prior to the expiration of the 20 millisecond timer.
Figure 3: Scheme C
Scheme C protects against closure into a bolted fault and also provides instantaneous stub bus
protection with the breakers closed and the line switch open. Since undervoltage is the sole
Page 7
Switch-On-To-Fault Technical Document
condition which arms SOTF tripping, it is important that consideration be given to the possible
loss of three-phase potential. With the voltage setting indicated, the scheme is otherwise immune
to undesired operation upon closing into an energized line.
Figure 4: Scheme D
Figure 5: Scheme E
Scheme E uses electromechanical relays and is applied on a breaker basis rather than on a line
basis. It is in service only at the instant of breaker closure, but as with Scheme D, it does not
discriminate between a live and a dead line. This requires that the breaker current fault detector
be set in accordance with NERC loadability requirements.
The three-second timer is a security measure intended to disable the scheme if for some reason
the close signal is maintained.
The 0.5 second timer is a “pulse stretcher”, which may be required for dependability if the nature
of the breaker closing control causes the closing pulse to cut off prematurely.
Page 8
Switch-On-To-Fault Technical Document
CONCLUSION
SOTF schemes are an important element of transmission system protection. However, unless
they are carefully applied, they may compromise the ability of the transmission system to tolerate
heavy loading. This paper has presented the relationship between the intended purpose of SOFT
schemes and introduced methods by which SOFT schemes can be made more tolerant of heavy
load conditions.