Week 3 - Basic Elements in Control System
Week 3 - Basic Elements in Control System
System
Steam in
TC
TT
Fluid in Fluid out
Heat Exchanger
Ti T desired
Steam out
Pressure
Flow
Level
Process Temperature
pH
dP cell
Capacitance
I/P
Sensor Radar, Sonic
Magnetic
Resistance
IR/Laser
4-20 mA
Transmitter 1-5 Vdc
Controller PID
Fuzzy logic
4-20 mA
Transducer 3-15 psig
Linear
Control valve Equal percentage
Span =30
zero =20
20 50
P (psig)
100 20
0 4
0 p(t), psig 200
What is the gain for each transmitter? What is zero for each
transmitter? What is span for each transmitter?
PV(s) C(s)
H(s)
Process variable Transmitter output
C(s) KT
H(s) = =
PV(s) T s + 1
KT = transmitter gain
T = transmitter time constant
100 20
0 4
0 p(t), psig 200
KT =
(20− 4)mA = 16mA = 0.08mA/ psig
(200− 0)psig 200psig
Or in percent transmitter output (%TO)
KT =
(100− 0)%TO = 0.5%TO/ psig
(200− 0)psig
Gain of a sensor-transmitter is the ratio of the span of the
output signal to the span of variable
Gain of nonlinear transducer
The signal
Pneumatic transmitter 3–15 psi.
electronics -current transmitter 4–20-mA output.
-Voltage transmitter 1-5 volt (VDC)
KT =
(20− 4)mA KT =
(5 −1)Volt
(200− 0)psig (200− 0)psig
KT =
(15− 3)psi
(200− 0)psig
Question
Calibration:
A temperature transmitter with a range of 100 to 350oF