Fire Alarm System

The document describes the FX2200CF range of conventional fire alarm control panels, including the FX2202CF 2-zone panel, FX2204CF 4-zone panel, and FX2208CF 8-zone panel. The panels provide features like one-shot auto-reset user testing, class change contacts, and battery monitoring. They can be surface or semi-flush mounted and include a log book holder. Custom configurations are also available to meet specific project needs. The panels are suitable for a variety of projects and provide discreet design, numerical codes, and easy maintenance.

Uploaded by

pawan
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
Download as pdf or txt
0% found this document useful (0 votes)
76 views10 pages

Fire Alarm System

The document describes the FX2200CF range of conventional fire alarm control panels, including the FX2202CF 2-zone panel, FX2204CF 4-zone panel, and FX2208CF 8-zone panel. The panels provide features like one-shot auto-reset user testing, class change contacts, and battery monitoring. They can be surface or semi-flush mounted and include a log book holder. Custom configurations are also available to meet specific project needs. The panels are suitable for a variety of projects and provide discreet design, numerical codes, and easy maintenance.

Uploaded by

pawan
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 10

Conventional Product Range

FX2200CF Range

FX2202CF - 2 Zone Control Panel

Overview Features
The FX2200CF range of conventional control • 1, 2, 4 or 8 zones panels
panels provide a solution to any conventional • Flexible, high specification
system
system requirement. The advanced features
• Surface or semi-flush
include a simple "one-shot" user test facility, mounting
class change contacts, battery voltage alarms • Simple "one-shot" auto-
and charger temperature compensation, all reset user test facility
included as standard to ensure ease of use • Maintenance free poly
and high reliability. switch circuit protection,
with auto reset
• Class change and
Attention to detail is emphasised by the neat log
programmable fire/fault
book holder feature, allowing essential records
relay as standard
to be stored close to hand, ready for quick
• Custom configured
reference.
versions available to meet
specific project requirements
For larger installations, custom configuration of
the panels offers even greater flexibility, allowing
project specific requirements to be easily met, in Benefits
a competitive and cost effective package.
• Suitable for a large range of
projects
• No fuses required
• Discreet panel design for
incorporation in to any
decor
• Numerical access code
(no lost keys)
• Easy to maintain/service
Conventional Control Panels - FX2200CF Range

Technical Specification
Code FX2202CF FX2204CF FX2208CF
Description 2 Zone Control Panel 4 Zone Control Panel 8 Zone Control Panel
Standards EN54 Pt2: 1997 + A1: 2006 EN54 Pt2: 1997 + A1: 2006 EN54 Pt2: 1997 + A1: 2006
EN53 Pt4: 19197 + A1: 2002 + A2: 2006 EN53 Pt4: 19197 + A1: 2002 + A2: 2006 EN53 Pt4: 19197 + A1: 2002 + A2: 2006
EN50130 Pt4 1996, EN50130 Pt4 EN50130 Pt4 1996, EN50130 Pt4 EN50130 Pt4 1996, EN50130 Pt4
Specification
Number of Zones 2 4 8
Detectors per Zone 32 32 32
Number of Alarm Circuits 2 (4 on FX22002CR) 2 (4 on FX22004CR) 4
Alarm Circuit Load 150mA per circuit, 0.3A total 400mA per circuit, 0.8A total 500mA per circuit, 2A total
End Of Line Devices Detection circuits: EOLM-1 monitoring unit Detection circuits: EOLM-1 monitoring unit Detection circuits: EOLM-1 monitoring unit
Alarm lines: 6.8KΩ resistor Alarm lines: 6.8KΩ resistor Alarm lines: 6.8KΩ resistor
Auxiliary Fire Signal/Fault Output 5A 24V dc single pole changeover contacts 5A 24V dc single pole changeover contacts 5A 24V dc single pole changeover contacts
Auxiliary DC Output No* No* 24V dc fused. 30mA
Repeater Port No* No* Yes
Mains Input Voltage 230V ac -15% +10% 230V ac -15% +10% 230V ac -15% +10%
System Operating Voltage 24V dc 24V dc 24V dc
Standby Duration 24 hours 24 hours 24 hours
Battery (Sealed Lead Acid) 1 x 3.2Ah 1 x 3.2Ah 2 x 3.2Ah
Recharge Period 24 hours 24 hours 24 hours
Environmental
Operating Temperature -5°C to +40°C -5°C to +40°C -5°C to +40°C
Humidity (Non Condensing) 0 to 75% RH 0 to 75% RH 0 to 75% RH
Physical
Construction Polycarbonate housing & back box Polycarbonate housing & back box Polycarbonate housing & back box
Dimensions (H x W x D) Surface: 270mm x 332mm x 90mm Surface: 270mm x 332mm x 90mm Surface: 270mm x 332mm x 90mm
Recessed: 279mm x 332mm x 122mm Recessed: 279mm x 332mm x 122mm Recessed: 279mm x 332mm x 122mm
Weight 5.2kg 5.8kg 6.0kg
Ingress Protection IP30 IP30 IP30
Cable Entry Top: 12x20mm entries with blanking plugs Top: 12x20mm entries with blanking plugs Top: 12x20mm entries with blanking plugs
Rear cable entry aperture Rear cable entry aperture Rear cable entry aperture

* Available on the FX2202CR and FX2204CR

Dimensions
D1
W Description H (mm) W (mm) D1 (mm) D2 (mm)
1 zone 212 260 72 -
2 / 4 / 8 zone 270 332 45 47

H
1 2 3
MUTE
BUZZER

4
SCROLL

5
Description Cut-out (mm)
2 / 4 / 8 zone 265 x327

Note: If surface mounting add D1 and D2 to obtain


depth dimension.
D2

Product Codes
Code Description
FX2202CF Conventional 2 Zone Panel
FX2204CF Conventional 4 Zone Panel
FX2208CF Conventional 8 Zone Panel
FX2202CR Conventional 2 Zone Panel (configured for use with a repeater)
FX2204CR Conventional 4 Zone Panel (configured for use with a repeater)
FXRP2200CF Conventional Repeater Panel
FX22003300 MB Steel Back Box (for use with FX2202CF/4/8)
MFALOG Fire Alarm System Log Book
Conventional Control Panels - FX2200CF Range

6. An alarm line delay feature can be specified


Installation Notes on custom configured versions (except single Repeater Panel
1. A full set of Installation and User Instructions zone panel). Preset delays of 30 seconds to 2 1. Repeater matches the style
is supplied with each panel to assist the minutes can be programmed at the factory. and appearance of main
installer to carry out the work efficiently and Zone LED flashes when fire signal is received control panels.
safely and the user to perform routine tests. and delay is in operation. 2. Facility for signalling to
2. Panels are wall mounted. Surface mounted repeater panel provided as
via 4 x screw fixing holes on back of housing. User Interface standard on 8 zone panel.
Use drill template supplied. Recessed 3. Specially configured
mounting requires appropriate cut-out for 1. Stylish and robust compact panel with simple versions of 2 and 4 zone
steel semi-recessing box, which is screw fixed 5 button keypad control of all functions. panels available for use
to wall. Panel is then screwed to back box 2. Simple "one-shot" weekly user test with auto- with a repeater panel.
via 4 x screw fixing holes (Note: Single zone reset facility. 4. Displays essential
panel cannot be recessed). 3. Comprehensive power, fire and fault LED information at other key
3. Mains power supply cable must be routed via indicators and integral piezo buzzer for on- locations in a large
the designated 20mm conduit entry on the board fire or fault indication. building/site
top or rear of the housing. The mains terminal 4. Battery high/low voltage alarm facility. • Zone fire and fault
block is provided with maintenance free poly 5. Neat log book storage facility behind hinged conditions
switch protection. door. • Test mode in operation
4. Conduit entries are provided on the top of the • Zones or alarm lines in
housing for zone, alarm and output cables. disabled mode
Blanking plugs are supplied for un-used entry Interface Options 5. Repeater panel requires
holes 1. Class change input facility. Terminals provided only a single pair of wires
5. Rear entry apertures are also provided for for switching of alarm circuits to indicate to receive signals from
back entry. school/college class change. main control panel, plus
6. Standby batteries connected via push-on 2. Programmable 5A 24V dc relay for remote local mains power supply,
terminal connectors. signalling of fire or fault conditions. Selectable reducing cost of installation.
7. End of line (EOL) devices are supplied with by jumper link.
the panel and must be fitted at the end of 3. Auxiliary 24V dc output power supply
each detector and alarm circuit wiring. provided as standard on 8 zone panel and 2
8. Front cover is screw fixed. System logbook is and 4 zone configured panels.
stored behind hinged door.
9. Walk test feature permits single person
testing for fast and efficient commissioning Detection Capacity
prior to handover.
1. Up to 32 detectors per zone. End of line
monitoring devices must be fitted and are
System Functionality supplied as standard.
2. Detector circuits are monitored for open
1. Normal and supervisor mode facility. circuit, short circuit and detector removal.
Supervisor mode protected by 4 digit security
code to prevent unauthorised use.
2. Supervisor mode provides access to test Alarm Capacity
mode, where a "one-shot" test facility can be
initiated by the user. When in operation, the 1. 2 separate alarm lines on 1, 2 and 4 zone
user has a period of time in which to put a call panels. Maximum rated load of 150mA
point into fire condition, after which the (1 and 2 zone) or 400mA (4 zone) per line.
system automatically resets and returns to 2. 4 separate alarm lines on 8 zone panel.
normal mode. 500mA maximum load per line.
3. Commissioning walk test feature permits the 3. Alarm lines are monitored for open circuit and
system to be easily tested after installation short circuit faults.
and prior to handover. The panel 4. Additional alarm line facilities on custom 2
automatically resets and returns to normal and 4 zone configured panels.
operation after a detection device has been
tested. Each device can then be tested in turn
via the same procedure.
4. Supervisor mode also provides facility to
disable the following for maintenance or other
purposes
• each detection zone independently
• the alarm circuits
5. Non-latching zone facility can be specified on
custom configured versions (except 1 zone
panel). Enables the direct interconnection of
panels in a simple network.
Conventional Control Panels - FX2200CF Range

Standard Panel Connections - FX2201CF / FX2202CF / FX2204CF

1 1

2 3 2 3
EOLM-1

DETECTORS AND CALLPOINTS


(REFER TO INDIVIDUAL WIRING DIAGRAMS)

END OF LINE
RESISTORS (6K8) DETECTORS AND CALLPOINTS
(REFER TO INDIVIDUAL WIRING DIAGRAMS)

1 1

2 3 2 3 EOLM-1

AS PER
AUXILLARY ZONES 1 & 2
RELAY

L N E + - + - NO C NC + - + - + - + -
CLASS SOUNDER 1 2 3 4
CHANGE CIRCUITS
ZONE CIRCUITS

Standard Panel Connections - FX2208CF

1 1

2 3 2 3 EOLM-1

DETECTORS AND CALLPOINTS


(REFER TO INDIVIDUAL WIRING DIAGRAMS)

END OF LINE RESISTORS (6K8) DETECTORS AND CALLPOINTS


(REFER TO INDIVIDUAL WIRING DIAGRAMS)

1 1

2 3 2 3 EOLM-1

VOLT FREE
NORMALLY
OPEN TO
FAULT AS PER ZONES 1 & 2
CONTACTS REPEATER
RELAY OUTPUT PANEL
F4

F3

F3
L N E NO C NC + - + - + - + - CLASS + - + - + - + - + - + - + - + - + - Tx+ Tx-
F4
AUXILLARY SOUNDER CIRCUITS CHANGE 1 2 3 4 5 6 7 8 24V dc REPEATER
F1 CIRCUIT SUPPLY OUTPUT
ZONE CIRCUITS

Descriptions represent only particulars of the goods to which they apply and do not form part of any contract. The company reserves the right to change specification without prior notification or public announcement.

Cooper Lighting and Safety Ltd, Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB. UK.
T: +44 (0) 1302 303350 l F: +44 (0) 1302 303332 l E: techsupport@cooperfire.com l W: www.cooperfire.com
Fire

Conventional Detectors
CPD321 / CPT341 / CFR330 / CMT360
DATA
CHT390 / MPD821 / MPT951/
SHEET
MFR830 / MMT860 / MHT890 / FXN533
FXN632 / FXN525 / FXN524 / FXN526

Cooper offers a comprehensive range of conventional Benefits and Features


detectors that are compatible with Cooper, Menvier and
JSB conventional control panels. > LPCB 3rd party approved / CPD approved

> Low profile design

> 360° viewable LED design

> Removable detector chamber for cleaning

> Common mounting base

> New enhanced detectors feature dual LEDs,

> Drift compensation and chamber monitoring


(Optical & Photo-Thermal)
Technical Specifications

Model CPD321 / MPD821 CPT341 / MPT951 CFR330 / MFR830 CMT360 / MMT860 CHT390 / MHT890
FXN533 FXN632 FXN525 FXN524 FXN526
Description Optical detector Photo-themal detector Heat detector (fast) Heat detector (med) Heat detector (high)
CPD approved product 0832CPD0633 0832CPD0629 0832CPD0233 0832CPD0236 0832CPD0237
Standards EN54: Pt 7; 2000 EN54: Pt 7; 2000 EN54: Pt 5; 2000 + A1 2002
+ A1 2002 + A1 2002 + A1 2002
EN54 Pt 5; 2000
+ A1 2002
Area coverage 100m² (subject to local standard) 50m² (subject to local standard)
System wiring 2 core
Indication 360° visibility light pipe
Mounting Surface mount CDBB300, FXN520 base
Detetion Mode light scatter principle light scatter principle heat sensitive element
heat sensitive element
Operating voltage 15 to 30 V dc
Max stand by current 30μA
Max Start up current 340μA 340μA NA
Max alarm current 25mA
Heat class NA A2S A2R BS CS
Alarm temperature NA 60°C 60°C 77°C 92°C
Environmental
IP rating IP40
Operating temperature -20°C to 60°C -20°C to 45°C -20°C to 60°C -20°C to 60°C -20°C to 75°C
Humidity 0 to 95% non condensing
EMC CE marked
Physical
Construction ABS
Colour White
Dimensions
Excluding base (Dia x H) 100mm x 43mm
Including base (Dia x H) 100mm x 45mm 101mm x 55mm
Compatibility Conventional fire systems

Wiring Diagram - Standard Conventional Base

+ Remote
+V e Indicator
LED
End of Line Monitor

(optional)
EOLM-1

1 1
+
Conventional
Fire Alarm Panels
Zone 4 4
_
2 2

3 3
-Ve

Earth screen of cable to be continuous between detectors

Product Codes
Conventional optical detector CPD321 / MPD821 / FXN533
Conventional photo-themal detector CPT341 / MPT951 / FXN632
Conventional heat detector (Fast) CFR330 / MFR830 / FXN525
Conventional heat detector (Med) CMT360 / MMT860 / FXN524
Conventional heat detector (High) CHT390 / MHT890 / FXN526
Conventional mounting base CDBB300 / FXN520

Cooper Lighting and Safety


Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB
www.cooperfire.com
Sales Technical Export
T: +44 (0)1302 303 999 T: +44 (0)1302 303 350 T: +44 (0)1302 303 344
F: +44 (0)1302 303 333 F: +44 (0)1302 303 332 F: +44 (0)1302 303 345
E: sales@cooperfire.com E: techsupport@cooperfire.com E: export@cooperfire.com

DS0035a
Fire

Conventional Callpoints
DATA CX201 / CX203
SHEET MBG914 / MBG917
FX201 / FX203

Conventional callpoints are available as both surface / Benefits and Features


flush and weatherproof versions and are approved to
EN54: Pt 13. > Approved to EN54: Pt 11

> Convenient clip fixed front cover

> One key for test and cover removal

> Available as surface / flush and weatherproof (IP67)


Technical Specifications

Model CX201 / MBG914 / FX201 CX203 / MBG917 / FX203


Description Conventional callpoint Conventional callpoint - weatherproof
CPD Approval 0832CPD084 0832CPD085
Configuration CX201 / FX201 and CX203 / FX203 Series resistor 680Ω. MBG914 and MBG917 Series resistor 470Ω
Rating 24V dc
Connection 4-way terminal block
Operating method Glass element with safety film
Test facility Unique key
Enviromental IP42. -10°C to +55°C IP67. -25°C to +55°C
Physical
Construction ABS
Dimensions (W x H x D) 86mm x 86mm x 20mm(S) 53mm(F) 110mm x 110mm x 65mm
Weight 0.19kg 0.29kg

Wiring Diagram - CX201 / FX201 / CX203 / FX203

680 ohm 680 ohm


common common

Wiring Diagram - MBG914 / MBG917

4V7 4V7
470 ohm 470 ohm
common common

Product Codes
Conventional callpoint, surface/flush mounting CX201 / MBG914 / FX201
Conventional callpoint, surface mounting, weatherproof CX203 / MBG917 / FX203
Accessories
Callpoint test keys - pack of 10 MFBGKEY3
Resettable plastic elements - pack of 10 MBGREKIT
Polycarbonate front cover CXCP / MBGHCC
Spare glasses - pack of 5 MBG118 / FX5G
Spare earth continuity links - pack of 5 MBG119
Mounting bezels - pack of 10 MBGBEZ
Spacer plates - pack of 10 MBGSP

Cooper Lighting and Safety


Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB
www.cooperfire.com
Sales Technical Export
T: +44 (0)1302 303 999 T: +44 (0)1302 303 350 T: +44 (0)1302 303 344
F: +44 (0)1302 303 333 F: +44 (0)1302 303 332 F: +44 (0)1302 303 345
E: sales@cooperfire.com E: techsupport@cooperfire.com E: export@cooperfire.com

DS0038a
Fire

Weatherproof version

Conventional Sounder Beacon


DATA FL-RL-R-S / FL-RL-R-D
SHEET MCD524DB
FX004R / FX000WP

This range of sounder beacons are available to Benefits and Features


complement purely audible alarms for use in areas either
where people may be present who have impaired hearing > High output sounder beacon
or areas with high ambient noise levels.
> Sounder and beacon with a single installation point
The device offers an audible and a visual alarm combined
together in one unit and require only a single installation > Unobtrusive low profile design
point. This greatly reduces installation time and cost and
is much less obtrusive than two separate devices. > Volume contol

Beacons have a high light output to maximise the > Lockable base
attention attracting potential of the device.

Lower power LED variants are also available which offer a


lower current consumption but have a consequently lower
light output.
Technical Specifications

Model FL-RL-R-S / FX002CR FL-RL-R-D / MCD524DB / FX000WP


Description Sonder beacon Sonder beacon - weatherproof
Operating voltage 18 to 30V dc
Sound output 101dB(A) at 24V dc
Current consumption 68mA at 24V dc
Environmental rating IP42. -10°C to +55°C IP66. -10°C to +55°C
Physical
Construction Lens - Polycarbonate, Base - ABS
Colour Red
Dimensions (Dia x D) 93mm x 92mm 93mm x 121mm
Weight 0.29kg 0.33kg
Compatibility Conventional fire systems

Product Codes
Conventional sounder beacon FL-RL-R-S / FX002CR
Conventional sounder beacon - weatherproof FL-RL-R-D / MCD524DB / FX000WP

Cooper Lighting and Safety


Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB
www.cooperfire.com
Sales Technical Export
T: +44 (0)1302 303 999 T: +44 (0)1302 303 350 T: +44 (0)1302 303 344
F: +44 (0)1302 303 333 F: +44 (0)1302 303 332 F: +44 (0)1302 303 345
E: sales@cooperfire.com E: techsupport@cooperfire.com E: export@cooperfire.com

DS0040a

You might also like