Manual 3 Phase Power Meter
Manual 3 Phase Power Meter
COM
Al l ri ghts res erved. No pa rts of thi s document ma y be reproduced i n a ny form or by a ny mea ns - gra phi c,
el ectroni c, or mecha ni ca l , i ncl udi ng photocopyi ng, recordi ng, ta pi ng, or i nforma ti on s tora ge a nd retri eva l
s ys tems - wi thout the wri tten permi s s i on of the publ i s her.
Products tha t a re referred to i n thi s document ma y be ei ther tra dema rks a nd/or regi s tered tra dema rks of the
res pecti ve owners . The publ i s her a nd the a uthor ma ke no cl a i m to thes e tra dema rks .
Whi l e every preca uti on ha s been ta ken i n the prepa ra ti on of thi s document, the publ i s her a nd the a uthor
a s s ume no res pons i bi l i ty for errors or omi s s i ons , or for da ma ges res ul ti ng from the us e of i nforma ti on
conta i ned i n thi s document or from the us e of progra ms a nd s ource code tha t ma y a ccompa ny i t. In no event
s ha l l the publ i s her a nd the a uthor be l i a bl e for a ny l os s of profi t or a ny other commerci a l da ma ge ca us ed or
a l l eged to ha ve been ca us ed di rectl y or i ndi rectl y by thi s document.
Publisher
Van Putten Instruments BV
Buitenwatersloot 335
2614 GS Delft
The Netherlands
3
Table of Contents
1 Warning - Read this first 5
2 Introduction 6
3 Product overview 7
4 Quick start 10
5 Measurement 13
6 Installation 14
1 Electrical connection ................................................................................................................................... 14
Single phase..........................................................................................................................................................
two wire with neutral 14
Single phase..........................................................................................................................................................
three wire 14
Single phase..........................................................................................................................................................
two wire without neutral 15
Three phase..........................................................................................................................................................
four wire 16
Three phase..........................................................................................................................................................
three wire delta without neutral 17
Grounded leg service
.......................................................................................................................................................... 17
2 Mechanical installation ................................................................................................................................... 18
3 Selecting Current Transformers
................................................................................................................................... 19
4 Connecting Current Transformers
................................................................................................................................... 20
5 Circuit protection ................................................................................................................................... 21
6 Connecting voltage terminals
................................................................................................................................... 21
8 Specification 50
12 Appendix C - Maintenance 57
1. Only qualified personnel or licensed electricians should install the meter. The
mains voltages of 120 Vac to 600 Vac can be lethal!
2. Follow all applicable local and national electrical and safety codes.
3. Install the meter in an electrical enclosure (panel or junction box) or in a limited
access electrical room.
4. Verify that circuit voltages and currents are within the proper range for the meter
model.
5. Use only current transformers (CTs) with built-in burden resistors, that generate
0.333 Vac (333 millivolts AC) at rated current. Do not use current output (ratio) CTs
such as 1 amp or 5 amp output CTs: they will destroy the meter and may create a
shock hazard. See Current Transformers for CT maximum input current ratings.
6. Ensure that the line voltage inputs to the meter are protected by fuses or circuit
breakers (not needed for the neutral wire). See Circuit Protection for details.
7. Equipment must be disconnected from the HAZARDOUS LIVE voltages before
access.
8. The terminal block screws are not insulated. Do not contact metal tools to the screw
terminals if the circuit is live!
9. Do not place more than one line voltage wire in a screw terminal; use wire nuts
instead. You may use more than one CT wire per screw terminal.
10. Before applying power, check that all the wires are securely installed by tugging on
each wire.
11. Do not install the meter where it may be exposed to temperatures below –30°C or
above 55°C, excessive moisture, dust, salt spray, or other contamination. The meter
requires an environment no worse than pollution degree 2 (normally only non-
conductive pollution; occasionally, a temporary conductivity caused by condensation
must be expected).
12. Do not drill mounting holes using the meter as a guide; the drill chuck can damage
the screw terminals and metal shavings can fall into the connectors, causing an arc
risk.
13. If the meter is installed incorrectly, the safety protections may be impaired.
2 Introduction
Congratulations on your purchase of the 3 Phase Power Meter.
This meter offers precision energy and power measurements in a compact package. It enables you to
make power and energy measurements within existing electric service panels avoiding the costly
installation of subpanels and associated wiring. It is designed for use in demand side management, sub-
metering, and energy monitoring applications. The meter communicates on an RS485 two-wire bus using
the Modbus protocol. Models are available for single-phase, three-phase wye, and three-phase delta
configurations for voltages from 120 VAC to 600 VAC at 50 and 60 Hz.
Great products deserve great user manuals. We have done our best to make this user manual as
complete as possible. New users, please read it carefully to familiarize yourself with our products.
Experienced users can check out the Quick start chapter.
Check the packaging box for any inconsistencies. Should there be any shipping damage, notify the local
carrier. At the same time a report should be submitted to Van Putten Instruments BV, Buitenwatersloot 335,
2614 GS DELFT, The Netherlands.
3 Product overview
Model Type L to N voltage L to L voltage Electrical service types
VPA.8000.Y208 Wye 120 208–240 1 Phase 2 Wire 120V with neutral
1 Phase 3 Wire 120V/240V with neutral
3 Phase 4 Wire Wye 120V/208V with neutral
VPA.8000.Y400 Wye 230 400 1 Phase 2 Wire 230V with neutral
3 Phase 4 Wire Wye 230V/400V with neutral
VPA.8000.D240 Delta 120–140 208–240 1 Phase 2 Wire 208V (no neutral)
or 1 Phase 2 Wire 240V (no neutral)
Wye 1 Phase 3 Wire 120V/240V with neutral
3 Phase 3 Wire Delta 208V (no neutral)
3 Phase 4 Wire Wye 120V/208V with neutral
3 Phase 4 Wire Delta 120/208/240V with
neutral
VPA.8000.D400 Delta 230 400 3 Phase 3 Wire Delta 400V (no neutral)
or 3 Phase 4 Wire Wye 230V/400V with neutral
Wye
VPA.8000.D480 Delta 277 480 3-Phase 3-Wire Delta 480V (No neutral)
or 3-Phase 4-Wire Wye 277/480V
Wye
VPA.8000.Y480 Wye 277 480 Single-Phase 277V with neutral
3-Phase 4-Wire Wye 277/480V
VPA.8000.Y600 Wye 347 600 3 Phase 4 Wire Wye 347V/600V with neutral
The wire count does NOT include ground. It only includes neutral (if present) and phase wires.
A Product information window. Contains product code, production date and serial number.
B Functional ground. This terminal should be connected to earth ground if possible. It is not
required for safety grounding, but ensures maximum meter accuracy.
C Neutral. This terminal “N” should be connected to neutral when available.
D, E, F Line voltage inputs. These terminals connect to the ØA (phase A), ØB (phase B), and ØC
(phase C) electric mains. On wye models the meter is powered from the ØA and N terminals.
On delta models, the meter is powered from the ØA and ØB terminals.
G FCC Mark. This logo indicates that the meter complies with part 15 of the FCC rules.
H CE Marking
I Line voltage measurement ratings. This block lists the nominal line-to-neutral “Ø-N 120V~”
voltage, line-to-line “Ø-Ø 240V~” voltage, and the rated measurement voltage and category
“240V CAT III” for this model. See the Specifications for more information about the
measurement voltage and category.
J Status LEDs. These are status LEDs used to verify and diagnose meter operation. See
Diagnostic LEDs for details.
K Current Transformer (CT) voltage rating. These markings “0.333V~” indicate that the meter
must be used with CTs that generate a full-scale output of 0.333 Vac (333 millivolts).
L DIP switch. This DIP switch block is used to set the Modbus address and baud rate. See
Modbus.
M, N, O Current Transformer (CT) inputs. These indicate CT screw terminals. Note the white and black
circles at the left edge of the label: these indicate the color of the CT wire that should be
inserted into the corresponding screw terminal. The terminals marked with black circles are
connected together internally.
P Auxiliary output terminal. This screw terminal is used for the X terminal options.
Q Modbus common terminal. This is the common or ground terminal for Modbus RS485
communication wiring. It is also the common for the X terminal options if they are installed.
R Modbus signal terminals. These are the RS485 A- and B+ signals (half-duplex, two-wire).
There are several names for these terminals:
· Inverting pin: A-, A, -, TxD-, RxD-, D0, and “B”
· Non-inverting pin: B+, B, +, TxD+, RxD+, D1, and “A”
S Communication status. This LED indicates communication status. See Communication
diagnostics for details.
T Serial number. This shows meter serial number and options if any are selected. The barcode
contains the serial number in Code 128C format.
U Model number. The “Y” or “D” indicates wye or delta models, although delta models can
measure wye circuits (the difference is in the power supply). The “208” (or other value)
indicates the nominal line-to-line voltage.
V Manufacture date. This is the date of manufacture for this meter.
W Caution, risk of electrical shock. This symbol indicates that there is a risk of electric shock
when installing and operating the meter if the installation instructions are not followed
correctly.
X Attention - consult Manual. This symbol indicates that there can be danger when installing and
operating the meter if the installation instructions are not followed correctly.
Symbols
Attention - consult Read, understand, and follow all instructions in this Installation
installation and operation and Operation Manual including all warnings, cautions, and
manual precautions before installing and using the product.
4 Quick start
To set up the Current Transformer (CT) ration and other parameters using Modbus RTU, follow these
instructions.
2. Connect the yellow/green wire to the safety ground terminal (right side in the picture).
3. Connect the “hot” lead to "A" on the power meter (right side in the picture).
4. Connect the “neutral” lead to "N" on the power meter (right side in the picture).
5. Turn on the power by plugging in the power plug into the power outlet. Verify that the status LEDs on
the power meter are on.
6. Turn off the power to the meter before continuing with the Modbus wire connections.
Signal Designation Terminal Strip (ATC converter) Power Meter (upper left side)
Modbus RS485 A 485 - A-
Modbus RS485 B 485 + B+
Modbus Common GND C
Note for the purpose of these instructions, COM 9 is specified. Change it to the COM port that is correct
for your computer per section C of these instructions.
G. Set a unique Modbus address for meters on the same Modbus daisy chain:
1. Remove power to the power meter when setting the Modbus address.
2. Use the DIP switches to set a unique Modbus address on each meter that is on a daisy chain. See
“Setting the Modbus Address in section 7.1.
Basic configuration
If you are planning on using demand measurements and you don’t want to use the default 15 minute
interval, you should set the DemPerMins as well.
Verify operation
You should be able to read several registers to check that the meter is correctly installed and measuring
power and energy. If your Modbus software supports floating point Modbus registers, you may want read
from the set Basic Register List - Floating Point. If you cannot easily read floating point values, use Basic
Register List - Integer instead. Verify registers in the following sequence:
· Freq (power line frequency): should be near 50 or 60 Hz (or 500 or 600 if you are reading the integer
registers).
· VoltA, VoltB, VoltC: should match your line-to-neutral voltage.
· PowerA, PowerB, PowerC: should be positive (unless you are measuring something that can generate
power like a PV system) and in a reasonable range for the load being measured (make sure your load is
ON). Note: the integer power registers are scaled, so if you expect to see 75,000 W (75 kW) and instead
you see 7500, that is probably because the meter is reporting integer power in 10 W increments. See
PowerIntScale for details.
· ErrorStatus: this will return 0 if there are no errors. If you see any non-zero values, write them down and
check the Diagnostic Registers section below to determine the problem. If you are measuring floating
point values and the numbers are way off, your software may be combining the floating point registers in
the wrong order. Compare the values to the integer registers and check to see if your software has an
option like “Float - swapped” or “Float - reversed”; if so, see if this fixes the problem.
· If you don’t get reasonable results, check Appendix B - Measurement Troubleshooting.
5 Measurement
The 3 Phase Power Meter measures the following:
· True RMS Power - Watts (Phase A, Phase B, Phase C, Sum)
· Reactive Power - VARs (Phase A, Phase B, Phase C, Sum)
· Power Factor (Phase A, Phase B, Phase C, Average)
· True RMS Energy - Watthours (Phase A, Phase B, Phase C, Sum)
· Reactive Energy - VAR-hours (Sum)
· AC Frequency
· RMS Voltage (Phase A, Phase B, Phase C)
· RMS Current (Phase A, Phase B, Phase C)
· Demand and Peak Demand
One 3 Phase Power Meter can measure up to three different “single-phase two-wire with neutral” branch
circuits from the same service by separately monitoring the phase A, B, and C values. If necessary, you can
use different CTs on the different circuits.
Measurement overview
The meter performs measurements every one second. The measurements are used to update three types
of registers:
· Energy registers: These accumulate up (or sometimes down) based on the consumed energy during
each measurement period. Energy values are preserved across power failures.
· Instantaneous registers: These are non-accumulating values, like power, volts, current, etc. These are
not preserved across power failures.
· Demand registers: these accumulate data from each measurement, but the reported demand values
only update at the completion of a demand interval (or subinterval), which is typically every 15 minutes.
Only the peak demand values are preserved across power failures.
6 Installation
Summary
1. Mount the meter.
2. Turn off power before installing solid-core (non-opening) CTs or making voltage connections.
3. Mount the CTs around the line voltage conductors being measured. Take care to orient the CTs facing
the source of power.
4. Connect the twisted white and black wires from the CT to the six position black terminal block on the
meter, matching the wire colors to the white and black dots on the front label.
5. Connect the voltage wires including ground and neutral (if present) to the green terminal block, and
check that the current (CT) phases match the voltage measurement phases.
6. Set the Modbus network address and baud rate with the DIP switches.
7. Connect the output terminals of the meter to the monitoring equipment.
8. Apply power to the meter.
9. Verify that the LEDs light correctly and don’t indicate an error condition.
Recommended models
The following table shows the models that should be used, depending on the line to neutral voltage.
Recommended models
The following table shows the models that can be used. If neutral may or may not be present, you should
use the VPA.8000.D240 (see Single-Phase Two-Wire without Neutral). If neutral is present, it must be
connected for accurate measurements. If phase B may not be present, you should use the VPA.8000.Y208
(see Single-Phase Two-Wire with Neutral).
For best accuracy, we recommend connecting the N (neutral) terminal to the ground terminal. This will not
cause ground current to flow because the neutral terminal does not power the meter.
Recommended model
This configuration is normally measured with the following model.
If neutral is available, you may also use the VPA.8000.Y208 model. If you use the VPA.8000.Y208, you will
need to hook up the meter as shown in section Single-Phase Three- Wire and connect neutral. You will
need two CTs.
If one of the conductors (phase A or phase B) is grounded, see Grounded Leg Service for
recommendations.
Recommended models
The following table shows the models that should be used, depending on the line-to-neutral voltage and
line-to-line voltage (also called phase-to-phase voltage).
Note: you may also use the following delta models to measure three-phase four-wire wye circuits. The only
difference is that delta models are powered from ØA and ØB, rather than N and ØA. If neutral is present, it
must be connected for accurate measurements.
For best accuracy, we recommend connecting the N (neutral) terminal to earth ground. This will not cause
ground current to flow because the neutral terminal is not used to power the meter.
Recommended models
The following table shows the models that should be used, depending on the line-to-line voltage (also
called phase-to-phase voltage).
The meter will correctly measure services with a grounded leg, but the measured voltage and power for the
grounded phase will be zero and the status LED will not light for whichever phase is grounded, because
the voltage is near zero. Also, one or both of the active (non-grounded) phases may indicate low power
factor because this type of service results in unusual power factors.
For optimum accuracy with a grounded leg, you should also connect the N (neutral) terminal on the meter
to the ground terminal; this will not cause any ground current to flow because the neutral terminal is not
used to power the meter. If you have a grounded leg configuration, you can save money by removing the CT
for the grounded phase, since all the power will be measured on the non-grounded phases. We
recommend putting the grounded leg on the ØB or ØC inputs and attaching a note to the meter indicating
this configuration for future reference.
The meter has two mounting holes spaced 5.375 inches (137 mm) apart (center to center). These
mounting holes are normally obscured by the detachable screw terminals. Remove the screw terminals by
pulling outward while rocking from end to end. The meter may be used as a template to mark mounting
hole positions, but do not drill the holes with the meter in the mounting position because the drill may
damage the connectors and leave drill shavings in the connectors.
You may mount the meter with the supplied #8 self-tapping sheet metal screws using 1/8 inch pilot hole
(3.2 mm). If you use screws, avoid over-tightening which can crack the case. If you don’t use the supplied
screws, the following sizes should work (bold are preferred); use washers if the screws could pull through
the mounting holes
We only offer CTs that measure AC current, not DC current. Significant DC current can saturate the CT
magnetic core, reducing the AC accuracy. Most loads only have AC current, but some rare loads draw DC
current, which can cause measurement errors.
CTs can measure lower currents than they were designed for by passing the wire through the CT more
than once. For example, to measure currents up to 1 amp with a 5 amp CT, loop the wire through the CT
five times. The CT is now effectively a 1 amp CT instead of a 5 amp CT. The effective current rating of the
CT is the labelled rating divided by the number of times that the wire passes through the CT.
If you are using the measurement phases of the meter (ØA, ØB, and ØC) to measure different circuits, you
can use CTs with different rated current on the different phases. Instead of setting one CtAmps value for all
phases, you can use different values for each phase: CtAmpsA, CtAmpsB, and CtAmpsC.
High current crest factors are usually not an issue when metering whole building loads, but can be a
concern when metering individual loads with high current crest factors. If the peak current is too high, the
meter’s CT inputs can clip, causing inaccurate readings.
This means that when measuring loads with high current crest factors, you may want to be conservative in
selecting the CT rated current. For example, if your load draws 10 amps RMS, but has a crest factor of 3.0,
then the peak current is 30 amps. If you use a 15 amp CT, the meter will not be able to accurately measure
the 30 amp peak current. Note: this is a limitation of the meter measurement circuitry, not the CT.
The following graph shows the maximum RMS current for accurate measurements as a function of the
current waveform crest factor. The current is shown as a percentage of CT rated current. For example, if you
have a 10 amp load with a crest factor of 2.0, the maximum CT current is approximately 85%. Eighty-five
percent of 15 amps is 12.75, which is higher than 10 amps, so your measurements should be accurate.
On the other hand, if you have a 40 amp load with a crest factor of 4.0, the maximum CT current is 42%.
Forty-two percent of a 100 amp CT is 42 amps, so you would need a 100 amp CT to accurately measure
this 40 amp load.
You frequently won’t know the crest factor for your load. In this case, it’s generally safe to assume the crest
factor will fall in the 1.4 to 2.5 range and select CTs with a rated current roughly 150% of the expected RMS
current. So if you expect to be measuring currents up to 30 amps, select a 50 amp CT.
To connect CTs, pass the wire to be measured through the CT and connect the CT to the meter. Always
remove power before disconnecting any live wires. Put the line conductors through the CTs as shown in
the section Electrical connection. You may measure generated power by treating the generator as the
source.
For solid-core CTs, disconnect the line voltage conductor to install it through the CT opening.
Split-core and bus-bar CTs can be opened for installation around a wire by puling the removable section
straight away from the rest of the CT or unhooking the latch; it may require a strong pull. Some CT models
include thumb-screws to secure the opening. The removable section may fit only one way, so match up the
steel core pieces when closing the CT. If the CT seems to jam and will not close, the steel core pieces are
probably not aligned correctly; DO NOT FORCE together. Instead, reposition or rock the removable portion
until the CT closes without excessive force. A nylon cable tie can be secured around the CT to prevent
inadvertent opening.
Some split-core CT models have flat mating surfaces. When installing this type of CT, make sure that
mating surfaces are clean. Any debris between the mating surfaces will increase the gap, decreasing
accuracy.
Next, connect the CT lead wires to the meter terminals labelled ØA CT, ØB CT, and ØC CT. Route the
twisted black and white wires from the CT to the meter. We recommend cutting off any excess length to
reduce the risk of interference. Strip 1/4 inch (6 mm) of insulation off the ends of the CT leads and connect
to the six position black screw terminal block. Connect each CT lead with the white wire aligned with the
white dot on the label, and the black wire aligned with the black dot. Note the order in which the phases are
connected, as the voltage phases must match the current phases for accurate power measurement.
Finally record the CT rated current as part of the installation record for each meter. If the conductors being
measured are passed through the CTs more than once, then the recorded rated CT current is divided by
the number of times that the conductor passes through the CT.
A Red Green Red Green Red Green Red Green Red Green Red Green
B Red Green Red Green Red Green Red Green Red Green Red Green
C Red Green Red Green Red Green Red Green Red Green Red Green
1.0 sec
The Modbus protocol is a master/slave protocol, with only one master and many slaves. The meter is
always a slave device, and responds only when queried.
Modbus functions
In most cases, your Modbus software will automatically use the correct Modbus command for any action
you wish to perform, so you may be able to skip this section. The Modbus specifications list numerous
possible commands, but the meter only supports the following:
· 03 (0x03) - Read Holding Registers: Holding registers can be read and written and are intended for
configuration values, but the meter treats input registers and holding registers interchangeably, so you
can use functions 04 or 03 to read any registers.
· 04 (0x04) - Read Input Registers: Input registers are generally read-only and report power, energy, and
related values. The meter treats input registers and holding registers as interchangeable, so you can
use functions 04 or 03 to read any registers.
· 06 (0x06) - Write Single Register: This writes a new value to a single register.
· 16 (0x10) - Write Multiple Registers: This writes a new value to a range of registers.
Other functions will result in Modbus exception 01 - Illegal Function Code.
Baud rates
The standard baud rates are 9,600 and 19,200 baud, and rates from 1,200 to 38,400 baud can be
configured by writing to the communication registers.
Communication parameters
The communication always uses 8 data bits and one stop bit. The parity defaults to none but can be
changed to even by writing to the communication registers.
Specification
Baud Rates 1200, 2400, 4800, 9600, 19200, 38400
Duplex Half (two-wire plus common)
Polarity Auto-detect Will automatically correct swapped A- and B+
terminals provided network has at least 200 millivolt
bias between A- and B+
Parity: Standard: N81 (no parity, eight data bits, one stop
bit)
Configurable: E81 (even parity, eight data bits, one
stop bit)
Modbus Buffer 256 bytes
Communication Response Time 5 - 25 milliseconds (may be longer immediately
after a Modbus write command while values are
saved to non-volatile memory)
RS485 interface
RS485 Output Isolation 4500 Vac RMS
Driver Output Voltage (Open Circuit) ±6 Vdc maximum Driver Output Voltage (54 Ω load):
±1.5 Vdc minimum Driver Output Current (54 Ω
load): ±60 mA typical
The meter supports Modbus addresses from 1 to 127 using the DIP switch. Address 0 is used for
broadcast messages and is not a valid address. As shipped from the factory, the
meter will be configured with an address of 0, which is invalid and will prevent any communication and
cause the “Com” LED to light solid red.
Set the Modbus address by switching DIP switch positions 1-7, each of which adds a different value to the
address. The change will take effect immediately.
DIP Switch 1 2 3 4 5 6 7
Up (1) Value 1 2 4 8 16 32 64
Address examples
For example, if DIP switch positions 3 and 5 are in the 1 (up) position and the rest are 0 (down), the
resulting Modbus address is 4 + 16 = 20.
Once you are communicating with the meter, you can change the address using either the DIP switches or
the Address(1652) register.
Setting all DIP switch positions to zero for ten seconds resets all communication settings to the factory
configuration.
19,200 1 (up)
7.1.1 Wiring
Connecting Modbus outputs
The meter communicates using a serial RS485 interface. The meter uses half-duplex two-wire (plus
common) communication, so the same pair of wires is used for sending AND receiving. Up to 127 devices
can be connected together on the same RS485 bus (or up to 247 devices if you assign Modbus addresses
using the Address register).
Length limits
Under ideal conditions, using cable with a 120 ohm impedance and proper termination, it should be
possible to run RS485 signals 1200 m (4000 ft) at up to 19,200 baud. However, a number of factors can
reduce this range, including electrical and magnetic interference (EMI), bus loading, poor termination, etc.
Repeaters are available to extend the range if necessary.
If it isn’t convenient to daisy-chain the main RS485 bus to each meter, you may use stubs or branches.
Long stubs or branches, greater than 30 m (100 ft), may cause signal reflections and should be avoided.
Termination
Networks shorter than 500 m (1650 ft) should not need termination. Longer networks and networks in
electrically noisy environments may need termination at both ends of the bus with 120 ohm resistors
between the “A-” and “B+” terminals. Generally, you will put one termination resistor at the PC or monitoring
device and one at the meter farthest from the monitoring device.
Some RS485 PC interfaces include jumpers or switches to provide internal termination at one end of the
bus.
In some cases, termination can cause problems. It dramatically increases the load on the bus, so that
some RS485 PC interfaces cannot handle the load (particularly port powered ones). Also, adding 120 ohm
termination resistors may require the addition of bias resistors (see next section).
Biasing
RS485 networks frequently use bias resistors to hold the bus in a “high” or logic 1 state when no devices
are transmitting. In this state, the Modbus “A-“ terminal is more negative than the “B+” terminal. Without
bias resistors, the bus can float and noise can appear as bogus data.
The meter uses an RS485 failsafe transceiver that eliminates the need for bias resistors except in noisy
environments. Furthermore, many RS485 PC interfaces include internal bias resistors, so it is rare to need
to add bias resistors.
If you determine that your network is experiencing noise problems, then you may want to add termination
and possibly bias resistors.
Wiring
Once you’ve planned the network and strung the cable, you can connect the meters.
· The Modbus terminals (A-, B+, C, and X) are completely isolated (4500 Vac RMS isolation) from
dangerous voltages, so you can connect them with the meter powered. They are also isolated from the
meter’s earth ground and neutral connections.
· When connecting meters to a PC or monitoring device, connect all “A-” terminals together, all “B+”
terminals together, and all “C” (common) terminals together. In most cases, if you swap “A-” and “B+”,
Modbus meters can auto-detect the polarity and communicate correctly. Note: if your RS485 network isn’t
properly biased (one terminal more positive than the other), then the auto-detect feature will not work.
· You may put two sets of wires in each screw terminal to make it easier to daisy-chain the network from
one device to the next. If you do this, we recommend that you twist the wires tightly together before putting
them into the screw terminal to ensure that one wire doesn’t pull free, causing communication
problems.
· If you are using shielded cable, you may use the shield to provide the Modbus common “C” connection
between all devices on the network.
· Connect the cable shield or Modbus common (if there is no shield) to earth ground at just the Modbus
master end of the cable. Grounding both ends can cause ground loops. Leaving the common floating
risks damaging the RS485 circuitry.
Modbus idle
Whenever the Modbus network is idle, the Com LED will stay off.
If you see this indication, make sure there are not two meters with the same Modbus address. You may
want to disconnect all but one meter to see if the problem goes away.
Invalid request
If the meter receives a valid packet, but with an invalid request (see below), Green Off
then the meter will respond with a Modbus exception message and store
an error in the ErrorStatus(1712-1723) registers. Because the packet was 0.2 sec
valid, Com LED will flash green for 200 milliseconds.
Modbus exceptions
If the meter receives an invalid request, it will reply with a Modbus exception code. In most cases, your PC
software should be able to display the code, which should help you determine the problem. For more
information about the problem, check the ErrorStatus(1712-1723) registers, which will provide more
detailed error codes.
· 01 - Illegal function code
o ErrorStatus 213: The Modbus function code is not supported by the meter, such as 07 Read Exception
Status.
· 02 - Illegal data address
o ErrorStatus 206: Attempted to read an invalid register address or write to a read-only register. This is
common if your addresses are off by one or you request extra registers.
o ErrorStatus 203: A partial 32 bit write (a dual register like ConfigPasscode) was aborted by a write to
an unrelated register.
· 03 - Illegal data value
o ErrorStatus 202: When changing the ConfigPasscode, the confirmation entry didn’t match the first
entry.
o ErrorStatus 205: Invalid ConfigPasscode value entered. You will have to wait five seconds to try again.
o ErrorStatus 207, 208: An attempt was made to write an illegal data value to a register.
o ErrorStatus 211, 212: The Modbus packet contained an invalid count of registers or an invalid byte
count.
· 04 - Slave device failure
o ErrorStatus 200: The correct ConfigPasscode must be entered before changing configuration
registers, or resetting the energy or demand registers.
o ErrorStatus 19, 20, 72, 79, 80, 215: Internal hardware failure.
o ErrorStatus 67: Calibration data lost. The meter will report a slave device failure until it is calibrated.
· 06 - Slave device busy
o ErrorStatus 209: Attempts to unlock the configuration with ConfigPasscode are locked out for five
seconds after entering an invalid passcode.
Diagnostic registers
If Modbus communications are working, but with intermittent problems, check the following diagnostic
registers (see Diagnostic Registers for details): ErrorStatus(1712-1723), CrcErrorCount(1712),
FrameErrorCount(1713), PacketErrorCount(1714), OverrunCount(1715).
7.1.3 Registers
This section lists the Modbus registers. The following sections provide detailed information about each
register. The registers are grouped as follows:
Register category Data type
Basic registers Floating point
Basic registers Integer
Advanced registers Floating point
Advanced registers Integer
Configuration registers Integer
Customer diagnostic registers Integer
Most of the integer registers are 16 bit signed integers that can report positive or negative values from -
32,768 to +32,767. In a few special cases, such as the energy registers, we use 32 bit signed integer
registers (sometimes called “long integer”), which use two adjacent Modbus registers and can report
values up to approximately ± two billion.
Floating point values can report positive or negative values with typically six or seven significant digits,
which is far higher than the meter’s accuracy. However, for energy measurements (kWh), floating point
values have a limitation: the effective resolution in kWh gets lower as more energy accumulates. If the total
energy exceeds 100,000 kWh, the resolution of the floating point energy will become coarser than 0.1 kWh,
the constant resolution of the integer energy values. At a total energy of 1,000,000 kWh, the floating point
energy resolution becomes 1.0 kWh.
underlying 32 bit register may be updated between the two read commands, resulting in an inconsistent
or scrambled value.
· When writing to 32 bit registers, the recommended approach is to use the Write Multiple Registers (16)
command to update both registers at the same time. However, meter incorporates logic to allow two
Write Single Register (06) commands within 30 seconds, provided no other Modbus commands are
issued between the two writes.
1205 - 1206 EnergySumNR * 0.1 kWh Total net (bidirectional) energy non
resettable
1207 - 1208 EnergyPosSumNR * 0.1 kWh Total positive energy non resettable
Power registers
1209 PowerSum PowerIntScale Real power, sum of active phases
1210 PowerA PowerIntScale Real power, phase A
1211 PowerB PowerIntScale Real power, phase B
1212 PowerC PowerIntScale Real power, phase C
Voltage registers
1213 VoltAvgLN 0.1 V Average line to neutral voltage
1214 VoltA 0.1 V RMS voltage, phase A to neutral
1215 VoltB 0.1 V RMS voltage, phase B to neutral
1216 VoltC 0.1 V RMS voltage, phase C to neutral
1217 VoltAvgLL 0.1 V Average line to line voltage
1218 VoltAB 0.1 V RMS voltage, line to line, phase A to B
1219 VoltBC 0.1 V RMS voltage, line to line, phase B to C
1220 VoltAC 0.1 V RMS voltage, line to line, phase A to C
Frequency register
1221 Freq 0,1 Hz Power line frequency
*These registers are preserved across power failures.
†These registers support resetting or presetting the value.
Energy registers
Commonly known as kWh (kilowatt-hours), the energy is the integral of power over time. Many installations
will only use the energy measurement. It is commonly used for billing or sub-metering. Because energy is
an accumulated value, it can be used on networks that are accessed infrequently (like a utility meter that
only needs to be read once a month). All energy register values are preserved through power failures.
In the meter, most energy registers can be reset to zero by writing “1” to the ZeroEnergy register. They can
also be set to zero or a preset value by writing the desired value directly to each register. All energy
registers ending with “NR” (for non-resetting) cannot be reset to zero for billing security. You can protect all
energy registers from being zeroed or preset by setting a ConfigPasscode.
All energy registers wrap around to zero when they reach 100 gigawatt-hours (100 x 109 watt- hours) or
negative 100 gigawatt-hours (only some energy registers allow negative values).
During a power outage, the energy consumed will not be measured. Whenever the line voltage drops
below 60–80% of nominal, the meter will shut down until power is restored. To preserve the energy
measurement across power outages, the meter writes the energy to non-volatile (ferroelectric RAM)
memory every second. When power returns, the last stored value is recovered.
EnergySum, EnergySumNR
EnergySum is the net real energy sum of all active phases, where “net” means negative energy will
subtract from the total. This value is appropriate for net metering applications (i.e. photovoltaic) where
you wish to measure the net energy in situations where you may sometimes consume energy and other
times generate energy. Use EnergyPosSum instead if you don’t want negative energy to subtract from
the total.
EnergyPosSum, EnergyPosSumNR
EnergyPosSum is equivalent to a traditional utility meter that can only spin in one direction. Every second,
the measured real energies for each active phase are added together. If the result is positive, it is added
to EnergyPosSum. If it is negative, then EnergyPosSum is left unchanged.
Power registers
PowerA, PowerB, PowerC
The meter measures real power (watts) for each phase (PowerA, PowerB, PowerC). The measured
power is generally positive, but may also be negative, either because you are generating power (such as
with solar panels), or because the meter isn’t connected properly.
The integer power registers are scaled by PowerIntScale to prevent overflow. The integer power registers
can only report values from -32767 to +32767. To allow for large power values, PowerIntScale acts as a
multiplier to multiply by 1, 10, 100, or 1000. See Configuration Registers for details. To scale the integer
PowerA, PowerB, PowerC, or PowerSum to watts, use the following equation:
For example, if PowerIntScale (1609) is 100, and the integer PowerSum (1209) reports 2500, then the
power sum is 2500 * 100 = 250,000 W (or 250 kW).
PowerSum
This is the sum of the real power for active phases (line voltage above 20% of nominal). This can include
negative values, so if one phase is negative, it will reduce the reported PowerSum.
Voltage registers
All integer voltage registers are reported in units of 0.1 VAC, so 1234 = 123.4 VAC.
VoltAvgLN
This is the average line-to-neutral voltage (average of VoltA, VoltB, and VoltC). Only active phases are
included (phases where the voltage is above 20% of nominal).
VoltAvgLL
This is the average line-to-line voltage (average of VoltAB, VoltBC, and VoltAC). All phases are included in
the average.
Frequency
Freq
The meter measures the AC line frequency in Hertz. The integer Freq register reports the frequency in
units of 0.1 Hz. All phases must have the same line frequency; otherwise this value will be erratic or
incorrect.
These values are reset to zero when “1” is written to the ZeroEnergy register. You may also reset them to
zero or load preset values by writing to these registers.
Positive energy
EnergyPosA, EnergyPosB, EnergyPosC
The per-phase positive energy registers measure the positive real energy for each phase. Negative
energy is ignored (instead of subtracting from the total). Energy is measured once per second, so the
determination of whether the energy is positive is based on the overall energy for the second.
These values are reset to zero when “1” is written to the ZeroEnergy register. You may also reset them to
zero or load preset values by writing to these registers.
Negative energy
The negative energy registers are exactly like the positive energy registers except they accumulate negative
energy. The reported energy values will be positive. In other words, if meter measures 1000 kWh of
negative energy, EnergyNegSum will report 1000 (not -1000).
The negative energy registers are reset to zero (except for EnergySumNegNR) when “1” is written to the
ZeroEnergy register. You may also reset them to zero or load preset values (except for EnergySumNegNR)
by writing to these registers.
EnergyNegSum
Every second, the measured real energies for each active phase are added together. If the result is
negative, it is added to EnergyNegSum. If it is positive, then EnergyNegSum is left unchanged.
EnergyNegSumNR
The EnergySumNegNR is identical to EnergyNegPos except that it cannot be reset to zero.
Reactive energy
EnergyReacSum, EnergyReacA, EnergyReacB, EnergyReacC
Reactive energy is also known as kVAR-hours. Inductive loads, like motors, generate positive reactive
power and energy, while capacitive loads generate negative reactive energy. These are all bidirectional
registers that can count up or down depending on the sign of the reactive power.
The meter only measures the fundamental reactive energy, not including harmonics.
These values are reset to zero when “1” is written to the ZeroEnergy register. You may also reset them to
zero or load preset values by writing to these registers.
Apparent energy
EnergyAppSum, EnergyAppA, EnergyAppB, EnergyAppC
Apparent energy (kVA-hours) is the accumulation of apparent power over time. The apparent power is
essentially the RMS voltage multiplied by the RMS current for each phase. For example, if you have 120
VAC RMS, 10 amps RMS, one phase, the apparent power will be 1200 VA. At the end of an hour, the
apparent energy will be 1.2 kVA-hour. Apparent energy is always positive.
The meter’s apparent energy includes real harmonics, but not reactive harmonics.
These values are reset to zero when “1” is written to the ZeroEnergy register. You may also reset them to
zero or load preset values by writing to these registers.
Power factor
The power factor is the ratio of the real power to the apparent power. Resistive loads, like incandescent
lighting and electric heaters, should have a power factor near 1.0. Power-factor corrected loads, like
computers, should be near 1.0. Motors can have power factors from 0.2 to 0.9, but are commonly in the 0.5
to 0.7 range.
If the power for a phase is negative, the power factor will also be negative. The reported power factor will be
1.0 for any phases measuring zero power, and will be 0.0 for any inactive phases (line voltage below 20%
of nominal VAC).
The meter measures the displacement or fundamental power factor, which does not include harmonics.
Integer power factor registers are reported in units of 0.01, so 85 equals a power factor of 0.85.
PowerFactorAvg
This is the average power factor, computed as PowerSum / ApparentPowerSum.
Reactive power
Reactive power is also known as VARs. Inductive loads, like motors, generate positive reactive power,
while capacitive loads generate negative reactive power. Reactive power transfers no net energy to the load
and generally is not metered by the utility. Loads with high reactive power relative to the real power will tend
to have lower power factors. The integer reactive power registers are scaled by PowerIntScale.
The meter only measures the fundamental reactive power, not including harmonics.
To scale the integer PowerReacA, PowerReacB, PowerReacC, or PowerReacSum to VARs, use the
following equation:
For example, if PowerIntScale (1609) is 100, and the integer PowerReacSum (1343) reports 1500, then the
reactive power sum is 1500 * 100 = 150,000 VAR (or 150 kVAR).
PowerReacSum
The PowerReacSum is the sum of the reactive power of active phases. This can include negative values,
so if one phase is negative, it will reduce the reported PowerReacSum.
Apparent power
Apparent power (VA) can be described three ways:
· The RMS voltage multiplied by the RMS current.
· The square root of the real power squared plus the reactive power squared.
· The absolute value or magnitude of the complex power.
The meter’s measurement of apparent power includes real, but not reactive harmonic apparent power
content.
Apparent power is always a positive quantity. The integer apparent power registers are scaled by
PowerIntScale.
PowerAppSum
The PowerAppSum is the sum of apparent power for active phases.
Current
The meter estimates the RMS current for each phase. This is an indirect measurement and does not
include all harmonic content, so the current is not as accurate as the power and energy measurements.
The floating point current registers are in units of amps. The integer current registers are in scaled amps
(CurrentIntScale, default value 20000), so the following equations will convert to amps.
For example, with 200 amp current transformers and CurrentIntScale = 20000, if CurrentAInt (1351)
reports 5000, the actual current is 5000 * 200 / 20000 = 50.00 amps.
Demand
Demand is defined as the average power over a specified time interval. Typical demand intervals are 5, 10,
15 (default), 30, 60, etc. up to 720 minutes, but the meter supports arbitrary demand intervals from 1 to 720
minutes (12 hours). The meter records the peak demand for metering applications where the
measurements may only be accessed weekly or monthly.
Since the meter can measure bidirectional power (positive and negative), and the demand is the average
power over an interval, demand can also be positive or negative. This is only likely to occur with something
like a grid-tied PV system, where you may put energy back into the grid at certain times of the day (negative
power). In this case, you would see negative demand. If you have both positive and negative power during a
demand interval, both the positive and the negative data will be averaged together, such that the negative
power subtracts from the positive, reducing the overall demand.
The meter also supports rolling demand (also called “sliding window”), in which the demand intervals are
evenly divided into a fixed number of subintervals. At the end of each subinterval, the average power over
the demand interval is computed and output. This results in better accuracy, especially for demand peaks
which would not have lined up with the demand interval without subintervals. On power up, the demand
measurements will report zero until one full demand interval is completed. From 1 to 10 subintervals are
supported. A subinterval count of one (or zero) results in the standard demand measurement without
rolling demand. See Configuration Registers for information on configuring the demand.
To manually zero some or all of the demand registers, see the ZeroDemand register in Configuration
Registers.
The floating point demand registers are reported in units of watts, while the integer demand registers must
be scaled by PowerIntScale to compute watts. To scale the integer Demand, DemandA, DemandB,
DemandC, DemandMin, DemandMax, or DemandApp, use the following equation:
For example, if PowerIntScale (1609) is 100, and the integer Demand (1354) reports 4700, then the
demand is 4700 * 100 = 470,000 watts (or 470 kW).
Demand
The Demand register is updated at the end of every subinterval with the average PowerSum over a full
demand interval. After a power cycle or configuration change, Demand will report zero until the
completion of one full demand interval.
DemandMin
The DemandMin is the smallest measured Demand (this may be negative for systems with power
generation). It is preserved across power failures and can be reset with the ZeroDemand register. Note:
there are no minimum or maximum demand registers for DemandA, DemandB, and DemandC.
DemandMax
The DemandMax is the largest measured Demand. It is preserved across power failures and can be reset
with the ZeroDemand register.
DemandApp
DemandApp is computed the same way as Demand, but using apparent power.
7.1.3.3 Configuration register list
You can read the ConfigPasscode register to determine if the meter is locked. You cannot read the
actual passcode itself. If you lose your passcode, contact support for assistance.
· 0 - Unlocked
· 1 - Locked
Invalid unlock attempts will result in the Modbus exception 03 - “Illegal data value”, and prevent more
attempts for five seconds. An unlocked meter will become locked again after five minutes or when “1” is
written twice to ConfigPasscode.
The passcode can be set (or changed) by writing the new passcode to ConfigPasscode twice within 30
seconds. If a passcode is already set, the meter must be unlocked first.
The passcode is a 32 bit value, so both register locations 1601 and 1602 must be written when
unlocking the meter or setting a passcode.
CtAmps (1603)
Writing the CtAmps register is a shortcut to quickly set CtAmpsA, CtAmpsB, and CtAmpsC to the same
value. If you read CtAmps and CtAmpsA, CtAmpsB, CtAmpsC are all identical, then CtAmps will return
the common value; otherwise it will return 0 (zero) to indicate there is no common value.
The specified rated CT amps for each phase (CtAmpsA, CtAmpsB, and CtAmpsC), affect the scaling
CurrentIntScale for the integer current registers CurrentA, CurrentB, and CurrentC. See section Current
above for details.
CtDirections (1607)
On occasion, current transformers are installed with the label “This side towards source” facing the load
instead of the source, or with the white and black wires swapped at the meter. If the electrical installer
notices this, they can fix it, but sometimes the problem isn’t noticed until the electrician is gone and
some or all of the reported power values are unexpectedly negative.
You can correct this with the CtDirections register:
· 0 - All CTs normal
· 1 - Flip phase A CT
· 2 - Flip phase B CT
· 4 - Flip phase C CT
· 3 - Flip phase A CT and flip phase B CT
· 5 - Flip phase A CT and flip phase C CT
· 6 - Flip phase B CT and flip phase C CT
· 7 - Flip all CTs (A, B, and C)
Flipping a CT with CtDirections will also reverse the status LED indications. So if the status LED for a
phase was flashing red and you flip the CT with CtDirections, the LED will change to green flashing. This
cannot be used to correct for situations where CT phases do not match the voltage phases, such as
swapping phases A and B on the current transformer inputs.
Averaging (1608)
The meter includes averaging for these registers: PowerSum, PowerA, PowerB, PowerC, VoltAvgLN,
VoltA, VoltB, VoltC, VoltAvgLL, VoltAB, VoltBC, VoltAC, Freq, PowerFactorAvg, PowerFactorA,
PowerFactorB, PowerFactorC, PowerReacSum, PowerReacA, PowerReacB, PowerReacC,
PowerAppSum, PowerAppA, PowerAppB, PowerAppC, CurrentA, CurrentB, CurrentC.
Averaging is beneficial because it reduces measurement noise, and if the meter is being polled less
often than once a second (say once a minute), then the average over the last minute provides a more
accurate reading than just the data from the last second, which might be randomly high or low. Averaging
is configured by setting the Averaging (1608) register to one of the following values:
When medium or slow averaging are specified, the reported values for averaged registers will only
update every 4 or 12 seconds respectively, instead of once a second.
PowerIntScale (1609)
In order to report power as an integer value (±32,767), the meter must scale the power so that it doesn’t
overflow. By default, the meter selects a PowerIntScale value of 1, 10, 100, or 1000 whenever the
CtAmps (or CtAmpsA, CtAmpsB, or CtAmpsC) are changed. The meter selects a value that won’t
overflow unless the power exceeds 120% of full-scale.
1 1 watt ±32767 W
10 10 watt ±327.67 kW
You may also choose your own custom value for PowerIntScale including values that are not multiples of
10.
If PowerIntScale is set to auto-configure, then reading PowerIntScale will show the actual scale factor
instead of 0.
To compute the actual power from integer power registers, use the following equation (note, there is no
scaling for the floating-point power registers, which always report power in watts):
PowerIntScale is used with the following registers: PowerSum, PowerA, PowerB, PowerC,
PowerReacSum, PowerReacA, PowerReacB, PowerReacC, PowerAppSum, PowerAppA, PowerAppB,
PowerAppC, Demand, DemandMin, DemandMax, DemandApp.
CurrentIntScale (1622)
When reporting current values as integers, the meter scales the current values so that a current equal to
the CT rated amps will result in an output value of CurrentIntScale. The default CurrentIntScale is 20000.
See CurrentA, CurrentB, CurrentC for more details.
Demand Configuration
DemPerMins, DemSubints (1610, 1611)
The variable DemPerMins sets the demand interval in minutes (default 15 minutes), and DemSubints
sets the number of demand intervals (default 1). The time period of each subinterval is the demand
interval divided by the number of subintervals. Setting DemSubints to 1 disables subinterval
computations. The demand period cannot be longer than 12 hours (720 minutes), and a demand
subinterval cannot be less than 1 minutes. The DemSubints can be set from 1 to 10.
An example configuration could use a demand period of 60 minutes with 4 subintervals. This would
result in a subinterval period of fifteen minutes. Every fifteen minutes, the average power over the last
hour would be computed and reported.
The default values for the GainAdjust registers are 10,000, resulting in no adjustment. Setting the value
to 10,200 increases all the power, energy, and current readings from the meter by 2% (10,200 / 10,000 =
102%). Setting the value to 9,800 decreases the readings by 2% (9,800 / 10,000 = 98%). The allowed
range is from 5,000 to 20,000 (50% to 200%).
The default adjustment is -1000; this corrects for a one degree phase lead in the CT. Since our CTs
typically have phase leads ranging from 0.2 degrees to 2.5 degrees, the default adjustment improves the
typical performance.
CreepLimit (1618)
Creep refers to the situation where the wheel on an traditional electro-mechanical energy meter moves
even though there is no power being consumed. The meter has no wheel, but all electrical systems have
some noise, which can cause small readings in the absence of any power consumption. To prevent
readings due to noise, if the readings fall below the creep limit, the meter forces the real and reactive
power values to zero, and stops accumulating energy. This is performed independently for each
measurement phase using the following equation.
Any measured power or reactive power below MinimumPower is forced to zero. FullScalePower is
defined as the nominal line-to-neutral VAC (see Specifications) multiplied by the full-scale or rated CT
current.
Generally, the default value of 1500 (which sets the creep limit to 1/1500th of full-scale power) works
well. Sometime, in electrically noisy environments, you may see non-zero power readings when the
power should be zero. You can adjust the creep limit to eliminate this problem. For example, to adjust
the creep limit to 1/500th of full-scale (0.2%), set CreepLimit to 500.
PhaseOffset (1619)
The meter cannot directly measure line-to-line voltages (VoltAB, VoltBC, VoltAC, VoltAvgLL). To estimate
these voltages, the meter must know the phase offset of the electrical service being measured. This
setting has no effect on any other measurements or registers and is only needed if you plan to monitor
the line-to-line voltages.
60 Three-phase grounded delta (grounded leg), where one phase is connected to earth
(rare)
Zeroing registers
ZeroEnergy (1620)
Writing 1 to ZeroEnergy will simultaneously set all of the energy registers to zero, except those ending in
“NR” (for non-resettable). They can also be set to zero or a preset value by writing the desired value
directly to each energy register. If a ConfigPasscode has been set, then you must unlock the meter
before you can zero or preset the energy.
ZeroDemand (1621)
The ZeroDemand register can be written with three values (or zero which does nothing). If a
ConfigPasscode has been set, then you must unlock the meter before you can zero demand.
· 1 - Zero DemandMin and DemandMax registers.
· 2 - Zero Demand, DemandA, DemandB, DemandC and DemandApp registers. Start a new demand
interval.
· 3 - Zero DemandMin, DemandMax, Demand, DemandA, DemandB, DemandC and DemandApp
registers. Start a new demand interval.
Most customers will never need these registers, but they can be useful for special situations. If you are
using these registers to configure multiple meters, you may want to use the broadcast address (0) so that
all meters will update together. This isn’t permitted for setting the address, because then multiple devices
would share the same address.
The communication configuration can be restored to factory defaults by switching all the DIP switches to
the OFF position and leaving them OFF for 10 seconds, then setting them to the desired address and baud
rate.
ApplyComConfig (1651)
If any of the following communication configuration registers are changed, the new values will not take
effect until “1234” (decimal) is written to this register. This makes it easier to configure multiple changes
and have them all take effect together.
Reads of ApplyComConfig will return “1” if there are any pending changes, otherwise “0”.
Address (1652)
This register can override the DIP switch address setting and also allows addresses to be assigned up
to 247 (the DIP switches can only set addresses up to 127). Set this register back to zero to use the DIP
switch setting.
BaudRate (1653)
This register overrides the DIP switch baud rate setting for speeds up to 38,400 baud.
· 0 - Use DIP switch assigned baud rate (9,600 or 19,200 baud)
· 1 - 1,200 baud
· 2 - 2,400 baud
· 3 - 4,800 baud
· 4 - 9,600 baud
· 5 - 19,200 baud
· 6 - 38,400 baud
ParityMode (1654)
The meter defaults to no parity, eight data bits, and one stop bit, but even parity is supported using this.
· 0 - N81 (no parity, one stop bit)
· 1 - E81 (even parity, one stop bit)
ReplyDelay (1656)
ReplyDelay configures a user-defined minimum Modbus reply delay between 5 and 180 milliseconds
(the default is 5 milliseconds). This is useful with some Modbus master devices or software that can
miss response data if the meter responds to a request too quickly.
These registers, all integer registers, provide information and diagnostics for the meter. UptimeSecs and
TotalSecs are 32 bit integer dual registers: the first register provides the lower 16 bits, and the second
register provides the upper 16 bits of the 32 bit value. See diagnostic registers and error codes below for
detailed information.
Model (1707)
This register can be used to determine the model.
· 201 - VPA.8000.Y208
· 202 - VPA.8000.Y400
· 203 - VPA.8000.Y480
· 204 - VPA.8000.Y600
· 205 - VPA.8000.D240
· 206 - VPA.8000.D400
· 207 - VPA.8000.D480
Version (1708)
This reports the meters firmware version. The firmware is not field upgradable.
Options (1709)
This register indicates factory configured options.
PowerFailCount (1711)
This counts (up to 32767) the number of times power has been cycled on this meter.
CrcErrorCount (1712)
This counts (up to 32767) the number of Modbus packets with an invalid CRC (cyclic redundancy check).
FrameErrorCount (1713)
This counts (up to 32767) the number of Modbus packets with framing errors. A framing error can
indicate bad baud rate, bad parity setting, RS485 noise or interference, or an RS485 bus collision.
PacketErrorCount (1714)
This counts (up to 32767) the number of Modbus packets that could not be parsed.
OverrunCount (1715)
This counts (up to 32767) the number of times the Modbus input buffer has been overrun. The buffer is
256 bytes and normal requests are less than 80 bytes, so an overrun normally indicates non-Modbus
traffic on the RS485 bus or severe noise on the bus.
Error codes
ErrorStatus (1710)
ErrorStatus1 - ErrorStatus8 (1716 - 1723)
The ErrorStatus registers hold queues of the most recent eight errors or status notifications.
ErrorStatus allows access to the eight most recent errors from a single Modbus register. Each time you
read it, you’ll get another value (starting with the oldest). When there are no more errors, ErrorStatus will
report 0. The ErrorStatus values are preserved across power failures. ErrorStatus is generally best used
with unattended data logging, since each error will only be reported once.
ErrorStatus1 through ErrorStatus8 also list the eight most recent errors, but with a few differences.
ErrorStatus1 lists the most recent error or status, while ErrorStatus8 lists the oldest. Reading these
registers won’t change the reported values for ErrorStatus1 through ErrorStatus8, so they can be read
repeatedly without clearing the values. ErrorStatus1 through ErrorStatus8 can all be cleared by writing 0
to any of them. They are not preserved across power failures. ErrorStatus1 through ErrorStatus8 are
generally best used when a person will be looking at the values in real time, because they provide a
visual history of recent errors and events and will not be cleared when they are read.
The following lists many of the error and status code values. For any not listed or those marked
“ERROR” contact technical support.
· 0: No error or status messages.
· 1-49, 50-58, 60-61, 71-73: ERROR: Internal firmware error. Contact technical support.
· 59: ERROR: Non-volatile data lost: energy, peak demand, etc.
· 62-66: WARNING: Internal energy measurement overflow
· 67: ERROR: Calibration data lost. Meter will not function until it is recalibrated.
· 68: ERROR: Configuration data lost (CtAmps, etc.)
· 69: WARNING: Could not measure AC line frequency, may indicate high noise condition.
· 70, 74: ERROR: Non-volatile memory failure: energy, demand, etc. will be lost when power fails.
· 75-77: ERROR: Internal measurement error.
· 78-83: WARNING: Measured high AC line voltage. Sustained high voltage may damage the WattNode.
· 84, 85, 86: INFO: EnergyA, B, C registers overflowed 100 gigawatt-hours, reset to 0.
· 87: INFO: EnergySum register overflowed 100 gigawatt-hours, reset to 0.
· 88: INFO: EnergySumNR register overflowed 100 gigawatt-hours, reset to 0.
· 89, 90, 91: INFO: EnergyReacA, B, C registers overflowed 100 gigawatt-hours, reset to 0.
· 92: INFO: EnergyReacSum register overflowed 100 gigawatt-hours, reset to 0.
· 93, 94, 95: INFO: EnergyPosA, B, C registers overflowed 100 gigawatt-hours, reset to 0.
· 96: INFO: EnergyPosSum register overflowed 100 gigawatt-hours, reset to 0.
· 97: INFO: EnergyPosSumNR register overflowed 100 gigawatt-hours, reset to 0.
· 98, 99, 100: INFO: EnergyNegA, B, C registers overflowed 100 gigawatt-hours, reset to 0.
· 101: INFO: EnergyNegSum register overflowed 100 gigawatt-hours, reset to 0.
· 102: INFO: EnergyNegSumNR register overflowed 100 gigawatt-hours, reset to 0.
· 103, 104, 105: INFO: EnergyAppA, B, C registers overflowed 100 gigawatt-hours, reset to 0.
· 106: INFO: EnergyAppSum register overflowed 100 gigawatt-hours, reset to 0.
· 107: INFO: PulseCount register overflowed from 4,294,967,295 to zero.
· 197: WARNING: Tried to write to read-only register.
· 198: WARNING: IoPinMode write not allowed because required option not installed.
· 199: WARNING: IoPinState write command rejected because IoPinMode is an input.
· 200: WARNING: Configuration register cannot be changed without entering ConfigPasscode first.
· 202: WARNING: ConfigPasscode update failed because second write (verify) did not match the first
write.
· 203: WARNING: A write to a dual register (typically ConfigPasscode) was aborted.
· 205: WARNING: Invalid ConfigPasscode entered.
· 206: WARNING: Invalid Modbus register address specified.
· 207: WARNING: Invalid Modbus register data value specified.
· 208: WARNING: Invalid configuration register value specified.
· 209: INFO: ConfigPasscode unlock attempt rejected because it was within five seconds of a previous
failed attempt.
· 211: WARNING: Invalid Modbus write length specified.
· 212: WARNING: Invalid Modbus single-register write length specified
· 213: WARNING: Invalid Modbus function code specified.
· 215: WARNING: Slave device failure exception occurred: ConfigPasscode required, etc.
· 216: ERROR: Custom register map error. Custom map disabled.
· 220: INFO: Factory reset of energies completed.
· 241: WARNING: Invalid Modbus TCP/IP header.
· 242, 246: WARNING: Modbus collision. The meter received extra data after receiving a command. This
may indicate an address conflict or electrical interference.
· 243: WARNING: Invalid Modbus message length.
· 244: WARNING: Timeout receiving the Modbus TCP header (only applies in TCP-RTU mode).
· 245: WARNING: Invalid length in the Modbus TCP header (only applies in TCP-RTU mode).
· 247: WARNING: RS485 parity error. Generally caused by baud rate mismatch, parity mode mismatch,
or electrical interference.
· 248: WARNING: RS485 bus contention during transmit. Generally caused by two or more meters with
duplicate Modbus addresses.
· 249: WARNING: Duplicate Modbus address detected.
· 250: WARNING: Modbus receiver overrun. This is generally caused by non-Modbus data on the bus or
packets longer than 256 bytes.
· 251: WARNING: RS485 receiver error. Generally caused by baud rate mismatch, parity mode
mismatch, or electrical interference.
· 252-253: WARNING: Short Modbus packet detected (less than four bytes). Modbus RTU uses a brief
pause (3.5 byte periods) to indicate the end of a packet, so any break in the stream of bytes can cause
this, such as hot-connecting the RS485 lines.
· 254: WARNING: False Modbus start bit. This generally indicates electrical noise, or inadequate
termination or biasing. See Termination and Biasing sections under Modbus wiring for more
information.
· 255: WARNING: Invalid Modbus packet cyclic redundancy check (CRC). This generally indicates
electrical noise on the RS485 bus.
Normal startup
On initial power-up, the LEDs will all light up in a red, yellow, green A Red Yellow Green
sequence. After this startup sequence, the LEDs will show the status, such
as Normal Operation below. B Red Yellow Green
C Red Yellow Green
1.0 sec 1.0 sec 1.0 sec
Normal operation
During normal operation, when positive power is measured on a Green Off Green Off Green Off
phase, the LED for that phase will flash green. Typical flash rates
are shown below.
100% 5.0 Hz 50
50% 3.6 Hz 36
25% 2.5 Hz 25
10% 1.6 Hz 16
5% 1.1 Hz 11
Zero power
For each phase, if line Vac is present, but the measured power is below Green
the minimum that the meter will measure(Creep Limit) the meter will
display solid green for that phase.
Inactive phase
If the meter detects no power and line voltage below 20% of nominal, it will Off
turn off the LED for the phase.
Negative power
If one or more of the phase LEDs are flashing red, it indicates negative power (flowing into the grid) on
those phases. The rate of flashing indicates magnitude of negative power. This can happen for the
following reasons:
· This is a bidirectional power measurement application, such as a photovoltaic system, where negative
power occurs whenever you generate more power than you consume.
· The current transformer (CT) for this phase was installed backwards on the current carrying wire or the
white and black wires for the CT were reversed at the meter. This can be solved by flipping the CT on the
wire or swapping the white and black wires at the meter. Alternatively, you can use the configuration
register CtDirections (1607) to reverse the polarity of one or more of the CTs.
· The CT wires are connected to the wrong inputs, such as if the CT wires for phases B and C are
swapped or the CT wires are rotated one phase.
Note: if all three LEDs are flashing red and they always turn on and off together, like the diagram for Low
Line Voltage below, then the meter is experiencing an error or low line voltage, not negative power.
Erratic flashing
If the LEDs are flashing slowly and erratically, sometimes green, sometimes red, this generally indicates
one of the following:
· Earth ground is not connected to the meter (the top connection on the green screw terminal).
· Voltage is connected for a phase, but the current transformer is not connected, or the CT has a loose
connection.
· In some cases, particularly for a circuit with no load, this may be due to electrical noise. This is not
harmful and can generally be disregarded, provided that you are not seeing substantial measured power
when there shouldn’t be any. Try turning on the load to see if the erratic flashing stops.
Meter error
If the meter experiences an internal error, it will light all LEDs red for three A Red
seconds or longer. Check the ErrorStatus (1710) register to determine the
exact error. If this happens repeatedly, return the meter for service. B Red
C Red
3.0 sec
Bad calibration
This indicates that the meter has detected bad calibration data and must A Red
be returned for service.
B Red
C Yellow
Whenever the meter detects line voltages over 125% of normal for one or more phases, it will display a fast
red/green flashing for the affected phases. This is harmless if it occurs due a momentary surge, but if the
line voltage is high continuously, the power supply may fail. If you see continuous over-voltage flashing,
disconnect the meter immediately! Check that the model and voltage rating is correct for the electrical
service.
A Red Yellow A Red Yellow A Red Off Red Off Red Off Red
B Red Yellow B Red Yellow B Red Off Red Off Red Off Red
C Red Yellow C Red Yellow C Red Off Red Off Red Off Red
1.0 sec 1.0 sec
No line voltage
If the measured line voltage on all three phases is less than 20% of the nominal line Vac, then the meter
will briefly flash all three status LEDs together every three seconds. This is very rare, but can indicate the
following:
· You have purchased a DC instrument powered meter and the meter has power, but the circuit being
monitored is off. You can check for this by measuring the AC volts from neutral to each phase or between
phases for delta circuits.
The measurement circuitry has been damaged and cannot read the line voltages.
The meters use CTs with built-in burden resistors generating 0.33333 Vac at rated AC current. The
maximum input current rating is dependent on the CT. Check the CT label to find the maximum current
rating. Exceeding the maximum input current rating may damage CTs, but should not harm the meter.
None of these CTs measure DC current and the accuracy can be degraded in the presence of DC currents,
as from half-wave rectified loads. The solid-core CTs are most susceptible to saturation due to DC
currents.
Specifications
Please always check the label of your product for the specifications.
Specifications are subject to change as we are continuously improving our products.
Please contact us to obtain the latest specification sheet.
Current transformers
Type Voltage output, integral burden resistor
Output voltage at rated current 0.333 Vac (one-third volt)
CT wires 1.05 m (4 feet), twisted pair, 0.34mm 2 (22AWG)
Accuracy ±1% from 5% tot 120% of rated current
Phase angle Less than 2 degrees at 50% of rated current
Insulation Voltage 600 Vac
Maximum primary voltage 5000 Vac (insulated coductor)
Operating temperature -15..60 °C | 5...76 °F
Frequency range 50-400Hz
8 Specification
Please always check the label of your product for the specifications.
Specifications are subject to change as we are continuously improving our products.
Please contact us to obtain the latest specification sheet.
Current transformers
Nominal input voltage (at CT 0.33333 Vac RMS
rated current
Absolute maximum input voltage 5.0 Vac RMS
Input impedance at 60/60 Hz 23 k Ohm
Environmental
Operating temperature -30...55 °C | -22...131 °F
Altitude Up to 2000 m | 6560 ft
Operating humidity Non-condensing, 5 to 90% relative humidity up to 40°C, decreasing
linearly to 50% RH at 55°C.
Pollution Pollution degree 2. Normally only non-conductive pollution; occasionally,
a temporary conductivity caused by condensation must be expected
Indoor use Suitable for indoor use
Outdoor use Suitable for outdoor use when mounted inside an electrical enclosure
that is rated NEMA 3R or 4 (IP 66)
Mechanical
Enclosure High impact, ABS and/or ABS/PC plastic
Flame resistance rating IEC FV-0
Size 153 x 85 x 38 mm | 6.02 x 3.35 x 1.50 inch
Weight 307..314 gram | 10.8...11.1 oz
Connectors Euroblock style pluggable terminal blocks
Green Up to 12 AWG (2.5mm), 600 V
Black Up to 12 AWG (2.5mm), 300 V
Certifications
Safety CAN/CSA-C22.2 No. 61010-1-04; IEC 61010-1
Immunity EN 61326:2002 (Industrial locations)
Electrostatic discharge EN 61000-4-2
Radiated RF immunity EN 61000-4-3; EN 61000-4-3; EN 61000-4-4; EN 61000-4-5; EN
61000-4-6
Voltage dips, Interrupts EN 61000-4-11
Emissions FCC part 16, Class B; EN 55022 1994, Class B
Electrical
Power Consumption: The following table shows typical power consumption and power factor values with
all three phases powered at nominal line voltages. The power supply draws most of the total power
consumed, while the measurement circuitry draws 1-10% of the total (6-96 milliwatts per phase,
depending on the model). Due to the design of the power supply, meters draw slightly more power at 50
Hz.
Model Active power Active power Power Rated Power supply Power supply
at 60 Hz at 50 Hz factor power* range terminals
VPA.8000.Y2 1.5 W 1.8 W 0.79 3W 96 – 138 Vac N and ØA
08
VPA.8000.Y4 1.6 W 1.8 W 0.73 3W 184 – 264 Vac N and ØA
00
VPA.8000.D 1.2 W 1.5 W 0.70 4W 166 – 276 Vac ØA and ØB
240
VPA.8000.D 1.1 W 1.4 W 0.67 3W 320 – 460 Vac ØA and ØB
400
VPA.8000.D 1.2 W 1.4 W 0.70 3W 384 – 552 Vac ØA and ØB
480
VPA.8000.Y4 1.6 W 2.0 W 0.73 4W 222 – 318 Vac N and ØA
80
VPA.8000.Y6 1.0 W 1.3 W 0.76 4W 278 – 399 Vac N and ØA
00
*Note: This is the maximum rated power at 115% of nominal Vac at 50 Hz. This is the same as the rated
power that appears on the front label of the meter.
Maximum Operating Power Supply Voltage Range: -20% to +15% of nominal (see table above). For the
VPA.8000.D240, this is -20% of 208 Vac (166 Vac) to +15% of 240 Vac (276 Vac).
Measurement category III is for measurements performed in the building installation. Examples are
measurements on distribution boards, circuit-breakers, wiring, including cables, bus-bars, junction boxes,
switches, socket-outlets in the fixed installation, and equipment for industrial use and some other
equipment, for example, stationary motors with permanent connection to the fixed installation.
The line voltage measurement terminals on the meter are rated for the following CAT III volt- ages (these
ratings also appear on the front label):
Accuracy
The following accuracy specifications do not include errors caused by the current transformer accuracy or
phase angle errors. “Rated current” is the current that generates a CT output voltage of 0.33333 Vac.
Condition 1 - Normal operation
Line voltage -20% to +15% of nominal
Power factor 1.0
Frequency 48 - 62 Hz
Ambient temperature 25 °C
CT current 5% - 100% of rated current
Accuracy ±0.5% of reading
Measurement
Creep Limit: 0.067% (1/1500th) of full-scale. Whenever the power or reactive power for a phase drops
below the creep limit, the power or reactive power for the phase will be forced to zero. Also, if the line
voltage for a phase drops below 20% of nominal Vac, the output power for the phase will be set to zero.
These limits prevent spurious readings due to measurement noise. To customize the creep limit, see
CreepLimit(1618) in Configuration Registers.
Update Rate: 1.0 second. Internally, all measurements are performed at this rate.
Start-Up Time: Approximately 1.0 second. The meter starts measuring 50-100 milliseconds after AC power
is applied, but requires a full 1.0 second measurement cycle before it starts reporting data. The meter does
not respond to Modbus packets during this start-up time.
Current Transformer Phase Angle Correction: 1.0 degree leading. Current transformers (CTs) typically have
a leading phase angle error ranging from 0.2 degrees to 2.5 degrees. The meter is normally programmed
to correct for a 1.0 degree phase lead to provide good accuracy with typical CTs. The CT phase angle
correction can be changed using the PhaseAdjustA, PhaseAdjustB, PhaseAdjustC registers.
Over-Voltage Limit: 125% of nominal Vac. If the line voltage for one or more phases exceeds this limit, the
status LEDs for these phases will flash alternating red-green as a warning. Extended over-voltage
operation can damage the meter and void the warranty.
Over-Current Limit: 120% of rated current. Exceeding 120% of rated current will not harm the meter but the
current and power will not be measured accurately.
The FCC limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the
following measures:
· Reorient or relocate the receiving antenna.
· Increase the separation between the equipment and receiver.
· Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
· Consult the dealer or an experienced radio/TV technician to help.
Voltage
Start by checking the reported voltage (VoltA, VoltB, VoltC) for active (connected) phases. Make sure the
voltages match the expected line-to-neutral voltages (or line-to-ground for delta circuits). You should check
the actual voltages present at the meter with a multimeter if possible.
· If one or more voltages are zero, then you either have a wiring problem or something is wrong with the
meter. Verify the actual voltages with a multimeter. In rare cases, with delta circuits, one phase may be
grounded and will read zero volts.
· If one or more voltages are too low (by more than 5%), then make sure you have the correct model. For
example, a VPA.8000.Y208 expects line-to-neutral voltages of 120 Vac and can measure up to about 150
Vac. If you apply 208 Vac line-to-neutral, the meter will read a voltage in the 150 Vac to 180 Vac range.
· If any voltages read high, then check your wiring. If the wiring is correct, contact support.
· If the voltages are close to the measured (or expected) values, continue with the next step.
Power
Next, check the measured power for each active phase (PowerA, PowerB, PowerC). If possible, estimate or
measure the actual power. Also, make sure the load you are measuring is currently on.
· If one or more active phases are reporting zero power, then the problem is probably one of the following:
o There is no active power (the load is off) or the power is too low to measure (generally less than
1/1000th of full-scale).
o CT wires are not securely connected.
o The CT or its wires are damaged.
o There is strong electrical interference, as might occur if the meter is in very close proximity to a variable
speed drive (also called variable frequency drive or inverter).
o The meter is not working correctly: try swapping it with a replacement meter.
· If one or more active phases are reporting negative power:
o The current transformer has been installed backward on the wire being measured. CTs are marked
with either an arrow or a label saying “This side toward source”. If the arrow or label are not oriented
toward the source of power (generally the panel or breaker), then the measured current will be inverted
and the power negative. This can be fixed either by flipping the CT or by swapping the white and black
wires where they enter the meter.
o The current transformer white and black wires have been swapped where they enter the meter (at the
black screw terminal block).
o The line voltage phases (green screw terminals) are not matched up with the current phases (black
screw terminals). For example, the phase A CT is around the phase B wire.
o This may be normal if you are measuring in an environment were power may be consumed or
generated, such as a house with PV panels.
· If one or more phases are reporting low or high power:
o Make sure the CtAmps configuration is set correctly for your current transformers.
o The current transformers may have a rated current too high or too low for your application. CTs should
be used between 10% and 100% of their rated current for best results. They generally work with
reduced accuracy as low as 0.5% to 0.1% of rated current.
o The CTs may not be installed properly. Check for: CTs touching each other or pre- existing CTs; CT
opening too large for the conductor being measured.
o The voltage phases (green screw terminal block) are not matched up with the current phases (black
screw terminal block). The easiest way to determine this is to skip ahead to the next troubleshooting
section: Power Factor and Reactive Power.
o Interference from a variable frequency or variable speed drive: VFD, VSD, inverter, or the like. Generally,
these drives should not interfere with the meter, but if they are in very close proximity, or if the CT leads
are long, interference can occur. Try moving the meter at least three feet (one meter) away from any
VFDs. Use short CT leads if possible. NEVER install the meter downstream of a VFD: the varying line
frequency and extreme noise will cause problems!
o Our current transformers can only measure AC currents. Strong DC currents will saturate the magnetic
core of the CT, preventing an accurate measurement of the AC current. The overwhelming majority of
AC powered electric devices do not draw significant DC current, so this is a rare occurrence.
o Loads with a high current crest factor (ratio of the peak current to the RMS current) can cause clipping
in the measurement circuitry, resulting in lower than expected readings. You can check for this with a
handheld power quality analyzer that can measure crest factor (CF) or by trying a CT with a higher
rated current, which should allow the meter to measure the peak current accurately.
o The CTs may be malfunctioning. If possible, use a current clamp to verify the current, then use a
multimeter to measure the AC voltage between the white and black wires from the CT (leave them
connected to the meter during this test). At rated current, the CT output voltage should equal 0.333 Vac
(333 millivolts AC). At lower currents, the voltage should scale linearly, so at 20% of rated current, the
output voltage should be 0.20 * 0.333 = 0.0666 Vac (66.6 millivolts AC).
o If possible, verify the expected power with a handheld power meter. Current clamps can be useful to
very roughly estimate the power, but since they measure current, not power, the estimated power
(voltage times current) may be off by 50% or more.
Negative power factor values either indicate you are generating power (as with a PV system) or that the CTs
are reversed.
If the measured power factor or reactive power appears to be outside the normal ranges, this most
commonly indicates that the voltage and current phases on the meter are not connected properly, although
some loads fall outside the normal ranges. Check the following:
· The CT connected to the ØA CT terminal is installed around the line wire being measured by the ØA Vac
terminal (green terminal block).
· The CT connected to the ØB CT terminal is installed around the line wire being measured by the ØB Vac
terminal (green terminal block).
· The CT connected to the ØC CT terminal is installed around the line wire being measured by the ØC Vac
terminal (green terminal block).
If this doesn’t solve your problem, contact technical support for more assistance.
12 Appendix C - Maintenance
Maintenance and Repair
The meter requires no maintenance. There are no user serviceable or replaceable parts except the
pluggable screw terminals.
The meter should not normally need to be cleaned, but if cleaning is desired, power must be disconnected
first and a dry or damp cloth or brush should be used.
The meter is not user serviceable. In the event of any failure, the meter must be returned for service using
our RMA form. In the case of a new installation, follow the diagnostic and troubleshooting instructions
before returning the meter for service, to ensure that the problem is not connection related.
Notes
Notes
VPInstruments
Buitenwatersloot 335
2614 GS Delft
The Netherlands
info@vpinstruments.com
www.vpinstruments.com
MAN-VP-AKW-EN-1900
Date: 22-07-2019