This manual contains important safety instructions that must be followed during the installation and
maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or
operate this UPS. Adhere to all warnings on the unit and in this manual. Follow all operating and user
instructions. This equipment can be operated by individuals without previous training.
This UPS contains no user-serviceable parts except the internal battery pack. The Off/Bypass
push button does not electrically isolate internal parts. Under no circumstances attempt to gain internal
access other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the
UPS if the front panel indications are not in accordance with these operating instructions or if the UPS
performance alters in use. Refer all faults to your local dealer, Vertiv™ representative or Vertiv™ Channel
Support.
This UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even if the
UPS is not connected to utility input power.
Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure that the
UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric
shock hazard.
To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.
When the UPS is connected to an IT power distribution system, a short-circuit protection device must be
installed on the neutral line.
Keep the air inlet and outlet of this UPS unobstructed. Poor ventilation will increase the internal
temperature of the UPS and can adversely affect the UPS and its batteries.
Keep liquid and foreign objects away from the UPS. Turn Off and isolate the UPS before cleaning it. Use
only a soft cloth, never liquid or aerosol cleaners.
In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may
cause electric shock.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for
example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half-wave
rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
This UPS is not for use in a computer room as defined in the standard for the Protection of Electronic
Computer/Data Processing Equipment, ANSI/NFPA 75.
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230,
120/208,120/240 or 127/220VAC, 50 or 60Hz supply. The factory default setting is 120/208VAC, 60Hz.
Installation instructions and warning notices are in this manual.
The Liebert GXT4 208VAC 5000 - 10000 is designed for use with a 4-wire input (L1, L2, N, G).
The Liebert GXT4-6000RTL630 is designed be used with a 3-wire, 2-phase utility source (L1, L2, G).
Battery Safety
WARNING! Risk of electric shock and explosion. Can cause equipment damage, injury and
death. Do not dispose of the battery in a fire. The battery may explode. Do not open or damage
the battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte comes
into contact with the skin, wash the affected area immediately with plenty of clean water and
get medical attention.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery
can present a risk of electrical shock and high short-circuit current.
ELECTROMAGNETIC COMPATIBILITY
The Liebert GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the
published technical standards. Continued compliance requires installation in accordance with these
instructions and use of accessories approved by Vertiv™.
This is a product for restricted sales distribution to informed partners. Installation restrictions
or additional measures may be needed to prevent radio interference.
UPS Servicing: UPS makes use of components dangerous for the environment (electronic cards,
electronic components). The components removed must be taken to specialized collection and disposal
centers.
The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle
wherever possible. Please be environmentally responsible and recycle this product through your
recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local
municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste
electrical and electronic equipment (WEEE).
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject
to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss, and
damage equipment.
The Liebert GXT4 protects equipment from these disturbances. The Liebert GXT4 continuously charges
its batteries from the mains, enabling it to supply power to connected loads, even when the mains fail.
2.1 Features
• Intelligent battery management to extend the battery life
• LCD for user-friendly operation and local monitoring and configuration of operational
parameters
• Flexible network management with Liebert MultiLink™ software
• Fan fault self-inspection and automated diagnostic function
• Intelligent fan operation, automatically changing rotation speed depending on system
requirements, to decrease power consumption and noise
• Input circuit breaker to ease recovery from overloads
• Safety approval from UL and cUL
• Communication options: USB port, Liebert IntelliSlot® port and terminal-block communication
• Dry contacts for remote monitoring
• Input power factor greater than 0.99
• Output voltage selection function
NO. DESCRIPTION
1 Upper bezel
4 USB port
NOTE: Hard-wired and hard-wired/receptacle boxes that include a manual bypass switch permit AC
power to continue to flow from the utility input to the load while the box is removed from the UPS. For
details, refer to Connecting Input/Output Power on page 28.
4 Push-button output-power breakers for L5-20R receptacles 11 PD2-005 Receptacles: four L5-20R, two L6-30R
5 PD2-001 Receptacles: four 5-20, one L14-30, one L6-30R 12 PD2-006 Receptacles: four L6-30R, two L6-20R
NOTE: PD2-001 is shown with labeled examples. Other boxes are arranged differently.
2 Output circuit-breaker switch for L6-30R pigtail #1 8 PD2-103 Receptacles: four L6-30R, four 5-20R
3 L6-30R output receptacle 9 PD2-104 Receptacles: four 5-20R, two L6-30R, two L6-20R
4 L6-30R output receptacle 10 PD2-105 Receptacles: four 5-20R, two L5-30R, two L5-20R
5 Output circuit-breaker switch for L6-30R pigtail #2 11 PD2-106 Receptacles: four L6-20R, four L5-20R
NOTE: PD2-101 is shown with labeled examples. Other boxes are arranged differently.
PD2-201
1 PD2-107 Receptacles: four L5-20R, four 5-15R 5
Receptacles: two IEC320-C19, eight IEC320-C13
GXT4 10,000-VA battery pack shown is shown in the figure. 5000-VA and 6000-VA battery packs have
the same features.
NO. DESCRIPTION
1 Battery handle
2 Battery connector
This results in cleaner power available to other devices in the building that are not protected by the
GXT4.
2.7.3 Inverter
In normal operation, the inverter utilizes the DC output of the PFC circuit to produce precise, regulated
sine-wave AC power. When mains power fails, the inverter receives DC power from the DC-to-DC
Converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise,
regulated AC output power.
2.7.6 Battery
The GXT4 uses valve-regulated, non-spillable, lead acid batteries. To maintain battery design life, Operate
the GXT4 in an ambient temperature of 15°C to 25°C (59°F to 77°F).
Optional external battery cabinets are available to extend battery run times.
To manually transfer the connected load from the inverter to bypass, press the Standby/Manual Bypass
button once and hold it for about 2 seconds
NOTE: The bypass power path does not protect the connected equipment from disturbances in the
mains supply.
Refer to Operation and Display Panel on page 33 for details about the operating mode indicators and
control buttons.
NOTICE
Risk of loss of power to the connected load. Can cause equipment damage.
Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load.
When the GXT4 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When
approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is
getting low (this Low Battery Warning is user-configurable).
In Battery Mode, the battery indicator will illuminate and the LCD will show the prompt u tility p ower n ot
availab le.
NOTICE
Risk of loss of power to the connected load. Can cause equipment damage.
Turning Off the GXT4 when it is in Battery Mode will result in loss of output power to the
connected load.
If the UPS is turned Off manually, it must be manually restarted after mains power returns.
If the UPS is turned Off by a communication signal or because the batteries are depleted, it will
operate as set in the configuration program for Auto-Restart (Refer to Configuration Program
on page 46).
NOTE: The default for all models of the Liebert GXT4 is “Auto Sensing - 50Hz or 60Hz – Bypass
Enabled.”
WARNING! Risk of electric shock. Can cause injury or death. Never touch the AC input
receptacle while the UPS is operating. Voltage may still be present even when the AC input
indicator is Off.
Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized
to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power
almost seamlessly if bypass power falls outside the user-set limits. Once bypass power returns within the
acceptable parameters, the UPS will return to Active ECO Mode operation.
NOTE: The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers
for tower configuration and one DC-power cable and rack-mounting hardware, including screws,
handles and mounting rail kit.
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier
and your local dealer or your Vertiv™ representative immediately.
• Check the accessories included in packaging list. If there is any discrepancy, contact your local
dealer or your Vertiv™ representative immediately.
CAUTION: The UPS is heavy (see Specifications). Take proper precautions when lifting or
moving it.
NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.
After installing the UPS as a tower or in a rack, and before attempting to start-up, you must install the
internal batteries. See Installing the Internal Battery Kit(s) on page 25.
NOTE: When installing the UPS or making input and output connections, comply with all relevant
safety codes and standards
NO. DESCRIPTION
1 Support bases
2. If optional, Liebert external battery cabinets will be connected, take out the spacers shipped
with the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 3.1 above. Each GXT4 requires
2 support bases, one in the front and one in the rear.
4. Adjust the direction of the operation and display panel and logo on the GXT4.
a. Remove the front plastic bezel cover as shown the following figure.
b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it
back into position, as shown.
c. Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and
snap it back into position.
Figure 3.2 Remove the front plastic bezel cover and rotate display
NO. DESCRIPTION
5. Place the GXT4 and any battery cabinets on the 2 support bases.
6. Now you are ready to install the internal batteries. See Installing the Internal Battery Kit(s) on
page 25.
3.4.2 Rack Installation
When installed in a rack enclosure, the GXT4 UPS and external battery cabinets (EBC) must be
supported by a shelf or rack-mount rails. The GXT4 and EBC units ship with all required hardware for
rack-mount installation. Because different rack-mount options install differently, refer to the installation
instructions provided with the rack mount kit being used.
Once the UPS is mounted in the rack, you are ready to install the internal batteries. See Installing the
Internal Battery Kit(s) on page 25.
CAUTION: The GXT4 is heavy. The UPS must be installed as near the bottom of a rack as
possible. If placed too high, it can make the rack top-heavy and prone to tipping over. For unit
weights, see Specifications on page 63.
1. Loosen and remove the screws on the battery door, as shown in Figure 3.3 on the next page.
2. Lay the battery door and screws aside for reassembly.
3. Unpack the new internal battery pack. Take care not to destroy the packing.
Figure 3.3 Removing the front bezel cover and battery door
3 Front bezel
6. Push the battery wire and internal battery pack into the UPS.
7. Attach the front battery door with the 6 screws.
8. Attach the front plastic bezel cover to the UPS.
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote
electric power supplies before working within. Ensure that the Liebert GXT4 is shut down and
power has been disconnected before beginning any work on or in the unit.
CAUTION: The external battery cabinet(s) are heavy (see Table 9.4 on page 66). Take proper
precautions when lifting them.
Optional, Liebert external battery cabinets (EBC) may be connected to the UPS to provide additional
battery run time. External battery cabinets are placed on one side of the UPS in a tower configuration or
stacked beneath the UPS in a rack configuration.
1. Inspect the EBC for freight damage. Report damage to the carrier and your local dealer or
Vertiv™ representative.
2. Optional rack-mount hardware is shipped with the external battery cabinet and may be
installed at this time.
• Securing hardware and slide rails are sold separately. Please contact your local dealer or
Vertiv™ representative for these additional options and any assistance needed. Fasten
the slides into position with the screws per the instructions included with the slide rails.
3. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of
support-base extensions ships with each EBC.
4. Verify the that the EBC breaker is in the "Off" position.
5. Connect the supplied EBC cable to the rear of the cabinet, then to the rear of the UPS.
6. Turn the EBC breaker to the "On" position.
7. Verify the circuit breaker on the EBC is in the "On" position.
8. Use the included configuration program or the LCD display to program the UPS with the
number of external battery cabinets connected. Instructions for the configuration program are
in Configuration Program on page 46.
The UPS is now equipped with additional back-up battery run time. For approximate battery run times,
refer to Table 9.8 on page 69.
NOTE: When removing an EBC, the circuit breaker on the rear of the cabinet must be turned off before
disconnecting the cable.
NOTE: If the UPS will be shipped or stored for an extended time, the connector should be
disconnected. This will minimize any stand-by current drain on the batteries and help attain their
design life.
NOTE: Do not operate the UPS with the power distribution box removed. To shut off all power to this
box and to the load, utility input power must be disconnected.
3.6.1 Installing the Power Distribution Box on 5000VA and 6000VA Models
1. Align the connectors and press the power-distribution box onto the UPS.
2. Hold the box firmly against the UPS and tighten the captive screws except the one over the
maintenance bypass breaker.
3. Turn the output and input breakers "On."
4. Start the UPS according to start-up instructions.
5. Verify that the UPS lamp is illuminated.
6. Turn the maintenance bypass breaker "Off."
7. Insert the maintenance-bypass-interlock bracket behind the captive screw and tighten the
screw.
NOTE: The maintenance bypass breaker interlock bracket must be installed behind the captive screw,
and the screw must be tightened for the UPS to operate in inverter mode.
WARNING! Risk of electric shock. Can cause injury or death. The UPS must be shut down or
the load must be transferred to an external maintenance bypass before a power distribution
box may be added, changed or removed. If the UPS will be shut down, the connected load must
be shut down (refer to Shutting Down the GXT4 on page 44). If the UPS will be transferred to
maintenance bypass, it must be transferred to an external maintenance bypass. A maintenance
bypass in the UPS frame must not be used. Verify that the GXT4 is shut down and that all local
and remote electric input power has been disconnected before beginning any work on or in the
UPS.
1. With the cover of distribution box removed, press the UPS and distribution box connectors
together. Ensure that the connectors are fully seated.
2. Align the screw holes and press the power distribution box onto the UPS, making sure that the
tabs at the bottom of the box fit into the slots on the UPS.
3. Attach the box to the UPS by installing screws into the two holes at the top of the box.
4. Tighten the screws.
5. Turn the output and input breakers On.
6. Start the UPS according to start-up instructions.
The installer must provide an upstream branch circuit breaker. The input circuit breaker on the
distribution box and the output circuit breaker on the rear of the power distribution box disconnect all
power between the main cabinet and the distribution box.
Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from
the input terminal block. The input circuit breaker on the distribution box does not disconnect power
from the manual bypass breaker.
circuit breaker ratings
5000VA
D Type 30A Long Delay
6000VA
8000VA
D Type 60A Long Delay
10,000VA
RECOMMENDED MAXIMUM
RECOMMENDED
WIRE WIRE
(MAXIMUM) TERMINAL
(INCLUDING ACCEPTED
UPS MODEL EXTERNAL TIGHTENING
GROUND WIRE) BY
OVERCURRENT TORQUE
(75°C COPPER TERMINAL
PROTECTION
WIRE) BLOCK
GXT4-5000RT208
GXT4-6000RT208 30A 10AWG (4mm2) 8AWG (6mm2)
GXT4-6000RTL630 20 in-lb
GXT4-8000RT208 4AWG (2.26 Nm)
60A 6AWG (10mm2)
GXT4-10000RT208 (16mm2)
The load is unprotected from disturbances in the power supply while the UPS is on bypass.
Figure 3.7 Power distribution box removal from 5000VA and 6000VA models
NO. DESCRIPTION
WARNING! Risk of electric shock. Can cause injury or death. The UPS must be shut down or
the load must be transferred to an external maintenance bypass before a power distribution
box may be added, changed or removed. If the UPS will be shut down, the connected load must
be shut down (refer to Shutting Down the GXT4 on page 44). If the UPS will be transferred to
maintenance bypass, it must be transferred to an external maintenance bypass. A maintenance
bypass in the UPS frame must not be used. Verify that the GXT4 is shut down and that all local
and remote electric input power has been disconnected before beginning any work on or in the
UPS.
1. Shut down the GXT4 (for help, refer to Shutting Down the GXT4 on page 44).
a. From the Main Menu select CO N T R O L, press Enter, then select T UR N O N & O FF.
b. Press the enter key.
c. Select T UR N UPS O FF, then press Enter.
Power to the connected loads is now Off.
2. Turn the output and input breakers Off.
3. Support the power distribution box and remove the two screws at the top of the box.
4. Remove the cover for power-distribution box from the UPS and set it aside.
5. If removing a power-distribution box, carefully pull apart the power-distribution-box connector
and the UPS connector.
Figure 3.8 Power distribution box removal from 8000VA and 10,000VA models
NO. DESCRIPTION
1 Remove screws.
• Inverter
• Battery
• Bypass
• ECO Mode
• Fault
Figure 4.1 above shows the indicators’ locations. Their descriptions and functions are as follows.
Bypass Amber On when the load is supplied by the mains through automatic/manual bypass
BUTTON DESCRIPTION
ESC Pressing this button returns to the previous menu or aborts any change in the input data field before confirming.
Pressing this button can move the cursor up or increase the value displayed in the input data field. When a menu is displayed on several
Up
screens, pressing the button can scroll up.
Pressing this button can move the cursor down or decrease the value displayed in the input data field. When a menu is displayed on
Down
several screens, pressing the button can scroll down.
Enter Pressing this button can enter the next level menu or confirm the parameter setting value.
4.3 LCD
The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in navigating
through the GXT4 menu (see Menu Structure on page 35).
After about 10 seconds, the LCD shows one of the "On" screens. The screen shown depends on whether or
not input power is available.
To turn On the UPS, press the Up or Down button to select YES and press the Enter button. The UPS will
start up, the LCD will display UPS S T AR T IN G and then S T AR T S UCCES S FUL after the UPS is turned On..
NOTE: Values shown in the default screen will vary depending on installation and configuration.
In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery
capacity with run time estimate and load percentage. The UPS operation mode (online/inverter, ECO,
Battery or Bypass) will be indicated by the LED indicators.
If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen-saver
mode (back light turns off). It will remain off until a control button is pressed.
To select a submenu, press the Up or Down button to move the cursor to the required item, then press the
Enter button to enter its submenu or set its parameter.
Menu options
STATUS Screen
In the MAIN MENU screen, select S T AT US to enter the Status Screen, displaying OUTPUT, LOAD,
INPUT, BATTERY and TIME SINCE STARTUP.
CONFIGURATION Screen
In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required
item, then press the Enter button to enter a submenu or set its parameters.
UPS Screen
Select MAIN MEN U > CO N FIGUR AT IO N > UPS to enter the UPS screen. This menu has six screens.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
Select MAIN MEN U > CO N FIGUR AT IO N > BAT T ER Y to enter the BATTERY screen. This menu has
four screens.
Press the Up or Down button to increase or decrease the value of the settings, and press the Enter
button to confirm it.
Select MAIN MEN U > CO N FIGUR AT IO N > ECO MO DE to enter the ECO MODE screens.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
Select MAIN MEN U > 2 CO N FIGUR AT IO N > 4 O UT LET 1 to enter the OUTLET1 screen. This menu
has two sub menus
Select 1 O UT LET CO N T R O L and press the Enter button to enter the OUTLET CONTROL screen.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
Select MAIN MEN U > 2 CO N FIGUR AT IO N > 4 O UT LET 1 to enter the OUTLET1 screen. This menu
has two sub menus
Select 2 O u tlet S ettin g and press the Enter button to enter the OUTLET SETTING screen.
Outlet2 Screen
The Outlet2 screens are the same as the Outlet1 screens. The same settings are available as on the
Outlet1 screen. If the Outlet2 group will have the same settings as the Outlet1 group, GXT4 offers a
programming shortcut. When configuring the Outlet2 group, select YES and press the Enter button
to apply the Outlet1 settings to the Outlet2 screen.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
LCD screen
Select Main Menu > 2 CO N FIGUR AT IO N > 6 LCD to enter the LCD screen. This menu has two sub
menus, LANGUAGE and COLOR.
Select 1 LAN GUAGE and press the Enter button to enter the LANGUAGE screen.
GXT4 supports multiple languages. For the list of supported languages and instructions on how to
upload them, refer to the Configuration Program user manual on the included CD.
Color screen
Select 2 CO LO R and press the Enter button to enter the COLOR screen.
Select MAIN MEN U > 2 CO N FIGUR AT IO N > 7 FACT O R Y DEFAULT to enter the FACTORY DEFAULT
screen.
Control Screen
Select MAIN MEN U > 3 CO N T R O L to enter the CONTROL screen. This screen has three sub menus,
TURN ON & OFF, ALARM CONTROL and BATT TEST.
In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and
press the Enter button to enter its sub menu.
Select MAIN MEN U -> 3 CO N T R O L -> 1 T UR N O N & O FF to enter the TURN ON & OFF screen. This
screen shows one of two displays, TURN ON UPS and TURN OFF UPS, depending on the state of the
UPS.
Select MAIN MEN U -> 3 CO N T R O L -> 2 ALAR M CO N T R O L to enter the ALARM CONTROL screen.
This section allows active audible alarms to be silenced.
To completely turn off the audible alarm, select CO N FIGUR AT IO N > UPS .
Select MAIN MEN U -> 3 CO N T R O L -> 3 BAT T T ES T to enter the BATT TEST screen.
Log Screen
Select MAIN MEN U -> 4 LO G to enter the LOG screen. This screen has two submenus, VIEW LOG
and CLEAR LOG.
Select MAIN MEN U > LO G > CLEAR LO G to enter the CLEAR LOG screen.
Press the Up or Down button to move the cursor to the required item. Press the Enter button to
confirm the settings.
Select MAIN MEN U> ABO UT to enter the ABOUT screen. The ABOUT screen displays UPS model,
serial number, software version and hardware version.
Network
The NETWORK screen displays the MAC address and the IPv4 IP address. If the GXT4 is fitted with
an optional Liebert IntelliSlot Web card (Liebert IS-WEBCARD), the screen will display IPv6 IP
address settings (IPv6 requires configuration).
PROMPT MEANINGS
Mains Power Restored The mains power returns and the UPS transfers back to mains (AC) mode.
UPS Return From A Low Battery Condition The UPS transfers back to mains (AC) mode from battery low mode.
UPS Return From Battery Mode The UPS transfers back to mains (AC) mode from battery mode.
UPS Shutdown Command Received The UPS shut down was initiated through communication.
UPS Turn Off The UPS shuts down and has no output power.
UPS Turn On The UPS starts up successfully and supplies protected power to the load.
UPS Shutdown Process Had Been Cancelled The shutdown command sent through Liebert MultiLink or SNMP card to the UPS is canceled,
ECO Mode Disabled The UPS is configured to Online mode, supplying protected power to the load through the inverter.
UPS Internal Temperature Return To Normal The internal temperature of the UPS recovers to normal range.
UPS Load Return From Overload The loads are reduced, and the UPS recovers to normal state from overload.
Load On Inverter The inverter is on and supplies protected power to the load.
Load On ECO Bypass The UPS is on ECO mode; the mains is supplying power to the load directly to reduce energy usage.
Bypass Power Restored The bypass power recovered and the UPS can now transfer to bypass.
WARNING DESCRIPTION
The mains power is not available, or it cannot satisfy the input requirements for the UPS to operate from mains
Mains Power Not Available
power
The UPS transfers to Bypass mode, at this point, the input mains power supplies power to the load directly, and the
Load On Bypass
load is not protected
Bypass Power Not Available The bypass power is not available, or it cannot satisfy the requirements for the UPS transfers to bypass
FAULT DESCRIPTION
UPS Overtemperature Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode.
If a fault occurs:
1. Enter the ALARM CONTROL screen, and select AUDIBLE ALAR M O N or AUDIBLE ALAR M O FF
to switch the alarm On or Off.
2. Enter the EVENT LOG screen, and select VIEW LO G to view the entire event log.
NOTE: There will be a short delay before the EVENT LOG screen displays the historical fault log to
allow the log to load.
NOTE: The GXT4's battery has been fully-charged before delivery, but some charge will be lost during
storage and shipping. To ensure that the battery has adequate reserve power to protect the connected
load, charge the battery for 5 hours before putting the UPS into service.
1. Check that the input plugs and loads are connected properly and reliably.
2. Check that the internal battery kits are installed.
3. Check that the battery cable is connected properly.
4. Check that the communication cables are connected properly.
4. On the LCD, press either the Up or Down button once, then press the Enter button to turn On
the UPS.
T h e UPS will sou n d th e au d ib le alarm ag ain as th e ou tp u t recep tacles are n ow b ein g p owered
b y th e in tern al b yp ass, th en will sou n d on e m ore tim e as th e in verter p owers th e con n ected
eq u ip m en t.
5. Check the LCD and LED indicators to ensure that the UPS is operating normally.
6. Check the load percentage on the default screen to ensure that the connected equipment is
not exceeding the UPS’s rated capacity.
The UPS is now providing conditioned and protected power to the connected equipment.
• If the battery test results show FAILED, allow the UPS to recharge the batteries for 24 hours.
• Retest the batteries after 24 hours of charging.
• After the batteries have been retested, if the battery test still shows FAILED, contact your local
Vertiv™ representative or Technical Support.
If the internal bypass is not available because of input power problems, pressing this button once will be
ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If
other indicators are illuminated, refer to Troubleshooting on page 59.)
1. From the Main Menu select CO N T R O L, press Enter, then select T UR N O N & O FF.
2. Press the Enter key.
3. Select T UR N UPS O FF, then press Enter. Press either the Up or Down button to move the
cursor to confirm the turn off command and press Enter.
T h e UPS will sou n d an au d ib le alarm . T h is is n orm al.
4. Power to the connected equipment is now Off.
The UPS display will still be illuminated because the batteries are still being charged. The UPS may now
be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds.
After powering Off the UPS, the UPS ceases output and the load is powered Off.
1. Place the UPS on internal bypass. This may be done by either of the following methods:
a. Refer to Performing Manual Bypass on page 44.
b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This
requires loosening the captive screw and sliding the bracket up and away from the
Manual Bypass breaker.
2. Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires
loosening the captive screw and sliding the bracket up and away from the Manual Bypass
breaker.
CAUTION: To maintain safety (SELV) barriers and for electromagnetic compatibility, signal
cables should be segregated and run separate from all other power cables.
The Liebert IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and
®
delivers support for Liebert MultiLink shutdown software.
The Liebert IntelliSlot MultiPort Card provides four sets of contacts for support of up to four computers
that have Liebert MultiLink installed.
The Liebert IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the
network and/or building management system. The Liebert IntelliSlot UNITY card also enables monitoring
external temperature, humidity and contact closure inputs using external sensors.
®
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink , the UPS or
any additional ancillary product for the Liebert GXT4. The instructions are available at
http://www.VertivCo.com/en-us/support/.
LiebertMultiLink can communicate with the UPS via the USB port, RS232 port, contact closures via
terminal block or over the network via SNMP using the Liebert IS-UNITY-DP card. An optional Liebert
MultiLink license kit permits shutting down multiple computers that are protected by the UPS.
For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert
MultiLink License Kits, visit www.VertivCo.com or contact your Vertiv™ representative.
For most users, the factory-default settings are adequate. This section give a brief overview of the
features and parameters that are available for modification, as well as the factory-default settings. Should
any changes be necessary, refer to the Configuration Program User Manual that is located on the
included CD for further details.
GXT4-5000RT208
GXT4-6000RT208
208/120 VAC 200/100V, 208/120V, 220/110V, 230/115V, 240/120V, 220/127V
GXT4-8000RT208
GXT4-10000RT208
NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected
loads.
NOTE: This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’ It
is not compatible with earlier versions of the Liebert GXT UPS.
A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows 7 or
Windows 8 is required to set up and run the configuration program.
NO. DESCRIPTION
2 On-battery warning
• Local Any Mode Shutdown can be performed by shorting the pins in terminal 3.
• Remote Any Mode Shutdown can be performed using a switch mounted at a remote location
and connected to the pins in terminal 3.
NOTE: Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
depending on the settings in the configuration program.
A current-limited source for this optocoupler (+12 VDC, 50 mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.
WARNING! When the Auto-Enable output option is selected and the UPS output is disabled
using Any Mode Shutdown, the GXT4 output can turn On automatically and without warning if
the connection is changed.
• Local Battery Mode shutdown can be performed by shorting the pins in terminal 4.
• Remote Battery Mode Shutdown can be performed using a switch mounted in a remote
location and connected to the pins in terminal 4.
6.3.3 On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the
battery this dry contact will be closed.
The rated values for the dry contacts for the On Battery and Low Battery signals are:
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input
feeder breaker to remove all sources of power to the UPS and connected equipment to comply with
national and local wiring codes and regulations.
NO. DESCRIPTION
UPS ships with REPO jumper installed, allowing the UPS to operate.
1
Normally-closed switch system (fail-safe)
CAUTION: To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables
should be shielded and run separately from power cables.
• The UPS ships with the jumper removed (jumper is in accessory bag.
• To operate the UPS without a REPO connection, the jumper must be installed as shown in the
figure.
• To operate connected to a normally-closed (NC) REPO connection, the jumper is not installed,
and the connection is wired to a remote switch.
Figure 6.6 UPS with jumper installed and wired to NO remote switch
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery
can present a risk of electrical shock and high short-circuit current.
REPLACEMENT INTERNAL
UPS MODEL NUMBER QUANTITY REQUIRED
BATTERY PACK MODEL NUMBER
GXT4-5000RT208
GXT4-144VBATKIT 1
GXT4-6000RT208
GXT4-6000RTL630 GXT4-240VBATKIT 2
GXT4-8000RT208
GXT4-288VBATKIT 2
GXT4-10000RT208
Figure 7.1 Removing the front bezel cover and battery door
3 Front bezel
NO. DESCRIPTION
2 Battery handles
6. Unpack the new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery pack to make sure they are the same type and
model. If so, proceed with 7. If they are different, stop and contact your Vertiv™ representative,
or Technical Support.
7. Line up and slide in the new internal battery pack.
8. Reconnect the battery plug and battery receptacle.
9. Push the battery wire and internal battery pack back into the UPS.
10. Reattach the front battery door with the 6 screws.
11. Reattach the front plastic bezel cover to the UPS.
NOTE: The internal battery pack is hot-swappable. However, caution should be exercised because
during this procedure the load is unprotected from disturbances and power outages. Do not replace
the battery while the UPS is operating in Battery Mode. This will result in a loss of output power and will
drop the connected load.
If the GXT4 will be stored for a long time, We recommend connecting the UPS to input power for at least
24 hours every 4 to 6 months to ensure full recharge of the batteries.
• Check if the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
• Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal Mode. If it
is operating in Bypass Mode, stop and contact your local Vertiv™ representative or Technical
Support.
• Check if the battery is discharging: When the utility input is normal, the battery should not
discharge. If the UPS is operating in Battery Mode, stop and contact your Vertiv™
representative or Technical Support.
Back-up the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are
normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators
are On and the UPS is operating normally.
3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.
The UPS should initiate battery self-test. Check to determine whether the battery is operating
normally. If not, stop and contact your Vertiv™ representative or Technical Support.
CAUTION: The UPS must be switched to maintenance bypass before personnel begin to
replace the power module.
NOTICE
During the procedure, the connected load will not be protected from power disturbances, such
as spikes, sags and failure.
To remove the UPS power module without shutting off power to the connected load:
1. Place the UPS on internal bypass. This may be done by any of the three following methods:
a. Refer to Performing Manual Bypass on page 44.
Figure 7.3 Removing power module from GXT4 8000 and 10,000VA models
NO. DESCRIPTION
NOTE: The power module restraint lever must be fully engaged for the UPS to operate in Normal Mode.
• The relative indicators illuminate, indicating the UPS has detected a problem.
• An alarm buzzer sounds, alerting the user that the UPS requires attention.
8.1.1 Indicator and LCD
In addition to the fault indicator being illuminated, the LCD will display the fault. The displayed fault on
the LCD is described in the following table
UPS self test failed The battery is bad or weak. Contact technical support.
UPS overload The UPS is overloaded. Reduce the load and contact technical support.
Fan Out of Order At least one fan is faulty. Contact technical support.
NOTE: If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the LCD
backlight will flash (on 1 second and off 1 second) as an alert.
Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the LCD
back light will flash again until the UPS fault is corrected.
CONDITION ALARM
UPS is short-circuited or Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure
overloaded loads are not defective or shorted internally.
UPS fails to Check to ensure the internal battery is connected. If it is not, make the connection and try to start the
Batteries are not charged
start unit. If the battery is connected, leave the UPS connected to input power for 24 hours to recharge
enough or not connected
batteries, then try to start the unit.
UPS is not plugged in UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle.
Battery UPS input protection fuse has UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then
indicator is blown/opened restart UPS.
illuminated
Mains power is out of UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is
tolerance within acceptable limits for UPS.
Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries.
UPS has
reduced UPS is overloaded Check load level indicator and reduce the load on the UPS.
battery
backup time Batteries may not be able to Replace batteries. Contact your local dealer, Vertiv™ representative or Technical Support for
hold a full charge due to age replacement battery kit.
Battery Check battery connections, completely power down and restart UPS.
Battery source is not available;
indicator is NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery
continuous horn.
flashing. test is performed.
Unit, in. (mm) 16.9 x 26.1 x 6.8 (430 x 662 x 173) 16.9 x 26.5 x 10.3 (430 x 672 x 261)
Weight lb (kg)
Input AC Parameters
L1-L2 Factory Default Input Phase Angle 120 degrees 120 degrees
User Configurable L1-N, L2-N VAC 100/110/115/120VAC (can be modified with configuration program)
Output AC Parameters
Allowable Output Phase Angle 120, 180, 240 degrees, auto-sensing on initial application of input AC
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
Environmental
Audible Noise less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Agency
Weight, lb (kg)
Input AC Parameters
208/220/230/240VAC
User Configurable VAC
(may be modified with configuration program)
Input Power Connection L6-30P Plug (on PD-L630 power distribution box)
Output AC Parameters
Waveform Sinewave
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
Environmental
Agency
ESD EN61000-4-2
GXT4-5000RT208 GXT4-8000RT208
USED WITH UPS MODEL GXT4-6000RTL630
GXT4-6000RT208 GXT4-10000RT208
Weight lb (kg)
GXT4-5000RT208 GXT4-8000RT208
USED WITH UPS MODEL GXT4-6000RTL630
GXT4-6000RT208 GXT4-10000RT208
Recharge Time 5 hours to 90% capacity after full discharge into 100% load
Environmental
Agency
GXT4-5000RT208 GXT4-8000RT208
USED WITH UPS MODEL GXT4-6000RTL630
GXT4-6000RT208 GXT4-10000RT208
Weight, lb (kg)
Battery Parameters
GXT4-5000RT208 GXT4-8000RT208
USED WITH UPS MODEL GXT4-6000RTL630
GXT4-6000RT208 GXT4-10000RT208
Environmental
Agency
for GXT4-5000RT208, GXT4-6000RT208 and GXT4-6000RTL630*
Dimensions, W x D x H, in (mm)
4.7x13.2x4.1
Unit 5.2x15.5x3.5 (132x393x88)
(119x335x105)
10.2x18.4x8.7
Shipping 9.5x20.7x9.1 (242x527x230) (260x467
x222)
Weight, lb (kg)
Unit 6 (2.7) 8.8 (4) 8.6 (3.9) 8.6 (3.9) 9.9 (4.5) 10.6 (4.8) 9.5 (4.3) 9.5 (4.3) 8.8 (4)
Shipping 8.2 (3.7) 11 (5) 10.8 (4.9) 10.8 (4.9) 12.1 (5.5) 12.8 (5.8) 11.7 (5.3) 11.7 (5.3) 11 (5)
Electrical Specifications
Amp Rating 30A 2-pole input breaker for UPS input power
Hard-Wired Terminal
Input Power
Block 3W + G (L-L-N- (1) L14-30P on a 10.5 ft. (3.2m) cord (1) L6-30P
Connections
G)
(4) 5-20R
Output Hard-Wired Terminal
(1) L14- (2) 5-20R (4) 5-20R (4) L5-20R (4) L5-20R (2) L5-20R (2) L6-30R
Power Block 3W + G (L-L-N- (4) L6-20R
30R (2) L6-20R (2) L6-30R (2) L5-30R (2) L6-30R (2) L6-20R (2) L6-20R
Connection G)
(1) L6-30R
for GXT4-8000RT208 and GXT4-10000RT208
Weight, lb (kg)
Unit 4.4 (2) 6.6 (3) 6.6 (3) 6.6 (3) 4.4 (2) 6.6 (3)
Shipping 6.6 (3) 8.8 (4) 8.8 (4) 8.8 (4) 6.6 (3) 8.8 (4)
Electrical Specifications
Input Power
Custom Connector 3W + G(L-L-N-G) to UPS
Connection
for GXT4-8000RT208 andGXT4-10000RT208
Weight, lb (kg)
Electrical Specifications
Input Power
Custom Connector 3W + G(L-L-N-G) to UPS
Connection
Output Power (4) L5-20R (2) L6-20R (4) IEC320-C19 (2) IEC320-C19 (2) IEC309-32A
(2) L14-30R (12) IEC320-C13
Connections (4) 5-15/20R (2) L6-30R (4) IEC320-C13 (8) IEC320-C13 (4) IEC320-C13
208 VAC RT
NUMBER OF LOAD 208/120 VAC RT MODELS
MODEL
EXTERNAL BATTERY PERCENT OF
CABINETS CAPACITY
5 KVA 6 KVA 8 KVA 10 KVA 6 KVA (L630)
20% 65 52 63 48 39
30% 39 31 42 32 34
40% 27 21 29 22 26
50% 20 15 22 16 18
70% 12 9 14 10 12
80% 10 8 11 7 10
90% 8 6 9 7 9
100% 7 5 8 5 8
30% 92 77 100 79 99
40% 67 53 72 55 67
+ 1 External 60% 40 32 44 34 44
Battery Cabinet 70% 33 26 36 27 34
80% 27 21 29 21 27
90% 23 18 25 20 24
100% 20 15 22 16 21
+ 2 External 60% 68 53 77 57 85
Battery Cabinets 70% 55 43 59 45 66
80% 46 38 49 37 52
90% 40 32 43 35 48
100% 36 27 39 29 43
208 VAC RT
NUMBER OF LOAD 208/120 VAC RT MODELS
MODEL
EXTERNAL BATTERY PERCENT OF
CABINETS CAPACITY
5 KVA 6 KVA 8 KVA 10 KVA 6 KVA (L630)
80% 68 53 72 53 83
90% 57 45 61 50 74
100% 50 40 55 42 65
80% 88 72 92 72 111
90% 78 60 83 67 100
100% 68 53 75 56 90
100% 84 67 91 73 115
208 VAC RT
NUMBER OF LOAD 208/120 VAC RT MODELS
MODEL
EXTERNAL BATTERY PERCENT OF
CABINETS CAPACITY
5 KVA 6 KVA 8 KVA 10 KVA 6 KVA (L630)
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 77°F (25°C) with 100%
resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the individual batteries.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-
discharge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the
battery above table will be restored. This will override any value that is auto-learned.