YORK® Chillers Proactive Parts Replacement Recommendations: Model YZ Magnetic Bearing Centrifugal Chillers
YORK® Chillers Proactive Parts Replacement Recommendations: Model YZ Magnetic Bearing Centrifugal Chillers
Replacement Recommendations
Model YZ Magnetic Bearing Centrifugal Chillers
Proactively check,
inspect, or replace
Major component Part description interval
(chiller run hours)
Chiller system O-rings
Waterbox channel gasket 26,280
and gaskets
Chiller system O-rings
Waterbox head gasket 26,280
and gaskets
Chiller system sensors Entering chilled water temperature sensor 52,560
Chiller system sensors Leaving chilled water temperature sensor 52,560
Chiller system sensors Entering condenser water temperature sensor 52,560
Chiller system sensors Leaving condenser water temperature sensor 52,560
Condenser liquid refrigerant temperature
Chiller system sensors 52,560
sensor / O-ring
Chiller system sensors High pressure cutout switch / O-ring 52,560
Chiller system purge unit Coil temperature sensor 52,560
Chiller system purge unit Suction temperature sensor 52,560
Chiller system sensors Evaporator and condenser water flow sensor 61,320
Chiller system motor
Motor cooling booster pump / O-ring 61,320
cooling
61,320
Compressor PRV/VGD actuators
Inspect; replace only
if necessary
OptiView Coin cell battery 70,080
Chiller system sensors Stall/Discharge pressure transducer / O-ring 87,600
Chiller system sensors Condenser pressure transducer / O-ring 87,600
Chiller system sensors Evaporator pressure transducer / O-ring 87,600
Chiller system valves and
Variable orifice valve actuator 87,600
actuators
Chiller system valves and
HGBP valve actuator (if applicable) 87,600
actuators
Chiller system valves and
FFBP valve actuator (if applicable) 87,600
actuators
Chiller system purge unit Purge inlet solenoid / O-ring 87,600
Chiller system purge unit Purge exhaust check valve / O-ring 87,600
Proactively check,
inspect, or replace
Major component Part description interval
(chiller run hours)
Chiller system motor
Motor cooling EEV / O-ring 87,600
cooling
87,600
1
Compressor Impeller
Check; replace only if
necessary
87,600
Compressor
1 Impeller seal rings
Check; replace only if
necessary
PCBAs VSD logic board 87,600
PCBAs SCR trigger board 100,000
PCBAs Gate driver board 100,000
OptiView Display (backlight) 100,000
Compressor MBC 100,000
VSD DC bus capacitor - main pole 100,000
2
VSD DC bus capacitor - filter pole 100,000
VSD
2 Trap capacitors 100,000
PCBAs Filter logic board 131,400
OptiView IO board (relays) 131,400
OptiView Keypad 131,400
1 Johnson Controls does not recommend teardown of centrifugal compressors based on time intervals. Please contact
Product Technical Support if you think the compressor needs to be inspected in detail and they will guide you through
special checks.
2 This only applies to units that have a harmonic filter option.
This document does not cover recommended maintenance items. Refer to Form 161.01-MR1 for
detailed maintenance recommendations for your equipment.
This document is intended for YORK® chillers that are out of the standard factory warranty.
The guidance in this document is proactive, not reactive. The document is for indicative purposes
only and is based on a wide variety of factors that differ globally, such as installation, usage,
environmental conditions, and maintenance performed since the initial start-up of the chiller.
Additionally, not all parts are stocked in parts centers, and lead times are subject to change. For
your specific chiller installation recommendations, lead times, and pricing guidance, please consult
with your local Johnson Controls service team.