Module 5: Activity No. 1: Length

This document summarizes a problem involving calculating the log mean temperature difference (LMTD), surface area, and flow rate for a water cooler using melting ice. It is given that 100 lb/hr of ice at 32°F is used to cool water from 80°F to 42°F with an inside heat transfer coefficient of 110 BTU/hr-ft2°F. The LMTD is calculated as 61°F. The inside surface area is calculated as 0.2513 ft2. The flow rate of cooled water is calculated as 0.7571 GPM.
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
Download as docx, pdf, or txt
0% found this document useful (0 votes)
95 views3 pages

Module 5: Activity No. 1: Length

This document summarizes a problem involving calculating the log mean temperature difference (LMTD), surface area, and flow rate for a water cooler using melting ice. It is given that 100 lb/hr of ice at 32°F is used to cool water from 80°F to 42°F with an inside heat transfer coefficient of 110 BTU/hr-ft2°F. The LMTD is calculated as 61°F. The inside surface area is calculated as 0.2513 ft2. The flow rate of cooled water is calculated as 0.7571 GPM.
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1/ 3

Module 5: Activity No.

1
Heat Exchangers and LMTD/AMTD Exercises Problem

Name: Quinit, Mel Anthony E.


Student No.: 20160150812
Problem:
A water cooler uses 100 lb/hr of melting ice (32 deg F) to cool running water from 80
deg F to 42deg F. Based on the inside coil area, U i= 110 BTU/hr- sq FT deg F, find:
a) LMTD;
b) Inside surface area
c) GPM of water cooled

LENGTH
GIVEN:
lb
mice =100
hr
BTU
Latent Heat of Fusion of Ice=144
lb
T 1water=80℉

T 2water=42℉

BTU
U i=110
hr −ft 2 ℉
SOLUTION:
Q=U i Ai (LMTD)
Q=mc p ∆ T

∴ U i A i ( LMTD )=mc p ∆ T

BTU
NOTE : For ice use latent heat of fusion of ice=144
lb

∴ U i A i ( LMTD )=m Lf

(110 hr BTU
−ft ℉ ) lb BTU
( A ) ( LMTD )=(100 hr )(144 lb )
2 i

( Ai ) ( LMTD )=130.9091 eqn. 1

Q ice =Qwater

m ice Lf =m water c p ∆ T

(100 hrlb )(144 BTU


lb )
=m water (1)(80−42)℉

lb
m water =378.95
hr

T i+ T o
a.) LMTD= 2

(80+42)℉
LMTD=
2

LMTD=61℉
b.) substitue LMTD=61 ℉ ¿ eqn . 1

130.9091 ft 2 . R
Ai =
( 61 ℉ +460 ) R

Ai=0.2513 ft 2

m water
c.) V = ρ
water

lb
378.95
hr 1 hour gallon
V =( )( )( )
lb 60 minutes 0.13368 f t 3
62.4 3
ft
V =0.7571GPM