Transformer Tests Objectives: Ee - 19 Module 4
Transformer Tests Objectives: Ee - 19 Module 4
TRANSFORMER TESTS
OBJECTIVES
4.1 . Introduction
parameter can be determined by two tests; the open circuit test and short circuit tests. These
tests are convenient and economical, because these can provide data without actually
The purpose of this test is to determine no-load loss or core loss and no-load
92
AMU - 2020
EE – 19 MODULE 4
In this test one of the windings of the transformer is left open and the other is
connected to its supply. A wattmeter, voltmeter and ammeter are connected in the supply
side. When voltage is applied, the flux will be set up in the core; hence, iron losses will
occur and these will be recorded by wattmeter. Cu loss is negligible in the supply side and
nil in the open side. Hence, the wattmeter reading represents practically the core loss under
no load condition.
It must be noted that is very small, and the coils of the voltmeter and the
wattmeter are connected such that current does not pass through them in the current coil of
wattmeter.
reading of the voltmeter gives the induced e.m.f. in the secondary winding. This helps to
Figure 53
= cos ∴ cos = /
load (i.e. ≅ ) and as the voltage drop in primary leakage impedance is small*, hence
93
AMU - 2020
EE – 19 MODULE 4
Example 4.1
In the no-load test of a single-phase transformer, the following test data were
obtained:
(i) its turns ratio (ii) its magnetising component during no-load current (iii) its loss
Solution:
4.3.
Transformer core loss depends on the frequency and maximum flux density when
the thickness of the core lamination and its volume are being given. Core loss is composed
of hysteresis-loss and eddy-current loss. Equations for these losses are given respectively
.
= and = where Q is a constant. For the total core loss, it
is the summation of hysteresis and eddy current loss and given by this equation
94
AMU - 2020
EE – 19 MODULE 4
.
= + = +
different frequencies but with the same maximum flux density, calculate eddy current and
Example 4.2
the same maximum flux density. Calculate the eddy current and hysteresis loss at 50 Hz.
Solution:
For the same maximum flux density, we can use these equations:
= = 0.9 × 50 = ; = = 0.01 × 50 =
Example 4.2
The maximum flux density and a waveform factor are maintained constants during
a power loss test on a 10 kg specimen of sheet steel laminations. During this tests, the
Frequency (Hz) 25 40 50 60 80
Solution:
For the same maximum flux density, we can use this equation;
= + or / = +
95
AMU - 2020
EE – 19 MODULE 4
25 40 50 60 80
The graph between and / has been plotted in Figure 54. As seen from it,
Figure 54
Example 4.3
The hysteresis loss in a 6.6 kV, 60 Hz transformer is 480 W. What will be the loss
Solution:
.
Using = and = 4.44 or = 4.44 ;
=
4.44
where = 1/4.44
96
AMU - 2020
EE – 19 MODULE 4
.
∴ =
.
= …(i)
. .
∴ 480 = (60)
= 4.3337 × 10
. .
∴ = 4.3337 × 10 (40)
=
∴ The hysteresis loss after being connected to a 6.9 kV, 40 Hz source is 657 W.
Example 4.4
that of total iron losses is 2500 W. But when the applied voltage and frequency was set to
220 V, 25 Hz, the iron loss became 850 W. Calculate the eddy current loss at normal
Solution:
The flux density in both cases is the same because in the second case voltage as
Hysteresis loss;
.
= ∝ =
= ∝ =
= + = + ∴ / = +
97
AMU - 2020
EE – 19 MODULE 4
= 250 ; = 850
∴ = = 0.64 × 50 =
4.4.
(iii) Knowing or , for the voltage drop and regulation of the transformer.
Figure 55 shows the short circuit configuration in which one side of the transformer
is being shorted.
Figure 55
98
AMU - 2020
EE – 19 MODULE 4
Figure 56
In this test, the voltage applied to the transformer is small compared to its normal
voltage, therefore the mutual flux produced by this transformer is also small. Hence,
Figure 56 shows the equivalent short circuit condition. If is the voltage required
Also =
∴ = /
∴ = ( − )
Figure 57 (a) present the equivalent vector diagram for short-circuit test. Figure 57
(b) shows the impedance triangle wherein you can determine the equivalent resistance to
primary.
99
AMU - 2020
EE – 19 MODULE 4
Figure 57
4.5. ?
The reason why the transformers rating is in kVA and not in kW is that loss of
transformer depends on the current and iron loss with respect to voltage. The total
transformer loss depends on volt-ampere (VA) and not on phase-angle between voltage
Example 4.5
resistance and reactance referred to primary are 21 ohms and 34 ohms respectively.
Calculate the short-circuit voltage referred to the primary and its power factor.
Solution:
= 230⁄6000 = 23⁄600, = 34 Ω
= + / = 20.9 Ω
= ( + )= 20.9 + 34 = 40 Ω
= 30,000⁄6000 = ; = = 5 × 40 =
100
AMU - 2020
EE – 19 MODULE 4
ℎ . .= / = 20.9/40 = .
Example 4.6
= 0.2 Ω; = 0.5 Ω
= 0.4 Ω; = 0.1 Ω
= 1500 Ω; = 750 Ω
Solution:
∴ = + = 0.745
The voltmeter, ammeter and wattmeter which are connected the primary will read
Suppose S.C. test is performed by short-circuiting the l.v. winding, i.e; the
101
AMU - 2020
EE – 19 MODULE 4
Example 4.7
A, has a power-factor of 0.86 lagging. The no-load current is 0.2 A at 0.21 lagging-power
Solution:
power factor of 0.86 lagging. To this, the no-load current should be added, as per the phasor
diagram in Figure 58. For the load current it has a phase angle of 30° lagging and the no-
Figure 58
= 2.165 + 0.0416
= .
102
AMU - 2020
EE – 19 MODULE 4
= 2.2066 − 1.447
.
= tan = . °
.
. . = cos 33.25 ° = .
103
AMU - 2020