Fault Discrimination Algorithm For Busbar Differential Protection
Fault Discrimination Algorithm For Busbar Differential Protection
ScholarWorks@UNO
Fall 12-16-2016
Recommended Citation
Hossain, Monir, "Fault Discrimination Algorithm for Busbar Differential Protection Relaying Using Partial
Operating Current Characteristics" (2016). University of New Orleans Theses and Dissertations. 2263.
https://scholarworks.uno.edu/td/2263
This Thesis is protected by copyright and/or related rights. It has been brought to you by ScholarWorks@UNO with
permission from the rights-holder(s). You are free to use this Thesis in any way that is permitted by the copyright
and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-
holder(s) directly, unless additional rights are indicated by a Creative Commons license in the record and/or on the
work itself.
This Thesis has been accepted for inclusion in University of New Orleans Theses and Dissertations by an
authorized administrator of ScholarWorks@UNO. For more information, please contact scholarworks@uno.edu.
Fault Discrimination Algorithm for Busbar Differential
Protection Relaying Using Partial Operating Current Characteristics
A Thesis
Master of Science
in
Engineering
Electrical Engineering
By
Monir Hossain
University of New Orleans
December, 2016
Acknowledgement
First of all, I would like to express my utmost gratitude to my academic and research
advisor Dr. Parviz Rastgoufard for his guidance and constant support to conduct and accomplish
this thesis. I would also like to express deepest appreciation to the members of the supervisory
committee, Dr. Ittiphong Leevongwat and Dr. Ebrahim Amiri for their enormous support
Finally, I like to wish acknowledge and thank to my parents, my wife and all of my
friends for their encouragement and moral support to finish this work.
ii
Table of Contents
List of Figures v
List of Table viii
Abstract ix
1 Introduction 1
1.1 Overview of Power System 1
1.2 Overview of Power System Protection 2
1.3 Overview of Busbar Protection 5
1.4 Low Impedance Differential Protection: CT Saturation Issues 10
1.5 Literature Review of Low Impedance Differential Protection 11
1.6 Current Transformer (CT) Saturation 16
1.7 Literature Review of CT Saturation Detection 18
1.8 Scope of Thesis 20
2 Mathematical Modeling 22
2.1 Differential Protection Principle 22
2.1.1 Basic of Differential Protection 22
2.1.2 Restrained Differential Protection 26
2.2 Mathematical Modeling of CT Saturation 28
2.3 Existing Methods to Discriminate Internal and External Faults 35
2.3.1 Phase Angle Comparison Method 35
2.3.2 Differential Rate of Change Method 37
3 Thesis Contribution 39
3.1 Problem Statement: Difficulties to Discriminate Faults 39
3.2 Objective 40
3.3 Mathematical Model of Partial Operating Current and Proposed Algorithm 40
3.3.1 Mathematical Model of Partial Operating Current 41
3.3.2 Proposed Algorithm 48
3.4 Relay Design 50
3.4.1 Data Processor 51
iii
3.4.2 CT Saturation Detection Algorithm 51
3.4.3 Trip Logic Unit 53
4 Test System 55
4.1 Description of the Test System 55
4.2 Transmission Line Data 55
4.3 Generator Data 56
4.4 Load Data 57
5 Simulation and Results 58
5.1 System Modeling at EMTP 58
5.2 Relay Modeling at Matlab 61
5.3 Bus Faults 62
5.4 Results and Discussion 64
6 Concluding Remarks and Future Research 90
Bibliography 93
Vita 97
iv
List of Figures
Figure 2.1 Electrical node or junction 23
Figure 2.2 Two terminal zone under normal condition 24
Figure 2.3 Two terminal zone under fault condition 24
Figure 2.4 Multi terminal zone under normal condition 25
Figure 2.5 Multi terminal zone under fault condition 25
Figure 2.6 Characteristics curve of double slope restrained differential relay 27
Figure 2.7 CT circuit model 28
Figure 2.8 CT excitation curve 29
Figure 2.9 Method of determining the parameters Vs and S 29
Figure 2.10 Postulated instantaneous values saturation curve 30
Figure 2.11 Comparison of the rms/peak relationship for two wave shapes 32
Figure 2.12 Definition of per unit remanence 34
Figure 2.13 External Fault scenario 36
Figure 2.14 Internal Fault scenario 36
Figure 2.15 Trajectory of 𝐼𝑜𝑝 and 𝐼𝑟 37
Figure 2.16 Logic Diagram of Differential Rate of Change Method 38
Figure 3.1 Single phase representation of a typical multi terminal protection zone 41
Figure 3.2 Normal operating condition 42
Figure 3.3 Phasor diagram in normal operational condition 43
Figure 3.4 Internal fault condition 44
Figure 3.5 Phasor diagram during internal fault condition 45
Figure 3.6 External fault condition 46
Figure 3.7 Phasor diagram during external fault condition without CT saturation 46
Figure 3.8 Phasor diagram during external fault condition with CT saturation 47
Figure 3.9 Flow chart of proposed algorithm 49
Figure 3.10 Block diagram of proposed relay 50
Figure 3.11 CT saturation detection algorithm 52
Figure 3.12 Fast CT saturation detection algorithm 52
v
Figure 3.13 Trajectory of operating and restrained current 53
Figure 3.14 Trip logic diagram 54
Figure 4.1 Three bus test system 55
Figure 5.1 EMTP model of three bus test system 59
Figure 5.2 EMTP current transformer (CT) model 60
Figure 5.3 CT secondary currents for LG internal fault 65
Figure 5.4 Responses from proposed method for LG internal fault 65
Figure 5.5 Comparative results for LG internal fault 66
Figure 5.6 CT secondary currents for LL internal fault 67
Figure 5.7 Responses from proposed method for LL internal fault 67
Figure 5.8 Comparative results for LL internal fault 68
Figure 5.9 CT secondary currents for LLG internal fault 69
Figure 5.10 Responses from proposed method for LLG internal fault 69
Figure 5.11 Comparative results for LLG internal fault 70
Figure 5.12 CT secondary currents for LLL internal fault 71
Figure 5.13 Responses from proposed method for LLL internal fault 71
Figure 5.14 Comparative results for LLL internal fault 72
Figure 5.15 CT secondary currents for LLLG internal fault 73
Figure 5.16 Responses from proposed method for LLLG internal fault 73
Figure 5.17 Comparative results for LLLG internal fault 74
Figure 5.18 CT secondary currents for LG high impedance internal fault 75
Figure 5.19 Responses from proposed method for LG high impedance internal fault 76
Figure 5.20 Comparative results for LG high impedance internal fault 76
Figure 5.21 CT secondary currents for LL high impedance internal fault 77
Figure 5.22 Responses from proposed method for LL high impedance internal fault 78
Figure 5.23 Comparative results for LL high impedance internal fault 78
Figure 5.24 CT secondary currents for LG external fault 80
Figure 5.25 Responses from proposed method for LG external fault 80
Figure 5.26 Comparative results for LG external fault 81
vi
Figure 5.27 CT secondary currents for LL internal fault 82
Figure 5.28 Responses from proposed method for LL internal fault 82
Figure 5.29 Comparative results for LLG internal fault 83
Figure 5.30 CT secondary currents for LLG internal fault 84
Figure 5.31 Responses from proposed method for LLG internal fault 84
Figure 5.32 Comparative results for LLG internal fault 85
Figure 5.33 CT secondary currents for LLL internal fault 86
Figure 5.34 Responses from proposed method for LLL internal fault 86
Figure 5.35 Comparative results for LLL internal fault 87
Figure 5.36 CT secondary currents for LL internal fault 88
Figure 5.37 Responses from proposed method for LL internal fault 88
Figure 5.38 Comparative results for LL internal fault 89
vii
List of Tables
Table 3.1 The truth table for trip logic 53
Table 4.1 Transmission line data 56
Table 4.2 Transmission line tower configuration 56
Table 4.3 Generator data 57
Table 4.4 Load data 57
Table 5.1 CT parameters 60
Table 5.2 CT Ψ-I characteristic 61
Table 5.3 Settings for proposed relay 62
Table 5.4 List of bus faults 63
Table 6.1 Comparative summary of the results 91
viii
Abstract
Differential protection is the unit protection system which is applied to protect a
particular unit of power systems. Unit is known as zone in protection terminology which is
equivalent to simple electrical node. In recent time, low impedance current differential
protection schemes based on percentage restrained characteristics are widely used in power
systems to protect busbar systems. The main application issue of these schemes is mis-operation
due to current transformer (CT) saturation during close-in external faults. Researchers have
suggested various solution of this problem; however, individually they are not sufficient to
puzzle out all mis-operational scenarios. This thesis presents a new bus differential algorithm
and investigating its performance for all practical bus faults. Mathematical model of partial
operating current and operating principle of the proposed bus differential relay are described in
details. A CT saturation detection algorithm which includes fast and late CT saturation
operating current based internal-external fault discriminator for high impedance internal faults.
Performance of the proposed relay is validated by an extensive test considering all possible
fault scenarios.
Discrimination; Relay.
ix
Chapter 1
1. Introduction
In Chapter 1 we provide a general idea about a power system and its protection,
especially the bus protection. Various differential protection schemes are used in modern
power systems. Particularly, for bus protection, low impedance differential protection is very
popular and effective [1]. However, current transformer (CT) saturation has a severe impact on
the performance of low impedance differential protection. The overview of current transformer
(CT) saturation and historical review of low impedance bus differential protection as well as
current transformer (CT) saturation are presented. After extensive historical review of existing
Modern power systems are the combination of various complex elements such as
generators, transformers, transmission lines, loads and protection and control equipments.
Generally, power systems are divided into three stages: generation, transmission and
distribution. The most convenient method to generate electricity is to burn fossil fuels to
convert water into steam which is used to rotate a turbine that is connected to the rotor shaft
of an electric generator. Water is also used to turn generators in hydro-electric power plant. In
the last few decades, various new sources of electricity has been introduced which is called
renewable energy such as solar, wind, geothermal and biomass etc. In all cases, the electricity
generated at these facilities flows across the transmission system. Voltage at the generating
stage is normally low, and hence, the generated voltage is raised by using step-up transformers
1
to transmit power over long distance to reduce the higher voltage level transmission loss by
reducing current. At the end of transmission system, voltage is stepped down by using step
down transformer for power flow through distribution system and for supplying to residential
The primary goal of any electric power utility is to provide uninterrupted power to the
end consumer, and to achieve the goal, electric utilities depend on protection systems to
transformers, bus bars, overhead transmission lines operating in abnormal or fault conditions.
Most important criteria of power systems are the balance between generation and
demand and to maintain the balance, utilities all over the world use various control systems
such as supervisory control and data acquisition (SCADA) system and automatic generation
The main purpose of a power system protection is to isolate a faulty section of the
electrical power system from rest of the healthy systems so that the remaining live portion can
function satisfactorily without any severe damage due to fault current [1]. Identification fault
and isolating faulty part from the remaining healthy systems to secure the continuation of
The elementary power system protective device is the fuse. When the current through a
fuse exceeds a certain threshold, the fuse element melts and produces an arc across the
resulting gap that is then extinguished to interrupt the circuit [2]. Given that fuses can be built
as the weak point of a system, fuses are ideal for protecting circuits from damage. Fuses
2
however have two problems: first, after they have functioned, fuses must be replaced as they
cannot be reset. This can prove inconvenient if the fuse is at a remote site or a spare fuse is not
on hand. And second, fuses are typically inadequate as the protective device in most power
systems as they allow current flows well in excess of that that would prove lethal to a human or
animal. In general, fuses are used to protect simple and low power equipments. They are not
suitable to use as the sole safety device in modern day high voltage and complex power
systems.
Modern day’s power system protection schemes are very sophisticated. They are built
by integrating various complex devices or components. Circuit breaker, relay and DC system are
the three main components of any protection scheme of power systems. All of these three
components of protection scheme work simultaneously to give effective security against faults.
Circuit breaker isolates the faulty system from rest of the healthy system and this circuit
breakers automatically open during fault condition due to its trip signal comes from protection
relays [1].
Depending on arc quenching mechanisms, circuit breakers are classified as bulk oil
circuit breaker, minimum oil circuit breaker, SF6 circuit breaker, air blast circuit breaker and
vacuum circuit breaker etc. They are also classified as solenoid circuit breaker, spring circuit
breaker, pneumatic circuit breaker, hydraulic circuit breaker etc. depending on operating
mechanisms.
Power system protection relays are classified as current relays, voltage relays,
impedance relays, power relays, frequency relays, etc. based on operating parameter. As per
3
operating characteristics, they are categorized as definite time relays, inverse time relays,
stepped relays etc. According to operating logic, they are categorized as over current relays,
All the circuit breakers of electrical power systems are DC (Direct Current) operated.
Because DC power can be stored in battery and if situation comes when total failure of AC
power occurs, still the circuit breakers can be operated for restoring the situation by the power
of storage battery . Hence the battery is another essential item of the power system protection.
Some time it is referred as the heart of the electrical substation. An electrical substation battery
or simply a station battery containing a number of cells accumulate energy during the period of
availability of AC supply and discharge at the time when relays operate so that relevant circuit
breaker is tripped.
The main philosophy of protection is that no protection of power systems can prevent
the flow of fault current through the system, it only can prevent the continuation of flowing of
fault current by quickly disconnect the short circuit path from the system [1] [3]. Protection
systems should have several important functional requirements to satisfy this quick
disconnection.
Reliability is the most important requisite of power system protection. The protection
relays should remain inoperative for a long time before a fault occurs; but if a fault occurs, they
should be operated in only those fault conditions for which schemes are commissioned in the
4
system. There may be some typical condition during fault for which some relays should not be
operated or operated after some definite time delay and so protection relays must be
The protective relays must be sufficiently sensitive so that it can be operated reliably
when level of fault condition just crosses the predefined set limit.
protective schemes must operate within set time duration after detecting fault. There must be
a correct coordination provided in various power system protection relays in such a way that
for the fault at one portion of the system should not disturb other healthy portions [4] [5]. Fault
current may flow through a part of healthy portion as they are electrically connected. However,
relays associated with that healthy portion should not be operated faster than the relays of
faulty portion otherwise undesired interruption of healthy systems may occur. If relay
associated with faulty portion is not operated in proper time due to any defect in it, then only
the next relay associated with the healthy portion of the system must be operated to isolate
the fault [4] [5]. Therefore, it should neither be too slow which may result in damage to the
equipment nor should it be too fast which may result in undesired operation.
supply and limit the material damage, are achieved by isolating the faulty element as quickly as
possible. Delay increases not only the risk of damage of faulty element and it’s adjacent
elements, but also the risk of undue disturbance of the normal operation of the whole systems
5
by, for example, loss of stability and reduction of voltage. Hence, no part of power systems can
safely be left unprotected, much less the busbars because of their especially vital position and
function in the system. All means of protection, even those applied to the earliest and simplest
system, have in some way or other contrived to satisfy the precept that all elements of the
system must be protected, including busbars [6]. Busbar is the most critical element of a power
and loads. The effect of a single bus fault is equivalent to many simultaneous faults and usually,
due to the concentration of supply circuits, involves high current magnitudes. Any incorrect
operation would cause the loss of all of these elements. Therefore, protection of busbar
demands high speed, reliability and stability. Failure-to-trip on an internal fault, as well as false
tripping of a busbar during service, or in case of an external fault, can both have disastrous
effect on the stability of the power system, and may even cause complete blackout of the
system [7]. So, it is very essential to incorporate precision and reliability factors during
designing a busbar protection scheme. It was a very old practice in small substations to provide
over-current relays to work for the protection of the busbar and no separate relays were used
for the purpose as this was not found to be cost effective. But, with the increase in substation
equipments and feeder’s complexity, it was felt necessary to go for reliable busbar protection
schemes. The methods most commonly used to protect busbars are frame leakage protection,
The frame leakage method involves insulating the bus-supporting structure and its
switch gear from ground; and interconnecting all the framework, circuit-breaker tanks, etc. to
provide a single ground connection through a current transformer (CT) [6]. The secondary side
6
of that CT is connected with an over current relay. The over current relay drives a multi-
contact auxiliary relay that trips the breakers of all circuits connected to the bus. This method
possible to design other types of switchgear with special provisions for making ground faults
the most probable. If phase to phase faults not involving ground occur, the frame leakage
method would probably not be justified. The frame leakage protection is quite popular in
small indoor installations [8]. This method is most effective for the metal-clad type installation
where provision can be made for effective insulation from ground. Certain existing
installation may not be adaptable to fault-bus protection, owing to the possibility of other
paths for short-circuit current to flow to ground. It is necessary to insulate cable sheaths
from the switchgear enclosure and entrance bushing support from the rest of the structure
otherwise cable ground-fault currents may find their way to ground through the fault-bus CT and
improperly trip all the switchgear breakers. For sectionalized bus structure, separate frame
leakage relaying must be employed for each section. The frame leakage method does not
of the fault currents flow in all the circuits connected to the busbar. For bus faults, currents
through all circuits connected to the bus flow toward bus; however, fault current flows
outward from the busbar in at least one circuit for external fault [6]. Typically, this principle
has been used only with ground relays, on the basis that most bus faults start as ground faults, or
at least that they very quickly involve ground. This greatly reduces the cost of the equipment.
7
Phase relays can also be used; however, it is more costly than other bus protection systems.
The chief disadvantage of this scheme is the greater maintenance required and the
greater probability of failure to operate because of the large number of contacts in series in
the trip circuit [3]. Another disadvantage is that connections from the current
transformers in all the circuits must be run all the way to the relay panel if phase relays were
used. Moreover, phase would depend on bus voltage for polarization, and, therefore, they
might not operate for a metallic short circuit that reduced the voltage practically to zero.
Differential protection is widely used to protect busbar because of its versatility and cost
effectiveness. Differential relays are very sensitive to the faults occurred within the protected
zone but they are least sensitive to the faults that occur outside the protected zone. The
operating principle of differential relay is somewhat different from other relay. The differential
relay operates when there is a difference between two or more similar electrical quantities
exceeds a set or threshold value. In differential relaying scheme, more than one current come
from different parts of an electrical node or junction. Summation of these currents passes
through the relay coil. According to Kirchhoff Law, the phasor sum of these currents is zero at
normal operating condition [9]. Therefore, no current will be flowing through the relay coil at
normal operating conditions. But due to any abnormality in the node or junction, the phasor
sum of these currents no longer remains zero and this non-zero current will be flowing through
the relay coil therefore relay being operated. In differential scheme, more than one set of
current transformer are involved to protect equipment by differential relay. The ratio of the
current transformer (CT) needs be chosen carefully. The polarity of CTs is another very
important issue for differential protection. Differential scheme is only used for clearing the fault
8
inside the protected zone or equipment in other words differential relay should clear only
internal fault of the zone or equipment [10]. Therefore, the protected zone or equipment
should be isolated as soon as any fault occurred inside the equipment or zone. They need not
be waiting or delaying for coordination with other relays in the system. There are mainly two
types of differential protection system depending upon the principle of operation: voltage
connected in such a way that EMF induced in the secondary of current transformers (CTs) will
oppose each other according to the original current direction at primary circuit. The differential
relay coil is connected in the loop created by series connection of secondary of CTs. In normal
operating conditions and also in through fault conditions, resultant EMF is zero and hence no
current would be flowing through the relay coil. But as soon as any internal fault occurs in the
protected zone, the resultant EMF is no longer balanced hence current starts flowing through
the relay coil and finally trips circuit breakers [3]. Multi tap transformer construction is required
such a way that the secondary currents of CTs will oppose each other according to the original
current direction at primary circuit. Summation of these currents which is called operating
current which passes through the operating coil of the relay element. Ideally, under normal
operating conditions or external through fault conditions, current summation is zero; hence no
current will be flowing through the relay coil. However, if any ground fault occurs inside the
9
protected zone, summation of secondary currents will be no longer zero. In this situation the
differential relay is being operated to isolate the faulty zone from the system [11] [12].
According to the type of relay used, there are two kinds of current balanced differential
resistance. Here, voltage relay is used that means relay is operated by voltage [3]. Any
operating current is forced through the high impedance causing voltage drop across the relay
In low impedance differential protection, a relay operated by current is used and it has
low impedance current inputs. If any operating current resulting from an internal fault passes
through the operating coil of the relay and relay gets trip.
become popular to protect busbars. Low impedance differential protection schemes are
operated based on operating current which is the summation of all CT secondary currents.
Practically summation of the secondary current is not zero even for normal operating
hence there may be spill current flowing through the relay in normal operating conditions.
the remote relay panel. These uneven pilot cables’ capacitance causes high current through the
relay operation coil when large external through fault occurs. This operating current is known
10
as false operating current and it becomes high during high loading conditions or high system
congestion. To overcome these issues, the concept of restrained current has been adapted with
low impedance differential scheme. This modified scheme is known as percentage restrained
differential protection because the operating current required to trip can be expressed as a
current. In most of the cases, the restrained current is defined by half of the summation of
secondary currents magnitude of all CTs involved with protected zone [13]. Under normal and
through fault conditions, operating current is less than a percentage of restraining current
therefore relay remains inactive. During internal fault, the operating current becomes greater
The main application issue with this modified differential protection is to make it secure
from mal-operation in response to the CT saturation during close-in external faults. During
close-in external faults, probability of CT saturation becomes high and this CT saturation creates
high operating current in CT secondary circuit which causes the undesired operation of relay.
The primary reason for such mal-operation is the fact that the traditional percentage
differential principle relies exclusively on current magnitude rather than directionality for
tripping decisions. Therefore, proper discrimination of external and internal fault becomes the
current transformer saturation especially during external fault, several techniques were
proposed by different scientists and researchers. This section reviews available fault
11
discrimination techniques to secure current balanced bus bar differential protection system
Multi slope Percentage restrained differential protection is one of the oldest forms of
adaptive protection algorithms. The slope characteristic can provide high sensitivity when low
levels of current are flowing in the zone of protection but has less sensitivity when high levels of
current are flowing [14]. This improves security because CTs are more prone to saturation when
they have to reproduce high levels of current in the primary circuits. Although the above slope
characteristic provides some security against CT errors, it is not adequate for all practical
scenarios. Two common failures reported with conventional slope characteristics are due to CT
saturation which occurs during close-in external faults and the subsidence currents present
prevent mal operation of bus differential relay during CT saturation in external fault. However,
they are failed to provide complete solution as CT can also be saturated during internal fault. A
the harmonics contained in the differential current are larger than the threshold, the relay is
inhibited. The method ensures stability on an external fault, but delays the operating time of a
relay for an internal fault until after the DC component decays to a low value. When a CT
saturates, the operating time is significantly increased. An algorithm that detects the onset of
CT saturation based on the first-difference function of the current was described by Phadke and
Thorp [16]. It assumes the current immediately collapses to zero when the CT enters saturation.
12
Difficulties arise if the current does not collapse to a low value during saturation. A solid-state
busbar protection relay was proposed by Royle and Hill [17]. The relay detects the onset of
saturation by detecting when the current collapses to a low value. It then shunts the current
away from the operating circuit by closing a switch adjacent to the saturated CT. Although this
technique prevents an external fault, the relay causes an operating time delay when a CT
countermeasure for CT saturation was reported by Andow et al. [18]. The waveform
discriminating element (WDE) is based on the assumption that the differential current during
an external fault is nearly zero between the periods that corresponds to CT saturation. The
WDE detects the onset of saturation by comparing the change in the instantaneous differential
current against the instantaneous restraining current. The relay is inhibited for a predetermined
period if the former is significantly less than the latter. The WDE is unable to indicate which CT
is saturated and the blocking scheme may delay the operation of the relay on an internal fault.
In addition, for a power system with a large primary time constant, a larger blocking period is
protection was described by Fernandez [19]. The detection algorithm relies on the assumption
that the current is decreased during saturation and thus the impedance is increased. The
impedance is calculated at the relaying point and compared with the source impedance. If the
estimated impedance is larger than the source impedance, saturation is detected and a
blocking signal is issued. The algorithm is only valid if, after fault occurrence, the change in the
impedance is negligible until saturation starts. Thus, it is difficult to detect saturation when the
13
impedance increases significantly after fault occurrence. In addition, the algorithm uses a
voltage signal to detect saturation and thus can cause an increase in the operating time. A
microprocessor-based bus bar protection system that estimates the impedances of the
positive- and negative sequence circuits for every feeder connected to the busbar was
proposed by Gill et al. [20]. The basic idea of the algorithm is similar to phase angle comparison.
It compares the direction of current flow for each feeder and consequently is less dependent on
the effect of CT saturation than a magnitude comparison algorithm [21]. The technique detects
an internal fault if all the impedances seen by every feeder are located in the third quadrant of
the impedance plane. The performance of the technique is satisfactory for mild saturation.
However, correct operation of the technique is not guaranteed for severe saturation caused by
a high level of remnant flux. Moreover, the technique requires significant computational
burden as compared with phase angle comparison, since it calculates the positive- and negative
sequence components of the voltages and currents for every feeder. Yong-Cheol Kang et al.,
has proposed a bus differential relay which operates in conjunction with a saturation detection
algorithm based on the third-difference function applied to the current signal [22]
A wavelet transform (WT) based busbar protection scheme that utilizes detail
decomposition of differential current to detect internal faults [23]. The algorithm relies on the
assumption of time shift in transients between differential current and source current as most
of the connected elements are inductive. However, the transients associated with the source
current and the fault current are independent of location of fault (internal or external) which
polarities of peak d-coefficients obtained from Multi Resolution Analysis to prevent this mal-
14
operation; even then, this technique is vulnerable at CT saturation and high impedance internal
fault.
The preservation of current phase angle always takes place even if CT saturation or dc
offset conditions occur to the input ac currents. As a result, if the phase angle of the current
waveforms is compared with the phase angle of each of the input bus currents, a decision can
be made whether a fault is external or internal to the differential protected zone irrespective of
the waveform distortions due to the errors in CTs. Comparing phase currents in near real time,
a comparison can be made between currents that are entering the bus and those currents that
are leaving the bus. This is intuitively true since Kirchoff’s law also applies to phase angles as
well as to current magnitudes. However, the key challenge in this method is estimation of
phase angles between all current phase angles rapidly in real time. A technique based on dot
product was used in reference [13] [24] to determine the differences in phase angles. This
technique is suitable for transformer differential protection where two input currents are
involved. But it is critical to implement for bus bar differential protection as more than two
input currents are involved. Moreover, during a high impedance internal bus fault, load flow
may continue to flow on passive elements and may cause the phase angles function to block
operating current and restrained current [24] [25]. The detection algorithm relies on the
assumption that for an internal bus fault, the rate of change of operating current is greater than
the rate of change of restrained current whereas for external faults, the rate of change of
15
restrained current is greater than the rate of change of operating current. This technique
provides security for low CT saturation during external fault. However, it has limitation for
saturated.
determine busbar fault type whether internal or external to make relay trip or no trip decision,
respectively [26]. The variance between any two signals is defined as the alienation coefficient,
which is obtained from correlation coefficient. For internal fault, alienation coefficient is greater
than zero and for external fault it is less than zero. In case of CT saturation, this technique
compares the alienation coefficients of unsaturated portion and saturated portion of current to
discriminate the fault. It assumes current remains unsaturated in first quarter cycle. This
technique provides security for slow CT saturation during external fault. However, it leads mal-
Protective relays are actuated by current and voltage supplied by current and voltage
transformers. These transformers provide insulation against the high voltage of the power
circuit and also supply the relays with quantities proportional to those of the power circuit,
but sufficiently reduced in magnitude so that the relays can be made relatively small and
cost effective. All types of current transformers are used for protective-relaying purposes. The
bushing CT is almost invariably chosen for relaying in the higher-voltage circuits because it is
less expensive than other types. It is not used in circuits below about 5 kV or in metal-clad
16
equipment [3]. All CT accuracy considerations require knowledge of the CT burden. The
external load applied to the secondary of a current transformer is called the burden. The
burden is expressed preferably in terms of the impedance of the load and its resistance and
reactance components. The term burden is applied not only to the total external load
connected to the terminals of a current transformer but also to elements of that load.
Protective relay accuracy and performance are directly related to the steady state and
transient performance of the CTs. Protective relays are designed to operate in a shorter time
than the time period of the transient disturbance during a system fault. Large errors of CT
transient may delay or prevent relay operation. CT output is impacted drastically when the CT
operates in the nonlinear region of its excitation characteristic [27]. Operation in this region is
initiated by:
o Residual magnetism left in the core from an earlier asymmetrical fault, or field
currents.
The instantaneous CT secondary current is the sum of the instantaneous burden current
and the magnetizing current. The CT steady-state magnetizing current is very negligible as long
as the CT operates in its linear region; therefore the burden current is a replica of the primary
current adjusted by the CT ratio. When the CT is forced to operate in its nonlinear region, the
magnetizing current can be very large due to a significant reduction of the saturable
17
magnetizing inductance value. The magnetizing current which can be considered as an error
current, subtracts from burden current and drastically affects the current seen by the
connected burden on the CT secondary winding. When the CT saturates because of the dc
component, it can do so in the first few cycles of the fault. Long dc time constant offset faults
saturation during close-in external faults. This CT saturation creates high operating current in
CT secondary circuit which causes the undesired operation of relay. Proper CT saturation
detection is one of the major concerns to prevent mal-operation of bus bar differential
protection.
A CT saturation algorithm has been proposed based on waveform model by A.G. Phadke
and J. S. Throp [16]. It is based on the fact that secondary current is abruptly changed when CT
saturation sets in. However, this algorithm fails when CT secondary current changes slowly.
Another waveform method based on long data window has been proposed to detect CT
saturation [29]. Computational time is comparatively high for this method because number of
involved variables is more. Therefore, this method is slow to use together with any fast tripping
algorithm. An algorithm based on the core flux calculating from a secondary current and then
compensating the distorted secondary current was proposed [30]. The algorithm can
successfully calculate the core flux and detect CT saturation in various conditions. However, this
method is based on the assumption that the remanent (residual) flux at the beginning of
calculation is zero.
18
Based on evaluating mean of error and the mean and variance of current amplitude, a
CT saturation detection method was suggested [31]. The error is calculated on the assumption
that the current is a perfect sinusoid. Hence the summation of the current and its second-order
detection algorithm for bus-bar differential protection [19]. It is based on the first-order
differential equation for the power system source impedance at the relay position and uses the
An algorithm based on the third difference of a secondary current has been presented
because it has large value than first and second difference. However, an anti-aliasing low-pass
filter softens the current and, thus, reduces the values of the third difference at those instants.
Selection of sampling rate is very important to overcome the effect of a remanent (a term used
by IEEE) flux in the core and a low-pass filter on the proposed algorithm.
current transformer (CT) saturation [33].The proposed algorithm computes the positive-
also monitors the rate of change of the sequence component currents. The sequence
component domain of differential current allows the differential protection scheme to more
sensitively detect the system changing from a symmetrical condition to an asymmetrical fault
condition. This concept is applied to detect CT saturation which gives an early indication of a CT
19
An algorithm has been developed to detect CT saturation by comparing the angle
difference between the second harmonics of the rate of change of operating current and the
rate of change of restrained current [34]. In this algorithm, the phase between the second
harmonic of the derivatives of the operating current and restrain current is estimated and
The purpose of this research is to develop a fault discrimination algorithm that is based
Finally, a bus differential relay is designed by incorporating the proposed fault discrimination
algorithm and its performance is validated by an extensive experimental study. The detail scope
o Modeling a three bus test system in EMTP which includes all possible elements
of power systems such as transmission line, generator (active source) and load
(inactive source).
20
o Simulating all possible bus faults (12 scenarios) and finding the responses of
proposed relay.
o Comparing results with two latest existing methods, namely, delta phase angle
21
Chapter 2
2 Mathematical Modeling
transformer (CT) saturation are discussed in detail. Different existing methods to discriminate
Power systems can be divided into different blocks or units such as generator,
transmission line, transformer, bus and motor etc. Protection systems are applied to the system
can be classified into two categories such as unit protection or non-unit protection. Differential
protection is the unit protection system which is applied to protect a particular unit. Unit is
known as zone in protection terminology which is equivalent to simple electrical node. The unit
Kirchhoff's current law is the principle of conservation of electric charge which implies
that: at any node (junction) in an electrical circuit, the sum of currents flowing into that node is
equal to the sum of currents flowing out of that node, or equivalently the algebraic sum of
22
Figure 2.1: Electrical node or junction [35]
∑ 𝐼𝑘 = 0 (2.1)
𝑘=1
Where n is the total number of branches with currents flowing towards or away from
∑ 𝐼⃗𝑘 = 0 (2.2)
𝑘=1
The law is based on the conservation of charge whereby the charge (measured in
coulombs) is the product of the current (in amperes) and the time (in seconds). Differential
protection works based on above mentioned Kirchhoff’s current law. According to Kirchhoff’s
current law, under normal condition input current equals to output current for a power system
23
zone [35]. In power system, zone can be two terminals such as transformer, transmission line
In case of two terminal zone as shown in Figure 2.2, when system is normal
With multi terminal zone as shown in Figure 2.4, when system is normal
𝐼𝑖𝑛 = 𝐼𝑜𝑢𝑡
𝐼2 + 𝐼3 = 𝐼1
24
𝐼1 − 𝐼2 − 𝐼3 = 0 (2.5)
𝐼1 + 𝐼2 + 𝐼3 = 0 (2.6)
Eq. (2.6) shows in normal system condition, vector summation of all terminal currents
With multi terminal zone as shown in Figure 2.5, when system is faulty
𝐼𝑖𝑛 ≠ 𝐼𝑜𝑢𝑡
𝐼2 + 𝐼3 ≠ 𝐼1
𝐼1 − 𝐼2 − 𝐼3 ≠ 0 (2.7)
𝐼1 + 𝐼2 + 𝐼3 ≠ 0 (2.8)
25
Figure 2.5: Multi terminal zone under fault condition
Eq. (2.8) shows in abnormal or faulty system condition, vector summation of all terminal
Practically, summation of CT secondary currents is not zero even for normal operating
conditions due to the mismatch of CT ratio and burden. Hence there is some spill current
flowing through the relay in normal operating conditions which is known as false operating
current. It becomes high during high loading conditions or high system congestion. To
overcome these issues, the concept of restrained current has been adapted with low
impedance differential scheme. This modified scheme is also known as percentage restrained
differential protection. In this scheme, the operating current is compared with the restrained
26
Figure 2.6: Characteristics curve of double slope restrained differential relay
Usually, restrained current defined by Eq. (2.10) is most widely used. The characteristics
27
𝐼𝑜𝑝 > 𝑆1 (𝐼𝑟 − 𝐼𝑟𝑜 ) + 𝐼𝑜𝑝0 → 𝑇𝑟𝑖𝑝
S1 and S2 are the slopes. The value of S1 varies from 0.4 to 0.7 and value of S2 varies from
0.5 to 0.75 [36]. Iop0, Iro and Ir1 are the relay settings and their values depend on system
parameters.
28
Figure 2.8: CT excitation curve [37]
Two parameters S and VS can be extracted from the curve as shown in Figure 2.9.
The reason for choosing the saturation voltage, Vs, at the point where the excitation
current is ten amps, is that this is the definition used in the standard [37]. The straight line
curve with slope 1/S shown in Figure 2.9 is not linear. It is a curve defined mathematically as
1
𝑙𝑜𝑔𝑉𝑒 = 𝑆 𝑙𝑜𝑔𝐼𝑒 + 𝑙𝑜𝑔𝑉𝑖 (2.12)
29
where Vi is the value of Ve for Ie=1, that is for log Ie=0.
1
𝑉𝑒 = 𝑉𝑖 𝐼𝑒𝑆 (2.13)
In order to solve the circuit of Figure 2.7, the instantaneous λ (flux-leakage) versus ie
𝑖𝑒 = 𝐴. 𝜆𝑆 (2.14)
is suitable as long as the exponent S is an odd integer [37]. In order to allow S to be any
positive number, and keep the function odd, the following expression can be used:
where sgn(λ) is the sign of λ as shown in See Figure 2.10 and A is a constant.
law [38] as
30
𝑑𝜆
𝑣𝑒 = (2.16)
𝑑𝑡
The excitation curve is assumed as sinusoidal voltage, which implies that the flux-
1
𝜆 = ∫ 𝑣𝑒 𝑑𝑡 = ∫ √2𝑉𝑒 cos(𝜔𝑡) 𝑑𝑡 = √2𝑉𝑒 sin(𝜔𝑡) (2.18)
𝜔
𝑆 𝑆
1 1
𝑖𝑒 = 𝐴𝜆 = 𝐴 [ √2𝑉𝑒 sin(𝜔𝑡)] = 𝐴 [ √2𝑉𝑒 ] sin𝑆 (𝜔𝑡)
𝑆
(2.19)
𝜔 𝜔
2𝑆
1 2𝜋 2 1 2𝜋 2 √2𝑉𝑒
𝐼𝑒 = √ ∫ 𝑖𝑒 𝑑𝑡 = √ ∫ 𝐴 [ ] sin2𝑆 (𝜔𝑡)𝑑𝑡
2𝜋 0 2𝜋 0 𝜔
𝑆
√2𝑉𝑒 1 2𝜋
= 𝐴[ ] √ ∫ sin2𝑆 (𝜔𝑡)𝑑𝑡 (2.20)
𝜔 2𝜋 0
𝑟𝑚𝑠
𝑅𝑃 = 𝑝𝑒𝑎𝑘 (2.21)
31
√ 1 ∫2𝜋 (√2𝐼𝑒 ) sin2𝑆 (𝜔𝑡)𝑑𝑡
2
2𝜋 0
𝑅𝑃 =
√2𝐼𝑒
1 2𝜋
= √ ∫ sin2𝑆 (𝜔𝑡)𝑑𝑡 (2.22)
2𝜋 0
The difference between RP for a sinusoid and RP the assumed excitation current
waveform is illustrated in Figure 2.11. The factor RP gets smaller as the value of S increases.
Figure 2.11: Comparison of the rms/peak relationship for two wave shapes [37]
𝑆
√2𝑉𝑒
𝐼𝑒 = 𝐴 [ ] 𝑅𝑃 (2.23)
𝜔
𝑆
√2𝑉𝑠
10 = 𝐴 [ ] 𝑅𝑃
𝜔
Solving for A:
32
10𝜔 𝑆 1
𝐴= 𝑆 (2.24)
(√2𝑉𝑆 ) 𝑅𝑃
10𝜔 𝑆 1
𝑖𝑒 = 𝑠𝑔𝑛(𝜆) 𝑆
|𝜆|𝑆 (2.25)
(√2𝑉𝑆 ) 𝑅𝑃
Now, applying Kirchhoff’s Voltage Law around the right-hand loop of the circuit in Figure
2.7, yields
𝑑
𝑣𝑒 − (𝑖𝑠 − 𝑖𝑒 )𝑅𝑡 − 𝐿𝑏 [𝑖 − 𝑖𝑒 ] = 0 (2.26)
𝑑𝑡 𝑠
𝑖1 √2𝐼𝑝 𝑡
𝑖𝑠 = = [𝑂𝑓𝑓. 𝑒 −𝜏 − cos(𝜔𝑡 − cos−1 𝑂𝑓𝑓)]
𝑁 𝑁
Where Off = per unit dc-offset magnitude and 𝜏 = system time constant.
Note that
𝑑𝑖𝑒 𝑑𝑖𝑒 𝑑𝜆
= . (2.28)
𝑑𝑡 𝑑𝜆 𝑑𝑡
𝑑𝑖𝑒
= 𝐴. 𝑆. |𝜆|𝑆−1 (2.29)
𝑑𝑡
33
Finally, with substitutions and manipulation, equation (2.26) can be re-written as
𝑑𝜆 𝑑𝑖𝑠
[1 + 𝐿𝑏 𝐴 𝑆 |𝜆|𝑆−1 ] = −𝑅𝑡 𝑖𝑒 + 𝑅𝑡 𝑖𝑠 + 𝐿𝑏 (2.30)
𝑑𝑡 𝑑𝑡
This first-order nonlinear differential equation is solved for λ(t) using standard numerical
analysis techniques. Then the excitation current ie is given by equation (2.14), and the actual
secondary current is
𝑖2 = 𝑖𝑠 − 𝑖𝑒 (2.31)
because non-zero λ cannot occur for zero ie . However, remanence can be approximated very
closely by simply assuming that the initial excitation current is non-zero. For convenience, λrem
𝑥
𝜆𝑟𝑒𝑚 = (2.32)
𝑉𝑆
In order to specify λrem accurately, x must be specified no greater than Vknee [37].
34
2.3 Existing Methods to Discriminate Internal and External Faults
against current transformer (CT) saturation; however, it is not enough for all practical external
fault scenarios. Researchers have proposed various techniques and schemes to discriminate
internal and external fault for providing more security for differential protection against CT
Phase Angle Comparison Method principle essentially monitors the phase angle
relationships with the incoming and the outgoing currents of a protected zone. As
implementing the phase angle in real time is a challenging task, the phase angles of the
combination of various incoming and outgoing currents are executed in real-time using the dot-
product method to compare whether the phase angle difference is within the threshold value
to declare whether the fault is internal or external (Figure 2.13 & 2.14) to the zone of
𝐼 . 𝐼
𝑐𝑜𝑠𝜃𝑖𝑗 = |𝐼𝑖 | |𝐼𝑗| (2.33)
𝑖 𝑗
Where, the term 𝑐𝑜𝑠𝜃𝑖𝑗 directly indicates the phase difference between the two
𝑖 , 𝑗 = 1,2, … , 𝑛
35
If 𝑐𝑜𝑠𝜃𝑖𝑗 is greater than a specific threshold value (𝑐𝑜𝑠𝜃0 ) for all combinations of i and j,
𝐼𝑖 . 𝐼𝑗
> 𝑐𝑜𝑠𝜃0
|𝐼𝑖 | |𝐼𝑗 |
Any phasor current with a magnitude less than a specific set value (𝐼0 ) is excluded from
this algorithm.
36
2.3.2 Differential Rate of Change Method (ROCOD)
During faults, operating current (𝐼𝑜𝑝 ) and restrained current (𝐼𝑟 ) change as Figure 2.15.
From the trajectory of 𝐼𝑜𝑝 and 𝐼𝑟 during internal and external faults, it can be concluded that
the rate of change of 𝐼𝑜𝑝 is greater than the rate of change of 𝐼𝑟 for an internal fault, whereas
for external faults, the rate of change of 𝐼𝑜𝑝 is less than the rate of change of 𝐼𝑟 [24] [25] [39].
Equation 2.35 indicates the condition for Internal Faults while External Faults satisfy
𝑑𝐼𝑜𝑝 𝑑𝐼𝑟
> (2.35)
𝑑𝑡 𝑑𝑡
𝑑𝐼𝑜𝑝 𝑑𝐼𝑟
< (2.36)
𝑑𝑡 𝑑𝑡
37
The detail logic of differential rate of change method is presented in Figure 2.16. To
declare a fault as an internal fault, the fault needs to satisfy two conditions. First, the rate of
change of operating current (Iop) as well as the rate of change of restraint current (Ir) must be
the positive. To ensure this the rate of change of operating current (Iop) as well as the rate of
change of restraint current (Ir) are compared with a small positive threshold value (Ith).
Secondly, the rate of change of 𝐼𝑜𝑝 must be greater than the rate of change of 𝐼𝑟 .
well as two widely used fault discrimination methods has been described in details. The next
chapter will cover the main contributions of this thesis which includes mathematical modeling
of a proposed fault discrimination algorithm as well as the design details of a differential bus
38
Chapter 3
3 Thesis Contributions
Chapter 2 has given the insight of differential protection principle, current transformer
(CT) saturation, and existing techniques to discriminate internal and external faults. This
chapter starts by describing the fault discrimination difficulties for low impedance current
balanced differential protection schemes and explains a new methodology to address the
issues. Finally, the design details of a differential bus protection relay are presented which
The main concern with bus differential protection is to make it secure from mal-
operation in response to the CT saturation during external faults. During external faults, when
fault current becomes high, CT can get saturated. The CT saturation creates high operating
current which causes the undesired operation of relay. The primary reason for such mal-
operation is the fact that the traditional differential principle relies exclusively on current
There are several existing techniques to discriminate between internal fault and
external fault for bus differential protection. CT saturation detection supervision is one of the
earliest techniques, however, it fails to provide complete solution as CT can also be saturated
during internal fault. Phase angle comparison is very widely used technique, although it has
computational complexity when large numbers of input currents are involved. Moreover,
during a high impedance internal bus fault, load flow may continue to flow on passive elements
39
which may cause the phase angles function to block the relay from tripping for the internal
fault. The latest proposed method is based on rate of change of operating and restrained
3.2 Objective
discriminate between internal and external faults. Based on this algorithm, a differential relay
will be designed for bus protection which is capable of overcoming the impact of CT saturation.
This thesis presents a new fault discrimination algorithm by defining partial operating current
In power system, differential protection zones are two types; two terminals such as
transformer or transmission line and multi terminals such as busbar. Figure 3.1 shows a typical
multi terminals protection zone which has three terminals. Terminal is a branch-circuit where
transmission line or generator or load is connected. This is the single phase representation of a
three phase system. Differential protection works on phase wise differential zone which means
all elements of a zone must be in same phase. Although Figure 3.1 displays a zone with three
terminal, physical zone may have more than three terminal which will be addressed in the later
40
Figure 3.1: Single phase representation of a typical multi terminal protection zone
terminal currents of a protection zone based on the definition of vector sum. The partial
operating current phasors 𝐼𝑜𝑝1 and 𝐼𝑜𝑝2 for Figure 3.1 are defined as Equation (3.1) and
𝐼𝑜𝑝1 = 𝐼1 + 𝐼2 (3.1)
In Equation (3.1) and Equation (3.2): 𝐼1 , 𝐼2 , and 𝐼3 are the phasor currents of three
terminals respectively. The magnitude and direction of any resultant partial operating current
depends on the magnitude and direction of its two input currents. If both input currents leave
the zone, then the resultant partial operating current will be greater than the larger one of its
two input currents in magnitude and its direction will be out of zone. Similarly, if both input
currents enter to the zone, then the resultant partial operating current will be greater than the
larger one of its two input currents in magnitude and its direction will be towards the zone.
However, if the input currents are in opposite direction which means one is toward zone and
another one is out of zone, then the resultant partial operating current will be smaller than the
41
larger one of its two input currents in magnitude and its direction will be same as larger input
current.
The operation of power systems are categorized as normal operation and fault
conditions. Faults can be categorized further as internal fault to the protection zone and
external fault to the protection zone. The characteristic metrics of newly defined partial
operating current corresponding to the three operation categories are described next.
Metric 1: Normal operation: As stated in Kirchhoff Current Law, for normal operational
condition the vector summation of the currents entering to a zone must be equal to vector
summation of the currents leaving from the zone [35]. Figure 3.2 shows a protection zone in
normal operating condition, where I1 and I2 are entering to the zone and I3 is leaving from the
zone. The partial operating currents Iop1 and Iop2 are presented as Equation (3.3) and Equation
(3.4) respectively.
𝐼𝑜𝑝1 = 𝐼1 + 𝐼2 (3.3)
Ideally, for normal operating condition, Iop2 = 0 . Figure 3.3 displays phasor
representation of the terminal and partial operating currents. As displayed in the phasor
42
diagram of Figure 3.3, for normal operation, magnitude of 𝐼𝑜𝑝1 is greater than the magnitude of
𝐼1 as well as magnitude of 𝐼2 ; however, magnitude of 𝐼𝑜𝑝2 is less than the magnitude of 𝐼𝑜𝑝1 as
|𝐼𝑜𝑝1 | > max(|𝐼1 |, |𝐼2 |) 𝑎𝑛𝑑 |𝐼𝑜𝑝2 | < max(|𝐼𝑜𝑝1 |, |𝐼3 |) (3.5)
Although Figure 3.2 displays a zone where I1 and I2 are entering to the zone and I3 is
leaving from the zone, current direction could be varied for a physical zone in normal
operation. If we consider 𝐼1 is entering the zone while 𝐼2 and 𝐼3 are leaving the zone, then the
|𝐼𝑜𝑝1 | < max(|𝐼1 |, |𝐼2 |) 𝑎𝑛𝑑 |𝐼𝑜𝑝2 | < max(|𝐼𝑜𝑝1 |, |𝐼3 |) (3.6)
Again, if we consider 𝐼1 is leaving the zone while 𝐼2 and 𝐼3 are entering the zone, then
|𝐼𝑜𝑝1 | < max(|𝐼1 |, |𝐼2 |) 𝑎𝑛𝑑 |𝐼𝑜𝑝2 | < max(|𝐼𝑜𝑝1 |, |𝐼3 |) (3.7)
43
Similarly, it can be proved that at least one of the resultant partial operating currents
𝐼𝑜𝑝1 or 𝐼𝑜𝑝2 is smaller than the larger one of its two input currents for all possible combination
of current direction in normal operation. Although the development is based on three terminal
zone; the above statement is true for any number of input or output currents of a protection
zone.
Metric 2: Internal Fault: If there is any fault within the zone which is called internal fault
or in zone fault, currents through all terminals connected to the protection zone flow toward
zone [6], [21]. As shown in Figure 3.4, all currents are following toward zone to feed the fault
current which means currents measured by CTs are in same direction. According to the
definition, two or more currents are in same direction when the maximum phase difference
among them is less than 90 degree [13]. 𝐼𝑓 is the phasor of fault current and for internal fault
𝐼𝑜𝑝2 = 𝐼𝑓 .
Figure 3.5 shows the phasor diagram of the currents during internal fault. According to
the phasor diagram (Figure 3.5), magnitude of 𝐼𝑜𝑝1 is greater than magnitude of 𝐼1 as well as
44
magnitude of 𝐼2 and magnitude of 𝐼𝑜𝑝2 is greater than the magnitude of 𝐼𝑜𝑝1 as well as
|𝐼𝑜𝑝1 | > max(|𝐼1 |, |𝐼2 |) 𝑎𝑛𝑑 |𝐼𝑜𝑝2 | > max(|𝐼𝑜𝑝1 |, |𝐼3 |) (3.8)
Equation (3.8) states that all of the resultant partial operating currents are
simultaneously greater than the larger one of its two input currents for internal fault condition.
This statement is true for any differential protection zone irrespective of terminal numbers.
Metric 3: External Fault: During external fault, current flows out-bound from the
protection zone at least in one terminal [6], [21]. As shown in Figure 3.6, all currents except the
current of faulted terminal are flowing toward zone to feed the fault current. Direction of the
faulted terminal current is opposite to the other terminal currents. Normally 𝐼𝑜𝑝2 = 0 for
external fault condition, however, 𝐼𝑜𝑝2 can be high due to CT saturation. When a CT saturates,
the magnitude of the fundamental component of the secondary current decreases and its
45
phase angle advances [40]. Figure 3.7 and 3.8 show the phasor diagram of currents during
According to the phasor diagrams (Figure 3.7 and 3.8), magnitude of 𝐼𝑜𝑝1 is greater than
the magnitude of 𝐼1 as well as magnitude of 𝐼2 ; however, magnitude of 𝐼𝑜𝑝2 is less than the
(3.9).
|𝐼𝑜𝑝1| > max(|𝐼1 |, |𝐼2 |) 𝑎𝑛𝑑 |𝐼𝑜𝑝2 | < max(|𝐼𝑜𝑝1 |, |𝐼3 |) (3.9)
Figure 3.7: Phasor diagram during external fault condition without CT saturation
46
Although Figure 3.6 displays an external fault at terminal 3, faults could occur at any
terminal of a physical protection zone. If we consider an external fault at terminal 1 of the zone
shown in Figure 3.6, then the relation described in Equation (3.9) will change as Equation (3.10).
|𝐼𝑜𝑝1 | < max(|𝐼1 |, |𝐼2 |) 𝑎𝑛𝑑 |𝐼𝑜𝑝2 | < max(|𝐼𝑜𝑝1 |, |𝐼3 |) (3.10)
Figure 3.8: Phasor diagram during external fault condition with CT saturation
Similarly, for an external fault at terminal 2 of the zone shown in Figure 3.6, the relation
|𝐼𝑜𝑝1 | < max(|𝐼1 |, |𝐼2 |) 𝑎𝑛𝑑 |𝐼𝑜𝑝2 | < max(|𝐼𝑜𝑝1 |, |𝐼3 |) (3.11)
From Equation (3.9), (3.10), and (3.11), it is obvious that at least one of the resultant
partial operating current is smaller than the larger one of its two input currents for external
fault condition. This statement is also true for any protection zone irrespective of terminal
numbers.
47
3.3.2 Proposed Algorithm
The proposed fault discrimination algorithm is based on the characteristic metrics of the
newly defined partial operating current of a protection zone. Above [Explain above]
mathematical analysis shows that during internal fault, all of the resultant partial operating
currents are simultaneously greater than the larger one of its two input currents as described in
Equation (3.8). However, for normal operation and external fault condition statement of
Equation (3.8) is violated. More generally, for n terminal zones, Equation (3.8) can be re-written
as Equation (3.12).
condition” and could be applied to discriminate between external and internal faults of a
protection zone may not have active sources behind them or any line can be opened from far
end. Load current or small charging current may continue to flow on these passive elements or
opened line during fault. The current through the terminal less than a specific set value 𝐼0 is
considered as zero and excluded from partial operating current phasor calculation. The value of
𝐼0 must be higher than the charging current of longest line connected to the zone. Flowchart of
48
the proposed fault discrimination algorithm is presented in Figure 3.9. The proposed algorithm
is summarizes as follows:
phasor is greater than 𝐼0 , tag the terminal as ”qualified terminal” and pass to
current calculation.
zero, set output as ”no fault” and display. If the number of qualified terminal is
one, set output as ”internal fault” and display. If the number of qualified
output as ”internal fault” and display, otherwise set output as ”external fault”
and display.
49
3.4 Relay Design
scheme for bus differential protection which is capable of discriminating between internal and
external faults to overcome the impact of CT saturation. In the previous section, a fault
discrimination algorithm has been proposed based on the cumulative vector sum concept. In
this section, a bus differential relay model has been presented by incorporating the proposed
fault discrimination algorithm. The block diagram of the proposed relay is shown in Figure 3.10.
The output of the CTs is instantaneous analog signal. A data processor is used to convert these
analog signals to digital phasor form. Dual slope restrained characteristics is used to detect fault
which is already described in section 2.1.3. Along with internal and external fault discrimination
to ensure high sensitivity for internal through fault (high impedance fault) condition. Detail
working principle of data processor, CT saturation detection and trip logic unit will be presented
in following sub-sections.
50
3.4.1 Data Processor
As the CT secondary currents are analog signals, they are sampled in a particular
sampling rate to convert them into digital signals. In this model, the sampling frequency is 200
samples per cycle. From these digital signals, phasor values are extracted by using Discrete
Fourier Transform (DFT) technique with a one cycle window. The DFT of a signal x is defined
[41] by
𝑁−1
𝑁−1
1
𝑥(𝑡𝑛 ) ≜ ∑ 𝑋(𝜔𝑛 )𝑒 𝑗𝜔𝑛𝑡𝑛 , 𝑛 = 0, 1, 2, … , 𝑁 − 1 (3.6)
𝑁
𝑛=0
In this relay model, fast CT saturation detection algorithm and late CT saturation
detection algorithm are considered [34] [42]. The outputs of the two algorithms are combined
by OR logic to ensure the sensitivity of saturation detection logic for fast and late saturation
Fast CT saturation algorithm has been developed based on the phase relationship of the
second harmonic components of 𝑑𝐼𝑜𝑝 /𝑑𝑡 and 𝑑𝐼𝑟 /𝑑𝑡. The estimated phase difference (𝑂𝑑 )
between the second harmonic of 𝑑𝐼𝑜𝑝 /𝑑𝑡 and 𝑑𝐼𝑟 /𝑑𝑡 is compared with a threshold value(𝑂𝑐 ).
𝑂𝑑 > 𝑂𝑐 → 𝐶𝑇 𝑠𝑎𝑡𝑢𝑟𝑎𝑡𝑒𝑑
𝑂𝑑 ≤ 𝑂𝑐 → 𝐶𝑇 𝑛𝑜𝑡 𝑠𝑎𝑡𝑢𝑟𝑎𝑡𝑒𝑑
51
Figure 3.11: CT saturation detection algorithm
The fast CT saturation detection algorithm is only effective when the CT saturation occurs in the
first cycle after the fault inception. It cannot detect the late CT saturation. The late CT saturation is
detected by using the Block Zone defined in Figure 3.13 (shaded region). This zone is bounded by 𝐼𝑟 =
2 𝑥 𝐼𝑟𝑠 and a line with 20% of slope which is passed through origin. The value of 𝐼𝑟𝑠 should be set a little
bit greater than the maximum bus transfer load [34]. The fault level must be high enough to make the
trajectory get into this zone for external fault with late CT saturation.
52
Figure 3.13: Trajectory of operating and restrained current [34]
Trip logic unit is the final step of the relay modeling. It decides whether to trip or block
based on the outputs of fault detector unit (F), internal-external fault discriminator unit (IEF)
and CT saturation detection unit (SAT). The truth table for trip logic is shown on Table 3.1. The
53
The output of this logic is directly connected to the trip coils of all circuit breakers
connected with the protected zone. The logic diagram is shown in Figure 3.14.
This chapter has covered the mathematical modeling of a fault discrimination algorithm
which has been proposed in this thesis. It has also described the design details of a differential
bus protection relay including proposed fault discrimination algorithm. The next chapter will
describe a test system where the proposed relay will be applied to check its performances.
54
Chapter 4
This chapter presents a three test system that is used to test the performance of the bus
A three bus 230kV system is used to test the performance of the proposed bus
differential protection scheme. The system has three generators, two transmission lines and
three loads at three buses. The system is shown in Figure 4.1. The proposed relay is used at
bus-1, where two transmission lines, one generator and one load are connected.
Transmission lines play a critical role in the generation of transients. The resistance,
inductance and capacitance of overhead transmission lines are evenly distributed along the line
electromagnetic transient programs contain two major categories of transmission line models:
55
Constant parameter models
Constant-parameter distributed line model [43] is used in this test system. Detail data of
1 1 2 30 1.216 0.09222 50
2 1 3 75 1.216 0.09222 50
Table 4.1: Transmission line data [44]
Tower configuration of transmission lines are considered as same and described in Table
4.2.
A 0 100.00 73.00
B 0 83.50 56.50
C 0 67.00 40.00
Table 4.2: Transmission line tower configuration [44]
The following two generator models are the most commonly used in the protective
relaying studies:
56
In this study, all three generators are modeled as ideal sinusoidal voltage sources behind
Thevenin impedances. Detail data of the transmission lines are given in Table 4.3.
Load Connected Bus Rated Voltage (kV) Load (MW) Load (MVAR)
#
1 1 230 45 21
2 2 230 45 21
3 3 230 45 21
This chapter has covered a three bus test system including all system parameters such as
generator data, transmission line data, and load data. The next chapter will describe the EMTP
model of the test system, Matlab model of the proposed relay, simulation methodology, and
57
Chapter 5
Chapter 5 includes the simulation methodology and the results found by using the Test
System described in Chapter 4. The results found from proposed method are compared with
two existing methods, namely, Phase Angle Comparison Method, and Rate of Change of
Differential (ROCOD) Method. To perform simulation of the Test System, we need to build the
system using Electromagnetic Transient Program (EMTP) and simulating by use of Matlab
Program. Building the System Model and its simulation appear in Section 5.1 and 5.2.
To test the proposed method, the three bus test system is built in EMTP as shown in
Figure 5.1. Initially, power flow is solved to verify the validity of data. The power flow results
are compared with Power System Analysis Framework (PSAF) model and POWER WORLD
model. Differential bus protection works on phase wise differential zone which means all
elements of a zone must be in same phase. EMTP model is built as three split phases where
proposed relay is connected in phase A of bus 1. Four current transformers (CTs) are used in
four branches connected with bus 1 to measure currents of those branches. Instantaneous
ideal switches are used to create fault. For high impedance fault, 200Ω resistance is connected
Modeling of current transformer is very important for testing the performance of any
relaying system. Figure 5.2 shows the current transformer (CT) model that is used in this study
to include the effect of CT saturation {45}. This model comprises of an equivalent circuit built
58
around an ideal transformer. CT parameters Rp, Lp, Ls, and inter-winding capacitance are very
small which can be neglected [44]. In this study, inter-winding capacitance is neglected;
however, Rp, Lp, and Ls are taken into consideration. Rb represents combined CT secondary
winding resistance, lead resistance, and the CT burden. Values of CT parameters are given in
table 5.1.
59
Figure 5.2: EMTP current transformer (CT) model
results are identical in both cases. Location on the secondary is preferred because V-I curve
measurements are regularly performed from the CT secondary. The magnetizing branch Lm is
60
represented by a nonlinear inductor element whose Ψ-I characteristic is specified in piecewise
linear form Same Ψ-I characteristic is used for all four CTs as shown in Table 5.2.
Current Flux
0.0198 0.2851
0.0281 0.6040
0.0438 1.1141
0.0565 1.5343
0.0694 1.8607
0.1025 2.2771
0.2167 2.6522
0.7002 3.0234
1.0631 3.1098
15.903 3.2261
The proposed relay in chapter 3 is modeled using Matlab. The proposed relay has three
separate working blocks. Block 1 detects fault or abnormality in the system based on dual slope
percentage restrained characteristics which has been described in section 2.1.3. Performance
of this block depends on five setting values such as minimum pickup (𝐼𝑜𝑝0), slope 1 (𝑆1 ), slope 2
(𝑆2 ), first transition point (𝐼𝑟0 ) and second transition point (𝐼𝑟1 ) . Table 5.3 shows the settings
61
Block 2 is internal and external fault discriminator unit which has been described in
detail in Section 3.3. A set value (𝐼0 ) is used to check the magnitude of each phasor current. If
the magnitude of any phasor is less than 𝐼0 , it will be excluded from this algorithm. The value of
Block 3 is used to detect CT saturation. Detail of this block has been described in Section
3.4.2. This section has two sub-blocks. One of these sub-blocks is responsible for detecting fast
CT saturation which depends on a threshold value 𝑂𝑐 and the second sub-block is responsible
for detecting late CT saturation. The late CT saturation is detected by using the Block Zone
defined in Figure 3.12 (shaded region). This zone is bounded by 𝐼𝑟 = 2 𝑥 𝐼𝑟𝑠 and a line with 20%
of slope which is passed through origin. The value of 𝐼𝑟𝑠 is given in Table 5.3.
Another two relays are also modeled using Matlab based on exiting phase angle
comparison method and ROCOD method. Same percentage restrained characteristic is used for
three relays. The value of threshold current ( 𝐼0 ), threshold angle (𝜃0 ) for phase angle
Faults involved with power systems are mainly classified into two categories:
symmetrical or balanced fault and asymmetrical or unbalanced fault. A fault which affects each
of the three phases equally is called symmetrical fault. Symmetrical fault includes three phase
fault (LLL) and three phase to ground fault (LLLG). An asymmetrical fault does not affect each of
62
the three phases equally. Asymmetrical fault includes phase to ground fault (LG), phase to
As a power system element, busbar can be affected by any one of the three mentioned
faults. According to the location, faults can be classified as internal or in zone fault and external
or out of zone fault. Faults listed in table 5.4 are considered in this study.
63
5.4 Results and Discussion
All twelve faults mentioned in Table 5.4 are simulated in EMTP model and measured
currents were set as the input of Matlab relay models. Total simulation time is 250 milliseconds
(ms) and fault is incepted at 50 ms. Measured currents for each fault and corresponding
response of the proposed relay are presented graphically in this section. The comparative result
found from three methods (proposed method and existing phase angle comparison and ROCOD
CT secondary currents (phase A only) for four branches during LG internal fault are
shown in Figure 5.3. The branch currents (i1, i2, i4) during normal operation (0-50ms) are very
low in comparison to faulty condition (50-250ms). After fault inception at 50ms, the current
through the load (i3) became zero as there was no active source at the other end of the load.
However, currents through all other three branches were very high during fault due to having
active sources behind them. The corresponding responses from the various components of
proposed relay for LG internal fault are shown in Figure 5.4. The output of fault detector (F)
became high (fault detected) within 1.5ms after fault inception. Also the output of internal-
external fault detector (IEF) became high (internal fault detected) within 1.5ms after fault
inception. However, the output of CT saturation detector remained low (no saturation) as there
was no CT saturation during this LG internal fault. Finally, the trip output of the proposed relay
(TRIP) became high (trip command issued) within 1.5ms as expected. The comparative results
with other two existing methods are shown in Figure 5.5. The results show that the ROCOD
64
method as well as phase comparison method issued trip command at same time as the
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
20
i2 (A)
-20
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
65
TRIP: PROPOSED METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LL internal fault are
shown in Figure 5.6. The branch currents (i1, i2, i4) during normal operation (0-50ms) are very
low in compare to faulty condition (50-250ms). After fault inception at 50ms, the current
through the load (i3) became low; however, not became zero even there was no active source
at the other end of the load. This happened because there was no ground involvement during
the LL fault. The currents through all other three branches were very high during fault due to
having active sources behind them. The corresponding responses from the various components
of proposed relay for LL internal fault are shown in Figure 5.7. The output of fault detector (F)
became high (fault detected) within 1.5ms after fault inception; however, the output of
internal-external fault detector (IEF) remained low (no internal fault) as the current through the
load (i3) was flowing out from bus and its magnitude was greater than I0. The output of CT
saturation detector remained low (no saturation) as there was no CT saturation during this LL
66
internal fault. However, the trip output of the proposed relay (TRIP) became high (trip
command issued) within 1.5ms as expected. The comparative results with other two existing
methods are shown in Figure 5.8. The results show that the ROCOD method issued trip
command at same time as the proposed method for this LL internal fault; however, the phase
angle comparison method did not issue trip command which is unexpected.
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
50
i2 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
67
TRIP: PROPOSED METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LLG internal fault are
shown in Figure 5.9. The branch currents (i1, i2, i4) during normal operation (0-50ms) are very
low in compare to faulty condition (50-250ms). After fault inception at 50ms, the current
through the load (i3) became zero as there was no active source at the other end of the load.
However, currents through all other three branches were very high during fault due to having
active sources behind them. The corresponding responses from the various components of
proposed relay for LLG internal fault are shown in Figure 5.10. The output of fault detector (F)
became high (fault detected) within 1.5ms after fault inception. Also the output of internal-
external fault detector (IEF) became high (internal fault detected) within 1.5ms after fault
inception. However, the output of CT saturation detector remained low (no saturation) as there
was no CT saturation during the above mentioned fault. Finally, the trip output of the proposed
68
relay (TRIP) became high (trip command issued) within 1.5ms as expected. The comparative
results with other two existing methods are shown in Figure 5.11. The results show that the
ROCOD method as well as phase comparison method issued trip command at same time as the
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
50
i2 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
69
Figure 5.10: Responses from proposed method for LLG internal fault
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LLL internal fault are
shown in Figure 5.12. The branch currents (i1, i2, i4) during normal operation (0-50ms) are very
low in compare to faulty condition (50-250ms). After fault inception at 50ms, the current
through the load (i3) became zero as there was no active source at the other end of the load.
However, currents through all other three branches were very high during fault due to having
active sources behind them. The corresponding responses from the various components of
proposed relay for LLL internal fault are shown in Figure 5.13. The output of fault detector (F)
became high (fault detected) within 1.5ms after fault inception. Also the output of internal-
external fault detector (IEF) became high (internal fault) within 1.5ms after fault inception.
However, the output of CT saturation detector remained low (no saturation) as there was no CT
saturation during the above mentioned fault. Finally, the trip output of the proposed relay
70
(TRIP) became high (trip command issued) within 1.5ms as expected. The comparative results
with other two existing methods are shown in Figure 5.14. The results show that the ROCOD
method as well as the phase comparison method issued trip command at same time as the
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
20
i2 (A)
-20
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
71
Figure 5.13: Responses from proposed method for LLL internal fault
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LLLG internal fault are
shown in Figure 5.15. The branch currents (i1, i2, i4) during normal operation (0-50ms) are very
low in compare to faulty condition (50-250ms). After fault inception at 50ms, the current
through the load (i3) became zero as there was no active source at the other end of the load.
However, currents through all other three branches were very high during fault due to having
active sources behind them. The corresponding responses from the various components of
proposed relay for LLLG internal fault are shown in Figure 5.16. The output of fault detector (F)
became high (fault detected) within 1.5ms after fault inception. Also the output of internal-
external fault detector (IEF) became high (internal fault detected) within 1.5ms after fault
inception. However, the output of CT saturation detector remained low (no saturation) as there
was no CT saturation during the above mentioned fault. Finally, the trip output of the proposed
72
relay (TRIP) became high (trip command issued) within 1.5ms as expected. The comparative
results with other two existing methods are shown in Figure 5.17. The results show that the
ROCOD method as well as the phase comparison method issued trip command at same time as
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
20
i2 (A)
-20
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
73
Figure 5.16: Responses from proposed method for LLLG internal fault
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LG high impedance
internal fault are shown in Figure 5.18. The branch currents (i1, i2, i4) during normal operation
(0-50ms) are low in compare to faulty condition (50-250ms). After fault inception at 50ms, the
current through the load (i3) was same as the current during normal operation even there was
no active source at the other end of the load. This happened because the fault impedance was
high as 200 Ohms. The currents through all other three branches were high during fault due to
the active sources behind them. The corresponding responses from the various components of
proposed relay for LG high impedance internal fault are shown in Figure 5.19. The output of
fault detector (F) became high (fault detected) within 4ms after fault inception. However,
output of internal-external fault detector (IEF) remained low (no internal fault) as the current
through the load (i3) was flowing out from bus and its magnitude was greater than I0. The
74
output of CT saturation detector also remained low (no saturation) as there was no CT
saturation during the above mentioned fault. Even then the trip output of the proposed relay
(TRIP) became high (trip command issued) within 4ms as expected. The comparative results
with other two existing methods are shown in Figure 5.20. The results show that the ROCOD
method issued trip command at same time as the proposed method for this LG high impedance
internal fault; however, the phase angle comparison method did not issue trip command which
is unexpected.
2
i1 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
1
i2 (A)
-1
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
5
i4 (A)
0
-5
0 0.05 0.1 0.15 0.2 0.25
Time (s)
75
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
Figure 5.19: Responses from proposed method for LG high impedance internal fault
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LL high impedance
internal fault are shown in Figure 5.21. The branch currents (i1, i2, i4) during normal operation
(0-50ms) are low in compare to faulty condition (50-250ms). After fault inception at 50ms, the
current through the load (i3) was same as the current during normal operation even there was
76
no active source at the other end of the load. This happened because the fault impedance was
high as 200 Ohms. The currents through all other three branches were high during fault due to
the active sources behind them. The corresponding responses from the various components of
proposed relay for LL high impedance internal fault are shown in Figure 5.22. The output of
fault detector (F) became high (fault detected) within 2ms after fault inception. However,
output of internal-external fault detector (IEF) remained low (no internal fault) as the current
through the load (i3) was flowing out from bus and its magnitude was greater than I0. The
output of CT saturation detector also remained low (no saturation) as there was no CT
saturation during the above mentioned fault. Even then the trip output of the relay (TRIP)
became high (trip command issued) within 2ms as expected. The comparative results with
other two existing methods are shown in Figure 5.23. The results show that the ROCOD method
issued trip command at same time as the proposed method for this LL high impedance internal
fault; however, the phase angle comparison method did not issue trip command which is
unexpected.
5
i1 (A)
-5
0 0.05 0.1 0.15 0.2 0.25
2
i2 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
10
i4 (A)
0
-10
0 0.05 0.1 0.15 0.2 0.25
Time (s)
77
Figure 5.21: CT secondary currents for LL high impedance internal fault
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
Figure 5.22: Responses from proposed method for LL high impedance internal fault
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
78
Phase to ground (LG) external fault:
CT secondary currents (phase A only) for four branches during LG external fault are
shown in Figure 5.24 where i2 is distorted as the CT connected to that branch was saturated.
The branch currents (i1, i2, i4) during normal operation (0-50ms) are low in compare to faulty
condition (50-250ms). After fault inception at 50ms, the current through the load (i3) became
close to zero as there was no active source at the other end of the load. The currents through
all other three branches were high during fault due to the active sources behind them. The
corresponding responses from the various components of proposed relay for LG external fault
are shown in Figure 5.25. The output of fault detector (F) became high (fault detected) within
6.5ms after fault inception even through the fault was incepted at out of zone (external fault).
This was happened due to the resultant differential current from distorted i 2 because of CT
saturation. However, output of internal-external fault detector (IEF) remained low (external
fault) as i2 was flowing out from bus. The output of CT saturation detector became high
(saturated) as the CT connected to the branch 2 got saturated. Therefore, the trip output of the
relay (TRIP) remained low (no trip command issued) as expected. The comparative results with
other two existing methods are shown in Figure 5.26. The results show that the ROCOD method
unexpectedly issued trip command after 6.5ms of fault inception for this LG external fault;
however, the phase angle comparison method did not issued trip command which is
79
50
i1 (A) 0
-50
0 0.05 0.1 0.15 0.2 0.25
100
i2 (A)
-100
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
80
TRIP: PROPOSED METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LL external fault are
shown in Figure 5.27 where i2 is distorted as the CT connected to that branch was saturated.
The branch currents (i1, i2, i4) during normal operation (0-50ms) are low in compare to faulty
condition (50-250ms). After fault inception at 50ms, a small current through the load (i 3) was
continuing to flow due to phase-to-phase (LL) fault. The currents through all other three
branches were high during fault due to the active sources behind them. The corresponding
responses from the various components of proposed relay for LL external fault are shown in
Figure 5.28. The output of fault detector (F) became high (fault detected) within 12ms after
fault inception even through the fault was incepted at out of zone (external fault). This was
happened due to the resultant differential current from distorted i 2 because of CT saturation.
However, output of internal-external fault detector (IEF) remained low (external fault) as i2 and
i3 were flowing out from bus. The output of CT saturation detector became high (saturated) as
81
the CT connected to the branch 2 got saturated. Therefore, the trip output of the relay (TRIP)
remained low (no trip command issued) as expected. The comparative results with other two
existing methods are shown in Figure 5.29. The results show that the ROCOD method
unexpectedly issued trip command after 12ms of fault inception for this LL external fault;
however, the phase angle comparison method did not issued trip command which is
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
200
i2 (A)
-200
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
82
TRIP: PROPOSED METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LLG external fault are
shown in Figure 5.30 where i2 is distorted as the CT connected to that branch was saturated.
The branch currents (i1, i2, i4) during normal operation (0-50ms) are low in compare to faulty
condition (50-250ms). After fault inception at 50ms, the current through the load (i 3) became
close to zero as there was no active source at the other end of the load. The currents through
all other three branches were high during fault due to the active sources behind them. The
corresponding responses from the various components of proposed relay for LLG external fault
are shown in Figure 5.31. The output of fault detector (F) became high (fault detected) within
5.5ms after fault inception even through the fault was incepted at out of zone (external fault).
This was happened due to the resultant differential current from distorted i 2 because of CT
saturation. However, output of internal-external fault detector (IEF) remained low (external
fault) as i2 was flowing out from bus. The output of CT saturation detector became high
(saturated) as the CT connected to the branch 2 got saturated. Therefore, the trip output of the
83
relay (TRIP) remained low (no trip command issued) as expected. The comparative results with
other two existing methods are shown in Figure 5.32. The results show that the ROCOD method
unexpectedly issued trip command after 5.5ms of fault inception for this LLG external fault;
however, the phase angle comparison method did not issued trip command which is
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
100
i2 (A)
-100
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
Figure 5.31: Responses from proposed method for LLG external fault
84
TRIP: PROPOSED METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LLL external fault are
shown in Figure 5.33 where i2 is distorted as the CT connected to that branch was saturated.
The branch currents (i1, i2, i4) during normal operation (0-50ms) are low in compare to faulty
condition (50-250ms). After fault inception at 50ms, the current through the load (i 3) became
close to zero as there was no active source at the other end of the load. The currents through
all other three branches were high during fault due to the active sources behind them. The
corresponding responses from the various components of proposed relay for LLL external fault
are shown in Figure 5.34. The output of fault detector (F) became high (fault detected) within
6ms after fault inception even through the fault was incepted at out of zone (external fault).
This was happened due to the resultant differential current from distorted i 2 because of CT
saturation. However, output of internal-external fault detector (IEF) remained low (external
fault) as i2 was flowing out from bus. The output of CT saturation detector became high
(saturated) as the CT connected to the branch 2 got saturated. Therefore, the trip output of the
85
relay (TRIP) remained low (no trip command issued) as expected. The comparative results with
other two existing methods are shown in Figure 5.35. The results show that the ROCOD method
unexpectedly issued trip command after 6ms of fault inception for this LLL external fault;
however, the phase angle comparison method did not issued trip command which is
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
100
i2 (A)
-100
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
Figure 5.34: Responses from proposed method for LLL external fault
86
TRIP: PROPOSED METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
CT secondary currents (phase A only) for four branches during LLLG external fault are
shown in Figure 5.36 where i2 is distorted as the CT connected to that branch was saturated.
The branch currents (i1, i2, i4) during normal operation (0-50ms) are low in compare to faulty
condition (50-250ms). After fault inception at 50ms, the current through the load (i 3) became
close to zero as there was no active source at the other end of the load. The currents through
all other three branches were high during fault due to the active sources behind them. The
corresponding responses from the various components of proposed relay for LLLG external
fault are shown in Figure 5.37. The output of fault detector (F) became high (fault detected)
within 5.5ms after fault inception even through the fault was incepted at out of zone (external
fault). This was happened due to the resultant differential current from distorted i2 because of
CT saturation. However, output of internal-external fault detector (IEF) remained low (external
fault) as i2 was flowing out from bus. The output of CT saturation detector became high
(saturated) as the CT connected to the branch 2 got saturated. Therefore, the trip output of the
87
relay (TRIP) remained low (no trip command issued) as expected. The comparative results with
other two existing methods are shown in Figure 5.38. The results show that the ROCOD method
unexpectedly issued trip command after 5.5ms of fault inception for this LLLG external fault;
however, the phase angle comparison method did not issued trip command which is
50
i1 (A)
-50
0 0.05 0.1 0.15 0.2 0.25
100
i2 (A)
-100
0 0.05 0.1 0.15 0.2 0.25
2
i3 (A)
-2
0 0.05 0.1 0.15 0.2 0.25
100
i4 (A)
0
-100
0 0.05 0.1 0.15 0.2 0.25
Time (s)
5
F
0
0 0.05 0.1 0.15 0.2 0.25
5
IEF
0
0 0.05 0.1 0.15 0.2 0.25
5
SAT
0
0 0.05 0.1 0.15 0.2 0.25
5
Trip
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
Figure 5.37: Responses from proposed method for LLLG external fault
88
TRIP: PROPOSED METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: ROCOD METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
TRIP: PHASE COMPARISON METHOD
10
0
0 0.05 0.1 0.15 0.2 0.25
Time (s)
This chapter has covered the detail simulation methodology and discussions on found
results. The results found from proposed method are also compared with two existing
methods, namely, Phase Angle Comparison Method, and Rate of Change of Differential
(ROCOD) Method. The next chapter will describe the conclusion remarks of this thesis and
89
Chapter 6
Matlab based on proposed algorithm which also includes percentage restrained characteristics
to detect faulty conditions. To ensure high sensitivity for through internal fault (high
algorithm. The performance of proposed algorithm and relay are validated by a three bus test
system. Proposed relay is applied in a bus which is connected with all possible elements of
power system such as transmission line, generator (active source) and load (inactive source).
The test system is built in EMTP. All possible bus fault scenarios are simulated in EMTP model
and measured currents are set as the input of Matlab relay model to find the responses of
proposed relay. Finally, results are compared with two latest existing methods, namely, delta
From the experimental results, it is found that proposed method has given correct
responses for all faults scenarios including fast CT saturation, late CT saturation as well high
impedance fault. The proposed relay gets trip for all types of internal faults irrespective of fault
impedances and restraints trip during external faults even with CT saturation. It is also found
that phase angle comparison method has given correct results for all external faults; however,
90
it fails to trip for phase to phase internal fault and all high impedance internal ground faults.
The rate of change of differential method responds correctly only for internal faults but it is
unable to restraint trip for external fault during CT saturation. Comparative summary of the
91
Moreover, the proposed relay has satisfied all four functional requirements of power
system protection schemes. Reliability is the most important requisite of power system
protection. The proposed relay remained inoperative for normal operation before a fault
occurs; but if a fault occurs, it responded quickly. Selectivity is another important requisite of
power system protection schemes. Relays should be operated in only those fault conditions for
which schemes are commissioned in the system. From the experimental results, we have seen
that the proposed relay operated only for internal faults and remained inoperative during all
external faults irrespective of CT saturation. The proposed relay is also sufficiently sensitive to
operate reliably when level of fault condition just crosses the predefined set limit. Another
important requisite of protection systems is the speed of operation. The results have shown
that the proposed relay operated within sub-cycle time ranges after fault inception.
From the listed experimental results and above performance analysis, it is clear that the
proposed relay including fault discrimination algorithm based on partial operating current
characteristics is performing superiorly. Although, this thesis has only covered the applicability
of the proposed fault discrimination algorithm in bus differential protection, it could be the
promising options for line differential as well as transformer differential protections. A detail
92
Bibliography
[1] Hewitso L.G., Brown Mark and Balakrishna Ramesh, “Practical Power System Protection”,
Elsevier Ltd., 2005.
[2] The Electricity Training Association, “Power System Protection, Volumes 1-4”, Institution of
Engineering and Technology, 1995.
[3] Mason C. Russell, “Art and Science of Protective Relaying”, John Wiley & Sons, New York,
1956.
[4] B. Chattopadhyay, M. S. Sachdev, and T. S. Sidhu, "An on-line relay coordination algorithm
for adaptive protection using linear programming technique", IEEE Trans. Power Delivery, vol.
11, pp.165 -171, 1996.
[5] So C. W. and Li K.K., “Time Coordination Method for Power System Protection by
Evolutionary Algorithm”, Industry Application, IEEE, Vol. 36, pp. 1235-1240, August 2002.
[6] Kaufman M. and Szwander W. “Busbar Protection: A Critical Review of Methods and
Practice”, The journal of the institution of electrical engineers, vol. 90, no. 17, Oct. 1943.
[7] Mohan Sundar M., Chatterjee S., “Busbar Protection – A Review”, IEEE Region 8 SIBIRCON-
2010, July 11 — 15, 2010.
[8] Brewis K., Hearfield K., Chapman K., “Theory and Practical Performance of Interlocked Over-
current Busbar Zone Protection in Distribution Substations”, Developments in Power System
Protection, Conference Publication No.479, IEE 2001.
[9] Martin C., Chase S., Nguyen T., Hawaz D. J., Pope J. and Labuschagne C., “Bus Protection
Considerations for Various Bus Types”, 40th Annual Western Protective Relay Conference, Oct.
2013.
[10] J. G. Adrichak and J. Cardenas, “Bus differential protection”, 22nd WPRC Conference,
Spokane, pp. 1-11, Oct 1995.
[11] Ken Behrendt, David Costello, and Stanley E. Zocholl, “Considerations for Using High-
Impedance or Low-Impedance Relays for Bus Differential Protection”, 35th Annual Western
Protective Relay Conference, IEEE, Oct 2008.
93
[12] Holbach, J., “Comparison between high impedance and low impedance bus differential
protection”, Power Systems Conference, IEEE, pp, 1-16, 2009.
[13] Krish Narendra, Dave Fedirchuk, “Secured Busbar Differential Protection Using A
Computationally Efficient Dot Product Technique”, Power System Protection and Automation
Conference, Dec. 2010.
[14] Michael J. Thompson: “Percentage Restrained Differential, Percentage of What?”,
IEEE Conference, 2011.
[15] Kennedy L.F., and Hayward C.D., “Harmonic-current-restrained relays for differential
protection”, AIEE Trans., vol. 57, pp. 262–266, 1938.
[16] Phadke A.G., and Thorp J.S., “Computer relaying for power systems”, (Research Studies
Press LTD., Baldock, UK, 1988), pp. 185–186.
[17] Royle J.B., and Hill A. “Low impedance biased differential busbar protection for application
to busbars of widely differing configuration” IEE 4th Int. Conf. on Developments in Power
System Protection, Edinburgh, UK, pp. 40–43, April 1989
[18] Andow F., Suga N., Murakamy Y., and Inamura K., “Microprocessor-based busbar
protection relay”, IEE 5th Int. Conf. on Developments in Power System Protection, York, UK, pp.
103–106, March 1993
[19] Fernandez, C., “An Impedance-based CT saturation detection algorithm for bus-bar
differential protection”, IEEE Trans. Power Deliv., vol. 16, (4), pp. 468–472, 2001.
[20] Gill H.S., Sidhu T.S., and Sachdev M.S., “Microprocessor-based busbar protection system”,
IEE Proc., Gener. Transm. Distrib., 147, (4), pp. 252–260, 2002.
[21] Horowitz S.H, and Phadke A.G., “Power system relaying” (Research Studies Press LTD.,
Baldock, UK), p. 226, 1992.
[22] Yong-Cheol Kang, Ui-Jai Lim, Sang-Hee Kang and Peter A. Crossley, “A Busbar Differential
Protection Relay Suitable for Use with Measurement Type Current Transformers”, IEEE
Transaction on Power Delivery, vol. 20, no. 2, April, 2005.
[23] Shaik Abul Gafoor, N. Rama Devi, and P. V. Ramana Rao, “A Transient Current Based Bus
Zone Protection Scheme Using Wavelet Transform”, ICSET, 2008.
94
[24] K. Narendra, D. Fedirchuk, N. Zhang, R. Midence, N. Perera, and V. Sood, “Phase Angle
Comparison and Differential Rate of Change Methods used for Differential Protection of
Busbars and Transformers”, Electrical Power and Energy Conference, IEEE, 2011.
[25] K. Narendra, D. Fedirchuk and N. Zhang, “Differential rate of change method for busbar
protection”, US Patent. Pending (Submitted-2010).
[26] R. Abd Allah, “Busbar Protection Scheme Based on Alienation Coefficients for Current
Signals”, IJEAT, Volume-3, Issue-4, April 2014.
[27] Transient Response of Current Transformers, The Institute of Electrical & Electronic
Engineers, Inc., New York, N. Y., 76 CH 1130-4 PWR, January 1976.
[28] Ionuţ Ciprian BORĂSCU, “The CT Behavior and Its Compatibility with Relay Protection”,
U.P.B. Sci. Bull., Series C, Vol. 76, 2014.
[29] A. Writght and C. Christopoulos, “Electrical Power System Protection” Chapman and Hall,
1993.
[30] Y. C. Kang, J. K. Park, S. H. Kang, A. T. Johns, and R. K. Aggarwal, “An algorithm for
compensating the secondary current of current trans-formers,” IEEE Trans. Power Delivery, vol.
12, pp. 116–124, Jan. 1997.
[31] T. Bunyagul, P. Crossley, and P. Gale, “Overcurrent protection using signals derived from
saturated measurement CTs”, in Proc. IEEE Power Eng. Soc. Summer Meeting, Vancouver, BC,
Canada, July 15–19, 2001.
[32] Y. C. Kang, S. H. Ok, and S. H. Kang, “A CT saturation detection algorithm,” IEEE Trans.
Power Delivery, vol. 19, no. 1, pp. 78–85, Jan. 2004
[33] Nicholas Villamagna and Peter A. Crossley, “A CT Saturation Detection Algorithm Using
Symmetrical Components for Current Differential Protection”, IEEE Transaction on Power
Delivery, vol. 21, no. 1, Jan. 2006.
[34] Zhiying Zhang, Krish Narendra, Dave Fedirchuk, George Punnoose, Premnath, “ A Novel CT
Saturation Detection Algorithm for Bus Differential Protection”.
[35] Paul Clayton R., “Fundamentals of Electric Circuit Analysis”, John Wiley & Sons, 2001.
[36] Q.H. Wu, Zhen Lu, Tianyao Ji , “ Protective Relaying of Power Systems Using Mathematical
Morphology”, Springer, 2009
95
[37] Tziouvaras, D.A., et al, Mathematical Models for Current, Voltage, and Coupling Capacitor
Voltage Transformers, Working Group C5 of PSRC, IEEE Trans. on Power Delivery, pp. 62-72, Jan
2000.
[38] Fawwaz T. Ulaby, “Fundamentals of Applied Electromagnetics”, 5 th edition, Prentice Hall,
2007.
[39] K. Narendra,A. Dasgupta, K. Ponram, N. Perera, R. Midence, A. Oliveira, “Micro Processor
Based Advanced Bus Protection Scheme Using IEC 61850 Process Bus (9-2) Sampled Values”.
[40] Bogdan Kasztenny, Gabriel Benmouyal, Hector J. Altuve, and Normann Fischer, Tutorial on
Operating Characteristics of Microprocessor-Based Multiterminal Line Current Differential
Relays, 38th Annual Western Protective Relay Conference, October, 2011.
[41] J.O. Smith, “Mathematics of the Discrete Fourier Transform (DFT)”, CCRMA, Stanford, July
2002.
[42] Dave FedirChuk et. al, “Electrical Bus Protection Method and Apparatus”, US Patent -
7,199,991 B2, Issued April 2007.
[43] Feng Gao, and K. Strunz, Modeling of Constant Distributed Parameter Transmission Tine for
Simulation of Natural and Envelope Waveforms in Power Electric Networks, Proceedings of the
37th Annual North American Power Symposium, 2005.
[44] EMTP reference models for transmission line relay testing, 2005.
[45] M. Kezunovic , Lj. Kojovic , A. Abur , C.W. Fromen , D.R. Sevcik , F. Phillips . Experimental
Evaluation of EMTP-Based Current Transformer Models for Protective Relay Transient Study.
IEEE Trans. Power Deliv., vol. 9, no. 1, January, 1994, pp 405 - 413.
[46] AC Transmission Line Model Parameter Validation, A report to the Line Protection
Subcommittee of the Power System Relay Committee of the IEEE Power and Energy Society,
Prepared by working group D6, Sept 2014.
96
Vita
Monir Hossain is a PhD student of Electrical Engineering at University of New Orleans (UNO),
LA, USA. He received his Bachelor Degree in Electrical Engineering from Bangladesh University
of Engineering & Technology (BUET). He has more than five years of experience in power
transmission engineering including SCADA system, protection system, and transmission system
planning. He was involved in transmission network extension plan development (2015-2030)
for Bangladesh, low-cost grid substation standard development for rural areas of Bangladesh
with NRECA, USA, and the development of the run-back scheme for first back to back HVDC
interconnection between Bangladesh and India. He participated in more than fifteen training
programs and workshops on power system engineering in all over the world. Currently, he is
working as a research assistant at UNO-Entergy research project on power system protection.
His research interest includes power system protection & relays, energy management, and
power system dynamics & oscillations.
97