EST Catalog u Intelligent Initiating

Intelligent
Break Glass
Call Point
SIGI-271

Overview Standard Features


SIGI-271 Fire Alarm Call Points are part of Edwards’s Signature • Intelligent Device with Integral Microprocessor
Series system. These integrated assemblies feature the familiar All decisions are made at the Call Point to allow lower commu-
KAC Installers’ Series Call Point packaged with Signature Series nication speed. Lower communication speeds are less sensitive
intelligent addressable/analogue interface electronics. to line noise; twisted or shielded wire is not required.
In all 271 Series Call Points, the switch is held off by the edge of • Automatic Device Mapping
the glass. When the glass is broken by pressing directly on it, the Each Call Point transmits wiring information regarding its loca-
switch is released and an alarm sent to the Signature loop con- tion with respect to other Signature devices on the circuit.
troller. A protective plastic coating on the glass prevents operator • Electronic Addressing
injury and inhibits the release of glass fragments. Addresses are downloaded from a PC, or the SIGA-PRO
Each Signature Series Call Point constantly runs self-checks to Signature Program/Service Tool. There are no switches or dials
provide important maintenance information. The results of the to set.
self-check are automatically updated and permanently stored in • Non-volatile Memory
the Call Point’s non-volatile memory. This information is accessible Permanently stores serial number, type of device, and job num-
for review any time at the control panel, PC, or by using the SIGA- ber. Automatically updated with historic information.
PRO Signature Program/Service Tool.
• Stand-alone Operation
The information stored in the Call Point’s memory includes: Call Point can input an alarm even if the loop controller’s polling
• Call Point serial number, address, type code. interrogation stops.
• Manufacture date, hours of operation, last maintenance date. • Alarm LED
• Number of recorded troubles, alarms, time and date of last Red led flashes to show “alarm” state.
alarm. • Designed For High Ambient Temperature Operation
• Up to 24 possible trouble codes that may be used to specifically Install in ambient temperatures up to 120 °F (49 °C).
diagnose faults.
• Flush or Surface Mount
The Signature loop controller learns where each device’s serial • Optional Markings Available
number address is installed relative to other Signature devices Glass inserts with multiple languages are available.
on the circuit. The loop controller keeps a “map” of the Signature
Series devices connected to it. • Designed To ISO 9001 Standard
Manufactured to strict international quality standards.

Page 1 of 4 D ATA S H E E T 85001-0349


Not to be used for installation purposes. Issue 2
Application
The operating characteristics of the fire alarm Call Point is deter-
mined by its sub-type code or “Personality Code”. NORMALLY
Installation and Mounting
OPEN ALARM - LATCHING (Personality Code 1) is assigned The Signature Series fire alarm Call Points flush
by the factory; no user configuration is required. The device is mount to standard European General Purpose
configured for Class B IDC operation. An ALARM signal is sent to Outlet Boxes using the KAC ETT/1-P European
the loop controller when the switch is closed (i.e. when the glass is Terminal Tray. Surface mounting requires the
broken). The alarm condition is latched at the station. KAC SR3T-P Surface Mounting Box. Edwards
recommends that Call Points be installed
according to latest recognized edition
of national and local fire alarm codes.
Compatibility
Signature Series Call Points are compatible only with Signature
Loop Controller. Electronic Addressing - The Signature
loop controller electronically address-
es each Call Point, saving valuable
time during system commissioning.
Testing & Maintenance Setting complicated switches or dials
To test the Call Point simply insert the special test key (provided is not required. Each Call Point has its own unique serial number
with every unit); the glass drops and the switch closes. Removing stored in its “on-board memory”. The loop controller identifies
the key restores the Call Point to normal. each device on the loop and assigns a “soft” address to each se-
rial number. If desired, the Call Points can be addressed using the
The Call Point’s automatic self-diagnosis identifies when it is defec-
SIGA-PRO Signature Program/Service Tool.
tive and causes a trouble message. The user-friendly maintenance
program shows the current state of each Signature Series device
and other pertinent messages. Single devices may be deactivated
temporarily, from the control panel. Availability of some mainte- Warnings & Cautions
nance features is dependent on the fire alarm system used. This device will not operate without electrical power. As fires fre-
Scheduled maintenance (Regular or Selected) for proper system quently cause power interruption, we suggest you discuss further
operation should be planned to meet the requirements of the safeguards with your fire protection specialist.
Authority Having Jurisdiction (AHJ).

Dimensions
Testing & Maintenance 89 mm (3.5 in)
27.5 mm 32 mm
(1.1 in) (1.3 in)

To test the Call Point simply insert


the special test key (provided
with every unit); the glass drops
93 mm (3.7 in)

and the switch closes. Removing


the key restores the Call Point to
normal.
The Call Point’s automatic self-
diagnosis identifies when it is
defective and causes a trouble
message. The user-friendly
maintenance program shows the
current state of each Signature Series device and other pertinent
messages. Single devices may be deactivated temporarily, from
the control panel. Availability of some maintenance features is
dependent on the fire alarm system used.
Scheduled maintenance (Regular or Selected) for proper system
operation should be planned to meet the requirements of the
Authority Having Jurisdiction (AHJ).

Page 2 of 4 D ATA S H E E T 85001-0349


Not to be used for installation purposes. Issue 2
Typical Wiring Specifications
Connecting to the Call Point is made easy, and virtually ‘Plug-in’. Addressing
Uses 1 module address
The Call Point is supplied with flying leads and grip forks that con- Requirements
nect to large terminals in the ETT/1 or SR3T mounting accessory. Standby = 250 µA
Operating Current
Installer cables are accommodated in robust ‘clamp type’ termi- Activated = 400 µA
nals that will each take two conductors in the manner required by Type Code Factory Set
BS5839: Part 2. See Signature Loop Controller catalogue sheet Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)
for detailed wiring requirement specifications. Operating Temp. 32 °F to 120 °F (0 °C to 49 °C)
Storage Temp. -4 °F to 140 °F (-20 °C to 60 °C)
Humidity 0 to 93% RH
REAR VIEW
Installation Instructions On-board RED led: Flashes when in alarm;
of CONNECT ONLY IN ACCORDANCE
SIGI-271 LED Operation Glows steady when in alarm-stand-alone
WITH ENCLOSED DATA mode
Compatibility Use with Signature Loop Controller
Call Point Material Thermoplastic (red)
Mounting Hole Agency Listings CE Compliant
(1 Each Side)

RED
DATA IN/OUT (+)
BLACK B/W
DATA IN (-) DATA OUT (-)
From Signature Controller
or Previous Device
1

B/W
Black Wire Wire Red Wire

Data In (+) Data Out (+)


Data In (-) Data Out (-)

KAC ETT1-P Tray Wiring

Data In (+) Data Out (+)


Data In (-) Data Out (-)

Black Red
Wire Wire

B/W
Wire

KAC SR3T-P Box Wiring

Page 3 of 4 D ATA S H E E T 85001-0349


Not to be used for installation purposes. Issue 2
Ordering Information
Model Description Carton Ship
Wt.
SIGI-271 Intelligent Call Point - English Markings 89 x 90 x 35mm 150g
Contact us...
Accessories
Email: edwards.fire@fs.utc.com
Web: www.est-fire.com SR3T-P Surface Mount Box - Red 89 x 90 x 35mm 50g
ETT/1-P European Terminal Tray (for flush mounting) 89 x 90 x 35mm 47g
EST is an EDWARDS brand.
271-KG1 Replacement Glass Pack (5 inserts) - English only 82 x 48 x 14mm 70g
1016 Corporate Park Drive
271-KG1-F005 Replacement Glass Pack (5 inserts) - Spanish only 82 x 48 x 14mm 70g
Mebane, NC 27302
271-KG1-F1 Replacement Glass Pack (5 inserts) - Polish/English 82 x 48 x 14mm 70g
In Canada, contact Chubb Edwards... 271-KG1-F2 Replacement Glass Pack (5 inserts) - Russian only 82 x 48 x 14mm 70g
Email: inquiries@chubbedwards.com
Web: www.chubbedwards.com 271-KG1-F200 Replacement Glass Pack (5 inserts) - Hungarian/ 82 x 48 x 14mm 70g
English
© 2013 UTC Fire & Security Americas 271-KG1-F3 Replacement Glass Pack (5 inserts) - Arabic/English 82 x 48 x 14mm 70g
Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.

06-27-13

Page 4 of 4 D ATA S H E E T 85001-0349


Not to be used for installation purposes. Issue 2