ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD
Copyright © 2012 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
Release Note:
ENHANCED TECHNOLOGY i
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
Table of Contents
A. Introduction ................................................................................................................... 1
ii ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
A. INTRODUCTION
Through the operation program, the user can remap the data map used in the protocol
communication of DNP 3.0, IEC60870-5-101/104, MODBUS and IEC61850. The “Base Map List”
on the left side of the diagram provides the list of all available data points and the ones that are
currently in use are shaded in grey. The “User Map List” on the right is the Data Map that applies
to Entec‟s Recloser Control (ETR300-R or EVRC2A-NT) choose the data point to add from the
“Base Map List” then drag it to the “User Map List” with the mouse and the data point is added.
Conversely, drag the data point from the “User Map List” to the “Base Map List” to delete from the
Data Map.
The remapped Data Map can be saved to file and managed or transmitted to Entec‟s Recloser
Control on-line.
Remapped Data Map must be transmitted through the operation program “UPLOAD >> DB
MAP CONFIG” menu to be applied to Entec‟s Recloser Control (For more details, refer to
“Interface Softwer User Manual”).
ENHANCED TECHNOLOGY 1
ETR300-R Communication Protocol MAP Configuration http://www.entecene.co.kr
1. Binary Input
Click the “Binary Single Input” or “Binary Double Input” Tap at the bottom of the “DB MAP
CONFIGURATION” window to move the Binary Input Map. The properties of Inver, Class, Var,
IEC Mask A and more can individually be set in the “User Map List” per each data point. The
property can be changed by clicking the corresponding property column (indicate the combo box)
when the data point to be changed is selected (indicate with a blue line).
The property setting items are as follows.
2 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
The Class & Var setting values are useful properties in the DNP3.0 communication and the
IEC Mask A/B and Index 60870 setting values are a useful property in the IEC60870
communication. The SMS setting value is a useful property in the SMS message transmitting
function.
As optional functions, the DNP3.0 communication, IEC60870 communication & SMS
message transmitting function will not cause any influence if the Entec‟s Recloser Control
does not support these functions.
The Binary Input‟s base data points are as follows. However, supported points may be different
according to the version and option of Control.
ENHANCED TECHNOLOGY 3
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 4
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 5
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 6
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 7
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 8
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 9
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 10
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 11
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
101 Loop Control Disabled NO 1 02/02 Group Group 2 Loop control function enabled Loop control function disabled
Auto restoration function disabled Auto restoration function of SEC, MID
enabled
Loop Control Auto Restore
102 NO 1 02/02 Group Group 2 This point can be set ('1') only when Loop
Enabled
control type setting is SEC, MID and the
above "Loop Control Auto Restore Enabled"
Auto restoration function of SEC, MID Auto restoration function disabled
Loop Control Auto Restore
103 NO 1 02/02 Group Group 2 enabled
Disabled
104 Hot-Line Tag Enabled NO 1 02/02 Group Group 2 Hot-Line Tag function disabled Hot-Line Tag function enabled
105 Hot-Line Tag Disabled NO 1 02/02 Group Group 2 Hot-Line Tag function enabled Hot-Line Tag function disabled
106 Aux1 Enabled NO 1 02/02 Group Group 2 Aux1 disabled Aux1 enabled
107 Aux1 Disabled NO 1 02/02 Group Group 2 Aux1 enabled Aux1 disabled
108 Aux 2 Enabled NO 1 02/02 Group Group 2 Aux 2 disabled Aux 2 enabled
109 Aux 2 Disabled NO 1 02/02 Group Group 2 Aux 2 enabled Aux 2 disabled
Primary Setting active Alternate Setting active
However, when the Loop control This point applies only when the Loop
110 Alternate Set Group Enabled NO 1 02/02 Group Group 2
function setting is disabled, this point is control function is enabled.
always cleared ('0').
ENHANCED TECHNOLOGY 12
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 13
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 14
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 15
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 16
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 17
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 18
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 19
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 20
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 21
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 22
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 23
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 24
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 25
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 26
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 27
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 28
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 29
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 30
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 31
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
fluctuation and its categories are as shown in “Ficture 2. IEEE 1159 Sag Under voltage
Voltage distortion summary”.
0.1 pu
Interruption
30cycle 3sec
0.5cycle 1min
ENHANCED TECHNOLOGY 32
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 33
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 34
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 35
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 36
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 37
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 38
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
*. NOTE ) Supported points may be different according to the option and version of controller.
ENHANCED TECHNOLOGY 39
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
2. Binary Output
Click “Binary Single Output” or “Binary Double Output” Tap in the bottom of the “DB MAP
CONFIGURATION” window to move to Binary Output Map. The properties of Invert, Control
Type and Index 60870 can be individually set in the “User Map List” per each data point. The
property can be changed by clicking the corresponding property column (indicate the combo box)
when the data point to be changed is selected (indicate with a blue line).
The property setting items are as follows.
The Control Type setting value is useful properties in the DNP3.0 communication and the
Index 60870 setting value is a useful property in the IEC60870 communication.
As optional functions, the DNP3.0 communication and IEC60870 communication will not
cause any influence if the Entec‟s Recloser Control does not support these functions.
The Binary output‟s base data points are as follows. However, upported points may be different
according to the option and version of controller;
40 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
Loop Auto Restore Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled
14
Loop Auto Restore Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled
15 Loop Auto Restore Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled
Hot Line Tag Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled
16
Hot Line Tag Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled
17 Hot Line Tag Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled
ENHANCED TECHNOLOGY 41
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
*. NOTE )
1. The value(TR/CL Field) of all BO Points can be inverted with PLC setting of ETIMS Interface software.
2. The BO points above apply in default PLC setting. In case of changes to PLC setting, the block
condition of BO points may change.
− BDO#C (#: point number) : The block condition for close command of BO points can be set.
− BDO#T (#: point number) : The block condition for trip command of BO points can be set.
3. Supported points may be different according to the option and version of controller.
42 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
3. Counters
Click “Counters” Tap in the bottom of the “DB MAP CONFIGURATION” window to move to
Counters Map. The properties of Inver, Class, Var, IEC Mask A and more can be individually set in
the “User Map List” per each data point. The property can be changed by clicking the
corresponding property column (indicate the combo box) when the data point to be changed is
selected (indicate with a blue line).
The property setting items are as follows.
Class : It is to set a class that is related with event occurring of DNP3.0 communication.
Var : It is to set Object/Variation to read corresponding data point in DNP3.0 communication.
- 22/01 : 32 bit Change with flag
- 22/02 : 16 bit Change with flag
- 22/05 : 32 bit Change with flag and time
- 22/06 : 16 bit Change with flag and time
- 22/08 : 16 bit Delta Change with time-tag
IEC Mask A : It is to set IEC60870 communication use, Fixed as Group(included in group),
Cyclic(Periodical polling), Group&Cyclic set options. In addition, if the Class attribute is
allocated to Class1, 2 or 3, it will have the Spontaneous point attribute in case of IEC60870
communication.
IEC Mask B : It is to set a group on IEC60870 communication use. Please refer to
“IEC60870-5-101/104 PROTOCOL Technical Manual” for more detail information.
Active Event : It sets whether a Counter event will occur or not.
- None : Regardless of the setting, it does not make a Counter event occur.
- Active : Makes a Counter event happen according to the class attribute. If the Class is set
as “None” or “Class 0”, it does not allow an event to occur.
*. NOTE ) Count event is generated when the value of the Counter's data is changed
(increased or reset to be "0").
Frozen Counter : It sets whether to used a Frozen counter value and event.
- None : Regardless of the setting, it does not used a Frozen counter value and event.
- Active : Use to a frozen counter value and event.
- Clear after local freeze : Counter is reset after the freeze by itself.
Index 60870 : It is to set the object address to read to corresponding data point in IEC60870
communication.
ENHANCED TECHNOLOGY 43
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
The Class & Var setting value are useful properties in the DNP3.0 communication and the
IEC Mask A/B & Index 60870 setting value are a useful property in the IEC60870
communication.
As optional functions, the DNP3.0 communication and IEC60870 communication function
will not cause any influence if the Entec‟s Recloser Control does not support these functions.
9 Sag Count - Long Time Class 0 22/02 Group Group 1 NONE NONE
17 Swell Count - Long Time Class 0 22/02 Group Group 1 NONE NONE
22 Interruption CumulativeTime [sec]- Momentary Class 0 22/02 Group Group 1 NONE NONE
44 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
24 Interruption CumulativeTime [sec] -Sustained Class 0 22/02 Group Group 1 NONE NONE
118 Current Unbalance Detect Class 0 22/02 Group Group 1 NONE NONE
119 Voltage Unbalance Detect (Source) Class 0 22/02 Group Group 1 NONE NONE
120 Voltage Unbalance Detect (Load) Class 0 22/02 Group Group 1 NONE NONE
121 Under Frequency Detect Class 0 22/02 Group Group 1 NONE NONE
122 Under voltage TOTAL(Source) Class 0 22/02 Group Group 1 NONE NONE
123 Under voltage A(Source) Class 0 22/02 Group Group 1 NONE NONE
124 Under voltage B(Source) Class 0 22/02 Group Group 1 NONE NONE
125 Under voltage C(Source) Class 0 22/02 Group Group 1 NONE NONE
126 Over voltage TOTAL(Source) Class 0 22/02 Group Group 1 NONE NONE
127 Over voltage A(Source) Class 0 22/02 Group Group 1 NONE NONE
128 Over voltage B(Source) Class 0 22/02 Group Group 1 NONE NONE
129 Over voltage C(Source) Class 0 22/02 Group Group 1 NONE NONE
ENHANCED TECHNOLOGY 45
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
132 Interruption Total Cumulitive Time Class 0 22/02 Group Group 1 NONE NONE
133 Interruption Cumulitive Time A Class 0 22/02 Group Group 1 NONE NONE
134 Interruption Cumulitive Time B Class 0 22/02 Group Group 1 NONE NONE
135 Interruption Cumulitive Time C Class 0 22/02 Group Group 1 NONE NONE
INTERRUPTION Momentary
136 Class 0 22/02 Group Group 1 NONE NONE
Cumulitive Time
INTERRUPTION Temporary
137 Class 0 22/02 Group Group 1 NONE NONE
Cumulitive Time
INTERRUPTION Sustained
138 Class 0 22/02 Group Group 1 NONE NONE
Cumulitive Time
139 User Count 1 Class 0 22/02 Group Group 1 NONE NONE
147 Instantaneous Overcurrent -TOTAL Class 0 22/02 Group Group 1 NONE NONE
151 Instantaneous Overcurrent -Ground Class 0 22/02 Group Group 1 NONE NONE
153 Sensitive Earth Fault Class 0 22/02 Group Group 1 NONE NONE
154 Instantaneous Overcurrent – Neq Class 0 22/02 Group Group 1 NONE NONE
155 Time Overcurrent -TOTAL Class 0 22/02 Group Group 1 NONE NONE
159 Time Overcurrent -Ground Class 0 22/02 Group Group 1 NONE NONE
162 Time Overcurrent – Neq Class 0 22/02 Group Group 1 NONE NONE
46 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
163 Unser Voltage -Total Class 0 22/02 Group Group 1 NONE NONE
171 Over Voltage -Total Class 0 22/02 Group Group 1 NONE NONE
176 Over Voltage -Neutral Class 0 22/02 Group Group 1 NONE NONE
177 Neg Seq‟ Over Voltage (47) Class 0 22/02 Group Group 1 NONE NONE
186 Under Frequency (81U) Class 0 22/02 Group Group 1 NONE NONE
187 Over Frequency (81O) Class 0 22/02 Group Group 1 NONE NONE
188 Frequency Decay (81D) Class 0 22/02 Group Group 1 NONE NONE
192 Broken Conduct (46BC) Class 0 22/02 Group Group 1 NONE NONE
193 Frequency (81) – Total Class 0 22/02 Group Group 1 NONE NONE
ENHANCED TECHNOLOGY 47
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
195 Positive Active Energy - A Class 0 22/02 Group Group 1 NONE NONE
196 Positive Active Energy - B Class 0 22/02 Group Group 1 NONE NONE
197 Positive Active Energy - C Class 0 22/02 Group Group 1 NONE NONE
198 Positive Active Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE
199 Negative Active Energy - A Class 0 22/02 Group Group 1 NONE NONE
200 Negative Active Energy - B Class 0 22/02 Group Group 1 NONE NONE
201 Negative Active Energy - C Class 0 22/02 Group Group 1 NONE NONE
202 Negative Active Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE
203 Positive Reactive Energy - A Class 0 22/02 Group Group 1 NONE NONE
204 Positive Reactive Energy - B Class 0 22/02 Group Group 1 NONE NONE
205 Positive Reactive Energy - C Class 0 22/02 Group Group 1 NONE NONE
206 Positive Reactive Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE
207 Negative Reactive Energy - A Class 0 22/02 Group Group 1 NONE NONE
208 Negative Reactive Energy - B Class 0 22/02 Group Group 1 NONE NONE
209 Negative Reactive Energy - C Class 0 22/02 Group Group 1 NONE NONE
210 Negative Reactive Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE
*. NOTE )
1. Counter format can be selected (16 bit or 32 bit(Default)) by “16 bit Count Use” in “MAIN MENU
>> GLOBAL SETTING >> GENERAL >> DEVICE >> OTHERS” menu.
- 16 bit Counter rollover Counter 65535.
- 32 bit Counter rollover Counter 1,000,000.
2. Supported points may be different according to the option and version of controller.
48 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
4. Analog Input
Click “Analog Normalized Input” and “Analog Scaled Input” Tap in the bottom of the “DB MAP
CONFIGURATION” window to move to Analog Input Map. The properties of Inver, Class, Var,
IEC Mask A and more can individually be set in the “User Map List” per each data point. The
property can be changed by clicking the corresponding property column (indicate the combo box)
when the data point to be changed is selected (indicate with a blue line).
The property setting items are as follows.
Class : It is to set a class that is related with event occurring of DNP3.0 communication.
Var : It is to set Object/Variation to read corresponding data point in DNP3.0 communication.
- 32/01 : 32 bit Change without time-tag
- 32/02 : 16 bit Change without time-tag
- 32/03 : 32 bit Change with time-tag
- 32/04 : 16 bit Change with time-tag
- 32/05 : Short Change floating point
IEC Mask A : It is to set IEC60870 communication use, there are Group(included in group),
Cyclic(Periodical polling), Group&Cyclic set options. In addition, if the Class attribute is allocated
to Class1, 2 or 3, it will have the Spontaneous point attribute in case of IEC60870 communication.
IEC Mask B : It is to set a group on IEC60870 communication use. Refer to “IEC60870-5-
101/104 PROTOCOL Technical Manual” for more detailed information.
Active Event : It sets whether an Analog Input(AI) event will occur or not.
- NONE(N/A) : It does not make an AI event occur
- Active : It does make an AI event occur
*. NOTE ) The occurring AI event type differs according to the “AI Evt Method” setting in
the “GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC SETUP” menu
of Entec‟s Recloser Control.
The setting value is set to ‘OFF’: AI event does not occur even if the
Active Event property is set as „Active‟.
The setting value is set to ‘TH’: AI event occurs due to Threshold
Configuration.
The setting value is set to ‘DB’ : AI event occurs due to Deadband
Configuration.
The setting value is set to ‘BOTH’: AI event occurs through both
Threshold & Deadband Configuration being applied.
ENHANCED TECHNOLOGY 49
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
*. NOTE ) A user will set the “AEvt Skip at Ft” setting value in the “GLOBAL SETTING/
COMMUNICATION/ EVENT&ETC SETUP” menu of Entec‟s Recloser
Control to determine whether AI event is generated or not at fault pickup.
The setting value is set to ‘YES’: AI event is not generated during Fault
pickup.
The setting value is set to ‘NO’: AI event is generated during Fault pickup.
Deadband Configuration
- Limit Low : It sets the lower limit to make the event happen. It does not make the AI
event happen in case the Point data is lower than the “Limit Low” setting value.
- Limit High : It sets the upper limit to make the event happen. It does not make the AI
event happen in case the Point data is higher than the “Limit High” setting value.
- Dead Band : It makes the AI event happen if the difference in size of the point data is
above the Dead Band set value during the Smoothing Factor time (1sec).
- Smoothing Factor : It is the delta time to compare the point data change and is set as
1sec.
Threshold Configuration
- Threshold Low : It makes the AI event occur in case it goes out of the Threshold Low
range because the point data decreases or the point data value increases again and restores
within the Threshold Low range
- Threshold High : It makes the AI event occur in case it goes out of the Threshold High
range because the point data increases or the point data value decreases again and restores
within the Threshold High range
* The IEC60870 communication does not make an AI event that applied a Threshold
Configuration happen.
Scale : It transfers the divided proportion of the Scale set value from the actual data value.
SMS : Set whether to transmit SMS messages in case of event occurrence in the corresponding
point.
- NO : Does not send SMS messages even if a Analog Input(AI) event occurs.
- YES : Sends SMS messages in case a AI event occurs.
Index 60870 : It is to set the object address to read to corresponding data point in IEC60870
communication.
50 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
The Class & Var setting values are useful properties in the DNP3.0 communication and the
IEC Mask A/B and Index 60870 setting values are a useful property in the IEC60870
communication. The SMS setting value is a useful property in the SMS message transmitting
function.
As optional functions, the DNP3.0 communication, IEC60870 communication & SMS
message transmitting function will not cause any influence if the Entec‟s Recloser Control
does not support these functions.
ENHANCED TECHNOLOGY 51
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
1 DPS Version No. None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 0.0.0.1/1 Count
2 Circuit +12V None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
3 Circuit -12V None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
4 Circuit Temperature None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1℃ / 1 Count
5 TD Input 1 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count
6 TD Input 2 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count
7 TD Input 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count
8 TD Input 4 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count
9 TD Input 5 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count
10 Self Diagnosis (Detail) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 Note 1)
NOTE
1) Diagnostics Details: This point is 16 bit data that shows recloser diagnosis. When 1 is set in each bit, indicates that the following failures were detected.
- bit 0: Self diagnosis Setting - bit 6: Self diagnosis Event Failure - bit 11: Self diagnosis Ethernet 1 Failure
- bit 1: Self diagnosis Global Setting Failure - bit 7: Self diagnosis Count Failure - bit 12: Self diagnosis Ethernet 2 Failure
- bit 2: Self diagnosis Group Setting Failure - bit 8: Self diagnosis RTC Failure - bit 13: Self diagnosis Goose Failure
- bit 3: Self diagnosis Memory Failure - bit 9: Self diagnosis CPU Failure - bit 14: Self diagnosis DSP Failure
- bit 4: Self diagnosis PLC Failure - bit 10: Self diagnosis Comm. Line Failure - bit 15: Self diagnosis Communication Failure
11 Battery Voltage None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
ENHANCED TECHNOLOGY 52
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
13 Gas Pressure (bar) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1bar / 1 Count
14 Gas Pressure (Volt) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
15 Reference Voltage None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
16 Charger Current None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
17 Temperature (OUT) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1℃ / 1 Count
18 Battery Capacity None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
19 Channel1 Frequency None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Hz / 1 Count
20 Channel2 Frequency None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Hz / 1 Count
21 Voltage Unbalance Rate (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
22 Voltage Unbalance Rate (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
23 Current Unbalance Rate None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
24 Sag Magnitude A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
25 Sag Duration A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
26 Sag Magnitude B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
27 Sag Duration B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
28 Sag Magnitude C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
29 Sag Duration C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
30 Swell Magnitude A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
ENHANCED TECHNOLOGY 53
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
32 Swell Magnitude B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
33 Swell Duration B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
34 Swell Magnitude C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
35 Swell Duration C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
36 Interruption Magnitude A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
37 Interruption Duration A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
38 Interruption Magnitude B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
39 Interruption Duration B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
40 Interruption Magnitude C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
41 Interruption Duration C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count
42 Voltage A DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
43 Voltage A 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
44 Voltage A 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
45 Voltage A 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
46 Voltage A 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
47 Voltage A 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
48 Voltage A 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
49 Voltage A 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
ENHANCED TECHNOLOGY 54
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
51 Voltage A 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
52 Voltage A 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
53 Voltage A 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
54 Voltage A 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
55 Voltage A 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
56 Voltage A 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
57 Voltage A THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
58 Voltage B DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
59 Voltage B 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
60 Voltage B 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
61 Voltage B 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
62 Voltage B 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
63 Voltage B 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
64 Voltage B 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
65 Voltage B 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
66 Voltage B 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
67 Voltage B 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
68 Voltage B 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
ENHANCED TECHNOLOGY 55
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
70 Voltage B 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
71 Voltage B 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
72 Voltage B 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
73 Voltage B THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
74 Voltage C DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
75 Voltage C 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
76 Voltage C 3rd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
77 Voltage C 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
78 Voltage C 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
79 Voltage C 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
80 Voltage C 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
81 Voltage C 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
82 Voltage C 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
83 Voltage C 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
84 Voltage C 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
85 Voltage C 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
86 Voltage C 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
87 Voltage C 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
ENHANCED TECHNOLOGY 56
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
89 Voltage C THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
90 Current A DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
91 Current A 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
92 Current A 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
93 Current A 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
94 Current A 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
95 Current A 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
96 Current A 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
97 Current A 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
98 Current A 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
99 Current A 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
100 Current A 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
101 Current A 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
102 Current A 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
103 Current A 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
104 Current A 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
105 Current A THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
106 Current B DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
ENHANCED TECHNOLOGY 57
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
108 Current B 3rd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
109 Current B 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
110 Current B 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
111 Current B 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
112 Current B 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
113 Current B 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
114 Current B 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
115 Current B 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
116 Current B 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
117 Current B 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
118 Current B 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
119 Current B 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
120 Current B 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
121 Current B THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
122 Current C DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
123 Current C 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
124 Current C 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
125 Current C 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
ENHANCED TECHNOLOGY 58
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
127 Current C 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
128 Current C 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
129 Current C 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
130 Current C 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
131 Current C 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
132 Current C 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
133 Current C 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
134 Current C 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
135 Current C 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
136 Current C 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
137 Current C THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
138 Current G DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
139 Current G 2nd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
140 Current G 3rd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
141 Current G 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
142 Current G 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
143 Current G 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
144 Current G 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
ENHANCED TECHNOLOGY 59
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
146 Current G 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
147 Current G 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
148 Current G 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
149 Current G 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
150 Current G 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
151 Current G 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
152 Current G 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
153 Current G THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
154 Current A (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
155 Current B (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
156 Current C (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
157 Current G (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
158 Current N (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
159 Current SEF (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
160 Current Angle A (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
161 Current Angle B (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
162 Current Angle C (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
163 Current Angle G (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
ENHANCED TECHNOLOGY 60
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
165 Current Angle SEF (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
166 Positive Current(I1) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
167 Negative Current(I2) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
168 Zero Seq. Current(I0) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
169 Positive Current(I1) Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
170 Negative Current(I2) Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
171 Zero Seq. Current(I0) Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
172 Current (TRUE RMS) A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
173 Current (TRUE RMS) B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
174 Current (TRUE RMS) C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
175 Current (TRUE RMS) G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
176 Current A (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
177 Current B (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
178 Current C (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
179 Current G (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
180 Current A (C-RMS) 2nd Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
181 Current B (C-RMS) 2nd Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
182 Current C (C-RMS) 2nd Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
ENHANCED TECHNOLOGY 61
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
184 Current A (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
185 Current B (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
186 Current C (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
187 Current G (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
188 Voltage A (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
189 Voltage B (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
190 Voltage C (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
191 Zero Seq. Voltage (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
192 Voltage Angle A (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
193 Voltage Angle B (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
194 Voltage Angle C (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
195 Zero Seq. Voltage Angle (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
196 Line-Line Voltage AB (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
197 Line-Line Voltage BC (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
198 Line-Line Voltage CA (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
199 Voltage Angle AB (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
200 Voltage Angle BC (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
201 Voltage Angle CA (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
ENHANCED TECHNOLOGY 62
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
203 Negative Voltage V2 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
204 Zero Seq. Voltage V0 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
205 Positive Voltage Angle V1 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
206 Negative Voltage Angle V2 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
207 Zero Seq. Voltage Angle V0 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
208 Voltage A (TRUE RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
209 Voltage B (TRUE RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
210 Voltage C (TRUE RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
211 Voltage A (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
212 Voltage B (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
213 Voltage C (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
214 Zero Seq. Voltage (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
215 Voltage Angle A (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
216 Voltage Angle B (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
217 Voltage Angle C (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
218 Zero Seq. Voltage Angle (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
219 Voltage AB (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
220 Voltage BC (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
ENHANCED TECHNOLOGY 63
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
222 Voltage Angle AB (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
223 Voltage Angle BC (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
224 Voltage Angle CA (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
225 Positive Voltage V1 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
226 Negative Voltage V2 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
227 Zero Seq. VoltageV0 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
228 Positive Voltage Angle V1 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
229 Negative Voltage Angle V2 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
230 Zero Seq. Voltage Angle V0 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count
231 Voltage A (TRUE RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
232 Voltage B (TRUE RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
233 Voltage C (TRUE RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
234 Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
235 Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
236 Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
237 Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
238 Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
239 Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
ENHANCED TECHNOLOGY 64
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
241 Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
242 Apparent Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count
243 Apparent Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count
244 Apparent Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count
245 Apparent Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count
246 Power Factor A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
247 Power Factor B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
248 Power Factor C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
249 Power Factor (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
250 POSITIVE Real Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
251 POSITIVE Real Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
252 POSITIVE Real Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
253 POSITIVE Real Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
254 NEGATIVE Real Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
255 NEGATIVE Real Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
256 NEGATIVE Real Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
257 NEGATIVE Real Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
258 POSITIVE Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
ENHANCED TECHNOLOGY 65
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
260 POSITIVE Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
261 POSITIVE Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
262 NEGATIVE Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
263 NEGATIVE Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
264 NEGATIVE Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
265 NEGATIVE Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
266 Demand A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
267 Demand B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
268 Demand C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
269 Demand G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
270 Demand Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
271 Demand Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
272 Demand Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
273 Demand Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
274 Demand Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
275 Demand Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
276 Demand Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
277 Demand Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
ENHANCED TECHNOLOGY 66
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
279 Block Demand B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
280 Block Demand C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
281 Block Demand G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
282 Block Demand Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
283 Block Demand Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
284 Block Demand Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
285 Block Demand Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
286 Block Demand Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
287 Block Demand Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
288 Block Demand Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
289 Block Demand Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
290 Hourly Maximum Load A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
291 Hourly Maximum Load B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
292 Hourly Maximum Load C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
293 Hourly Maximum Load G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
294 Hourly Maximum Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
295 Hourly Maximum Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
296 Hourly Maximum Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
ENHANCED TECHNOLOGY 67
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
298 Hourly Maximum Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
299 Hourly Maximum Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
300 Hourly Maximum Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
301 Hourly Maximum Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
302 Today Maximum Load A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
303 Today Maximum Load B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
304 Today Maximum Load C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
305 Today Maximum Load G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
306 Today Maximum Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
307 Today Maximum Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
308 Today Maximum Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
309 Today Maximum Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
310 Today Maximum Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
311 Today Maximum Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
312 Today Maximum Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
313 Today Maximum Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
314 Yesterday Maximum Load Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
315 Yesterday Maximum Load Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
ENHANCED TECHNOLOGY 68
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
317 Yesterday Maximum Load Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
318 Yesterday Maximum Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
319 Yesterday Maximum Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
320 Yesterday Maximum Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
321 Yesterday Maximum Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
322 Yesterday Maximum Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
323 Yesterday Maximum Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
324 Yesterday Maximum Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
325 Yesterday Maximum Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
326 Fault Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
327 Fault Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
328 Fault Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
329 Fault Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
330 Fault Current SEF None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
331 Fault Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
332 Fault Voltage A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
333 Fault Voltage B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
334 Fault Voltage C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
ENHANCED TECHNOLOGY 69
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
336 Contact Wear B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
337 Contact Wear C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count
338 First Fault Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
339 First Fault Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
340 First Fault Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
341 First Fault Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
342 First Fault Current SEF None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
343 First Fault Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
344 First Fault Voltage A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
345 First Fault Voltage B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
346 First Fault Voltage C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count
347 Latitude(1:south,2:north) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 -
348 Degree None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1˚/1Count
349 Minute None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1‟/1Count
350 Second None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1”/1Count
351 Longitude(1:east,2:west) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 -
352 Degree None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1˚/1Count
353 Minute None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1‟/1Count
ENHANCED TECHNOLOGY 70
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
355 Peak Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
356 Peak Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
357 Peak Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
358 Peak Current G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
359 Peak Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
360 Pos Max Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
361 Pos Max Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
362 Pos Max Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
363 Pos Max Active Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
364 Pos Max Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
365 Pos Max Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
366 Pos Max Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
367 Pos Max Reactive Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
368 Neg Max Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
369 Neg Max Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
370 Neg Max Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
371 Neg Max Active Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count
372 Neg Max Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
ENHANCED TECHNOLOGY 71
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
374 Neg Max Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
375 Neg Max Reactive Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count
376 Operation Count None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count
377 Trip Count None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count
378 External TD 1 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count
379 External TD 2 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count
380 External TD 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count
381 External TD 4 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count
382 External TD 5 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count
383 Fault Location None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1km / 1 Count
384 Fault Reactance None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Ω / 1Count
385 Max Demand Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
386 Max Demand Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
387 Max Demand Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
388 Max Demand Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
389 Max Demand Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count
390 Mechanical Wear None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 % / 1 Count
391 Z0 Impedance Rms None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Ω / 1Count
ENHANCED TECHNOLOGY 72
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr
393 Y0 Admitance Rms None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1mS / 1Count
394 Y0 Admitance Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1˚/1Count
*. NOTE )
1. The Data Format of all AI Points can be changed with Scale setting of ETIMS Interface software.
2. Supported points may be different according to the option and version of controller.
ENHANCED TECHNOLOGY 73
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
5. Analog Output
Click “Analog Normalized Output” and “Analog Scaled Output” Tap in the bottom of the “DB
MAP CONFICURATION” window to move to Analog Output Map. The properties of Class & Var
can individually be set in the “User Map List” per each data point. The property can be changed by
clicking the corresponding property column (indicate the combo box) when the data point to be
changed is selected (indicate with a blue line).
The property setting items are as follows.
Class : It is to set a class that is related with event occurring of DNP3.0 communication.
The Class & Var setting value are useful properties in the DNP3.0 communication. If Entec‟s
Recloser Control does not support the DNP3.0 communication function, the corresponding
property will not cause any influence.
74 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
GROUP1(0), GROUP2(1),
11 Primary Setting Group NONE 1 GROUP1
GROUP3(2), GROUP4(3)
GROUP1(0), GROUP2(1),
12 Alternate Setting Group NONE 1 GROUP1
GROUP3(2), GROUP4(3)
13 Loop Control Type Select NONE NONE(0), SEC(1), MID(2), TIE(3) 1 NONE
ENHANCED TECHNOLOGY 75
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
OFF(0), TRIP(1),
38 (+) Phase Fast Overcurrent (51P-1) Function NONE 1 TRIP
ALARM(2), TR&AL(3)
76 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
52 (+) Phase Delay Overcurrent (51P-2) Reset Method NONE INST(0), LINEAR(1) 1 INST
OFF(0), TRIP(1),
54 (+) Ground Fast Overcurrent (51G-1) Function NONE 1 TRIP
ALARM(2), TR&AL(3)
OFF(0), TRIP(1),
62 (+) Ground Delay Overcurrent (51G-2) Function NONE 1 TRIP
ALARM(2), TR&AL(3)
ENHANCED TECHNOLOGY 77
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
OFF(0), TRIP(1),
70 (+) Neg. Seq Fast Overcurrent (51Q-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)
OFF(0), TRIP(1),
78 (+) Neg. Seq Delay Overcurrent (51Q-2) Function NONE 1 OFF
ALARM(2), TR&AL(3)
78 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 79
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
OFF(0), TRIP(1),
110 (+) Sensitive Earth Fault (50SEF) Function NONE 1 OFF
ALARM(2), TR&AL(3)
111 (+) Sensitive Earth Fault (50SEF) Pickup NONE 0.1 ~ 160.0 s 0.1 10.0
112 (+) Sensitive Earth Fault (50SEF) Time Delay NONE 0~600 s 0.01 0
113 Phase Direction (67P) Type NONE NONE(0), FOR(1), REV(2) 1 NONE
114 Phase Direction (67P) Maximum Torque Angle NONE 0~359 Lag 1 60
80 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
117 Ground Direction (67G) Type NONE NONE(0), FOR(1), REV(2) 1 NONE
120 Ground Direction (67G) Block Overcurrent NONE NO(1), YES(1) 1 YES
121 Sensitive Earth Fault Direction (67SEF) Type NONE NONE(0), FOR(1), REV(2) 1 NONE
125 Neg. Seq Direction (67Q) Type NONE NONE(0), FOR(1), REV(2) 1 NONE
128 Neg. Seq Direction (67Q) Block Overcurrent NONE NO(1), YES(1) 1 YES
ENHANCED TECHNOLOGY 81
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
OFF(0), TRIP(1),
145 (-) Ground Fast Overcurrent (51G-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)
82 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 83
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
84 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
ENHANCED TECHNOLOGY 85
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
203 (-) Sensitive Earth Fault (50SEF) Time Delay NONE 0~600 s 0.01 0
206 Phase Fast Curve Active at Shot 1 NONE NO(0), YES(1) 1 YES
207 Phase Fast Curve Active at Shot 2 NONE NO(0), YES(1) 1 YES
212 Ground Fast Curve Active at Shot 1 NONE NO(0), YES(1) 1 YES
213 Ground Fast Curve Active at Shot 2 NONE NO(0), YES(1) 1 YES
219 Neg. Seq Fast Curve Active at Shot 1 NONE NO(0), YES(1) 1 YES
220 Neg. Seq Fast Curve Active at Shot 2 NONE NO(0), YES(1) 1 YES
221 Neg. Seq Fast Curve Active at Shot 3 NONE NO(0), YES(1) 1 NO
222 Neg. Seq Fast Curve Active at Shot 4 NONE NO(0), YES(1) 1 NO
223 Neg. Seq Fast Curve Active at Shot 5 NONE NO(0), YES(1) 1 NO
224 Phase OverCurrent 1st Reclosing Time NONE 0.1~1800 s 0.01 0.6
228 Ground OverCurrent 1st Reclosing Time NONE 0.1~1800 s 0.01 0.6
86 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
233 Sensitive Earth Fault 2nd Reclosing Time NONE 0.1~1800 s 0.01 2
234 Sensitive Earth Fault 3rd Reclosing Time NONE 0.1~1800 s 0.01 15
235 Sensitive Earth Fault 4th Reclosing Time NONE 0.1~1800 s 0.01 15
243 Sensitive Earth Fault Inrush Restraint Function NONE DISABLE(0), ENABLE(1) 1 DISABLE
244 Neg. Seq Inrush Restraint Function NONE DISABLE(0), ENABLE(1) 1 DISABLE
251 Sensitive Earth Fault Pickup Restore Function NONE DISABLE(0), ENABLE(1) 1 DISABLE
252 Neg. Seq Pickup Restore Function NONE DISABLE(0), ENABLE(1) 1 DISABLE
253 Inrush Restraint Minimum Response Time NONE 0.01~600 s 0.01 0.6
257 Neg. Seq Inrush Restraint Reset Current NONE 10~1600 A 1 500
ENHANCED TECHNOLOGY 87
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
261 Inrush Restraint Function Active using Current NONE NO(0), YES(1) 1 NO
266 Phase Reset Method at Inrush Restraint Duration NONE INST(0), LINEAR(1) 1 INST
271 Ground Reset Method at Inrush Restraint Duration NONE INST(0), LINEAR(1) 1 INST
280 Cold Load Pickup Function Active using Current NONE NO(0), YES(1) 1 NO
88 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
OFF(0), TRIP(1),
286 Under Voltage1 (27-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)
287 Under Voltage1 (27-1) Pickup Level NONE 0.1~1.4 xVT 0.01 0.8
288 Under Voltage1 (27-1) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1
290 Under Voltage1 (27-1) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P
OFF(0), TRIP(1),
291 Under Voltage2 (27-2) Function NONE 1 OFF
ALARM(2), TR&AL(3)
292 Under Voltage2 (27-2) Pickup Level NONE 0.1~1.4 xVT 0.01 0.8
293 Under Voltage2 (27-2) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1
295 Under Voltage2 (27-2) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P
OFF(0), TRIP(1),
296 Over Voltage1 (59-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)
297 Over Voltage1 (59-1) Pickup Level NONE 0.1~1.4 xVT 0.01 1.1
299 Over Voltage1 (59-1) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P
OFF(0), TRIP(1),
300 Over Voltage2 (59-2) Function NONE 1 OFF
ALARM(2), TR&AL(3)
301 Over Voltage2 (59-2) Pickup Level NONE 0.1~1.4 xVT 0.01 1.1
303 Over Voltage2 (59-2) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P
OFF(0), TRIP(1),
304 Neutral Over Voltage1 (64N-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)
305 Neutral Over Voltage1 (64N-1) Pickup Level NONE 0.1~1.4 xVT 0.01 0.5
306 Neutral Over Voltage1 (64N-1) Time Delay NONE 0~600 s 0.01 5
ENHANCED TECHNOLOGY 89
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
308 Neutral Over Voltage2 (64N-2) Pickup Level NONE 0.1~1.4 xVT 0.01 0.5
309 Neutral Over Voltage2 (64N-2) Time Delay NONE 0~600 s 0.01 5
310 Under Voltage Auto Restoration Function NONE DISABLE(0), ENABLE(1) 1 DISABLE
311 Under Voltage Auto Restoration Pickup Level NONE 0.1~1.4 xVT 0.01 0.95
314 Under Voltage Restoration Source Side NONE VS(0), VL(1), VS&VL(2) 1 VS
315 Under Voltage Restoration Phase Type NONE 1P(0), 2P(1), 3P(2) 1 3P
316 Over Voltage Auto Restoration Function NONE DISABLE(0), ENABLE(1) 1 DISABLE
317 Over Voltage Auto Restoration Pickup Level NONE 0.1~1.4 xVT 0.01 1.05
320 Over Voltage Restoration Source Side NONE VS(0), VL(1), VS&VL(2) 1 VS
321 Over Voltage Restoration Phase Type NONE 1P(0), 2P(1), 3P(2) 1 3P
323 Under Frequency1 (81U-1) Pickup Frequency NONE 45~65 Hz 0.01 58.5
326 Under Frequency1 (81U-1) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1
329 Under Frequency2 (81U-2) Pickup Frequency NONE 45~65 Hz 0.01 58.5
332 Under Frequency2 (81U-2) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1
90 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
RS232-1(0), RS232-2(1),
ETH1(3),ETH2(4)
RS232-1(0), RS232-2(1),
ETH1(3),ETH2(4)
ENHANCED TECHNOLOGY 91
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
374 Z0 Addmittance (21YN) Operation Type NONE G&B(0), G(1), B(2) 1 G&B
375 Z0 Addmittance (21YN) Directional Type NONE NONE(0), FOR(1), REV(2) 1 NONE
376 Z0 Addmittance (21YN) Minimum SEF Current NONE 0.1 ~ 160.0 A 0.1 1.0
377 Z0 Addmittance (21YN) Minimum 3V0 NONE 0.10 ~ 1.40 xVT 0.01 0.10
378 Z0 Addmittance (21YN) Time Delay NONE 0.00 ~ 600.00 sec 0.01 2.00
379 Z0 Addmittance (21YN) Reset Time NONE 0.00 ~ 600.00 sec 0.01 0.10
380 Z0 Addmittance (21YN) Forward(Right) Conductance NONE 0.02 ~ 500.00 mS 0.01 1.00
381 Z0 Addmittance (21YN) Reverse(Left) Conductance NONE 0.02 ~ 500.00 mS 0.01 1.00
382 Z0 Addmittance (21YN) Forward(Up) Susceptance NONE 0.02 ~ 500.00 mS 0.01 1.00
383 Z0 Addmittance (21YN) Reverse(Down) Susceptance NONE 0.02 ~ 500.00 mS 0.01 1.00
OFF(0), TRIP(1),
384 Neg. Seq Voltage1 (47-1) Fuction NONE 1 OFF
ALARM(2), TR&AL(3)
385 Neg. Seq Voltage1 (47-1) Pickup Level NONE 0.10 ~ 1.40 xVT 0.01 0.50
386 Neg. Seq Voltage1 (47-1) Time Delay NONE 0.00 ~ 600.00 sec 0.01 5.00
OFF(0), TRIP(1),
387 Neg. Seq Voltage1 (47-2) Fuction NONE 1 OFF
ALARM(2), TR&AL(3)
388 Neg. Seq Voltage1 (47-2) Pickup Level NONE 0.10 ~ 1.40 xVT 0.01 0.50
389 Neg. Seq Voltage1 (47-2) Time Delay NONE 0.00 ~ 600.00 sec 0.01 5.00
92 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr
*. The range, step and default of AO points may be different according to the version of Entec‟s Recloser
Control firmware.
*. Supported points may be different according to the option and version of controller.
ENHANCED TECHNOLOGY 93