Release Date: Dec. 2019 / Manual Revision: 1.

12

Recloser Control ETR300-R & EVRC2A-NT

Communication Protocol MAP


Configuration User Manual

ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright © 2012 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Release Note:

[Apr. 2017] Ver1.00


Newly Made “New type ETR300-R DB MAP CONFIGURATION User Manual”.

[Jul. 2018] Ver1.01


Manual additionally applicable for new type Recloser Control EVRC2A-NT

[Oct. 2018] Ver1.10


1. Add the “No. 385 ~ 427” points in “Table 1. BASE DATA POINTS – BINARY INPUT”.
2. Change the “No. 192 ~ 194” points in “Table 3. BASE DATA POINTS – COUNTERS”.
3. Add the “No. 390 ~ 394” points in “Table 4. BASE DATA POINTS – ANALOG INPUT”.
4. Add the “No. 337 ~ 383” points in “Table 5. BASE DATA POINTS – ANALOG OUTPUT”.

[Nov. 2018] Ver1.11


1. Add the “No. 428 ~ 429” points in “Table 1. BASE DATA POINTS – BINARY INPUT”.
2. Add the “No. 384 ~ 389” points in “Table 5. BASE DATA POINTS – ANALOG OUTPUT”.

[Dec. 2019] Ver1.12


3. Add the “No. 430 ~ 447” points in “Table 1. BASE DATA POINTS – BINARY INPUT”.

ENHANCED TECHNOLOGY i
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table of Contents

A. Introduction ................................................................................................................... 1

1. Binary Input .............................................................................................................................. 2


2. Binary Output .......................................................................................................................... 40
3. Counters .................................................................................................................................. 43
4. Analog Input ............................................................................................................................ 49
5. Analog Output ......................................................................................................................... 74

ii ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

A. INTRODUCTION
Through the operation program, the user can remap the data map used in the protocol
communication of DNP 3.0, IEC60870-5-101/104, MODBUS and IEC61850. The “Base Map List”
on the left side of the diagram provides the list of all available data points and the ones that are
currently in use are shaded in grey. The “User Map List” on the right is the Data Map that applies
to Entec‟s Recloser Control (ETR300-R or EVRC2A-NT) choose the data point to add from the
“Base Map List” then drag it to the “User Map List” with the mouse and the data point is added.
Conversely, drag the data point from the “User Map List” to the “Base Map List” to delete from the
Data Map.
The remapped Data Map can be saved to file and managed or transmitted to Entec‟s Recloser
Control on-line.

Remapped Data Map must be transmitted through the operation program “UPLOAD >> DB
MAP CONFIG” menu to be applied to Entec‟s Recloser Control (For more details, refer to
“Interface Softwer User Manual”).

Figure 1. Operation Program DB MAP CONFIGURATION Screen

ENHANCED TECHNOLOGY 1
ETR300-R Communication Protocol MAP Configuration http://www.entecene.co.kr

1. Binary Input

Click the “Binary Single Input” or “Binary Double Input” Tap at the bottom of the “DB MAP
CONFIGURATION” window to move the Binary Input Map. The properties of Inver, Class, Var,
IEC Mask A and more can individually be set in the “User Map List” per each data point. The
property can be changed by clicking the corresponding property column (indicate the combo box)
when the data point to be changed is selected (indicate with a blue line).
The property setting items are as follows.

 Invert : It is used to invert a value of corresponding data point.


- NO(NONE) : Invert is not applied. If the corresponding point condition is „1‟, it shall be
transmitted as „1‟ and if the condition is „0‟, it shall be transmitted as point data „0‟.
- YES(OK) : Invert is applied. If the corresponding point condition is „1‟, transmit the data
point as „0‟ by inverting it and if the condition is „0‟, transmit the data point as „1‟.
 Class : It is to set a class that is related with event occurring in DNP3.0 communication.
 Var : It is to set Object/Variation to read to corresponding data point in DNP3.0
communication.
- 02/01 : Digit Change without time-tag
- 02/02 : Digit Change with time-tag
- 02/01 : Digit Change with relative time-tag
 IEC Mask A : It is to set IEC60870 communication use, there are Group(included in group),
Cyclic(Periodical polling), Group&Cyclic set options. Also, if the Class attribute is allocated to
Class1, 2 or 3, it will have the Spontaneous point attribute in case of IEC60870 communication.
 IEC Mask B : It is to set a group on IEC60870 communication use. Refer to “IEC60870-5-
101/104 PROTOCOL Technical Manual” for more detail information.
 SMS : Set whether to transmit SMS messages in case of event occurrence in the corresponding
point.
- NO : Does not send SMS messages even if a Binary Input(BI) event occurs.
- YES : Sends SMS messages in case a BI event occurs.
 Index 60870 : It is to set the object address to read to corresponding data point in IEC60870
communication.

2 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

The Class & Var setting values are useful properties in the DNP3.0 communication and the
IEC Mask A/B and Index 60870 setting values are a useful property in the IEC60870
communication. The SMS setting value is a useful property in the SMS message transmitting
function.
As optional functions, the DNP3.0 communication, IEC60870 communication & SMS
message transmitting function will not cause any influence if the Entec‟s Recloser Control
does not support these functions.

The Binary Input‟s base data points are as follows. However, supported points may be different
according to the version and option of Control.

ENHANCED TECHNOLOGY 3
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(1/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Panel sleep mode cleared Panel sleep mode entered
Sleep mode will be released if pressing the LCD back light and lamps except RUN lamp
[AWAKE] key on the panel or control box is off, and Initial Logo display.
0 Panel Sleep Mode NO 1 02/02 Group Group 2
is open.
In case “Panel Sleep Time” is set for “OFF”,
panel does not enter into sleep mode.
Normal operation mode Fault simulation mode entered
Can be accessed using fault simulator of
1 Fault Simulation Mode NO 1 02/02 Group Group 2 ETIMS interface software. In this mode, fault
operation is performed even if there is no
actual fault.
Indicates the CB status of the actual Virtual contact mode entered
Recloser. In Fault simulation mode, actual Recloser
2 Virtual Contact Mode NO 1 02/02 Group Group 2 does not operate and thus the fault operation
can be checked with the virtual CB
operation.
Recloser operation mode Sectionalizer operation mode
3 Sectionalizer Mode NO 1 02/02 Group Group 2 This point is cleared („0‟) in case the This point is set („1‟) in case the “Control
“Control Type” setting is RECLOSER. Type” setting is SECTIONALIZER.
Value for Setting normal. Value for Setting error.
4 Diagnostic Setting NO 1 02/02 Group Group 2 If this point is set ('1'), controller setting
values are is changed to default settings.
Memory normal. Memory error.
If this point is set ('1'), data recorded in
5 Diagnostic Memory NO 1 02/02 Group Group 2
controller memory such as event and counter
is reset.
RTC Time normal. RTC Time error.
6 Diagnostic RTC NO 1 02/02 Group Group 2 If this point is set ('1'), time is initialized to
January 1, 2000.

ENHANCED TECHNOLOGY 4
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(2/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Signal Processing Unit (DSP Module) Signal Processing Unit (DSP Module) error.
Diagnostic Signal
7 NO 1 02/02 Group Group 2 normal. If this point is set ('1'), won‟t perform proper
Processing Unit
protection operation.
Communication module normal. Communication module error.
Diagnostic Communication
8 NO 1 02/02 Group Group 2 If this point is set ('1'), won‟t perform proper
Error
communication operation.
Recloser Contact Wear normal. Recloser Contact Wear alarm.
This point is set(„1‟) when recloser contact
9 Diagnostic Contact Wear NO 1 02/02 Group Group 2
wear is less than “Alarm Pickup” set value of
Contact Wear Monitoring function.
Recloser Operation Counter normal. Recloser Operation Counter alarm.
This point is set(„1‟) when recloser operation
10 Diagnostic Operation Count NO 1 02/02 Group Group 2
counter reaches “Alarm Count” set value of
Operation Count Monitoring function.
11 User LED - 1 *.Note 1) NO 1 02/02 Group Group 2 User LED - 1 OFF User LED - 1 ON
*.Note 1)
12 User LED - 2 NO 1 02/02 Group Group 2 User LED - 2 OFF User LED - 2 ON
13 User LED - 3 *.Note 1) NO 1 02/02 Group Group 2 User LED - 3 OFF User LED - 3 ON
14 User LED - 4 *.Note 1) NO 1 02/02 Group Group 2 User LED - 4 OFF User LED - 4 ON
*.Note 1)
15 User LED - 5 NO 1 02/02 Group Group 2 User LED - 5 OFF User LED - 5 ON
*.Note 1)
16 User LED - 6 NO 1 02/02 Group Group 2 User LED - 6 OFF User LED - 6 ON
*.Note 1)
17 User LED - 7 NO 1 02/02 Group Group 2 User LED - 7 OFF User LED - 7 ON
*.Note 1)
18 User LED - 8 NO 1 02/02 Group Group 2 User LED - 8 OFF User LED - 8 ON
*. NOTE 1) User LED can be mapped using the PLC setting (ULED1~8) through the interface Software.
19 User Logic Bit – 01 *.Note2) NO 1 02/02 Group Group 4 User Logic Bit - 01 not assert User Logic Bit - 01 assert
*.Note2)
20 User Logic Bit - 02 NO 1 02/02 Group Group 4 User Logic Bit - 02 not assert User Logic Bit - 02 assert
*.Note2)
21 User Logic Bit - 03 NO 1 02/02 Group Group 4 User Logic Bit - 03 not assert User Logic Bit - 03 assert
*.Note2)
22 User Logic Bit - 04 NO 1 02/02 Group Group 4 User Logic Bit - 04 not assert User Logic Bit - 04 assert

ENHANCED TECHNOLOGY 5
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(3/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
*.Note2)
23 User Logic Bit - 05 NO 1 02/02 Group Group 4 User Logic Bit - 05 not assert User Logic Bit - 05 assert
*.Note2)
24 User Logic Bit - 06 NO 1 02/02 Group Group 4 User Logic Bit - 06 not assert User Logic Bit - 06 assert
*.Note2)
25 User Logic Bit - 07 NO 1 02/02 Group Group 4 User Logic Bit - 07 not assert User Logic Bit - 07 assert
*.Note2)
26 User Logic Bit - 08 NO 1 02/02 Group Group 4 User Logic Bit - 08 not assert User Logic Bit - 08 assert
*.Note2)
27 User Logic Bit - 09 NO 1 02/02 Group Group 4 User Logic Bit - 09 not assert User Logic Bit - 09 assert
*.Note2)
28 User Logic Bit - 10 NO 1 02/02 Group Group 4 User Logic Bit - 10 not assert User Logic Bit - 10 assert
29 User Logic Bit - 11 *.Note2) NO 1 02/02 Group Group 4 User Logic Bit - 11 not assert User Logic Bit - 11 assert
*.Note2)
30 User Logic Bit - 12 NO 1 02/02 Group Group 4 User Logic Bit - 12 not assert User Logic Bit - 12 assert
*.Note2)
31 User Logic Bit - 13 NO 1 02/02 Group Group 4 User Logic Bit - 13 not assert User Logic Bit - 13 assert
*.Note2)
32 User Logic Bit - 14 NO 1 02/02 Group Group 4 User Logic Bit - 14 not assert User Logic Bit - 14 assert
*.Note2)
33 User Logic Bit - 15 NO 1 02/02 Group Group 4 User Logic Bit - 15 not assert User Logic Bit - 15 assert
*.Note2)
34 User Logic Bit - 16 NO 1 02/02 Group Group 4 User Logic Bit - 16 not assert User Logic Bit - 16 assert
*.Note2)
35 User Logic Bit - 17 NO 1 02/02 Group Group 2 User Logic Bit - 17 not assert User Logic Bit - 17 assert
*.Note2)
36 User Logic Bit - 18 NO 1 02/02 Group Group 2 User Logic Bit - 18 not assert User Logic Bit - 18 assert
*.Note2)
37 User Logic Bit - 19 NO 1 02/02 Group Group 2 User Logic Bit - 19 not assert User Logic Bit - 19 assert
*.Note2)
38 User Logic Bit - 20 NO 1 02/02 Group Group 2 User Logic Bit - 20 not assert User Logic Bit - 20 assert
*.Note2)
39 User Logic Bit - 21 NO 1 02/02 Group Group 2 User Logic Bit - 21 not assert User Logic Bit - 21 assert
*.Note2)
40 User Logic Bit - 22 NO 1 02/02 Group Group 2 User Logic Bit - 22 not assert User Logic Bit - 22 assert
*.Note2)
41 User Logic Bit - 23 NO 1 02/02 Group Group 2 User Logic Bit - 23 not assert User Logic Bit - 23 assert
*.Note2)
42 User Logic Bit - 24 NO 1 02/02 Group Group 2 User Logic Bit - 24 not assert User Logic Bit - 24 assert
*.Note2)
43 User Logic Bit - 25 NO 1 02/02 Group Group 2 User Logic Bit - 25 not assert User Logic Bit - 25 assert
*.Note2)
44 User Logic Bit - 26 NO 1 02/02 Group Group 2 User Logic Bit - 26 not assert User Logic Bit - 26 assert
*.Note2)
45 User Logic Bit - 27 NO 1 02/02 Group Group 2 User Logic Bit - 27 not assert User Logic Bit - 27 assert

ENHANCED TECHNOLOGY 6
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(4/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
*.Note2)
46 User Logic Bit - 28 NO 1 02/02 Group Group 2 User Logic Bit - 28 not assert User Logic Bit - 28 assert
*.Note2)
47 User Logic Bit - 29 NO 1 02/02 Group Group 2 User Logic Bit - 29 not assert User Logic Bit - 29 assert
*.Note2)
48 User Logic Bit - 30 NO 1 02/02 Group Group 2 User Logic Bit - 30 not assert User Logic Bit - 30 assert
*.Note 2)
49 User Logic Bit - 31 NO 1 02/02 Group Group 2 User Logic Bit - 31 not assert User Logic Bit - 31 assert
*.Note 2)
50 User Logic Bit - 32 NO 1 02/02 Group Group 2 User Logic Bit - 32 not assert User Logic Bit - 32 assert
*. NOTE 2) Status can be mapped by User Logic Bits available in the PLC settings (ULB01~32) of ETIMS Interface Software.
If you want to use BI points that are not supported in the Base Map, use the "User Logic Bit" BI point after configuring the status of the user logic bits in
the PLC.
A/D Converter normal. A/D Converter error.
Diagnostic ADC
51 NO 1 02/02 Group Group 10 If this point is set ('1'), metering is not
(A/D Converter)
accurate
Recloser operation power normal Recloser operation power error
52 Diagnostic Operation Power NO 1 02/02 Group Group 10 If this point is set ('1'), recloser doesn‟t
perform close/open operation
Recloser close coil normal Recloser close coil error
53 Diagnostic Close Coil NO 1 02/02 Group Group 10 If this point is set ('1'), recloser doesn‟t
perform close operation
Recloser trip coil normal Recloser trip coil error
54 Diagnostic Trip Coil NO 1 02/02 Group Group 10 If this point is set ('1'), recloser doesn‟t
perform open operation
Recloser IGBT module normal Recloser IGBT module error
55 Diagnostic IGBT NO 1 02/02 Group Group 10 If this point is set ('1'), recloser doesn‟t
perform close/open operation
IRIG module normal IRIG module error
If IRIG is not installed (“IRIG Use” set
56 Diagnostic IRIG Module NO 1 02/02 Group Group 2
is “OFF”), this point is always
cleared(„0‟)

ENHANCED TECHNOLOGY 7
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(5/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
IRIG link normal IRIG link(connection) fail
If IRIG is not installed (“IRIG Use” set
57 Diagnostic IRIG Link Fail NO 1 02/02 Group Group 2
is “OFF”), this point is always
cleared(„0‟)
External I/O unit normal External I/O unit error
If External I/O unit is not installed
58 Diagnostic External I/O Uint NO 1 02/02 Group Group 2
(“EXT. I/O Use” set is “OFF”), this point
is always cleared(„0‟)
Wifi module normal Wifi module error
59 Diagnostic Wifi Module NO 1 02/02 Group Group 2 If Wifi is not installed (“Wif Use” set is
“OFF”), this point is always cleared(„0‟)
If Wifi is not installed (“Wif Use” set is Wifi link(connection) fail
60 Diagnostic Wifi Link Fail NO 1 02/02 Group Group 2
“OFF”), this point is always cleared(„0‟)
System normal System alarm
“DIAG/ERROR” lamp is ON when this point
is set(„1‟).
61 Diagnostic Alarm Status NO 1 02/02 Group Group 10
System alarm status for the above diagnostic
items can be mapped through PLC setting
(DIGARM) of ETIMS Interface Software.
System normal System error.
“DIAG/ERROR” lamp is ON when this point
is set(„1‟).
62 Diagnostic Error Status NO 1 02/02 Group Group 10
System error status for the above diagnostic
items can be mapped through PLC setting
(DIGERR) of ETIMS Interface Software.
63 Close Status NO 1 02/02 Group Group 1 Recloser not closed Recloser closed
64 Open Status NO 1 02/02 Group Group 1 Recloser not opened Recloser opened(tripped)

ENHANCED TECHNOLOGY 8
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(6/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
52 Contact Status normal 52 Contact Status trouble
This includes;
65 Contact Trouble Status NO 1 02/02 Group Group 1 - Both Close and Open status are set(„1‟)
- Both Close and Open status are
cleared(„0‟)
Recloser opened or Recloser status not Recloser closed
66 Recloser Contact 52A Status NO 1 02/02 Group Group 2
known
Recloser Mechanism is freed. Recloser Mechanism is locked.
67 Mechenism Lock NO 1 02/02 Group Group 1 Recloser does‟t operate with Close and Open
state.
Gas pressure normal or high Gas pressure is low.
If the recloser is not gas type (“Gas ; Gas pressure< 0.1 Bar
68 Gas Low Alarm NO 1 02/02 Group Group 2
Sensor” set is “OFF”), this point is
always cleared(„0‟)
Gas pressure normal or low Gas pressure is high.
If the recloser is not gas type (“Gas ; Gas pressure > 1.5 Bar
69 Gas High Alarm NO 1 02/02 Group Group 2
Sensor” set is “OFF”), this point is
always cleared(„0‟)
Gas pressure normal Gas pressure is low or high
If the recloser is not gas type (“Gas ; Gas pressure< 0.1 Bar
70 Gas Alarm NO 1 02/02 Group Group 1
Sensor” set is “OFF”), this point is or Gas pressure > 1.5 Bar
always cleared(„0‟)
71 Door Open NO 1 02/02 Group Group 2 Door Closed Door Opened
If not virtual contact mode, or Virtual Virtual recloser close status in virtual contact
72 Virtual Contact Close Status NO 1 02/02 Group Group 2 recloser open status in virtual contact mode of Fault simulation.
mode
If not virtual contact mode, or Virtual Virtual recloser open status in virtual contact
73 Virtual Contact Open Status NO 1 02/02 Group Group 2 recloser close status in virtual contact mode of Fault simulation.
mode

ENHANCED TECHNOLOGY 9
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(7/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
74 AC Power Fail NO 1 02/02 Group Group 2 External AC power is supplied. External AC power is not supplied.
Charge Circuit Voltage is normal or high. Charge Circuit Voltage is low or high.
75 Charger Voltage Bad NO 1 02/02 Group Group 2 ; Charger Voltage ≤ 25V or
Charger Voltage ≥ 29V
Battery Voltage is normal or high, Battery Voltage is low or high.
76 Battery Voltage Bad NO 1 02/02 Group Group 2 or Battery Discharge Test is failed. ; 15V< Battery Voltage ≤ 21V or
Battery Voltage ≥ 28V
System power is normal. Power down mode entered.
77 Power Down NO 1 02/02 Group Group 2 ; Batt. Volt. Above≤ 18V, 10sec
20V< Batt. Volt above≤ 21V, 10min
Battery Voltage is normal or not grouned Battery is grounded.
78 Battery No NO 1 02/02 Group Group 2
; Battery Voltage ≤ 15V
79 Spare NO 1 02/02 Group Group 2 - -
80 Spare NO 1 02/02 Group Group 2 - -
Recloser open/close coil normal Recloser open/close coil error
81 Coil Alarm NO 1 02/02 Group Group 2 ; Diagnostic Close Coil(No. 53) or
Diagnostic Trip Coil(No. 54)
Setting Group 1 inactived Setting Group 1 actived
82 Setting Group1 Active NO 1 02/02 Group Group 6 Group Setting is applied by the value of
Setting Group 1.
Setting Group 2 inactived Setting Group 2 actived
83 Setting Group2 Active NO 1 02/02 Group Group 6 Group Setting is applied by the value of
Setting Group 2.
Setting Group 3 inactived Setting Group 3 actived
84 Setting Group3 Active NO 1 02/02 Group Group 6 Group Setting is applied by the value of
Setting Group 3.

ENHANCED TECHNOLOGY 10
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(8/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Setting Group 4 inactived Setting Group 4 actived
85 Setting Group4 Active NO 1 02/02 Group Group 6 Group Setting is applied by the value of
Setting Group 4.
Setting Group 5 inactived Setting Group 5 actived
86 Setting Group5 Active NO 1 02/02 Group Group 6 Group Setting is applied by the value of
Setting Group 5.
Setting Group 6 inactived Setting Group 6 actived
87 Setting Group6 Active NO 1 02/02 Group Group 6 Group Setting is applied by the value of
Setting Group 6.
88 Protection Enabled NO 1 02/02 Group Group 2 Protection function disabled Protection function enabled
89 Protection Disabled NO 1 02/02 Group Group 2 Protection function enabled Protection function disabled
90 Ground Protection Enabled NO 1 02/02 Group Group 2 Ground Protection function disabled Ground Protection function enabled
91 Ground Protection Disabled NO 1 02/02 Group Group 2 Ground Protection function enabled Ground Protection function disabled
92 SEF Protection Enabled NO 1 02/02 Group Group 2 SEF Protection function disabled SEF Protection function enabled
93 SEF Protection Disabled NO 1 02/02 Group Group 2 SEF Protection function enabled SEF Protection function disabled
94 Reclose Enabled NO 1 02/02 Group Group 2 Reclose function disabled Reclose function enabled
95 Reclosed Disabled NO 1 02/02 Group Group 2 Reclose function enabled Reclose function disabled
96 Control Lock NO 1 02/02 Group Group 2 Local/Remote control unlocked Local/Remote control locked
97 Control Unlock NO 1 02/02 Group Group 2 Local/Remote control locked Local/Remote control unlocked
Remote control disabled Remote control enabled
98 Remote Enabled NO 1 02/02 Group Group 2
Local control enabled Local control disabled
Remote control enabled Remote control disabled
99 Remote Disabled NO 1 02/02 Group Group 2
Local control disabled Local control enabled

ENHANCED TECHNOLOGY 11
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(9/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Loop control function disabled Loop control function enabled
This point can be set ('1') only under the
conditions shown in the table below;
Loop Control Setting Recloser
100 Loop Control Enabled NO 1 02/02 Group Group 2
Function Type Select Status
ENABLE SEC CLOSED
ENABLE MID CLOSED
ENABLE TIE OPEN

101 Loop Control Disabled NO 1 02/02 Group Group 2 Loop control function enabled Loop control function disabled
Auto restoration function disabled Auto restoration function of SEC, MID
enabled
Loop Control Auto Restore
102 NO 1 02/02 Group Group 2 This point can be set ('1') only when Loop
Enabled
control type setting is SEC, MID and the
above "Loop Control Auto Restore Enabled"
Auto restoration function of SEC, MID Auto restoration function disabled
Loop Control Auto Restore
103 NO 1 02/02 Group Group 2 enabled
Disabled

104 Hot-Line Tag Enabled NO 1 02/02 Group Group 2 Hot-Line Tag function disabled Hot-Line Tag function enabled
105 Hot-Line Tag Disabled NO 1 02/02 Group Group 2 Hot-Line Tag function enabled Hot-Line Tag function disabled
106 Aux1 Enabled NO 1 02/02 Group Group 2 Aux1 disabled Aux1 enabled
107 Aux1 Disabled NO 1 02/02 Group Group 2 Aux1 enabled Aux1 disabled
108 Aux 2 Enabled NO 1 02/02 Group Group 2 Aux 2 disabled Aux 2 enabled
109 Aux 2 Disabled NO 1 02/02 Group Group 2 Aux 2 enabled Aux 2 disabled
Primary Setting active Alternate Setting active
However, when the Loop control This point applies only when the Loop
110 Alternate Set Group Enabled NO 1 02/02 Group Group 2
function setting is disabled, this point is control function is enabled.
always cleared ('0').

ENHANCED TECHNOLOGY 12
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(10/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Recloser close/open operation block status due to
abnormal gas pressure (low or high):
111 Gas Low Lock NO 1 02/02 Group Group 6 -
This point is set ('1') only when Opr' Block GPF
(Operation block at gas pressure failure) is ON.
Local Manual Close Delay Status
After controlling from the CLOSE button on the
112 Manual Close Delay NO 1 02/02 Group Group 2 -
front panel, close delayed status by the set time in
manual close time delay
Lockout status due to manual close control during
Maunal Close On To Fault fault sequence (79 cycle)
113 NO 1 02/02 Group Group 2 -
Lockout At 79 Cycle Even if the auto reclosing sequence remains, it is
locked out and cannot be reclosed.
(-) NEG SEQ Time Fault Trip was caused by (-) NEG SEQ Time
114 NO 1 02/02 Group Group 2 -
Overcurrent (251Q) Trip Overcurrent (251Q) protection element.
Alarm occurrence was caused by (-) NEG SEQ
(-) NEG SEQ Time Time Overcurrent (251Q) protection element.
115 NO 1 02/02 Group Group 2 -
Overcurrent (251Q) Alarm If this point is set ('1'), recloser does not perform
trip operation.
(-) Sensitive Earth Fault Time Fault Trip was caused by (-) Sensitive Earth Fault
116 NO 1 02/02 Group Group 2 -
Overcurrent (251SG) Trip Time Overcurrent (251SG) protection element.
Alarm occurred by (-) Sensitive Earth Fault Time
(-) Sensitive Earth Fault Time Overcurrent (251SG) protection element.
117 NO 1 02/02 Group Group 2 -
Overcurrent (251SG) Alarm If this point is set ('1'), recloser does not perform
trip operation.
Alarm occurred by (+) Sensitive Earth Fault
(+) Sensitive Earth Fault Instantaneous Overcurrent (150SG) protection
118 Instantaneous Overcurrent NO 1 02/02 Group Group 2 - element.
(150SG) Alarm If this point is set ('1'), recloser does not perform
trip operation.

ENHANCED TECHNOLOGY 13
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(11/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Alarm occurred by (-) Sensitive Earth Fault
(-) Sensitive Earth Fault
Instantaneous Overcurrent (250SG) protection element.
119 Instantaneous Overcurrent NO 1 02/02 Group Group 2 -
If this point is set ('1'), recloser does not perform trip
(250SG) Alarm
operation.
Controller external temperature (Control box internal
External Temperature temperature) high 2; Temperature ≥ 31℃
120 NO 1 02/02 Group Group 2 -
High-High Level *.Note 3) If this point is set ('1'), it performs the corresponding
control box temperature management.
Controller external temperature (Control box internal
External Temperature temperature) high 1; 31℃ > Temperature ≥ 29℃
121 NO 1 02/02 Group Group 2 -
High-Low Level *.Note 3) If this point is set ('1'), it performs the corresponding
control box temperature management.
Controller external temperature (Control box internal
External Temperature temperature) Low 1; 7℃ ≥ Temperature > 4℃
122 NO 1 02/02 Group Group 2 -
Low-High Level *.Note 3) If this point is set ('1'), it performs the corresponding
control box temperature management.
Controller external temperature (Control box internal
External Temperature Low- temperature) Low 2 ; Temperature ≤ 4℃
123 NO 1 02/02 Group Group 2 -
Low Level *.Note 3) If this point is set ('1'), it performs the corresponding
control box temperature management.
*. NOTE 3) If the external temperature sensor is not set (“EXT.Temper‟ Use” set is “OFF”), external related points are not set ('1').

ENHANCED TECHNOLOGY 14
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(12/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
124 SCADA Input Port - 1 NO 1 02/02 Group Group 3 SCADA Input Port - 1 (IN101) not assert SCADA Input Port - 1 (IN101) assert
125 SCADA Input Port - 2 NO 1 02/02 Group Group 3 SCADA Input Port - 2 (IN102) not assert SCADA Input Port - 2 (IN102) assert
126 SCADA Input Port - 3 NO 1 02/02 Group Group 3 SCADA Input Port - 3 (IN103) not assert SCADA Input Port - 3 (IN103) assert
127 SCADA Input Port - 4 NO 1 02/02 Group Group 3 SCADA Input Port - 4 (IN104) not assert SCADA Input Port - 4 (IN104) assert
128 SCADA Input Port - 5 NO 1 02/02 Group Group 3 SCADA Input Port - 5 (IN105) not assert SCADA Input Port - 5 (IN105) assert
129 SCADA Input Port - 6 NO 1 02/02 Group Group 3 SCADA Input Port - 6 (IN106) not assert SCADA Input Port - 6 (IN106) assert
130 SCADA Input Port - 7 NO 1 02/02 Group Group 3 SCADA Input Port - 7 (IN107) not assert SCADA Input Port - 7 (IN107) assert
131 SCADA Input Port - 8 NO 1 02/02 Group Group 3 SCADA Input Port - 8 (IN108) not assert SCADA Input Port - 8 (IN108) assert
132 SCADA Input Port - 9 NO 1 02/02 Group Group 3 SCADA Input Port - 9 (IN109) not assert SCADA Input Port - 9 (IN109) assert
133 SCADA Input Port - 10 NO 1 02/02 Group Group 3 SCADA Input Port - 10 (IN111) not assert SCADA Input Port - 10 (IN111) assert
134 SCADA Input Port - 11 NO 1 02/02 Group Group 3 SCADA Input Port - 11 (IN111) not assert SCADA Input Port - 11 (IN111) assert
135 SCADA Input Port - 12 NO 1 02/02 Group Group 3 SCADA Input Port - 12 (IN112) not assert SCADA Input Port - 12 (IN112) assert
*.Note 4)
136 External Input Port - 1 NO 1 02/02 Group Group 3 External Input Port - 1 (IN301) not assert External Input Port - 1 (IN301) assert
*.Note 4)
137 External Input Port - 2 NO 1 02/02 Group Group 3 External Input Port - 2 (IN302) not assert External Input Port - 2 (IN302) assert
*.Note 4)
138 External Input Port - 3 NO 1 02/02 Group Group 3 External Input Port - 3 (IN303) not assert External Input Port - 3 (IN303) assert
*.Note 4)
139 External Input Port - 4 NO 1 02/02 Group Group 3 External Input Port - 4 (IN304) not assert External Input Port - 4 (IN304) assert
*.Note 4)
140 External Input Port - 5 NO 1 02/02 Group Group 2 External Input Port - 5 (IN305) not assert External Input Port - 5 (IN305) assert
*.Note 4)
141 External Input Port - 6 NO 1 02/02 Group Group 2 External Input Port - 6 (IN306) not assert External Input Port - 6 (IN306) assert
*.Note 4)
142 External Input Port - 7 NO 1 02/02 Group Group 2 External Input Port - 7 (IN307) not assert External Input Port - 7 (IN307) assert
*.Note 4)
143 External Input Port - 8 NO 1 02/02 Group Group 2 External Input Port - 8 (IN308) not assert External Input Port - 8 (IN308) assert
144 SCADA Output Port - 1 NO 1 02/02 Group Group 2 SCADA Output Port - 1 (OUT101) not assert SCADA Output Port - 1 (OUT101) assert
145 SCADA Output Port - 2 NO 1 02/02 Group Group 2 SCADA Output Port - 2 (OUT102) not assert SCADA Output Port - 2 (OUT102) assert
146 SCADA Output Port - 3 NO 1 02/02 Group Group 2 SCADA Output Port - 3 (OUT103) not assert SCADA Output Port - 3 (OUT103) assert

ENHANCED TECHNOLOGY 15
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(13/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
147 SCADA Output Port - 4 NO 1 02/02 Group Group 2 SCADA Output Port - 4 (OUT104) not assert SCADA Output Port - 4 (OUT104) assert
148 SCADA Output Port - 5 NO 1 02/02 Group Group 3 SCADA Output Port - 5 (OUT105) not assert SCADA Output Port - 5 (OUT105) assert
149 SCADA Output Port - 6 NO 1 02/02 Group Group 3 SCADA Output Port - 6 (OUT106) not assert SCADA Output Port - 6 (OUT106) assert
150 SCADA Output Port - 7 NO 1 02/02 Group Group 3 SCADA Output Port - 7 (OUT107) not assert SCADA Output Port - 7 (OUT107) assert
151 SCADA Output Port - 8 NO 1 02/02 Group Group 3 SCADA Output Port - 8 (OUT108) not assert SCADA Output Port - 8 (OUT108) assert
*.Note 4)
152 External Output Port - 1 NO 1 02/02 Group Group 3 External Output Port - 1 (OUT301) not assert External Output Port - 1 (OUT301) assert
153 External Output Port - 2 *.Note 4) NO 1 02/02 Group Group 3 External Output Port - 2 (OUT302) not assert External Output Port - 2 (OUT302) assert
*.Note 4)
154 External Output Port - 3 NO 1 02/02 Group Group 3 External Output Port - 3 (OUT303) not assert External Output Port - 3 (OUT303) assert
*.Note 4)
155 External Output Port - 4 NO 1 02/02 Group Group 3 External Output Port - 4 (OUT304) not assert External Output Port - 4 (OUT304) assert
*.Note 4)
156 External Output Port - 5 NO 1 02/02 Group Group 2 External Output Port - 5 (OUT305) not assert External Output Port - 5 (OUT305) assert
*.Note 4)
157 External Output Port - 6 NO 1 02/02 Group Group 2 External Output Port - 6 (OUT306) not assert External Output Port - 6 (OUT306) assert
*.Note 4)
158 External Output Port - 7 NO 1 02/02 Group Group 2 External Output Port - 7 (OUT307) not assert External Output Port - 7 (OUT307) assert
*.Note 4)
159 External Output Port - 8 NO 1 02/02 Group Group 2 External Output Port - 8 (OUT308) not assert External Output Port - 8 (OUT308) assert
*. NOTE 4) If external I/O unit is not set (“EXT. I/O Use” set is “OFF”), external input/output related points are not set ('1').
(-) Sesitive Earth Fault Fault Trip caused by (-) Sesitive Earth
160 NO 1 02/02 Group Group 2 -
(250SG) Timeout Fault (250SG) protection element.
Fault Trip caused by (-) Negative
(-) Neg Seq Instantaneous
161 NO 1 02/02 Group Group 2 - Sequence Instantaneous Overcurrent
Overcurrent (250Q) Timeout
(250Q) protection element.
Fault Trip caused by (+) Phase
(+) Phase Instantaneous
162 NO 1 02/02 Group Group 2 - Instantaneous Overcurrent (150P-1)
Overcurrent (150P-1) Timeout
protection element.
(+) Phase Instantaneous Fault Trip caused by (+) Phase
163 Lockout Overcurrent NO 1 02/02 Group Group 2 - Instantaneous Lockout Overcurrent
(150P-2) Timeout (150P-2) protection element.

ENHANCED TECHNOLOGY 16
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(14/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Timeout for Phase fault indication
164 Phase FI (150P-3) Timeout NO 1 02/02 Group Group 2 - However, it is applicable only in the sectionalizer mode
("Control Type" setting is SECTIONALIZER).
(+) Ground Instantaneous Fault Trip caused by (+) Ground Instantaneous
165 NO 1 02/02 Group Group 2 -
Overcurrent (150G-1) Timeout Overcurrent (150G-1) protection element.
(+) Ground Instantaneous Fault Trip caused by (+) Ground Instantaneous Lockout
166 Lockout Overcurrent NO 1 02/02 Group Group 2 - Overcurrent (150G-2) protection element.
(150G-2) Timeout
Timeout for Ground fault indication
167 Ground FI (150G-3) Timeout NO 1 02/02 Group Group 2 - However, it is applicable only in the sectionalizer mode
("Control Type" setting is SECTIONALIZER).
(+) Sensitive Earth Fault 1 Fault Trip caused by (+) Sensitive Earth Fault 1 (150SG-
168 NO 1 02/02 Group Group 2 -
(150SG-1) Timeout 1) protection element.
(+) Sensitive Earth Fault 2 Fault Trip caused by (+) Sensitive Earth Fault 2 (150SG-
169 NO 1 02/02 Group Group 2 -
(150SG-2) Timeout 2) protection element.
Timeout for Sensitive earth fault indication
Sensitive Earth Fault FI
170 NO 1 02/02 Group Group 2 - However, it is applicable only in the sectionalizer mode
(150SG-3) Timeout
("Control Type" setting is SECTIONALIZER).
(+) Neg Seq Instantaneous Fault Trip caused by (+) Negative Sequence
171 NO 1 02/02 Group Group 2 -
Overcurrent (150Q-1) Timeout Instantaneous Overcurrent (150Q-1) protection element.
(+) Neg Seq Instantaneous Fault Trip caused by (+) Negative Sequence
172 Lockout Overcurrent NO 1 02/02 Group Group 2 - Instantaneous Lockout Overcurrent (150Q-2) protection
(150Q-2) Timeout element.
Timeout for Negative Sequence fault indication
173 Neg Seq FI (150Q-3) Timeout NO 1 02/02 Group Group 2 - However, it is applicable only in the sectionalizer mode
("Control Type" setting is SECTIONALIZER).
(-) Phase Instantaneous Fault Trip caused by (-) Phase Instantaneous Overcurrent
174 NO 1 02/02 Group Group 2 -
Overcurrent (250P-1) Timeout (250P-1) protection element.

ENHANCED TECHNOLOGY 17
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(15/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
(-) Phase Instantaneous Fault Trip caused by (-) Phase Instantaneous Lockout
175 Lockout Overcurrent NO 1 02/02 Group Group 2 - Overcurrent (250P-2) protection element.
(250P-2) Timeout
(-) Ground Instantaneous Fault Trip caused by (+) Phase Instantaneous
176 NO 1 02/02 Group Group 2 -
Overcurrent (250G-1) Timeout Overcurrent (150P-1) protection element.
(-) Ground Instantaneous Fault Trip caused by (-) Ground Instantaneous Lockout
177 Lockout Overcurrent NO 1 02/02 Group Group 2 - Overcurrent (250G-2) protection element.
(250G-2) Timeout
178 Spare NO 1 02/02 Group Group 2 - -
179 Spare NO 1 02/02 Group Group 2 - -
(+) Phase Fast Time Fault Trip caused by (+) Phase Fast Time Overcurrent
180 NO 1 02/02 Group Group 2 -
Overcurrent (151P-1) Timeout (151P-1) protection element.
(+) Phase Delay Time Fault Trip caused by (+) Phase Delay Time Overcurrent
181 NO 1 02/02 Group Group 2 -
Overcurrent (151P-2) Timeout (151P-2) protection element.
(+) Ground Fast Time Fault Trip caused by (+) Ground Fast Time Overcurrent
182 NO 1 02/02 Group Group 2 -
Overcurrent (151G-1) Timeout (151G-1) protection element.
(+) Ground Delay Time Fault Trip caused by (+) Ground Delay Time Overcurrent
183 NO 1 02/02 Group Group 2 -
Overcurrent (151G-2) Timeout (151G-2) protection element.
184 Spare NO 1 02/02 Group Group 2 - -
185 Spare NO 1 02/02 Group Group 2 - -
(+) Neg Seq Fast Time Fault Trip caused by (+) Negative Sequence Fast Time
186 NO 1 02/02 Group Group 2 -
Overcurrent (151Q-1) Timeout Overcurrent (151Q-1) protection element.
(+) Neg Seq Delay Time Fault Trip caused by (+) Negative Sequence Delay Time
187 NO 1 02/02 Group Group 2 -
Overcurrent (151Q-2) Timeout Overcurrent (151Q-2) protection element.
(-) Phase Fast Time Fault Trip caused by (-) Phase Fast Time Overcurrent
188 NO 1 02/02 Group Group 2 -
Overcurrent (251P-1) Timeout (251P-1) protection element.

ENHANCED TECHNOLOGY 18
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(16/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
(-) Ground Fast Time Fault Trip caused by (-) Phase Delay Time Overcurrent
189 NO 1 02/02 Group Group 2 -
Overcurrent (251G-1) Timeout (251P-2) protection element.
(-) Phase Delay Time Fault Trip caused by (-) Ground Fast Time Overcurrent
190 NO 1 02/02 Group Group 2 -
Overcurrent (251P-2) Timeout (251G-1) protection element.
(-) Ground Delay Time Fault Trip caused by (-) Ground Delay Time Overcurrent
191 NO 1 02/02 Group Group 2 -
Overcurrent (251G-2) Timeout (251G-2) protection element.
A-Phase Demand Current Fault Trip caused by A-Phase Demand Current (49D-P)
192 NO 1 02/02 Group Group 2 -
(49D-P) Timeout fault protection element.
B-Phase Demand Current Fault Trip caused by B-Phase Demand Current (49D-P)
193 NO 1 02/02 Group Group 2 -
(49D-P) Timeout fault protection element.
C-Phase Demand Current Fault Trip caused by C-Phase Demand Current (49D-P)
194 NO 1 02/02 Group Group 2 -
(49D-P) Timeout fault protection element.
Ground Demand Current Fault Trip caused by Ground Demand Current (49D-G)
195 NO 1 02/02 Group Group 2 -
(49D-G) Timeout fault protection element.
Neg Seq Demand Current Fault Trip caused by Negative Sequence Demand
196 NO 1 02/02 Group Group 2 -
(49D-Q) Timeout Current (49D-Q) fault protection element.
Active Demand Power Fault Trip caused by Active Demand Power (49D-W)
197 NO 1 02/02 Group Group 2 -
(49D-W) Timeout fault protection element.
Reactive Demand Power Fault Trip caused by Reactive Demand Power (49D-V)
198 NO 1 02/02 Group Group 2 -
(49D-V) Timeout fault protection element.
Direction Power 1 Fault Trip caused by Direction Power 1 (32P-1)
199 NO 1 02/02 Group Group 2 -
(32P-1) Timeout protection element.
Direction Power 2 Fault Trip caused by Direction Power 2 (32P-1)
200 NO 1 02/02 Group Group 2 -
(32P-2) Timeout protection element.
Forward Power 1 Fault Trip caused by Forward Power 1 (32FP-1)
201 NO 1 02/02 Group Group 2 -
(32FP-1) Timeout protection element.

ENHANCED TECHNOLOGY 19
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(17/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Forward Power 2 Fault Trip caused by Forward Power 2 (32FP-2)
202 NO 1 02/02 Group Group 2 -
(32FP-2) Timeout protection element.
203 Power Factor 1 (55-1) Timeout NO 1 02/02 Group Group 2 - Power Factor 1 (55-1) detected
204 Power Factor 2 (55-2) Timeout NO 1 02/02 Group Group 2 - Power Factor 2 (55-2) detected
Broken Conduct Fault Trip caused by Broken Conduct (46BC) protection
205 NO 1 02/02 Group Group 2 -
(46BC) Timeout element.
Alarm occurred by Direction Power 1 (32P-1) or
Direction Power 2 (32P-1) protection element.
206 Direction Power (32P) Alarm NO 1 02/02 Group Group 2 -
If this point is set ('1'), recloser does not perform trip
operation.
Alarm occurred by Forward Power 1 (32FP-1) or
Forward Power 2 (32FP-2) protection element.
207 Forward Power (32FP) Alarm NO 1 02/02 Group Group 2 -
If this point is set ('1'), recloser does not perform trip
operation.
Under Voltage 1 Fault Trip caused by Under Voltage 1 (27-1) protection
208 NO 1 02/02 Group Group 2 -
(27-1) Timeout element.
Under Voltage 2 Fault Trip caused by Under Voltage 2 (27-2) protection
209 NO 1 02/02 Group Group 2 -
(27-2) Timeout element.
Fault Trip caused by Over Voltage 1 (59-1) protection
210 Over Voltage 1 (59-1) Timeout NO 1 02/02 Group Group 2 -
element.
Fault Trip caused by Over Voltage 2 (59-2) protection
211 Over Voltage 2 (59-2) Timeout NO 1 02/02 Group Group 2 -
element.
212 Spare NO 1 02/02 Group Group 2 - -
213 Spare NO 1 02/02 Group Group 2 - -
Neutral Over Voltage 1 Fault Trip caused by Neutral Over Voltage 1 (64N-1)
214 NO 1 02/02 Group Group 2 -
(64N-1) Timeout protection element.

ENHANCED TECHNOLOGY 20
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(18/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Neutral Over Voltage 2 Fault Trip caused by Neutral Over Voltage 2 (64N-2)
215 NO 1 02/02 Group Group 2 -
(64N-2) Timeout protection element.
Negative Sequence Over Fault Trip caused by Negative Sequence Over Voltage 1
216 NO 1 02/02 Group Group 2 -
Voltage 1 (47-1) Timeout (47-1) protection element.
Negative Sequence Over Fault Trip caused by Negative Sequence Over Voltage 2
217 NO 1 02/02 Group Group 2 -
Voltage 2 (47-2) Timeout (47-2) protection element.
218 Load Current Alarm - A NO 1 02/02 Group Group 6 - A phase load current alarm occurred
219 Load Current Alarm - B NO 1 02/02 Group Group 6 - B phase load current alarm occurred
220 Load Current Alarm - C NO 1 02/02 Group Group 6 - C phase load current alarm occurred
221 Load Current Alarm - Ground NO 1 02/02 Group Group 2 - Ground load current alarm occurred
222 Load Current Alarm - Neg Seq NO 1 02/02 Group Group 2 - Negative sequence load current alarm occurred
Under Frequency 1 Fault Trip caused by Under Frequency 1 (81U-1)
223 NO 1 02/02 Group Group 2 -
(81U-1) Timeout protection element.
Under Frequency 2 Fault Trip caused by Under Frequency 2 (81U-2)
224 NO 1 02/02 Group Group 2 -
(81U-2) Timeout protection element.
Over Frequency 1 Fault Trip caused by Over Frequency 1 (81O-1)
225 NO 1 02/02 Group Group 2 -
(81O-1) Timeout protection element.
Over Frequency 2 Fault Trip caused by Over Frequency 2 (81O-2)
226 NO 1 02/02 Group Group 2 -
(81O-2) Timeout protection element.
Frequency Decay 1 Fault Trip caused by Frequency Decay 1 (81D-1)
227 NO 1 02/02 Group Group 2
(81D-1) Timeout protection element.
Frequency Decay 2 Fault Trip caused by Frequency Decay 2 (81D-2)
228 NO 1 02/02 Group Group 2
(81D-2) Timeout protection element.

ENHANCED TECHNOLOGY 21
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(19/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
79 RESET not assert 79 RESET assert
- Either “79 CYCLE” or “79 LOCKOUT” “79 RESET” lamp on panel is ON in case
state. this point is set(„1‟).
229 79 Reset NO 1 02/02 Group Group 6 - This point is cleard(„0‟) by the “OPEN”
operation performed by recloser.
- “79 RESET” lamp on panel is OFF in
case this point is cleard(„0‟).
79 CYCLE not assert 79 CYCLE assert
- Either “79 RESET” or “79 LOCKOUT” “79 CYCLE” lamp on panel is ON in
230 79 Cycle NO 1 02/02 Group Group 6 state. case this point is set(„1‟).
- “79 CYCLE” lamp on panel is OFF in
case this point is cleard(„0‟).
79 LOCKOUT not assert 79 LOCKOUT assert
- Either “79 CYCLE” or “79 RESET” state. This point is set(„1‟) by the “OPEN”
231 79 Lockout NO 1 02/02 Group Group 6 - “79 LOCKOUT” lamp on panel is OFF in operation performed by recloser.
case this point is cleard(„0‟). “79 LOCKOUT” lamp on panel is ON in
case this point is set(„1‟).
Reclosing Shot 0 OFF Reclosing Shot 0 ON
*. This point is always set to set(„1‟)
232 Reclose Sequence 0 NO 1 02/02 Group Group 6
while reclosing functionality is
disable.
233 Reclose Sequence 1 NO 1 02/02 Group Group 6 Reclosing Shot 1 OFF Reclosing Shot 1 ON
234 Reclose Sequence 2 NO 1 02/02 Group Group 6 Reclosing Shot 2 OFF Reclosing Shot 2 ON
235 Reclose Sequence 3 NO 1 02/02 Group Group 6 Reclosing Shot 3 OFF Reclosing Shot 3 ON
236 Reclose Sequence 4 NO 1 02/02 Group Group 6 Reclosing Shot 4 OFF Reclosing Shot 4 ON

ENHANCED TECHNOLOGY 22
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(20/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
This point is cleared(„0‟) by “FI RESET” Recloser closes due to normal frequency
command. recovery in case of trip due to Frequency
Frequency Restoration Under This point always gets cleared („0‟) in protection element.
237 NO 1 02/02 Group Group 2
Latch case the “Auto Restoration Function” However, the “Auto Restoration Function”
setting of the “FREQUENCY” menu is setting in the “FREQUENCY” menu should be
OFF. ON.
Recloser Contact Wear normal. Recloser Contact Wear alarm.
This point always gets cleared („0‟) in This point is set(„1‟) when recloser contact
Breaker Wear Monitor
238 NO 1 02/02 Group Group 2 case the “Function” setting of the wear is less than “Contact Wear Alarm
Detected
“CONTACT WEAR Monitor” menu is Pickup” set value.
OFF.
Source Side Live Line detected
Live Line Timeout :
239 NO 1 02/02 Group Group 5 - Any of the three phases of the designated
Source Voltage
source side is(are) live.
Dead Line Timeout : Source Side Deade Line detected
240 NO 1 02/02 Group Group 2 -
Source Voltage All phases of the source side are dead.
Load Side Live Line detected
Live Line Timeout :
241 NO 1 02/02 Group Group 5 - Any of the three phases of the designated
Load Voltage
load side is(are) live.
Dead Line Timeout : Load Side Dead Line detected
242 NO 1 02/02 Group Group 2 -
Load Voltage All phases of the load side are dead.
Normal time overcurrent operation time Cold Load Pickup duration ON
243 Activate Cold Load Pickup NO 1 02/02 Group Group 2 Time overcurrent pickup level has risen
during this period.
The 2nd harmonic current detected for
244 2nd Harmonic Blocking NO 1 02/02 Group Group 2 -
blocking over current protection
The 5th Harmonic current detected for
245 5Th Harmonic Blocking NO 1 02/02 Group Group 2 -
blocking over current protection

ENHANCED TECHNOLOGY 23
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(21/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Tree-Pole OPEN Timeout not Tree-Pole OPEN Timeout detected
246 Three-Pole Open Timeout NO 1 02/02 Group Group 2 detected If more than 1% of the rated current in case of recloser
open status, this point is set(„1‟).
247 VT Fail Timeout NO 1 02/02 Group Group 2 VT normal VT fail
248 Trip Coil Failure NO 1 02/02 Group Group 2 Trip coil normal Trip coil fail
249 Close Coil Failure NO 1 02/02 Group Group 2 Close ccoil normal Close coil fail
Trip was caused by A phase fault current.
250 Fault Timeout - A NO 1 02/02 Group Group 6 Note 5)
“A FAULT” lamp is ON when this point is set(„1‟).
251 Trip was caused by B phase fault current.
Fault Timeout - B NO 1 02/02 Group Group 6 Note 5)
“B FAULT” lamp is ON when this point is set(„1‟).
Trip was caused by C phase fault current.
252 Fault Timeout - C NO 1 02/02 Group Group 6 Note 5)
“C FAULT” lamp is ON when this point is set(„1‟).
Trip was caused by ground fault current.
253 Fault Timeout - Ground NO 1 02/02 Group Group 6 Note 5) “GROUND” lamp is ON when this point is
set(„1‟).
254 Spare NO 1 02/02 Group Group 2 - -
Fault Timeout - SEF Trip was caused by S.E.F fault current.
255 NO 1 02/02 Group Group 6 Note 5)
“SEF” lamp is ON when this point is set(„1‟).
Fault Timeout - Neg Seq Trip was caused by negative sequence fault
256 NO 1 02/02 Group Group 6 Note 5)
current.
*. NOTE 5) All the points in respect of over current protection can be cleared by doing the following actions;
- [FI RESET] button on the front panel of Entec‟s Recloser Control.
- “FI RESET” command by using remote control.
- When “F/I RESET” is set to “AUTO”, please execute “CLOSE” action
Fault Direction – Fault Direction Forward not assert Fault Direction Forward assert
257 NO 1 02/02 Group Group 2
Forward Fault Direction Forward is “Direction” setting.

ENHANCED TECHNOLOGY 24
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(22/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Fault Direction – Fault Direction Reverse not assert Fault Direction Reverse assert
258 NO 1 02/02 Group Group 2
Reverse Fault Direction Reverse is “Direction” setting.
259 Fault Timeout - Etc NO 1 02/02 Group Group 2 Note 5) Trip was caused by other protection elements
Phase Instantaneous Trip was caused by Phase Instantaneous
260 NO 1 02/02 Group Group 6 -
Overcurrent (50P) Timeout Overcurrent (50P) protection element.
Ground Instantaneous Trip was caused by Ground Instantaneous
261 NO 1 02/02 Group Group 6 -
Overcurrent (50G) Timeout Overcurrent (50G) protection element.
262 Spare NO 1 02/02 Group Group 2 - -
Sesitive Earth Fault Trip was caused by Sesitive Earth Fault
263 NO 1 02/02 Group Group 6 -
(50SG) Timeout (50SG) protection element.
Trip was caused by Negative Sequence
Neg Seq Instantaneous
264 NO 1 02/02 Group Group 6 - Instantaneous Overcurrent (50Q) protection
Overcurrent (50Q) Timeout
element.
Phase Time Overcurrent Trip was caused by Phase Time Overcurrent (51P)
265 NO 1 02/02 Group Group 6 -
(51P) Timeout protection element.
Ground Time Overcurrent Trip was caused by Ground Time Overcurrent
266 NO 1 02/02 Group Group 6 -
(51G) Timeout (51G) protection element.
267 Spare NO 1 02/02 Group Group 2 - -
268 Spare NO 1 02/02 Group Group 2 - -
Neg Seq Time Overcurrent Trip was caused by Negative Sequence Time
269 NO 1 02/02 Group Group 6 -
(51Q) Timeout Overcurrent (51Q) protection element.
Trip was caused by Under Voltage (27) protection
270 Under Voltage (27) Timeout NO 1 02/02 Group Group 6 -
element.
Trip was caused by Over Voltage (59) protection
271 Over Voltage (59) Timeout NO 1 02/02 Group Group 6 -
element.
272 Spare NO 1 02/02 Group Group 2 - -

ENHANCED TECHNOLOGY 25
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(23/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Neutral Over Voltage Trip was caused by Neutral Over Voltage
273 NO 1 02/02 Group Group 2 -
(64N) Timeout (64N) protection element.
Under Frequency Trip was caused by Under Frequency
274 NO 1 02/02 Group Group 6 -
(81U) Timeout (81U) protection element.
Over Frequency Trip was caused by Over Frequency
275 NO 1 02/02 Group Group 6 -
(81O) Timeout (81O) protection element.
Trip was caused by Demand (49D)
276 Demand (49D) Timeout NO 1 02/02 Group Group 6 -
protection element.
Direction Power Trip was caused by Direction Power
277 NO 1 02/02 Group Group 6 -
(32P) Timeout (32P) protection element.
Forward Power Trip was caused by Forward Power
278 NO 1 02/02 Group Group 6 -
(32FP) Timeout (32FP) protection element.
279 Powr Factor (55) Timeout NO 1 02/02 Group Group 2 - Powr Factor (55) element detected
Open Voltage-A phase not detected Open Voltage-A phase detected
This point is cleared(„0‟) under the If A phase voltage is less than “Off
following conditions; Level” set value in case source side is
- A phase voltage is more than “On live line(either one or two phase(s)
280 Open Phase - A NO 1 02/02 Group Group 5 Level” set value.
is(are) more than “On Level”).
- All phases of source voltage are less
“VA” lamp on panel is ON in case this
than “Off Level” set value.
point is set(„1‟).
“VA” lamp on panel is ON in case this point
is cleared(„0‟).
Open Voltage-B phase not detected Open Voltage-B phase detected
This point is cleared(„0‟) under the If B phase voltage is less than “Off
following conditions; Level” set value in case source side is
- B phase voltage is more than “On live line(either one or two phase(s)
281 Open Phase - B NO 1 02/02 Group Group 5 Level” set value.
is(are) more than “On Level”).
- All phases of source voltage are less
“VB” lamp on panel is ON in case this
than “Off Level” set value.
point is set(„1‟).
“VB” lamp on panel is ON in case this point
is cleared(„0‟).

ENHANCED TECHNOLOGY 26
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(24/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Open Voltage-C phase not detected Open Voltage-C phase detected
This point is cleared(„0‟) under the If C phase voltage is less than “Off
following conditions; Level” set value in case source side is
- C phase voltage is more than “On live line(either one or two phase(s)
282 Open Phase - C NO 1 02/02 Group Group 5 Level” set value. is(are) more than “On Level”).
- All phases of source voltage are less “VC” lamp on panel is ON in case this
than “Off Level” set value. point is set(„1‟).
“VC” lamp on panel is ON in case this point
is cleared(„0‟).
Open Voltage-R phase not detected Open Voltage-R phase detected
This point is cleared(„0‟) under the If R phase voltage is less than “Off
following conditions; Level” set value in case load side is live
- R phase voltage is more than “On line(either one or two phase(s) is(are)
283 Open Phase - R NO 1 02/02 Group Group 5 Level” set value. more than “On Level”).
- All phases of load voltage are less than “VR” lamp on panel is ON in case this
“Off Level” set value. point is set(„1‟).
“VR” lamp on panel is ON in case this point
is cleared(„0‟).
Open Voltage-S phase not detected Open Voltage-S phase detected
This point is cleared(„0‟) under the If S phase voltage is less than “Off
following conditions; Level” set value in case load side is live
- S phase voltage is more than “On line(either one or two phase(s) is(are)
284 Open Phase - S NO 1 02/02 Group Group 5 Level” set value. more than “On Level”).
- All phases of load voltage are less than “VS” lamp on panel is ON in case this
“Off Level” set value. point is set(„1‟).
“VS” lamp on panel is ON in case this point
is cleared(„0‟).

ENHANCED TECHNOLOGY 27
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(25/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Open Voltage-T phase not detected Open Voltage-T phase detected
This point is cleared(„0‟) under the If T phase voltage is less than “Off
following conditions; Level” set value in case load side is live
- T phase voltage is more than “On line(either one or two phase(s) is(are)
285 Open Phase - T NO 1 02/02 Group Group 5 Level” set value. more than “On Level”).
- All phases of load voltage are less than “VT” lamp on panel is ON in case this
“Off Level” set value. point is set(„1‟).
“VT” lamp on panel is ON in case this point
is cleared(„0‟).
286 Phase Difference Timeout - A NO 1 02/02 Group Group 5 Phase Difference – A not detected Note 6) Phase Difference – A detected Note 7)
287 Phase Difference Timeout - B NO 1 02/02 Group Group 5 Phase Difference – B not detected Note 6) Phase Difference – B detected Note 7)
288 Phase Difference Timeout - C NO 1 02/02 Group Group 5 Phase Difference – C not detected Note 6) Phase Difference – C detected Note 7)
Phase Difference not detected Note 6) Phase Difference detected Note 7)
289 Phase Difference Timeout NO 1 02/02 Group Group 2 This includes;
Phase Difference A, B or C
*. NOTE 6) Phase Difference is not detected under the following conditions;
- Recloser closed
7) Phase Difference is detected under the following conditions;
- The voltage difference of synchronism voltages is more than “M.V.D” set value.
- The angle difference of synchronism voltages is more than “M.A.D” set value.
- The frequency difference of synchronism voltages is more than “M.F.D” set value.
*. If Phase Difference being detected then it‟s impossible to have recloser do close operation.
Outage Condition Timeout Outage Condition ON For Inrush
290 NO 1 02/02 Group Group 2 -
For Inrush Restraint Restraint Active
291 Inrush Restraint Reset - Phase NO 1 02/02 Group Group 2 - Phase Inrush Restraint Reset
Inrush Restraint Reset – Ground Inrush Restraint Reset
292 NO 1 02/02 Group Group 2 -
Ground

ENHANCED TECHNOLOGY 28
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(26/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
293 Inrush Restraint Reset - S.E.F NO 1 02/02 Group Group 2 - Sensitive Earth Fault Inrush Restraint Reset
Inrush Restraint Reset – Negative Sequence Inrush Restraint Reset
294 NO 1 02/02 Group -
Neg Seq Group 2
Inrush Restraint Phase Inrush Restraint restore duration enterd
295 NO 1 02/02 Group -
Restore Pickup - Phase Group 2
Inrush Restraint Ground Inrush Restraint restore duration enterd
296 NO 1 02/02 Group -
Restore Pickup - Ground Group 2
Inrush Restraint Negative Sequence Inrush Restraint restore duration
297 NO 1 02/02 Group -
Restore Pickup - Neg Seq Group 2 enterd
Inrush Restraint Sensitive Earth Fault Inrush Restraint restore
298 NO 1 02/02 Group -
Restore Pickup - S.E.F Group 2 duration enterd
Activate Inrush Restraint For Phase Time Overcurrent Trip during Inrush Restraint
299 NO 1 02/02 Group
Phase Time Overcurrent Group 6 Restore Duration
Activate Inrush Restraint For Ground Time Overcurrent Trip during Inrush
300 NO 1 02/02 Group
Ground Time Overcurrent Group 6 Restraint Restore Duration
Activate Inrush Restraint For Sensitive Earth Fault Trip during Inrush Restraint
301 NO 1 02/02 Group
S.E.F Time Overcurrent Group 6 Restore Duration
Activate Inrush Restraint For Negative Sequence Overcurrent Trip during Inrush
302 NO 1 02/02 Group
Neg Seq Time Overcurrent Group 6 Restraint Restore Duration
303 Pq Under Volt Timeout - A NO 1 02/02 Group Group 8 Note 8) Under Voltage A-PQ detected
304 Pq Under Volt Timeout - B NO 1 02/02 Group Group 8 Note 8) Under Voltage B-PQ detected
305 Pq Under Volt Timeout - C NO 1 02/02 Group Group 8 Note 8) Under Voltage C-PQ detected
306 Pq Under Volt Timeout - R NO 1 02/02 Group Group 8 Note 8) Under Voltage R-PQ detected
307 Pq Under Volt Timeout - S NO 1 02/02 Group Group 8 Note 8) Under Voltage S-PQ detected
308 Pq Under Volt Timeout - T NO 1 02/02 Group Group 8 Note 8) Under Voltage T-PQ detected

ENHANCED TECHNOLOGY 29
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(27/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
309 Pq Over Volt Timeout - A NO 1 02/02 Group Group 8 Note 8) Over Voltage A-PQ detected
310 Pq Over Volt Timeout - B NO 1 02/02 Group Group 8 Note 8) Over Voltage B-PQ detected
311 Pq Over Volt Timeout - C NO 1 02/02 Group Group 8 Note 8) Over Voltage C-PQ detected
312 Pq Over Volt Timeout - R NO 1 02/02 Group Group 8 Note 8) Over Voltage R-PQ detected
313 Pq Over Volt Timeout - S NO 1 02/02 Group Group 8 Note 8) Over Voltage S-PQ detected
314 Pq Over Volt Timeout - T NO 1 02/02 Group Group 8 Note 8) Over Voltage T-PQ detected
315 Sag Timeout - A NO 1 02/02 Group Group 8 Note 8) Sag A detected
316 Sag Timeout - B NO 1 02/02 Group Group 8 Note 8) Sag B detected
317 Sag Timeout - C NO 1 02/02 Group Group 8 Note 8) Sag C detected
318 Sag Timeout - P NO 1 02/02 Group Group 2 Note 8) Sag A, B or C detected
319 Swell Timeout - A NO 1 02/02 Group Group 8 Note 8) Swell A detected
320 Swell Timeout - B NO 1 02/02 Group Group 8 Note 8) Swell B detected
321 Swell Timeout - C NO 1 02/02 Group Group 8 Note 8) Swell C detected
322 Swell Timeout - P NO 1 02/02 Group Group 2 Note 8) Swell A, B or C detected
323 Interruption Timeout - A NO 1 02/02 Group Group 8 Note 8) Interruption A detected
324 Interruption Timeout - B NO 1 02/02 Group Group 8 Note 8) Interruption B detected
325 Interruption Timeout - C NO 1 02/02 Group Group 8 Note 8) Interruption C detected
326 Interruption Timeout - P NO 1 02/02 Group Group 2 Note 8) Interruption A, B or C detected
Unbalance Timeout –
327 NO 1 02/02 Group Group 8 Note 8) Voltage Unbalance (Source) detected
Source Voltage
Unbalance Timeout –
328 NO 1 02/02 Group Group 8 Note 8) Voltage Unbalance (Load) detected
Load Voltage
329 Unbalance Timeout - Current NO 1 02/02 Group Group 8 Note 8), 9) Current Unbalance detected

ENHANCED TECHNOLOGY 30
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(28/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
330 Pq Under Frequency Timeout NO 1 02/02 Group Group 8 Note 8) Under Frequency-PQ detected
331 Sag Instantaneous Occured NO 1 02/02 Group Group 2 Note 8) Sag Instantaneous detected Note 10)
332 Sag Momentary Occured NO 1 02/02 Group Group 2 Note 8) Sag Momentary detected Note 10)
333 Sag Temporary Occured NO 1 02/02 Group Group 2 Note 8) Sag Temporary detected Note 10)
334 Sag Long Time Occured NO 1 02/02 Group Group 2 Note 8) Sag Longtime detected Note 10)
335 Swell Instantaneous Occured NO 1 02/02 Group Group 2 Note 8) Swell Instantaneous detected Note 10)
336 Swell Momentary Occured NO 1 02/02 Group Group 2 Note 8) Swell Momentary detected Note 10)
337 Swell Temporary Occured NO 1 02/02 Group Group 2 Note 8) Swell Temporary detected Note 10)
338 Swell Long Time Occured NO 1 02/02 Group Group 2 Note 8) Swell Longtime detected Note 10)
Interruption Momentary
339 NO 1 02/02 Group Group 2 Note 8) Interruption Momentary detected Note 10)
Occured
Interruption Temporary
340 NO 1 02/02 Group Group 2 Note 8) Interruption Temporary detected Note 10)
Occured
Interruption Long Time
341 NO 1 02/02 Group Group 2 Note 8) Interruption Longtime detected Note 10)
Occured
342 Voltage Thd Timeout - A NO 1 02/02 Group Group 8 Note 8) Voltage THD A detected
343 Voltage Thd Timeout - B NO 1 02/02 Group Group 8 Note 8) Voltage THD B detected
344 Voltage Thd Timeout - C NO 1 02/02 Group Group 8 Note 8) Voltage THD C detected
Voltage THD detected
345 Voltage Thd Timeout - T NO 1 02/02 Group Group 2 Note 8) This includes;
- Voltage THD A/B/C detected
346 Current Thd Timeout - A NO 1 02/02 Group Group 8 Note 8), 9) Current THD A detected
347 Current Thd Timeout - B NO 1 02/02 Group Group 8 Note 8), 9) Current THD B detected
348 Current Thd Timeout - C NO 1 02/02 Group Group 8 Note 8), 9) Current THD C detected

ENHANCED TECHNOLOGY 31
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(29/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Current THD detected
349 Current Thd Timeout - T NO 1 02/02 Group Group 2 Note 8), 9) This includes;
Current THD A/B/C detected
*. NOTE 8) All the points related to PQM function can be cleared(„0‟) by “PQM Transient Short duration Long duration
RESET” command.
Instant Moment Temporary
9) If current is less than “ITHD/UBI I Limit” set value, the current
Swell Over voltage
unbalance and current harmonic distortion element is not detected. 1.1 pu
10) PQM functions follows IEEE 1159 standard. IEEE 1159 standard
determines under categorizing into several groups depending on 1.0 pu Normal Range

electric fluctuation depending on size and continuous time. Voltage 0.9 pu

fluctuation and its categories are as shown in “Ficture 2. IEEE 1159 Sag Under voltage
Voltage distortion summary”.
0.1 pu
Interruption

30cycle 3sec
0.5cycle 1min

Figure 2. IEEE 1159 Voltage distortion summary


350 DC1-1 Timeout NO 1 02/02 Group Group 2 - DC1-1 detected
351 DC1-2 Timeout NO 1 02/02 Group Group 2 - DC1-2 detected
352 DC2-1 Timeout NO 1 02/02 Group Group 2 - DC2-1 detected
353 DC2-2 Timeout NO 1 02/02 Group Group 2 - DC2-2 detected
354 DC3-1 Timeout NO 1 02/02 Group Group 2 - DC3-1 detected
355 DC3-2 Timeout NO 1 02/02 Group Group 2 - DC3-2 detected
356 DC4-1 Timeout NO 1 02/02 Group Group 2 - DC4-1 detected
357 DC4-2 Timeout NO 1 02/02 Group Group 2 - DC4-2 detected

ENHANCED TECHNOLOGY 32
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(30/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
358 External DC1-1 Timeout NO 1 02/02 Group Group 2 - External DC1-1 detected
359 External DC1-2 Timeout NO 1 02/02 Group Group 2 - External DC1-2 detected
360 External DC2-1 Timeout NO 1 02/02 Group Group 2 - External DC2-1 detected
361 External DC2-2 Timeout NO 1 02/02 Group Group 2 - External DC2-2 detected
362 External DC3-1 Timeout NO 1 02/02 Group Group 2 - External DC3-1 detected
363 External DC3-2 Timeout NO 1 02/02 Group Group 2 - External DC3-2 detected
364 External DC4-1 Timeout NO 1 02/02 Group Group 2 - External DC4-1 detected
365 External DC4-2 Timeout NO 1 02/02 Group Group 2 - External DC4-2 detected
Phase Time Overcurrent Phase Time Overcurrent (51P) Alarm occur
366 NO 1 02/02 Group Group 7 -
(51P) Alarm occurred.
Ground Time Overcurrent Ground Time Overcurrent (51G) Alarm
367 NO 1 02/02 Group Group 7 -
(51G) Alarm occurred.
Neutral Time Overcurrent Neutral Time Overcurrent (51N) Alarm
368 NO 1 02/02 Group Group 2 -
(51N) Alarm occurred.
Sesitive Earth Fault Sesitive Earth Fault Time Overcurrent (51SG)
369 Time Overcurrent NO 1 02/02 Group Group 2 - Alarm occurred.
(51SG) ALARM
Neg Seq Time Overcurrent Negative Sequence Time Overcurrent (51Q)
370 NO 1 02/02 Group Group 7 -
(51Q) Alarm Alarm occurred.
371 Under Voltage (27) Alarm NO 1 02/02 Group Group 7 - Under Voltage (27) Alarm occurred
372 Over Voltage (59) Alarm NO 1 02/02 Group Group 7 - Over Voltage (59) Alarm occurred
Neutral Over Voltage Neutral Over Voltage (64N) Alarm occurred
373 NO 1 02/02 Group Group 7 -
(64N) Alarm

ENHANCED TECHNOLOGY 33
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(31/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Loop control type is not sectionalizing Loop control type is sectionalizing recloser.
374 Selected Sec Recloser NO 1 02/02 Group Group 2 recloser. The “Type Select” setting of “LOOP
CONTROL” menu has been set as “SEC”.
Loop control type is not midpoint Loop control type is midpoint recloser.
375 Selected Mid Recloser NO 1 02/02 Group Group 2 recloser. The “Type Select” setting of “LOOP
CONTROL” menu has been set as “MID”.
Loop control type is not tie point Loop control type is tie point recloser.
376 Selected Tie Recloser NO 1 02/02 Group Group 2 recloser. The “Type Select” setting of “LOOP
CONTROL” menu has been set as “TIE”.
It does not get detected in the The Sectionalizing recloser has automatically
following condition; returned after the Sectionalizing recloser
- Sectionalizing recloser did not operation because the line voltage was
operate (line voltage is normal) normally restored.
377 Section Reset NO 1 02/02 Group Group 2 - The Sectionalizing recloser is
operating because the Line voltage
has not returned to normal
condition.
It is not set as Sectionalizing recloser.
It does not get detected in the The Tiepoint recloser has automatically
following condition; returned after the Tiepoint recloser operation
- Tiepoint recloser did not operate because the line voltage was normally restored.
(line voltage is normal)
378 Tie Reset NO 1 02/02 Group Group 2
- The Tiepoint recloser is operating
because the Line voltage has not
returned to normal condition.
It is not set as Tiepoint recloser.
The recloser has been automatically open or
379 Section Operate Indicator NO 1 02/02 Group Group 2 -
close due to the Section function.

ENHANCED TECHNOLOGY 34
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(32/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
The recloser has been automatically open due
380 Section Open Indicator NO 1 02/02 Group Group 2 -
to the Section function.
The recloser has been automatically close due
381 Tie Close Indicator NO 1 02/02 Group Group 2 -
to the Tie Type function.
The recloser has been automatically open due
382 Tie Open Indicator NO 1 02/02 Group Group 2 -
to the Tie Type function.
Power Flow Forward not assert Power Flow Forward assert
383 Forware Power Flow NO 1 02/02 Group Group 2 Forward Power is determined by 3-phase
power factor.
Power Flow Reverse not assert Power Flow Reverse assert
Reverse Power is determined by 3-phase power
384 Reverse Power Flow NO 1 02/02 Group Group 2 factor.
“REVERSE POWER” lamp in panel is ON
when this point is set(„1‟).
- Trip was caused by Z0 Admittance (21YN)
385 Z0 Admittance (21YN) Timeout NO 1 02/02 Group Group 6
protection element.
386 Multi-Bit A Communication OK NO 1 02/02 Group Group 10 Note 11) Multi-Bit A protocol communication normal
Multi-Bit A Communication Link Error occurred in Multi-Bit A protocol
387 NO 1 02/02 Group Group 10 Note 11) communication
Link Error
Multi-Bit A Communication Receive Error occurred in Multi-Bit A
388 NO 1 02/02 Group Group 10 Note 11) protocol communication
Receive Error
Multi-Bit A Communication CRC Error occurred in Multi-Bit A protocol
389 NO 1 02/02 Group Group 10 Note 11) communication
CRC Check Error
Multi-Bit A Communication ID ID Error occurred in Multi-Bit A protocol
390 NO 1 02/02 Group Group 4 Note 11) communication
Error
*. NOTE 11) If Multi-Bit A protocol communication is OFF (“Function” set is “DISABLE”), these points are always cleared(„0‟).

ENHANCED TECHNOLOGY 35
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(33/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
391 Receive Multi-Bit 01 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 01 - A not assert Receive Multi-Bit 01 - A assert
392 Receive Multi-Bit 02 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 02 - A not assert Receive Multi-Bit 02 - A assert
393 Receive Multi-Bit 03 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 03 - A not assert Receive Multi-Bit 03 - A assert
394 Receive Multi-Bit 04 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 04 - A not assert Receive Multi-Bit 04 - A assert
395 Receive Multi-Bit 05 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 05 - A not assert Receive Multi-Bit 05 - A assert
396 Receive Multi-Bit 06 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 06 - A not assert Receive Multi-Bit 06 - A assert
397 Receive Multi-Bit 07 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 07 - A not assert Receive Multi-Bit 07 - A assert
398 Receive Multi-Bit 08 - A NO 1 02/02 Group Group 4 Receive Multi-Bit 08 - A not assert Receive Multi-Bit 08 - A assert
399 Transmit Multi-Bit 01 - A *.Note 12) NO 1 02/02 Group Group 4 Transmit Multi-Bit 01 - A not assert Transmit Multi-Bit 01 - A assert
*.Note 12)
400 Transmit Multi-Bit 02 - A NO 1 02/02 Group Group 4 Transmit Multi-Bit 02 - A not assert Transmit Multi-Bit 02 - A assert
*.Note 12)
401 Transmit Multi-Bit 03 - A NO 1 02/02 Group Group 4 Transmit Multi-Bit 03 - A not assert Transmit Multi-Bit 03 - A assert
*.Note 12)
402 Transmit Multi-Bit 04 - A NO 1 02/02 Group Group 4 Transmit Multi-Bit 04 - A not assert Transmit Multi-Bit 04 - A assert
403 Transmit Multi-Bit 05 - A *.Note 12) NO 1 02/02 Group Group 4 Transmit Multi-Bit 05 - A not assert Transmit Multi-Bit 05 - A assert
404 Transmit Multi-Bit 06 - A *.Note 12) NO 1 02/02 Group Group 4 Transmit Multi-Bit 06 - A not assert Transmit Multi-Bit 06 - A assert
*.Note 12)
405 Transmit Multi-Bit 07 - A NO 1 02/02 Group Group 4 Transmit Multi-Bit 07 - A not assert Transmit Multi-Bit 07 - A assert
*.Note 12)
406 Transmit Multi-Bit 08 - A NO 1 02/02 Group Group 4 Transmit Multi-Bit 08 - A not assert Transmit Multi-Bit 08 - A assert
*. NOTE 12) Status can be mapped by Transmit Multi-Bit available in the PLC settings of ETIMS Interface Software.
Multi-Bit B protocol communication
407 Multi-Bit B Communication OK NO 1 02/02 Group Group 10 Note 13)
normal
Multi-Bit B Communication Link Link Error occurred in Multi-Bit B
408 NO 1 02/02 Group Group 10 Note 13) protocol communication
Error
Multi-Bit B Communication Receive Error occurred in Multi-Bit B
409 NO 1 02/02 Group Group 10 Note 13) protocol communication
Receive Error

ENHANCED TECHNOLOGY 36
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(34/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Multi-Bit B Communication CRC CRC Error occurred in Multi-Bit B
410 NO 1 02/02 Group Group 10 Note 13) protocol communication
Check Error
Multi-Bit B Communication ID ID Error occurred in Multi-Bit B
411 NO 1 02/02 Group Group 10 Note 13) protocol communication
Error
*. NOTE 13) If Multi-Bit A protocol communication is OFF (“Function” set is “DISABLE”), these points are always cleared(„0‟).
412 Receive Multi-Bit 01 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 01 - B not assert Receive Multi-Bit 01 - B assert
413 Receive Multi-Bit 02 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 02 - B not assert Receive Multi-Bit 02 - B assert
414 Receive Multi-Bit 03 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 03 - B not assert Receive Multi-Bit 03 - B assert
415 Receive Multi-Bit 04 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 04 - B not assert Receive Multi-Bit 04 - B assert
416 Receive Multi-Bit 05 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 05 - B not assert Receive Multi-Bit 05 - B assert
417 Receive Multi-Bit 06 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 06 - B not assert Receive Multi-Bit 06 - B assert
418 Receive Multi-Bit 07 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 07 - B not assert Receive Multi-Bit 07 - B assert
419 Receive Multi-Bit 08 - B NO 1 02/02 Group Group 4 Receive Multi-Bit 08 - B not assert Receive Multi-Bit 08 - B assert
*.Note 12)
420 Transmit Multi-Bit 01 - B NO 1 02/02 Group Group 4 Transmit Multi-Bit 01 - B not assert Transmit Multi-Bit 01 - B assert
*.Note 12)
421 Transmit Multi-Bit 02 - B NO 1 02/02 Group Group 4 Transmit Multi-Bit 02 - B not assert Transmit Multi-Bit 02 - B assert
*.Note 12)
422 Transmit Multi-Bit 03 - B NO 1 02/02 Group Group 4 Transmit Multi-Bit 03 - B not assert Transmit Multi-Bit 03 - B assert
423 Transmit Multi-Bit 04 - B *.Note 12) NO 1 02/02 Group Group 4 Transmit Multi-Bit 04 - B not assert Transmit Multi-Bit 04 - B assert
*.Note 12)
424 Transmit Multi-Bit 05 - B NO 1 02/02 Group Group 4 Transmit Multi-Bit 05 - B not assert Transmit Multi-Bit 05 - B assert
*.Note 12)
425 Transmit Multi-Bit 06 - B NO 1 02/02 Group Group 4 Transmit Multi-Bit 06 - B not assert Transmit Multi-Bit 06 - B assert
*.Note 12)
426 Transmit Multi-Bit 07 - B NO 1 02/02 Group Group 4 Transmit Multi-Bit 07 - B not assert Transmit Multi-Bit 07 - B assert
*.Note 12)
427 Transmit Multi-Bit 08 - B NO 1 02/02 Group Group 4 Transmit Multi-Bit 08 - B not assert Transmit Multi-Bit 08 - B assert
Trip was caused by Neg Seq‟ Over
428 Neg Seq‟ Over Volate (47) Timeout NO 1 02/02 Group Group 2 -
Volate (47) protection element.

ENHANCED TECHNOLOGY 37
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(35/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
429 Neg Seq‟ Over Volate (47) Alarm NO 1 02/02 Group Group 2 - Neg Seq‟ Over Volate (47) Alarm occurred
430 Under Frequency 1 (81U-1) Alarm NO 1 02/02 Group Group 2 - Under Frequency 1 (81U-1) Alarm occurred
431 Under Frequency 2 (81U-2) Alarm NO 1 02/02 Group Group 2 - Under Frequency 2 (81U-2) Alarm occurred
432 Under Frequency (81U) Alarm NO 1 02/02 Group Group 2 - Under Frequency (81U) Alarm occurred
433 Over Frequency 1 (81O-1) Alarm NO 1 02/02 Group Group 2 - Over Frequency 1 (81O-1) Alarm occurred
434 Over Frequency 2 (81O-2) Alarm NO 1 02/02 Group Group 2 - Over Frequency 2 (81O-2) Alarm occurred
435 Over Frequency (81O) Alarm NO 1 02/02 Group Group 2 - Over Frequency (81O) Alarm occurred
436 Frequency Decay 1 (81D-1) Alarm NO 1 02/02 Group Group 2 - Frequency Decay 1 (81D-1) Alarm occurred
A-Phase Demand Current (49D-P) A-Phase Demand Current (49D-P) Alarm
437 NO 1 02/02 Group Group 2 -
Alarm occurred
B-Phase Demand Current (49D-P) B-Phase Demand Current (49D-P) Alarm
438 NO 1 02/02 Group Group 2 -
Alarm occurred
C-Phase Demand Current (49D-P) C-Phase Demand Current (49D-P) Alarm
439 NO 1 02/02 Group Group 2 -
Alarm occurred
Ground Demand Current (49D-G) Ground Demand Current (49D-G) Alarm
440 NO 1 02/02 Group Group 2 -
Alarm occurred
Neg Seq‟ Demand Current (49D-Q) Neg Seq‟ Demand Current (49D-Q) Alarm
441 NO 1 02/02 Group Group 2 -
Alarm occurred
Active Demand Power (49D-W)
442 NO 1 02/02 Group Group 2 - Active Demand Power (49D-W) Alarm occurred
Alarm
Reactive Demand Power (49D-V) Reactive Demand Power (49D-V) Alarm
443 NO 1 02/02 Group Group 2 -
Alarm occurred
444 Demand (49D) Alarm NO 1 02/02 Group Group 2 - Demand (49D) Alarm occurred
445 Z0 Admittance (21YN) Alarm NO 1 02/02 Group Group 2 - Z0 Admittance (21YN) Alarm occurred
446 Broken Conduct (46BC) Alarm NO 1 02/02 Group Group 2 - Broken Conduct (46BC) Alarm occurred

ENHANCED TECHNOLOGY 38
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 1. BASE DATA POINTS – BINARY INPUT(36/36)


IEC Mask Status
No Description Invert Class Var
A B Cleared = ‘0’ Set = ‘1’
Battery Voltage Alarm not Battery Voltage Alarm detected.
detected. - Battery Volt. ≥ Alarm level in case of Over
; If Battery Voltage Alarm is
447 NO 1 02/02 Group Group 2 Type
OFF (“Bat. Alarm LV” set is
- Or, Battery Volt. ≤ Alarm level in case of
“OFF” in Batt. Management
Battery Voltage Alarm menu), Under Type

*. NOTE ) Supported points may be different according to the option and version of controller.

ENHANCED TECHNOLOGY 39
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

2. Binary Output

Click “Binary Single Output” or “Binary Double Output” Tap in the bottom of the “DB MAP
CONFIGURATION” window to move to Binary Output Map. The properties of Invert, Control
Type and Index 60870 can be individually set in the “User Map List” per each data point. The
property can be changed by clicking the corresponding property column (indicate the combo box)
when the data point to be changed is selected (indicate with a blue line).
The property setting items are as follows.

 Invert : It is used to invert a value of corresponding data point.


- NONE(NO) : Invert does not apply. It transmits “1” as the command value in case of
“CLOSE” controlling and “0” as the command value in case of “TRIP” controlling.
- OK(YES) : Invert is applied. The actual transmitted command value is “TRIP(„0‟)” when
“CLOSE(„1‟)” is controlling.
 Control Type : It is to set the control type of corresponding data point in DNP3.0
communication.
- SBO : “Select before operate” control type support
- DO : “Direct operate” control type support
- SBO&DO : both “Select before operate” and “Direct operate” control types support
- NONE : no control support using data point
 Index 60870 : It is to set the object address to read to corresponding data point in IEC60870
communication.

The Control Type setting value is useful properties in the DNP3.0 communication and the
Index 60870 setting value is a useful property in the IEC60870 communication.
As optional functions, the DNP3.0 communication and IEC60870 communication will not
cause any influence if the Entec‟s Recloser Control does not support these functions.

The Binary output‟s base data points are as follows. However, upported points may be different
according to the option and version of controller;

40 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 2. BASE DATA POINTS – BINARY OUTPUT(1/2)


Code TR/CL
No Description Invert Block Condition
Field Field

CLOSE Command NO Pulse ON CLOSE Control Locked, Remote Disabled


0
OPEN Command NO Pulse ON TRIP Control Locked, Remote Disabled

1 OPEN Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Protection Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled


2
Protection Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

3 Protection Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Protection Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled


4
Protection Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

5 Protection Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

SEF Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled


6
SEF Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

7 SEF Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Reclosing Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled


8
Reclosing Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

9 Reclosing Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Control Lock Command NO Pulse ON CLOSE Remote Disabled


10
Control Unlock Command NO Pulse ON TRIP Remote Disabled

11 Control Unlock Command NO Pulse ON CLOSE Remote Disabled

Loop Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled


12
Loop Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

13 Loop Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Loop Auto Restore Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled
14
Loop Auto Restore Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

15 Loop Auto Restore Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Hot Line Tag Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled
16
Hot Line Tag Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

17 Hot Line Tag Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Aux1 Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled


18
Aux1 Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

19 Aux1 Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

Aux 2 Enable Command NO Pulse ON CLOSE Control Locked, Remote Disabled


20
Aux2 Disable Command NO Pulse ON TRIP Control Locked, Remote Disabled

ENHANCED TECHNOLOGY 41
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 2. BASE DATA POINTS – BINARY OUTPUT(2/2)


Code TR/CL
No Description Invert Block Condition
Field Field

21 Aux2 Disable Command NO Pulse ON CLOSE Control Locked, Remote Disabled

22 Battery Test Command NO Pulse ON CLOSE

23 FI Reset Command NO Pulse ON CLOSE

24 Spare NO Pulse ON CLOSE

25 PQ Event Reset Command NO Pulse ON CLOSE

26 PQ Count Initialize Command NO Pulse ON CLOSE

27 PQ Interruption Time Initialize Command NO Pulse ON CLOSE

28 Max Demand Clear Command NO Pulse ON CLOSE

29 Energy Clear Command NO Pulse ON CLOSE

30 Waveform Capture Command NO Pulse ON TRIP

31 Peak Current Clear Command NO Pulse ON CLOSE

32 Spare NO Pulse ON CLOSE

33 Spare NO Pulse ON TRIP

34 Set Group 1 Command NO Pulse ON CLOSE

35 Set Group 2 Command NO Pulse ON CLOSE

36 Set Group 3 Command NO Pulse ON TRIP

37 Set Group 4 Command NO Pulse ON CLOSE

38 Set Group 5 Command NO Pulse ON CLOSE

39 Set Group 6 Command NO Pulse ON TRIP

40 Spare NO Pulse ON CLOSE

*. NOTE )
1. The value(TR/CL Field) of all BO Points can be inverted with PLC setting of ETIMS Interface software.
2. The BO points above apply in default PLC setting. In case of changes to PLC setting, the block
condition of BO points may change.
− BDO#C (#: point number) : The block condition for close command of BO points can be set.
− BDO#T (#: point number) : The block condition for trip command of BO points can be set.
3. Supported points may be different according to the option and version of controller.

42 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

3. Counters

Click “Counters” Tap in the bottom of the “DB MAP CONFIGURATION” window to move to
Counters Map. The properties of Inver, Class, Var, IEC Mask A and more can be individually set in
the “User Map List” per each data point. The property can be changed by clicking the
corresponding property column (indicate the combo box) when the data point to be changed is
selected (indicate with a blue line).
The property setting items are as follows.

 Class : It is to set a class that is related with event occurring of DNP3.0 communication.
 Var : It is to set Object/Variation to read corresponding data point in DNP3.0 communication.
- 22/01 : 32 bit Change with flag
- 22/02 : 16 bit Change with flag
- 22/05 : 32 bit Change with flag and time
- 22/06 : 16 bit Change with flag and time
- 22/08 : 16 bit Delta Change with time-tag
 IEC Mask A : It is to set IEC60870 communication use, Fixed as Group(included in group),
Cyclic(Periodical polling), Group&Cyclic set options. In addition, if the Class attribute is
allocated to Class1, 2 or 3, it will have the Spontaneous point attribute in case of IEC60870
communication.
 IEC Mask B : It is to set a group on IEC60870 communication use. Please refer to
“IEC60870-5-101/104 PROTOCOL Technical Manual” for more detail information.
 Active Event : It sets whether a Counter event will occur or not.
- None : Regardless of the setting, it does not make a Counter event occur.
- Active : Makes a Counter event happen according to the class attribute. If the Class is set
as “None” or “Class 0”, it does not allow an event to occur.
*. NOTE ) Count event is generated when the value of the Counter's data is changed
(increased or reset to be "0").
 Frozen Counter : It sets whether to used a Frozen counter value and event.
- None : Regardless of the setting, it does not used a Frozen counter value and event.
- Active : Use to a frozen counter value and event.
- Clear after local freeze : Counter is reset after the freeze by itself.
 Index 60870 : It is to set the object address to read to corresponding data point in IEC60870
communication.

ENHANCED TECHNOLOGY 43
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

The Class & Var setting value are useful properties in the DNP3.0 communication and the
IEC Mask A/B & Index 60870 setting value are a useful property in the IEC60870
communication.
As optional functions, the DNP3.0 communication and IEC60870 communication function
will not cause any influence if the Entec‟s Recloser Control does not support these functions.

The Counter‟s data points are as follows;

Table 3. BASE DATA POINTS – COUNTERS(1/5)


IEC Mask Active Frozen
No Description Class Var
A B Event Counter

0 Restart Count Class 0 22/02 Group Group 1 NONE NONE

1 Diagnosis Count Class 0 22/02 Group Group 1 NONE NONE

2 Sag Count - Total Class 0 22/02 Group Group 1 NONE NONE

3 Sag Count - A Class 0 22/02 Group Group 1 NONE NONE

4 Sag Count - B Class 0 22/02 Group Group 1 NONE NONE

5 Sag Count - C Class 0 22/02 Group Group 1 NONE NONE

6 Sag Count - Instantaneous Class 0 22/02 Group Group 1 NONE NONE

7 Sag Count - Momentary Class 0 22/02 Group Group 1 NONE NONE

8 Sag Count - Temporary Class 0 22/02 Group Group 1 NONE NONE

9 Sag Count - Long Time Class 0 22/02 Group Group 1 NONE NONE

10 Swell Count - Total Class 0 22/02 Group Group 1 NONE NONE

11 Swell Count - A Class 0 22/02 Group Group 1 NONE NONE

12 Swell Count - B Class 0 22/02 Group Group 1 NONE NONE

13 Swell Count - C Class 0 22/02 Group Group 1 NONE NONE

14 Swell Count - Instantaneous Class 0 22/02 Group Group 1 NONE NONE

15 Swell Count - Momentary Class 0 22/02 Group Group 1 NONE NONE

16 Swell Count - Temporary Class 0 22/02 Group Group 1 NONE NONE

17 Swell Count - Long Time Class 0 22/02 Group Group 1 NONE NONE

18 Interruption CumulativeTime [sec]-Total Class 0 22/02 Group Group 1 NONE NONE

19 Interruption CumulativeTime [sec]-A Class 0 22/02 Group Group 1 NONE NONE

20 Interruption CumulativeTime [sec]- B Class 0 22/02 Group Group 1 NONE NONE

21 Interruption CumulativeTime [sec]- C Class 0 22/02 Group Group 1 NONE NONE

22 Interruption CumulativeTime [sec]- Momentary Class 0 22/02 Group Group 1 NONE NONE

23 Interruption CumulativeTime [sec]-Temporary Class 0 22/02 Group Group 1 NONE NONE

44 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 3. BASE DATA POINTS – COUNTERS(2/5)


IEC Mask Active Frozen
No Description Class Var
A B Event Counter

24 Interruption CumulativeTime [sec] -Sustained Class 0 22/02 Group Group 1 NONE NONE

25 Voltage THD - Total Class 0 22/02 Group Group 1 NONE NONE

26 Current THD - Total Class 0 22/02 Group Group 1 NONE NONE

27 Voltage THD - A Class 0 22/02 Group Group 1 NONE NONE


28~
Spare - - - - - -
41
42 Voltage B THD Class 0 22/02 Group Group 1 NONE NONE
43~
Spare - - - - - -
56

57 Voltage C THD Class 0 22/02 Group Group 1 NONE NONE


58~
Spare - - - - - -
71
72 Current A THD Class 0 22/02 Group Group 1 NONE NONE
73~
Spare - - - - - -
86
87 Current B THD Class 0 22/02 Group Group 1 NONE NONE
88~
Spare - - - - - -
101
102 Current C THD Class 0 22/02 Group Group 1 NONE NONE
103~
Spare - - - - - -
116
117 Current G THD Class 0 22/02 Group Group 1 NONE NONE

118 Current Unbalance Detect Class 0 22/02 Group Group 1 NONE NONE

119 Voltage Unbalance Detect (Source) Class 0 22/02 Group Group 1 NONE NONE

120 Voltage Unbalance Detect (Load) Class 0 22/02 Group Group 1 NONE NONE

121 Under Frequency Detect Class 0 22/02 Group Group 1 NONE NONE

122 Under voltage TOTAL(Source) Class 0 22/02 Group Group 1 NONE NONE

123 Under voltage A(Source) Class 0 22/02 Group Group 1 NONE NONE

124 Under voltage B(Source) Class 0 22/02 Group Group 1 NONE NONE

125 Under voltage C(Source) Class 0 22/02 Group Group 1 NONE NONE

126 Over voltage TOTAL(Source) Class 0 22/02 Group Group 1 NONE NONE

127 Over voltage A(Source) Class 0 22/02 Group Group 1 NONE NONE

128 Over voltage B(Source) Class 0 22/02 Group Group 1 NONE NONE

129 Over voltage C(Source) Class 0 22/02 Group Group 1 NONE NONE

130 Operation Class 0 22/02 Group Group 1 NONE NONE

131 Trip Class 0 22/02 Group Group 1 NONE NONE

ENHANCED TECHNOLOGY 45
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 3. BASE DATA POINTS – COUNTERS(3/5)


IEC Mask Active Frozen
No Description Class Var
A B Event Counter

132 Interruption Total Cumulitive Time Class 0 22/02 Group Group 1 NONE NONE

133 Interruption Cumulitive Time A Class 0 22/02 Group Group 1 NONE NONE

134 Interruption Cumulitive Time B Class 0 22/02 Group Group 1 NONE NONE

135 Interruption Cumulitive Time C Class 0 22/02 Group Group 1 NONE NONE
INTERRUPTION Momentary
136 Class 0 22/02 Group Group 1 NONE NONE
Cumulitive Time
INTERRUPTION Temporary
137 Class 0 22/02 Group Group 1 NONE NONE
Cumulitive Time
INTERRUPTION Sustained
138 Class 0 22/02 Group Group 1 NONE NONE
Cumulitive Time
139 User Count 1 Class 0 22/02 Group Group 1 NONE NONE

140 User Count 2 Class 0 22/02 Group Group 1 NONE NONE

141 User Count 3 Class 0 22/02 Group Group 1 NONE NONE

142 User Count 4 Class 0 22/02 Group Group 1 NONE NONE

143 User Count 5 Class 0 22/02 Group Group 1 NONE NONE

144 User Count 6 Class 0 22/02 Group Group 1 NONE NONE

145 User Count 7 Class 0 22/02 Group Group 1 NONE NONE

146 User Count 8 Class 0 22/02 Group Group 1 NONE NONE

147 Instantaneous Overcurrent -TOTAL Class 0 22/02 Group Group 1 NONE NONE

148 Instantaneous Overcurrent -A Class 0 22/02 Group Group 1 NONE NONE

149 Instantaneous Overcurrent -B Class 0 22/02 Group Group 1 NONE NONE

150 Instantaneous Overcurrent -C Class 0 22/02 Group Group 1 NONE NONE

151 Instantaneous Overcurrent -Ground Class 0 22/02 Group Group 1 NONE NONE

152 Spare Class 0 22/02 Group Group 1 NONE NONE

153 Sensitive Earth Fault Class 0 22/02 Group Group 1 NONE NONE

154 Instantaneous Overcurrent – Neq Class 0 22/02 Group Group 1 NONE NONE

155 Time Overcurrent -TOTAL Class 0 22/02 Group Group 1 NONE NONE

156 Time Overcurrent -A Class 0 22/02 Group Group 1 NONE NONE

157 Time Overcurrent -B Class 0 22/02 Group Group 1 NONE NONE

158 Time Overcurrent -C Class 0 22/02 Group Group 1 NONE NONE

159 Time Overcurrent -Ground Class 0 22/02 Group Group 1 NONE NONE

160 Spare Class 0 22/02 Group Group 1 NONE NONE

161 Spare Class 0 22/02 Group Group 1 NONE NONE

162 Time Overcurrent – Neq Class 0 22/02 Group Group 1 NONE NONE

46 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 3. BASE DATA POINTS – COUNTERS(4/5)


IEC Mask Active Frozen
No Description Class Var
A B Event Counter

163 Unser Voltage -Total Class 0 22/02 Group Group 1 NONE NONE

164 Unser Voltage -A Class 0 22/02 Group Group 1 NONE NONE

165 Unser Voltage -B Class 0 22/02 Group Group 1 NONE NONE

166 Unser Voltage -C Class 0 22/02 Group Group 1 NONE NONE

167 Spare Class 0 22/02 Group Group 1 NONE NONE

168 Spare Class 0 22/02 Group Group 1 NONE NONE

169 Spare Class 0 22/02 Group Group 1 NONE NONE

170 Spare Class 0 22/02 Group Group 1 NONE NONE

171 Over Voltage -Total Class 0 22/02 Group Group 1 NONE NONE

172 Over Voltage -A Class 0 22/02 Group Group 1 NONE NONE

173 Over Voltage -B Class 0 22/02 Group Group 1 NONE NONE

174 Over Voltage -C Class 0 22/02 Group Group 1 NONE NONE

175 Spare Class 0 22/02 Group Group 1 NONE NONE

176 Over Voltage -Neutral Class 0 22/02 Group Group 1 NONE NONE

177 Neg Seq‟ Over Voltage (47) Class 0 22/02 Group Group 1 NONE NONE

178 Spare Class 0 22/02 Group Group 1 NONE NONE

179 Spare Class 0 22/02 Group Group 1 NONE NONE

180 Spare Class 0 22/02 Group Group 1 NONE NONE

181 Spare Class 0 22/02 Group Group 1 NONE NONE

182 Spare Class 0 22/02 Group Group 1 NONE NONE

183 Spare Class 0 22/02 Group Group 1 NONE NONE

184 Demand (49) Class 0 22/02 Group Group 1 NONE NONE

185 Power (32/32P) Class 0 22/02 Group Group 1 NONE NONE

186 Under Frequency (81U) Class 0 22/02 Group Group 1 NONE NONE

187 Over Frequency (81O) Class 0 22/02 Group Group 1 NONE NONE

188 Frequency Decay (81D) Class 0 22/02 Group Group 1 NONE NONE

189 Spare Class 0 22/02 Group Group 1 NONE NONE

190 Spare Class 0 22/02 Group Group 1 NONE NONE

191 Spare Class 0 22/02 Group Group 1 NONE NONE

192 Broken Conduct (46BC) Class 0 22/02 Group Group 1 NONE NONE

193 Frequency (81) – Total Class 0 22/02 Group Group 1 NONE NONE

194 Y0 Admittance (21YN) Class 0 22/02 Group Group 1 NONE NONE

ENHANCED TECHNOLOGY 47
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 3. BASE DATA POINTS – COUNTERS(5/5)


IEC Mask Active Frozen
No Description Class Var
A B Event Counter

195 Positive Active Energy - A Class 0 22/02 Group Group 1 NONE NONE

196 Positive Active Energy - B Class 0 22/02 Group Group 1 NONE NONE

197 Positive Active Energy - C Class 0 22/02 Group Group 1 NONE NONE

198 Positive Active Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE

199 Negative Active Energy - A Class 0 22/02 Group Group 1 NONE NONE

200 Negative Active Energy - B Class 0 22/02 Group Group 1 NONE NONE

201 Negative Active Energy - C Class 0 22/02 Group Group 1 NONE NONE

202 Negative Active Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE

203 Positive Reactive Energy - A Class 0 22/02 Group Group 1 NONE NONE

204 Positive Reactive Energy - B Class 0 22/02 Group Group 1 NONE NONE

205 Positive Reactive Energy - C Class 0 22/02 Group Group 1 NONE NONE

206 Positive Reactive Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE

207 Negative Reactive Energy - A Class 0 22/02 Group Group 1 NONE NONE

208 Negative Reactive Energy - B Class 0 22/02 Group Group 1 NONE NONE

209 Negative Reactive Energy - C Class 0 22/02 Group Group 1 NONE NONE

210 Negative Reactive Energy - 3Φ Class 0 22/02 Group Group 1 NONE NONE

*. NOTE )
1. Counter format can be selected (16 bit or 32 bit(Default)) by “16 bit Count Use” in “MAIN MENU
>> GLOBAL SETTING >> GENERAL >> DEVICE >> OTHERS” menu.
- 16 bit Counter rollover Counter 65535.
- 32 bit Counter rollover Counter 1,000,000.

2. Supported points may be different according to the option and version of controller.

48 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

4. Analog Input

Click “Analog Normalized Input” and “Analog Scaled Input” Tap in the bottom of the “DB MAP
CONFIGURATION” window to move to Analog Input Map. The properties of Inver, Class, Var,
IEC Mask A and more can individually be set in the “User Map List” per each data point. The
property can be changed by clicking the corresponding property column (indicate the combo box)
when the data point to be changed is selected (indicate with a blue line).
The property setting items are as follows.

 Class : It is to set a class that is related with event occurring of DNP3.0 communication.
 Var : It is to set Object/Variation to read corresponding data point in DNP3.0 communication.
- 32/01 : 32 bit Change without time-tag
- 32/02 : 16 bit Change without time-tag
- 32/03 : 32 bit Change with time-tag
- 32/04 : 16 bit Change with time-tag
- 32/05 : Short Change floating point
 IEC Mask A : It is to set IEC60870 communication use, there are Group(included in group),
Cyclic(Periodical polling), Group&Cyclic set options. In addition, if the Class attribute is allocated
to Class1, 2 or 3, it will have the Spontaneous point attribute in case of IEC60870 communication.
 IEC Mask B : It is to set a group on IEC60870 communication use. Refer to “IEC60870-5-
101/104 PROTOCOL Technical Manual” for more detailed information.
 Active Event : It sets whether an Analog Input(AI) event will occur or not.
- NONE(N/A) : It does not make an AI event occur
- Active : It does make an AI event occur
*. NOTE ) The occurring AI event type differs according to the “AI Evt Method” setting in
the “GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC SETUP” menu
of Entec‟s Recloser Control.
 The setting value is set to ‘OFF’: AI event does not occur even if the
Active Event property is set as „Active‟.
 The setting value is set to ‘TH’: AI event occurs due to Threshold
Configuration.
 The setting value is set to ‘DB’ : AI event occurs due to Deadband
Configuration.
 The setting value is set to ‘BOTH’: AI event occurs through both
Threshold & Deadband Configuration being applied.

ENHANCED TECHNOLOGY 49
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

*. NOTE ) A user will set the “AEvt Skip at Ft” setting value in the “GLOBAL SETTING/
COMMUNICATION/ EVENT&ETC SETUP” menu of Entec‟s Recloser
Control to determine whether AI event is generated or not at fault pickup.
 The setting value is set to ‘YES’: AI event is not generated during Fault
pickup.
 The setting value is set to ‘NO’: AI event is generated during Fault pickup.
 Deadband Configuration
- Limit Low : It sets the lower limit to make the event happen. It does not make the AI
event happen in case the Point data is lower than the “Limit Low” setting value.
- Limit High : It sets the upper limit to make the event happen. It does not make the AI
event happen in case the Point data is higher than the “Limit High” setting value.
- Dead Band : It makes the AI event happen if the difference in size of the point data is
above the Dead Band set value during the Smoothing Factor time (1sec).
- Smoothing Factor : It is the delta time to compare the point data change and is set as
1sec.
 Threshold Configuration
- Threshold Low : It makes the AI event occur in case it goes out of the Threshold Low
range because the point data decreases or the point data value increases again and restores
within the Threshold Low range
- Threshold High : It makes the AI event occur in case it goes out of the Threshold High
range because the point data increases or the point data value decreases again and restores
within the Threshold High range
* The IEC60870 communication does not make an AI event that applied a Threshold
Configuration happen.
 Scale : It transfers the divided proportion of the Scale set value from the actual data value.
 SMS : Set whether to transmit SMS messages in case of event occurrence in the corresponding
point.
- NO : Does not send SMS messages even if a Analog Input(AI) event occurs.
- YES : Sends SMS messages in case a AI event occurs.
 Index 60870 : It is to set the object address to read to corresponding data point in IEC60870
communication.

50 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

The Class & Var setting values are useful properties in the DNP3.0 communication and the
IEC Mask A/B and Index 60870 setting values are a useful property in the IEC60870
communication. The SMS setting value is a useful property in the SMS message transmitting
function.
As optional functions, the DNP3.0 communication, IEC60870 communication & SMS
message transmitting function will not cause any influence if the Entec‟s Recloser Control
does not support these functions.

The Analog Input‟s base data points are as follows.

ENHANCED TECHNOLOGY 51
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(1/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
0 MPU Version No. None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 0.0.0.1/1 Count

1 DPS Version No. None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 0.0.0.1/1 Count

2 Circuit +12V None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

3 Circuit -12V None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

4 Circuit Temperature None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1℃ / 1 Count

5 TD Input 1 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count

6 TD Input 2 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count

7 TD Input 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count

8 TD Input 4 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count

9 TD Input 5 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / Count

10 Self Diagnosis (Detail) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 Note 1)

NOTE
1) Diagnostics Details: This point is 16 bit data that shows recloser diagnosis. When 1 is set in each bit, indicates that the following failures were detected.
- bit 0: Self diagnosis Setting - bit 6: Self diagnosis Event Failure - bit 11: Self diagnosis Ethernet 1 Failure

- bit 1: Self diagnosis Global Setting Failure - bit 7: Self diagnosis Count Failure - bit 12: Self diagnosis Ethernet 2 Failure

- bit 2: Self diagnosis Group Setting Failure - bit 8: Self diagnosis RTC Failure - bit 13: Self diagnosis Goose Failure

- bit 3: Self diagnosis Memory Failure - bit 9: Self diagnosis CPU Failure - bit 14: Self diagnosis DSP Failure

- bit 4: Self diagnosis PLC Failure - bit 10: Self diagnosis Comm. Line Failure - bit 15: Self diagnosis Communication Failure

- bit 5: Self diagnosis Flash-Rom Failure

11 Battery Voltage None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

ENHANCED TECHNOLOGY 52
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(2/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
12 Charger Voltage None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

13 Gas Pressure (bar) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1bar / 1 Count

14 Gas Pressure (Volt) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

15 Reference Voltage None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

16 Charger Current None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

17 Temperature (OUT) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1℃ / 1 Count

18 Battery Capacity None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

19 Channel1 Frequency None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Hz / 1 Count

20 Channel2 Frequency None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Hz / 1 Count

21 Voltage Unbalance Rate (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

22 Voltage Unbalance Rate (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

23 Current Unbalance Rate None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

24 Sag Magnitude A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

25 Sag Duration A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

26 Sag Magnitude B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

27 Sag Duration B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

28 Sag Magnitude C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

29 Sag Duration C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

30 Swell Magnitude A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

ENHANCED TECHNOLOGY 53
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(3/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
31 Swell Duration A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

32 Swell Magnitude B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

33 Swell Duration B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

34 Swell Magnitude C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

35 Swell Duration C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

36 Interruption Magnitude A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

37 Interruption Duration A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

38 Interruption Magnitude B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

39 Interruption Duration B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

40 Interruption Magnitude C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

41 Interruption Duration C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1cycle / 1 Count

42 Voltage A DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

43 Voltage A 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

44 Voltage A 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

45 Voltage A 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

46 Voltage A 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

47 Voltage A 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

48 Voltage A 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

49 Voltage A 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

ENHANCED TECHNOLOGY 54
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(4/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
50 Voltage A 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

51 Voltage A 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

52 Voltage A 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

53 Voltage A 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

54 Voltage A 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

55 Voltage A 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

56 Voltage A 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

57 Voltage A THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

58 Voltage B DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

59 Voltage B 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

60 Voltage B 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

61 Voltage B 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

62 Voltage B 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

63 Voltage B 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

64 Voltage B 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

65 Voltage B 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

66 Voltage B 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

67 Voltage B 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

68 Voltage B 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

ENHANCED TECHNOLOGY 55
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(5/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
69 Voltage B 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

70 Voltage B 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

71 Voltage B 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

72 Voltage B 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

73 Voltage B THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

74 Voltage C DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

75 Voltage C 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

76 Voltage C 3rd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

77 Voltage C 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

78 Voltage C 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

79 Voltage C 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

80 Voltage C 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

81 Voltage C 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

82 Voltage C 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

83 Voltage C 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

84 Voltage C 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

85 Voltage C 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

86 Voltage C 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

87 Voltage C 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

ENHANCED TECHNOLOGY 56
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(6/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
88 Voltage C 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

89 Voltage C THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

90 Current A DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

91 Current A 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

92 Current A 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

93 Current A 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

94 Current A 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

95 Current A 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

96 Current A 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

97 Current A 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

98 Current A 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

99 Current A 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

100 Current A 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

101 Current A 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

102 Current A 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

103 Current A 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

104 Current A 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

105 Current A THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

106 Current B DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

ENHANCED TECHNOLOGY 57
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(7/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
107 Current B 2nd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

108 Current B 3rd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

109 Current B 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

110 Current B 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

111 Current B 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

112 Current B 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

113 Current B 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

114 Current B 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

115 Current B 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

116 Current B 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

117 Current B 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

118 Current B 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

119 Current B 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

120 Current B 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

121 Current B THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

122 Current C DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

123 Current C 2nd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

124 Current C 3rd Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

125 Current C 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

ENHANCED TECHNOLOGY 58
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(8/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
126 Current C 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

127 Current C 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

128 Current C 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

129 Current C 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

130 Current C 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

131 Current C 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

132 Current C 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

133 Current C 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

134 Current C 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

135 Current C 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

136 Current C 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

137 Current C THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

138 Current G DC Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

139 Current G 2nd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

140 Current G 3rd Harmonic Conten None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

141 Current G 4th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

142 Current G 5th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

143 Current G 6th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

144 Current G 7th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

ENHANCED TECHNOLOGY 59
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(9/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
145 Current G 8th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

146 Current G 9th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

147 Current G 10th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

148 Current G 11th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

149 Current G 12th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

150 Current G 13th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

151 Current G 14th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

152 Current G 15th Harmonic Content None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

153 Current G THD None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

154 Current A (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

155 Current B (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

156 Current C (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

157 Current G (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

158 Current N (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

159 Current SEF (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

160 Current Angle A (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

161 Current Angle B (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

162 Current Angle C (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

163 Current Angle G (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

ENHANCED TECHNOLOGY 60
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(10/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
164 Current Angle N (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

165 Current Angle SEF (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

166 Positive Current(I1) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

167 Negative Current(I2) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

168 Zero Seq. Current(I0) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

169 Positive Current(I1) Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

170 Negative Current(I2) Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

171 Zero Seq. Current(I0) Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

172 Current (TRUE RMS) A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

173 Current (TRUE RMS) B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

174 Current (TRUE RMS) C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

175 Current (TRUE RMS) G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

176 Current A (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

177 Current B (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

178 Current C (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

179 Current G (C-RMS) Fundamental Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

180 Current A (C-RMS) 2nd Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

181 Current B (C-RMS) 2nd Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

182 Current C (C-RMS) 2nd Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

ENHANCED TECHNOLOGY 61
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(11/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
183 Current G (C-RMS) 2nd Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

184 Current A (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

185 Current B (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

186 Current C (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

187 Current G (C-RMS) 5th Harmonic None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

188 Voltage A (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

189 Voltage B (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

190 Voltage C (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

191 Zero Seq. Voltage (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

192 Voltage Angle A (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

193 Voltage Angle B (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

194 Voltage Angle C (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

195 Zero Seq. Voltage Angle (RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

196 Line-Line Voltage AB (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

197 Line-Line Voltage BC (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

198 Line-Line Voltage CA (RMS) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

199 Voltage Angle AB (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

200 Voltage Angle BC (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

201 Voltage Angle CA (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

ENHANCED TECHNOLOGY 62
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(12/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
202 Positive Voltage V1 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

203 Negative Voltage V2 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

204 Zero Seq. Voltage V0 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

205 Positive Voltage Angle V1 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

206 Negative Voltage Angle V2 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

207 Zero Seq. Voltage Angle V0 (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

208 Voltage A (TRUE RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

209 Voltage B (TRUE RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

210 Voltage C (TRUE RMS) (Source) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

211 Voltage A (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

212 Voltage B (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

213 Voltage C (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

214 Zero Seq. Voltage (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

215 Voltage Angle A (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

216 Voltage Angle B (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

217 Voltage Angle C (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

218 Zero Seq. Voltage Angle (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

219 Voltage AB (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

220 Voltage BC (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

ENHANCED TECHNOLOGY 63
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(13/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
221 Voltage CA (RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

222 Voltage Angle AB (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

223 Voltage Angle BC (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

224 Voltage Angle CA (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

225 Positive Voltage V1 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

226 Negative Voltage V2 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

227 Zero Seq. VoltageV0 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

228 Positive Voltage Angle V1 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

229 Negative Voltage Angle V2 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

230 Zero Seq. Voltage Angle V0 (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1° / 1 Count

231 Voltage A (TRUE RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

232 Voltage B (TRUE RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

233 Voltage C (TRUE RMS) (Load) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

234 Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

235 Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

236 Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

237 Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

238 Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

239 Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

ENHANCED TECHNOLOGY 64
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(14/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
240 Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

241 Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

242 Apparent Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count

243 Apparent Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count

244 Apparent Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count

245 Apparent Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVA / 1 Count

246 Power Factor A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

247 Power Factor B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

248 Power Factor C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

249 Power Factor (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

250 POSITIVE Real Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

251 POSITIVE Real Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

252 POSITIVE Real Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

253 POSITIVE Real Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

254 NEGATIVE Real Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

255 NEGATIVE Real Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

256 NEGATIVE Real Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

257 NEGATIVE Real Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

258 POSITIVE Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

ENHANCED TECHNOLOGY 65
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(15/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
259 POSITIVE Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

260 POSITIVE Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

261 POSITIVE Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

262 NEGATIVE Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

263 NEGATIVE Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

264 NEGATIVE Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

265 NEGATIVE Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

266 Demand A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

267 Demand B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

268 Demand C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

269 Demand G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

270 Demand Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

271 Demand Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

272 Demand Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

273 Demand Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

274 Demand Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

275 Demand Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

276 Demand Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

277 Demand Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

ENHANCED TECHNOLOGY 66
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(16/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
278 Block Demand A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

279 Block Demand B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

280 Block Demand C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

281 Block Demand G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

282 Block Demand Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

283 Block Demand Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

284 Block Demand Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

285 Block Demand Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

286 Block Demand Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

287 Block Demand Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

288 Block Demand Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

289 Block Demand Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

290 Hourly Maximum Load A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

291 Hourly Maximum Load B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

292 Hourly Maximum Load C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

293 Hourly Maximum Load G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

294 Hourly Maximum Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

295 Hourly Maximum Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

296 Hourly Maximum Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

ENHANCED TECHNOLOGY 67
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(17/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
297 Hourly Maximum Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

298 Hourly Maximum Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

299 Hourly Maximum Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

300 Hourly Maximum Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

301 Hourly Maximum Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

302 Today Maximum Load A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

303 Today Maximum Load B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

304 Today Maximum Load C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

305 Today Maximum Load G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

306 Today Maximum Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

307 Today Maximum Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

308 Today Maximum Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

309 Today Maximum Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

310 Today Maximum Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

311 Today Maximum Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

312 Today Maximum Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

313 Today Maximum Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

314 Yesterday Maximum Load Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

315 Yesterday Maximum Load Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

ENHANCED TECHNOLOGY 68
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(18/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
316 Yesterday Maximum Load Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

317 Yesterday Maximum Load Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

318 Yesterday Maximum Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

319 Yesterday Maximum Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

320 Yesterday Maximum Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

321 Yesterday Maximum Active Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

322 Yesterday Maximum Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

323 Yesterday Maximum Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

324 Yesterday Maximum Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

325 Yesterday Maximum Reactive Power (3Φ) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

326 Fault Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

327 Fault Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

328 Fault Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

329 Fault Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

330 Fault Current SEF None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

331 Fault Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

332 Fault Voltage A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

333 Fault Voltage B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

334 Fault Voltage C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

ENHANCED TECHNOLOGY 69
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(19/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
335 Contact Wear A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

336 Contact Wear B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

337 Contact Wear C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1% / 1 Count

338 First Fault Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

339 First Fault Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

340 First Fault Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

341 First Fault Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

342 First Fault Current SEF None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

343 First Fault Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

344 First Fault Voltage A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

345 First Fault Voltage B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

346 First Fault Voltage C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1V / 1 Count

347 Latitude(1:south,2:north) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 -

348 Degree None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1˚/1Count

349 Minute None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1‟/1Count

350 Second None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1”/1Count

351 Longitude(1:east,2:west) None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 -

352 Degree None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1˚/1Count

353 Minute None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1‟/1Count

ENHANCED TECHNOLOGY 70
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(20/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
354 Second None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1”/1Count

355 Peak Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

356 Peak Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

357 Peak Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

358 Peak Current G None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

359 Peak Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

360 Pos Max Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

361 Pos Max Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

362 Pos Max Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

363 Pos Max Active Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

364 Pos Max Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

365 Pos Max Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

366 Pos Max Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

367 Pos Max Reactive Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

368 Neg Max Active Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

369 Neg Max Active Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

370 Neg Max Active Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

371 Neg Max Active Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kW / 1 Count

372 Neg Max Reactive Power A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

ENHANCED TECHNOLOGY 71
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(21/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
373 Neg Max Reactive Power B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

374 Neg Max Reactive Power C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

375 Neg Max Reactive Power 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1kVar / 1 Count

376 Operation Count None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count

377 Trip Count None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count

378 External TD 1 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count

379 External TD 2 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count

380 External TD 3 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count

381 External TD 4 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count

382 External TD 5 None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 / 1 Count

383 Fault Location None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1km / 1 Count

384 Fault Reactance None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Ω / 1Count

385 Max Demand Current A None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

386 Max Demand Current B None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

387 Max Demand Current C None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

388 Max Demand Current N None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

389 Max Demand Current Q None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1A / 1 Count

390 Mechanical Wear None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1 % / 1 Count

391 Z0 Impedance Rms None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1Ω / 1Count

ENHANCED TECHNOLOGY 72
ETR300-R & EVRC2A-NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 4. BASE DATA POINTS – ANALOG INPUT(22/22)


IEC Mask DeadBand Threshold
Active
No Description Class Var Limit Limit Dead Scale Data Format
A B Event Low High
Low High Band
392 Z0 Impedance Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1˚/1Count

393 Y0 Admitance Rms None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1mS / 1Count

394 Y0 Admitance Angle None 32/04 Group Group 16 None -32000 32000 50 1 -32000 32000 1˚/1Count

*. NOTE )
1. The Data Format of all AI Points can be changed with Scale setting of ETIMS Interface software.
2. Supported points may be different according to the option and version of controller.

ENHANCED TECHNOLOGY 73
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

5. Analog Output

Click “Analog Normalized Output” and “Analog Scaled Output” Tap in the bottom of the “DB
MAP CONFICURATION” window to move to Analog Output Map. The properties of Class & Var
can individually be set in the “User Map List” per each data point. The property can be changed by
clicking the corresponding property column (indicate the combo box) when the data point to be
changed is selected (indicate with a blue line).
The property setting items are as follows.

 Class : It is to set a class that is related with event occurring of DNP3.0 communication.

The Class & Var setting value are useful properties in the DNP3.0 communication. If Entec‟s
Recloser Control does not support the DNP3.0 communication function, the corresponding
property will not cause any influence.

The Analog Output‟s base data points are as follows.

74 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(1/19)


Index Remark
Description Var
No. Range Step Default
0 External Channel DC3-2 Alarm Pickup NONE 0~6000 0.1 0

External Channel DC3-2 Alarm Time


1 NONE 0.01~600s 0.01 0
Delay

2 External Channel DC4 Rate NONE 1~200 1 40

3 External Channel DC4 Ratio NONE 1~3000 1 1

4 External Channel DC4 Offset NONE -10000~10000 1 0

5 External Channel DC4-1 Alarm Type NONE Under(0), Over(1) 1 Under

6 External Channel DC4-1 Alarm Pickup NONE 0~6000 0.1 0

External Channel DC4-1 Alarm Time


7 NONE 0.01~600s 0.01 2
Delay

8 External Channel DC4-2 Alarm Type NONE Under(0), Over(1) 1 Under

9 External Channel DC4-2 Alarm Pickup NONE 0~6000 0.1 0

External Channel DC24-2 Alarm Time


10 NONE 0.01~600s 0.01 2
Delay

GROUP1(0), GROUP2(1),
11 Primary Setting Group NONE 1 GROUP1
GROUP3(2), GROUP4(3)

GROUP1(0), GROUP2(1),
12 Alternate Setting Group NONE 1 GROUP1
GROUP3(2), GROUP4(3)

13 Loop Control Type Select NONE NONE(0), SEC(1), MID(2), TIE(3) 1 NONE

Voltage Response Side in SEC or MID


14 NONE VS(0), VL(1), VS&VL(2) 1 VS
Type

15 Voltage Response Side in TIE Type NONE VS(0), VL(1), VS&VL(2) 1 VS

Source Side Voltage Sensor Wiring 3PN:0, 3PP:1, 1PN(A):2,


16 NONE 1 0
Type 1PN(B):3, 1PN(C):4,1PP(AB):5,

17 Load Side Voltage Sensor Wiring Type NONE 1PP(BC):6, 1PP(CA):7 1 0

Auto Alternate Setting Group Change


18 NONE OFF(0), ON(1) 1 OFF
in MID Type

Auto Alternate Setting Group Change


19 NONE OFF(0), ON(1) 1 OFF
in TIE Type

Loop Control Auto Enabled after Close


20 NONE DISABLE(0), ENABLE(1) 1 DISABLE
in SEC Type

Loop Control Auto Enabled after Open


21 NONE DISABLE(0), ENABLE(1) 1 DISABLE
in TIE Type

ENHANCED TECHNOLOGY 75
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(2/19)


Index Remark
Description Var
No. Range Step Default
Open Time when Both(Source Side/Load
22 NONE 0.01~600s 0.01 10
Side) Dead Line in TIE Type

23 Auto Restoration Time in SEC or MID Type NONE 0.01~600s 0.01 5

24 Dead Line Maximum Voltage Level NONE 0.1~1.4xVT 0.01 0.2

25 Live Line Minimum Voltage Level NONE 0.1~1.4xVT 0.01 0.7

26 Dead Line Detection Time Delay NONE 0.01~600s 0.01 50

27 Live Line Detection Time Delay NONE 0.01~600s 0.01 50

28 Dead Line Detection Reset Time Delay NONE 0.01~600s 0.01 5

Auto Reclosing Block Time after Loop


29 NONE 0.01~600s 0.01 5
Control Operation in MID or TIE Type

30 Loop Control Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

31 Fault Pop-up Message Use NONE OFF(0), ON(1) 1 OFF

32 Battery Management Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

33 Battery Charging Time NONE 60~6000 m 1 780

34 Battery Discharging Time NONE 60~6000 m 1 1440

35 Battery Alarm Level NONE 0~100% 0.01 50

36 Initial Value at Reset Battery Capacity NONE 0~100% 0.01 100

37 LCD Initial Logo Main Screen Select NONE 1~8 1 2

OFF(0), TRIP(1),
38 (+) Phase Fast Overcurrent (51P-1) Function NONE 1 TRIP
ALARM(2), TR&AL(3)

(+) Phase Fast Overcurrent (51P-1) Pickup


39 NONE 10~1600 A 1 500
Current

40 (+) Phase Fast Overcurrent (51P-1) TC Curve NONE Not 1) 1 41

(+) Phase Fast Overcurrent (51P-1) Time


41 NONE 0.01~15 0.01 1
Dial for TC Curve

(+) Phase Fast Overcurrent (51P-1) Time


42 NONE 0~600s 0.01 0
Adder for TC Curve

(+) Phase Fast Overcurrent (51P-1)


43 NONE 0~10s 0.01 0
Minimum Response Time

(+) Phase Fast Overcurrent (51P-1) Reset


44 NONE INST(0), LINEAR(1) 1 INST
Method

(+) Phase Fast Overcurrent (51P-1) Low Set


45 NONE 0.01~600 s 0.01 0
Definite Time

76 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(3/19)


Index Remark
Description Var
No. Range Step Default
OFF(0), TRIP(1),
46 (+) Phase Delay Overcurrent (51P-2) Function NONE 1 TRIP
ALARM(2), TR&AL(3)

(+) Phase Delay Overcurrent (51P-2) Pickup


47 NONE 10~1600 A 1 500
Current

48 (+) Phase Delay Overcurrent (51P-2) TC Curve NONE Not 1) 1 41

(+) Phase Delay Overcurrent (51P-2) Time Dial for


49 NONE 0.01~15 0.01 1
TC Curve

(+) Phase Delay Overcurrent (51P-2) Time Adder


50 NONE 0~600s 0.01 0
for TC Curve

(+) Phase Delay Overcurrent (51P-2) Minimum


51 NONE 0~10s 0.01 0
Response Time

52 (+) Phase Delay Overcurrent (51P-2) Reset Method NONE INST(0), LINEAR(1) 1 INST

(+) Phase Delay Overcurrent (51P-2) Low Set


53 NONE 0.01~600 s 0.01 0
Definite Time

OFF(0), TRIP(1),
54 (+) Ground Fast Overcurrent (51G-1) Function NONE 1 TRIP
ALARM(2), TR&AL(3)

(+) Ground Fast Overcurrent (51G-1) Pickup


55 NONE 10~1600 A 1 250
Current

56 (+) Ground Fast Overcurrent (51G-1) TC Curve NONE Not 1) 1 41

(+) Ground Fast Overcurrent (51G-1) Time Dial for


57 NONE 0.01~15 0.01 1
TC Curve

(+) Ground Fast Overcurrent (51G-1) Time Adder


58 NONE 0~600s 0.01 0
for TC Curve

(+) Ground Fast Overcurrent (51G-1) Minimum


59 NONE 0~10s 0.01 0
Response Time

(+) Ground Fast Overcurrent (51G-1) Reset


60 NONE INST(0), LINEAR(1) 1 INST
Method

(+) Ground Fast Overcurrent (51G-1) Low Set


61 NONE 0.01~600 s 0.01 0
Definite Time

OFF(0), TRIP(1),
62 (+) Ground Delay Overcurrent (51G-2) Function NONE 1 TRIP
ALARM(2), TR&AL(3)

(+) Ground Delay Overcurrent (51G-2) Pickup


63 NONE 10~1600 A 1 250
Current

ENHANCED TECHNOLOGY 77
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(4/19)


Index Remark
Description Var
No. Range Step Default
64 (+) Ground Delay Overcurrent (51G-2) TC Curve NONE Note 1) 1 41

(+) Ground Delay Overcurrent (51G-2) Time Dial


65 NONE 0.01~15 0.01 1
for TC Curve

(+) Ground Delay Overcurrent (51G-2) Time


66 NONE 0~600s 0.01 0
Adder for TC Curve

(+) Ground Delay Overcurrent (51G-2) Minimum


67 NONE 0~10s 0.01 0
Response Time

(+) Ground Delay Overcurrent (51G-2) Reset


68 NONE INST(0), LINEAR(1) 1 INST
Method

(+) Ground Delay Overcurrent (51G-2) Low Set


69 NONE 0.01~600 s 0.01 0
Definite Time

OFF(0), TRIP(1),
70 (+) Neg. Seq Fast Overcurrent (51Q-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)

(+) Neg. Seq Fast Overcurrent (51Q-1) Pickup


71 NONE 10~1600 A 1 500
Current

72 (+) Neg. Seq Fast Overcurrent (51Q-1) TC Curve NONE Note 1) 1 41

(+) Neg. Seq Fast Overcurrent (51Q-1) Time Dial


73 NONE 0.01~15 0.01 1
for TC Curve

(+) Neg. Seq Fast Overcurrent (51Q-1) Time Adder


74 NONE 0~600s 0.01 0
for TC Curve

(+) Neg. Seq Fast Overcurrent (51Q-1) Minimum


75 NONE 0~10s 0.01 0
Response Time

(+) Neg. Seq Fast Overcurrent (51Q-1) Reset


76 NONE INST(0), LINEAR(1) 1 INST
Method

(+) Neg. Seq Fast Overcurrent (51Q-1) Low Set


77 NONE 0.01~600 s 0.01 0
Definite Time

OFF(0), TRIP(1),
78 (+) Neg. Seq Delay Overcurrent (51Q-2) Function NONE 1 OFF
ALARM(2), TR&AL(3)

(+) Neg. Seq Delay Overcurrent (51Q-2) Pickup


79 NONE 10~1600 A 1 500
Current

80 (+) Neg. Seq Delay Overcurrent (51Q-2) TC Curve NONE Note 1) 1 41

(+) Neg. Seq Delay Overcurrent (51Q-2) Time Dial


81 NONE 0.01~15 0.01 1
for TC Curve

78 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(5/19)


Index Remark
Description Var
No. Range Step Default
(+) Neg. Seq Delay Overcurrent (51Q-2) Time
82 NONE 0~600 s 0.01 0
Adder for TC Curve

(+) Neg. Seq Delay Overcurrent (51Q-2) Minimum


83 NONE 0~10 s 0.01 0
Response Time

(+) Neg. Seq Delay Overcurrent (51Q-2) Reset


84 NONE INST(0), LINEAR(1) 1 INST
Method

(+) Neg. Seq Delay Overcurrent (51Q-2) Low Set


85 NONE 0.01~600 s 0.01 0
Definite Time

(+) Phase Instantaneous Overcurrent (50P-1) DISABL


86 NONE DISABLE(0), ENABLE(1) 1
Function E

(+) Phase Instantaneous Overcurrent (50P-1)


87 NONE 10~20000 A 1 4000
Pickup

(+) Phase Instantaneous Overcurrent (50P-1) Time


88 NONE 0~600 s 0.01 0
Delay

(+) Phase Instantaneous Overcurrent (50P-1)


89 NONE 1~5 1 1
Active Shot

(+) Phase Instantaneous Overcurrent Lockout (50P- DISABL


90 NONE DISABLE(0), ENABLE(1) 1
2) Function E

(+) Phase Instantaneous Overcurrent Lockout (50P-


91 NONE 10~20000 A 1 8000
2) Pickup

(+) Phase Instantaneous Overcurrent Lockout (50P-


92 NONE 0~600 s 0.01 0
2) Time Delay

(+) Phase Instantaneous Overcurrent Lockout (50P-


93 NONE 1~5 1 1
2) Active Shot

(+) Ground Instantaneous Overcurrent (50G-1) DISABL


94 NONE DISABLE(0), ENABLE(1) 1
Function E

(+) Ground Instantaneous Overcurrent (50G-1)


95 NONE 10~20000 A 1 4000
Pickup

(+) Ground Instantaneous Overcurrent (50G-1)


96 NONE 0~600 s 0.01 0
Time Delay

(+) Ground Instantaneous Overcurrent (50G-1)


97 NONE 1~5 1 1
Active Shot

ENHANCED TECHNOLOGY 79
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(6/19)


Index Remark
Description Var
No. Range Step Default
(+) Ground Instantaneous Overcurrent Lockout
98 NONE DISABLE(0), ENABLE(1) 1 DISABLE
(50G-2) Function

(+) Ground Instantaneous Overcurrent Lockout


99 NONE 10~20000 A 1 8000
(50G-2) Pickup

(+) Ground Instantaneous Overcurrent Lockout


100 NONE 0~600 s 0.01 0
(50G-2) Time Delay

(+) Ground Instantaneous Overcurrent Lockout


101 NONE 1~5 1 1
(50G-2) Active Shot

(+) Neg. Seq Instantaneous Overcurrent (50Q-1) OFF(0), TRIP(1),


102 NONE 1 OFF
Function ALARM(2), TR&AL(3)

(+) Neg. Seq Instantaneous Overcurrent (50Q-1)


103 NONE 10~20000 A 1 4000
Pickup

(+) Neg. Seq Instantaneous Overcurrent (50Q-1)


104 NONE 0~600 s 0.01 0
Time Delay

(+) Neg. Seq Instantaneous Overcurrent (50Q-1)


105 NONE 1~5 1 1
Active Shot

(+) Neg. Seq Instantaneous Overcurrent Lockout OFF(0), TRIP(1),


106 NONE 1 OFF
(50Q-2) Function ALARM(2), TR&AL(3)

(+) Neg. Seq Instantaneous Overcurrent Lockout


107 NONE 10~20000 A 1 8000
(50Q-2) Pickup

(+) Neg. Seq Instantaneous Overcurrent Lockout


108 NONE 0~600 s 0.01 0
(50Q-2) Time Delay

(+) Neg. Seq Instantaneous Overcurrent Lockout


109 NONE 1~5 1 1
(50Q-2) Active Shot

OFF(0), TRIP(1),
110 (+) Sensitive Earth Fault (50SEF) Function NONE 1 OFF
ALARM(2), TR&AL(3)

111 (+) Sensitive Earth Fault (50SEF) Pickup NONE 0.1 ~ 160.0 s 0.1 10.0

112 (+) Sensitive Earth Fault (50SEF) Time Delay NONE 0~600 s 0.01 0

113 Phase Direction (67P) Type NONE NONE(0), FOR(1), REV(2) 1 NONE

114 Phase Direction (67P) Maximum Torque Angle NONE 0~359 Lag 1 60

Phase Direction (67P) Minimum Polarizing


115 NONE 0.1~0.8 xVT 0.01 0.3
Voltage

80 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(7/19)


Index Remark
Description Var
No. Range Step Default
116 Phase Direction (67P) Block Overcurrent NONE NO(1), YES(1) 1 YES

117 Ground Direction (67G) Type NONE NONE(0), FOR(1), REV(2) 1 NONE

Ground Direction (67G) Maximum Torque


118 NONE 0~359 Lag 1 60
Angle

Ground Direction (67G) Minimum Polarizing


119 NONE 0.1~0.8 xVT 0.01 0.3
Voltage

120 Ground Direction (67G) Block Overcurrent NONE NO(1), YES(1) 1 YES

121 Sensitive Earth Fault Direction (67SEF) Type NONE NONE(0), FOR(1), REV(2) 1 NONE

Sensitive Earth Fault Direction (67SEF)


122 NONE 0~359 Lag 1 60
Maximum Torque Angle

Sensitive Earth Fault Direction (67SEF)


123 NONE 0.1~0.8 xVT 0.01 0.3
Minimum Polarizing Voltage

Sensitive Earth Fault Direction (67SEF) Block


124 NONE NO(1), YES(1) 1 YES
Overcurrent

125 Neg. Seq Direction (67Q) Type NONE NONE(0), FOR(1), REV(2) 1 NONE

Neg. Seq Direction (67Q) Maximum Torque


126 NONE 0~359 Lag 1 60
Angle

Neg. Seq Direction (67Q) Minimum Polarizing


127 NONE 0.1~0.8 xVT 0.01 0.3
Voltage

128 Neg. Seq Direction (67Q) Block Overcurrent NONE NO(1), YES(1) 1 YES

OFF(0), TRIP(1), ALARM(2),


129 (-) Phase Fast Overcurrent (51P-1) Function NONE 1 OFF
TR&AL(3)

(-) Phase Fast Overcurrent (51P-1) Pickup


130 NONE 10~1600 A 1 500
Current

131 (-) Phase Fast Overcurrent (51P-1) TC Curve NONE Not 1) 1 41

(-) Phase Fast Overcurrent (51P-1) Time Dial


132 NONE 0.01~15 0.01 1
for TC Curve

(-) Phase Fast Overcurrent (51P-1) Time Adder


133 NONE 0~600 s 0.01 0
for TC Curve

(-) Phase Fast Overcurrent (51P-1) Minimum


134 NONE 0~10 s 0.01 0
Response Time

(-) Phase Fast Overcurrent (51P-1) Reset


135 NONE INST(0), LINEAR(1) 1 INST
Method

ENHANCED TECHNOLOGY 81
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(8/19)


Index Remark
Description Var
No. Range Step Default
(-) Phase Fast Overcurrent (51P-1) Low Set
136 NONE 0.01~600 s 0.01 0
Definite Time

OFF(0), TRIP(1), ALARM(2),


137 (-) Phase Delay Overcurrent (51P-2) Function NONE 1 OFF
TR&AL(3)

(-) Phase Delay Overcurrent (51P-2) Pickup


138 NONE 10~1600 A 1 500
Current

139 (-) Phase Delay Overcurrent (51P-2) TC Curve NONE Not 1) 1 41

(-) Phase Delay Overcurrent (51P-2) Time Dial


140 NONE 0.01~15 0.01 1
for TC Curve

(-) Phase Delay Overcurrent (51P-2) Time


141 NONE 0~600 s 0.01 0
Adder for TC Curve

(-) Phase Delay Overcurrent (51P-2) Minimum


142 NONE 0~10 s 0.01 0
Response Time

(-) Phase Delay Overcurrent (51P-2) Reset


143 NONE INST(0), LINEAR(1) 1 INST
Method

(-) Phase Delay Overcurrent (51P-2) Low Set


144 NONE 0.01~600 s 0.01 0
Definite Time

OFF(0), TRIP(1),
145 (-) Ground Fast Overcurrent (51G-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)

(-) Ground Fast Overcurrent (51G-1) Pickup


146 NONE 10~1600 A 1 250
Current

147 (-) Ground Fast Overcurrent (51G-1) TC Curve NONE Note 1) 1 41

(-) Ground Fast Overcurrent (51G-1) Time Dial


148 NONE 0.01~15 0.01 1
for TC Curve

(-) Ground Fast Overcurrent (51G-1) Time


149 NONE 0~600 s 0.01 0
Adder for TC Curve

(-) Ground Fast Overcurrent (51G-1) Minimum


150 NONE 0~10 s 0.01 0
Response Time

(-) Ground Fast Overcurrent (51G-1) Reset


151 NONE INST(0), LINEAR(1) 1 INST
Method

(-) Ground Fast Overcurrent (51G-1) Low Set


152 NONE 0.01~600 s 0.01 0
Definite Time

82 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(9/19)


Index Remark
Description Var
No. Range Step Default
(-) Ground Delay Overcurrent (51G-2) OFF(0), TRIP(1), ALARM(2),
153 NONE 1 OFF
Function TR&AL(3)

(-) Ground Delay Overcurrent (51G-2) Pickup


154 NONE 10~1600 A 1 250
Current

(-) Ground Delay Overcurrent (51G-2) TC


155 NONE Note 1) 1 41
Curve

(-) Ground Delay Overcurrent (51G-2) Time


156 NONE 0.01~15 0.01 1
Dial for TC Curve

(-) Ground Delay Overcurrent (51G-2) Time


157 NONE 0~600 s 0.01 0
Adder for TC Curve

(-) Ground Delay Overcurrent (51G-2)


158 NONE 0~10 s 0.01 0
Minimum Response Time

(-) Ground Delay Overcurrent (51G-2) Reset


159 NONE INST(0), LINEAR(1) 1 INST
Method

(-) Ground Delay Overcurrent (51G-2) Low Set


160 NONE 0.01~600 s 0.01 0
Definite Time

(-) Neg. Seq Fast Overcurrent (51Q-1) OFF(0), TRIP(1), ALARM(2),


161 NONE 1 OFF
Function TR&AL(3)

(-) Neg. Seq Fast Overcurrent (51Q-1) Pickup


162 NONE 10~1600 A 1 250
Current

(-) Neg. Seq Fast Overcurrent (51Q-1) TC


163 NONE Note 1) 1 41
Curve

(-) Neg. Seq Fast Overcurrent (51Q-1) Time


164 NONE 0.01~15 0.01 1
Dial for TC Curve

(-) Neg. Seq Fast Overcurrent (51Q-1) Time


165 NONE 0~600 s 0.01 0
Adder for TC Curve

(-) Neg. Seq Fast Overcurrent (51Q-1)


166 NONE 0~10 s 0.01 0
Minimum Response Time

(-) Neg. Seq Fast Overcurrent (51Q-1) Reset


167 NONE INST(0), LINEAR(1) 1 INST
Method

(-) Neg. Seq Fast Overcurrent (51Q-1) Low Set


168 NONE 0.01~600 s 0.01 0
Definite Time

ENHANCED TECHNOLOGY 83
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(10/19)


Index Remark
Description Var
No. Range Step Default
(-) Neg. Seq Delay Overcurrent (51Q-2) OFF(0), TRIP(1), ALARM(2),
169 NONE 1 OFF
Function TR&AL(3)

(-) Neg. Seq Delay Overcurrent (51Q-2)


170 NONE 10~1600 A 1 500
Pickup Current

(-) Neg. Seq Delay Overcurrent (51Q-2) TC


171 NONE Note 1) 1 41
Curve

(-) Neg. Seq Delay Overcurrent (51Q-2) Time


172 NONE 0.01~15 0.01 1
Dial for TC Curve

(-) Neg. Seq Delay Overcurrent (51Q-2) Time


173 NONE 0~600 s 0.01 0
Adder for TC Curve

(-) Neg. Seq Delay Overcurrent (51Q-2)


174 NONE 0~10 s 0.01 0
Minimum Response Time

(-) Neg. Seq Delay Overcurrent (51Q-2) Reset


175 NONE INST(0), LINEAR(1) 1 INST
Method

(-) Neg. Seq Delay Overcurrent (51Q-2) Low


176 NONE 0.01~600 s 0.01 0
Set Definite Time

(-) Phase Instantaneous Overcurrent (50P-1)


177 NONE DISABLE(0), ENABLE(1) 1 DISABLE
Function

(-) Phase Instantaneous Overcurrent (50P-1)


178 NONE 10~20000 A 1 4000
Pickup

(-) Phase Instantaneous Overcurrent (50P-1)


179 NONE 10~20000 A 1 4000
Time Delay

(-) Phase Instantaneous Overcurrent (50P-1)


180 NONE 1~5 1 1
Active Shot

(-) Phase Instantaneous Overcurrent Lockout


181 NONE DISABLE(0), ENABLE(1) 1 DISABLE
(50P-2) Function

(-) Phase Instantaneous Overcurrent Lockout


182 NONE 10~20000 A 1 8000
(50P-2) Pickup

(-) Phase Instantaneous Overcurrent Lockout


183 NONE 0~600 s 0.01 0
(50P-2) Time Delay

(-) Phase Instantaneous Overcurrent Lockout


184 NONE 1~5 1 1
(50P-2) Active Shot

84 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(11/19)


Index Remark
Description Var
No. Range Step Default
(-) Ground Instantaneous Overcurrent (50G-1)
185 NONE DISABLE(0), ENABLE(1) 1 DISABLE
Function

(-) Ground Instantaneous Overcurrent (50G-1)


186 NONE 10~20000 A 1 4000
Pickup

(-) Ground Instantaneous Overcurrent (50G-1)


187 NONE 10~20000 A 1 4000
Time Delay

(-) Ground Instantaneous Overcurrent (50G-1)


188 NONE 1~5 1 1
Active Shot

(-) Ground Instantaneous Overcurrent Lockout


189 NONE DISABLE(0), ENABLE(1) 1 DISABLE
(50G-2) Function

(-) Ground Instantaneous Overcurrent Lockout


190 NONE 10~20000 A 1 8000
(50G-2) Pickup

(-) Ground Instantaneous Overcurrent Lockout


191 NONE 0~600 s 0.01 0
(50G-2) Time Delay

(-) Ground Instantaneous Overcurrent Lockout


192 NONE 1~5 1 1
(50G-2) Active Shot

(-) Neg. Seq Instantaneous Overcurrent (50Q- OFF(0), TRIP(1), ALARM(2),


193 NONE 1 OFF
1) Function TR&AL(3)

(-) Neg. Seq Instantaneous Overcurrent (50Q-


194 NONE 10~20000 A 1 4000
1) Pickup

(-) Neg. Seq Instantaneous Overcurrent (50Q-


195 NONE 0~600 s 0.01 0
1) Time Delay

(-) Neg. Seq Instantaneous Overcurrent (50Q-


196 NONE 1~5 1 1
1) Active Shot

(-) Neg. Seq Instantaneous Overcurrent OFF(0), TRIP(1), ALARM(2),


197 NONE 1 OFF
Lockout (50Q-2) Function TR&AL(3)

(-) Neg. Seq Instantaneous Overcurrent


198 NONE 10~20000 A 1 8000
Lockout (50Q-2) Pickup

(-) Neg. Seq Instantaneous Overcurrent


199 NONE 0~600 s 0.01 0
Lockout (50Q-2) Time Delay

(-) Neg. Seq Instantaneous Overcurrent


200 NONE 1~5 1 1
Lockout (50Q-2) Active Shot

ENHANCED TECHNOLOGY 85
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(12/19)


Index Remark
Description Var
No. Range Step Default
OFF(0), TRIP(1), ALARM(2),
201 (-) Sensitive Earth Fault (50SEF) Function NONE 1 OFF
TR&AL(3)

(-) Sensitive Earth Fault (50SEF)


202 NONE 0.1 ~ 160.0 s 0.1 10.0
Pickup

203 (-) Sensitive Earth Fault (50SEF) Time Delay NONE 0~600 s 0.01 0

204 Auto Reclosing (79) Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

205 Phase OverCurrent Total Operation Shots NONE 1~5 1 4

206 Phase Fast Curve Active at Shot 1 NONE NO(0), YES(1) 1 YES

207 Phase Fast Curve Active at Shot 2 NONE NO(0), YES(1) 1 YES

208 Phase Fast Curve Active at Shot 3 NONE NO(0), YES(1) 1 NO

209 Phase Fast Curve Active at Shot 4 NONE NO(0), YES(1) 1 NO

210 Phase Fast Curve Active at Shot 5 NONE NO(0), YES(1) 1 NO

211 Ground OverCurrent Total Operation Shots NONE 1~5 1 4

212 Ground Fast Curve Active at Shot 1 NONE NO(0), YES(1) 1 YES

213 Ground Fast Curve Active at Shot 2 NONE NO(0), YES(1) 1 YES

214 Ground Fast Curve Active at Shot 3 NONE NO(0), YES(1) 1 NO

215 Ground Fast Curve Active at Shot 4 NONE NO(0), YES(1) 1 NO

216 Ground Fast Curve Active at Shot 5 NONE NO(0), YES(1) 1 NO

217 Sensitive Earth Fault Total Operation Shots NONE 1~5 1 4

218 Neg. Seq OverCurrent Total Operation Shots NONE 1~5 1 4

219 Neg. Seq Fast Curve Active at Shot 1 NONE NO(0), YES(1) 1 YES

220 Neg. Seq Fast Curve Active at Shot 2 NONE NO(0), YES(1) 1 YES

221 Neg. Seq Fast Curve Active at Shot 3 NONE NO(0), YES(1) 1 NO

222 Neg. Seq Fast Curve Active at Shot 4 NONE NO(0), YES(1) 1 NO

223 Neg. Seq Fast Curve Active at Shot 5 NONE NO(0), YES(1) 1 NO

224 Phase OverCurrent 1st Reclosing Time NONE 0.1~1800 s 0.01 0.6

225 Phase OverCurrent 2nd Reclosing Time NONE 0.1~1800 s 0.01 2

226 Phase OverCurrent 3rd Reclosing Time NONE 0.1~1800 s 0.01 15

227 Phase OverCurrent 4th Reclosing Time NONE 0.1~1800 s 0.01 15

228 Ground OverCurrent 1st Reclosing Time NONE 0.1~1800 s 0.01 0.6

229 Ground OverCurrent 2nd Reclosing Time NONE 0.1~1800 s 0.01 2

230 Ground OverCurrent 3rd Reclosing Time NONE 0.1~1800 s 0.01 15

231 Ground OverCurrent 4th Reclosing Time NONE 0.1~1800 s 0.01 15

86 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(13/19)


Index Remark
Description Var
No. Range Step Default
232 Sensitive Earth Fault 1st Reclosing Time NONE 0.1~1800 s 0.01 0.6

233 Sensitive Earth Fault 2nd Reclosing Time NONE 0.1~1800 s 0.01 2

234 Sensitive Earth Fault 3rd Reclosing Time NONE 0.1~1800 s 0.01 15

235 Sensitive Earth Fault 4th Reclosing Time NONE 0.1~1800 s 0.01 15

236 Reset Time from Auto Reclose NONE 0.1~600 s 0.01 30

237 Reset Time from Lockout NONE 0.1~600 s 0.01 10

238 Reclosing Wait Time NONE 0.1~600 s 0.01 60

239 Sequence Coordination Function NONE OFF(0), ON(1) 1 OFF

240 Lockout Priority NONE PHASE(0), GROUND(1) 1 GROUND

241 Phase Inrush Restraint Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

242 Ground Inrush Restraint Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

243 Sensitive Earth Fault Inrush Restraint Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

244 Neg. Seq Inrush Restraint Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

Phase Pickup Current at Inrush Restraint


245 NONE 10~20000 A 1 2000
Duration

Ground Pickup Current at Inrush Restraint


246 NONE 10~20000 A 1 2000
Duration

Sensitive Earth Fault Pickup Current at Inrush


247 NONE 0.1~2000 A 0.1 20
Restraint Duration

Neg. Seq Pickup Current at Inrush Restraint


248 NONE 10~20000 A 1 2000
Duration

249 Phase Pickup Restore Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

250 Ground Pickup Restore Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

251 Sensitive Earth Fault Pickup Restore Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

252 Neg. Seq Pickup Restore Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

253 Inrush Restraint Minimum Response Time NONE 0.01~600 s 0.01 0.6

254 Phase Inrush Restraint Reset Current NONE 10~1600 A 1 500

255 Ground Inrush Restraint Reset Current NONE 10~1600 A 1 250

Sensitive Earth Fault Inrush Restraint Reset


256 NONE 0.1~160 A 0.1 10
Current

257 Neg. Seq Inrush Restraint Reset Current NONE 10~1600 A 1 500

258 Inrush Restraint Reset Time NONE 0.01~600 s 0.01 0.6

ENHANCED TECHNOLOGY 87
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(14/19)


Index Remark
Description Var
No. Range Step Default
259 Outage Time for Inrush Restraint Function Active NONE 0.01~600 s 0.01 5

Outage Current for Inrush Restraint Function


260 NONE OFF(0), 1~630 A 1 2
Active

261 Inrush Restraint Function Active using Current NONE NO(0), YES(1) 1 NO

262 Phase TC Curve at Inrush Restraint Duration NONE Note 1) 1 41

Phase Time Dial for TC Curve at Inrush Restraint


263 NONE 0.01~15 0.01 1
Duration

Phase Time Adder for TC Curve at Inrush Restraint


264 NONE 0~600 s 0.01 0
Duration

Phase Minimum Response Time at Inrush Restraint


265 NONE 0~10 s 0.01 0
Duration

266 Phase Reset Method at Inrush Restraint Duration NONE INST(0), LINEAR(1) 1 INST

267 Ground TC Curve at Inrush Restraint Duration NONE Note 1) 1 41

Ground Time Dial for TC Curve at Inrush Restraint


268 NONE 0.01~15 0.01 1
Duration

Ground Time Adder for TC Curve at Inrush


269 NONE 0~600 s 0.01 0
Restraint Duration

Ground Minimum Response Time at Inrush


270 NONE 0~10 s 0.01 0
Restraint Duration

271 Ground Reset Method at Inrush Restraint Duration NONE INST(0), LINEAR(1) 1 INST

272 Neg. Seq TC Curve at Inrush Restraint Duration NONE Note 1) 1 41

Neg. Seq Time Dial for TC Curve at Inrush


273 NONE 0.01~15 0.01 1
Restraint Duration

Neg. Seq Time Adder for TC Curve at Inrush


274 NONE 0~600 s 0.01 0
Restraint Duration

Neg. Seq Minimum Response Time at Inrush


275 NONE 0~10 s 0.01 0
Restraint Duration

Neg. Seq Reset Method at Inrush Restraint


276 NONE INST(0), LINEAR(1) 1 INST
Duration

277 Multiple of Cold Load Pickup NONE 1~5 xMTC 0.1 2

278 Cold Load Pickup Duration Time NONE 1~720 m 1 10

279 Cold Load Pickup Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

280 Cold Load Pickup Function Active using Current NONE NO(0), YES(1) 1 NO

88 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(15/19)


Index Remark
Description Var
No. Range Step Default
OFF(0), TRIP(1),
281 Broken Conductor (46BC) Function NONE 1 OFF
ALARM(2), TR&AL(3)

282 Broken Conductor (46BC) Pickup Level(I2/I1, %) NONE 1~100 % 1 5

283 Broken Conductor (46BC) Minimum Current NONE 1~630 A 1 60

284 Broken Conductor (46BC) Time Delay NONE 0~600 s 0.01 4

285 Broken Conductor (46BC) Maximum Current NONE 10~1600 A 1 500

OFF(0), TRIP(1),
286 Under Voltage1 (27-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)

287 Under Voltage1 (27-1) Pickup Level NONE 0.1~1.4 xVT 0.01 0.8

288 Under Voltage1 (27-1) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1

289 Under Voltage1 (27-1) Time Delay NONE 0~600 s 0.01 5

290 Under Voltage1 (27-1) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P

OFF(0), TRIP(1),
291 Under Voltage2 (27-2) Function NONE 1 OFF
ALARM(2), TR&AL(3)

292 Under Voltage2 (27-2) Pickup Level NONE 0.1~1.4 xVT 0.01 0.8

293 Under Voltage2 (27-2) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1

294 Under Voltage2 (27-2) Time Delay NONE 0~600 s 0.01 5

295 Under Voltage2 (27-2) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P

OFF(0), TRIP(1),
296 Over Voltage1 (59-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)

297 Over Voltage1 (59-1) Pickup Level NONE 0.1~1.4 xVT 0.01 1.1

298 Over Voltage1 (59-1) Time Delay NONE 0~600 s 0.01 5

299 Over Voltage1 (59-1) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P

OFF(0), TRIP(1),
300 Over Voltage2 (59-2) Function NONE 1 OFF
ALARM(2), TR&AL(3)

301 Over Voltage2 (59-2) Pickup Level NONE 0.1~1.4 xVT 0.01 1.1

302 Over Voltage2 (59-2) Time Delay NONE 0~600 s 0.01 5

303 Over Voltage2 (59-2) Pickup Phase Type NONE 1P(0), 2P(1), 3P(2) 1 1P

OFF(0), TRIP(1),
304 Neutral Over Voltage1 (64N-1) Function NONE 1 OFF
ALARM(2), TR&AL(3)

305 Neutral Over Voltage1 (64N-1) Pickup Level NONE 0.1~1.4 xVT 0.01 0.5

306 Neutral Over Voltage1 (64N-1) Time Delay NONE 0~600 s 0.01 5

ENHANCED TECHNOLOGY 89
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(16/19)


Index Remark
Description Var
No. Range Step Default
OFF(0), TRIP(1),
307 Neutral Over Voltage2 (64N-2) Function NONE 1 OFF
ALARM(2), TR&AL(3)

308 Neutral Over Voltage2 (64N-2) Pickup Level NONE 0.1~1.4 xVT 0.01 0.5

309 Neutral Over Voltage2 (64N-2) Time Delay NONE 0~600 s 0.01 5

310 Under Voltage Auto Restoration Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

311 Under Voltage Auto Restoration Pickup Level NONE 0.1~1.4 xVT 0.01 0.95

Auto Close Time Delay when Voltage Normal


312 NONE 0~600 s 0.01 30
Restoration

Under Voltage Auto Restoration Function Reset


313 NONE DISABLE(0), ENABLE(1) 1 DISABLE
Time

314 Under Voltage Restoration Source Side NONE VS(0), VL(1), VS&VL(2) 1 VS

315 Under Voltage Restoration Phase Type NONE 1P(0), 2P(1), 3P(2) 1 3P

316 Over Voltage Auto Restoration Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

317 Over Voltage Auto Restoration Pickup Level NONE 0.1~1.4 xVT 0.01 1.05

Over Auto Close Time Delay when Voltage Normal


318 NONE 0~600 s 0.01 30
Restoration

Over Voltage Auto Restoration Function Reset


319 NONE 1~100 m 1 5
Time

320 Over Voltage Restoration Source Side NONE VS(0), VL(1), VS&VL(2) 1 VS

321 Over Voltage Restoration Phase Type NONE 1P(0), 2P(1), 3P(2) 1 3P

322 Under Frequency1 (81U-1) Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

323 Under Frequency1 (81U-1) Pickup Frequency NONE 45~65 Hz 0.01 58.5

324 Under Frequency1 (81U-1) Time Delay NONE 0~600 s 0.01 2

325 Under Frequency1 (81U-1) Reset Time NONE 0~600 s 0.01 2

326 Under Frequency1 (81U-1) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1

327 Under Frequency1 (81U-1) Minimum Current NONE 1~630 A 1 60

328 Under Frequency2 (81U-2) Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

329 Under Frequency2 (81U-2) Pickup Frequency NONE 45~65 Hz 0.01 58.5

330 Under Frequency2 (81U-2) Time Delay NONE 0~600 s 0.01 2

331 Under Frequency2 (81U-2) Reset Time NONE 0~600 s 0.01 2

332 Under Frequency2 (81U-2) Minimum Voltage NONE 0~1.4 xVT 0.01 0.1

333 Under Frequency2 (81U-2) Minimum Current NONE 1~630 A 1 60

334 Over Frequency1 (81O-1) Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

90 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(17/19)


Index Remark
Description Var
No. Range Step Default
335 Over Frequency1 (81O-1) Pickup Frequency NONE 45~65 Hz 0.01 62.5

336 Over Frequency1 (81O-1) Time Delay NONE 0~600 s 0.01 2

337 Multi-Bit A Protocol Function NONE DISABLE(0), ENABLE(1) 1 0

RS232-1(0), RS232-2(1),

338 Multi-Bit A Protocol Communication Port NONE RS485(2), 1 0

ETH1(3),ETH2(4)

339 Multi-Bit A Transmitting ID NONE 1~8 1 1

340 Multi-Bit A Received ID NONE 1~8 1 2

341 Multi-Bit A Communication Period NONE 10~60000ms 1 50

342 Multi-Bit A TCP/UDP Select NONE TCP(0), UDP(1) 1 0

343 Multi-Bit A TCP Port Number NONE 1~65535 1 21000

344 Multi-Bit A UDP Port Number NONE 1~65535 1 21001

345 Multi-Bit A Link IP Address 1 Oct NONE 0~255 1 0

346 Multi-Bit A Link IP Address 2 Oct NONE 0~255 1 0

347 Multi-Bit A Link IP Address 3 Oct NONE 0~255 1 0

348 Multi-Bit A Link IP Address 4 Oct NONE 0~255 1 0

Multi-Bit A Communication Link Time-out for NONE


349 1~60000 1 15
Ethernet Port

Multi-Bit A Receive Bit Pickup & Dropout NONE


350 1~100 1 10
Debounce

351 Multi-Bit A ID Error Debounce NONE 1~100 1 10

352 Multi-Bit A CRC Error Debounce NONE 1~100 1 10

353 Multi-Bit A Receive Error Debounce NONE 1~100 1 10

354 Multi-Bit A M/S Mode NONE SLAVE(0), MASTER(1) 1 0

355 Multi-Bit B Protocol Function NONE DISABLE(0), ENABLE(1) 1 0

RS232-1(0), RS232-2(1),

356 Multi-Bit B Protocol Communication Port NONE RS485(2), 1 0

ETH1(3),ETH2(4)

357 Multi-Bit B Transmitting ID NONE 1~8 1 1

358 Multi-Bit B Received ID NONE 1~8 1 2

359 Multi-Bit B Communication Period NONE 10~60000ms 1 50

360 Multi-Bit B TCP/UDP Select NONE TCP(0), UDP(1) 1 0

361 Multi-Bit B TCP Port Number NONE 1~65535 1 21000

ENHANCED TECHNOLOGY 91
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(18/19)


Index Remark
Description Var
No. Range Step Default
362 Multi-Bit B UDP Port Number NONE 1~65535 1 21001

363 Multi-Bit B Link IP Address 1 Oct NONE 0~255 1 0

364 Multi-Bit B Link IP Address 2 Oct NONE 0~255 1 0

365 Multi-Bit B Link IP Address 3 Oct NONE 0~255 1 0

366 Multi-Bit B Link IP Address 4 Oct NONE 0~255 1 0

Multi-Bit B Communication Link Time-out for


367 NONE 1~60000 1 15
Ethernet Port

Multi-Bit B Receive Bit Pickup & Dropout


368 NONE 1~100 1 10
Debounce

369 Multi-Bit B ID Error Debounce NONE 1~100 1 10

370 Multi-Bit B CRC Error Debounce NONE 1~100 1 10

371 Multi-Bit B Receive Error Debounce NONE 1~100 1 10

372 Multi-Bit B M/S Mode NONE SLAVE(0), MASTER(1) 1 0

373 Z0 Addmittance (21YN) Function NONE DISABLE(0), ENABLE(1) 1 DISABLE

374 Z0 Addmittance (21YN) Operation Type NONE G&B(0), G(1), B(2) 1 G&B

375 Z0 Addmittance (21YN) Directional Type NONE NONE(0), FOR(1), REV(2) 1 NONE

376 Z0 Addmittance (21YN) Minimum SEF Current NONE 0.1 ~ 160.0 A 0.1 1.0

377 Z0 Addmittance (21YN) Minimum 3V0 NONE 0.10 ~ 1.40 xVT 0.01 0.10

378 Z0 Addmittance (21YN) Time Delay NONE 0.00 ~ 600.00 sec 0.01 2.00

379 Z0 Addmittance (21YN) Reset Time NONE 0.00 ~ 600.00 sec 0.01 0.10

380 Z0 Addmittance (21YN) Forward(Right) Conductance NONE 0.02 ~ 500.00 mS 0.01 1.00

381 Z0 Addmittance (21YN) Reverse(Left) Conductance NONE 0.02 ~ 500.00 mS 0.01 1.00

382 Z0 Addmittance (21YN) Forward(Up) Susceptance NONE 0.02 ~ 500.00 mS 0.01 1.00

383 Z0 Addmittance (21YN) Reverse(Down) Susceptance NONE 0.02 ~ 500.00 mS 0.01 1.00

OFF(0), TRIP(1),
384 Neg. Seq Voltage1 (47-1) Fuction NONE 1 OFF
ALARM(2), TR&AL(3)

385 Neg. Seq Voltage1 (47-1) Pickup Level NONE 0.10 ~ 1.40 xVT 0.01 0.50

386 Neg. Seq Voltage1 (47-1) Time Delay NONE 0.00 ~ 600.00 sec 0.01 5.00

OFF(0), TRIP(1),
387 Neg. Seq Voltage1 (47-2) Fuction NONE 1 OFF
ALARM(2), TR&AL(3)

388 Neg. Seq Voltage1 (47-2) Pickup Level NONE 0.10 ~ 1.40 xVT 0.01 0.50

389 Neg. Seq Voltage1 (47-2) Time Delay NONE 0.00 ~ 600.00 sec 0.01 5.00

92 ENHANCED TECHNOLOGY
ETR300-R & EVRC2A–NT Communication Protocol MAP Configuration http://www.entecene.co.kr

Table 5. BASE DATA POINTS – ANALOG OUTPUT(19/19)


*. NOTE )
1) The range of points rated to TC curve is as follows;

Table 6. Recloser time-current operation characteristic setting range

*. The range, step and default of AO points may be different according to the version of Entec‟s Recloser
Control firmware.
*. Supported points may be different according to the option and version of controller.