26 41 00 Surge Protective Device
26 41 00 Surge Protective Device
PART 1 - GENERAL
1.1 SUMMARY
1.2 REFERENCES
1.3 SUBMITTALS
.1 SHOP DRAWINGS
.1 Submit shop drawings for product specified in this section.
.1 Provide verification that the SPD’s device complies with the
required UL 1449 SVRs.
.2 Provide actual let through voltage test data in the form of
oscillo-graph results for both the ANSI/IEEE C62.41 Category C3
(combination wave) and B3 (ring wave) tested in accordance with
ANSI/IEEE C62.45.
.3 Provide spectrum analysis of each unit based on MIL-STD-
220A test procedures between 50 kHz and 200 kHz verifying the
device's noise attenuation exceeds 50 dB at 100 kHz.
.4 Electrical/mechanical drawings showing unit dimensions,
weights, installation instruction details, and wiring configuration.
PART 2 - PRODUCTS
PART 3 - Surge protective device (spd)
PART 4 - Surge protective device is to be installed on the main distribution panel servicing outlets for electronic equipment and
the panel servicing the ABM with its associated equipment.
PART 5 - The SPD application covered under this Section include distribution and branch panel locations. The branch panel
located SPD shall be tested to demonstrate they are suitable for ANSI/IEEE C62.41 Category C1 environments.
PART 6 - The individual units shall be UL Listed under UL 1449 complimentary listed under UL 1283 and CSA Standards.
PART 7 - The UL 1449 surge ratings and CSA label shall be permanently affixed to the SPD unit.
.1 All surge protection devices in the switchboard and subpanels shall be from the same
manufacturer.
.2 Electrical requirements:
.1 Unit Operating Voltage: Refer to drawings for operating voltage and unit
configuration.
.2 Maximum Continuous Operating Voltage (MCOV). The MCOV shall be
greater than 115% of the nominal system operating voltage.
.3 Protection Modes. For a wye configured system, the device must have
directly connected suppression elements between line-neutral (L-N), line-ground
(L-G), and neutral-ground (N-G). For a delta configured system, the device
must have suppression elements between line to line (L-L) and line to ground
(L-G).
.4 Surge Current Capacity. Total surge current per phase (based on an
8x20 microsecond waveform) that the device is capable of surviving shall not be
less than 120 kA per phase, or 60 kA per mode on L-G, L-N and N-G modes
(Wye system); L-L and N-G (Delta system).
.5 UL 1449 SVRs. The manufacturer must provide certified UL 1449 SVRs
on all protected modes. The maximum UL 1449 SVR for the device must not
exceed the following:
.6 (SVR must be for complete device; modular only SVR are not
acceptable)
.7 ANSI/IEEE Cat C3 Let Through Voltage. The let through voltage based
on IEEE C62.41 and C62.45 recommended procedures for Category C3 surges
(20 kV, 10kA) must be included in the submittal package and shall be less than:
Modes
208Y/120 480Y/277 600Y/347
PART 9 - EXECUTION
PART 10 - installation
END OF SECTION