Product Introduction - Series MG: Rotary Power Conditioning System
Product Introduction - Series MG: Rotary Power Conditioning System
The motor will operate from a utility whose voltage ranges from 10% continuously high
to 20% continuously low, and can sag to -60% of nominal for up to 30 seconds. The
synchronous motor also presents a unity power factor load to the utility. The generator
produces utility grade voltage regulated to within 1%. This combination isolates the
customer and the utility from each other.
The customer can no longer be affected by sags, surges, transients, short term power
outages. The utility, because of the high power factor and linear current drawn by the
motor, can make better use of their transmission lines and is protected for any harmonic
currents drawn by the customer’s equipment.
Depending on the part of the country, short power outages are a major concern. Short
term power losses can be broken down into three classes:
The causes of these outages are the operation of protective devices located on the
utility network. Instantaneous outages are caused by a single fast recloser, the
momentary outage normally is one fast and two slow reclosures. These are the three
tries and out logic where after the third automatic reclosure, a line crew would be
dispatched. The temporary outages can have many causes. However, in each case,
the only means of a customer isolating themselves from these temporary outages is
with a UPS.
1
Power Systems and Controls
Richmond, Virginia USA
Series MG
Rotary Power Conditioning System
In general, and independent of location, power users have over a 90% probability that
the voltage will sag below 80% of rated voltage every month. In industrial
environments, this is a major cause of less than expected equipment reliability.
At one manufacturer’s plant, the estimated cost for repair of CNC controllers exceeded
$5,000 per month. After conducting power quality monitoring, it was determined that
the most likely cause of controller failures was the daily sags in the utility voltage
caused by motor starting. Dependent on the manufacturing process, voltage dips and
switching transients can cause complete process shutdown. In many cases where the
production equipment must be cleaned out before the process can be restarted, the
cost can be dramatically high.
In these cases, the Series MG was a cost effective solution. The true cost of power
quality was easily determined. Given a five year lease program, the monthly cost
avoidance paid the annual lease payment in five months. The savings over the next
seven months represented additional profit for the company.
2
Power Systems and Controls
Richmond, Virginia USA
Series MG
Rotary Power Conditioning System
Series MG Features
Optional Features
Standard Features
• Remote Annunciator Panel
• Brushless Synchronous Motor
• Remote Control Panel
• Brushless Synchronous Alternator
• Modem & Serial Port
• Bearing Temperature Sensor
• Maintenance Bypass
• 10% Output Voltage Adjustment
• Paralleling Capability
• Over/Undemgrequency Protection
• Circuit Breaker In Bypass Path
• Over/Under Output Voltage Protection
• Outdoor Enclosure
• Output Meters (voltage & current)
• Sound Enclosure
• Status Indicator Lights
• Auto Bypass Function Packaging
• Touch Screen Digital Control Panel
• Integrated, Free Standing Metal
• Maximum Vibration Level 2.0 mils
This panel can be used to control and monitor the MG. All voltages and currents within the MG are
available via this panel.
The following metered functions are The touch screen control panel can
shown: pemgorm the following functions:
3
Power Systems and Controls
Richmond, Virginia USA
FEATURE DESCRIPTION
Remote Monitor/Control Panel
This panel can be used to control or monitor the MG. The remote control panel requires
the optional RS-485 serial port. All voltages and currents within the MG are available
via this panel. All functions of the touch screen control panel are duplicated in the
remote monitor/control panel (see above).
This panel is used to give the user an indication of a fault in the motor generator at a
remote location. It contains annunciation, alarm reset button and an ESTOP push-
button.
Modem
A modem connection is available for users wishing PS&C to monitor the status of their
motor-generator. A dedicated telephone line is attached to the modem and data is
passed via an RS-232 port in the M-G's PLC to a modem. All vital MG parameters and
fault conditions can be monitored by PS&C’s Field Service.
Serial Port
The serial port, either RS-485 or RS-232, is available to communicate all pemgormance
data, fault and status data to the user's computer monitoring system, SCADA.
Monitoring software, sold by PS&C, is required to present this data to the user's
computer. The use of PS&C's software, the serial port option and the user's computer,
form a powemgul remote monitoring function. The user will need an RS-485 to RS-232
converter for terminating at the computer when the RS-485 connection is used.
An automatic circuit breaker can be supplied to provide protection for wiring and loads
to be connected to the bypass path when other protective elements are inadequate.
This optional circuit breaker replaced the standard contactor used for bypass transfers.
Benefit
Synchronous motors naturally run at their synchronous speed, which is 1,800 RPM for
60 Hz applications. This constant speed is maintained across a wide range of voltages
and independent of load. While synchronous motors cost more than induction motors,
the stable output frequency more than compensates for the added cost. If induction
motors were used, the M-G would run faster or slower as the utility voltage sagged or
surged. The M-G would also speed up or slow down as the customer’s load increased
or decreased.
The synchronous generator with its 2/3 pitch winding produces utility grade voltage with
the ability to cancel the triplen harmonics. This ensures that the customer has the same
high grade power their processes were designed to operate on.
Feature
Benefit
The advantage of a synchronous motor is its constant speed. The disadvantage is that
it is very hard to start. If it were placed across the line, it could take as much as ten
times its full load current just to get it up to speed. The Series MG’s pony motor is a
small induction motor selected to be large enough to spin the unloaded motor and
generator up very close to synchronous speed. The maximum current required for the
pony motor is never greater than 1.5 times the full rated current of the main machine.
This means that the electrical service does not have to be oversized to allow for
starting. Also, using the pony motor prevents voltage sags to other customers on the
same service during start-up of the M-G.
The pony motor is connected to the main machine with belts, which are selected to
break in the event of a pony motor failure. This is to avoid a standard, off the shelf
induction motor being the reason an M-G trips off line. If there were a failure in a pony
motor bearing, a new motor could be shipped and installed the next time the M-G was
conveniently shut down.
Feature
Benefits
When the M-G is used as a power conditioner, the use of separate machines allows the
motor to be selected for the real power needed to support the load. The generator can
be selected for power quality. In cases where the customer’s load is rich in harmonics
or has a low power factor, a larger generator is used. The large generator is better able
to start motors, furnish nonlinear current, or high reactive power without impacting the
voltage quality. This can be thought of in the same way that power customers closer to
the power station have better voltage quality than the ones at the far end of the line.
The energy stored in the rotating inertia of the M-G set provides ride-through allowing
the M-G to carry the critical load over many utility disturbances or interruptions. The
synchronous motor has substantial ability to continue operation during temporary single
phase conditions. In addition, the synchronous motor can carry full load while
remaining in synchronism with the utility, even when the utility voltage drops to very low
values - levels that the majority of electric power utilization equipment is not expected
to, and cannot, tolerate. This means that the M-G set can provide quality power to the
protected load during brownouts and for voltage sags to relatively low utility voltage
levels. Quality power means that the utilization equipment is provided with rated
frequency and voltage, even during a utility brownout and during many utility voltage
sags.
1) Voltage Spikes
2) Single Phase
In applying the Series MG, the voltage droop category is the most important. This is
because of the substantial ability of the M-G to tolerate and handle voltage spikes and
single phase conditions.
Additionally, the “clean break” power loss is a relatively rare occurrence. The M-G also
has significant ability to handle these when they are of short duration, a capability we
will expand on later. For very long utility outages, considerably more energy storage is
required than an M-G can provide. These situations require battery or fuel energy
storage or both. For applications requiring these measures, PS&C can also provide
high quality, reliable equipment.
VOLTAGE SPIKES
Lightning causes voltage spikes by inducing large, but very short overvoltages on the
utility. Additionally, when switching events occur on utility distribution systems, longer
duration transients occur, which may be a combination of under and overvoltage.
Some types of electrical equipment can tolerate the majority of these transients without
malfunction or damage, but not computers. The M-G protects equipment from this type
of disturbance because it provides electrical isolation between utility power and the
equipment. The motor and generator used are physically separated. Consequently, the
protected generator load does not see voltage spike transients.
Distribution systems can usually provide a degree of protection against voltage spikes.
The quality of the insulation system of the motor is such that other loads on these
utilities are usually affected before the M-G. This is also true if the transient is of
excessive duration because the M-G inertial energy has the ability to “soak up”
considerable transient energy.
SINGLE PHASE
In a three phase system, one of the three supply lines may be lost through the action of
a protective device, e.g., a single fuse opening up. The result is single phase voltage
being applied to the motor stator. A lightly loaded system may run undisturbed
indefinitely and the synchronous motor may even carry loads approaching full load for
some period of time, although it is likely that some motor overheating may result.
Correcting the single phase condition will require resetting a protective device or
replacing the fuse up line from the synchronous motor. Single phase conditions are
readily detectable. Commercially available devices may be used to detect and
enunciate the condition, thus initiating the corrective action. The M-G synchronous
motor can, in a great number of cases, provide the time needed for the user to have the
single phase condition corrected while still supplying quality power to the critical load.
VOLTAGE DROOP
One variety of a voltage droop is the voltage sag that can occur on a utility distribution
system and may persist for a matter of seconds. These may be caused by distribution
system faults somewhere other than the user location. This is a prevalent type of utility
Another variety of voltage droop is a called a brownout. The utility voltage reduction
during a brownout is not as severe in magnitude as that which may occur during a
voltage sag. Utility distribution system’s protection normally operates if brownout
reductions are less than 85% of rated voltage and persist for any significant period of
time. Synchronous motors have no trouble providing the torque and speed required for
the generator to provide rated quality power to the computer at these voltage reduction
levels. The motor draws more current to do this, however, and this must be considered
in the selection of input circuit protection for the motor.
POWER LOSS
A rapid drop of utility voltage to near zero is a power loss. An example of such a loss
would be the rapid opening of a three phase circuit breaker immediately up line of the
synchronous motor. When this happens, utility power flow to the motor is quickly cut off
and the energy source necessary for the generator to supply electric power to the
computer load is the inertial energy of the M-G set.
This type of utility disturbance is relatively rare as compared to the voltage droop. It
usually occurs due to a temporary fault on the utility line, and in response, a protective
switchgear briefly opens the line and then tries to reconnect utility power. Utility
experience demonstrates that more than 80% of these temporary faults have
disappeared by the time utility power is reconnected. The great majority of the
interruptions caused by the action of the protective utility switchgear are five cycles or
about 80 milliseconds long. In the rarer cases, the protective switchgear may interrupt
power for up to 500 milliseconds. As will be explained later in this article, a loaded M-G
continues providing power using its inertial energy and doesn’t really pull out of
synchronism with the utility for the shorter interruptions.
For the maximum interruptions, the energy the M-G delivers to the load reduces its
speed and therefore degrades the frequency. However, rated generator voltage is
maintained and PS&C’s experience shows that computers stay online, even for the
longer utility interruptions. What has been shown is that PS&C’s M-G provides
immunity to a substantial majority of types of utility disturbances. In order to better
understand the M-G’s capabilities, and in particular, the value of these capabilities in
providing reliable power, it is worthwhile to consider further what happens during
“voltage droops” and “power losses”.
Motor thermal capacity is also a consideration during such voltage sags. Motor stator
conductor losses during this test were almost 280% of rated. Providing adequate
thermal overload protection for the motor in such an application would be required if
very long voltage sag conditions were likely. For the 85% rated voltage extreme of a
brownout condition, the M-G synchronous motor would have the thermal capability of
operating for several hours.
Knowledge of the severity and duration of utility voltage droops is valuable information
in the application of M-G’s to a customer’s facility. PS&C’s successful experience in
M-G applications can be put to optimum use when such utility information is available.
It is useful to have a physical picture of what happens in the synchronous motor as the
motor is loaded and as motor terminal voltage is reduced at a constant load. If it were
possible to ride the peak of the synchronous motor stator flux wave, which rotates at the
motor synchronous speed locked to the utility frequency, we would find ourselves
looking at the center of the rotor field pole. From our position on the stator flux wave,
the rotor pole would appear stationary. As full load torque was applied to the
synchronous motor rotor, we would see the center of the rotor pull falling back
approximately 15-20 electrical degrees just as if the rotor were connected to the stator
flux wave by strong rubber bands. This rubber band connection is the effect provided
by the flux coupling between the synchronous motor rotor and the stator flux wave.
Under normal conditions, the 15-20 electrical degree fall back, called the synchronous
motor load angle, is maintained and the rotor operates in synchronism with the stator
flux wave, which is itself in synchronism with the utility frequency. Now let’s “turn down”
the utility voltage in the same manner that takes place during a voltage sag. As the
utility voltage decreases, the spring constant of the flux rubber bands between the stator
flux wave and the rotor is reduced. We could say that these flux rubber bands become
more springy. As a result, they are stretched and the motor load angle increases. As
we sit on the peak of the stator flux wave, we see the center of the rotor pull falling back
further behind us but still staying stationary and in synchronism with the stator flux wave
The protected load is totally unaffected by these extreme events. The synchronous
motor can maintain this condition for a long period of time, as long as its thermal
capacity is not exceeded. Another requirement is that protective devices are not
triggered by the higher synchronous motor current levels. We can simulate the end of
the voltage sag by “turning up” the motor voltage. In this case, the flux rubber bands
become less springy, thus pulling the motor towards us as we ride the peak of the stator
flux wave, reducing the motor load angle. As we reach rated utility voltage, normal
operation is restored with no disturbance to the critical load’s power.
What if the utility voltage drops too low? If this occurs, we can visualize the flux rubber
bands becoming so springy that they “break”. This is called pulling out of step. For all
practical purposes, when the utility voltage is low, we can say that the utility power can
no longer support the computer load. As a matter of fact, the utility would not have
supported the critical load at a considerably higher voltage level were it not for the
presence of the synchronous motor and generator applied in the M-G.
To summarize the above, the synchronous motor flux rubber bands keep the
synchronous motor synchronized with the utility line down to voltages of 60% of rated or
less while the M-G supplies rated voltage frequency and power to an uninterrupted
computer operation.
Now let’s see what happens in the synchronous motor during a power loss. Once
again, we are operating under rated conditions and riding the peak of the stator flux
wave. Our hypothetical circuit breaker opens and suddenly, both the flux rubber bands
and the stator flux wave we were riding are gone. To really follow what goes on, we
also need a hypo-thetical reference stator flux wave to tell us where the utility frequency
and phase will be whenever it comes back. We know that electrical utilities are linked in
a network that stretches across the United States. Consequently, when power is
reconnected, it will come back at exactly a standard 60 Hz frequency and in phase with
our hypothetical reference stator flux wave, which has been rotating at synchronous
speed during the interruption just as though nothing had happened. For all practical
purposes, we are now riding the peak of the reference stator flux wave. We note that
the rotor is falling away behind us but not very rapidly. We know that it didn’t stop
instantly because it has rotating inertial energy (I/2 x I x Omega squared that describes
rotating flywheel action) and that it is now supplying the energy needed by the generator
by slowing down. This rotating inertial energy is the other tool in the kit we referred to
in the paragraph above for the five cycles or 80 millisecond interruption described
earlier and which is most prevalent on utility systems.
The rotor fall back is typically about 60° or less when the input voltage returns. Under
these conditions, the rotor quickly pulls forward as the flux rubber bands are
What we have just described is known as synchronous ride-through. The rotor has
slowed down to supply the energy needed by the generator, but not rapidly, and the fall
back angle only reached 60 electrical degrees or less. While mathematically we can
say that a change of the angle in a period of time is a frequency change, for all practical
purposes, the generator frequency never really deviated from synchronous, rated
voltage and power was delivered and the load was never interrupted.
Now let’s suppose the power loss period is longer, up to 500 milliseconds. For full load
on the generator, we will have exceeded a 60o fall back. Additionally, the synchronous
motor rotor speed will be noticeably below synchronous at the time of the return of utility
voltage. Under these circumstances, the synchronous motor operates as an induction
motor utilizing its amortiser windings, which are “cage windings“ like those utilized on
induction motors. PS&C installs a device that protects the synchronous motor field
during this mode of operation. The synchronous motor accelerates as an induction
motor to a near synchronous speed. At this point, the protective device re-enables the
synchronous motor field and the motor quickly pulls into a surge of synchronous motor
current approaching the motor locked rotor current has occurred during the induction
motor acceleration, but as before, this is a relatively brief period of time.
Generator voltage and power output have been maintained at rated during this long
utility power loss disturbance, and although the generator frequency has decreased
during this time, PS&C has ample experience showing that the M-G’s maintain
computers online up to 500 milliseconds with full load maintained on the generators.
For application purposes, we can quantify the effect of a flywheel or inertial energy.
This is true because the product of the real load on the M-G set and the time period of a
power loss interruption is proportional to the product of the rotor RPM2 and the inertia or
WK2 of the M-G rotors. The power x time product is normally expressed in kilowatt
seconds. We can make a ratio of the rotor WK2 to the generator load kilowatts. We also
need to account for the M-G losses and thus need to reduce the effect of the WK2 by
the efficiency of the M-G. Taking into account these three parameters, we can define an
X factor as shown above.
Where
η = efficiency
WK 2 = Rotor inertia
KW = ℜ Load
Figure 1, which is an M-G application aid, shows the average generator frequency
Ride Through
during a power loss interruption vs. the interruption time in milliseconds for X factor
ratios of 1, 12 and 2.
Incidentally, the M-G’s represented on this curve will hold a rotor fall back angle of less
than 60° for interruptions six cycles long with full load on the generators.
When the utility line opens, this rotor locked flux generates a voltage at a frequency
corresponding to the speed of the motor rotor. If there is load on the utility lines up-line
of the motor, but down-line of the power break that has occurred, the motor acting as a
generator may supply this load from its store of inertial energy. When this happens,
energy that was intended to keep the critical load online is diverted to an up line load;
the result is that the effective ride-through of the unit is reduced. For a synchronous
motor whose field is typically excited during the power disturbance, this power feedback
can be greater and last longer. For voltage droop, voltage or power feedback is not a
significant factor. Only the voltage that the utility can’t maintain during this situation
determines the ability of the M-G to keep the critical load online. As previously stated,
the M-G tolerance for low voltage operation is significant.
In those unusual applications where power loss occurrences are significant, power
feedback has the capability of reducing effective ride-through and therefore the length of
power disturbance that the M-G can tolerate. For those applications, PS&C can apply a
device that will effectively detect reverse power flow, thus allowing the application of a
fast power switch to quickly interrupt the power diverted by these parasitic up-line loads.
In summary, M-G’s have the ability to immunize sensitive electrical loads from the four
major categories of utility disturbances: voltage spikes, single phasing, voltage droops
(including sags and brownouts) and power losses. The M-G’s are particularly effective
against the most common of these disturbances, the voltage droop. Drawing on a
wealth of successful experiences with motor-generators, PS&C can supply valuable
application information and also assist in the application of these economical and
effective UPS system power continuity problems. PS&C also has the capability to
detect power feedback and to provide corrective control action in situations where
power feedback is a significant factor.
FUNCTIONAL DESCRIPTION: The M-G set and associated controls shall provide a
means of electromechanically isolating, and filtering disturbances in the AC power
source from the electronic data processing systems.
PHYSICAL DESCRIPTION: The M-G set shall consist of the following elements:
CONTROLS: The M-G set shall be equipped with the following controls:
1. Motor Control: START switch at the M-G set, which activates the
reduced current motor starter.
The M-G set shall be equipped with a pony motor type starter that reduces
the starter that reduces the starting inrush to less than 1.5 x nameplate
amperage.
• Output Overvoltage/Undervoltage
• Starter Overload
• Output Undemgrequency - Shutdown Only
• Motor Overload
• Motor Overtemperature
• Motor and Generator Bearing Overtemperature
• Motor On
• Load On
• System Bypass
• System Fault
INPUT:
Frequency 60 Hz
OUTPUT:
Transient Voltage + 8%
Regulation
50 step load
MOTOR-GENERATOR BEARINGS
Power Systems & Controls Series MG motor generator contains four (4) bearings. Each
bearing requires annual lubrication to insure maximum bearing life. Our Standard
Warranty provides replacement of any failed component during that period.
Bearings supplied by Power Systems & Controls are expected to provide trouble free
Service for a minimum of ten (10) years. Average bearing life exceeds twelve (12) years,
and we do not recommend a replacement of bearings at any fixed time. Our Series MG
motor-generator has temperature monitors installed in each bearing chase, and will give
notice of bearing problems long before a failure. Only when detected should bearings be
replaced.
The Power Systems & Controls Total Maintenance Contract will cover replacement of a
failed bearing, provided the system has been under our Maintenance contract for at least
three years prior to a failure. We will provide bearing replacements under a Time And
Materials Contract for systems not under contract.
Where
2
J MG = Combinded Motor - Generator Inerria (lb - ft )
ω I = Initial rotational velocity (radians)
P l = Power load
P P = Parasitic load (kW)
P I = Internal losses (kW)
P T = P L + P P + P I (kW)
Assume P I = 10% • P L or actual losses
ω 2 = End of event velocity
1.475 PT t
( π f 1 ) - ( π ft 2 ) =
2 2
Substituting electrical frequency for mechanical frequency
J MG
0.1495 PT t
f 12 - f 22 = J MG supplies by vendor in lb - ft
2
J MG
2 2
lb - ft must be converted into lb - ft _32.2
4.814 PT t
f 22 - f 12 = Equation is now dimensionally correct
J MG
4.814 PT t
f 22 = f 12 -
J MG
and
∆ω ∆2 ω
T = J MG α = J MG = J MG
∆t ∆ t2
Θ = Θ0 + ωt + ‰α t 2
Equation of Motion
T
φ = t2
J MG
Θ = φ/2 Mechanical to electrical
⎛ PT ⎞
T 737.6 • 32.2 ⎜ ⎟
Θ = ‰ = ⎜ J MG ⎟ t 2 J MG = J MGOVER 32.2
φ 2π 30 ⎜ ⎟
⎝ ⎠
126 PT t 2
φ =
J MG
737.6 PT
T =
2πI30
2πI30 = 1800 RPM converted to milliseconds
Where:
φ = Resultant electrical phase displacement
t = milliseconds
PT = Killowatts
2
J MG = lb - ft
Where:
t = milliseconds
PT = Killowatts
2
J MG = lb - ft
f = electrical frequency
The above equation defines the end frequency from the generator, but is not in a form
that leads to a solution.
4.814 PT t
f2 = f 12 -
J MG
1.26 • 10 -4 PT t 2
Recall φ =
J MG
PT φ
Rewrite =
J MG 1.26 • 10 -4 t 2
38.206 φ
f2 = f 12 - Equation used to determine ride - through for motor - generator
t
Recall
1.26 • 10 -4 PT t 2
φ =
J MG
Timing
Shunt Trip = 15 - 20 mSec
PLC Scan _ 10 mSec
Detection Time = 9 mSec
Given:
2
J MG = 1399 lb - ft
P L = 800 kW
PP = 0
P I = 80 kW
φ ≤ 1 Radian, limit imposed by surge current upon return of utility voltage
F 1 = 60 hz
Note: Inertia values for pony motor and miscellaneous are not included.
φ J MG
t =
1.26 • 10 -4 PT
1 • 1399
t =
1.26 • 10 -4 • 880
4.814 PT t
F2 = f2 -
J MG
t min to 58 hz = 20 mSec
P max = 3429 kW
PL = 800 kW, P I = 80 kW, P P = 2549
Note: The maximum parasitic load (PP) is found by this method. Larger parasitic
loads will cause the frequency of the generator to be below our imposed limit of
57 hz. Larger parasitic loads cause the input circuit breaker to the motor-
generator to trip on return of the utility voltage.
• Load On
• System Bypass
• System Fault
• Audible Alarm (sounds when any of the above fault
conditions occur)
QUALITY
All materials, parts, and components used will be new and of high grade.
TESTING
The total system will be exposed to a functional and load test and will be subject
to a factory full load test prior to shipment. Tests conducted at 1.0 P.F.
Power Systems & Controls will furnish dual input synchronous isolation system(s)
with a 900 amp (750 kVA, 600 kW) continuous rating.
FUNCTIONAL DESCRIPTION:
This system shall provide continuous, isolated and filtered power to the protected
load with two (2) synchronous motor-generators. These machines will each be
connected to different utility feeds. During normal operation, the motor-
generators will operate in parallel, sharing the load and drawing equal amounts of
energy from each utility source. The motor-generators will each be rated at 750
kVA.
In the event of a failure of one of the two sources, the system logic will detect
reverse power from the motor connected to the failed feeder. The system control
will, within 40 sec., open (trip) the electrically operated input circuit breaker
preventing back feed to the failed source. Transfer control logic will then close
an alternate source circuit breaker, connecting both motor-generators to the
remaining feeder. During the detection and transfer time, the machine connected
to the remaining utility source assumes 100 % of rated system load (900 amps).
This places a worst case overload equal to 150% of the rated continuos capacity
of one motor-generator.
On closure of the alternate feed tie circuit breaker, the second system draws a
small additional current to reaccelerate the motor to reach the same power angle
as the loaded system. The detection, opening, and reclosure/transfer time is
less than two seconds. The total overload time for the loaded machine is less
than two seconds, which is well within the thermal limits of the machine that is
rated for 150% for 30 seconds.
During the time of the source transfer, the motor-generator uses its mass and
inertia to buffer the protected load from any variations in voltage or frequency
during the input source transfer.
The dual feed synchronous isolation system shall consist of the following self
contained elements:
Each element of the system shall be capable of being installed separately from
the other components of the system to facilitate system installation and
maintenance in existing facilities.
ELECTRICAL CHARACTERISTICS:
INPUT:
H. Transient Voltage + 8%
Regulation
50% step load
TRANSFER CONDITIONS:
The system shall transfer from the preferred power source to the alternate power
source for the following conditions:
The system shall inhibit transfer to the alternate source for the following
conditions:
RETRANSFER CONDITIONS:
TRANSFER TIME:
Transfer Sensing Time - Maximum transfer sensing time for loss of preferred
source voltage shall be 2 seconds or less.
CONTROLS:
The following controls shall be furnished on the front of transfer system cabinet:
a. Output Overvoltage/Undervoltage
b. Starter Overload
c. Output Under Frequency - Shutdown Only
d. Motor Overload
e. Motor Overtemperature
f. Motor and Generator Bearing Overtemperature
INDICATORS:
The following functions shall be monitored and indicated with lights on the front
panel of the system control console:
The following functions shall be monitored and indicated with lights on the front of
the control console:
• Motor On
• Load On
• System Bypass
• System Fault
Remote Monitor: The system shall have a separate desk top alarm panel which
includes the following monitoring and alarm functions:
• Load On
• System Bypass
• System Fault
• Audible Alarm (sounds when any of the above fault conditions occur)
The following functions of the system shall have alarm contacts (SPDT 2 Ampere
rating) available for connection to purchaser’s alarm system:
DESIGN:
System Controls:
Motor-Generator (M-G):
CONSTRUCTION:
Enclosure: The transfer system shall be housed in a code gauge steel, NEMA
1 enclosure requiring access from the front for all servicing
adjustments. Access shall be through a hinged door with a tumbler
lock and latch handle. The enclosure shall be primed and painted
inside and outside with a suitable semi-gloss enamel. The
enclosure shall be either of the wall mount or free-standing floor
mount design.
COOLING:
Cooling shall be by natural convection or forced air by fans. If forced air cooling
is used, then the fans shall be protected with individual fuses so that if a problem
develops in one, it will not affect others. Natural convection cooled modules may
require rear clearance for adequate air flow.
ENVIRONMENTAL CHARACTERISTICS:
OPTIONAL FEATURES:
Sound Enclosure: The M-G sets will be equipped with a sound attenuation
device to reduce noise emission to less than 65 dBa at 2 meters
free field. The
Exhaust Silencer: The M-G sets will be equipped with a sound attenuation
device to reduce exhaust noise emission to less than 78 dBa at 2
meters. The device will be an integral part of the M-G assembly.
TESTING:
The total system will be exposed to a functional and load test and will be subject
to a factory full load test prior to shipment. Tests conducted at 1.0 P.F.
This section has been intentionally left blank. This section will be completed in
accordance with the specific requirements set forth by NIPSCO.
This section has been intentionally left blank. This section will be completed in
accordance with the specific requirements set forth by NIPSCO.
Local Service
Power Systems & Controls maintains a factory technical support service center in
Richmond, VA and local first response via
This operation is on call and available 24 hours a day, seven days a week, 365
days a year. This organization has the ability, training and over sixty years of
experience servicing PS&C UPS systems to insure that this site will receive the
best possible service. PS&C also maintains a local service operation in which is
able to respond on-site to needs within four hours. Service descriptions are as
follows:
Power Systems & Controls' provides seven days a week, 24 hour a day hotline
support for any PS&C customer whether covered by Power Systems & Controls'
warranty or a service contract.
Power Systems & Controls' service mission is to respond to all trouble calls with
a trained technician/engineer within 30 minutes of the time the call is received.
The technician returning the customer’s phone call will be fully trained and versed
in the customer’s equipment.
In all cases, Power Systems & Controls' customers are directly in the decision
making loop as to what is an appropriate response and the time in which service
can be delivered which best serves Power Systems & Controls and our
customers.
Power Systems & Controls warrants its equipment to be free from manufacturing
defects for a period of 12 months from date of bring-up or 18 months from date of
shipment for all commercial sales. Standard warranty statements from PS&C are
contained in this section.
In addition to the base warranty, PS&C provides two types of product support for
its systems.
PM
The majority of the PM work required to maintain the reliability of your system
can be pemgormed by your staff if they are properly trained. Training is available
at our Richmond VA factory at a nominal charge. Our belief is regular PM
service by a factory field engineer is best for critical power systems. In addition
to the inspections and actions listed above, our factory representative brings with
him years of experience with similar systems. His on site knowledge of PS&C
equipment and its operational characteristics is invaluable in spotting problems
and equipment trends. With this in mind, we have priced our PM service
aggressively to encourage all owners of our power conditioning systems to take
advantage of factory PM service.
FSM
Full Service Maintenance of your system provides you with factory service and
repair of any component for the contract period. Should any component fail it
will be replaced at no additional charge to you. Emergency service is provided
24 hours per day, 7 days per week at no additional charge. Scheduled repairs
will be made during normal business hours. No additional charges for travel,
Exclusions from our FSM program are simple. They include Acts of God, abuse,
severe overload, environmental events (such as earthquake, flood, temperature,
etc.), manmade disaster (war, riot, etc.) and lightning.
FSM contract periods are available on a contract basis for a long as the
equipment is in service. Pricing for FSM service will be reviewed every three
years and will remain firm during the period of coverage. Contract periods as
short as one year are available.
The courses range from basic system operation for your facilities personnel to
operation theory for your engineering department. We also offer a short course for
your computer operation personnel.
The computer operator course is geared to educate your personnel on the system
which will be protecting your critical load. Instruction is given on the remote monitor
and what actions are required for each alarm, who to contact and what information
they should gather prior to calling for assistance.
PS&C's field engineers will work with your operations staff to develop an emergency
procedure tailored to both your operation and the qualifications of your personnel.
The second level of training offered, is geared towards the people who will operate
the power system.
This course communicates the operating plan developed by your staff. This opens
lines of communications between your people and PS&C's field service group.
Equipment operators are instructed in transferring the critical load from protection
power to normal utility for equipment maintenance. Upon completion your staff
should be able to:
This course is held in your facility on your equipment, and allows your people to
develop procedures and check lists during the course which will be used during the
equipment service life. PS&C offers this training on completion of system start-up,
before committing systems to critical load.
This allows your people to operate the equipment without endangering your critical
load.
The third level of training PS&C can provide is an in depth course on the equipment.
This course covers all the fundamentals for the circuits and systems contained in
your system. Each major section is broken down and explained.
1. Replace components
2. Pemgorm electrical maintenance
3. Pemgorm all function presented in the level 2 course
The goal of this program is to explain the operation of the system to computer room
personnel and operational requirements to the facilities department. Site personnel
who will be operating the system should have a basic understanding of electrical
systems
and circuit breaker operation.
1. Theory of operation
This course may be adapted to the type of personnel the customer elects to send to
the course or the depth that the customer would like to train their personnel.
The goal of this program is to explain the operation of the system to computer room
personnel and operational requirement to the facilities department. Site personnel
who will be operating the system should have a basic understanding of electrical
systems
and circuit breaker operation.
1. Theory of operation
The course is intended to fill the needs of the customers project, and may be
adapted to the type of personnel the customer elects to send to the course or the
depth that the customer would like to train their personnel.
I. Classroom Work
I. General Summary
II. Customer Questions