Technical Data Sheet (Triad Cable For Gas Detector)
Technical Data Sheet (Triad Cable For Gas Detector)
11 OUTER SHEATH
HR PVC compound (Type-ST2), conf. to IS: 5831/84 with FRLS
a) Material properties
b) Type Extruded
c) Thickness(Min) mm 1.24 mm
Overall Diameter (approx) mm 12.5 mm
d) Colour of outer sheath Black
Marking on outer sheath SRTL SIZE & TYPE 600 V, shelded, Armoured, FRLS Instrumentation Cable MFY-
e) 2021 with Meter Marking
Drum Length (Packing shall be done 3 drums of 1000 mtrs with +/-5% tolerance and1 drum of 700 mtrs with +/-5%
in nonreturnable wooden drum) mtrs toleranceNOTE: The payment shall be made for the supplied restricted to PO
12a) quantity of 3700 mtrs.
Tolerance on individual drum length
b) %& overall quantity (+/-5 %)
13 ELECTRICAL PARAMETERS
Max. DC resistance of
a) conductor of Ω/Km completed cable at 20 12.3
Deg. C
Max. mutual capacitance of pairs or pF/mtr 250
b) adjacent core at 1KHz
Max. mutual capacitance between any pF/mtr 400
c) core or screen at 1 KHz.
d) Max. L/R ratio μH/Ω 40
Min. insulation resistance at 200 C of
e) completed cables MΩ/Km 10
Max. drain wire resistance
f) including Ω/Km shield at 20 DegC 30
g) High voltage test 1 kV (rms) for 1 minute(core to core)AND 0.5 KV for 1 minute(core to armour)
14 FRLS Properties (On outer sheath)
a) Oxygen Index Min. as per ASTM 2863 % 29 ( at 27°c)
Max. HCL emission as
c) per IEC: 754-I % 20 By weigth
Max. smoke density
d) ratingASTMD: 2843 % 60
e) Flamability test as per IEC-332- max. 60 second/min 50 mm(ineffactive portion)
1 Each cable drum shall be marked with : manufacturer’s name,
15 DRUM IDENTIFICATION details of cable, batch no. / lot no. , length of cable & gross weight.
SRTL/DS/QC/313 Dated :25.06.2021 REV:00
Designed By
Approved By VINOD KUMAR (Q.A. Head)
For Shriram Telelink