Grid Connected Inverter Reference Design: Design Guide: TIDM-HV-1PH-DCAC
Grid Connected Inverter Reference Design: Design Guide: TIDM-HV-1PH-DCAC
Description Features
This reference design implements single-phase • 380-DC VIN, 110 VRMS, 60 Hz, 400-VA Max Output,
inverter (DC/AC) control using a C2000™ 20-kHz Switching
microcontroller (MCU). The design supports two • Approximately 97% Efficiency
modes of operation for the inverter: a voltage source • <2% Total Harmonic Distortion at >50% Rated
mode using an output LC filter, and a grid connected Power
mode with an output LCL filter. High-efficiency, low
THD, and intuitive software make this design attractive • powerSUITE™ Support for Easy Adaptation of the
for engineers working on an inverter design for UPS Design for User Requirement
and alternative energy applications such as PV • SFRA and Compensation Designer for Ease of
inverters, grid storage, and micro grids. The hardware Tuning of Control Loops
and software available with this reference design • Supports TMS320F28377D and TMS320F280049C
accelerate time to market.
Applications
Resources
• Photovoltaic Inverters
TIDM-HV-1PH-DCAC Design Folder • Micro Grids
TIEVM-HV-1PH-DCAC Orderable EVM Tool • Grid Storage
TMS320F28377D Product Folder
• Active Rectifier
TMS320F280049C Product Folder
AMC1304 Product Folder
OPA4350 Product Folder
UC3845 Product Folder
An IMPORTANT NOTICE at the end of this TI reference design addresses authorized use, intellectual property matters and other
important disclaimers and information.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 1
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
System Description www.ti.com
1 System Description
WARNING
TI intends this design to be operated in a lab
environment only and does not consider it to be a
finished product for general consumer use. The
design is intended to be run at ambient room
temperature and is not tested for operation under
other ambient temperatures. TI intends this design to
be used only by qualified engineers and technicians
familiar with risks associated with handling high-
voltage electrical and mechanical components,
systems, and subsystems. There area accessible high
voltages present on the board. The board operates at
voltages and currents that may cause shock, fire, or
injury if not properly handled or applied. Use the
equipment with necessary caution and appropriate
safeguards to avoid injuring yourself or damaging
property.
WARNING
High voltage! There are accessible high voltages
present on the board. Electric shock is possible. The
board operates at voltages and currents that may
cause shock, fire, or injury if not properly
handled..Use the equipment with necessary caution
and appropriate safeguards to avoid injuring yourself
or damaging property. For safety, use of isolated test
equipment with over-voltage and over-current
protection is highly recommended. TI considers it the
user's responsibility to confirm that the voltages and
isolation requirements are identified and understood
before energizing the board or simulation. When
energized, do not touch the design or components
connected to the design.
2 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com System Description
WARNING
Hot surface! Contact may cause burns. Do not touch!
Some components may reach high temperatures
>55°C when the board is powered on. The user must
not touch the board at any point during operation or
immediately after operating, as high temperatures may
be present.
WARNING
Do not leave the design powered when unattended.
Grid connected inverters (GCI) are commonly used in applications such as photovoltaic inverters to
generate a regulated AC current to feed into the grid. The control design of this type of inverter may be
challenging as several algorithms are required to run the inverter. This reference design uses the C2000
microcontroller (MCU) family of devices to implement control of a grid connected inverter with output
current control. A typical inverter comprises of a full bridge that is constructed with four switches that are
modulated using pulse width modulation (PWM) and an output filter for the high-frequency switching of the
bridge, as shown in Figure 1. An inductor capacitor (LCL) output filter is used on this reference design.
The design firmware is supported in the powerSUITE framework, which enables easy adaptation of the
software and control design. All key algorithms such as phase locked loop (PLL) for grid synchronization
and proportional resonant (PR) controllers provide good gain at selected frequencies. The adaptive notch
filter actively dampens the resonance of the LCL filter that is implemented.
The high efficiency, low THD, and intuitive software of this reference design make it fast and easy to get
started with the grid connected inverter design.
To regulate the output current, for example, the current feeds into the grid; voltages and currents must be
sensed from the inverter. Sigma delta-based sensing provides easy isolation and superior sensing of
these signals. Many C2000 MCUs have sigma-delta modulators to sense these parameters from the
power stage. Sigma-delta modulators provide easy isolation and high quality reading of the physical
variables, thus improving the overall quality of the control. Built-in sigma-delta demodulators on C2000
MCUs make using sigma delta-based sensing straight forward and easy to use.
Once the current and voltage parameters are sensed, the C2000 MCU runs the control algorithm to
compute the modulation required for regulated operation. Compensation designer implements the model
of the power stage, which makes the design of digital control loop simple. The software frequency
response analyzer (SFRA) enables measurement of the frequency response in-circuit to verify the
accuracy of the model and ensure accuracy of control.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 3
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
System Description www.ti.com
4 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com System Overview
2 System Overview
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 5
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
System Overview www.ti.com
6 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com System Overview
Figure 4. AC Output Voltage Differential Sensing Using Resistor Divider and Op Amp
V+ Ví
Rc Rc
Rd
Rc
V out _ fdbk V V 1.65
í Rd
+
Rd
1.65 V
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 7
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
System Overview www.ti.com
Figure 6. RC Filter
Figure 7. Trip Generation for PWM Using Comparators and Reference Generators
8 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com System Overview
All of this circuitry is avoided when using C2000 MCUs such as the TMS320F28377D, which has an on-
chip windowed comparator internally connected to the PWM module that can enable fast tripping of the
PWM. This connection saves board space, and cost in the end application as extra components can be
avoid using on-chip resources. Figure 8 shows the comparator subsystem used for overcurrent protection.
ADC
Comparator subsystem
COMPL
DACLVAL
+
To PWM trip
+ DACHVAL
COMPH
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 9
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
System Overview www.ti.com
Figure 10. SDFM-Based Isolated Voltage Sensing for DC Bus and Output Voltage
2.2.2.2.3 Protection
In addition to the data filter, which can demodulate the SDFM stream generated by the modulator with
specified oversampling rate (OSR) and filter order (SINC1, SINC2, SINC3), the SDFM has additional
comparator filters that can be programmed with a much lower OSR and filter order to enable fast trip of
the PWM.
10 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com System Overview
Figure 11. SDFM Filter Reset Being Generated From the PWM Module and ISR Trigger to Read SDF
Registers
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 11
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
System Overview www.ti.com
Figure 12. Control Scheme Used for Grid Connected Inverter Control
First, the grid voltage, VO, is sensed in the variable invVoInst. A software PLL algorithm is then run to
compute the angle and phase of the grid, invSine. This invSine value is then multiplied with the reference
current command invIoRef, which generates the instantaneous current command reference invIoRefInst.
This reference is then compared with the sensed output current, invIoInst, and the error fed into the
current compensator, Gi, as shown in Equation 1. The goal of the current compensator is to zero the error
between the reference and the measured value. A typical proportional integral (PI) controller can zero the
error for the DC value; however, for a sinusoidal reference, the controller cannot reduce the error to zero.
Thus, proportional resonant (PR) controllers are used as part of the current compensator Gi to zero the
error at the AC frequency.
Additional resonant controllers are added to the current compensator to zero the error at harmonic
frequency of the fundamental frequencies that are generated. A lead lag compensator is added to the
current compensator to improve the phase margin in the design, and a PI controller is added to reduce
startup current. Equation 1 shows the current compensator Gi.
æ (s + z0) N K iI _ nH 2 wrcI _ nH s ö
G i = ç Kp
ç
+ K pI _1H + å 2 2
÷ G Lead _ Lag
÷
n =1 s + 2 wrcI _ nH s + w o _ nH ø
s
è (1)
12 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com System Overview
Figure 13 shows that the grid voltage acts as a disturbance in the system, which can be modeled as an
impedance with regards to the current reference. The harmonic PR controllers help by increasing the
impedance at harmonic frequencies, thus reducing distortion in the grid feed current where N is the total
number of harmonic compensators added in the control loop. This reference design uses a total of five
resonant compensators that compensate the first, third, fifth, seventh, and ninth harmonic. The
compensation designer models the current loop plant and enables tuning of the compensator coefficients
through the powerSUITE page.
Voltage at
the input of
the filter
' imax
' i pp
'imax
D * Ts
Ts
The voltage across the inductor is given by:
di
V = Li ´
dt (2)
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 13
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
System Overview www.ti.com
For the full bridge inverter with an AC output, write the equation as:
Dipp
=> (VBus - VO ) = Li ´
D ´ Ts (3)
1
Ts =
Where Fsw is the switching period. Now, rearrange the current ripple at any instant in the AC
waveform, given as:
D ´ Ts ´ (VBus - VO )
=> Dipp =
Li (4)
Assuming the modulation index to be ma, the duty cycle is given as:
D(wt) = ma ´ sin(wt) (5)
The output of the inverter must match the AC voltage as it is safe to assume:
VO = VDC ´ D (6)
Therefore,
VBus ´ Ts ´ ma ´ sin(wt) ´ (1 - ma sin(wt))
Dipp =
Li (7)
As seen in Equation 7, the peak ripple is a factor of where the inverter is in the sinusoidal waveform (for
example, the modulation index). To find the modulation index where the maximum ripple is present,
differentiate Equation 7 with regards to time to get Equation 8, and equate to zero.
d( Dipp )
= K{cos(wt)(1 - ma sin(wt)) - ma sin(wt) * cos(wt)} = 0
dt (8)
1
=> sin(wt) =
2 ma (9)
Equation 9 then gives the modulation index for which the ripple is maximum, substituting back in
Equation 7. The inductance value required to tolerate the ripple is shown in Equation 10 and Equation 11:
V ´ Ts
Dipp = Bus
max 4 ´ Li (10)
VBus
Li =
4 ´ Fsw ´ Dipp
max (11)
For this reference design, the rating is 600 VA, the switching frequency is 20 kHz, and the bus voltage is
380 V. Assume that the ripple is 20% and is tolerable by the inductor core, and the minimum inductance
required is calculated as:
380
L= = 3.08 mH
4 ´ 20000 ´ 5.45 ´ 1.414 ´ 0.20 (12)
These calculations are also provided inside an Excel sheet form for convenience located at:
C:\ti\c2000\C2000Ware_DigitalPower_SDK_<version>\solutions\tidm_hv_1ph_dcac\hardware\baseboard\c
alculation.xlsx sheet → UPS Li & Cf Sel.
Select an appropriate core with these values in mind, and the inductor is designed to meet the inductance
value.
VDC
Li =
4 ´ Fsw ´ Dipp
max (13)
380
L= = 3.08 mH
4 ´ 20000 ´ 5.45 ´ 1.414 ´ 0.20 (14)
14 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com System Overview
For this reference design, the rating is 600 VA, the switching frequency is 20 kHz, and the bus voltage is
380 V. Assuming a 20% ripple is tolerable by the inductor core, the minimum inductance needed is
calculated as:
<sdk_install_path>\solutions\tidm_hv_1ph_dcac\hardware\baseboard\calculation.xlsx sheet
sheet→Grid Conn. Li, cf, Lg Sel
sheet→LI Design
Select an appropriate core with these values in mind, and the inductor is designed to meet this inductance
value.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 15
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
3.1.1 Hardware
This section details the hardware and explains the different sections on the board. If using just the
firmware of the design through powerSUITE, this section may not be valid.
NOTE: This reference design is also available for order as TIEVM-HV-1PH-DCAC. Note the 15-V
DC, 15-W power supply is not shipped with the design and must be arranged for by the user.
A two-pronged power supply is recommended so it is truly floating and isolated. Cables,
loads, oscilloscopes, and current probes must be arranged for by the user and connected to
this EVM according to the user guide instructions and observing local compliance and
standards for wiring. Only use isolated power supplies.
Also, the shipped EVM is configured in voltage source mode and the user will need to
depopulate the C1 20-µF capacitor and populate it with a C1 1-µF capacitor, which is
provided in the EVM box. In addition to this, the L2 and L2N, which are jumper wired on the
voltage source inverter, are populated in this reference design. L2 and L2N are also provided
in the EVM box but need to be soldered on by the user.
16 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
L2N
J17
DC Input
(380 V)
L2
J10 Relay
J4
J1- AC Output
J15-J16
Connector
Control Card
Connector
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 17
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
Figure 16 shows the hardware setup to run software for Build Level 1.
Fully Isolated
DC Power Differential Load
J17 HV-1PH-DCAC J1 (100-Ÿ 3RZHU
Supply Voltage Probe
(380 V, 2 A) Resistors)
18 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 19
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
2. Do not cross the USB cable directly over the high-voltage section by the following connection of the
USB cable.
20 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
NOTE: The firmware for this reference design is supported on both the TMS320F283779D and
TMS320F280049C devices.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 21
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
Figure 19. powerSUITE Page for the Grid Connected Inverter Solution
22 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
NOTE: Figure 20 shows the project for F28377D; however, if a different device is chosen from the
powerSUITE page, the structure will be similar.
Solution specific and device independent files are gridconnectedinvlclfltr.c/h. This file consists of the
main.c file of the project and is responsible for the control structure of the solution.
Board specific and device specific files are hv1phdcac_board.c/h. This file consists of device specific
drivers to run the single-phase inverter.
The powerSUITE page can be opened by clicking on the main.syscfg file, listed under the project explorer.
The powerSUITE page generates the gridconnectedinvlclfltr_settings.h file. This file is the only file used in
the compile of the project that is generated by the powerSUITE page. Pin mapping and other user defined
settings are located in gridconnectedinvlclfltr_user_settings.h.
The Kit.json and solution.js files are used internally by the powerSUITE and must also not be modified by
the user. Any changes to these files will result in the project not functioning properly.
The project consists of an interrupt service routine which is called every PWM cycle called inverterISR()
where the control algorithm is executed. In addition, there are background tasks A0–A4, B0–B4, and
C0–C4 which are called in a polling fashion, and may be used to run slow tasks for which absolute timing
accuracy is not required.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 23
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
freq
stepAngleMax invModIndex invDutyPU
+ - invModIndex
DLOG_4CH
PWM
PWM
Vbus
POWER_MEAS_SINE 1A 2A
Io
_ANALYZER invVbusInst
T=1/f Read VAC
.V Read
ADC
invIiInst ADC
.l and +
and
scale to
sampleFreq Load
invVoInst scale
PU
threshold .acFreq
1B 2B
24 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 25
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
6. Verify the inverter current and voltage measurements by viewing the data in the graph window. These
values are logged in the inverterISR() routine.
7. Go to Tools → Graph → DualTime.
8. Click on Import.
9. Point to the graph1.GraphProp file inside the project folder, and the graph properties window
populates.
10. Alternatively, the user may enter the values as shown in Figure 23.
11. When the entries are verified, click OK.
12. Two graphs appear in CCS.
13. Click Continuous refresh on these graphs.
14. If desired, add a second set of graphs by importing the graph2.GraphProp file.
26 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
button.
2. If a message box appears, select YES to enable debug events.
3. Set bit 1 (DGBM bit) to 0, and the memory and register values can be passed to the host processor for
updating the debugger windows.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 27
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
28 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
17. Use the graph to view the AC waveforms, as shown in Figure 25.
Figure 25. Build Level 1 Graph1.GraphProp File Showing Measured Per-Unit Voltage and Current Values
a. First, halt the processor by clicking the halt button on the toolbar, , or by using Target → Halt.
26. Click the Terminate Debug Session button, to close the CCS debug session, or go to Target →
Terminate all.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 29
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
Gi_pr1
Gi_r7
Gi_r9
PI controller
DCL_PI
pi
DC bus
voltage
PWM invDutyPU feedforward
PWM
Vbus
POWER_MEAS_SINE
_ANALYZER 1A 2A
Io
invVbusInst
T=1/f
.V Read VAC
Read
ADC
.l invIiInst ADC
and +
sampleFreq and
scale to Load
threshold .acFreq invVoInst scale
PU
1B 2B
DLOG_4CH
30 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
Figure 27. Hardware Setup to Run Software for Build Level 2: DC Check
Current Probe
iinv
Fully
Isolated Fully Isolated DC
Differential
DC Power J17 HV-1PH-DCAC J1 Voltage Probe Power Supply
Supply (150 V, 4 A)
(380 V, 2 A)
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 31
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
NOTE: If the project is not selected from the solution adapter, the compensator cannot be changed.
For a unique design, select the solution through the solution adapter.
10. Close the compensation designer and return to the powerSUITE page.
12. Click on the Continuous Refresh button, , on the watch window to enable the continuous update of
32 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
button.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 33
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
NOTE: Verify the sign of the output voltage guiVo is also correct (that is, 20 V). If not, reduce the DC
source connected to the output from 20 V to 0 V, reduce the input DC source voltage to 0,
and swap the connection terminals of the output terminal. A re-load of the code may be
necessary. Resume the debug and verify that now the guiVo is read as 20 V.
13. Increase invloRef to 0.01 to check the output current control of the inverter. This PU reference for this
design corresponds to approximately 0.17 A. Additionally, the variable invIoInst is monitored in the
watch window and can be used to check closed loop operation. This variable is the actual output
current measured and will follow the reference current set in invIoRef.
14. Observe that the current supplied by the DC source at the output decreases, and the inverter supplies
the rest of the DC current.
15. Increase the DC bus to 380 V. Maintain the closed loop operation as the user raises the DC bus. The
feedforward term of the DC bus ensure that the closed loop performance remains the same.
16. Increase the DC voltage of the power supply connected at the output to approximately 120 V.
17. Increase the invloRef further to 0.07 in steps of 0.01.
18. Observe that with each increment, more current is sourced from the inverter and less current is
supplied by the DC source connected at the output.
19. Make sure that the DC current from the supply connected at the output is never zero. This verifies that
the output current control is working to verify robustness.
20. SFRA is integrated in the software of this build which may be used to verify the designed
compensators, and check if enough gain and phase margin are present.
21. Keep the project running to run the SFRA from the cfg page.
22. Click on the SFRA icon.
23. The SFRA GUI appears.
24. Select the options for the device on the GUI. For example, select floating point for F28377D.
25. Click setup connection.
26. Select an appropriate COM port.
27. Click OK.
28. Return to the SFRA GUI.
29. Click Connect.
30. The SFRA GUI connects to the device.
31. Click Start Sweep to begin an SFRA sweep.
32. The complete SFRA sweep takes around 5 minutes to finish.
33. Monitor activity by watching the progress bar on the SFRA GUI and by checking the flashing of the
blue LED light on the back of the control card that indicates UART activity. Alternatively, the user can
enter "SFRA1". The FreqIndex variable in the watch window tells where the SFRA is in the frequency
sweep. The sweep is of 100 points in this software and will complete when this variable reached a
value of 100.
34. Once complete, a graph with the open loop plot appears, as shown in Figure 30.
35. The plot verifies that the designed compensator is stable.
34 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
NOTE: The SFRA GUI is designed for log step frequency points hence in case of this project where
this is not valid the SFRA GUI can crash and not display the complete waveform. Under
such a situation, the following workaround is recommended:
1. Close the SFRA GUI, go to <sdk_install_path>/libraries/sfra/GUI and launch the
SFRA.exe file from here.
2. Connect the SFRA GUI and make sure "Save SFRA Data as CSV" is not checked. This
forces the SFRA data to be saved into an Excel sheet. Even when the SFRA GUI
reports an error after the retrieval of the data, select continue and the Excel sheet will be
populated with all the frequency data. This data can then be used in MATLAB or saved
as a .CSV file and used in compensation designer.
3. If the SFRA GUI errors out, skip the following steps from 36 to 45.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 35
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
36. The frequency response data is also saved in the project folder, under an SFRA Data Folder, and is
stamped with the time of the SFRA run.
37. Go back to the powerSUITE page.
38. Open Compensation Designer once the sweep is complete.
39. Click on Compensation Designer.
40. Choose SFRA Data for the plant option on the GUI.
41. The SFRA Data uses the measured plant information to designer the compensator. This option may
be used to fine-tune the compensation.
42. By default, the compensation designer points out the latest SFRA run.
43. If a previous SFRA run plant information is required to be used, select the SFRAData.csv file and click
Browse SFRA DATA.
44. Close the compensation designer to return to the configuration page. Figure 31 shows the
compensation designer with measured plant frequency response data.
Figure 31. Compensation Designer With Measured Plant Frequency Response Data
45. This verifies the current compensation design, both modeled and measured to match closely. The
compensator may further be adjusted to achieve the best performance from the system.
46. Set the invIoRef to zero.
36 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
51. Halt the processor by using the Halt button on the toolbar, , or by using Target → Halt.
54. Click on the Terminate Debug Session button, , or go to Target → Terminate All to close the CCS
debug session.
Fully Isolated
DC Power Differential
Fully Isolated AC
J17 HV-1PH-DCAC J1 Voltage Probe Power Supply
Supply
(380 V, 2 A) (110 Vrms, 4 A)
J2
Power Meter can be connected
in between J1 and the load to
15-V DC, 1-A Load measure THD and Power
Power Supply
(100- Power
Resistors)
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 37
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
12. Click on the Continuous Refresh button, , on the watch window to enable a continuous update of
values from the controller.
13. Figure 33 shows how the watch window appears.
14. Use the graph window to observe the variables as this is a check.
15. Enable real-time mode by hovering the cursor on the buttons on the horizontal toolbar and clicking
38 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
NOTE: As the inverter is operating at very low power, observe any spikes around the zero crossing.
Ignore these spikes for now as they reduce once operating at rated current and voltage. An
audible buzz may also be heard.
a. Click the Halt Button on the toolbar, , or use Target → Halt to stop the processor.
19. Click the Terminate Debug Session button, , or go to Target → Terminate All to close the CCS
debug session.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 39
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
12. Click on the Continuous Refresh button, , on the watch window to enable a continuous update of
values from the controller.
13. Figure 34 shows how the watch window appears.
40 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
14. Hover the cursor on the buttons on the horizontal toolbar to enable real-time mode.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 41
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
14. Fully halting the MCU when in real-time mode is a two-step process:
a. Click the Halt Button on the toolbar, , or use Target → Halt to stop the processor.
16. Click the Terminate Debug Session button, , or go to Target → Terminate All to close the CCS
debug session.
3.2.1 Test Results With Grid Connection at 120 VRMS and 60-Hz Loads
Figure 35. Efficiency of the Design When Operating at 120 VRMS of Output
97.2%
96.9%
96.6%
96.3%
96%
Efficiency
95.7%
95.4%
95.1%
94.8%
94.5%
94.2%
93.9%
0 50 100 150 200 250 300 350 400 450 500 550
POUT (W) D001
42 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
Figure 36. Steady-State Output Voltage and Current at 120 VRMS, POUT of 500 W, Zoomed In
Figure 37. Steady-State Output Voltage and Current Waveform at 120 VRMS, POUT of 500 W, Multiple Cycles
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 43
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
Figure 38 shows the steady state voltage and current operating at 160 W with 120 VRMS of output voltage.
Figure 38. Steady-State Output Voltage and Current at 120 VRMS, POUT of 160 W, Zoomed In
44 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Hardware, Firmware, Testing Requirements, and Test Results
NOTE: The THD of the current is lower than the THD of the voltage at power level greater than 30%
rated load.
0.1
0.08
THD
0.06
0.04
0.02
0
0 50 100 150 200 250 300 350 400 450 500 550
PIN (W) D002
The harmonic controllers are added one by one in the current compensator and the THD of the current
plotted in Figure 41 for each combination. Table 5 lists the complete test data. Observe that the first, third,
fifth, and seventh harmonic controllers affect the THD significantly; however, with the addition of the ninth
harmonic controller the THD improves marginally.
Figure 41. THD at 120 VRMS With Different Resonant Controller Combination
45%
1H
1H + 3H
40% 1H + 3H + 5H
1H + 3H + 5H + 7H
35% 1H + 3H + 5H + 7H + 9H
30%
25%
THD I
20%
15%
10%
5%
0
0 50 100 150 200 250 300 350 400 450 500 550
POUT (W) D003
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 45
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Hardware, Firmware, Testing Requirements, and Test Results www.ti.com
Table 6. Test Data Table for SDFM-Based Sensing and Output Current Control at 110 VRMS
VIN lIN VOUT IOUT PIN POUT THDi EFFICIENCY PF THDv
382.8 0.071 122.27 0.2162 27.1788 25.524 14 0.93911431 0.96 2.01
382.8 0.142 122.41 0.4325 54.3576 52.48 6.5 0.965458372 0.9917 2.01
382.8 0.287 122.53 0.8714 109.8636 106.54 3.4 0.969747942 0.9977 2.01
382.6 0.433 122.72 1.3118 165.6658 160.9 2.3 0.971232445 0.9987 2.01
382.8 0.581 122.93 1.7522 222.4068 215.18 1.78 0.967506389 0.9989 2.01
382.6 0.729 122.99 2.1929 278.9154 269.44 1.46 0.966027692 0.999 2.01
382.8 0.841 122.98 2.5229 321.9348 310.07 1.3 0.963145333 0.999 2.01
382.8 0.919 123.36 2.7427 351.7932 338.15 1.2 0.961218125 0.999 2.01
382.8 1.111 123.55 3.2926 425.2908 406.59 1.18 0.956028205 0.999 2.01
382.8 1.265 123.86 3.7325 484.242 462.12 1.08 0.95431623 0.999 2.01
382.8 1.377 123.55 4.0561 527.1156 500.03 0.99 0.948615446 0.999 2.01
46 Grid Connected Inverter Reference Design TIDUB21D – November 2015 – Revised March 2020
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
www.ti.com Design Files
4 Design Files
For schematics, bill of materials (BOM), the altium project, and Gerber files, see
http://www.ti.com/tool/TIDM-HV-1PH-DCAC or to the DigitalPower SDK package at:
<sdk_install_path>/solutions/tidm_hv_1ph_dcac
5 Software Files
To download the software files for this reference design, see the link at
http://www.ti.com/tool/C2000WARE-DIGITALPOWER-SDK. This reference design can also be found at:
<sdk_install_path>/solutions/tidm_hv_1ph_dcac
\docs → Documentation
\hardware → PCB Altium Project, Gerbers, BOM, sense_calculation.xlsx
\<device> <control_mode> → CCS Project
6 Related Documentation
• Department of Energy Technology, Design and Control of an Inverter for Photovoltaic Applications,
PHD Theses, Aalborg University, 2009
• IEEE, Filter Design for grid connected PV inverters in ICSET, 2008.
• IET Power Electronics, Frequency Tracking of Digital Resonant Filters for Control of Power Converter
Connected to Public Distribution Systems, vol. 4, no. 4, pp. 454-462, Apr 2011.
• IEEE, A New Single Phase PLL Structure Based on Second Order Generalized Integrator, 37th IEEE
PESC, 2006.
• Texas Instruments, C2000™ Software Frequency Response Analyzer (SFRA) Library and
Compensation Designer User’s Guide
• Texas Instruments, TMS320F2837xD Dual-Core Delfino™ Microcontrollers Technical Reference
Manual
• Texas Instruments, TMS320F2837xD Dual-Core Delfino™ Microcontrollers Data Sheet
• Texas Instruments, TMS320F28004x Piccolo™ Microcontrollers Technical Reference Manual
• Texas Instruments, TMS320F28004x Piccolo™ Microcontrollers Data Sheet
6.1 Trademarks
C2000, E2E, powerSUITE, Code Composer Studio, Delfino, Piccolo are trademarks of Texas Instruments.
Excel is a registered trademark of Microsoft Corporation.
All other trademarks are the property of their respective owners.
TIDUB21D – November 2015 – Revised March 2020 Grid Connected Inverter Reference Design 47
Submit Documentation Feedback
Copyright © 2015–2020, Texas Instruments Incorporated
Revision History www.ti.com
Revision History
NOTE: Page numbers for previous revisions may differ from page numbers in the current version.
• Changed powerSUITE Page for the Grid Connected Inverter Solution image .................................................. 22
• Changed Project Explorer View of Solution Project image ......................................................................... 23
• Changed Current Loop Design Using Compensation Designer image ........................................................... 32
• Changed Compensation Designer With Measured Plant Frequency Response Data image ................................. 36
• Changed SPRUHZ5 to SPRUIK4 link ................................................................................................. 47
TI PROVIDES TECHNICAL AND RELIABILITY DATA (INCLUDING DATASHEETS), DESIGN RESOURCES (INCLUDING REFERENCE
DESIGNS), APPLICATION OR OTHER DESIGN ADVICE, WEB TOOLS, SAFETY INFORMATION, AND OTHER RESOURCES “AS IS”
AND WITH ALL FAULTS, AND DISCLAIMS ALL WARRANTIES, EXPRESS AND IMPLIED, INCLUDING WITHOUT LIMITATION ANY
IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR NON-INFRINGEMENT OF THIRD
PARTY INTELLECTUAL PROPERTY RIGHTS.
These resources are intended for skilled developers designing with TI products. You are solely responsible for (1) selecting the appropriate
TI products for your application, (2) designing, validating and testing your application, and (3) ensuring your application meets applicable
standards, and any other safety, security, or other requirements. These resources are subject to change without notice. TI grants you
permission to use these resources only for development of an application that uses the TI products described in the resource. Other
reproduction and display of these resources is prohibited. No license is granted to any other TI intellectual property right or to any third
party intellectual property right. TI disclaims responsibility for, and you will fully indemnify TI and its representatives against, any claims,
damages, costs, losses, and liabilities arising out of your use of these resources.
TI’s products are provided subject to TI’s Terms of Sale (www.ti.com/legal/termsofsale.html) or other applicable terms available either on
ti.com or provided in conjunction with such TI products. TI’s provision of these resources does not expand or otherwise alter TI’s applicable
warranties or warranty disclaimers for TI products.
Mailing Address: Texas Instruments, Post Office Box 655303, Dallas, Texas 75265
Copyright © 2020, Texas Instruments Incorporated