Power and Voltage Control in A Grid-Connected Microgrid System With A Back-to-Back Converter
Power and Voltage Control in A Grid-Connected Microgrid System With A Back-to-Back Converter
H. Sekhavatmanesh, Student Member, H. Mokhtari, Member, IEEE, M. Hamzeh, Member, IEEE, and
IEEE,
A. Asbafkan
Department of Electrical Engineering, Sharif University of Technology, Tehran, Iran
Department of Electrical and Computer Engineering, Shahid Beheshti University, Tehran, Iran
h sekhavat@ee.sharif.edu, mokhtari@shari£edu, mo hamzeh@sbu.ac.ir, asbafkan@ee.shari£edu
Fig. 2. Back to back converter operated in the PQ control mode (mode-I) or voltage control mode (mode-2)
section III, the control modes are introduced first, and then the the voltage of the AC microgid is set by its own resources and
design procedure of control loops for each mode is explained. the converter has no contribution to it. As shown in Fig. 2, in
Finally, in the section IV, the simulation results are provided. this mode, the b-to-b converter is controlled to inject or absorb
pre-specific amount of active and reactive power to or from
II. POWER CIRCUIT STRUCTURE the microgrid depending on the operator decisions. In another
Fig. 2 shows a schematic diagram of the system under control mode, the b-to-b converter controls the voltage of the
study. It consists of an active rectifier with an LCL filter, a microgrid or contributes to it in conjunction with the resources
DC-link capacitor and an inverter with another LCL filter. The in the microgrid.
parameters of the LCL-filters are determined according to As illustrated in Fig. 2, the control loop of the utility side
some factors such as current ripple, resonant frequency, the converter is unique in both modes of operation. In this
permissible reactive power injected by the filter capacitor, converter, a current controller is used in which the magnitude
voltage attenuation caused by the filter and passive and active and the phase of the current reference are determined
damping that must be added in series with the capacitor of the respectively, to control the DC-link voltage and to not draw
filter. any reactive power from the utility. However the microgrid
In this work, active damping is used and introduced as the side converter uses different control loops. In Mode-I, a
inner loop of the controllers. The configuration and parameters current controller is applied to inject the desired active and
of the filters of the rectifier and inverter used in the proposed reactive power to the microgrid but in Mode-2, a voltage
inter-link converter are the same. These parameters have been control loop is used to control the voltage of the microgrid
designed according to the characteristics of the power circuit system. The inner loop in both voltage and current control
and the aforementioned factors. The electrical characteristics loops is used for active damping and fast dynamic response.
of the power circuit and parameter values are listed in Table I. In this paper, the basic ABC frame is chosen for the
III. CONTROL SYSTEM STRUCTURE
controller strategy. In this frame, each phase can be controlled
separately, while it would still work properly in unbalanced
The b-to-b converter can be used in two different modes conditions. For better tracking and rejecting of sinusoidal
depending on the structure of the microgrid. In Mode-I, the signals resonant controllers are used. This controller has an
proposed inter-link converter is used in a condition in which infinite gain at a certain frequency called resonant frequency
TABLE I: Electrical and Physical Characteristics of the System
and almost zero gain at other frequencies. The theory beyond
this kind of controller is discussed in more details in [6]. To
Pnom
Nominal active power flow through the converter 100 kW avoid stability problems associated with an infinite gain at the
Line to line voltage of the microgrid and the utility 380 V
resonant frequency, some damping can be added to have a
Vgrid grid quasi-resonant integrator as follows:
Frequency of the microgrid and the utility grid. 50 Hz
.!net Ge ( S) =
2k/JJe s
(1)
Converter-side inductor 290 JiH 2 2 '
S + 2we s + Wo
4
grid-side inductor 1 70 pH where We is the resonant frequency.
L2
FiIter capacitance 76. 7JiF The controller gain is now finite but still relatively high to
Cf have a small steady state error. The controller bandwidth is
DC-link voltage 750 V widened by setting larger values for We. This could help the
Vdc controller work properly in spite of variations in the
DC-link capacitor 2. 7 mF
Cdc frequency. If the resonant integrator is accompanied by a
1 0 kHz
proportional term, the result will be a proportional resonant
Switching frequency
fS1" ( PR) controller as expressed in (2).
469
Fig. 3. Modeling of an inverter operated as a voltage controller
50
iii'
:e.
Gain=O.1 ..
..,
Damping: 0.7
.�
�-.
�� Overshoot(%):4.5
g>
:!;;
-50
�
� 0 .. ········ ....... ······· ... ·..·· a------ ············· , ·······....... -100
90
�
Phase Margin:
c "6l
.. 50.1 degree
'2> ;. -90 At frequency: 50Hz At frequency:
.s
�h�s�:. :.5.�4_d,:g':.ee_._
� -180 . 902 Hz
- - _-::
-i�o::o::-o - -:c
80�00=-L-- - -4-0LOO:-----20LOO----'-
60�00:-- 0 --...J
2000
Real Axis (seconds·1) FreQuencv (rad/s)
Fig. 4. Root locus of the open loop system in voltage control mode Fig. 5. Bode diagram of the open loop system with voltage controller
designed
2 es
Ge (s) = kp + 2 k/JJ 2' (2) Then, the value of Kp must be determined considering the
s +2wes+wO system dynamic performance. As depicted in Fig. 5, the root
where Kp is the proportional gain. locus of the system is optimized for the damping ratio of 0.7
As in the PI controller, the dynamic response of the system with the controller parameters of Ke=4 and Kp=O.l. In addition
such as bandwidth, phase and gain margins is dominantly to the resonant controller at the operating frequency, harmonic
tuned by Kp and the steady state behavior of the system can be resonant controllers must be added for the rejection of load
tuned by choosing an appropriate value for Ki• harmonic currents as given in (3).
5
A. Voltage Control Loop
" 2kih(hwc)S
Gc(s)=kp+ L. 2 + 2(hwc)s +(hw )2· (3)
k=O S O
In voltage control mode the magnitude and frequency of h=2k+1
the grid are controlled under load current variations. In this
The integral term for each frequency is determined
mode, the voltage of the capacitor of the filter is measured and
according to its desired magnitude. Assuming that We is equal
compared with the reference voltage, and the output is given
to the controller. In this scheme, an inner current loop is to 1.5rad/s, the integral terms are tuned to have the desired
bandwidth and provide maximum possible magnitude at the
introduced not only for damping the LC-resonance introduced
operating frequency and its harmonics. Here the bandwidth is
by the filter but also for improving the overall system stability.
set to 5500 rad/s. The bode diagram of the final open-loop
For this reason, the capacitor current of the output filter is fed
system is illustrated in Fig. 5.
back into the current control loop so as to provide both active
damping and disturbance rejection enhancement.
The inner controller is a gain (Ke) that is selected such that B. PQ control Loop
its effect on the outer loop is considered. The system is
modeled in Fig. 3. The load is modeled as two parts, a linear Another operation mode of the inverter is the PQ control
part and a non-linear part. The linear current load is modeled mode. In this mode the microgrid includes voltage sources as
as a function of the output voltage, however the non-linear well. In this condition, the reference of the current is
part is considered as a disturbance in the model. determined based on the desirable active and reactive powers
and the load voltage. The inner current loop is the same as that
In the design process, the value of Ke is set to a very low in the voltage control mode, and the inverter must inject a
value for damping the resonant frequency. Larger values of Ke particular amount of active and reactive powers which
result in higher gains at lower frequencies that could amplify determines the magnitude and phase of the reference current.
low-frequency noises [3]. Additionally, larger values of Ke Fig. 6 shows a block diagram of the inverter working in this
produce larger phase lag at the operating frequency that could mode of operation.
deteriorate both reference tracking and disturbance rejection.
470
�-------------------------�
Fig. 6. Modeling of an inverter operated as a PQ controller
2
Gain: 0.26
o
Damping: 0.7 50 Hz
._._._._._._._._._ . _.
At frequency:
��
c:
Overshoot: 4.5%i Magnitude: 58 dB
8..
�
� 01----------------.<························
m :=::=:::::�
::: :::=
=::=:::::::
: ::: =:=::::=
:: ��::::�
:: =::;:=::::::�
Phase I argin:
-
-62.9
Phase:
...
degree
-3 60'"::--�....-:-�...: :...
.... .. -�....,...
:--" .. �-....
.- -��..J
...,.
-3 ��������������---7����
-2
-3.5 -3 25 - -1.5
. -1 -0.5 1.5 IJ II II II IJ 11
Real Axis (seconds·1) x 1 0' Frequency (rad/sl
Fig. 7. Root locus of the open loop system in the PQ control mode Fig. 8. Bode diagram of the open loop system with current controller
The design process of the outer and inner controller in this grid voltage in order not to draw any reactive power from the
mode is the same as the process described for the voltage utility. The model of the DC-bus voltage control loop is shown
control loop, i.e. Ke=4. To determine a proper value for K,,, the in fig. 9. In this figure, T, is the time constant of the current
root locus of the system is plotted in Fig. 7. As it can be seen control loop of the grid-side converter which is equal to:
from this figure, a suitable value for Kp to have an optimum
1
dynamic behavior is 0.26.
1) =------ __=3.5x 10-4 ' (4)
B Wcurrentloop 2840
Now, the integral term and the cutoff frequency are
specified according to the desired bandwidth and tracking at where Ro and K are the steady-state equivalent resistance and
the operating frequency. In the PQ control mode, there is no the transfer function from the current amplitude to the active
need to add a harmonic resonant controller. Within the power, respectively, which can be found as:
previous assumption for We, the value of the integral term is
= de = Je =
tuned at 100 to have a bandwidth equal to 2840radls, which is V V 7502
R =5.625!1, (5)
small enough as compared to the resonant frequency. To o Ide P 105
achieve this bandwidth the value of Kp must be increased, such
P 3x V 'd
that the damping ratio will be decreased enough. For this k=-= gTi =466.7. (6)
reason, a phase lead compensator is added to increase the I II J2
phase at the cross over frequency. The bode diagram of the As shown in Fig. 9, the system has a right-hand pole.
final open loop system is illustrated in Fig. 8. Therefore the phase and gain margin criteria could not be used
for stability of the closed loop system. Thus the design
e. DC-link Voltage Control Loop
procedure must be done using the zero/pole placement in the
To maintain the voltage of the DC-link in a back to back Z-plane [7]. The PI controller is designed as:
converter at a constant value, the active power that flows into
the DC-link must be equal to the active power absorbed by the Ge =_(p+i) ' (7)
load. For this purpose, the voltage of the capacitor must be S
measured and compared to the reference one. The error is where P=1. 1 and 1=52.
given to a PI controller to produce the amplitude of the current The performance of the designed controller is investigated in
reference of the grid-side converter. It is worth mentioning the next section.
that this current reference must be in-phase with the utility
IV. SIMUL AnON RESUL TS
To investigate the effectiveness of the proposed control
schemes, the system of Fig. 2 is simulated in Matlab/Simulink.
The system is composed of a b-to-b converter with an LCL
filter on both sides, which is used as an interlink converter
between the utility grid and the microgrid. The electrical and
Fig. 9. Modeling of the system used for controlling of the DC-link voltage physical parameters of the system are given in Table I.
471
A. Simulation in Voltage Control Mode the DC-link is shown in Fig. 12.
In the next simulation, a single-phase load of 40kW and
First, the performance of the proposed inter-link converter
PF=1 is added to the system load. The results are shown in
is simulated in the voltage control mode. In this mode, the
Figs. 13, 14 and 15. As it can be seen in these figures, the b
converter controls the voltage of the microgrid. The microgrid
to-b converter controls the voltage of the microgrid in spite of
is composed of only loads without any voltage sources.
non-linear unbalanced load current while the grid current stays
Initially, the microgrid is operating under balanced and linear
sinusoidal and balanced.
load conditions. At t=0.08s, a six-pulse diode rectifier of
60kVA and PF=0.95 is added to the microgrid. The voltage of
the microgrid and the current of the microgrid and the utility
grid are shown in Figs. 10 and 11 respectively. The voltage of
400 400 .---�-�-�-�-�--�-�-�--,
,--�-�-�-�-�-�-�-;:::=:::===L.,
:E:
�
.r
:;;: -100
40
40 - £04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13
- £04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13 Time(secolld)
Time(second)
Fig. 10. Three phase voltage of the microgrid in the voltage control mode Fig. 13. Three phase voltage of the microgrid in the voltage control mode
with adding six-pulse rectifier to load at t�O. 08. with adding single phase load at t�. 08.
0.05 0.06 0.07 0.08 0.09 0.1 0.05 0.06 0.07 0.08 0.09 0.1
Time(seco"d) Time(secolld)
Fig. 11. Three phase current of the microgrid(top figure) and utility
Fig. 14. Three phase current of the microgrid (top figure) and utility grid
grid(lower figure) in the voltage mode control with addmg sIx-pulse
(lower figure) in the voltage mode control with adding single phase load
rectifier to load at t�O. 08
at t�O. 08.
800 .---�---.----�--.---�---,
8001 r---�--�--��---
65 �0 L---�--������--������--���
£04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 0.1 2 0.13 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13
Time(second) Time(second)
Fig. 12. DC-bus voltage in the voltage mode control with adding six Fig. 15. DC-bus voltage in the voltage mode control with adding six
pulse rectifier at t�O. 08. pulse rectifier at t�O. 08.
472
B. Simulation in PQ Control Mode REFERENCES
To see the performance of the b-to-b converter in the PQ [I] R. Majumder. A. Ghosh. G. Ledwich. and F. Zare. "Power management
and power flow control with back-to-back converters in a utility
control mode, the microgrid must include voltage resources. In
connected microgrid," IEEE Trans. Power Systems. , vol. 25, no. 2, pp.
this mode, the task of the inter-link converter is to inject pre 0885-8950, May. 2 010.
specified amount of active and reactive powers into the [2] U. Nutkani, P. C. Loh, and F. Blaabjerg, "Distributed operation of
microgrid. For simulation purposes, initially the converter interlinked AC microgrids with dynamic active and reactive power
provides 50kW at a unity power factor to the microgrid. At tuning, " IEEE Trans. Ind. App. , vol. 49, no. 5, pp. 0093-9994, Sep/Oct.
t=O.08, the reference of the active power is doubled. The 2 013.
tracking of the active power and the current injected into the [3] J. He, and Y. W. Li, "Generalized closed-loop control schemes with
microgrid are illustrated in Figs. 16 and 17. embedded virtual impedances for voltage source converters with LC or
LCL filters, " IEEE Trans. Power. Electron. , vol. 2 7, no. 4, pp. 0885-
8993, April. 2 012.
V. CONCLUSION
[4] M. Vilathgamuwa, A. A. D. Ranjith Perera, and S. S. Choi,
This paper presents the application of the b-to-b converter "Performance improvement of the dynamic voltage restorer with c1osed
and its advantages in power/voltage control of a grid loop load volt- age and current-mode control," IEEE Trans. Power
connected microgrid system. Two modes of operation are Electron. , vol. 1 7, no. 5, pp. 824-834, Sep. 2 002.
studied. In the first one, i.e. the PQ control mode, the proposed [5] F. Liu, S. Duan, J. Yin, B. Liu, and F. Liu, "Parameter design of a two
current-loop controller used in a grid-connected inverter system with
system offers precise active/reactive power control from the
LCL filter," IEEE Trans. Ind. Electron. , vol. 56, no. II, pp. 4483-4491,
grid side. The grid has no contribution to the control of the Nov. 2 0 09.
microgrid voltage. In the second control mode, i.e. Voltage [6] R. Teodorescu, F. Blaabjerg, U. Borup, M. Liserre, "A new control
control mode, although the grid has a role in the control of structure for grid-connected LCL PV inverters with zero steady-state
both the power flow and voltage of the microgrid, it is slightly error and selective harmonic compensation," IEEE 2 0 04.
affected by the disturbances in the microgrid system. [ 7] R. Teodorescu, M. Liserre, P. Rodriguez, "Grid converters for
photovoltaic and wind power systems," John Wiley & Sons, Ltd 2 011.
[8] M. Hamzeh, H. Mokhtari, and H. Karimi, "A Decentralized Self
Adjusting Control Strategy for Reactive Power Management in an
Islanded Multi-Bus MV Microgrid," Canadian Joumal of Electrical and
Computer Engineering, vol. 3 6, no. I, pp. 18-25, Winter 2 013.
[9] M. Hamzeh, H. Karimi, and H. Mokhtari, "Harmonic and Negative
Sequence Current Control in an Islanded Multi-Bus MV
Microgrid," IEEE Transactions on Smart Grid, vol. 5, no. I, pp. 16 7-1 76,
Jan. 2 014.
-150
-200
-250 '---'-----'--'--'
0.04 0.05 0.06 0.0 7 0.08 0.09 0.1 0.11 0.12 0.11
Time(second)
,
x·1.�0�-- -- -- -- --
11 , _. _r � .- �������
- rea/ active power
- actit'e power reference
10
4L-_�_�_-L_-'-_�_-'__L-_��
0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13
Tillle(second)
Fig. 1 7. Active power tracking. injected to the microgrid in PQ control
mode.
473