Liebert gxt4 230v 5000 10000va User Manual SLI 23197
Liebert gxt4 230v 5000 10000va User Manual SLI 23197
GXT4™ UPS
Installer/User Guide
230 V, 5000 VA – 10,000 VA
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
This manual contains important safety instructions that must be followed during the installation and
maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or
operate this UPS.
UPS Safety Notes
This UPS contains no user-serviceable parts except the internal battery pack. The Off/Bypass
push button does not electrically isolate internal parts. Under no circumstances attempt to gain internal
access other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the
UPS if the front panel indications are not in accordance with these operating instructions or if the UPS
performance alters in use. Refer all faults to your local dealer, Vertiv representative or Vertiv Channel
Support.
This UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even if the
UPS is not connected to utility input power.
Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure that the
UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric
shock hazard.
To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.
When the UPS is connected to an IT power distribution system, a short-circuit protection device must be
installed on the neutral line.
Keep the air inlet and outlet of this UPS unobstructed. Poor ventilation will increase the internal
temperature of the UPS and can adversely affect the UPS and its batteries.
In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may
cause electric shock.
This product is designed for commercial/industrial use only. This UPS is not intended for use with life
support and other designated critical devices. Maximum load must not exceed that shown on the UPS
rating label. This UPS is designed for data processing equipment. If uncertain, consult your local dealer or
Vertiv representative.
WARNING! Risk of electric shock and explosion. Can cause equipment damage, injury and
death. Do not dispose of the battery in a fire. The battery may explode. Do not open or damage
the battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte comes
into contact with the skin, wash the affected area immediately with plenty of clean water and
get medical attention.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery
can present a risk of electrical shock and high short-circuit current.
ELECTROMAGNETIC COMPATIBILITY The Liebert® GXT4 series complies with the limits for a CLASS A
DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following conditions:
Operating this device in a residential area is likely to cause harmful interference that users must correct
at their own expense.
The Liebert® GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the
published technical standards. Continued compliance requires installation in accordance with these
instructions and use of accessories approved by Vertiv.
UPS Servicing: UPS makes use of components dangerous for the environment (electronic cards,
electronic components). The components removed must be taken to specialized collection and disposal
centers.
NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This product has been
supplied from an environmentally aware manufacturer that complies with the Waste Electrical and
Electronic Equipment (WEEE) Directive 2002/96/CE.
The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle
wherever possible. Please be environmentally responsible and recycle this product through your
recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local
municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste
electrical and electronic equipment (WEEE). C
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject
to voltage sags, spikes, and complete failure that may interrupt computer operations, cause data loss, and
damage equipment.
The Liebert® GXT4 protects equipment from these disturbances. The Liebert® GXT4 continuously
charges its batteries from the mains, enabling it to supply power to connected loads, even when the mains
fail.
2.1 Features
• Intelligent battery management to extend the battery life
• LCD for user-friendly operation and local monitoring and configuration of operational
parameters
• Fan fault self-inspection and automated diagnostic function
• Intelligent fan operation, automatically changing rotation speed depending on system
requirements, to decrease power consumption and noise
• Input circuit breaker to ease recovery from overloads
• CE mark and safety approval from CE
• Communication options: USB port, Liebert® IntelliSlot™ port and terminal-block communication
• Dry contacts for remote monitoring
• Input power factor greater than 0.99
• Output voltage selection function
GXT4-5000RT230
5000VA / 4000W
GXT4-5000RT230E
GXT4-6000RT230
6000VA / 4800W
GXT4-6000RT230E
GXT4-10000RT230
10000VA / 9000W
GXT4-10000RT230E
2 GXT4 Description 11
2.3 Front Panel and Controls
The Liebert GXT4 rack/tower models in various power ratings have the same general appearance,
controls and features as shown in the following figure. The various rack/towermodels differ largely in the
type of receptacles each has.
NO. DESCRIPTION
1 Upper bezel
NOTE: Hard-wired and hard-wired/receptacle boxes that include a manual bypass switch permit AC
power to continue to flow from the utility input to the load while the box is removed from the UPS. For
details, refer to Connecting Input/Output Power on page 25.
2 GXT4 Description 13
Figure 2.3 Rear panel—10,000VA
NO. DESCRIPTION
1 Outer-surface view
2 Quick-connect
NO. DESCRIPTION
2 Inner-surface view
3 Quick-connects
GXT4 10,000-VA battery pack shown is shown in the figure. 5000-VA and 6000-VA battery packs have
the same features.
2 GXT4 Description 15
Figure 2.6 Internal battery pack with connector
NO. DESCRIPTION
1 Battery handle
2 Battery connector
This results in cleaner power available to other devices in the building that are not protected by the
GXT4.
2.7.3 Inverter
In normal operation, the inverter utilizes the DC output of the PFC circuit to produce precise, regulated
sine-wave AC power. When mains power fails, the inverter receives DC power from the DC-to-DC
Converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise,
regulated AC output power.
2.7.6 Battery
The GXT4 uses valve-regulated, non-spillable, lead acid batteries. To maintain battery design life, Operate
the GXT4 in an ambient temperature of 15°C to 25°C (59°F to 77°F).
Optional external battery cabinets are available to extend battery run times.
To manually transfer the connected load from the inverter to bypass, press the Standby/Manual Bypass
button once and hold it for about 2 seconds
2 GXT4 Description 17
2.7.8 Maintenance Bypass
The GXT4 provides a manual maintenance bypass in a removable section of the rear of the UPS. This
allows replacement of the UPS in the event of a UPS malfunction while keeping the connected equipment
powered with utility power.
NOTE: The bypass power path does not protect the connected equipment from disturbances in the
mains supply.
Refer to Operation and Display Panel on page 31 for details about the operating mode indicators and
control buttons.
Risk of loss of power to the connected load. Can cause equipment damage.
Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load.
When the GXT4 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When
approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is
getting low (this Low Battery Warning is user-configurable).
In Battery Mode, the battery indicator will illuminate and the LCD will show the prompt utility power not
available.
Risk of loss of power to the connected load. Can cause equipment damage.
Turning Off the GXT4 when it is in Battery Mode will result in loss of output power to the
connected load.
If the UPS is turned Off manually, it must be manually restarted after mains power returns.
If the UPS is turned Off by a communication signal or because the batteries are depleted, it will
operate as set in the configuration program for Auto-Restart (Refer to Configuration Program
on page 43).
NOTE: The default for all models of the Liebert® GXT4 is “Auto Sensing - 50 Hz or 60Hz – Bypass
Enabled.”
Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized
to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power
almost seamlessly if bypass power falls outside the user-set limits. Once bypass power returns within the
acceptable parameters, the UPS will return to Active ECO Mode operation.
2 GXT4 Description 19
This page intentionally left blank
WARNING! Risk of electrical shock. Can cause equipment damage, injury and death. Before
beginning installation, verify that all external overcurrent protection devices are open (Off), and
that they are locked-out and tagged appropriately to prevent activation during the installation,
verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal
protective equipment (PPE) per NFPA 70E. Failure to comply can cause serious injury or death.
Before proceeding with installation, read all instructions. Follow all local codes.
NOTE: The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers
for tower configuration and one DC-power cable and rack-mounting hardware, including screws,
handles and mounting rail kit (not included with “E” models).
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier
and your local dealer or your Vertiv representative immediately.
• Check the accessories included in packaging list. If there is any discrepancy, contact your local
dealer or your Vertiv representative immediately.
CAUTION: The UPS is heavy (see Specifications on page 55). Take proper precautions when
lifting or moving it.
3 Installation 21
3.3 Preparation for Installation
NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.
NOTE: When installing the UPS or making input and output connections, comply with all relevant
safety codes and standards
NO. DESCRIPTION
1 Support bases
2. If optional, Liebert® external battery cabinets will be connected, take out the spacers shipped
with the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 3.1 above. Each GXT4 requires
2 support bases, one in the front and one in the rear.
Figure 3.2 Remove the front plastic bezel cover and rotate display
NO. DESCRIPTION
5. Place the GXT4 and any battery cabinets on the 2 support bases.
CAUTION: The GXT4 is heavy. The UPS must be installed as near the bottom of a rack as
possible. If placed too high, it can make the rack top-heavy and prone to tipping over. For unit
weights, see Specifications on page 55.
3 Installation 23
3.5 Installing External Battery Cabinets
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote
electric power supplies before working with the UPS. Ensure that the unit is shut down and
power has been disconnected before beginning any maintenance.
CAUTION: The external battery cabinet(s) are heavy (see Table 9.3 on page 57). Take proper
precautions when lifting them.
Optional, Liebert® external battery cabinets (EBC) may be connected to the UPS to provide additional
battery run time. External battery cabinets are placed on one side of the UPS in a tower configuration or
stacked beneath the UPS in a rack configuration.
NO. DESCRIPTION
1 GXT4
1. Inspect the EBC for freight damage. Report damage to the carrier and your local dealer or
Vertiv representative.
2. Optional rack-mount hardware is shipped with the external battery cabinet and may be
installed at this time.
The UPS is now equipped with additional back-up battery run time. For approximate battery run times,
refer to Table 9.4 on page 61.
NOTE: When removing an EBC, the circuit breaker on the rear of the cabinet must be turned off before
disconnecting the cable.
NOTE: If the UPS will be shipped or stored for an extended time, the connector should be
disconnected. This will minimize any stand-by current drain on the batteries and help attain their
design life.
To configure and use the Liebert® IntelliSlot communication card, refer to the card’s user manual. Find
manuals online at http://www.VertivCo.com/en-us/support/.
NOTE: Do not operate the UPS with the power distribution box removed. To shut off all power to this
box and to the load, utility input power must be disconnected.
3 Installation 25
7. Insert the maintenance-bypass-interlock bracket behind the captive screw and tighten the
screw.
NOTE: The maintenance bypass breaker interlock bracket must be installed behind the captive screw,
and the screw must be tightened for the UPS to operate in inverter mode.
• PD2-CE6HDWRMBS fits the 5000 and 6000VA models of the Liebert GXT4
• PD2-CE10HDWRMBS fits the 10,000VA model of the Liebert GXT4
The installer must provide an upstream branch circuit breaker. The input circuit breaker on the
distribution box and the output circuit breaker on the rear of the power distribution box disconnect all
power between the main cabinet and the distribution box.
Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from
the input terminal block. The input circuit breaker on the distribution box does not disconnect power
from the manual bypass breaker.
GXT4-5000RT230 6 mm2 (8
32-A 4 mm2 (10 AWG)
GXT4-6000RT230 AWG)
2.26 Nm
16 mm2 (4 (20 in-lb)
GXT4-10000RT230 63-A 10 mm2 (6 AWG)
AWG)
3 Installation 27
3.6.3 Removing the Power Distribution Box
1. Manually transfer the connected equipment to the internal bypass.
a. From the main menu select CONTROL, then press Enter.
b. Select TURN ON & OFF and press Enter.
c. Select TURN ON UPS BYPASS and press Enter.
The UPS transfers the connected loads to the internal bypass. (For help, refer to
Performing Manual Bypass on page 42.)
d. Loosen the captive screw over the maintenance bypass breaker (see the following figure
for the breaker’s location).
e. Turn the maintenance bypass breaker On.
NOTICE
The load is unprotected from disturbances in the power supply while the UPS is on bypass.
NO. DESCRIPTION
NO. DESCRIPTION
1 Remove screws.
3 Installation 29
This page intentionally left blank
• Inverter
• Battery
• Bypass
• ECO Mode
• Fault
Figure 4.1 above, shows the indicators’ locations. Their descriptions and functions are as follows.
Bypass Amber On when the load is supplied by the mains through automatic/manual bypass
ESC Pressing this button returns to the previous menu or aborts any change in the input data field before confirming.
Pressing this button can move the cursor up or increase the value displayed in the input data field. When a menu is
Up
displayed on several screens, pressing the button can scroll up.
Pressing this button can move the cursor down or decrease the value displayed in the input data field. When a menu is
Down
displayed on several screens, pressing the button can scroll down.
Enter Pressing this button can enter the next level menu or confirm the parameter setting value.
4.3 LCD
The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in navigating
through the GXT4 menu (see Menu Structure on the facing page).
After about 10 seconds, the LCD shows one of the "On" screens. The screen shown depends on whether or
not input power is available.
To turn On the UPS, press the Up or Down button to select YES and press the Enter button. The UPS will
start up, the LCD will display UPS STARTING and then START SUCCESSFUL after the UPS is turned On.
NOTE: Values shown in the default screen will vary depending on installation and configuration.
In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery
capacity with run time estimate and load percentage. The UPS operation mode (online/inverter, ECO,
Battery or Bypass) will be indicated by the LED indicators.
If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen-saver
mode (back light turns off). It will remain off until a control button is pressed.
To select a sub menu, press the Up or Down button to move the cursor to the required item, then press
the Enter button to enter its sub menu or set its parameter.
Menu options
STATUS Screen
In the MAIN MENU screen, select STATUS to enter the Status Screen, displaying OUTPUT, LOAD,
INPUT, BATTERY and TIME SINCE STARTUP.
CONFIGURATION Screen
In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required
item, then press the Enter button to enter a sub menu or set its parameters.
UPS Screen
Select MAIN MENU > CONFIGURATION > UPS to enter the UPS screen. This menu has six screens.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
Select MAIN MENU > CONFIGURATION > BATTERY to enter the BATTERY screen. This menu has
four screens.
Press the Up or Down button to increase or decrease the value of the settings, and press the Enter
button to confirm it.
Select MAIN MENU > CONFIGURATION > ECO MODE to enter the ECO MODE screens.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
Select MAIN MENU > 2 CONFIGURATION > 4 OUTLET1 to enter the OUTLET1 screen. This menu has
two sub menus
Select 1 OUTLET CONTROL and press the Enter button to enter the OUTLET CONTROL screen.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
Select MAIN MENU > 2 CONFIGURATION > 4 OUTLET1 to enter the OUTLET1 screen. This menu has
two sub menus
Select 2 Outlet Setting and press the Enter button to enter the OUTLET SETTING screen.
Outlet2 Screen
The Outlet2 screens are the same as the Outlet1 screens. The same settings are available as on the
Outlet1 screen. If the Outlet2 group will have the same settings as the Outlet1 group, GXT4 offers a
programming shortcut. When configuring the Outlet2 group, select YES and press the Enter button
to apply the Outlet1 settings to the Outlet2 screen.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to
confirm the settings.
LCD screen
Select Main Menu > 2 CONFIGURATION > 6 LCD to enter the LCD screen. This menu has two sub
menus, LANGUAGE and COLOR.
Select 1 LANGUAGE and press the Enter button to enter the LANGUAGE screen.
Language screen
GXT4 supports multiple languages. For the list of supported languages and instructions on how to
upload them, refer to the Configuration Program user manual on the included CD.
Color screen
Select 2 COLOR and press the Enter button to enter the COLOR screen.
Select MAIN MENU > 2 CONFIGURATION > 7 FACTORY DEFAULT to enter the FACTORY DEFAULT
screen.
Control Screen
Select MAIN MENU > 3 CONTROL to enter the CONTROL screen. This screen has three sub menus,
TURN ON & OFF, ALARM CONTROL and BATT TEST.
In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and
press the Enter button to enter its sub menu.
Select MAIN MENU -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen. This
screen shows one of two displays, TURN ON UPS and TURN OFF UPS, depending on the state of the
UPS.
Select MAIN MENU -> 3 CONTROL -> 2 ALARM CONTROL to enter the ALARM CONTROL screen.
This section allows active audible alarms to be silenced.
To completely turn off the audible alarm, select CONFIGURATION > UPS.
Select MAIN MENU -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen.
Log Screen
Select MAIN MENU -> 4 LOG to enter the LOG screen. This screen has two submenus, VIEW LOG
and CLEAR LOG.
CLEAR LOG Screen
Select MAIN MENU > LOG > CLEAR LOG to enter the CLEAR LOG screen.
Press the Up or Down button to move the cursor to the required item. Press the Enter button to
confirm the settings.
ABOUT Screen
Select MAIN MENU> ABOUT to enter the ABOUT screen. The ABOUT screen displays UPS model,
serial number, software version and hardware version.
Network
The NETWORK screen displays the MAC address and the IPv4 IP address. If the GXT4 is fitted with
an optional Liebert® IntelliSlot Web card (Liebert IS-WEBCARD), the screen will display IPv6 IP
address settings (IPv6 requires configuration).
Mains Power Restored The mains power returns and the UPS transfers back to mains (AC) mode.
UPS Return From Battery Mode The UPS transfers back to mains (AC) mode from battery mode.
UPS Shutdown Command Received The UPS shut down was initiated through communication.
UPS Turn Off The UPS shuts down and has no output power.
UPS Turn On The UPS starts up successfully and supplies protected power to the load.
The UPS is configured to Online mode, supplying protected power to the load through
ECO Mode Disabled
the inverter.
UPS Load Return From Overload The loads are reduced, and the UPS recovers to normal state from overload.
Load On Inverter The inverter is on and supplies protected power to the load.
The UPS is on ECO mode; the mains is supplying power to the load directly to reduce
Load On ECO Bypass
energy usage.
Bypass Power Restored The bypass power recovered and the UPS can now transfer to bypass.
The mains power is not available, or it cannot satisfy the input requirements for the UPS to operate
Mains Power Not Available
from mains power
The UPS transfers to Bypass mode, at this point, the input mains power supplies power to the load
Load On Bypass
directly, and the load is not protected
The bypass power is not available, or it cannot satisfy the requirements for the UPS transfers to
Bypass Power Not Available
bypass
UPS Overtemperature Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode.
1. Enter the ALARM CONTROL screen, and select AUDIBLE ALARM ON or AUDIBLE ALARM OFF
to switch the alarm On or Off.
2. Enter the EVENT LOG screen, and select VIEW LOG to view the entire event log.
NOTE: There will be a short delay before the EVENT LOG screen displays the historical fault log to
allow the log to load.
NOTE: The GXT4's battery has been fully-charged before delivery, but some charge will be lost during
storage and shipping. To ensure that the battery has adequate reserve power to protect the connected
load, charge the battery for 5 hours before putting the UPS into service.
1. Check that the unit was wired by a qualified electrician and loads are connected properly and
reliably.
2. Check that the battery cable is connected properly.
3. Check that the communication cables are connected properly.
4. On the LCD, press either the Up or Down button once, then press the Enter button to turn On
the UPS.
The UPS will sound the audible alarm again as the output receptacles are now being powered
by the internal bypass, then will sound one more time as the inverter powers the connected
equipment.
5. Check the LCD and LED indicators to ensure that the UPS is operating normally.
6. Check the load percentage on the default screen to ensure that the connected equipment is
not exceeding the UPS’s rated capacity.
The UPS is now providing conditioned and protected power to the connected equipment.
• If the battery test results show FAILED, allow the UPS to recharge the batteries for 24 hours.
• Retest the batteries after 24 hours of charging.
• After the batteries have been retested, if the battery test still shows FAILED, contact your local
Vertiv representative or Technical Support.
5 Operation 41
5.4 Performing Manual Bypass
To manually transfer the connected equipment to the internal bypass:
If the internal bypass is not available because of input power problems, pressing this button once will be
ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If
other indicators are illuminated, refer to Troubleshooting on page 51.)
1. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF.
2. Press the Enter key.
3. Select TURN UPS OFF, then press Enter. Press either the Up or Down button to move the
cursor to confirm the turn off command and press Enter.
The UPS will sound an audible alarm. This is normal.
4. Power to the connected equipment is now Off.
The UPS display will still be illuminated because the batteries are still being charged. The UPS may now
be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds.
After powering Off the UPS, the UPS ceases output and the load is powered Off.
1. Place the UPS on internal bypass. This may be done by either of the following methods:
a. Refer to Performing Manual Bypass above.
b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This
requires loosening the captive screw and sliding the bracket up and away from the
Manual Bypass breaker.
2. Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires
loosening the captive screw and sliding the bracket up and away from the Manual Bypass
breaker.
CAUTION: To maintain safety (SELV) barriers and for electromagnetic compatibility, signal
cables should be segregated and run separate from all other power cables.
The Liebert® IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network.
The Liebert® IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the
network and/or building management system. The Liebert® IntelliSlot UNITY card also enables
monitoring external temperature, humidity and contact closure inputs using external sensors.
Follow instructions provided with the Liebert IntelliSlot card to configure the UPS or any additional
ancillary product for the Liebert® GXT4. The instructions are available at http://www.VertivCo.com/en-
us/support/.
A standard B-type USB port is provided to allow connection to a computer or network server. The USB
port can be used to communicate with the GXT4 configuration program (see section Configuration
Program below for details) or the Microsoft Windows shut-down feature.
For most users, the factory-default settings are adequate. This section give a brief overview of the
features and parameters that are available for modification, as well as the factory-default settings. Should
any changes be necessary, refer to the Configuration Program User Manual that is located on the
included CD for further details.
6 Communication 43
• Select frequency converter operation with a fixed output frequency of 50 Hz or 60 Hz, bypass
disabled (default is Auto-Select with bypass enabled)
• Set the Low Battery Warning alarm time from 2 to 30 minutes (default is 2 minutes)
• Enable/Disable the Auto-Battery test (default is Enable)
• Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable)
• Set the wiring mode of Remote shutdown (default is normally open)
• Set the Auto-Enable output after remote shutdown (default is Disable)
• Set the Auto-Battery test to 8, 12, 16, 20, or 26 weeks (default is 8 weeks)
• Select the number of external battery cabinets connected to the UPS to adjust the remaining
run time calculated by Vertiv software products (default is zero)
• Select one of multiple output voltages to match various voltages.
Table 6.1 Output voltage option
UPS MODEL FACTORY DEFAULT SETTING OUTPUT VOLTAGE OPTION
NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected
loads.
NOTE: This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’ It
is not compatible with earlier versions of the Liebert® GXT UPS.
A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows 7 or
Windows 8 is required to set up and run the configuration program.
NO. DESCRIPTION
2 On-battery warning
• Local Any Mode Shutdown can be performed by shorting the pins in terminal 3.
• Remote Any Mode Shutdown can be performed using a switch mounted at a remote location
and connected to the pins in terminal 3.
NOTE: Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
depending on the settings in the configuration program.
A current-limited source for this optocoupler (+12 VDC, 50 mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.
WARNING! When the Auto-Enable output option is selected and the UPS output is disabled
using Any Mode Shutdown, the GXT4 output can turn On automatically and without warning if
the connection is changed.
• Local Battery Mode shutdown can be performed by shorting the pins in terminal 4.
• Remote Battery Mode Shutdown can be performed using a switch mounted in a remote
location and connected to the pins in terminal 4.
6.3.3 On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the
battery this dry contact will be closed.
6 Communication 45
6.3.4 Low Battery
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from
the battery and has reached the Low Battery Warning time selected in the configuration program, this
dry contact will be closed.
The rated values for the dry contacts for the On Battery and Low Battery signals are:
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input
feeder breaker to remove all sources of power to the UPS and connected equipment to comply with
national and local wiring codes and regulations.
NO. DESCRIPTION
UPS ships with REPO jumper installed, allowing the UPS to operate.
1
Normally-closed switch system (fail-safe)
CAUTION: To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables
should be shielded and run separately from power cables.
GXT4-5000RT230
GXT4-240VBATKIT 2
GXT4-5000RT230E
GXT4-6000RT230
GXT4-240VBATKIT 2
GXT4-6000RT230E
GXT4-10000RT230
GXT4-240RTBKIT 2
GXT4-10000RT230E
7 Maintenance 47
7.1.1 Battery Replacement Procedures
Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the
UPS is always in a restricted access location (such as a rack or server closet). Contact your local dealer or
Vertiv representative to obtain the pricing of the appropriate replacement battery pack.
Figure 7.1 Removing the front bezel cover and battery door
3 Front bezel
NO. DESCRIPTION
2 Battery handles
6. Unpack the new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery pack to make sure they are the same type and
model. If so, proceed with 7. If they are different, stop and contact your Vertiv representative, or
Technical Support.
7. Line up and slide in the new internal battery pack.
8. Reconnect the battery plug and battery receptacle.
9. Push the battery wire and internal battery pack back into the UPS.
10. Reattach the front battery door with the 6 screws.
11. Reattach the front plastic bezel cover to the UPS.
NOTE: The internal battery pack is hot-swappable. However, caution should be exercised because
during this procedure the load is unprotected from disturbances and power outages. Do not replace
the battery while the UPS is operating in Battery Mode. This will result in a loss of output power and will
drop the connected load.
If the UPS will be stored for a long time, We recommend connecting the UPS to input power for at least 24
hours every 4 to 6 months to ensure full recharge of the batteries.
7 Maintenance 49
7.3 Precautions
Although the Liebert® GXT4 is designed and manufactured to ensure personal safety, improper use can
result in electrical shock or fire. To ensure safety, observe the following precautions:
• Check if the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
• Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal Mode. If it
is operating in Bypass Mode, stop and contact your local Vertiv representative or Technical
Support.
• Check if the battery is discharging: When the utility input is normal, the battery should not
discharge. If the UPS is operating in Battery Mode, stop and contact your Vertiv representative
or Technical Support.
Back-up the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are
normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators
are On and the UPS is operating normally.
3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.
The UPS should initiate battery self-test. Check to determine whether the battery is operating
normally. If not, stop and contact your Vertiv representative or Technical Support.
• The relative indicators illuminate, indicating the UPS has detected a problem.
• An alarm buzzer sounds, alerting the user that the UPS requires attention.
8.1.1 Faults
When the fault indicator is illuminated, the LCD displays the fault. The faults are described in Table 8.1
below.
UPS self test failed The battery is bad or weak. Contact technical support.
Over-temperature occurs to the UPS and the UPS will Reduce the load and contact technical
UPS Overtemperature
transfer to Bypass mode. support.
Fan Out of Order At least one fan is faulty. Contact technical support.
NOTE: If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the LCD
back light will flash (on 1 second and off 1 second) as an alert.
Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the LCD
back light will flash again until the UPS fault is corrected.
8 Troubleshooting 51
8.1.2 Audible Alarm
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS
operating status. The audible alarm will sound as described in the following table.
UPS is short-circuited or Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output
overloaded receptacles. Ensure loads are not defective or shorted internally.
UPS fails to Check to ensure the internal battery is connected. If it is not, make the connection and
Batteries are not charged
start try to start the unit. If the battery is connected, leave the UPS connected to input power
enough or not connected
for 24 hours to recharge batteries, then try to start the unit.
UPS is operating from battery mode. Ensure UPS is securely plugged into the wall
UPS is not plugged in
receptacle.
Battery
UPS input protection fuse UPS is operating from battery mode. Save data and close applications. Replace UPS input
indicator is
has blown/opened fuse, then restart UPS.
illuminated
Mains power is out of UPS is operating from battery mode. Save data and close applications. Ensure mains
tolerance supply voltage is within acceptable limits for UPS.
Battery Check battery connections, completely power down and restart UPS.
Battery source is not
indicator is NOTE: If the battery circuit opens while the UPS is running, it will be detected when the
available; continuous horn.
flashing. next battery test is performed.
Because the voltage or The AC input powers the PFC input and serves as the bypass source. If the AC is present
Bypass
frequency is outside but the voltage or frequency exceeds the acceptable range for safe operation with a load,
indicator is
acceptable limits, the the bypass will be disabled and this indicator will flash, indicating that the bypass is
flashing.
bypass is disabled. unavailable.
When reporting a UPS issue to Vertiv, include the UPS model and serial number. These are located in
several places for your ease of location:
8 Troubleshooting 53
This page intentionally left blank
Dimensions, mm (in)
Weight, kg (lb)
Input AC Parameters
220/230/240VAC
User-Configurable VAC
(May be modified using included configuration program)
Output AC Parameters
Waveform Sinewave
Main Mode Overload >200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute
9 Specifications 55
Table 9.1 Specifications (continued)
GXT4-5000RT230 GXT4-6000RT230 GXT4-10000RT230
MODEL NUMBER
GXT4-5000RT230E GXT4-6000RT230E GXT4-10000RT230E
Battery Parameters
Quantity x V 20 x 12V
5AH battery, CSB HR1221W or YUASA 9AH battery, CSB UPS12460F2 or CSB
Battery Mfr. / Part #
NPH5-12 HR1234WF2
Recharge Time (Internal Batteries) 5 hr. to 90% capacity after full discharge into 100% load
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Audible Noise <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides
Agency
Two IEC320 C19 16A/250V Sockets Four IEC320 C19 16A/250V Sockets,
Includes: Six C13 10A/250V Sockets Four C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps Manual Bypass Switch with Indicator Lamps
Dimensions, W x D x H, mm (in.)
Weight, kg (lb)
Unit 65 (143.3)
Battery Parameters
Quantity x V 1 x 20 x 12V
Environmental
Agency
9 Specifications 57
Table 9.4 Battery run times, minutes
230VAC RT MODELS
NUMBER OF LOAD PERCENT OF
BATTERIES/CABINETS CAPACITY
5KVA 6KVA 10-KVA
10% 95 86 99
20% 42 38 44
30% 36 31 25
40% 29 23 17
50% 24 17 13
70% 14 11 7
80% 12 9 6
90% 11 7 4
100% 9 7 4
30% 107 86 63
40% 80 61 44
+ 1 External 60% 49 36 26
Battery Cabinet 70% 38 29 21
80% 33 24 17
90% 29 21 14
100% 24 18 12
+ 2 External 60% 94 69 44
Battery Cabinets 70% 72 56 37
80% 63 47 29
90% 56 42 24
100% 47 37 22
80% 97 73 43
90% 88 64 37
100% 74 58 33
9 Specifications 59
Table 9.4 Battery run times, minutes (continued)
230VAC RT MODELS
NUMBER OF LOAD PERCENT OF
BATTERIES/CABINETS CAPACITY
5KVA 6KVA 10-KVA
80% 130 99 57
90% 118 90 48
100% 100 82 43
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 25°C
(77°F) with 100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the batteries.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-
discharge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the
battery above table will be restored. This will override any value that is auto-learned.
9 Specifications 61
This page intentionally left blank
e: eoc@vertivco.com
e: liebert.upstech@vertivco.com
e: liebert.monitoring@vertivco.com
e: microups.warranty@vertivco.com
63
This page intentionally left blank