Project Report On Transformer Testing
Project Report On Transformer Testing
Report Title
Transformer Testing:
Testing Methods and Testing Purposes
Submitted to
Submitted By
Specification of Transformer
Introduction
Transformer
A transformer is a stationary machine which facilitates in the transformation of electric power
from one circuit to another circuit of same frequency. The objective of a transformer is to convert
power from one system voltage to another. For a distribution transformer, this voltage
relationship, or voltage ratio, is determined by the ratio of the number of turns on the high
voltage winding to the number of turns on the low voltage
winding. As the alternating current in the high voltage
winding changes polarity 50 or 60 times a second (50Hz or
60Hz ac voltage), it induces a current in the low voltage
winding that is proportional to the voltage of the high
voltage winding divided by the ratio of the number of turns.
As the transformer works, it incurs power (and thus energy)
losses in the high voltage winding, the low voltage winding,
the core steel and in the surrounding transformer tank /
housing and fittings (called stray losses). The magnitude of
these losses relative to the power throughput determines
the efficiency of the transformer.
Various tests are done on a transformer to know its
efficiency and condition. The primary incentive of these tests
is to make sure the transformer meets manufacturing
specifications. Type test of transformer confirms basic
criteria of production lot. For confirming operational Fig. 1:A Distribution Transformer
performance of individual unit in a production lot routine test
is done. In this paper we have discussed in detail about some important test of a distribution
transformer.
Core
The core of the transformer is used to support the windings. It is
made of soft iron to reduce eddy current loss and Hysteresis loss
and provides low reluctance path to the flow of magnetic flux. The
diameter of a transformer’s core is directly proportional to copper
loss and inversely proportional to iron loss.
Windings
Fig. 2: Transformer Core
Windings consist of several copper coil turns bundled
together; each bundle connected to form a complete winding.
Windings can be based either on the input-output supply or
on the voltage range. Windings that are based on supply are
classified into primary and secondary windings, meaning the
windings to which the input and output voltage is applied
respectively. On the other hand, windings based on voltage
range can be classified into high voltage and low voltage Fig. 3: Transformer Windings
windings.
Insulating materials
Insulating materials like papers and card boards are used to isolate primary and secondary
windings from each other as well as the transformer core. These windings are made of copper
due to high conductivity and ductility. High conductivity minimizes the amount of copper needed
and minimizes losses. Moreover, high ductility results in easy bending of conductors into tight
winding around the core that also minimizes the amount of copper and volume of winding.
Transformer oil
The transformer oil insulates as well as cools the core and coil assembly. The core and windings
of the transformer must be completely immersed in the oil that normally contains hydrocarbon
mineral oils.
3
Conservator
The conservator is an airtight metallic cylindrical drum fitted
above the transformer that conserves the transformer oil. It
is vented at the top and is filled only half with the oil to allow
expansion and contraction during temperature variations.
However, the main tank of the transformer with which the
conservator is connected is filled with the oil through a
pipeline.
The breather is a cylindrical container filled with silica gel, which is used to keep the air that enters
the tank moisture-free. This is because the insulating oil when reacts with moisture can affect
the insulation and cause internal faults, which is why it is a must to keep the air free from
moisture. In the breather, when the air passes through the silica gel, the moisture contents are
absorbed by the silica crystals.
Tap changer
To balance voltage variations within the transformer, tap changers are used. There are two types
of tap changers – on load and off load. In on load tap changers, tapping can be changed without
isolating transformer from the supply, while in off load, the transformer needs to be
disconnected from the supply.
Cooling tubes
As the name suggests, cooling tubes are used to cool the transformer
oil. The circulation of oil within the transformer may be natural or
forced. In the case of natural circulation, when the oil temperature
rises, the hot oil naturally moves to the top and cold oil moves down,
while in case of forced circulation, an eternal pump is used.
Buchholz Relay
Placed over the connecting pipe that runs from the main tank to
conservator tank the Buchholz Relay senses the faults occurring
within the transformer. It operates by the gases emitted due to
decomposition of transformer oil during internal faults. Thus, this
device is used to sense and in turn protect the transformer from
internal faults.
Explosion vent
Fig. 6: Buchholz Relay
The boiling hot oil from the transformer is expelled during internal faults
through the explosion vent to avoid explosion of the transformer. This is generally placed above
the level of the conservatory tank.
Now, it is necessary to define measurement accuracy (or uncertainty levels) of test methods to make sure
that the manufacturer, the customer, and energy regulator all obtain the same result while testing
distribution transformers.
IEC:
The IEC is a worldwide standardization organization made up of national electrotechnical committees.
Purpose of the IEC is to facilitate international co-operation on all matters concerning standardization in
the electrical and electronic fields. The IEC, therefore, prepare and publishes international testing
standards through technical committees made up of representatives from any IEC National Committees
who are interested. International, governmental, and non-governmental organizations also participate in
this process. The set of international standards published under IEC 60076, Power Transformers, were
5
prepared by IEC Technical Committee 14. IEC mentioned of how to test transformer and standard of
testing value in their publication.
b) Routine Tests of Transformer Routine tests of transformer are to confirm an operating performance
of a separate unit in a production lot. Routine tests are conducted on every unit manufactured. Routine
tests of transformer also include:
Method:
IEC 60076-1 and IEEE C57.12.90 standards state that turns
ratio test will be carried out on a rated or lower test voltage
and rated frequency, by applying voltage on the HV side and
measuring the induced voltage. The turns ratio test is
conducted by applying a lowered test voltage to HV terminals Fig 8: Reading from turn ratio tester
and measuring an induced voltage at LV terminals, under no-
load transformer conditions. The ratio of those measured voltages is roughly equal to
transformer turns ratio. The turns ratio should be checked on each tap position. In the case of three-
phase transformers, when each phase is independent and easily accessible, single-phase power needs to
be used, although, when it is convenient, three-phase power can be used.
7
Our transformer is Dyn11. We are using Vanguard ATRT-03 S2 transformer turn ratio tester. This test
device produces and applies a true three-phase excitation test voltage to the three transformer primary
windings(H). The induced three-phase voltages across the unloaded transformer windings(X) is measured
and the transformer turns ratio is calculated for all three phases. In the display it shows the turn ratio of
every winding, excitation current and percentage difference of the measured ratio and calculated ratio.
Dyn11 Connection:
Dyn11 is vector group representation of transformer means
LV winding, which is star connected (written in small
letters means LV side) is 30 degrees lagging by HV(capital
letters) winding which is delta connected.
Step 03:
Measure Voltage between
1.1W and 2v (V1W2v)
2.1W and 2w (V1W2w) Fig 11: Connection for step 03
V1W2v > V1W2w
Step 04:
Measure Voltage between
1.1V and 2v (V1V2v)
2.1V and 2w (V1V2w)
V1V2v > V1V2w
Note:
1.Ensure only one terminal of HV and one terminal of LV is connected.
Fig 12: Connection for step 04
2.Ensure the additive voltage does not exceed the safe limit.
9
Method:
Normally, this test is conducted on low
voltage side of the transformer, i.e., all
measuring devices such as voltage (V),
wattmeter (W) and ammeter (A) are
connected in low-voltage side (say
primary). The primary winding is then
plugged into normal rated voltage V1, and Fig 16: Open circuit test connection
frequency as given on the name plate of the
transformer. The secondary side is being held open or is connected to a voltmeter V’. Since the
secondary (high voltage winding) is open circuited, the current drawn by the primary is called no-
load current I0 measured by the ammeter A. The value of no-load current I0 is very small usually
2 to 10% of the rated full-load current. Thus, the copper loss in the primary is negligible and no
copper loss takes place in the secondary as it is open. Thus, wattmeter reading W0 only
represents the core or iron losses for all practical purposes. These core losses are constant at all
loads. The Iron losses measured by this test is used to determine the transformer efficiency and
parameters of exciting circuit of a transformer
For Dyn11,
❖ Open the high voltage side (11kV side)
❖ Connect Voltmeter, Ammeter and Wattmeter as showing in the figure.
❖ Measure the volage, current and power.
Result:
No-load loss=Power consumed by the transformer(W1+W2).
No-load current=Ammeter reading.
Result:
Load loss=Power consumed by the transformer(W1+W2).
Impedance voltage =Voltmeter reading.
Acceptance Criteria:
The test is successful if no break down takes place at full test voltage during the test.
Why need transformer oil testing: Transformer oil, a type of insulating and cooling oil used
in transformers. Thus, the dielectric quality of transformer oil is essential for the secure operation
of a transformer. That’s why transformer oil needs to
be tested periodically to ensure that it is still fit for purpose.
Reason for this is transformer oil deteriorates through aging
and moisture entry, transformer oil should, depending on
economics, transformer duty and other factors, be tested
on a regular basis. Through such testing, transformers' lives
can be significantly increased, thus delaying new
investment of replacement transformer assets.
❖ At certain voltage level breakdown occurs in an electric arc, leading to a collapse of the
test voltage.
❖ An instant after ignition of the arc, the test voltage is off automatically by the testing
device. Ultra-fast switch off is desirable, as the carbonization due to the electric arc must
be limited to keep the additional pollution as low as possible.
❖ The transformer oil testing device measures and reports the root mean square value of
the breakdown voltage.
❖ After the transformer oil test is completed, the insulation oil is stirred automatically and
the test sequence is performed repeatedly: typically, 5 repetitions, depending on the
standard.
❖ As a result, the breakdown voltage is calculated as mean value of the individual
measurements.