ARCFLASH Analysis
ARCFLASH Analysis
Guidelines set in IEEE Standard 1584 will be used for this technical
report. Low Voltage equipment will be calculated using both IEEE
1584:2002 and IEEE 1584:2018 guidelines for comparison. High
tension equipment will be calculated using “Ralph Lee Method” which
is proposed and accepted method in the NFPA 70E standard.
Page | 263
Figure 44: IEEE 1584:2018 Arc Flash Calculation Process, Hazard
Determination Process
Page | 264
EC (Electrode Configuration) =VCB
Voltage Category for “k” constants =600V
Enclosure:
Actual width = 650mm
Actual height = 750mm
Actual depth =650mm
Page | 265
Reference U: Working Distances for different class of equipment
Electrode Configuration
Page | 266
3.14.1.2 Step 2: Calculate Intermediate arcing Current
(Iarc_Voc)
k1+k2logIbf +k3logG
Iarc_600 =10 ×
6 5 4 3 2
k4Ibf +k5Ibf +k6Ibf +k7Ibf +k8Ibf +k9Ibf + k10
Where:
Iarc_600 = Arcing current at Voc = 600 V, in (kA)
VOC = Open-circuit voltage (kV)
Ibf = three-phase symmetrical bolted fault current (kA)
G = gap distance between electrodes (mm)
Log base =10
1
Iarc =
2 2 2
0.6 1 0.6 -VOC
× 2-
VOC Iarc_600
2
0.6 ×Ibf
2
Where:
Iarc_600 = Arcing current at Voc = 600 V, in (kA)
VOC = Open-circuit voltage (kV)
Ibf = three-phase symmetrical bolted fault current (kA)
Iarc = 16.23kA
T = 30.2ms
Page | 268
3.14.1.4 Step 4: Calculate Enclosure Size Correction Factor
VOC +A -1
Width1 = 660.4+ Width-660.4 ×( ) × 25.4 (1)
B
VOC +A -1
Height1 = 660.4+ Height-660.4 ×( ) × 25.4 (2)
B
Width1 + Height1
EES= (3)
2
2
CF=b1×EES +b2×EES+b3 (4)
Where:
Height1 = Equivalent enclosure height
Width1 = Equivalent enclosure width
Width = Actual enclosure width
Height = Actual enclosure height
VOC = System voltage (kV)
A = Constant equal to 4 for VCB and 10 for VCBB and HCB
B = Constant equal to 20 for VCB,24 for VCBB, and 22 for
HCB
EES = Equivalent enclosure size
CF = Enclosure size correction factor
b1 to b3 = Coefficient for Formula (4) provided in table:
0.4+4 -1
Height1 = 660.4+ 750-660.4 ×( ) × 25.4
20
Height1 = 26.78mm
25.91+ 26.78
EES=
2
EES= 26.343
b1 = -0.0001923
b2 = 0.01935
b3 = 0.6899
2
CF=-0.0001923×26.343 +0.01935×26.343+0.6899
CF=1.066
12.552 t
E600 = ×T×10
50
k3Iarc600
t=k1+k2logG+ 7 6 5 4 3 2
k4Ibf +k5Ibf +k6Ibf +k7Ibf +k8Ibf +k9Ibf +k10Ibf
+k11logIbf + k12logD + k13logIarc + log (1/CF)
Page | 270
Where:
Iarc_600 = Arcing current at Voc = 600 V (kA)
Iarc = Arcing current (kA)
VOC = Open-circuit voltage (kV)
Ibf = three-phase symmetrical bolted fault current (kA)
D = working distance (mm)
G = gap distance between electrodes (mm)
CF = Enclosure size correction factor
k1 to k13 coefficients are given from this table:
Page | 271
3.14.1.6 Step 6: Arc Flash Boundary (AFB)
k3Iarc_600
k1+k2logG+ 7 6 5 4 3 2
⎛ k4Ibf +k5Ibf +k6Ibf +k7Ibf +k8Ibf +k9Ibf +k10Ibf⎞
⎜ 1 20 ⎟
+k11logIbf+k13logIarc+log -log
⎜ CF T ⎟
⎜ -k12 ⎟
⎜ ⎟
AFB600 = 10⎝ ⎠
Where:
Iarc_600 = Arcing current at Voc = 600 V (kA)
Iarc = Arcing current (kA)
VOC = Open-circuit voltage (kV)
Ibf = three-phase symmetrical bolted fault current (kA)
D = working distance (mm)
G = gap distance between electrodes (mm)
CF = Enclosure size correction factor
k1 to k13 coefficients are same values taken from computation of
incident energy.
AFB600 = 10⎝ ⎠
AFB600 = 454.14mm
Page | 272
Figure 45: Illustration of Arc Flash Boundary
6 5 4 3 2
VarCf = k1*Voc +k2*Voc +k3*Voc +k4*Voc +k5*Voc +
k6*Voc+k7
Where:
VOC = Open-circuit voltage (kV) = 0.4kV
k1 to k7 coefficients are given from this table:
Page | 273
Reference Z: Coefficient for Arcing Current Variation Correction
Factor
Cf = 1-0.5*VarCf
Formula 49: Arcing Current Variation Correction Factor
Page | 274
3.14.1.9 Step 9: Calculate Intermediate Incident Energy
(E_Voc) - Minimum
12.552 t
E600_min = ×T×10
50
k3Iarc600
t=k1+k2logG+ 7 6 5 4 3 2
k4Ibf +k5Ibf +k6Ibf +k7Ibf +k8Ibf +k9Ibf +k10Ibf
+k11logIbf + k12logD + k13logIarc_min + log
(1/CF)
Where:
Iarc_600 = Arcing current at Voc = 600 V (kA)
Iarc_min = Arcing current (kA) , minimum
VOC = Open-circuit voltage (kV)
Ibf = three-phase symmetrical bolted fault current (kA)
D = working distance (mm)
G = gap distance between electrodes (mm)
CF = Enclosure size correction factor
k1 to k13 coefficients are given from previous Incident energy
calculation
Page | 275
3.14.1.10 Step 10: Arc Flash Boundary (AFB) - Minimum
AFB600 _min=
k3Iarc_600
k1+k2logG+ 7 6 5 4 3 2
⎛ k4Ibf +k5Ibf +k6Ibf +k7Ibf +k8Ibf +k9Ibf +k10Ibf⎞
⎜ 1 20 ⎟
+k11logIbf+k13logIarc_min+log -log
⎜ CF T ⎟
⎜ -k12 ⎟
⎜ ⎟
10⎝ ⎠
Where:
Iarc_600 = Arcing current at Voc = 600 V (kA)
Iarc_min = Arcing current (kA) , minimum
VOC = Open-circuit voltage (kV)
Ibf = three-phase symmetrical bolted fault current (kA)
D = working distance (mm)
G = gap distance between electrodes (mm)
CF = Enclosure size correction factor
k1 to k13 coefficients are same values taken from computation of
incident energy.
AFB600_min = 10⎝ ⎠
AFB600_min = 418.5mm
Page | 276
3.14.2 IEEE 1584:2002, Low Voltage Arc Flash Calculation
Low voltage equipment will be calculated based on IEEE
1584:2002. Outcome will be compared and tabulated with earlier
calculation results of IEEE 1584:2018.
Iarc=10^[k+0.662logIbf+0.0966V+0.000526G+0.5588V(l
ogIbf)-0.00304G(logIbf)]
Where:
Iarc = arcing current in (kA)
V = system voltage (kV)
Ibf = three-phase symmetrical bolted fault current (kA)
G = gap distance between electrodes (mm)
k =0.153 for open air and -0.097 for arcs in a box
log base =10
Given:
Ibf = 24.18 kA
V = 0.4 kV
G = 32 mm
k = -0.097
Page | 277
3.14.2.2 Step 2: Calculate Incident Energy (Ei)
Ein=10^{k1+k2+[1.081x(logIarc)]+0.0011G}
Formula 54: Normalized Incident Energy, IEEE 1584:2002
Where:
Iarc = arcing current in (kA)
k1 = -0.792 for open air and -0.555 for arcs in a box
k2 = 0 for high impedance and -0.113 for grounded
Cf = calculation factor 1.0 for V>1kV, 1.5 for V<=1kV
t = arching time in seconds from time current curve
G = gap distance between electrodes (mm)
X = distance exponent,
switchgear=1.473, MCC and panel = 1.641
D = working distance
Given:
Iarc = 11.194kA
k1 = -0.555
k2 = -0.113
Cf = 1.5
t = 0.0302s
G = 32mm
X = 1.473
D = 609.60mm
Page | 278
Substituting Values to formula:
Ein=10^{-0.555-0.113+[1.081x(log11.194)]+0.0011(32)}
Ein=3.171cal/cm²
Where:
AFB = Arc Flash Boundary in mm
Eb = Incident Energy at arc flash boundary, typically
1.2cal/cm² or 5j/cm²
Ein = Incident Energy normalized
Cf = calculation factor 1.0 for V>1kV, 1.5 for V<=1kV
t = arching time in seconds from time current curve
X = distance exponent,
switchgear=1.473, MCC and panel = 1.641
Given:
Eb = 5j/cm²
Ein = 3.171cal/cm²
Cf = 1.5
t = 0.0302s
X = 1.473
Substituting Values to formula:
AFB={4.184 x 1.5 x 3.171 [(0.0302/0.2)x (610^1.473/5)]} ^
(1/1.473)
AFB=431.69mm
Page | 279
3.14.3 Arc flash Calculation for 22kV equipment
To calculate arcing current, incident energy and arc flash boundary
at 22kV equipment, Ralph Lee method will be used.
Iarc=10^(0.00402+0.983logIbf)
Formula 57: Arc Flash Boundary, Lee method
Where:
Ibf =three-phase symmetrical bolted fault current (kA)
=20.97kA at fault 1
Substituting Values to formula:
Iarc =10^(0.00402+0.983log20.97)
Iarc =20.098kA
6 t
Ei= 2.142X10 VIbf 2
D
Formula 58: Incident Energy, Lee method
Where:
V = voltage system
Ibf = Three Phase Bolted fault current
D = Distance from possible arc point to person in mm
t = Is the arcing time in Sec.
Given:
V = 22kV
Ibf = 20.97kA
D = 910mm
t = 0.08 seconds (Refer to next table, for the clearing Time)
Page | 280
Reference AA: Power Circuit Breaker Operating Times from IEEE
Std. 1584 Guide for Performing Arc Flash Hazards Calculation,2002
6 .08
Ei= 2.142X10 (22)(20.97) 2
910
Ei= 95.466 J/cm² or 22.82cal/cm²
6 t
AFB = 2.142×10 VIbf
Eb
Where:
V = voltage system
Ibf = Three Phase Bolted fault current
Eb = incident energy at the boundary distance in J/cm²
Typical value is 5J/ cm²
t = Is the arcing time in Sec.
Page | 281
Given:
V = 22kV
Ibf = 20.97kA
Eb = 5J/ cm²
t = 0.08 seconds
6 0.08
AFB = 2.142×10 ×22×20.97
5
AFB = 3676.31mm
Iarc@0.85 =10^(0.00402+0.983log17.825)
Iarc@0.85 =17.131kA
6 0.08
Ei@0.85 = 2.142X10 (22)(17.825) 2
910
Ei@0.85 = 81.146 J/cm² or 19.395 cal/cm²
6 0.08
AFB@0.85 = 2.142×10 ×22×17.825
5
AFB@0.85 = 3665.98mm
Page | 282
3.14.3.5 Tabulation of Calculated Results and Identifying
Flash Hazard Risk Category
Note: There are three Low voltage equipment fault points
considered for this report’s arc flash calculation. Only MSB-B fault
point’s arc flash calculation has been shown in detail. The summary
will include two more points which are in sub and distribution board
level subsequently. Detailed calculations for both were done in
Microsoft Excel Program.
Range of
Flash
Calculated Minimum
Hazard
Incident PPE Rating Clothing Required
Risk
Energy [cal/cm2]
Category
[cal/cm2]
As result, all low voltage equipment has very low calculated incident
energy and therefore identified as “0” under Flash Hazard Risk
Category. The circuit breaker has a very fast short circuit current
clearing time which results to diminish the growth of incident energy
during fault.
Page | 283
Table 38: Summary of Arc Flash Analysis (0.4kV) IEEE 1584:2018
Page | 284
Table 39: Summary of Arc Flash Analysis (0.4kV) IEEE 1584:2002
As observed, both calculations of IEEE 1584 for 2002 and 2018
versions have almost same incident energy results and the hazard
risk fell into same category. On the other hand, the calculated arcing
current has significant non-similarity due to more detailed calculation
approach in IEEE 1584:2018 version.
The hazard risk category in High Tension side landed in category “3”
for having an incident energy of more than 8 but less than 25. This
project has SF6 gas insulated switchgear for 22kV switchboard. It
may not be necessary for working personnel to wear a PPE with
minimum rating of 25cal/cm² due to the arc quenching feature of the
switchgear. Furthermore, the design of 22kV network on this project
allows the total de-energization of switchgear, if necessary, by
isolating the “before and after” adjacent switchgear in the loop. The
calculation done on high tension side is good for studying purpose
only.
Currently, there are no visible Danger Sign for Arc Flash Hazard at
site substation. It may not be necessary for the reason that the Flash
Hazard risk category on low voltage side is “0”. Also, for high tension
side, it’s good to know that the incident energy calculated can
correspond to category “3” hazard. However, having a Gas Insulated
Switchgear played its important part to mitigate any high current
arching that can result to release of huge incident energy.
Page | 285
Page | 286
Table 40: Summary of Arc Flash Analysis (22kV) Lee method
Figure 46: Arc Flash Hazard Danger Sign
Page | 287
Figure 47: Arc Flash Hazard Risk Categories and Personal
Protection Equipment (PPE) Ratings
Page | 288