Type Tests Defined in IEC 61439
Type Tests Defined in IEC 61439
Table of contents:
They cover the following checks for type tests:
1. Type tests:
1. Temperature rise limits
2. Dielectric properties
3. Short-circuit resistance
4. Effectiveness of the protective circuit
5. Clearances and creepage distances
6. Mechanical operation
7. Degree of protection (IP)
And there are also six tests designed to check the construction quality are
added to the above type tests in standard IEC 61439-1.
1. Type tests
1.1 Temperature rise limits
Verification in temperature rise limits test is one of the most critical in
determining the reliability and long service capability of a low voltage assembly
and must not be overlooked. Excessive temperatures result in premature
ageing of components and insulation, and ultimately failure.
Option 1
The incoming circuit and at least one outgoing circuit of each rating are loaded
to their rated current. If a circuit of each basic type is not included in the test,
further tests are carried out until one outgoing circuit of each type has been
included. This approach is suitable where a specific arrangement and design
of assembly is to be verified with the minimum amount of testing.
As the outgoing circuits are tested with a diversity (loading) factor of unity, it
does, however, result in a more onerous test than necessary for most
applications.
Option 2
Outgoing circuits are temperature rise tested individually to verify they are
capable of carrying their rated current. The incoming circuit is then supplied to
its rated current. This is distributed through as many outgoing circuits as
practical, including one outgoing circuit of each basic type and in the most
onerous configuration, with each circuit loaded to its rated current multiplied by
the rated diversity (loading) factor .
Again, this test regime is only suitable for a specific arrangement and
design of assembly, but it does better reflect the normal loading of an
assembly.
Option 3
This alternative has been included to enable modular assembly systems to
be fully verified. Horizontal busbars, vertical busbars and outgoing functional
units are tested individually. The assembly as a whole is then verified as in
Option 2.
Whilst this method of temperature rise testing involves a lot of testing, once it is
completed it covers all the possible arrangements available in a flexible
modular system, and avoids any concerns that may previously have arisen
due to the specific arrangement supplied not being exactly as that tested.
Note that temperature rise tests are time consuming. A lot of time is
required to connect all the circuits to be included in the test, balance the current
and insert the thermocouples. Current is applied until conditions stabilize,
usually around eight hours, and, in the final hours, temperatures are monitored,
normally with thermocouples.
Note that temperatures rises are given in Kelvin to differentiate them from
temperatures given in °C.
1.1.2 Temperature rise test on busbars
The various currents given for all the bar and distribution systems have been
checked under the most severe conditions, according to the degree of
ventilation of the enclosure (IP ≤ 30 and IP > 30), so that the temperature rise
of the busbars does not exceed 65 K.
Impulse
withstand voltage test performed on assemblies (on photo: Tests in the impulse current
laboratory by DEHN)
The continuity of the protective circuit is also checked at a high fault current that
could occur following accidental detachment of a conductor.
The protective circuits (conductors, terminals or collector bars), are sized and
tested to withstand the maximum short-circuit thermal stress that could occur
according to the current at the supply end of the assembly.
When modular devices and equipment are installed in accordance with the
specified conditions, the distances are observed for the insulation voltages of
these devices. Experience has shown that the greatest risk is in the wiring.
Connections, bundles of conductors and busbars must be meticulously
checked.
Unsuitable connectors, bolted connections, joints and metal supports can
reduce the initially planned insulation values.
The insulation used has a tracking current resistance of at least 400 V, which
means it is not very sensitive to damp (group I and group II according to IEC
60664-1).
Extinguishing must take place in less than 30 seconds. All elements that make
up LV assemblies comply with this requirement.
The electrical circuit of the control unit is fully protected by fuses and
a miniature circuit breaker and incorporates mains on off switching and push
button control of the output current. Self contained cabinet with large viewing
window and dark colored interior.
With a temperature-rise test, the object will be tested up to reaching the point of steady
temperature condition, according to the rated current, specified by the
manufacturer/customer. The examination, significant for all equipment, is considered as
passed, when the high temperature, determined at different measuring stations, does not
exceed the fixed level specified in the test requirements.
Temperature rise depend on the circulating electric current, the materials involved, and the
contact resistances, the ambient air temperature, the air velocity and the geometry of
conductors and compartment components.
Test procedure:
All circuit within the assembly shall be individually capable of carrying their rated current
(sec: IEC61439-1/sec.5.3.2). However, the current carrying capacity may be influenced by
adjacent circuits. So, Test shall be conducted with maximum current of each incomer and
outgoer. We have chosen two combinations to match incomer value.
1. Bring all external connections of Breaker 2 meters outside the panel, by using sufficient
cables or busbars as recommended in IEC 61439-1, Sec: 10.10.2.3.2, table 11 & 12.
3. Switch ON incomer and outgoers, which are participating in test (i.e., in test-1, Feeders
IC, OG-1, 3, 5, 6). Make sure that other outgoers, which do not use in this test is in OFF
condition.
4. In each outgoer, connect 2 meter extended external terminals of all phases together
(make star point) as shown in figure1.
5. Inject the current of 800A to the incomer. Read the current in each phase of the extended
terminals of outgoers, which is shorted.
6. If the outgoers load current is not matching with customer requirement (in our case,
Values as shown in Table 1, Test-1/2). Balance the load current to requirement by
adding/removing the cables.
That means, to increase the load current we can either add the cross sectional area of cable
or reduce the cable length and vice-versa.
Switch OFF the transformer main supply after load balancing.
7. After balancing the load, Place the temperature sensor probes (thermocouples) in the
different place where temperature may vary and rise gradually. IEC standard suggests to
place thermocouple at
a. Busbar joints
b. Incoming and outgoing terminals of each breaker which are participating in
testing. (OGs & IC)
c. Terminal blocks of each outgoer which is participating in test.
d. Body of each breaker which is participating in test.
e. Extended rotary handle/external knobs of breakers (which is testing)
f. Body of the panel.
g. At least two ambient temperature points.
8. These probes shall be connected to a local monitoring system. And we can read the
temperature at every point from here.