Precimeasure: MODEL - 1007 SERIES...
Precimeasure: MODEL - 1007 SERIES...
The WTI instruments have a built in Thermal imaging system for transformer’s hot spot indication.
WTIs are calibrated & supplied suitable for range of CT secondary input & temperature rise.
Instrument cases are aluminium die casted and polyester powder coated, and provided with projection mounting clamps.
As per enclosure part no. EN7.
Switch Differential S1& S2: 3°C to 9°C (6±3°C)Fixed S3 to S4: 8°C to 40°C Adjust-
able.
1/4
Optional Spec
Temperature Range 0-1600C / 30-1500C / -20-1400C / other range on request
1007H Built in CCU Model 2245H Suitable Hybrid Model Connection from built-in
CCU inside Local OTI/WTI
1007H Built in CCU and external PSU Model 2245 Suitable for 4 - 20mA input from External PSU
Resolution 0.10C
Degree of protection IP 20
Signal input Suitable for connection from built-in CCU inside the Local OTI/WTI / Ex-
ternal PSU
Signal output Refer table below (Remote Indicator Output Options) Remote Indicator 96 Sq
Signal input Suitable for connection from built-in CCU inside Local OTI/WTI
Note: Available Scheme options referenced below. Please contact us for details.
1. Standard (1007)
2. Hybrid and External Remote Indicator (1007H + RI)
3. Hybrid and External PSU (1007H + PSU)
4. Hybrid & External PSU + Remote Indicator (1007H + PSU + RI)
2/4
Routine and Type Tests Basic Ordering Information
Conducted Select Your Model Standard -1007
1 Routine test : HV Test and IR Test and Calibra- with 1 inbuilt PT 100 Sensor (Simplex) & CCU - 1007H
tion Test
Switch Contact Rating OP1 - Option 1 - Standard Micro Switch
OP 2 - Option 2 - Magnetic Blowout Micro Switch
2 Protection class:
IP55 as per IEC 60529 CAT II. Type of Instrument OTI/WTI
Range R1.0 - 1500C
R2.0 - 1600C
3 Cold Test: -400C as per IEC 60068-2-1
R3.30 - 1500C
Dry Heat Test: + 700C as per IEC 60068-2-2
R4. -20 to 1400C
(other ranges on request)
4 Vibration Test: as per IEC 60068-2-6
No. of Switches S2 -2switches
Displacement : 0.15mm,
Frequency: 10-55Hz, S3 -3switches.........upto S4 switches
Duration: 1hr. 20min/X,Y,& Z axis
Switch Configuration L- Normally open contact
L2 - Changeover contact
5 Salt Spray Test: Capillary Length C3 - 3 mtrs C5 - 5 mtrs
For polyester powder coating and C8 - 8 mtrs C10 - 10 mtrs
SS 304 Armour for 500 Hrs as per C12 - 12 mtrs C15 - 15 mtrs
DIN 50021 Standard
C20 - 20 mtrs C25 - 25 mtrs
Union Type U1 - ½” BSP Male
6 Micro Switch rating Test: U2 - ¾” BSP Male
a) 15A @ 250V AC & U3 - 1” BSP Male
0.5A @ 250V DC U4 - ½”BSP Female
U5 - ¾” BSP Female
b) 15A @ 250V AC &
Other threads on request
5A @ 250V DC
Indicator RI - Remote Indicator (for options please see Note below)
If WTI please specify Transformer CT Secondary output ..............
Simulated Temperature rise over top oil ..........
Contact Precimeasure for gradient graph
Note:
Remote Indicator Options
T1 - Indication only.
T2 - 2Nos, 4-20mA DC outputs.
T3 - one 4-20mA DC output + 2Nos. Change over relay contacts
T4 - one 4-20mA DC output + RS 485 Modbus RTU protocol
T5 - 4Nos. of 4-20mA DC outputs.
Note: WTI Gradient calibration is factory set as per customer specification. If required,
a provision is made for small adjustment at site.
Sample Ordering Information : 1007\OP1\WTI\R1\S4\L2\C6\U1\RI-T1\........... Amps .......... oC