Data Sheet GST
Data Sheet GST
RU
E-MAIL: hombi@hombi.ru HTTP://GSTRU.RU HTTP://WWW.HOMBI.RU
Digital Optical Smoke
Detector DI-9102
Electrical
Box
60
Conduit
MARK 1
MARK 2
DETECTOR
Base
78mm
Detector
Programming
The address and sensitivity of the detector
100m m
can be programmed using GST handheld
programmer (P-9910), purchased separately.
Connect the two wires of the handheld
75 programmer to any two opposite terminals of
the detector.
60
45
DETECTOR TERMINAL
REMOTE INDICATOR
Electrical
Box
60
Conduit
MARK 1
MARK 2
DETECTOR
Base
78mm
Detector
Programming
The address and sensitivity of the detector
100m m
can be programmed using GST handheld
programmer (P-9910), purchased separately.
Connect the two wires of the handheld
75 programmer to any two opposite terminals
of the detector.
60
45
DETECTOR TERMINAL
REMOTE INDICATOR
ROTATE CLOCKWISE
TERMINALS
1 2
MOUNTING DETECTOR TERMINAL
FROM CONTROL PANEL TO NEXT DEVICE FIELD DEVICE PROGRAMMER
1 PAIR FIRE CABLE 1 PAIR FIRE CABLE
4 3
Ordering Information:
Detector Installation
Part No Description Weight Pack
The Intelligent Multi sensor should be /Kg Qty
installed in compliance with all local codes per
having a jurisdiction in your area or NFPA 72 Box
National Fire Alarm Code, NFPA 70 National I-9101 Intelligent Multi 0.123 120
Electrical Code, BS 5389 and EN54. Before Sensor
installation verify the proper wiring and base DZ-03 Standard 0.050 360
are firmly mounted to prevent detector Detector Base
damage before the installation. Point the
MANUFACTURED IN ACCORDANCE WITH
DETECTOR TERMINAL
TERMINALS
TO NEXT DEVICE
1 PAIR FIRE CABLE Selection of compatible Control Panels
1 2 Compatible with all GST Intelligent Fire
FROM CONTROL PANEL Alarm Panels GST 100, GST 200, GST 5000
and GST 9000.
1 PAIR FIRE CABLE
4 3
REMOTE INDICATOR
Ordering Information:
Part No Description Weight Pack
Detector Installation /Kg Qty
per
The Intelligent optical smoke detector should
Box
be installed in compliance with all local codes
I-9102 Intelligent 0.123 120
having a jurisdiction in your area or NFPA 72 Optical Smoke
National Fire Alarm Code, NFPA 70 National Detector with
Electrical Code, BS 5389 and EN54. Before Remote
installation verify the proper wiring and base Indicator
are firmly mounted to prevent detector DZ-03 Standard 0.050 360
damage before the installation. Point the Detector Base
detector in the base by the mark-line and
secure the detector in that position by
rotating it clockwise until it reaches the next MANUFACTURED IN ACCORDANCE WITH
mark line.
ROTATE CLOCKWISE
CONCRETE PAD OR EMBEDDED BOX
HOLDING PAD
SCREW
Programming
TO NEXT DEVICE
1 PAIR FIRE CABLE
DETECTOR TERMINAL
1 2
4 3
REMOTE INDICATOR
Selection of compatible Control Panels
1.0mm².
TERMINALS
1 2
MOUNTING
DETECTOR TERMINAL
4 3
Selection of compatible Control Panels
TO POWER SUPPLY
24VDC
D1 D2 Z1 Z2
The Intelligent beam detector should be Compatible with all GST Intelligent Fire
installed in compliance with all local codes Alarm Panels GST 200, GST 500, GST 5000,
having a jurisdiction in your area or NFPA 72 GST 9000.
National Fire Alarm Code, NFPA 70 National
Electrical Code, BS 5389 and EN54. The
detector can be mounted in 2 ways: the
installed onto standard two gang electrical Ordering Information:
box, or directly by drilling the holes and
fixing with plugs. Part No Description Weight Pack
/Kg Qty
per
Box
I-9105R Intelligent 1.3 10
Reflector Beam
Detector
Technical Specifications
Programming
¡Ý cm
Gas 1. 5m<L<4m
Stove
V1 V2 Z1 Z2 D1 D2
Liquefied Petroleum
Gas Detector Within 30cm
Floor
FIELD DEVICE PROGRAMMER
Connect the wires to the required terminal Compatible with all GST Intelligent control
according to the wiring diagram. D1, D2: To panel.
power bus, non-polarized. Z1, Z2: To signal
bus, non-polarized. V1, V2: To pipe pulse Ordering Information:
solenoid valve, when the detector alarms, Part No Description Weight Pack
there is a forward 12V pulse between V2 and /Kg Qty
V1 (V2 is + and V1 is -). per
Box
I-9602LW Addressable .230 100
Gas Detector
Description
The DP9100 Duct Probe is the latest
innovation for early detection of smoke
present in the air moving through HVAC
ducts in commercial, industrial and
residential application. The unit is designed to
prevent the circulation or spread of smoke
within air handling systems, fans and blowers.
The complete system may be shutdown in
the event of smoke detector alarm provided
by the fire alarm control panel.The GST Duct
Wiring and Connection
Probe is built to meet the all local code
Refer to installation manual.
requirements.
Ordering Information:
Selection of compatible Control Panels
Part No Description Weigh Pack
Compatible with all GST Addressable and t/Kg Qty
Conventional Optical Smoke detector. per
Box
DP9100 GST Duct Probe 0.99 1
Feature
A Description Label
Record Label
B
• Non polarized terminals Multi-
positioning designs allows easy
direction adjustment of the
detectors
• Compatible with GST conventional
detectors using 4K7 Ohms resistor
EOL Mounting
• Common base for GST 1- Hole
Anti-tamper Hole
9101/2/3/4
Description
DZ-03 Base is used to mount conventional Wiring and Connection
and intelligent smoke, heat and Refer to installation detectors manual.
combination detectors as their conductive
base. It’s made of flame-resistant plastic Ordering Information:
ABS, which is a UL94 listed material. It
features attractive appearance, novel Part No Description Weigh Pack
structure and stable performance. Its t/Kg Qty
flame class is V-0. During installation, you per
Box
can easily fix the base before connecting
DZ03 GST Standard 0.059 360
cables, and then twist the detector onto the Base
base. DZ-03D GST Standard 0.059 360
Diode Base
ELECTRICAL
modern building interior. BACK BOX
B−9201
Contain integral LED indicator to denote BACK BOX
operational mode.
Programming
6 5 4 3 2 1
12 11 10 9 8 7
MANUFACTURED IN ACCORDANCE WITH
Z1 AND Z2
TERMINAL
Technical Specifications
• Standard: EN54-part 11
• Approval: LPCB,CE
• Protection rating: IP 40
• Operating voltage: 24Vdc Loop
• Operating current:
Standby current 0.8mA
Alarm Current 2mA
• Operating temperature: -10°C to
+50°C
• N/O Output contact: 60Vdc, 0.1A
• Contact resistance: 100mΩ
• Relative humidity: 95%
• Application: Indoor use
Features and Benefits • Visual Indicator: LED, Red ( lit
steady when alarm, 3 sec interval
1. Compatible with latest EN standards blinking at normal state)
2. Re-settable (non-breaking glass) • Front Cover: Plastic glass (optional)
3. Optional flipping plastic cover (C-92FC) • Material and colour: ABS, red
4. Additional volt free contact • Wiring: 1 pair non polarized
5. Electronically addressed (by P-9910B) • Dimensions: 97x100x45.5mm
6. Friendly installation and test
Description
Mounting Base
Designed for the purpose of raising an alarm
manually once verification of a fire or The manual call point should be installed in
emergency condition has occurred. By compliance with all local codes having a
pressing the non breakable glass. Meets the jurisdiction in your area or NFPA 72
standard requirement of EN 54 part 11, National Fire Alarm Code, NFPA 70 National
European Standard and approved by Loss Electrical Code, BS 5389 and EN54. Surface
Prevention Certificate Board (LCPB). mount and it is installed onto a standard
The I-9202 constructed of high impact red one gang electrical box with a mounting
ABS with a modern pleasing appearance. The hole that has 52mm~68mm spacing.
terminating back box enables first fix
installation and termination leaving the fascia
with integral electronics to be simply plugged
into base at the time of commissioning. Non
breakable glass that can be reset with the I−9202
GST standard reset key. WALL
The I-9202 operated via a micro-switch that
when pressed a signal will be transmitted to FIRE
the panel and the volt free contact will be ALARM ACTION
ELECTRICAL
latched. Contains integral LED indicator to BACK BOX
confirm operation. PRESS HERE
1 23 4
5 6 7 8
K1 K2 Z1 Z2
LOOP IN
LOOP OUT
Programming
Z1 AND Z2
TERMINAL
Description
Designed to protect manual call point from an accidental operation and suitable for 92 MCP
series. The C-92FC constructed of high plastic quality with a modern pleasing appearance.
Technical Specifications
Ordering Information
Technical Specifications
Connect the wires to the required terminal Compatible with all GST Intelligent Fire
according to the wiring diagram. The Z1 (14), Alarm Panels GST 200, GST 5000, GST
Z2 (15) connect to addressable fire detection 9000.
loop, non-polarized, while G (11) and I1 (12)
connect to field device passive contact. The Ordering Information:
cable must be fire rated type and the size
depends on the distance and application. Part No Description Weight Pack Qty
Minimum size gauge 1.0mm²(18 AWG) /Kg per Box
I-9300 Addressable .180 120
Input Module
G I1 Z1 Z2
NO/NC
FIELD DEVICE
Programming
1 2 3 4 5 6 7 8
16 15 14 13 12 11 10 9
Features and Benefits The input can be linked through a volt free
contact switch output of ancillary
1. Addressable I/O with 24Vdc/5A, equipment reporting to the fire alarm
110Vac/3A relay output contacts controller. According to the pre-inputted
2. Input can be configured as NO/NC or cause and effects interface programming,
self confirmation output the alarm controller sends out a start
3. LED status indicator command to the equipment required to
4. Electronically addressable start. After receiving the command, the
5. Characteristics one input or output module activates its relay to change state.
6. First fix base for easy and safe Once the equipment under control has
installation. operated a confirmation signal can be sent
Description back to the fire alarm controller. The I-
9303 has two addresses, which can receive
Intelligent addressable input/output module. A the two different action orders from the
single/double volt free relay with N/O and N/C controller and has two different control
change over contacts that can be driven via outputs and can affirm two different input
the fire alarm loop. Commonly used for answering signals. Electronic addressing
overriding equipment such as AHU’s, Smoke can be done through Handheld
extracts, Lift returns, auto dialer, BMS, etc. Programming tool (P-9910), purchased
separately.
Specification
Action
Intelligent I/O Monitor Unit
ELECTRICAL
BACK BOX 1 2 3 4 5 6 7 8
MOUNTING
BASE
16 15 14 13 12 11 10 9
V+ G COM1 NO1 NC1 COM2 NO2 NC2 Part No Description Weight Pack
/Kg Qty
per
Box
I-9303
Intelligent
Single
I-9301 .198 120
D1 D2 G I1 I2 Z1 Z2 Input/Output
Module
Intelligent
Double
I-9303 .210 120
Input/Output
V+ G COM1 NO1 NC1 Module
I-9301
D1 D2 G I1 Z1 Z2
Technical Specifications
• Protection rating: IP 30
• Output Contact: 24Vdc/5A
• Output Contact Mode: Normally
Open or Closed
• Operating voltage: 24Vdc Loop
voltage
• Power Supply: 24Vdc
• Operating Current:
Loop Monitoring current 1mA
Loop Action Current: 4mA
• Operating temperature: -10°C to
+50°C
• Relative humidity: 95%
• Application: Indoor use
• Visual Indicator: twin LED, Red ( lit
steady when alarm, 3 sec interval
Features and Benefits blinking at normal state) Yellow
(fault)
• Programming mode: Electronic
programming within 1~242,
1. Zonal switch for voice alarm line
2. Multi contact output energized occupying one address
simultaneously. • Material and colour: ABS, ivory-
3. Microprocessor to monitor the cable white
4. Photoelectric isolation for the loop • Wiring: 3 pair non polarized
and power supply. • Dimensions: 120mmx80mmx39mm
5. Electronically addressed
6. Twin LED status indicator Mounting Module Base
ELECTRICAL
Electronic addressing can be done through BACK BOX
Handhold Programming tool (P-9910),
purchased separately.
Action
Addressable Input Module
MOUNTING
BASE
Connect the wires to the required terminal The address of voice alarm module can be
according to the wiring diagram. The cable programmed using GST handheld
must be fire rated type and the size depends programmer (P-9910), connect the two
on the wiring distance and application. wires of the handheld programmer to Z1
Minimum size gauge 1.0mm²(18 AWG) and Z2 terminals of the module.
Mounting Mounting
SP1 XF1 ZC1 SP2 XF2 ZC2
Hole Hole
8 7 2 1 Mounting Direction
1 2 3 4 5 6 7 8
9 10 15 16
D1 D2 G I1 Z1 Z2
16 15 14 13 12 11 10 9
Ordering Information:
Background Music
Technical Specifications
• Protection rating: IP 30
• Output Capacity: 500mA
• Control Mode: Pulse
• Operating voltage: 24Vdc Loop
voltage
• Power Supply: 24Vdc
• Operating Current:
• Loop Monitoring current 1mA
• Loop Action Current: 4m
• Power Monitoring current: 10mA
Power Action Current:
500mA
• Operating temperature: -10°C to
Features and Benefits +50°C
• Relative humidity: 95%
• End of Line: 4.7KΩ 1/4watt
1. Interface with conventional polarized • Application: Indoor use
sounder and bell • Visual Indicator: twin LED, Red ( lit
2. Microprocessor to monitor the cable steady when alarm, 3 sec interval
3. Photoelectric isolation for the loop blinking at normal state) Yellow
and power supply. (fault)
4. Electronically addressed • Programming mode: Electronic
5. Utilized two addresses ( Alert and programming within 1~242,
Evacuate) occupying two addresses
6. East installation and connection. • Material and colour: ABS, ivory-
7. Twin LED status indicator white
• Wiring: 2 pair non polarized
• Dimensions: 120mmx80mmx39mm
Description
ELECTRICAL
priority. BACK BOX
MOUNTING
Electronic addressing can be done through BASE
Handhold Programming tool (P-9910),
purchased separately.
FIELD DEVICE
PROGRAMMER
4.7 Kohms
RESISTOR
O+ O−
D1 D2 I1 Z1 Z2
24VDC SUPPLY
LOOP IN LOOP OUT
Compatible with all GST Intelligent Fire
NON−P0LARIZED Alarm Panels GST 200, GST 5000, GST
9000.
Programming
Ordering Information:
The address of Sounder circuit module can be Part No Description Weight Pack
/Kg Qty
programmed using GST handheld
per
programmer (P-9910), connect the two wires Box
of the handheld programmer to Z1 and Z2 I-9308 Intelligent .191 120
terminals of the module. Program the 1st Sounder Driver
address, the module will automatically take Module
the next address also. See Manual for more
information
• Protection rating: IP 32
• Operating voltage: 24Vdc Loop
voltage
• Power Supply: 24Vdc
• Operating Current:
Monitoring current 0.5mA
Action Current: 5mA
• Operating temperature: -10°C to
+50°C
• Relative humidity: 95%
• Capability: 15 conventional detector
( AEOL); 25 detectors (EOLR)
• End of Line: 4.7KΩ or AEOL
• Application: Indoor use
Features and Benefits • Visual Indicator: LED, steady red
when in alarm state, 3 sec interval
1. Interface with conventional fire blinking at normal state; Yellow
devices/non-addressable unit (fault)
2. Secure and speedy communication • Material and colour: ABS, off-white
3. Monitored cable • Wiring: 2 pair non polarized
4. Electronically addressed • Dimensions: 120mmx80mmx40mm
5. LED status indicator
6. Ideal for integrating Sprinkler Zone
Valve and Flow Switches
O+ O−
1 2 1 2 1 2
O+ O−
V+ v−
K1 K2
D1 D2 I1 Z1 Z2 4 3 4 3 4 3
C−9201 MANUAL CALL POINT C−9102 SMOKE DETECTOR C−9103 HEAT DETECTOR P−9907 ACTIVE
I−9319 ADDRESSABLE ZONE MONITOR UNIT END OF LINE
CONVENTIONAL ZONE
CONNECTION
FIELD DEVICE
PROGRAMMER
O+ O−
D1 D2 I1 Z1 Z2
Fig.1
Ordering Information:
Part No Description Weight Pack
Programming /Kg Qty
per
The address of the module can be Box
programmed using GST handhold I-9319 Addressable .180 120
programmer (P-9910), purchased separately. Zone Monitor
Connect the two wires of the handheld Unit
programmer to Z1 (14), Z2 (15) terminals of MANUFACTURED IN ACCORDANCE WITH
the module.fig1
Technical Specifications
100mm
90mm
43 21 Ordering Information:
XS3
Part No Description Weight/ Pack Qty
Kg per Box
Addressable
Multi Channel
200mm interface Module
DI-9309 .180 120
(Electrical box
Wiring and Connection excluded in the
1) Fig.2 shows the system connection with volt- package)
free normally open input.
4.7k¦ ¸
470¦ ¸
Volt free
contact
I(n) G
INPUT(n)
Fig. 2
D1 D2 Z1 Z2
D I-9 3 0 9
N C 1 (2 ) C O M 1 (2 ) N O 1 (2 )
Control Input
C o n tro lle d E q u ip m e n t
Description
C-9302 Interposing Relay Module is a non-addressable module, used together with I-9301
module to control the activating devices with higher current capacity and transforming control
of AC 220V devices in order to avoid mixing of DC and AC voltages to isolate the loop.
Specification
ELECTRICAL
BACK BOX
MOUNTING
BASE
C-9302 Wiring
• COM, NO, NC: Output signal, passive
normally open, normally closed contact. Selection of compatible intelligent
• O, G: Active DC24V control signal modules
input terminals.
Compatible with GST I-9301 Intelligent
Single I/O Module and I-9303 Intelligent
EQUIPMENT Dual I/O module
Ordering Information:
AC soure
Part No Description Weight Pack
220vac
/Kg Qty
per
Box
Interposing
C-9302 .198 120
Relay Modules
Double Action
C-9302A Interposing .210 120
relay
C−9504
WALL
Action
Short Circuit Isolator
ELECTRICAL
BACK BOX
Features and Benefits MOUNTING
BASE
Description
LOOP OUT
Technical Specifications
Detector Installation
• Protection rating: IP 30 Connect as per the marking on the base.
• Approval: LPCB
• Operating voltage: 24Vdc Selection of compatible Control Panels
• Operating Current: 270mA Compatible with all GST Intelligent Fire
• Operating temperature: -10°C to Alarm Panels GST 100, GST 200, GST 9000.
+50°C
• Relative humidity: 90%
Ordering Information:
• Application: Indoor use
Part No Description Weight Pack
• Output Capacity: 30Vdc / 5 mA
/Kg Qty
• Visual Indicator: RED LED ( lit steady per
when alarm, off normal state) Box
• Material and colour: ABS, off-white C-9503 Short Circuit 0.100 120
• Wiring: 1 pair non polarized Isolator
• Dimensions: 120mm x 80mm x
39mm Note: Specifications are subject to change without notice.
CEILING ELECTRICAL
BACK BOX
C−9504
DETECTOR
Features and Benefits
Description
OU
T£
-
loop will defect the problem and open circuit
«
T£
OU
Technical Specifications
• Operating voltage: 24Vdc non-
polarized
• Operating Current:
24Vdc: Standby current 10mA
Action current 160mA
Loop: Standby current 0.8mA
Action current 6mA
• Operating temperature: -10°C to
+50°C
• Flashing Frequency: 20x180per min.
• Alarm Volume (SPL): 90dB @
1metre
• Relative humidity: 95%
• Application: Indoor use
• Material and colour: ABS,ivorywhite,
red plexiglass
• Wiring: 2 pairs ; 1 pair 24vdc
supply and 1 pair for loop
• Dimensions: 144x90x57mm
24VDC LOOP
FIELD DEVICE
PROGRAMMER
D1 D2 Z1 Z2
Ordering Information:
Technical Specifications
• Operating voltage: 24Vdc non-
polarized
• Operating Current:
• Standby current 1mA
• Action current 7mA
• Operating temperature: -10°C to
+50°C
• Loop capacity: 30 pcs. p/loop
• Relative humidity: 95%
• Sound Output: 85dB @ 1metre
• Application: Indoor use
• Material and colour: ABS,ivorywhite
• Wiring: 1 pair polarized
• Dimensions: diameter 10cm;
height : 3.5cm (w/o cover), 4.5cm
(w/ cover)
Ordering Information:
LOOP IN LOOP OUT
Part No Description Weight Pack
/Kg Qty
per
Box
1 2
I-9402 Addressable .120 100
Sounder Base
4 3
Programming
Z1 AND Z2
TERMINAL
1 2
4 3
FIELD DEVICE
PROGRAMMER
Description
Specification
Part Number I-9403 I-9404
Protection rating IP 33
Approval LPCB,CE CE
Standard EN54-part 3
Sound level output Alert Sound: 75dB; Evacuate sound: 85dB ( at 3 meter)
Main Sound Frequency 2.8Khz
Strobe 6 highlight LED’ No feature
Operating voltage Loop 24vdc ; Power Supply 24Vdc(16~28Vdc)
Loop: standby 1mA/ alarm 5mA ; Loop: standby 1mA/ alarm 5mA ; Supply
Operating current Supply current: standby 3mA / alarm current: standby 3mA / alarm 35mA
65mA
Operating Temperature -10°C to 50°C @ 95% relative humidity
Addressing Mode Electronic programming with 1~242
Application Indoor and outdoor use
Materials and colour ABS / red; plexiglass / red
Dimension Ø 110mm x 97.5 mm
Wiring 4 wires: 2 wires for loop ( non-polarized) ; 2 wires for power cable( non-polarized)
WALL
ELECTRICAL
BACK BOX
Z1 AND Z2
TERMINAL
MOUNTING
BASE
Loop out
Description:
The panel displays the zone, time and address with graphical icon once fire and fault
occurs this is saved on a non-volatile memory, which can store up to 999 fire
messages and 500 for fault. By utilizing advanced GST Protocol, the system is
compatible with the complete range of GST intelligent detectors, sounders, interface
module and MCP, and optional RS485 protocol for connecting repeater or networking
to other GST intelligent panels.
Technical Specification
Notes:
The GST 100 does not provide control for GST intelligent loop driven devices.
Ordering Information:
Description:
Technical Specification
Standard EN54 Part 2/4 ; BS5839 Part 4
Approvals LPCB,TRL Compliance, EEC, CE
Main Input Voltage 220 ± 10% VAC 50/60 Hz
Input Current Rating 0.75A
System Operating Voltage 24 VDC Nominal (17-29 VDC)
Zone Capacity 30 Zones programmable
Loop length 1.2 Km using 1.5mmsq cable
Standby Batteries Twin 12 Vdc Bat;12AH, 24 hours
Sounder Circuits (3) Output voltage 17 to 29 VDC
Output current: 500mA per output
Maximum total load 1.5A
EOL 10K resistor
Fuses Mains 1A (20mm A/S ceramic)
Sounders (2): 1A (20mm A/S)
Fire alarm Output 0.5A (20mm A/S)
Battery: 2A (20mm A/S HRC ceramic)
(Fire alarm) Relay Output 0.5A at 24VDC
Common Fault Relay Output Volt-free changeover 1.0A at 24 VDC
24 VDC Fused Output Maximum load 500mA at 17-28VDC
Battery Charging Current Limit 600mA
Ordering Information:
Description:
Technical Specification
Standard EN54 Part 2/4 ; BS5839 Part 4
Loop Capacity GST5000/2:480 addresses
GST5000/4:960 addresses
Loop Length 1.2Km using 1.5 mmsq.
Main Input Voltage 220 ± 10% VAC 50/60 Hz
Input Current Rating 1.5A
System Operating Voltage 24 VDC Nominal (17-29 VDC)
Standby Batteries 2 x 12AH, 24 hours
Sounder-Alarm Circuits (3) Settable dry contact or 24Vdc Output
Output voltage 17 to 29 VDC
Output current: 1.0A
Maximum total load 1.5A
AOL 10K resistor
Fuses Mains 1A (20mm A/S ceramic)
Sounders (2): 1A (20mm A/S)
Fire alarm Output 0.5A (20mm A/S)
Battery: 2A (20mm A/S HRC ceramic)
(Fire alarm) Relay Output 0.5A at 24VDC
Common Fault Relay Output Volt-free changeover 1.0A at 24 VDC
24 VDC Fused Output Maximum load 500mA at 17-28VDC
Battery Charging Current Limit 600mA
Dimension 500mm x 700mm x 170 mm
Selection of GST5000/2/4 compatible addressable devices and Panels
9 GST200/2 Single or Twin Loops Intelligent Fire Alarm Controller
9 GST5000/8 4 to 8 Loops Intelligent Fire Alarm Controller
9 GST5000R/C 1-20 Loops Intelligent Fire Alarm Controller
9 GST852RP LCD Passive Repeater Panel
9 GST852RPX LCD Active Repeater Panel
9 DI-9102 Innovation Intelligent Optical
9 DI-9103 Innovation Intelligent Combined Rate of Rise and Fixed Temperature.
9 I-9101 Intelligent Multi detector
9 I-9102 Intelligent Optical Detector
9 I-9103 Intelligent Dual Heat Detector
9 I-9104 Intelligent UV Flame Detector
9 I-9105R Intelligent Beam Detector
9 I-9201 Addressable Manual Call points
9 I-9300 Addressable Series interfaces (Complete range for all requirements)
9 I-9400 Addressable Series Sounders and strobes
9 I-9600 Intelligent Series Combustible gas detectors
Ordering Information:
Part No Description Weight/Kg Pack Qty per
Box
GST5000/2 Intelligent Two Loop Fire Alarm Panel 23.690 1
GST5000/4 Intelligent Four Loop Fire Alarm Panel 23.720 1
MANUFACTURED IN ACCORDANCE WITH
Description
Technical Specification
Ordering Information:
Part No Description Weight/Kg Pack Qty per
Box
GST5000/8 Intelligent Modular 8 Loops Fire Alarm Control 35 1
Panel
Main Supply and Battery 13 1
MANUFACTURED IN ACCORDANCE WITH
Technical Specification
• Standard EN54 Part 2/4 ; BS5839 Part 4
• Loop Capacity GST5000/2:480 devices
GST5000/4:960 devices
• Main Input Voltage 220 ± 10% VAC 50/60 Hz
• Input Current Rating 3A
• System Operating Voltage 24 VDC Nominal (17-29 VDC)
• Standby Batteries
Twin 12volt Battery (panel) 40Ah, 24hours
Twin 12volt Battery (PSU) Ampere-Hour according to the load application
• Sounder Circuits (2) Output voltage 17 to 29 VDC
• Output current: 1.0A
• Maximum total load 1.5A
• EOL 10K resistor
• Fuses Mains 1A (20mm A/S ceramic)
• Sounders (2): 1A (20mm A/S)
• Fire alarm Output 0.5A (20mm A/S)
• Battery: 2A (20mm A/S HRC ceramic)
• (Fire alarm) Relay Output 0.5A at 24VDC
• Common Fault Relay Output Volt-free changeover 1.0A at 24 VDC
• 24 VDC Fused Output Maximum load 500mA at 17-28VDC
• Battery Charging Current Limit 600mA
• Dimension 580mm x 520mm x 1873mm ( Rack type)
1080mm x 1113mm x 1350 mm (2bay console)
Selection of GST5000R/C compatible addressable devices and Panels
9 GST200/2 Single or Twin Loops Intelligent Fire Alarm Controller
9 GST5000/2/4 2 to 4 Loops Intelligent Fire Alarm Controller
9 GST5000/8 5 to 8 Loops Intelligent Fire Alarm Controller
9 GST852RP LCD Passive Repeater Panel
9 GST852RPX LCD Active Repeater Panel
9 DI-9102 Innovation Intelligent Optical
9 DI-9103 Innovation Intelligent Combined Rate of Rise and Fixed Temperature.
9 I-9101 Intelligent Multi detector
9 I-9102 Intelligent Optical Detector
9 I-9103 Intelligent Dual Heat Detector
9 I-9104 Intelligent UV Flame Detector
9 I-9105R Intelligent Beam Detector
9 I-9200 Addressable Series Manual Call points
9 I-9300 Addressable Series interfaces (Complete range for all requirements)
9 I-9400 Addressable Series Sounders and strobes
9 I-9600 Intelligent Series Combustible gas detectors
Ordering Information:
Part No Description Weight/Kg Pack Qty per
Box
GST5000R Intelligent Modular 1-20 Loop Fire Alarm 75.00 1
Control Panel ( Rack type)
GST5000C Intelligent Modular 1-20 Loop Fire Alarm 105.00 1
Control Panel (2bay Console type)
MANUFACTURED IN ACCORDANCE WITH
Technical Specifications
1. Active repeater
2. Silence and reset the panel
3. Back Lit LCD displays
4. Connected to network RS 485
5. Compact size and easy to install
Description
GST852RPX Active LCD Repeater Panel is
design to control and reset the alarm
remotely and display detectors healthy, fire
and fault. This repeater panel can display the
location numbers and information of the
detectors and sends out audible and optical
signals. Through RS our 485 communication
network the repeater can be connected to all
GST Intelligent fire alarm controllers.
Compact size and easy to install. The
repeater can be used whenever there is a
need to relay information to multipoint
informing key personnel.
Selection of compatible Control Panels
Compatible with all GST Intelligent fire alarm
panel.
Ordering Information:
Specifications
Part No Description Weigh Pack
• Operating voltage: 24Vdc
t/Kg Qty per
• Power Consumption:
Box
Standby power: 2W
GST852RX LCD Repeater 1.60 1
Maximum: 2mA
Panel
• Display: 4x80 characters
• Operating temperature: -10°C to
+50°C
• Relative humidity: 95%
• Application: Indoor use
• Material and colour: ABS, Off-white
• Wiring: 2 pair polarized: 1 pair supply
and 1 pair data signal
• Dimensions: 230 x 210 x 50 mm
Description:
Specification
• Display Range: 1 up to 100 group code points. The code supports the mode of wildcard
character.
• Display Capacity: There is no more than 100 pieces of fire information displayed by the
repeater panel.
• Wiring: Connected with fire alarm controller with two polarized wires; connected with
power supply with two 24VDC power lines, non-polarized.
• Operating Current:
• Monitoring Current ≤25mA
• Alarming Current ≤100mA
• Environment Temperature: 0ºC+40ºC
• Relative Humidity: ≤95%, non condensing
• Power: Centralized power supply by 18VDC-28VDC, static state power consumption
≤0.7W, maximal power consumption ≤3W
• Dimension: 380mm×480mm×70mm
• Installation Hole Distance: 260mm
Ordering Information:
Technical Specification
Selection of compatible
Feature Compatible with all GST Intelligent devices
• Portable programming tool for
addressing and testing of intelligent Ordering Information:
devices
• Digital programming Part No Description Pack Qty
• Programs all loop devices (1-242 per Box
addresses per loop) P-9910 Handheld Programmer 1
• Non-polarized 2 wire intelligent
programmer
• Interrogates devices for conditions
• Reprogram facility enables
adjustment to alarm sensitivity of
detectors
• Adjust inputs modules to accept N/C
or N/O contacts
• Low power consumption with sleep
and auto off mode.
• Battery low indication
• Display type: Four-bit LCD
• Easy operation Hand held engineering
tool.
Description
MANUFACTURED IN ACCORDANCE WITH
• Operating 24VDC
Voltage
• Loop Input ≤1000m
Distance
• Loop Output ≤1000m
Distance
• Power Voltage 24VDC (18VDC 27VDC)
• Operating ≤50mA
Current in
Empty Load
• Operating ≤200mA
Current in Full
Load
• Load Ability Connecting with 1-150 loop
and devices, compatible with all
Compatibility the loop devices.
• Isolation Isolation voltage between loop
Voltage input and loop output is not
less than 1500V.
• LED Red LED lights when FACP
sends signals.
• Operating Temperature: -10 +50
Environment Relative Humidity: ≤95%, non
Feature condensing.
• Dimension 85mm×128mm×56mm
• Material and Q235A, grayish white
Color of
• Digital communication with fire Enclosure
alarm control panel ensures
immunity to electromagnetic Wiring and Connection
interference and reliable operation. Refer to installation detectors manual.
• Optoisolated output signal,
resistant to industrial frequency 85mm
50mm 56mm
interference.
P-9903
Loop Relay Module
Description
128mm
116mm
M4 Screw
Z1o Z2o
P-9903
and prolongs the loop distance. +24V Loop Device Loop Device
Description
The GST Loop Splitter is used for additional
loop interface for the control panel without
affecting the loop configuration.
Terminals
z Input Side (XT1, XT3 & XT4)
XT1 (Zin+ & Zin-): Loop from
loop card
XT3 (24+ & 24-): 24VDC in
XT4 (24+ & 24-): 24VDC out
z Output Side (XT2)
ZO+ & ZO-: Ordering Information:
Part No Description Weight Pack
Loop Out
/Kg Qty
ZI+ & ZI-: per
Loop In Box
P-9902 Loop Splitter .003 N/a
System Connection
The system should be connected as below.
Loop Splitter
Sub-Loop 1
24VDC
Splitter Sub-Loop 2
Splitter Sub-Loop 3
Note
z The splitters are programmed by P-
9910B handhold programmer, taking
individual addresses on the loop.
Special program should be applied on the
panel.
Feature
Description
The new developed GSTGMC2.0 Graphic
Monitor Centre is the new developed software.
With friendly interface, the software may
support 8 client stations plus local monitor
station, making complete monitoring and
control. Also with Open Protocol
Communication (OPC), the communication
with panel can also be integrated into other
systems. The related panel types include Selection of compatible Control Panels
GST200, GST500 & GST5000. The main Compatible with all GST Intelligent fire alarm
features of this highly intelligent package are: panel.
The self-reacting communication module
automatically maintains data communication Ordering Information:
with panel. The operator can test the
communication at any time to ensure the Part No Description Pack Qty
reliable running of system per Box
The communication server connects to panel GSTGMC Graphic Monitor CD
directly. The monitor stations can be set Centre
locally or through LAN or even through WAN. P-9931 RS 232 1
Multi-level password control Communication Board
Simple, direct and complete user graphics
view interface, switching between device
layouts of different monitoring zones.
Pop out layout of abnormal information
automatically. Flash the abnormal device(s)
in different colours for alarm, plant, fault and
isolation.
Complete functions of database management
and data copy ensure system safety by
minimizing possibility of data loss.
System Requirement
Hardware
CPU: Pentium III 600 or Higher
Minimum free Hard disk:2GB MANUFACTURED IN ACCORDANCE WITH
Memory:128MB
Software
Windows 98SE, Windows 2000 or Windows
XP Professional
Note: Specifications are subject to change without notice.
Description
The GSTOPC Fire Alarm OPC Server is the
new developed software communication with
panel can be integrated into other systems
and Building Management System. The
related panel types include GST200 and
GST5000 series. The main features of this
highly intelligent package are:
The self-reacting communication module
automatically maintains data communication
with panel. The operator can test the
communication at any time to ensure the
reliable running of system through GSTGMC
2.0 Server. Selection of compatible Control Panels
Ensure easy and uniform integration of Compatible with all GST Intelligent fire alarm
subsystem from different manufacturer and panel.
open Building Management System.
The communication server connects to panel Ordering Information:
directly. The monitor stations can be set
locally or through LAN Part No Description Pack Qty
Multi-level password control per Box
Display of information automatically for GSTOPC Fire Alarm OPC Server CD
modules, sounders and sensor GSTGMC Graphic Monitor CD
GSTOPC code tag 0-ok, 1-isolate, 2-alarm, 3- Centre Server
Action,4-fault, 5-start, 6-stop, 7-release, 8- P-9931 RS 232 1
restore, 9-mute, 11-reset, others-panel Communication Board
disconnect.
Complete functions of database management
and data copy ensure system safety by MANUFACTURED IN ACCORDANCE WITH
Ordering Information:
Ordering Information:
Description
D081A Intelligent fire alarm board for PSTN up to 4 telephone line input.
Specifications
Ordering Information:
• Interface type: Relay
Part No Description Weight Pack
• Port Resistance: 600Ω
/Kg Qty per
• Frequency Range: 300~3.4Khz
Box
• Compatible PC: PCI slot of Pentium 1
D081A Intelligent 1.20 1
or above
Alarm Card
• Cache on board: 64Kb, 16Kb for
voice
• Digital Voice: ADPCM
• Baud Rate: 64kbps, 32 kbps
• Sampling Rate: 8K
• Volume Control: -20dB to +50db
• Signaling: DTMF
• Dialing Monitor: Dialing tone/Reverse
Polarity
• Modulation type 1: 1.2Khz±1%
MANUFACTURED IN ACCORDANCE WITH
Description
The GST2000 Fire Alarm Transmitting
Equipment (FATE) can receive and monitor
fire alarm information from GST Fire
controllers and then report to the Central
office where GST-911Net fire alarm
monitoring and management system is
installed utilizing different transmission
protocol such as LAN/WAN/TCP/IP. The
system is compatible with the complete
range of GST intelligent panel. The FATE
enables total monitoring like serial port
disconnection and controller failure.
Support alarm sound and voice recording
including manual/automatic answer on duty
host computer. Easy to programme and
install.
Technical Specification
Ordering Information:
Specification
Part Number PSU24-3A PSU24-3
Output capacity Rating: 24Vdc/ 3A
Operating Temperature -10°C to 40°C @ 95% relative humidity
Power Supply Primary:220Vac ±15%; Standby:2x12Vdc/7A sealed lead acid
Electronic programming with 1~242,
Addressing Mode No Feature
occupying 1 address
Application Indoor use
Colour Ivory white
Dimension 310mm x 400mm x 115mm
Specification
Part Number PSU24-6A PSU24-6
Output capacity Rating: 24Vdc/ 6A ; Max: 24Vdc/ 8A
Operating Temperature -10°C to 40°C @ 95% relative humidity
Power Supply Primary:220Vac ±15%; Standby:24/24Ah (maximum capacity) sealed lead acid
Electronic programming with 1~242,
Addressing Mode No Feature
occupying 1 address
Application Indoor use
Colour Ivory white
Dimension 500mm x 170mm x 440mm
MANUFACTURED IN ACCORDANCE WITH
Technical Specification
Technical Specification
Mounting
Installation Hole
Installation Hole
Wiring Diagram
4.7K¦ ¸
Control Panels
L3 L3 L4 L3 L4
GST 306 6 Zone 7.3 1
Addressable Gas
Extinguishing
DC1+ DC1+ J11
Solenoid of Cylinder
DC1- DC1- J12
Control Panels
C- 9329
YK1 YK1 K11
Pressure Switch
Extinguishing Control Panel
COM
Driving device Solenoid of Cylinder
NO controlled by a
contact
R R1 R2 R1 R2
C- 9318 C- 9318 4. 7K¦ ¸
GND G1 G2 G1 G2
K1
K2
G S G S G S
+24V
Zone 1
1. Normally installed above the entrance Connect the wires to the required terminal
to a gas extinguishing control area. according to the diagram. The cable must
2. Will eliminate and activate internal be fire rated type and the size depends on
sounder prior to gas release. the distance and application. Minimum size
3. "Gas Extinguishing DO NOT ENTER" is gauge 1.0mm²(18 AWG). See installation
printed on the panel of the indicator. and operation for more information.
4. Highlight LED
5. Compatible with GST series of gas
extinguishing control panel
1 PAIR FIRE CABLE
Description
Gas Gas
G2 R2
G1 R1
G2 R2
XT1 XT1
DC-9103 has rate of rise and fixed temperature Using active end of line can connect up to 15
mode. The rate-of-rise feature detects intense detectors and base with diode.
fires by quickly responding to rapid
temperature increases. The fixed temperature
feature reacts to fires when a specific
temperature is reached.
Selection of compatible Control Panels Using 4.7KΩ end of line resistor can connect
Compatible with all GST Conventional panel up to 25 detectors
and GST Intelligent Fire Alarm Panels using
Zone monitor module: Ordering Information:
Part No Description Weigh Pack
t/Kg Qty per
Box
DC-9103 Innovative 0.110 120
Conventional
Dual Heat
Detector
DB-01 Detector Base 0.049 360
DB-01D Base with Diode 0.049 360
Note: Specifications are subject to change without notice.
LED INDICATOR
PANEL
1 2 1 2 1 2
ZONE
processing area like computer room and MONITOR
MODULE
telephone exchange.
4 3 4 3 4 3
P−9907 ACTIVE
END OF LINE
Technical Specifications C−9102 SMOKE DETECTOR C−9101 SMOKE/HEAT DETECTOR
LED INDICATOR
PANEL
The conventional type can be used directly 1 2 1 2 1 2
−
OR
Technical Specifications
C−9102 SMOKE DETECTOR C−9101 SMOKE/HEAT DETECTOR
•
•
Approval: LPCB,UL,CE
Protection rating: IP 32
− +
• Detecting Range:80m² at 6-12meter
ceiling height; and 60m² below 1 2
6meter
TO NEXT DEVICE
• FROM CONTROL PANEL
1 PAIR FIRE CABLE
HOLE
1 PAIR FIRE CABLE
• Operating Current:
Stanby: 0.1mA; Alarm:8mA
• Operating temperature: -10°C to Ordering Information:
+50°C Part Description Weight Pack Qty
• Relative humidity: 95% No /Kg per Box
• Application: Indoor use C-9102 Conventional Optical 0.12 120
• Material and colour: ABS, off-white Smoke Detector
• Wiring: 1 pair polarized DZ-03 Detector Base -EOLR 0.05 360
DZ-03D Base with Diode AOL 0.05 360
• Dimensions: diameter 10cm; height
5cm
MANUFACTURED IN ACCORDANCE WITH
PANEL
1 2 1 2 1 2
ZONE
Technical Specifications
C−9103 HEAT DETECTOR C−9103 HEAT DETECTOR
•
•
Standard: EN54-part5,part6
Approval: LPCB,CE − +
• Protection rating: IP 32
• Detecting Range: 30 sqm for normal 1 2
24Vdc) polarized
• Operating Current: HOLE 4 3
Detector Installation
The combination of fire detection should be
installed complied with all local codes and /
or NFPA 72 National Fire Alarm Code, NFPA
70 National Electrical Code. Verify the
proper wiring and base is firmly mounted to
prevent detector damage before the
installation. Point the detector in the base
by the mark-line and secure the detector in
Features: that position by rotates it clockwise until it
reaches the next mark line.
1. Not sensitive by sunlight
2. Dust /corrosion/humidity resistance CONCRETE PAD OR
HOLDING PAD
EMBEDDED BOX
PANEL
1 2 1 2 1 2
ZONE
MONITOR
dust, oil, tolerance of fume, and humidity. C−9102 SMOKE DETECTOR C−9101 SMOKE/HEAT DETECTOR
Ordering Information:
Technical Specifications Part No Description Weight Pack
• Protection rating: IP 32 /Kg Qty per
Box
• Operating voltage: 24Vdc
C-9104 Conventional 0.123 120
• Operating Current: Ultraviolet Flame
Standby current 1.5mA Detector
Alarm Current 10mA DZ-03 Detector Base -EOLR 0.05 360
• Operating temp:-10°C to +50°C DZ-03D Base with Diode AOL 0.05 360
• Relative humidity: 95%
• Application: Indoor use
MANUFACTURED IN ACCORDANCE WITH
Technical Specifications
• Standards: BS EN54 Part-12
• Protection Rating: IP20*
(IP 66 thru glue seal)
• Operating Voltage
Power Voltage: 24Vdc (±10%)
Loop Voltage: 24Vdc
• Operating Current
Features and Benefits Standby current: 12mA
Alarm current: 22mA
1. Wide monitoring area, range 8-100 • Length of Optical Pathway:
metres o 8-100meter
2. Combination of the emitting and • Monitoring width: 14m
receiving parts makes mounting easy • Monitoring Area: 1400m²
and optical pathway accurate • Commissioning Tools: Magnet
3. Simple and cost effective to install • Operating Temperature:
transmitter and reflective ‘honey -10°C to +50°C
comb’ mirror. • Relative humidity: 95%
4. Quick and easy to set up visual • Application: Indoor use
strength indication. • Material and Colour: ABS, Gray
5. Build-in microprocessor • Wiring: 1 pair -24Vdc, 1pair- loop
6. Self-diagnosis function can monitor • Dimensions:206mmX95mmX95mm
the inner fault.
7. Automatic compensation for factors
weakening received signals, such as
dust contamination, positional
excursion and ageing transmitter.
8. SMT processing technology Indication of Detector State:
9. Attractive and decent appearance
Commission: Green LED and Yellow LED
are lit or flash in a certain way.
Description
Normal monitoring state: Red LED
C-9105R Conventional Reflective Beam flashes periodically (with loop connected)
Detector is an addressable reflective infrared Fire: Red LED constantly illuminates, and
beam smoke detector that can be directly Yellow LED turns off. The fire signal has
connected to a fire alarm controller, by to be cleared by the controller
transmitting status information via bus Fault: Yellow LED constantly illuminates.
between the detector and controller. The
detector must be used together with a
reflector. The number of reflector(s) to be
used (one or four) depends on the distance
from the detector.
FIRE ALARM
OUTPUT
CONTACT
(TO FACP) TO POWER SUPPLY
24VDC
Ordering Information:
Part No Description Weight Pack
/Kg Qty
per
Box
C-9105R Conventional 1.3 10
Reflector Beam
Detector
Smoke
Exhauster
¡Ý cm
Gas 1. 5m<L<4m
Stove
Floor
Selection of compatible Control Panels
Ordering Information:
Part No Description Weight/Kg Pack Qty per Box
C-9602LW-NG Conventional Gas Detector Natural Gas .250 100
C-9602LW-LPG Conventional Gas Detector LPG Low Pressure .254 100
Gas
C-9602LW-CG Conventional Gas Detector Coal Gas .252 100
anti-light disturbance.
The detector is non-addressable and can start
operation by applying DC power. It has a
LED INDICATOR
0.21dB/m
• Output Control Mode: Passive
normally open, closes and self-locks
after alarming, and contact rated
Note: Specifications are subject to change without notice.
capacitance (1A, 30VDC)
• Indicator: Red, not lit in normal
operation, and constantly lit when
alarming.
Technical Specifications
• Power Supply: PP3 (H6F22) DC9V
battery
• Indicator: Red flashes in every 50
seconds in normal condition.
• Output Interface: Available for
optional use
• Network Output: Maximum 30
alarm in one system, available for
optional use.
• Photoelectric Output: 5mA /30VDC,
Optional
• Sound level : 80dB
Features and Benefits • Detection Area: 40m2
• Operating Environment:
1. Self contain Optical Smoke detector • Temperature: -10 ~ +50
and alarm sounder • Relative Humidity: 95%
2. With test and reset button • Dimension: 140 x 54mm(D x H,
3. 9v operated with base)
4. Low battery indication • Material and Color: ABS white
5. Battery removable will inhabit cover • Weight: 235g
from closing ( as per UL standard) • Mounting Hole Distance:
6. Easy installation 50mm~108mm
7. LED indicator for 360º vision
8. Connection port to link up to 30
detectors in a single network Detector Installation and Wiring
9. Output to interface with other
security equipment The Smoke Alarm should be installed in
compliance with all local codes having a
jurisdiction in your area or NFPA 72
Description National Fire Alarm Code, NFPA 70 National
S-9102 Smoke Alarm is designed for Electrical Code, BS 5389 and EN54. For
domestic usage such as a house, villa and information about installation refers to
apartment, etc. Built with high-quality manual.
components and advanced technology, the
alarm has an excellently stable performance
and low power consumption. A 9V battery Ordering Information:
will operate up to one year. It can be easily
installed, no commission required. Part No Description Weight Pack
/Kg Qty
Utilize internal buzzer to provide a loud local per
Box
alarm. By using the output terminal, the
S-9102 Smoke Alarm 0.300 30
alarm can be linked to other alarms in a
common alarm network (up to 30 alarms) or
can be interfaced to other systems.
MANUFACTURED IN ACCORDANCE WITH
Technical Specifications
• Standard: EN54-part 11
• Approval: CE
• Protection rating: IP 40
• Operating voltage: 24Vdc Loop
• Operating current:
Standby current 0.8mA
Alarm Current 2mA
• Operating temperature: -10°C to
+50°C
• N/O Output contact: 60Vdc, 0.1A
• Contact resistance: 100mΩ
• Relative humidity: 95%
• Application: Indoor use
Features and Benefits • Visual Indicator: LED, Red ( lit
1. Re-settable (non-breaking glass) steady when alarm, 3 sec interval
2. Additional volt free contact blinking at normal state)
3. Friendly installation and test • Material and colour: ABS, red
• Wiring: 1 pair polarized
Description • Dimensions: 90x122x48.5mm
Designed for the purpose of raising an alarm
manually once verification of a fire or Mounting Base
emergency condition exists, by pressing the The location of manual call point should be
non breakable glass. Meets the standard installed in compliance with all local codes
requirement of EN 54 part 11, European and / or NFPA 72 National Fire Alarm Code,
Standard and approved by Loss Prevention NFPA 70 National Electrical Code. Surface
Certificate Board (LCPB). mount and it is installed onto a standard
The C-9201 constructed of high impact red
ABS with a modern pleasing appearance. The I−9201
WALL
terminating back box enables first fix
installation and termination leaving the fascia FIRE
ELECTRICAL
with integral electronics to be simply plugged BACK BOX
PANEL
1 2
Note: Specifications are subject to change without notice.
K1 K2
−
OR
ZONE
MONITOR
TO NEXT DETECTOR
MODULE
I+ I− O− 0+
4 3 OR
AEOL
PANEL
1 2
−
OR
ZONE
operational mode.
C−9202 MANUAL CALL POINT DETECTOR
installation.
Mounting Hole Mounting Hole
Description
The conventional sounder beacon is suitable
for warehouse, security post, schools and
industrial area. The I-9401 is designed to S1 G
DETECTOR
DETECTOR COMMON
Features and Benefits BASE
SOUNDER WITH
COVER
1. High sound level Wiring and Connection
2. Low power consumption Connect the wires to the required terminal
3. Can be used as a detector base according to the wiring diagram. The 5,6 is
4. Wall or ceiling mounting. Easy for 24VDC power supply, note the polarity 5
installation and connection. is positive and 6 is negative. The cable
must be fire rated type and the size
Description depends on the wiring distance. Minimum
In Fire and Security system the sounder is size gauge 1.0mm²(18 AWG).
the most effective device for alerting POWER SUPPLY/SOUNDER OUTPUT
personnel to evacuate the area. In the
POSITIVE WIRE NEGATIVE WIRE
buildings such as hotels where thick doors (5) (6)
and walls prevent external sound penetration,
the use of a combined detector base with
buit-in sounder present a cost effective 5 6
1 2
solution.
The GST C-9402 is a non-addressable
sounder base on which can mounted a
conventional detector to provide the dual
function of detection and alarm device or it
can be used as a single sounder. 4 3
Technical Specifications
• Operating voltage: 24Vdc (16Vdc to
28Vdc) polarized Selection of compatible Control Panels
• Operating Current: 15mA Compatible with all GST Conventional panel
• Operating temperature: -10°C to and GST Intelligent Fire Alarm Panels using
+50°C sounder output and Intelligent Sounder
• Relative humidity: 95% Driver Module
• Sound Output: 85dB @ 1metre
• Application: Indoor use Ordering Information:
• Material and colour: ABS, off-white Part No Description Weight Pack
• Wiring: 1 pair polarized /Kg Qty
• Dimensions: diameter 10cm; height : per
Box
3.5cm (w/o cover), 4.5cm (w/ cover)
C-9402 Conventional .120 100
Sounder Base
Note: Specifications are subject to change without notice.
Specification
MOUNTING
BASE
Power Supply
24Vdc
Sounder Installation
Sounder Installation
• Operating Voltage
DC24V±15% or AC220V 50Hz
• Stand-by batteries are configured on
order. The battery capacity can be
calculated according to the formula in
Clause 5.6 of this manual. The
maximum capacity is 4Ah (lasting for 24
hours in monitoring state).
• Output voltage: DC20V DC28V
• Static current: 2.4mA (connected with
15 conventional detectors)
• Resistance when alarming fire: 150Ω
1.5kΩ (normally 470Ω)
• Terminal resistor: 4.7kΩ or using active
end of line unit(.AEOL)
• Sounder: Output voltage DC20V to
DC28V, output current 1A, terminal
Features and Benefits resistor 4.7kΩ.
• Fault: Passive contact output, capacity
1. Microprocessor controlled SMT 1A DC24V
Electronics • Dimension:210mm×297mm×90mm
2. Compliant with EN54 part 2&4, &
BS5839, Part 4, 1988
3. Both end of line resistors and active
end of line can be used. Selection of compatible devices.
4. Programmable sounder circuits and
Compatible with all GST conventional detectors
outputs
and sounders.
5. Fully monitored sounder circuits
6. Key control evacuate over-ride
7. Class change terminals for remote Ordering Information:
control Part No Description Weight Pack
8. Up to 25 fire detectors and infinite /Kg Qty per
manuals call points zone capacity Box
GST101 1 Zone 2.45 1
Description Conventional
Fire Alarm
GST101 Conventional Fire Panel is a kind of Control Panel
multi-wire fire panel using single-chip
microprocessor. It can detect 1 zone. Each
zone can at most be connected with 15
conventional detectors. It has 2 output
control points through which it can control
some indicators, such as sounder strobes and
sounders, etc. The panel is designed with
stand-by batteries (two sealed acid storage
batteries) and reserved space for installation;
It has functions of operation indication, fault
indication, alarm indication and cable MANUFACTURED IN ACCORDANCE WITH
Technical Specification
Part Number GST 102 GST104
Operating voltage 220Vac ± 15% , 50hz
Standard BS5839, Part 4, 1988 and EN 54 parts 2 and 4
Approval CE, LPCB final stage
Operating Temperature -10°C to 40°C @ 95% relative humidity
Number of Zone Two zone Four Zone
Zone Capacity 15 detectors (AOL);25 detectors (EOLR)
Standby Batteries 5AH , 24hours monitoring state
Output Voltage 20Vdc to 28 Vdc
Static Loading Current 2.5mA ( when connected with 15 conventional detector
Fire Alarming Resistance 150Ω-1.5KΩ ( normal 470Ω)
End Of Line resistor 4.7KΩ or AEOL ( Active End Of Line)
No. of Sounder Output 2
Sounder Output Current 1 Ampere (500mA per output)
Sounder Output Voltage 20Vdc to 28 Vdc
Aux.Power Output 20Vdc to 28 Vdc
Application Indoor use
Materials and colour Coated Metal / Grey
Dimension 380mm x 320mm x 95mm
Fig.1
Fig.2
Fig.3
Fig.1 Using End of Line resistor, in compliance with
EN/BS standard, when using EOL resistor, call points
should be wired before detectors, so that the removal of
any detector will not inhibit call point from operating.
Description
remote control
11. Up to 15 fire detectors and
infinite manuals call points each
zone
Note: Specifications are subject to change without notice.
Technical Specification
Part Number GST 108 GST116
Operating voltage 220Vac ± 15% , 50hz
Standard BS5839, Part 4, 1988 and EN 54 parts 2 and 4
Approval CE, LPCB final stage
Operating Temperature -10°C to 40°C @ 95% relative humidity
Standby Baterries 7AH , 24hours monitoring state
Output Voltage 20Vdc to 28 Vdc
Static Loading Current 2.4mA ( when connected with 15 conventional detectors
Fire Alarming Resistance 150Ω-1.5KΩ ( nominal 470Ω)
End Of Line 4.7KΩ or AEOL ( Active End Of Line)
Sounder Output 4:Output voltage: 20Vdc ~28Vdc ; Output current: 1 A
Fire Alarm Output Output voltage: 20Vdc ~28Vdc ; Output current: 0.5 A
Fault Output Capacity Passive contact output :24vdc / 1 A
Aux.Power Output 20Vdc to 28 Vdc, 0.5A
Repeater Panel Outpt 10mA
Zone Capacity 8 zone 16 Zone
Application Indoor use
Materials and colour Coated metal/Grey
Dimension 380mm x 320mm x 95mm
Fig.1
Fig.2
Fig.3
G S T−R P 16 C O N V E N TIO N A L R E P E A TE R P A N E L
24V G N D F IR E1 FIR E 2 FIR E 3 F IR E4 FIR E 5 F IR E 6 F IR E7 F IR E8 FA U 1 F IR E9 F IR E10 FIR E 11 FIR E 12 F IR E13 FIR E 14 FIR E 15 F IR E16 FA U 2
AU X FAU LT O U TP U T
PW COM COM COM COM SU P PLY
E AR TH O N 0V D AY FIR E IS O FLT Z8 Z7 Z6 Z5 Z4 Z3 Z2 Z1 − + NO COM NC
L N
Technical Specifications
• Frequency Range: 300-3400Hz
• Ring Sound level: 70 db(A)
• Voice Distortion: less than 10%
• Jack Diameter: 6mm
• Operating Current: 17~31mA
• Operating temperature: 0C to
+40°C
• Relative humidity: 95%
• Application: Indoor use
• Material and colour: ABS, red
• Wiring: 1 pair polarized
Ordering Information:
Part No Description Weight Pack
Features and Benefits /Kg Qty
per
1. Easy to insert mobile handset Box
P-9911(M) Fire Telephone .250 10
2. Compatible with GST Fire Telephone
Mobile
Jack Handset
Technical Specifications
• Jack Diameter: 6mm
• Operating temperature: -10°C to
+50°C
• Relative humidity: 95%
• Application: Indoor use
• Material and colour: ABS,white, red
• Wiring: 1 pair polarized
• Dimensions: 850mm x 850mm x
120mm
manual.
Technical Specifications
• Frequency Range: 300 to 3400hz
• Ring sound: >70dBA
• Operating temperature: -10°C to
+40°C
• Relative humidity: 95%
• Application: Indoor use
• Material and colour: ABS,white, red
• Wiring: 1 pair polarized
• Dimensions: 234 x 146mm x 60mm
Description
The GST8101 provides a fully loaded user friendly Touch screen controlled PC
front end, providing a flexible management window to the entire system.
Enabling both Engineers to configure all aspects of the system, while system
managers can configure and control the day to day operation of the system. This
includes back ground music source selection, volume control routing to any
individual area, zone or group of zones,
Up to three Cybernet touch screen controllers can be utilized on any one system.
Technical Specification
Description
The GST8102 is the heart of the system providing direct communication and
programming of all VA modules. The Master Controller provides complete reporting and
fault diagnostics.
Technical Specification
Power Supply AC220V±10%/50/60 HZ
Power Consumption 30Watts
Keypad 1 Direction Key;9 Function Keys;2 Shortcut Keys
Display 192X64 LCD, English Menu;2 LED Fault Indicators
Communication Protocol RS-232, DB9, IN;RS422, RJ45, OUT
Baud Rate 4800bps
Case Material Black Stainless Steel
Back up Supply Battery 17AH/24VDC with battery box
Net Weight 12.5kg (without battery)
Description
The Emergency Interface provides a simple and reliable interface to any fire
alarm system. The GST8101S can perform the most complicated cause and
effect with care.
Technical Specification
Description
The Emergency Message Generator stores up to four non volatile messages of up to 50b
seconds in length. The message can be accessed independently and broadcast to any
combination of zones.
Technical Specification
Power Supply AC220V±10%/50/60 HZ
Power Consumption 30Watts
Display 6 LED, level Indicator
Communication Protocol RS422, RJ45, IN/OUT
Channel Insulation ›40dB
Volume Adjustment -∞ to 0 dB
S/N Ratio 95dB
Baud Rate 4800bps
Frequency Range 30-20Khz
Record Input Terminals 6.5mm jack;Mic: 600Ω/10mV; Line: 10kΩ/0.775V
Audio Output Terminals 2 channels, 6.5mm jack, 1kΩ/0-1.5V
Rack Space & Dimension 3U: 555 X 555 X 235mm
Case Material Black Stainless Steel
Back up Supply Battery 17AH/24VDC with battery box
Net Weight 12.5kg (without battery)
1. Single CD player
2. Micro-processor
controlled
3. Local control
4. Programmed flexibly
controlled by TW-010
5. Self-diagnostics
6. 220 AC / 24V DC operation
Description
The CD Players provides high quality sampling of CD’s in both standard format
and MP3 format. The CD is fully programmable and ultimately reliable
Technical Specification
1. Micro-processor controlled
2. Backlight LCD display
3. Local /remote channel selection
4. FM/AM 99 individuals presetting
5. Accurate frequency control
6. Self -diagnostics
Description
The Digital Tuner is ideal for background music , the tuner provides up to 99
pre-programmed radio stations for excellent music selection
Technical Specification
Description
The Node Terminals Addressable Amplifier range provides truly distributed voice evacuate plus
background music system. The amplifier is mounted in self contained enclosures combined with
power supply and battery space. Distribution of amplifiers provides excellent wiring saving
capabilities and enhanced local control is achieved via three direct audio inputs and volume control
with master override.
Technical Specification
1. Addressable amplifier
2. 6-channels input
3. 100V/70V output
4. Local 3 BGM channel selection and
32 level volume control
5. Maximum volume override in case of emergency
6. DC speaker line monitoring
7. Self diagnostics
8. 220 AC / 24V DC operation
Description
The Node Terminals Addressable Amplifier range provides intelligent addressable
distributed voice evacuate plus background music system. The amplifiers are
rack mounted with integral power supply and battery space. Option intelligent
soft start power supply to avoid inrush current use TW 090 is achieved via three
local audio inputs and volume control with master override
Technical Specification
Part Number GST8330R GST83120R GST3240R GST8350R
Dimension 484×450×132mm
Technical Specification
Model GST8401
Operation Voltage 70/100V
Rated Power 6W
Max. Power 9W
Sound Level (@6W/1W,
94dB/88dB(SPL)
1kHz,1M)
Frequency Range 80Hz to 18kHz
Transformer Tapping 1.5W, 3W, 6W
Opening Angle 150°
UL 1411 / IEC 268-5 / UL94 V0 /
Compatible Standard
EN60065
Case Material Fire Resistance ABS
Grid Material Steel
Color White (RAL 9010)
Weight 650g
Speaker Size 152.4mm
Total Dimension 198X91.44 mm
Operation Temperature -25°C to +55°C
M
Technical Specification
Model GST8411
Operation Voltage 100V
Rated Power 10W
Max. Power 15W
Sound Level (@6W/1W,
89dB±3dB(SPL)
1kHz,1M)
Frequency Range 120Hz to 15kHz
Case Material High quality plastic PVC
Grid Material Steel
Colour White (RAL 9010)
Weight 2.2 Kg
Total Dimension 215x170x150 mm
Operation Temperature -25°C to +50°C
Technical Specification
Model GST8421
Speaker Unit 5” woofer paper
Operation Voltage 70/100V
Rated Power 9W
Max. Power 9W
Sound Level (1W,,1M) 95dB±3 (SPL)
Frequency Range 110Hz to 13kHz
Transformer Tapping 3W, 6W, 9W
Terminals 4-core
Case Material Plastic
Grid Material Plastic
Color Silver-gray
Weight 1.45Kg
Total Dimension Ǿ172x285mm
Technical Specification
Model GST8431
Operation Voltage 100V
Rated Power 10W
Max. Power 15W
Sound Level (@6W/1W,
102dB±3 (SPL)
1kHz,1M)
Frequency Range 250Hz to 8 KHz
Case Material Aluminum alloy
Grid Material Steel
Color White
Weight 2.1Kg
Total Dimension 102
Technical Specification
Technical Specification
Technical Specifications
Z2
Z1 MANUFACTURED IN ACCORDANCE WITH
DI-9104Exd Detector
Installation
Note: Specifications are subject to change without notice.
Note: The detector shall be installed in
compliance with relative installation codes.
Make sure the housing is in good condition.
M6×60
M3 ×
Technical Specifications
Features:
Detection 17m
• Communication with integrated Distance
microprocessor. Ingress Protection IP66
Ambient -20°C to +40°C
• High sensitivity, reliable performance.
Temperature
• Dust /corrosion/humidity resistante Relative Humidity ≤95%RH, non-
• Secure and speedy communication condensing
• Effective range 12 to 25 metres Dimensions 147mm×103mm×92mm
• Twin LED for 360º vision Material and Color ZL102 Aluminum alloy,
• Mounting bracket support wall or silvery grey.
ceiling mount. Weight 1.5kg
Installation Hole 110mm×72mm
Spacing
Description: Explosion-proof Ex d0CT6
Mark
DC-9104Exd is a light-sensitive detector that Explosion-proof CE061027
detects fire by picking up the ultraviolet light certificate
Standards to EN 54-10
from flaming material. It’s designed for areas
comply with in GB 3836.1 GB 3836.2
where an open fire is liable to occur with design IEC 60079-0 IEC
large amount of radiation, with no 60079-1
smoldering stage, or where quick response to
a fire is required. This detector can be
applicable to zone 1 and 2 of explosive areas
Z2
Screws M3×16 2
Z1
Installation
Note: The detector shall be installed in Note: Specifications are subject to change without notice.
compliance with relative installation codes.
Make sure the housing is in good condition.
M6×60
M3 ×
Technical Specifications
• Operating Voltage:
Bus Voltage: 24V Range Allowed: 16V-
28V
Power Voltage: 24VDC Range
Allowed: 20VDC 28VDC
• Operating Current:
Standby Current≤0.5mA
Alarm Current≤5mA
• Programming mode: Electronic
programming within 1-242, occupying
one loop address.
• Wiring: Non-polarized two-bus with the
controller; non-polarized two-wire with
DC24V power cable; polarized two-wire
with explosion-proof devices.
Features and Benefits • Operating Environment:
Temperature: -10°C+5°C
1. Interface for Intrinsically safe detectors
and manual call point Relative Humidity≤95%, no
2. Electronically addressed condensation
3. Microprocessor supervises running status • Dimension: 200mm×162mm×85mm
and gives diagnosis message. • Safety Barrier Parameters: U0=28V,
4. With a built-in safety barrier, the I0=93mA, L0=4.3mH, C0=0.04μF
interface can directly match with • Weight: 1.5kg
intrinsically safe devices. • Mounting Hole Spacing: 192mm
212mm
• Material and Color of Enclosure: Q235A,
Description grayish white
• Ingress Protection level: IP 33
I-9332 Interface can match with explosion-
proof devices (explosion-proof smoke Selection of compatible Control Panels
detector, heat detector, combination
smoke/heat detector or manual call point) to Compatible with all GST Intelligent Fire
form an intrinsically safe system. When fire Alarm Panels.
occurs, the interface sends alarm signal to
fire alarm controller through loop and the Ordering Information:
controller will give alarm signal and display
the alarm address of the interface. When the Part No Description Weight/ Pack
interface itself is in fault, the controller will Kg Qty per
Box
give fault signal and display the fault address
I-9332 Addressable .180 120
of the interface.
Interface for
Detectors & MCP
including Zener
Electronic addressing can be done through Safety Barrier-Ex
Handheld Programming tool (P-9910),
purchased separately.
MANUFACTURED IN ACCORDANCE WITH
• Operating Voltage:
Bus Voltage: 24V
Range Allowed: 16V 28V
Power Voltage: 24VDC
Range Allowed: 20VDC -
28VDC
• Operating Current:
Standby Current≤0.5mA
Alarm Current≤500mA
• Programming mode: Electronic
programming within 1-242,
occupying one loop address.
• Wiring: Non-polarized two-bus with
the controller; non-polarized two-
wire with DC24V power cable;
polarized two-wire with explosion-
proof devices.
• Operating Temp: -10ºC to 50ºC
Features and Benefits • Relative Humidity≤95%, no
condensation
1. Interface for Intrinsically safe sounder • Dimension:
and sounder strobe 200mm×162mm×85mm
2. Electronically addressed • Weight: 1.5kg
3. Microprocessor supervises running status • Mounting Hole Spacing: 192mm
and gives diagnosis message. 212mm
4. With a built-in safety barrier, the • Material and Color of Enclosure:
interface can directly match with Q235A, grayish white
intrinsically safe devices. • Ingress Protection Level: IP33
I-8333 Interface can match with explosion- Compatible with all GST Intelligent Fire
proof sounder to form an intrinsically safe Alarm Panels.
system. When fire occurs, the interface
received alarm signal to fire alarm controller Ordering Information:
through loop and the controller will give
alarm signal activate the alarm. When the Part No Description Weight/ Pack
interface itself is in fault, the controller will Kg Qty per
Box
give fault signal and display the fault address
I-9333 Addressable .180 120
of the interface. Interface for
Sounder
Electronic addressing can be done through including Zener
Handheld Programming tool (P-9910), Safety Barrier-Ex
purchased separately.
K1 K2
O2 O1 I1 I2 Terminal Resistor
Sample wiring diagram above show detectors are connected with I-9333 Interface. There are four
terminals with numbers on the explosion-proof orientation base, “1” is the anode input, “2” is the
anode output, “3” is the power cathode, “4” is null.
Ordering Information:
Part No Description Weight/Kg Pack Qty per
Box
Intrinsically Safe Combined Smoke and
C-9101Ex 0.221 120
Heat Detector
DZB Intrinsically Safe Detector Base 0.050 360
I-9332 Interface Module 1.5Kg 1
Technical Specifications
K1 K2
O2 O1 I1 I2 Terminal Resistor
Sample wiring diagram above show detectors are connected with I-9333 Interface. There are four
terminals with numbers on the explosion-proof orientation base, “1” is the anode input, “2” is the
anode output, “3” is the power cathode, “4” is null.
Ordering Information:
Part No Description Weight/Kg Pack Qty per
Box
C-9103Ex Intrinsically Safe Dual Heat Detector 0.220 120
DZB Intrinsically Safe Detector Base 0.050 360
I-9332 Interface Module 1.5Kg 1
Technical Specifications
K1 K2
O2 O1 I1 I2 Terminal Resistor
Sample wiring diagram above show manual call point connected with I-9333 Interface. The
terminals I1, I2: to intrinsically safe side of the Safety Barrier.; K1, K2: Normally open output
terminals; while O2, O1: To next MCP.
Ordering Information:
Part No Description Weight/Kg Pack Qty per
Box
Intrinsically Safe Conventional Manual
C-9201Ex 0.221 120
Call Point
I-9332 Interface Module 1.5Kg 1
Description
The C-9403 (Ex) is an Intrinsically Safe
conventional combined sounder and strobe
while the C-9404 (Ex) is identical in
appearance and features to the C-9404 (Ex)
but without strobe element and are suitable
used for petroleum and chemical industrial.
This Using six highlights LED’s for high
intensity visual alarm to warn the people
especially the persons with hearing
difficulties. The audio efficiency and sound
distribution generate over 94 dB at 1
Features and Benefits meters distance giving an excellent
audibility from the device location.
This conventional electronic wall mounted
1. High intensity and long life LED
device initiated by fire alarm point using I-
cluster
9333Ex Interface (see manual for more
2. High sound level and Low power
information) with safety barrier to make an
consumption
explosion proof system.
3. Initiated by fire alarm control panel
4. Easy installation and connection
Specification
Part Number C-9403Ex C-9404Ex
Protection rating IP 33
Sound level output 85 dB to 115 dB
Main Sound Frequency 2.8Khz
Strobe / Frequency 6 highlight LED; 1.4 Hz± 20% No feature
Explosion Proof Marking Exib□CT6
Tone Modification Period 0.7s ± 20%
Operating voltage Power Supply 24Vdc(16~28Vdc)
Supply current: standby 5mA / alarm current: standby 3mA / alarm 35mA
Operating current
50mA
Operating Temperature -10°C to 50°C @ 95% relative humidity
Application Indoor and outdoor use
Materials and colour ABS / red; plexiglass / red
Dimension Ø 110mm x 97.5 mm
Wiring 2 wire (polarized)
Sounder Installation
The sounder base should be installed Selection of compatible ControPanels
complied with all local codes or NFPA 72 Compatible with all GST Intelligent Fire
National Fire Alarm Code, NFPA 70 National Alarm Panels via I-9333Ex Explosion Proof
Electrical Code, BS5839, EN54.It is installed Interface (purchased separately)
onto a standard one gang electrical box with
a mounting hole that have 6.5cm spacing.
Ordering Information:
Part No Description Weight Pack
WALL /Kg Qty per
ELECTRICAL
Box
BACK BOX
Intrinsically Safe
C-9403Ex Conventional 0.350 45
MOUNTING
Sounder Strobe
A hK k ff H l
BASE Intrinsically Safe
C-9404Ex Conventional 0.340 45
Sounder Strobe
Wiring and Connection I-9333 Interface Module 1.5Kg 1
Sample wiring diagram below show sounder
connected with I-9333 Interface. The
sounder D1 (+) 9; D2 (-), is for 24VDC
power supply polarized, connected to 3 and 4
of Interface. Each interface can only connect
with one sounder Ex or sounder strobe Ex.
Note that Interface should be installed in the
safety area and the cable must be fire rated
type and the size depends on the distance
and application. Minimum size gauge
1.0mm²(18 AWG)
I-9333 Ex-Interface
3(+)
I-9333Ex L+ 1(+) N F928 Zener
Circuit Board L- 2(-) Safety Barrier 4(-)
D1 D2 Z1 Z2