Hoja de Datos XMTN-800 Series

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

1.2.

List of common input types and Temperature ranges


XMTN-800 series Multi-channel Independent Auto
Maximum range of measurement
tuning PID Temperature Controller Operation Manual No. Input type SN Graduation
Degrees Celsius(℃) Fahrenheit(℉)
1 thermocouple 1 E -270~1000 -454~1832
2 thermocouple 2 J -210~1200 -346~2192
1. Wiring warning 3 thermocouple 3 K -270~1372 -454~2501
If the controller fails or an error occurs, the system may fail and an external protection circuit is 4 thermocouple 4 N -270~1300 -454~2372
installed to prevent such an accident.
5 RTD 15 Pt100 -200~0850 -328~1562
To prevent the controller from damage or failure, use proper fuse to protect the power cord and
input/output line from current shock. 6 Other sensors Customized -500~4000
2. Power supply of controller 1.3. Main technical indicators
To prevent electric shock or controller failure, please check the connection after all connection work 1) measurement accuracy: + 0.5%FS + 1db; Cycle control cycle: 0.2 second/every 8 loops.
is completed.
3. Use near flammable gas is prohibited 2) power supply: 24VDC + / - 10%Also can customize 100 ~ 240VAC power supply form.
In order to prevent fire, explosion or controller damage, it is prohibited to use in places where 3) operating environment: atmospheric pressure: 86 ~ 106kPa; 10 ~ 50 ℃ ambient temperature:
inflammable, explosive gas or steam is discharged. -Relative humidity: 45 ~ 85% RH.
4. Do not touch the inside of the controller
Do not touch the inside of the controller to prevent electric shock or burning. If it occurs any quality 4) avoid:
problem, please contact Shanghai yatai instrument Co., LTD. Only the service engineer of yatai can Condensation that can be caused by a sharp change in ambient temperature.
check the internal circuit or change parts. The controller has high voltage and high temperature
Direct vibration or impact of the main structure.
components inside, it is very dangerous to touch it without permission!
5. It is strictly forbidden to change the instrument Water, oil, chemicals, smoke or steam pollution. Corrosive and flammable gases.
In order to prevent accidents or controller failure, it is strictly forbidden to change the controller.
Too much dust, salt, or metal powder.
6. Maintain
In order to prevent electric shock, the controller is useless or invalid. Only Yatai service engineer can
2. Appearance and installation
replace the parts. The controller should be maintained regularly to ensure long-term safe operation.
Some parts inside the controller may be damaged with the extension of time. 2.1. Controller appearance
7. Clean
Wipe the controller after power off. To remove stains from the display, use a soft cloth or cotton paper.
The display is prone to scratches. Don't rub or touch with hard objects. Do not use screwdriver or pen
or other hard objects to operate the button, otherwise it will damage or scratch the button.
1. Product confirmation
1.1. Please refer to the following selection code to confirm whether the product delivered is
completely consistent with the model you selected

The maximum height of the controller (including the terminal) is 112mm;


The width of the controller is 56mm, 76mm and 116mm.
The depth of the controller is 78mm.
2.2. Controller installation 3.2. Wiring diagram of lower terminal
M3 screw installation, mounting hole is 102mm X (width -10mm) rectangular diagonal point.
DIN46277 rail (35mm wide) rail mounting. Remove the controller by pulling down the
assembly hook of the guide rail。
2.3. Display and operation panel

3. Terminal blocks
3.1. Wiring diagram of upper terminal
The hundred digits of XXX are positive and
4. Control parameter setting Positive and negative control options: X=0: reaction control
negative (heating type); 1: positive action control (cooling
4.1. Boot information action control type). The ten digit of XXX is first choice of alarm
7 EA 000~111 — 011
full screen >>> XMTN(N shows the quantity of zones)>>> V3.00(Software version and first 2, the single digit of XXX is first choice of alarm 1:
power on X=0: After the power on the alarm condition does
number)>>> normal condition alarm enable not alarm, then all alarm if the alarm condition is
4.2. CHANNEL SELECT met; 1: all alarm if the alarm condition is met.
After long press or for one second, the current loop number starts flashing, and then Regulation of proportional action: the larger the P,
the smaller the proportional action, the lower the
short press or to switch the control loop. The N+1 channel is the temperature display system gain. 0: change to on-off control mode. At
Proportional
8 P 0~9999 ℃ this point, the integral time I becomes 0.1 times of 30
band
of the environment (cold end of thermocouple). the upper limit of the insensitive region and the
differential time D becomes 0.1 times of the lower
4.3. Control parameter setting limit of the insensitive region.
Long press for 3 seconds to enter the setting state of control parameters. At this time, Integral action time constant: the larger the I, the
weaker the integral action, mainly used to eliminate
the upper row displays parameter prompt SV, and the lower row displays control parameters. the static difference. 0: become a PD control
9 Integral time I 0~9999 Sec. method, the integral inhibit Ar to set (RESET), and 240
At this point, the single digit flashes, short press and move the flshing digits. After the Ar is set to zero, the unit for ℃, is used to
eliminate static error. When P=0, see the description
selecting the number of digits to be modified, short press or to modify the control of P.
parameter. Continue to press , and display each parameter prompt in the upper row. After Differential action time constant: the larger the D,
Differential the stronger the differential action, which is mainly
10 d 0~9999 Sec. 60
finding the parameter that needs to be modified, continue to press to move the flshing Time used to restrain the overshoot of measured values.
When P=0, see the description of P.
digits. After selecting the number that needs to be modified, press or again to modify Restrained Integration ratio: the larger the Ar, the
larger the overthrust, and the smaller the Ar, the
the control parameter. Restrained
11 Ar 0~100 % possible static difference. 100
Integration
When the integral time I is equal to 0, see the
Long press for more than 1 second, the controller automatically returns to the normal description of the integral time I
control state (no button operation within 60 seconds, the controller automatically returns to the 12 Control cycle t Sec.
Output of thyristor or solid-state relay: 2~3 seconds;
3
1~100
Relay output: 20~30 seconds
normal control state).
Sensor error Used to correct measurement error caused by sensor
13 Pb -500~4000 ℃ 0.0
4.4. A list of control parameter Settings correction and thermocouple compensation wire
Parameter Initial YES: start self-tuning and restore nO after
No. Symbol Data Range Unit Introductions self-tuning. If the self-tuning rule is not completed
Name value —
14 Auto tuning At nO or YES within 4 hours, the original P, I and D values are still nO
1 Set value SVL~SVH ℃ The set target value of the zone of the controller 100 used for control.
The lower
2 AL1 -500~4000 ℃ See 4.5, alarm output instructions for details 50 In order to overcome the overshoot phenomenon of
limit alarm 1 Auto tuning
The lower Same as AL1, but can only be output through 15 AtU 0~100 % the Auto tuning time, the Auto tuning control point 100
3 AL2 ℃ 50 Limit
-500~4000 can be lowered to SV x ATU.
limit alarm 2 communication
See 1.2 list of commonly used input types and range
4
Upper limit
AH1 ℃ See 4.5, alarm output instructions for details 50 16 Graduation Sn 0~18 — 3-K
-500~4000 for details.
alarm 1
Upper limit Same as AH1, but can only be output through Decimal 0:the resolution of the measured values PV 1 ℃;
5 AH2 -500~4000 ℃ 50 17 dP 0~1 — 0
alarm 2 communication point 1:the resolution of the measured values PV 0.1 ℃
The single digit of XX is type 1 of alarm, while the The smaller this value, the faster the measured value
ten digit is type 2 of alarm. X=0: no alarm; 1: upper Filter responds, but there may be fluctuations; The larger
limit deviation alarm; 2: lower limit deviation alarm; 18 FILt 0~250 — 125
coefficients this value, the slower the measured value response
6 Alarm type SA 00~66 — 3: alarm outside the deviation value of upper and 01 and the more stable the display.
lower limits; 4: alarm within the deviation value of Used to suppress the change sensitivity of the
upper and lower limits; 5: upper absolute value Screen
19 dt 0~250 ℃ display value, and the range of inhibition is 0.1 15
alarm; blanking
times of the display inhibition dt.
Alarm1
20 differential FH1 -500~4000 ℃ The differential gap is 0.1 times of FH1 4
gap
21 Upper limit -500~4000 ℃ The highest measured value is SVH 300
of measured
value
4.6. Alarm output instruction
Lower limit The lowest measured value is SVL. Action condition Schematic diagram (for example,
22 of -500~4000 ℃ This parameter should be lowered if the ambient 0 No. Type
Alarm1 Alarm2 alarm 1 only)
measurement temperature is too low
0: control output off (SV displays 0FF under normal 1 alarm free Single-digit of SA =0。 tens digit of SA =0。 ——
Control the
23 SSt 0~1 — state), and only the output is off, others such as 1
output switch
alarm normal work;1: output open.
Alarm2 Single-digit of SA =1; tens digit of SA =1;
24 differential FH2 -500~4000 ℃ The differential gap is 0.1 times of FH2 4 Upper limit
2 deviation PV>SV+AH1 Alarm; PV>SV+AH2 Alarm;
gap
alarm PV≤SV+AH1-FH1 PV≤SV+AH2-FH2
Temperature remove alarm remove alarm
0:℃;
25 of the unit Ctr 0~1 — 0
switch 1:℉。
Overshoot
26 Ar2 0~250 — Reserved, not used now 0
restrain
Note: if you did not press for more than 1 second after modifying the parameter, the individual Single-digit of SA =2; tens digit of SA =2;
Minimum
parameters may not be saved. PV<SV-AL1 Alarm; PV<SV-AL2 Alarm;
3 deviation
alarm PV≥SV-AL1+FH1 PV≥SV-AL2+FH2
The change of each parameter in the list may change the control effect. Please be careful! remove alarm remove alarm
4.5. Auto tuning PID parameter function
Follow 4.4. Control parameter setting operation to find the auto tuning start parameter AT,
and display the “AT” prompt on the upper row, and “nO” prompt on the lower row, indicating Single-digit of SA =3; tens digit of SA =3;
that currently No limit setting or auto tuning function has been opened, Click to display the PV>SV+AH1 Alarm; PV>SV+AH2 Alarm;
Upper and
“YES” prompt below, indicating that the user is ready to start the loop auto tuning function; If PV≤SV+AH1-FH1 PV≤SV+AH2-FH2
lower limit
the temperature in the loop system is not allowed to exceed the set value SV too much, the next 4 remove alarm; remove alarm;
deviation
parameter can be set as auto tuning limit ATU, which can be set as between 70 and 80% (Auto outside alarm PV<SV-AL1 Alarm; PV<SV-AL2 Alarm;
PV≥SV-AL1+FH1 PV≥SV-AL2+FH2
tuning is carried out on 70 ~ 80% of the set value), Then remove alarm remove alarm
press more than 1 second to exit parameters Settings,
AT this point the AT indicator will flicker, indicate that the
Single-digit of SA =4; tens digit of SA =4;
controller in the process of auto tuning, temperature Upper and SV-AL1<PV<SV+AH SV-AL2<PV<SV+AH
fluctuations after two to three times to complete the whole lower limit 1 Alarm; 2 Alarm;
5
process of auto tuning, then the AT indicator light off, it is deviation PV≥SV+AH1+FH1 or PV≥SV+AH2+FH2 or
within alarm PV≤SV-AL1-FH1 PV≤SV-AL2-FH2
concluded that a set of suitable for the loop control of P, I,
remove alarm remove alarm
D parameter values, and according to the new P, I, D
parameters control, this P, I, D parameters will be forever in the controller.
Alarm
If the auto tuning process needs to be interrupted during the setting process, the control Output
parameter menu needs to be re-entered, Set the auto tuning start parameter AT to nO, and then Single-digit of SA =5; tens digit of SA =5;
Upper
exit the control parameter menu. AT this time, the AT indicator is off, and the controller will PV>AH1 Alarm; PV>AH2 Alarm; Alarm
6 absolute
control according to the original P, I ,D parameters. PV≤AH1-FH1 remove PV≤AH2-FH2 remove Remove
value alarm
alarm alarm FH1

AH1 PV

Single-digit of SA =6; tens digit of SA =6;


Lower limit
7 absolute PV<AL1 Alarm; PV<AL2 Alarm;
value alarm PV≥AL1+FH1 remove PV≥AL2+FH2 remove
alarm alarm
4.7. Error message 0X:The single digit is used to limit the control loop
When the measured value PV is lower than SVL, it is shown as oooo (communication number,The set range of X is 1~8(match with
The number of hardware) 。
output is -16666), indicating that the thermocouple is inversely connected, thermal resistance Measurement
X0:10 digits for manual/automatic inspection function
short-circuit or three-wire connection is wrong, and the ambient temperature (cold end 3 and automatic CHLS 01~88 28
inspection setting;
temperature) is too low. Please check whether the sensor wiring is correct or the sensor is X=0:Manually switch the loop to be displayed;
function
damaged. When the ambient temperature is too low, the lower limit SVL can be lowered to test. X=1 ~ 8 : Show stop time for each channel during
When the measured value PV is higher than SVH, it is shown as oooo (communication automatic inspection, unit is second.
output is 18888), which indicates that the thermocouple is open circuit or the thermal resistance
is open circuit, and the actual measurement temperature is higher than the upper limit of the 6. Maintenance and preservation
range (the sensor and the heating unit do not form the same loop, resulting in long-term heating).
6.1. Maintenance: within 18 months following the purchase of the instrument, the factory shall be
Please check whether the sensor is damaged and the control loop is connected correctly responsible for the overall warranty for the failure of manufacturing quality. If the instrument is
5. Communication connection and set-up damaged due to improper use, the factory will charge users repair cost, and the instrument has
lifetime warranty.
5.1. Multiple controller communication connection 6.2. Storage: the instrument should be kept in dry, ventilated and free of corrosive gas with complete
When the sensor indexing code Sn is not set to a valid value, it is displayed as Erro package.
(communication output is 15555).
Phone:021-66186368;021-66186369
Fax : 021-66186226 technology consulting :
021-36160962
E-mail:[email protected] http://www.yatai.sh.cn
Address: no. 128, zhenyuan road, baoshan city
上海亚泰仪表有限公司 industrial park, Shanghai
Shanghai yatai instrument co., LTD Document number:YT 01 20170303 2.0

5.2. Communication parameter setting(In normal state, long press for more than 3 seconds
to enter the communication parameter setting)
Initial
No Parameter Name Symbol Data Range Introductions
value
Common addresses are 0 ~ 9 and can be extended to
254;
Including:
0 is broadcast address;
Communication 251 is the initial value address of all parameters restored
1 Addr 0~254 1
address at factory:
When Addr=251, press and all parameters of the
controller are restored to the factory initial value. About 5
seconds later, the system will restart and enter the normal
working state automatically.
Communication The 0:600; 1:1200; 2:2400; 3:4800;
2 rate bAUd value of 4:9600;5:14400;6:19200;7:28800;8:38400; 9600
(bps) 0~10 9:57600; 10:115200。