Chapter Two
Chapter Two
Institute of Technology
School of computing and Electrical Engineering
Power system I
2. Representation of Power system components
Ahunim Abebe
Email: ahunim@gmail.com
1
Outline
Single-phase solution of balanced three-phase networks
One-line diagram
Impedance or reactance diagram
Per unit (PU) system
2
Introduction
The basic equipments of a power system are generators, transformers,
transmission lines, and loads
The interconnections among these components in the power system
may be shown in a so called one line diagram
For analysis, the equivalent circuits of the components are shown in a
reactance diagram or an impedance diagram
3
Single-phase solution of balanced three-phase networks
Figure 2.1
4
The neutral impedance z n does not affect network behavior
For the reference phase a
Ea (zG zL )Ia .............(2.1)
The current and the voltage in the other phases have the same magnitude
but progressively shifted by 1200
Equation 2.1 corresponds to the single phase network of figure 2.2 below
The solution of fig. 2.2 completely determines the solution of the three
phase network
Figure 2.2
5
Consider the case where a three phase transformer forms part of a three
phase system
If the transformer is Y/Y connected as shown in fig. 2.3a, in the single
phase equivalent of the three phase circuit it can be obviously represented
by a single phase transformer (as in fig. 2.3b) with primary and secondary
pertaining to phase a of the three phase transformer
Figure 2.3
6
If the transformer is Y/∆ connected as in figure 2.4a below, the delta side
has to be replaced by an equivalent star connection as shown doted so as to
obtain the single phase equivalent of fig. 2.4b
When the load is balanced, the impedance of each leg of the Y is one third
the impedance of each leg of the ∆
Since both phase voltage and line current shift through the same phase
angle from star to delta side, the transformer per phase impedance and
power flow are preserved in the single phase equivalent
7
Figure 2.4
9
One-line diagram
Power system networks are represented by one-line diagrams using
suitable symbols for generators, motors, transformers and loads
A one-line diagram of a power system shows the main connections and
arrangements of components
Figure 2.5 shows the symbols used to represent the typical components of
a power system
Figure 2.6 is a one line diagram for a power system consisting of two
generating stations connected by a transmission line; note the use of the
symbols of fig. 2-5
The advantage of such a one-line representation is its simplicity: one phase
representation all three phases of the balanced system; the equivalent
circuit of the components are replaced by their standard symbols; and the
completion of the circuit through the neutral is omitted
10
11
Fig. 2.6
12
IMPEDANCE AND REACTANCE DIAGRAMS
In power system analysis it is necessary to draw an equivalent circuit for
the system.This is an impedance diagrams.
However, in several studies, including short-circuit analysis it is
sufficient to consider only reactances neglecting resistances. Hence, we
draw reactance diagrams.
For 3-phase balanced systems, it is simpler to represent the system by a
single line diagram without losing the identity of the 3-phase system.
Thus, single line reactance diagrams can be drawn for calculation.
13
The one-line diagram may serve as the basis for a circuit representation
that includes the equivalent circuits of the components of the power
system.
Such a representation is called an impedance diagram or a reactance diagram
if resistances are neglected.
The impedance and reactance diagrams corresponding to Fig. 2-6 are shown in Fig.
2-8(a) and (b), respectively. Note that only a single phase is shown.
14
15
The following assumptions have been incorporated into Fig. 2-8(a):
1. A generator can be represented by a voltage source in series with an
inductive reactance. The internal resistance of the generator is
negligible compared to the reactance.
2. The loads are inductive.
3. The transformer core is ideal, and the transformer may be represented
by a reactance.
4. The transmission line is a medium-length line and can be denoted by a T
circuit. An alternative representation, such as a circuit, is equally applicable.
5. The delta-wye-connected transformer T1 may be replaced by an
equivalent wye-wye-connected transformer (via a delta-to-wye
transformation) so that the impedance diagram may be drawn on a per-
phase basis.
The reactance diagram, Fig. 2-8(b), is drawn by neglecting all resistances, the static
loads, and the capacitance of the transmission line.
16
PER-UNIT REPRESENTATION
Computations for a power system having two or more voltage levels become very
cumbersome when it is necessary to convert currents to a different voltage level
wherever they flow through a transformer (the change in current being inversely
proportional to the transformer turns ratio).
In an alternative and simpler system, a set of base values, or base quantities, is
assumed for each voltage class, and each parameter is expressed as a decimal
fraction of its respective base.
For instance, suppose a base voltage of 345 kv has been chosen, and under certain
operating conditions the actual system voltage is 334 kV: then the ratio of actual
to base voltage is 0.97.
The actual voltage may then be expressed as 0.97 per-unit. In an equally common
practice, per-unit quantities are multiplied by 100 to obtain percent quantities:
our example voltage would then be expressed as 97 percent.
Per-unit and percent quantities and their bases exhibit the same relationships and
obey the same laws (such as Ohm's law and Kirchhoff’s laws) as do quantities in
other systems of units.
17
A minimum of four base quantities is required to completely define a per-
unit system: these are voltage, current, power, and impedance (or
admittance). If two of them are set arbitrarily, then the other two become
fixed.
Base values can be determined by three ways
Taking the largest value
Taking the total sum
Any arbitrary
The per unit value of any quantity is the ratio of the actual value in any
units to the chosen base quantity of the same dimensions expressed as a
decimal.
Actual value in any units
Per unit quantity
Base or reference value in the same unit
In power systems the basic quantities of importance are voltage, current,
impedance and power. For all per unit calculations a base KVA or MVA
and a base KV are to be chosen.
Once the base values or reference values are chosen, the other quantities
can be obtained as follows:
18
Where base KVA and base MVA are the total or three phase values.
If phase values are used
base voltage
Base impedance in ohm =
base current
(base K V) 2 / 1000
base K V A per phase
In all the above relations the power factor is assumed unity, so that
19
Selecting the total or 3-phase KVA as base KVA, for a 3-phase system
(base KV (line-to-line)2
Base Impedance in ohms = base MVA
20
Some times, it may be required to use the relation
actual Impedance in ohm = (Per unit impedance in ohms) (base KV) 2
(base M VA)
Very often the values are in different base values. In order to convert the
per unit impedance from given base to another base, the following relation
can be derived easily.
Per unit impedance on new base
2
b a se k V o ld b a se k V A n ew
Z (p u ) n ew Z ( p u ) o ld X x
b ase k V n ew b ase k V A g iv en
21
In general :
Base current = base volt amperes/base voltage (in amperes)
Base impedance = base voltage/ base current (in ohms)
Per-unit voltage = actual voltage / base voltage (per unit, or pu)
Per-unit current = actual current / base current (per unit, or pu)
Per-unit impedance = actual impedance /base impedance (per unit, or
pu)
The impedances of transmission lines are expressed in ohms, but can be
easily converted to pu values on a given voltampere base using above
expressions.
22
Advantages of Per Unit System
1. While performing calculations, referring quantities from one side of
the transformer to the other side serious errors may be committed. This
can be avoided by using per unit system.
2. Voltages, currents and impedances expressed in per unit do not
change when they are referred from one side of transformer to the
other side.This is a great advantage'.
3. Per unit impedances of electrical equipment of similar type usually
lie within a narrow range, when the equipment ratings are used as base
values.
4.Transformer connections do not affect the per unit values.
5. Manufacturers usually specify the impedances of machines and
transformers in per unit or percent of name plate ratings.
23