Equipment, Design & Service Manual: U.S. & Foreign Patents Doc. P/N 06-917 Rev. 0 / June, 2019
Equipment, Design & Service Manual: U.S. & Foreign Patents Doc. P/N 06-917 Rev. 0 / June, 2019
Explosion Protection
Overpressure Protection
Pressure Activation
COPYRIGHT INFORMATION
© Copyright 2019, Fike Corporation. All rights reserved. Printed in the U.S.A.
This document may not be reproduced, in whole or in part, by any means without the prior written consent of Fike. All
Fike documentation and hardware are copyrighted with all rights reserved.
TRADEMARKS
Fike, SHP-Pro®, Cheetah® Xi, are registered trademarks of Fike. All other trademarks, trade names or company names
referenced herein are the property of their respective owners.
TERMS OF USE
Do not alter, modify, copy, or otherwise misappropriate any Fike product, whether in whole or in part. Fike assumes no
responsibility for any losses incurred by you or third parties arising from such alteration, modification, copy or otherwise
misappropriation of Fike products.
Do not use any Fike products for any application for which it is not intended. Fike shall not be in any way liable for any
damages or losses incurred by you or third parties arising from the use of any Fike product for which the product is not
intended by Fike.
You should install and use the Fike products described in this document within the range specified by Fike, especially
with respect to the product application, maximum ratings, operating supply voltage range, installation and other
product characteristics. Fike shall have no liability for malfunctions or damages arising out of the use of Fike products
beyond such specified ranges.
You should install and use the Fike products described in this document in compliance with all applicable laws,
standards, and regulations. Fike assumes no liability for damages or losses occurring as a result of your noncompliance
with applicable laws and regulations.
It is the responsibility of the buyer or distributor of Fike products, who distributes, disposes of, or otherwise places the
product with a third party, to notify such third party in advance of the contents and conditions set forth in this document.
Fike assumes no responsibility for any losses incurred by you or third parties as a result of unauthorized use of Fike
products.
QUALITY NOTICE
Fike has maintained ISO 9001 certification since 1996. Prior to shipment, we thoroughly test our products and review
our documentation to assure the highest quality in all respects.
TABLE OF CONTENTS
Section Page No.
1. Introduction................................................................................................................................................................. 1
2. System Components.................................................................................................................................................... 2
2.1. 3M™ Novec™ 1230 Fire Protection Fluid ............................................................................................................. 2
2.2. Agent Storage Containers..................................................................................................................................... 4
2.3. Impulse Valve ....................................................................................................................................................... 6
2.3.1. Valve Recharge Kits .................................................................................................................................... 8
2.4. Pressure Gauge .................................................................................................................................................... 9
2.5. Liquid Level Indicator (LLi).................................................................................................................................. 10
2.6. Low Pressure Switch (LPS).................................................................................................................................. 11
2.7. Mounting Straps and Brackets ........................................................................................................................... 12
2.8. Impulse Valve Operator (IVO) ............................................................................................................................ 13
2.9. Impulse Energetic Actuator (IEA) ....................................................................................................................... 14
2.10. Impulse Valve Pneumatic Operator (IVPO)....................................................................................................... 15
2.11. Impulse Valve Operator Supervisor (IVOS) ....................................................................................................... 16
2.12. Discharge Pressure Switch (DPS) ...................................................................................................................... 17
2.13. Discharge Nozzles ............................................................................................................................................. 18
2.14. Check Valves ..................................................................................................................................................... 19
2.15. Caution/Advisory Signs ..................................................................................................................................... 20
2.16. Nitrogen Actuator Assembly............................................................................................................................. 22
2.17. UVO Primary Completer Kit .............................................................................................................................. 23
2.18. UEA Primary Completer Kit............................................................................................................................... 24
2.19. Secondary Completer Kit .................................................................................................................................. 25
2.20. Selector Valve Assembly ................................................................................................................................... 26
2.21. Suppression Disconnect Switch ........................................................................................................................ 28
3. System Design ........................................................................................................................................................... 29
3.1. Evaluate Enclosure Integrity ............................................................................................................................. 29
3.2. Subfloor Protection........................................................................................................................................... 30
3.3. Determine Hazard Classification....................................................................................................................... 30
3.4. Determine Enclosure Volume ........................................................................................................................... 30
3.5. Calculate Reduced Volume ............................................................................................................................... 30
3.6. Determine Minimum Design Concentration..................................................................................................... 31
3.7. Determine Minimum Quantity of Agent Required ........................................................................................... 31
3.8. Apply Altitude Correction Factor ...................................................................................................................... 33
Enough information is provided in this manual to allow those responsible for designing a Fike fire suppression system
to properly do so, and for the parties responsible for verifying the system design to determine if the design parameters
have in deed been met.
Fike fire suppression systems may be UL/ULC Listed and/or FM Approvals Approved depending on where and how the
system containers where filled. Special codes following the container part number designate which approval your
system has, but the governing indicator is whether the system container labels bear the agency’s official markings.
Systems bearing the UL and ULC mark have been designed, tested and filled per UL 2166,
Halocarbon Clean Agent Extinguishing System Units.
Systems bearing the FM Approved mark have been designed, tested and filled to meet FM 5600,
Approval Standard for Clean Agent Extinguishing Systems.
If any of these marks are absent from the container label, the system containers, while still designed and tested per
relevant UL and FM standards, were not filled at a UL/ULC Listed and/or FM Approved fill location.
Any questions concerning the information presented in this manual should be addressed to:
Extinguishing Method
Novec 1230 fluid extinguishes a fire primarily through heat absorption. The gaseous mixture created when Novec 1230
fluid discharges into air has a much higher heat capacity than air alone. The gaseous mixture absorbs large amounts of
heat due to the high heat capacity and extinguishes fires by sufficiently cooling the combustion zone. It is important to
note, Novec 1230 fluid does not use the depletion of oxygen to extinguish a fire.
Approvals
Approvals include, but are not limited to:
Class A and C hazards including electrical and electronic hazards, telecommunication facilities and high value
assets where the associated down-time would be costly
Novec 1230 fluid shall NOT be used on fire involving the following materials:
Chemicals or mixtures of chemicals capable of rapid oxidation in the absence of air, such as cellulose nitrate and
gunpowder
Reactive metals such as lithium, sodium, potassium, magnesium, titanium, zirconium, uranium and plutonium
Chemicals capable of undergoing auto-thermal decomposition, such as organic peroxides, pyrophoric materials,
and hydrazine
NOTE: Fike does not recommend this system to be used in any normally occupied spaces where the design
concentration required is above 10.0%.
Specific Heat, Liquid (Cp) @ 25°C (77°F), kJ/kg-°C (Btu/lb-°F) 1.103 (0.2634)
Specific Heat, Vapor (Cp) @ 25°C (77°F), kJ/kg-°C (Btu/lb-°F) and 1 ATM 0.891 (0.2127)
Global Warming Potential, GWP (100 yr. ITH. For CO2, GWP = 1) ≤1
The Impulse Valve contains a fast-acting rupture disc that retains the agent
within the container until the disc is ruptured by an electric or pneumatic
actuator (ordered separately), which allows the agent to be released from the
container.
Each container is factory filled with 3M™ Novec™ 1230 Fire Protection Fluid in 1
lb. (0.5 kg.) increments up to their maximum capacity and is then super-
pressurized with dry nitrogen to 500 psig at 70°F (34.5 bar at 21°C). Fill density
must be specified when ordering. Containers sharing the same manifold must be
equal in size and fill density.
Specifications
Super – Pressurization Level 500 psig at 70°F (34.5 bar at 21°C) after filling with dry nitrogen
Storage Temperature Limitation 32°F (0°C) Minimum to 130°F (54.4°C) Maximum (see note)
If the container pressure reaches 720 to 800 psi (49.6 to 55.2 bar), valve will open
Safety Relief Range automatically. This fulfills the pressure relief valve requirements in accordance with DOT
regulations.
Container Rating DOT 4BW500 / TC 4BWM534
Actuation Methods Electric / Pneumatic / Manual
Color Options White (default) or Red, Baked Enamel Finish
Fill Increments 1.0 lbs.(0.5 kg)
Fill Range 30 to 70 lbs/ft3 (481 to 1121 kg/m3)
P/N ending in -3P: UL/ULC Listed and FM Approved
Approvals
P/N ending in –UL: UL/ULC Listed Only
Note: If container temperature exceeds 130°F (54.5°C), system performance may be affected.
Item
Description
Number Item 1
1 Grooved Coupling & Nipple Item 2
Item 3
2 Impulse Valve Item 4
3 Pressure Gauge
4 LLi Boss (see note 1)
5 Liquid Level Indicator (LLi) Item 6
The valve’s rupture disc assembly also acts as the pressure relief device
for the container in accordance with DOT regulations by automatically
opening if the container temperature exceeds 130°F (54.4°C).
Each Impulse Valve is equipped with the following ports: Impulse Valve
Agent Discharge Port allows agent release from container and also fulfills the pressure relief valve requirements in
accordance with DOT regulations.
Agent Fill Port used to fill (refill) and pressurize the container and also used for the Low Pressure Switch.
Actuator Port used to connect an Impulse Valve Operator (IVO) with Manual Strike Button for electric and manual
actuation of the container or an Impulse Valve Pneumatic Operator (IVPO) for pneumatic operation.
Pressure Gauge Port is used to connect a Pressure Gauge that will monitor internal container pressure, also
equipped with an orifice plug that allows the pressure gauge to be removed safely when the container is
pressurized.
Discharge Port
Fill Port
Discharge Port
Pressure Gauge
Actuator Port
Actuator Pin
For a detailed procedure on recharging a Fike container with an Impulse Valve refer to Fike’s Recharge Manual, P/N 06-
852.
The pressure gauge port on the Impulse Valve is designed to allow the
gauge to be removed/replaced on a charged container without
removing the agent first. The port allows a small controlled amount of
leakage past its internal threads. This provides enough flow to operate Pressure Gauge
the pressure gauge while being small enough to allow the gauge to be
removed and replaced safely without excessive pressure or agent loss.
Specifications
Type: Bourdon Tube Pressure Gauge
Diameter: 1.6 in. (40 mm)
Pressure Range: 0 to 760 psi (0 to 52.4 bar)
Connection: 1/8 in. NPT
Accuracy: ±4% at charge (±20 psi)
US Standard Metric
Temperature Pressure Temperature Pressure
(°F) (psig) (°C) (bar)
32 453 0 30.3
40 463 10 32.1
50 475 15 32.9
60 488 20 33.8
70 500 25 34.7
80 513 30 35.6
90 525 35 36.5
100 538 40 37.4
110 550 45 38.2
120 563 50 39.1
130 575 55 40.0
The liquid level is found by lifting the measuring tape from inside the
tube to the end above the anticipated liquid level and slowly lowering
the tape until a magnetic interlock with the float is felt. The tape will
then remain in the locked position, allowing a reading to be taken at the
top of the LLi boss. The weight of the agent in the container is
determined by converting the level measurement into a weight
measurement using the tables provided in the Liquid Level Indicator
manual (P/N 06-869).
CONTAINER APPROXIMATE
LLi PART
SIZE LENGTH
NUMBER
lb. (L) in. (mm)
100 (44) 70-1353-27 27 (686)
150 (61) 70-1353-14 14 [356)
215 (88) 70-1353-18 18 (457)
375 (153) 70-1353-27 27 (686)
650 (267) 70-1353-38 38 (965)
Liquid Level Indicator
1000 (423) 70-1353-49 49 (1245)
Specifications
Mounting Thread: 1 5/16-12UN-2A NPT
Stem Material: Brass
Mounting Material: Brass
Float Material: Buna-N
Accuracy: ±4% at charge (±14 psi)
NOTE: Liquid Level Indicator (LLi) must be installed while the container is empty.
The LPS may be ordered along with a configured Impulse Valve container or
as a separate item that can be installed on a fully pressurized container
without loss of agent or pressure. Low Pressure Switch (LPS)
Specifications
Temperature Limits +32°F to +130°F (0°C to 54.4°C)
Enclosure Classification NEMA 4
Single pole, double throw; 5 amps
resistive, 3 amps inductive @ 30 VDC
Contact Rating
(can be wired for normally open or
normally closed operation)
Body Material Aluminum with irridite finish
Weight 6.5 oz (184 g)
Pressure Connection M10 x 1-6G
Electrical Connection 1/2 in. NPT (15 mm)
4.375 in. (111 mm) Long
LPS Length (approximate)
(including both connectors)
Thee, 18 gauge x 48 in. (1.2 m) Long
Wire Leads
Violet (Common), Blue (N.O.), Black (N.C.)
Pressure Setting 450 psig (31 bar), decreasing
Activation of the IVO provides the force required to extend its stainless
steel piston through the base of the actuator where it will impact the
container’s rupture disc valve causing it to open, allowing the agent to
be released from the container. The IVO can easily be reset after
activation to return it to normal operation.
Specifications
Ordering Information
The IVO can be ordered separately or it can be ordered as part of the
following kit.
Specifications
Construction Brass
Conduit Connection 1/2 in. NPT Male threads
Wires Two, 20 AWG Red Wires, 36 in. (914 mm) long
Normal Supply Voltage 24 VDC
Monitoring Current 0.01 Amps (battery calculations)
Firing Current 1 Amp max.
Auto Ignition Temp. ≥ 170°C (338 °F)
Storage Temp. Min. 5°C (41 °F), max 25°C (77 °F)
Shelf Life 1 year
Service Life (ambient) 10 years
Approvals UL Listed Only
Ordering Information
The IEA can be ordered separately or it can be ordered as part of the
following kit.
The pneumatic pressure fed into the IVPO provides the force required to
extend its stainless steel piston through the base of the actuator where
it will impact the container’s rupture disc valve causing it to open,
allowing the agent to be released from the container. The IVPO can be
easily reset after activation to return it to normal operation. Impulse Valve Pneumatic
Connection of the IVPO to the container’s actuator port must be Operator (IVPO)
continuously supervised. This is accomplished by using a Fike Impulse
Valve Operator Supervisor (P/N 02-14263) to secure the IVPO to the
container’s actuator port. See Section 2.11 for IVOS details.
Specifications
Ordering Information
The IVPO can be ordered separately or it can be ordered as part of the
following kit.
The IVOS has a built-in Form-C push-button switch that supervises the
connection of the electric actuator or pneumatic actuator to the
Impulse Valve Operator
containers discharge valve. Removal of the IVOS from the discharge
Supervisor (IVOS)
valve will trigger the IVOS switch causing a visual and audible “Trouble
or Supervisory” indication at the Fike control panel signaling that the
container’s actuator has been removed.
Specifications
− Plastic housing with insert molded SST clip and
sealed push-button switch (Form C)
− SST flexible conduit, 0.25 in. (6.4 mm) ID, 33.5 in.
Construction (850.9 mm) long
− 3/8 in. electrical connector for 1/2 in. knockout
− 22 AWG wire leads, 44 in. (1117.6 mm) long; Black
(NC) / White (NO) / Red (Common)
Ordering Information
The IVOS can be ordered separately or it can be ordered as part of the
following kits.
Specifications
Temperature Limits 32 to 130°F (0 to 54°C)
Enclosure Classification NEMA 4
Single pole, double throw; 5 amps resistive @ 30 VDC
Contact Rating
(can be wired for normally open or normally closed operation)
Body Material Aluminum with irridite finish
Pressure Connection 1/4 in. (6 mm) NPT
4.125 in. (105 mm)
Approximate Length
(including both connectors)
Electrical Connection 1/2 in. (15 mm) NPT
Three, 18 gauge x 20 in. (508 mm) long
Wire Leads
Violet (C), Blue (NO), Black (NC)
Pressure Setting 40 psig (3 bar), increasing
Weight 6.5 oz (184 g)
NOTE: NFPA 2001 requires the installation of a discharge pressure switch on all systems
where mechanical system actuation is possible. The discharge pressure switch shall
provide an alarm-initiating signal to the releasing panel. The discharge pressure
switch can be omitted if the hazard being protected is unoccupiable and is in a
remote location where personnel are not normally present.
Seven sizes of discharge nozzles are available, 1/2" (15 mm) through 2" (50
mm). The size refers to the size of schedule 40 or 80 pipe that the nozzle can
be connected to. Each nozzle has NPT female threads for connection to the
pipe network.
Each discharge nozzle comes with a brass orifice plate that controls the flow
of agent through the nozzle. The hole diameter of the orifice plate is 360° Nozzle
determined by performing a hydraulic calculation using Fike’s Flow
Calculation Program. Engineered nozzle(s) should not be ordered until the
clean agent system pipe network is installed and an “As Built” hydraulic
calculation is performed. Orifice plate drilling must be done at the Fike
factory, or at a UL listed nozzle drill station.
Ordering
Part Number Description
80-124-50-X 1/2 in. (15 mm) 360° nozzle
80-124-75-X 3/4 in. (20 mm) 360° nozzle
80-124-100-X 1 in. (25 mm) 360° nozzle 180° Nozzle
80-124-125-X 1 1/4 in. (32 mm) 360° nozzle
80-124-150-X 1 1/2 in. (40 mm) 360° nozzle
80-124-200-X 2 in. (50 mm) 360° nozzle
80-122-50-X 1/2 in. (15 mm) 180° nozzle
80-122-75-X 3/4 in. (20 mm) 180° nozzle
80-122-100-X 1 in. (25 mm) 180° nozzle
80-122-125-X 1 1/4 in. (32 mm) 180° nozzle
80-122-150-X 1 1/2 in. (40 mm) 180° nozzle
80-122-200-X 2 in. (50 mm) 180° nozzle
NOTE: -XXXX in part number is the orifice code designation.
Specifications
Part No. 02-2980-1 02-4158-1 70-317 02-16557 02-16558 70-356
Swing Swing Swing
Type Ball Check Ball Check Ball Check
Gate Gate Gate
1 in. 2 in. 3 in. 1 in. 2 in. 3 in.
Size
(25 mm) (50 mm) (80 mm) (25 mm) (50 mm) (80 mm)
4.3 in. 6.0 in. 8.0 in. 4.2 in. 6.4 in. 11.0 in.
Length (A)
(108 mm) (152 mm) (203 mm) (107 mm) (162 mm) (281 mm) 70-356 Check Valve
3.6 in. 4.4 in. 5.8 in. 2.8 in. 1.8 in. 6.5 in.
Height (B)
(91 mm) (111 mm) (147 mm) (70 mm) (46 mm) (165 mm)
5 lbs. 13 lbs. 28 lbs. 5 lbs. 16 lbs. 37 lbs.
Weight
(2.3 kg) (5.9 kg) (12.7 kg) (2.3 kg) (7.3 kg) (16.8 kg)
Sch. 40 Sch. 40
15.8 ft. 50.0 ft.
Equivalent 2.0 ft. 4.0 ft. 4.0 ft. (4.82 m) (15.24 m) 14.0 ft.
Length (0.61 m) (1.22 m) (1.22 m) Sch. 80 Sch. 80 (4.27 m)
10.1 ft. 36.6 ft.
(3.08 m) (11.16 m)
Carbon Carbon Ductile Carbon Carbon Ductile
Material 02-16557 and 02-16558
Steel Steel Iron Steel Steel Iron
Check Valves
NPT NPT NPT NPT NPT Grooved
Ends
Female Female Female Female Female
Working 750 psi 750 psi 750 psi 2000 psi 2000 psi 750 psi
Pressure (50 bar) (50 bar) (50 bar) (138 bar) (138 bar) (50 bar)
Mounting Horizontal or Vertical (with flow arrow up)
The sign is 13 in. (330 mm) x 10 in. (254 mm), with white
lettering on a blue backgound for NOTICE and black lettering
on a white background for instructional text.
A completer kit must be purchased separately and installed onto the Nitrogen
Actuator Assembly to facilitate electrical/manual, electric or pneumatic
activation of the assembly. See Section 2.17, 2.18 and 2.19 for completer kit
details.
NOTE: When used for selector valve activation, the nitrogen actuator assembly
and completer kit are furnished with the selector valve.
Specifications
Nitrogen Cylinder Nitrogen Actuator
Fill Pressure 1800 psig (124 barg) Assembly
Volume 28 in3 (460 ml)
Classification DOT 3E1800 / TC-3EM 124
Temperature Range -4°F to 130°F (-20°C to 54°C)
Valve
Body Brass
Retaining Clip SST
Fill Valve Plug SST
ERD Plug SST
O-Ring Polyurethane
Pressure Gauge
Housing SST Case, Polycarbonate Lens, Brass Adaptor
Contact Rating Contacts rated at 333 mA / 30V DC
Electrical Connection 18 AWG, 12 in. Leads
1621 psi (112 bar) decreasing
Switch Setting
(Normally Open at Operating Pressure)
Ordering
Part Number Description
70-325-1 Nitrogen Actuator Assembly (Cylinder Pressurized)
70-325-3 Nitrogen Actuator Assembly (Cylinder not Pressurized)
The following parts are included in the UVO Primary Completer Kit. See diagram
below.
Item
Part Number Description
No.
1 02-13571 Universal Valve Operator (UVO)
2 02-2213 Security Tie
3 02-13640 1/8 in. NPT x 1/4 in. NPT Adapter
4 C02-1335 1/4 in. NPT Street Tee
5 02-11766 1/4 in. NPT x G1/4 Adapter
6 02-10926 1/4 in. Sealing Washer
7 IG71-026 Vent Valve Assembly
8 02-4530 1/4 in. NPT x 1/4 in. JIC Adapter Nitrogen Actuator Assembly
9 02-4977 35 in. Hose (1/4 JIC x 1/4 JIC) with UVO (Primary)
The UEA provides a means to electrically activate the Nitrogen Actuator Assembly with
a 24 VDC signal from the Fike control panel. The UEA does not provide a means to
manually activate the Nitrogen Actuator. Activation of the UEA allows pressure from
the Nitrogen Actuator Assembly to flow through a stainless steel pneumatic actuation
line to the controlled system component resulting in activation.
The following parts are included in the UEA Primary Completer Kit. See diagram below.
Item
Part Number Description
No.
1 IG71-247 Universal Energetic Actuator (UEA)
2 02-13640 1/8 in. NPT x 1/4 in. NPT Adapter
3 C02-1335 1/4 in. NPT Street Tee
Nitrogen Actuator Assembly
4 02-11766 1/4 in. NPT x G1/4 Adapter
5 02-10926 1/4 in. Sealing Washer with UEA (Primary)
6 IG71-026 Vent Valve Assembly
7 02-4530 1/4 in. NPT x 1/4 in. JIC Adapter
8 02-4977 35 in. Hose (1/4 JIC x 1/4 JIC)
9 02-14627 Universal Valve Operator Supervisor (UVOS)
10 02-11902 1/8 BSPT Plug (not shown)
11 10-2748 Impulse Releasing Module (IRM)
The following components are included in the Secondary Completer Kit. See
diagram below.
Item
Part Number Description
No.
1A* IG71-120 Pneumatic Relay
1B* 02-11243 1/8 in. x 1/4 in. JIC Hex Nipple
1C* 02-4977 1/4 in. JIC x 1/4 in. JIC Braided Hose, 36 in. long
2 02-14721 1/4 in. JIC x 1/4 in. FNPT Branch Tee
Nitrogen Actuator Assembly
3 02-11766 1/4 in. NPT x G1/4 Adapter
with Pneumatic Relay
4 02-10926 1/4 in. Sealing Washer
(Secondary)
5 IG71-026 Vent Valve Assembly
6 02-11346 1/4 in. JIC Coupling
*Part of pneumatic relay assembly (P/N 70-334)
Selector valves are closed during normal operation, blocking the flow of agent
through the piping network. A nitrogen actuator with compatible actuator
must be installed and connected to each selector valve actuator via a stainless
steel pilot line connection. This connection allows the pressure from the
nitrogen actuator to be delivered to the selector valve actuator for valve Selector Valve Assembly
activation. After activation, the selector valve must be manually closed (reset). (Actuation Components not Shown)
Specifications
Standard Port Ball Valve
NPT Threads
Body: Carbon Steel or Stainless Steel
Valve
Ball: Stainless Steel
Pressure Rating: 1 in. (25 mm) = 2000 psi (138 bar)
All others = 1500 psi (103 bar)
Rack and Pinion Pneumatic Actuator, ¼ turn, Double Acting
Actuator Pressure Rating: 80 – 142 psi (5.5 – 9.8 bar)
Factory Installed on Ball Valve
1/4 in. NPT ASME Relief Valve for Air or Gas Service
Set Pressure: 100 psi (6.9 bar)
Pop-Off Relief Capacity: 92 SCFM
Valve Body, Nozzle, Stem and Spring Material: Stainless Steel
Seat Material: Silicone
Conforms to ASME Section VIII Pressure Vessel Code
Ordering
The base selector valve can be ordered seperately for replacement purposes as identified in the following
table.
Part Number Description
02-15708-10 Selector Valve, Carbon Steel, 1 in. NPT
02-15708-15 Selector Valve, Carbon Steel, 1.5 in. NPT
02-15708-20 Selector Valve, Carbon Steel, 2 in. NPT
02-15708-30 Selector Valve, Carbon Steel, 3 in. NPT
02-15708-40* Selector Valve, Carbon Steel, 4 in. NPT
02-15709-10 Selector Valve, Stainless Steel, 1 in. NPT
02-15709-15 Selector Valve, Stainless Steel, 1.5 in. NPT
02-15709-20 Selector Valve, Stainless Steel, 2 in. NPT
02-15709-30 Selector Valve, Stainless Steel, 3 in. NPT
02-15709-40* Selector Valve, Stainless Steel, 4 in. NPT
*Selector valve is not UL Listed or FM Approved.
The assembly consists of a stainless steel faceplate with etched black text, two-
position keyed switch, and normally open and/or normally closed contact blocks. The
switch key can only be removed in the ARMED position.
The assembly can be ordered with or without status LEDs (Green – ARMED and Red
– DISARMED). The LEDs provide positive indication of the status of the releasing
Disconnect Switch with LEDs
circuit. LEDs require 24 VDC auxiliary power from the associated control panel for
operation.
NOTE: NFPA requires that a listed disconnect switch be installed on all electrically activated suppression systems to
prevent false discharges when the system is being tested or serviced. Upon activation, the switch shall cause a
supervisory signal at the control panel.
Specifications
Input Voltage 15 – 30 VDC
Current 0 mA (no LEDs) / 13.1 mA (LED active)
Circuit Limitations Class B only
Contact Ratings 8A @ 24 VDC resistive / 4A @ 24 VDC inductive
Operating Temperature 32 to 120°F (0 to 49°C)
Operating Humidity 93% RH
Weight 0.55 lb. (0.25 kg)
Dimensions (LxH) 4.50 in. x 4.5 in. (114.4 mm x 114.4 mm)
Ordering
Part Number Description
10-2698 Suppression Disconnect Switch, no LEDs
10-2699 Suppression Disconnect Switch, with LEDs
02-2153 Two-gang masonry box, 2.5 in. deep (RACO 691 or equal) used with 10-2698 switch
02-11881 Two-gang masonry box, 3 in. deep (RACO 696 or equal) used with 10-2699 switch
Spare Parts
Part Number Description Part Number Description
02-12294 Double contact block (2 NC) 02-12315 3 block switch
02-12295 Double contact block (2 NO) 02-12316 Single contact block (NC)
02-12296 Replacement keys 02-12318 Locking ring wrench
02-12298 5 block switch 10-2714 Cover plate, no LED holes
02-12300 Single contact block (NO) - -
1. Doors - All doors entering and/or existing from the perimeter of the protected space(s) should have drop seals on
the bottom, weather-stripping around the jams, latching mechanisms and door closure hardware. In addition,
double doors should have a weather-stripped astragal to prevent leakage between doors and a coordinator to
assure the proper sequence of closure. Doors that cannot be kept normally closed shall be equipped with door
closure hardware and magnetic door holders that will release the door(s) prior to system discharge.
2. Ductwork - All ductwork leading into or out of the protected space(s) should be isolated with sealed “low smoke”
dampers. Dampers should be spring loaded or motor operated to provide 100% air shutoff upon activation to
ensure an adequate seal and prevent leakage.
3. Air Handling/Ventilation - Forced air ventilation systems, others than those necessary to ensure safety, shall be shut
down or closed automatically where their continued operation would adversely affect the performance of the fire
extinguishing system or result in propagation of the fire. Self-contained air recirculation systems, if not shut down
or closed automatically, shall have the volume of the associated ductwork and components mounted below the
ceiling height of the protected space considered as part of the total hazard volume when determining the quantity
of agent.
4. Penetrations - To prevent the loss of agent through openings to adjacent hazards or work areas, openings (e.g.,
holes, cracks, gaps, pipe chases, cable trays, floor drains, etc.) shall be permanently sealed or equipped with
automatic closures. Floor drains should be equipped with traps filled with non-evaporating product to prevent
leakage.
5. Walls Construction - All perimeter walls of the protected space(s) that define the hazard should extend slab-to-slab
and each should be sealed at the top and bottom on the interior side. Where walls do not extend slab-to-slab,
bulkheads will have to be installed to achieve the desired sealing characteristics. Porous block walls must be sealed
to prevent agent leakage through the wall.
6. Pressurization – The protected enclosure(s) shall have the structural strength and integrity necessary to contain the
agent discharge. The designer shall take into consideration the pressures developed by the agent discharge into the
enclosure and determine if venting is required to prevent excessive pressures that could present a threat to the
structure strength of the enclosure.
At the discretion of the AHJ, a room integrity fan pressurization test may be required to determine how long the
protected enclosure will hold the agent after a discharge. The room integrity fan pressurization test must be performed
in accordance with the equipment manufacturer’s requirements and NFPA 2001, Annex C.
Where reasonable confinement of the agent discharge is not achievable or practical, protection shall be expanded to
include the adjacent connected hazards or work areas.
Class A Fires involving ordinary combustible materials, such as wood, cloth, paper, rubber and many plastics (i.e.,
anything that leaves an ash residue after combustion).
Class B Fires involving flammable liquids, combustible liquids, petroleum greases, tars, oils, oil-based paints,
solvents, lacquers, alcohols, and flammable gases.
If the ceiling height exceeds the maximum allowable ceiling height allowed for the nozzle selected, multiple levels of
nozzles must be designed into the system. In this case, it is usually beneficial to treat each level as a separate protected
area so that proper agent distribution is achieved.
Calculate the volume of all solid, permanent objects and add them together for each hazard area to determine the
volume that can be deducted from the total volume of the hazard area. Subtract the Solid Object Volume from the Total
Volume to determine the Reduced Volume.
Using the Hazard Classification (Class A, B or C) determined for each protected hazard, use the following table to
determine the minimum design concentration that must be used for a particular hazard.
Plug the temperature and design concentration values into the following formula to determine the minimum design
quantity of agent required for the hazard. The amount of agent in the system must always be at least this much and
may be exceeded. Failure to supply the minimum amount of agent calculated may inhibit the system from suppressing
a fire.
The minimum design quantity of agent needed can be determined using the following formula:
To determine the minimum quantity of agent required, multiply the hazard volume by the Flooding Factor determined
from the tables below. Repeat this step for each area protected by the system.
To make the necessary adjustments, first look up the altitude or pressure of the hazard in the following Altitude
Correction Factors table; then, multiply the quantity of agent required for each hazard, as determined in the previous
steps, by the Altitude Correction Factor.
NOTE: Fike’s Flow Calculation Program will automatically calculate the agent required based on the altitude correction
factor entered.
NOTE: Engineered systems can be designed with the containers arranged in a Modular or Central Storage or
Manifold configuration.
2) Modular System – Individual containers are strategically located throughout or around the protected area(s) with
each having a dedicated piping system and nozzles to distribute the clean agent supply. This arrangement keeps
the discharge piping requirements down to a minimum, but increases the electrical materials necessary to reach
each individual container location.
A modular approach is often desirable (or necessary) for larger applications to reduce the amount of piping
materials and installation labor necessary to complete the project. In some instances, this approach will be
necessary in order to make the system flow the agent required within the design guidelines identified for an
Engineered system.
3) Central Storage System – All containers are located in one location with each having a dedicated piping system
and nozzles to distribute the clean agent supply to the protected space(s) from this location. This concept often
requires more discharge piping, but it decreases the electrical materials necessary to reach the singular
container(s) location. This concept may be more difficult to design due to the increased piping runs involved and
the installation labor will tend to be more costly.
4) Selector Valve System – A single agent supply is provided to protect multiple hazards by utilizing selector valves
and dedicated piping systems to direct the flow of agent into the affected hazard area. By providing a central
agent supply sized to protect the largest hazard area, the total amount of agent required to protect multiple
hazards is reduced. All containers are located in one location and are connected together via a manifold. All
containers connected to the manifold must be the same size with the same fill density. This concept often
requires more discharge piping, but it decreases the electrical materials necessary to reach the singular
container(s) location. This concept may be more difficult to design due to the increased piping runs involved and
the installation labor will tend to be more costly. Selector Valve systems can only provide protection for a single
hazard at a time and will not be effective if more than one hazard is involved in a fire. See Section 4.3.4 for
container manifold configurations.
5) Main/Reserve System – A connected reserve agent supply is installed to provide immediate protection of the
hazard should the primary supply be discharged. The main/reserve container(s) are manifolded together with
check valves to allow either container to be removed from service without impacting the operation of the
suppression system. Main and reserve containers must be the same size with the same fill density. See Section
4.3.4 for container manifold configurations.
NOTE: The IVO shown in the diagram above can be replaced with an IEA; however, there is no strike button provided
on the IEA to permit mechanical manual activation of the container as described above. Electric manual
activation must be used to manually activate the container. System actuation using the IEA is not FM approved
as it does not provide a true mechanical means of activating the container.
NOTE: The IVO shown in the diagram above can be replaced with an IEA; however, there is no strike button provided
on the IEA to permit mechanical manual activation of the container. Electric manual activation must be used to
manually activate the container. System actuation using the IEA is not FM approved as it does not provide a
true mechanical means of activating the container.
NOTE: The IVO shown in the diagram above can be replaced with an IEA; however, there is no strike button provided
on the IEA to permit mechanical manual activation of the container as described above. Electric manual
activation must be used to manually activate the container. System actuation using the IEA is not FM approved
as it does not provide a true mechanical means of activating the container.
NOTE: The IVO shown in the diagram above can be replaced with an IEA; however, there is no strike button provided
on the IEA to permit mechanical manual activation of the container as described above. Electric manual
activation must be used to manually activate the container. System actuation using the IEA is not FM approved
as it does not provide a true mechanical means of activating the container.
NOTE: This actuation method is commonly used for system actuation in hazardous locations; however, the discharge
pressure switch cannot be installed in the hazardous location.
NOTE: The UVO shown in the diagram above that is connected to the Primary Nitrogen Actuator Assembly can be
replaced with a Universal Energetic Actuator (UEA); however, there is no strike button provided on the UEA to
permit mechanical manual activation of the containers as described above. Electric manual activation must be
used to manually activate the container. Activation of the Primary Nitrogen Actuator using the UEA is not FM
approved as it does not provide a true mechanical means of activating the system.
NOTE: This actuation method is commonly used for system actuation in hazardous locations; however, the discharge
pressure switch cannot be installed in the hazardous location
Selector Valve Activation using Primary and Secondary Nitrogen Actuator Assemblies
CAUTION: Selector valve systems can only be used to protect one hazard at a time and will not be effective if two or more
hazards are involved in a fire simultaneously.
CAUTION: When using selector valves to protect hazards with similar volumes, it is extremely important that the system
designer evaluate the final design concentration that will be reached in each hazard area served by the selector
valve system to determine the impact on exposure limitations. See Section 3.21.
1) Container(s) must be installed in area that is capable of maintaining an ambient temperature of 32-130°F (0-
54.4°C). At temperatures outside this range, the system may not supply the desired quantity of agent or may
accidentally discharge due to over-pressure. The flow calculation program predictions are based on a container
storage temperature range of 60-80°F (16-27°C).
2) The gross weight of the container must be considered when selecting the container location. The floor must be
able to support the total weight of the container(s) as they are moved into position. Excessive floor loading
may require relocating the container(s) to a more suitable location.
3) Container(s) should be located as close as possible to or within the hazard(s) that they protect in order to
reduce the length of the distribution piping. For large systems, it may be necessary to sub-divide the piping
network into small configurations with separate containers.
4) Container(s) should be located in a clean, dry, and relatively vibration free area. Avoid aisle ways and other
high traffic areas where physical damage or tampering is more likely.
5) Container(s) should not be located where they would be subject to physical damage, exposure to corrosive
chemicals, or harsh weather conditions. Container(s) should not be located where they could potentially be
splashed or submerged with any liquid.
6) Container(s) should be located where they can be easily accessed for maintenance and service.
All nozzles used for the fire suppression system using 3M™ Novec™ 1230 Fire Protection Fluid are required to discharge
the agent into the protected hazard within 6 to 10 seconds; therefore, the number of nozzles provided for any area
must be capable of delivering the flow rate required to meet this timing criteria.
Each size nozzle is capable of delivering a defined flow rate. To estimate the minimum number and size of nozzles
required for each area, divide the total quantity of agent required for the protected hazard by 10 seconds to determine
the hazards total flow rate; then, use the Nozzle Flow Rate table below to select the nozzle(s) size best suited to provide
the required flow rate. More than one nozzle may be required for each protected hazard.
If the flow rate approaches the top end of the allowable flow rate for a given size pipe, it may be in the designer’s best
interest to increase the pipe size.
NOTE: The values listed in the table are provided for estimation purposes only. The final system design MUST be
verified using Fike’s Flow Calculation Program.
NOTE: A maximum nozzle flow rate of 17 lbs/sec (7.7 kg/sec) is recommended for all areas with false ceilings or
delicate operations where a higher flow rate may dislodge objects or affect a process.
1.32 to 13.45
180° 44.91 (13.69)
(0.40 to 4.10)
1.32 to 13.45
360° 28.41 (8.66)
(0.40 to 4.10)
NOTE: Enclosure heights <1.32’ (0.4 m) shall be ½ of the nozzle area coverage.
Below Ceiling 1.0 (0.3) 1.0 (0.3) Maximum distance above highest point of
Away from Sidewall 1.0 (0.3) --- protection when stacking nozzles.
“R” 40.35 ft
(12.3 m)
“R”
40.02 ft 40.02 ft
(12.2 m) (12.2 m)
13.5' max
(4.1 m max)
1.0' max
(0.3 m max)
13.5' max
(4.1 m max)
20'-8" max
(6.3 m max)
20'-8" max
(6.3 m max) Example 3:
Systems with a
Example 1: single level of
Systems with a single level of nozzle(s) below
nozzle(s) above container outlet container outlet
20'-8" max
(6.3 m max)
NOTE: These limitations only apply to system where multiple hazards are protected by a single piping network.
Beam, Ductwork,
Cable Tray, etc.
A minimum of 2.41 feet (0.73 m) must be maintained A minimum of ten (10) pipe diameters must be
between tees for pipe sizes 2-1/2 inch (65 mm) and maintained between an elbow and a tee or a tee and
smaller. For pipe sizes 3 inch (80 mm) and larger, a an elbow.
minimum of ten (10) pipe diameters must be maintained
between tees.
The ten (10) pipe diameter rule does not apply when using back-to-back 180° nozzle configurations as long as:
1) Agent supplied and flow rate from both nozzles are the same.
2) Pipe size from tee to both nozzles is the same.
3) Pipe lengths from tee to each nozzle are within 10% of each other.
Pipe size estimations are based on the design flow rate for each pipe section. To determine the flow rate of a pipe
section, divide the amount of agent flowing through the pipe section by the discharge time (10 seconds).
Pipe Size Pipe Minimum Design Flow Rate Maximum Design Flow Rate
lbs/sec (kg/sec) lbs/sec (kg/sec)
In. NPT (mm) Schedule (System Limitation) (Estimate)
1/2 (15) 40 1.50 (0.68) 3.76 (1.71)
3/4 (20) 40 2.65 (1.21) 6.65 (3.02)
1 (25) 40 4.33 (1.96) 10.83 (4.91)
1 1/4 (32) 40 7.55 (3.42) 18.88 (8.56)
1 1/2 (40) 40 10.31 (4.68) 25.78 (11.69)
2 (50) 40 17.10 (7.76) 42.75 (19.39)
2 1/2 (65) 40 24.51 (11.12) 61.28 (27.80)
3 (80) 40 38.05 (17.26) 95.13 (43.15)
4 (100) 40 65.95 (29.91) 164.88 (74.79)
6 (150) 40 151.16 (68.57) 377.90 (171.41)
8 (200) 40 263.51 (119.53) 658.78 (298.82)
Pipe Size estimations are based on Schedule 40 pipe.
Generally, the size selection should be based on the smallest pipe size that will handle the design flow rate for the
branch lines supplying the discharge nozzles and the next to smallest for trunk lines. If the flow rate approaches the top
end of the allowable flow rate for a given pipe size, it may be necessary to increase the pipe size.
WARNING: DO NOT install the piping system based on the pipe size estimates from the chart above. The pipe system
design must be verified using Fike’s Flow Calculation Program prior to installing the system.
1) Starting from the point where the piping enters the hazard that is located farthest (hydraulically) from the agent
container(s), count the number of tees in the direct flow path as it returns to the agent container(s). Do not
include tees that are used in the manifold (if applicable). If you are not sure which hazard is farther away, count
the tees in the flow path from each hazard and use the highest number.
2) Any tee within the hazard that supplies agent to another hazard shall be included in the tee count for the hazard.
3) After determining the tee count, use the chart below to determine the Tee Design Factor.
4) Apply the Tee Design Factor to the Agent Quantity calculations by multiplying the Tee Design Factor by the
amount of agent previously determined in the volumetric calculations.
#1
#5
#4
Hazard
#3
#2
NOTE: Fike recommends increasing the design concentration to 4.7% for Class A or Class C when protecting multiple
hazards with single agent supply. This will satisfy the tee design factor requirement.
100WS
C= ----------
V + WS
Where: W= Agent Weight in lbs. (kg)
V= Hazard Volume / ft3 (m3)
C= Design Concentration, % by volume
S= Specific Vapor in ft3/lb (m3/kg)
See Flooding Factor Table on page 31 to determine the “S” value
NOTE: It is important to verify that the worst case design concentration will not exceed the limits for fire suppression
on the low end and life safety on the high end.
NOTE: Fike’s Flow Calculation Program will automatically calculate the design concentration at the maximum ambient
temperature entered.
1. When Novec 1230 fluid is used in a “Normally Occupied” area, a maximum design concentration of 10% is
allowed. Concentrations greater than 10% can only be used in “Unoccupied” areas.
2. When Novec 1230 fluid is used in a “Normally Occupied” area and is designed to concentrations up to the
NOAEL, the maximum exposure time shall not exceed 5 minutes.
3. When Novec 1230 fluid is used in a “Not Normally Occupied” area and is designed to concentrations above the
LOAEL, the following provisions shall apply:
A. Where egress takes long than 30 seconds but less than 1 minute, the agent concentration shall not exceed
its LOAEL.
B. Concentrations exceeding the LOAEL shall be permitted provided that any personnel in the area can escape
within 30 seconds.
C. A pre-discharge alarm and time delay shall be provided.
2.0 seconds
2.5 seconds
3.15 seconds
In the example above, if liquid agent takes 2 seconds to arrive at the first nozzle (the closest nozzle to the container)
after system discharge, liquid agent must arrive at the remaining nozzles within 1.15 second (3.15 seconds maximum
after system discharge).
7.0 seconds
7.9 seconds
8.5 seconds
In the example above, if liquid runout time for the first nozzle (the closest nozzle to the container) takes 7 seconds
after system discharge, the liquid runout time for the remaining nozzles must not exceed 8.5 seconds.
To account for this loss of agent flow, the layout of the piping network supplying the selector valves must be evaluated
to verify that the piping network will not allow more than 10% of the supplied agent quantity to become trapped in the
piping, regardless of which selector valve activates.
Step 1. Perform flow calculations for each hazard to determine the required pipe sizes and schedule for the pipe
network.
Step 2. Using the determined pipe size and schedule from the flow calculations, refer to the table on the following
page to determine the multiplier that must be used to calculate the maximum allowable length of pipe in feet
for each pipe size and schedule.
The following table lists the equivalent length values used by Fike’s Flow Calculation Program for various pipe fittings.
Values are based on Schedule 40 pipe.
Pipe Size Union 45° Elbow 90° Elbow Thru Tee Side Tee Check Valve
In. NPT (mm) ft. (m) ft. (m) ft. (m) ft. (m) ft. (m) ft. (m)
1/2 (15) 0.4 (0.12) 0.8 (0.24) 1.7 (0.52) 1.0 (0.30) 3.4 (1.04) ---
3/4 (20) 0.5 (0.15) 1.0 (0.30) 2.2 (0.67) 1.4 (0.43) 4.5 (1.37) ---
1 (25) 0.6 (0.18) 1.3 (0.40) 2.8 (0.85) 1.8 (0.55) 5.7 (1.74) 2.0 (0.61)
1-1/4 (32) 0.8 (0.24) 1.7 (0.52) 3.7 (1.13) 2.3 (0.70) 7.5 (2.29) ---
1-1/2 (40) 0.9 (0.27) 2.0 (0.61) 4.3 (1.31) 2.7 (0.82) 8.7 (2.65) ---
2 (50) 1.2 (0.37) 2.6 (0.79) 5.5 (1.68) 3.5 (1.07) 11.2 (3.41) 4.0 (1.22)
2-1/2 (65) 1.4 (0.43) 3.1 (0.94) 6.6 (2.01) 4.1 (1.25) 13.4 (4.08) ---
3 (80) 1.8 (0.55) 3.8 (1.16) 8.2 (2.50) 5.1 (1.55) 16.6 (5.06) 4.0 (1.22)
4 (100) 2.4 (0.73) 5.0 (1.52) 10.7 (3.26) 6.7 (2.04) 21.8 (6.64) ---
6 (150) 3.5 (1.07) 7.6 (2.32) 16.2 (4.94) 10.1 (3.08) 32.8 (10.00) ---
The following table lists equivalent length values for the container Impulse valves.
Specific installation drawings must be prepared for the hazard area in accordance with the system design as calculated
by Fike’s Flow Calculation Program. System installation shall closely follow the drawings to ensure the system meets its
design criteria. The piping network is designed to obtain correct discharge time, nozzle pressures, agent quantity and
various other design considerations. If for any reason, the pipe network requires modifications, the system must be
recalculated before proceeding with installation.
When clean agent containers are located on a raised floor, floor integrity must be considered to determine if
the type of tile and vertical floor support can handle the increased load. If necessary, additional floor supports
can be added.
To help distribute the container weight over a greater area, a 1/4 inch thick steel plate sized to span multiple
floor supports can be placed under the container(s). If the container spans multiple floor tiles, add additional
floor supports in the area where the container(s) are installed. Minimum of four floor supports, one at each
corner of floor tile, must be used. Excessive floor loading may require relocating the container(s) to a more
suitable location. See the floor loading information table below for container floor loading information.
Before mounting the container, check the container label to verify the container part number against the system
installation drawings to make sure that the correct container is being installed.
4.2.1. Mounting Detail for 5, 10, 20 and 35 lb. (2, 4, 8.5 and 15 L) Containers
Step 1. Secure the container mounting bracket to the wall or floor using suitable hardware (not supplied).
WARNING: Containers shall NOT be mounted horizontally. Mounting in the horizontal position will result in an
incomplete discharge.
Step 2. Install the container into the mounting bracket making sure that the container foot-ring is resting on the
bracket seat.
Step 3. Position the container within the mounting bracket so the pressure gauge and actuator port are easily visible
and accessible.
Step 4. Insert the top and bottom container U-bolts through the holes provided in the mounting bracket and secure
with the washers and nuts provided.
CONTAINER SIZE
DIMENSION 5 lb. (2 L) 10 lb. (4 L) 20 lb. (8.5 L) 35 lb. (15 L)
in. (mm) in. (mm) in. (mm) in. (mm)
A 12.3 (313) 12.3 (313) 16.3 (413) 16.3 (413)
B 4.0 (102) 4.0 (102) 6.9 (175) 6.9 (175)
C 5.7 (145) 5.7 (145) 7.5 (191) 7.5 (191)
D 1.4 (35) 1.4 (35) 2.0 (51) 2.0 (51)
E 4.0 (102) 4.0 (102) 6.5 (165) 6.5 (165)
F 1.0 (25) 1.0 (25) 1.0 (25) 1.0 (25)
G 2.5 (64) 2.5 (64) 3.0 (75) 3.0 (75)
H 8.0 (203) 8.0 (203) 9.7 (246) 9.7 (246)
I 1.8 (45) 1.8 (45) 3.6 (91) 3.6 (91)
J 5.0 (127) 5.0 (127) 7.5 (191) 7.5 (191)
K 3.0 (76) 3.0 (76) 5.0 (127) 5.0 (127)
L N/A N/A 2.3 (58) 2.3 (58)
All dimensions are approximate.
WARNING: Containers shall NOT be mounted horizontally. Mounting in the horizontal position will result in an
incomplete discharge.
Step 2. Install the container into the mounting bracket making sure that the container foot-ring is resting on the
bracket seat.
Step 3. Position the container within the mounting bracket so the pressure gauge and actuator port are easily visible
and accessible.
Step 4. Insert the top and bottom container U-bolts through the holes provided in the mounting bracket and secure
with the washers and nuts provided.
WARNING: Containers shall NOT be mounted horizontally. Mounting in the horizontal position will result in an
incomplete discharge.
Step 3. Position the container so the pressure gauge and actuator port are easily visible and accessible.
Step 4. Secure the mounting bracket to the wall using suitable hardware (not supplied).
Step 2. Insert the Unistrut spring nut into the channel roughly where the container mounting bracket mounting holes
will be located; then turn the nut 90° clockwise to align the grooves in the spring nut with the edges of the
channel to hold the spring nut in place.
Step 3. Install the container into position against the Unistrut in the upright (valve up) position making sure that the
pressure gauge and actuator port are easily visible and accessible.
WARNING: Containers shall NOT be mounted horizontally. Mounting in the horizontal position will result in an
incomplete discharge.
Step 4. Install the mounting bracket around the container and secure it to the Unistrut channel using the Unistrut
hex-head bolt.
CONTAINER SIZE
DIMENSION 100 lb. (44 L) 215 lb. (88 L) 375 lb. (153 L) 650 lb. (267 L) 1000 lb. (423 L)
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
A 1.50 (38.1) 2.00 (51.0) 2.00 (51.0) 2.00 (51.0) 2.00 (51.0)
B 13.26 (336.8) 23.00 (584.2) 23.00 (584.2) 27.38 (696.5) 27.38 (696.5)
C 12.25 (311.2) 21.74 (522.2) 21.74 (522.2) 26.12 (663.5) 26.12 (663.5)
D 5.50 (139.7) 10.00 (254.0) 10.00 (254.0) 12.19 (309.6) 12.19 (309.6)
E 11.00 (279.8) 20.42 (518.7) 20.42 (518.7) 24.00 (610.0) 24.00 (610.0)
F 1.13 (28.7) 1.50 (38.1) 1.50 (38.1) 1.50 (38.1) 1.50 (38.1)
G 20.00 (508.0) 11.00 (279.0) 24.00 (609.6) 28.00 (711.0) 40.00 (1016.0)
All dimensions are approximate.
NOTE: For additional information on pressure rating of pipe and fittings, plus recommended pipe supports and hangers,
refer to FSSA’s Pipe Design Handbook, FSSA PDH-01.
CAUTION: Cast iron pipe, steel pipe conforming to ASTM A120, or nonmetallic pipe shall not be used.
Fitting materials must conform to the requirements outlined in NFPA 2001. Fitting sizes up to and including six inch NPT
shall be Class 300 malleable or ductile iron. Fittings over six inch NPT shall be Class 300 flanged fitting.
All grooved fittings must be UL Listed and conform to the pressure requirements outlined in NFPA 2001, latest edition.
Cast iron or Class 150 fittings shall not be used.
NOTE: The General Piping Requirements outlined in Section 4.3.3 must be adhered to when constructing manifolds.
NOTE: Refer to FSSA Pipe Design Guide (PDH-01) for addition guidance on pipe hangers and supports.
General Guidelines:
Pipe hangers and supports shall be installed in accordance with recognized industry practices and
manufacturer’s instructions.
All pipe hangers and supports shall be attached directly to a rigid fixed structure.
All hangers and components shall be steel.
Ordinary cast-iron hangers/supports, conduit clamps, or “C” clamps shall not be used.
Rigid hangers shall be installed wherever a change in elevation or direction occurs.
Nozzles shall be supported so as to prevent movement of the nozzle of the nozzle during discharge.
Where seismic bracing is required, bracing shall be in accordance with local codes and the AHJ.
All pipe supports shall be designed and installed to prevent lateral movement of supported pipe during
system discharge while permitting longitudinal movement to accommodate expansion and contraction
caused by temperature changes.
Pipe hangers must be spaced according to the size of pipe as indicated in the following table.
Maximum Distance
Pipe Size Rod Diameter
Between Supports
in. (mm) in. (mm)
ft. (m)
1/2 (15) 7 (2.1) 3/8 (9.5)
3/4 (20) 7 (2.1) 3/8 (9.5)
1 (25) 7 (2.1) 3/8 (9.5)
1 1/4 (32) 7 (2.1) 3/8 (9.5)
1 1/2 (40) 9 (2.7) 3/8 (9.5)
2 (50) 10 (3.0) 3/8 (9.5)
2 1/2 (65) 11 (3.4) 1/2 (12.7)
3 (80) 12 (3.7) 1/2 (12.7)
4 (100) 14 (4.3) 5/8 (15.9)
6 (150) 17 (5.2) 3/4 (19.0)
Hangers must be placed within 12 in. (300 mm) of each discharge nozzle and between elbows that are more
than 24 in. (600 mm) apart.
Step 5. Remove plug from item 3A. Retain for future use.
Step 6. Screw the items assembled in Step 4 into the threaded port on item 3A. Secure wrench tight. Orient the
assembly so the side outlet of item 3D is positioned horizontally.
Step 7. Screw item 3E into the side outlet of item 3D. Secure wrench tight.
Step 10. Connect one end of item 3J to item 3H. Secure wrench tight.
Step 11. Connect the other end of item 3J to the JIC fitting on the selector valve. Secure wrench tight.
Step 12. Check to ensure that item 3A is armed (firing pin retracted).
CAUTION: Do NOT install the actuator to the nitrogen actuator with the firing pin extended as this may cause
accidental discharge.
Step 13. Connect item 3A wire leads to the host control panel or module. See 4.7.6.1.
Step 14. Connect item 3B wire leads to the host control panel or module. See 4.7.9.1.
Step 15. Remove the retaining clip and valve plug from item 2. Keep these items for future use should the container
have to be removed for service.
Step 16. Connect item 3A to item 2 and secure in place with item 3B. See 4.7.9.
CAUTION: Installation of the system actuation components should be the last item completed before the system is
placed into service.
Item
Part Number Description Notes
No.
02-15708-XX Carbon Steel Selector Valve1
1
02-15709-XX Stainless Steel Selector Valve1
2 70-325-X Nitrogen Actuator Assembly
02-13571 Universal Valve Operator (UVO)
3A
IG71-247 Universal Energetic Actuator (UEA)
3B 02-14627 Universal Valve Operator Supervisor (UVOS)
Part of 70-396 Selector Valve
3C 02-13640 1/8 in. NPT x 1/4 in. NPT Adapter Assembly
3D C02-1335 1/4 in. NPT Street Tee
3E 02-11766 1/4 in. NPT x G1/4 Adapter
3F 02-10926 1/4 in. Sealing Washer
3G IG71-026 Vent Valve Assembly
3H 02-4530 1/4 in. NPT x 1/4 in. JIC Adapter
3J 02-4977 1/4 in. JIC x 1/4 in. JIC Hose, 35 in. (889 mm) Long
1
Valve material supplied is based on selector valve assembly part number.
Step 2. Install item 2 (secondary nitrogen actuator) in close proximity to the selector valve to allow connection of item
3C. See Section 4.7.5 for installation instructions.
Step 3. Apply PTFE tape to the NPT male threads of items 3B, 3E, 4C, 4D, 4E and 4G. Do NOT allow tape to overlap the
end of the fitting as this could cause possible blockage of the pressure port.
Step 4. Assemble items 3D, 3E, 3F, 3G and 3H together. Wrench tight.
Step 5. Connect items assembled in Step 4 to the JIC connector on the selector valve. Secure wrench tight.
Step 6. Remove the plug from item 3A. Retain for future use.
Step 7. Screw item 3B into the threaded port. Secure wrench tight.
Step 8. Install item 2 (primary nitrogen actuator) at the location indicated on the installation drawings. See Section
4.7.5 for installation instructions.
Step 9. Assemble item 4C, item 4D and item 4E together. Secure wrench tight.
Step 11. Screw the items assembled in Step 9 into the threaded port on item 4A. Secure wrench tight. Orient the
assembly so the side outlet of item 4D is positioned horizontally.
Step 12. Screw item 4G into the side outlet of item 4D. Secure wrench tight.
Step 14. Screw item 4J onto item 4G. Secure wrench tight.
Step 15. Install the pilot line components items 5, 6 and 7. Apply PTFE tape to all NPT male threads. Do NOT allow tape
to overlap the end of the fitting as this could cause possible blockage of the pressure port. The pilot line
between the primary and secondary nitrogen actuator shall not exceed a maximum length of 150 ft. (45 m)
including hoses. Secure all connections wrench tight.
Step 16. Connect one end of item 4F to item 4E. Secure wrench tight.
Step 17. Connect the other end of item 4F to the pilot line item 5. Secure wrench tight.
Step 18. Connect the G1/4 end of item 8 to item 3A. Secure wrench tight.
Step 19. Connect the other end of item 8 to the pilot line item 5. Secure wrench tight.
Step 20. Check to ensure that items 3A and 4A are armed (firing pin retracted).
CAUTION: Do NOT install the actuator to the nitrogen actuator with the firing pin extended as this may cause
accidental discharge.
Step 22. Connect item 4B wire leads to the host control panel or module. See 4.7.9.1.
Step 23. Remove the retaining clip and plug from the Primary nitrogen actuator assembly. Keep these items for future
use should the container have to be removed for service.
Step 24. Connect item 4A to item 2 (primary nitrogen actuator) and secure in place with item 4B. See 4.7.9.
Step 25. Remove the retaining clip and plug from item 2 (secondary nitrogen actuator).
Step 26. Insert item 3A into the nitrogen actuator valve and secure in place with the retaining clip removed in Step 25.
Selector Valve Activation with Primary and Secondary Nitrogen Actuator Assembly
See next page for description of the numerical callouts shown in the diagram above.
NOTE: Primary nitrogen actuator and pilot line components shown above are not included in the selector valve
assembly and must be purchased separately.
Each impulse valve is equipped with a groove connection on the outlet. Piping systems with a groove connection can be
attached directly to the impulse valve.
When using a discharge pressure switch or secondary container activation, there are two adapter nipple options
available; groove to groove and groove to thread. The adapter nipple is equipped with a 1/4 inch NPT female hub that
provides a connection point for these options. See following figures.
Baffle Plate
1” Grooved Coupling
Impulse Valve
Container
3” Adapter Nipple
(P/N 70-2163)
Baffle Plate
3” Grooved Coupling
Impulse Valve
Container
Step 1. Lubricate the LPS O-Ring with Molykote 55 or equivalent. Use care not to get lubricant into the end of the
switch. Do NOT apply PTFE tape to LPS threads.
Step 2. Remove plug from valve fill port and retain for future use.
Step 3. Remove the rubber cap from the LPS and screw it into the fill valve port until the switch bottoms out (hand
tight). Do NOT cross thread the LPS during installation. Switch installation will open the ports internal check
valve allowing internal container pressure to reach the switch.
Step 4. Use leak test fluid to leak check around the pressure gauge port. If a leak is detected, remove the LPS from
the fill port and remove the lubricant and contaminants from the O-Ring, threads, and valve port using
isopropyl alcohol and a soft clean cloth. Lubricate the O-Ring with Molykote 55 or equivalent and reinstall.
Leak test around the fill port. If a leak is still detected, remove the LPS from the fill port, remove and replace
the O-Ring, lubricate the O-Ring with Molykote 55 or equivalent, install the LPS in the fill port and leak test
around the fill port.
Step 5. Connect conduit connector to the low pressure switch. Secure hand tight only. Over tightening may cause
damage to the switch or to the fill port threads.
Step 6. Connect the low pressure switch wire leads to a supervisory input on the host control panel. See wiring
diagram below. Refer to control panel manual for specific wiring criteria.
Fill Port
Step 1. Remove the rubber cap from the discharge pressure switch and apply PTFE tape to the male threads of the
switch.
Step 3. Thread the discharge pressure switch into the ¼” NPT port on adaptor nipple (wrench tight). Only use the
wrench on the brass hex flats.
Step 4. Connect conduit connector to the discharge pressure switch. Secure hand tight only. Over tightening may
cause damage to the switch or to the adapter nipple pressure port.
Step 5. Connect the discharge pressure switch wire leads to a manual release input on the host control panel. See
wiring diagram below. Refer to control panel manual for specific wiring criteria.
Discharge
Pressure Switch
Adapter Nipple
Impulse Valve
Discharge Outlet
Compare the part number that is stamped on the closed end of the nozzle to be installed with the nozzle part
number listed on the system installation plans. It is extremely important that the nozzle part numbers match in
order to ensure that proper agent design quantities and concentrations are achieved.
Verify that there are no obstructions located in the nozzles discharge path that could obstruct the distribution of
the agent during discharge.
Verify that the position of each discharge nozzle is located within 1 ft. (0.3 m) of its intended location as indicated
on the system installation plans.
Verify that piping discharge nozzles are properly braced to prevent movement during discharge. 180° nozzles
require back bracing.
Verify that the distribution piping network has been blown clear to remove chips, mill scale, or metal shavings, and
has been cleaned to remove dirt and cutting oil before installing nozzles.
Verify that discharge nozzles are mounted in a vertical position, facing either up or down, as depicted in the
following diagrams.
Ceiling Mount
Subfloor Mount
Step 1. Apply PTFE tape or joint compound to the male threads of the distribution piping. Do NOT allow tape to
overlap the pipe opening as this could cause possible blockage of the nozzle.
Step 2. Thread the nozzle onto the pipe. Secure wrench tight.
Step 3. If installing 180° discharge nozzles, verify that the nozzle orifice holes are correctly orientated to allow proper
agent discharge.
CAUTION: Do NOT install the IVO to the container with the firing pin extended as this may cause accidental
discharge.
Step 2. Install conduit (rigid or flexible) from the Impulse Release Module (IRM) electrical box to the IVO. The IVO is
equipped with ½” NPT female threads for conduit connection.
Step 4. Connect the IVO wire leads to the IRM. See 4.7.1.1.
Step 5. Remove the plug from the container’s actuator port. Keep for future use should the container have to be
removed for service.
Step 6. Insert the IVO into the actuator port and secure in place with the IVOS retaining clip. See 4.7.4.
Impulse Valve
Operator
Actuator Port
Supervisor (IVOS)
Impulse Valve
Operator (IVO)
Disarmed Armed
See Section 3.10 for specific details on the various system activation methods using the IVO.
CAUTION: Do NOT install the IEA to the container with the firing pin extended as this indicates that the IEA has been
activated and must be replaced. Installing the IEA with the firing pin extended may cause accidental
discharge.
Step 2. Install conduit (rigid or flexible) from the Impulse Release Module (IRM) electrical box to the IEA. The IEA
adapter body provides a connection point for ½” rigid conduit compression fitting.
Step 4. Connect the IEA wire leads to the IRM. See 4.7.2.1.
Step 5. Remove the retaining clip and plug from the container’s actuator port. Keep these items for future use should
the container have to be removed for service.
Step 6. Insert the IEA into the actuator port and secure in place with the IVOS retaining clip. See Section 4.7.4.
Impulse Valve
Operator
Actuator Port
Supervisor (IVOS)
Impulse Energetic
Actuator (IEA)
Disarmed Armed
NOTE: An IVOS must be installed to supervise the connection of the IEA to each container.
See Section 3.10 for specific details on the various system activation methods using the IEA.
CAUTION: Do NOT install the IVPO to the container with the firing pin extended as this may cause accidental
discharge.
Step 2. Apply PTFE tape to the male threads of the adapter. Do NOT allow tape to overlap the end of the adapter as
this could cause possible blockage of the pressure port.
Step 3. Screw the R1/8 x ¼ JIC adapter into the threaded port on the IVPO. Secure wrench tight.
Step 4. Screw one end of the pilot line hose supplied with the IVPO to the ¼ JIC end of the adapter installed in Step 3.
Secure wrench tight.
Step 5. Connect the other end of the pilot line hose to the pilot line tubing from the previous container or nitrogen
actuator assembly. See Section 3.10 for specific details on the various system activation methods using the
IVPO.
Step 6. Remove the retaining clip and plug from the container’s actuator port. Keep the plug for future use should
the container have to be removed for service.
Step 7. Insert the IVPO into the actuator port and secure in place with the IVOS retaining clip. See Section 4.7.4.
1/8” x ¼” JIC
Adapter
Disarmed Armed
NOTE: An IVOS must be installed to supervise the connection of the IVPO to each container.
Step 2. Connect the IVOS wire leads to a “Supervisory” input on a Fike releasing panel. See 4.7.4.1.
Step 3. Install the actuator (IVO, IEA or IVPO) into the valve actuator port.
Step 4. Position the IVOS so the retaining pins are facing the valve, as shown below.
Step 5. Align the IVOS retaining pins with the holes provided in the valve actuator port.
Step 6. Gently squeeze the IVOS retaining pins together and insert them into the holes provided in the actuator port
body until the IVOS is fully seated.
Step 7. Verify that the IVOS pushbutton switch is fully depressed and that the actuator is securely held in place.
Actuator Port
Impulse Actuator
Impulse Valve
Operator
Supervisor (IVOS)
Step 1. Use the Nitrogen Actuator Assembly mounting bracket as a template to mark and drill the mounting holes.
NOTE: When using a Universal Valve Operator (UVO) with manual strike button to activate the Nitrogen Actuator
Assembly, the UVO strike button shall NOT be located greater than 4 ft. (1.2 m) above the floor.
Step 2. Secure the Nitrogen Actuator Assembly to the mounting surface using suitable anchors, provided by others.
Step 3. Attach the chosen actuator (UVO, UEA or Pneumatic Relay) to the Nitrogen Actuator Assembly valve following
the steps indicated in Sections 4.7.6, 4.7.7, and 4.7.8.
See Section 3.10 for specific details on the various system activation methods using the Nitrogen Actuator Assembly.
Step 2. Assemble item 7, item 8, and item 12 together. Secure wrench tight.
Step 4. Screw the items assembled in Step 2 into the threaded port on item 4. Secure wrench tight. Orient the assembly
so the side outlet of item 8 is positioned horizontally.
Step 5. Screw item 9 into the side outlet of item 8. Secure wrench tight.
Step 8. Connect one end of item 13 to item 12. Secure wrench tight.
Step 9. Connect the other end of item 13 to the pilot line tubing (not shown). Secure wrench tight.
Step 10. Check to ensure that item 4 is armed (firing pin retracted).
CAUTION: Do NOT install the UVO to the container with the firing pin extended as this may cause accidental
discharge.
Step 11. Connect item 4 wire leads to the host control panel or module. See 4.7.6.1.
Step 12. Connect item 6 wire leads to the host control panel or module. See 4.7.9.1.
Step 13. Remove item 2 and item 3 from item 1. Keep these items for future use should the container have to be
removed for service.
Step 14. Connect item 4 to item 1 and secure in place with item 6. See 4.7.9.
CAUTION: Installation of the system actuation components should be the last item completed before the system is
placed into service.
Item Part
Description Notes
No. Number
1 70-325-X Nitrogen Actuator Assembly
Part of 70-325 Nitrogen Actuator
2 02-11755 Retaining Clip
Assembly
3 IG71-0151 Valve Fill Adapter Plug
4 02-13571 Universal Valve Operator (UVO)
5 02-14053 Pipe Plug
6 02-14627 Universal Valve Operator Supervisory (UVOS)
7 02-13640 1/8 in. NPT x 1/4 in. NPT Adapter
8 C02-1335 1/4 in. Street Tee
Part of 70-335 Primary Completer Kit
9 02-11766 1/4 in. NPT x G1/4 Adapter
10 02-10926 1/4 in. Sealing Washer
11 IG71-026 Vent Valve Assembly
12 02-4530 1/4 in. NPT x 1/4 in. JIC Adaptor
13 02-4977 1/4 in. JIC x 36 in. (0.9 m) Long Actuation
Step 2. Assemble item 7, item 8, and item 12 together. Secure wrench tight.
Step 4. Screw the items assembled in Step 2 into the threaded port on item 4. Secure wrench tight. Orient the
assembly so the side outlet of item 8 is positioned horizontally.
Step 5. Screw item 9 into the side outlet of item 8. Secure wrench tight.
Step 8. Connect one end of item 13 to item 12. Secure wrench tight.
Step 9. Connect the other end of item 13 to the pilot line tubing (not shown). Secure wrench tight.
Step 10. Check to ensure that item 4 is armed (firing pin retracted).
CAUTION: Do NOT install the UEA to the container with the firing pin extended as this may cause accidental
discharge.
Step 11. Connect item 4 wire leads to the host control panel or module. See 4.7.7.1.
Step 12. Connect item 6 wire leads to the host control panel or module. See 4.7.9.1.
Step 13. Remove item 2 and item 3 from item 1. Keep these items for future use should the container have to be
removed for service.
Step 14. Connect item 4 to item 1 and secure in place with item 6. See 4.7.9.
CAUTION: Installation of the system actuation components should be the last item completed before the system is
placed into service.
Item Part
Description Notes
No. Number
1 70-325-X Nitrogen Actuator Assembly
Part of 70-325 Nitrogen Actuator
2 02-11755 Retaining Clip
Assembly
3 IG71-0151 Valve Fill Adapter Plug
4 IG71-247 Universal Energetic Actuator (UEA)
5 02-14053 Pipe Plug
6 02-14627 Universal Valve Operator Supervisory (UVOS)
7 02-13640 1/8 in. NPT x 1/4 in. NPT Adapter
8 C02-1335 1/4 in. Street Tee
9 02-11766 1/4 in. NPT x G1/4 Adapter Part of 70-400 Primary Completer Kit
10 02-10926 1/4 in. Sealing Washer
11 IG71-026 Vent Valve Assembly
12 02-4530 1/4 in. NPT x 1/4 in. JIC Adaptor
13 02-4977 1/4 in. JIC x 36 in. (0.9 m) Long Actuation Hose
14 10-2748 Impulse Releasing Module (IRM), not shown
Step 3. Connect the other end of item 3 to the pilot line tubing (not shown). Secure wrench tight.
CAUTION: Do NOT install the pneumatic relay to the container with the firing pin extended as this may cause
accidental discharge.
Step 5. Remove item 1C and item 1B from item 1A. Keep these items for future use should the container have to be
removed for service.
Step 6. Connect item 2A to item 1A and secure in place with item 1C.
CAUTION: Installation of the system actuation components should be the last item completed before the system is
placed into service.
Step 7. Connect free end of item 2C to the pilot line, IVPO or selector valve. Secure wrench tight.
Step 8. Install pilot line vent components (items 5 thru 8) as shown in Section 4.3.6.2 or 4.8.4.
Item Part
Description Notes
No. Number
1A 70-325-X Nitrogen Actuator Assembly
Part of 70-325 Nitrogen Actuator
1B IG71-0151 Valve Fill Adapter Plug
Assembly
1C 02-11755 Retaining Clip
2A 70-334 Pneumatic Relay Assembly
Part of 70-334 Pneumatic Relay
2B 02-11243 R1/8 in. x 1/4 in. JIC Hex Nipple
Assembly
2C 02-4977 1/4 in. JIC x 36 in. (0.9 m) Long Actuation
G1/4 x 1/4 in. JIC x 39 in (1 m) Long Actuation Ordered separately
3 02-10801
Hose
4 02-14721 1/4 in. JIC x 1/4 in. FNPT Branch Tee
5 02-11346 1/4 in. JIC Coupling, Swivel
6 02-11766 1/4 in. NPT x G1/4 Adapter
7 02-10926 1/4 in. Sealing Washer
8 IG71-026 Vent Valve Assembly
Step 2. Connect the UVOS wire leads to a “Supervisory” input on a Fike releasing panel. See 4.7.9.1.
Step 3. Install the actuator (UVO, UEA or Pneumatic Relay) into the valve actuator port.
Step 4. Position the UVOS so the retaining pins are facing the brass valve, as shown below.
Step 5. Align the UVOS retaining pins with the holes provided in the valve actuator port.
Step 6. Gently squeeze the UVOS retaining pins together and insert them into the holes provided in the actuator port
body until the UVOS is fully seated.
Step 7. Verify that the UVOS pushbutton switch is fully depressed and that the actuator is securely held in place.
Universal Valve
Operator
Retaining Pins
Facing Container
Valve
Impulse Valve
Operator
Supervisor (IVOS) Retaining Clip
Plug
Nitrogen Actuator
Step 2. Assemble items as shown in the diagram below. Secure wrench tight.
Step 3. Remove 1/4” NPT plug from the primary container’s adapter nipple and thread item 5 into port. Secure
wrench tight.
Step 4. Connect system actuation components (IVO, IEA, IVPO) to the containers. See Section 4.7 for details.
Item
Part Number Description Notes
No.
1A 02-12728 Impulse Valve Operator (IVO)* Part of 70-279 Kit
1B 70-374 Impulse Energetic Actuator (IEA) Part of 70-390 Kit
2 02-12729 Impulse Valve Pneumatic Operator (IVPO)
2A 02-4535 1/8 in. NPT x 1/4 in. JIC Adaptor Part of 70-280 IVPO Kit
2B 02-4977 1/4 in. JIC x 36 in. (0.9 m) Long Actuation Hose
3 02-12926 1/4 in. JIC Male Adaptor
4 02-4977 1/4 in. JIC x 36 in. (0.9 m) Long Actuation Hose
5 02-4530 1/4 in. NPT x 1/4 in. JIC Adaptor
* The IVO shown can be replaced with a IEA (Item 1B); however, there is no strike button provided on the IEA to permit mechanical manual
activation of the container. Electric manual activation must be used to manually activate the container.
Step 2. Apply PTFE tape or thread sealant to all items (parts) equipped male NPT threads. Do NOT allow tape or
sealant to overlap end of fitting.
Step 3. Assemble items as shown in the diagram below. Secure wrench tight.
Step 4. Remove ¼” NPT plug from the primary container’s adapter nipple and thread item 9 into port. Secure wrench
tight.
Step 5. Connect system actuation components (IVO, IEA, IVPO) to the containers. See Section 4.7 for details.
Item
Part Number Description Notes
No.
1A 02-12728 Impulse Valve Operator (IVO)* Part of 70-279 Kit
1B 70-374 Impulse Energetic Actuator (IEA) Part of 70-390 Kit
2 02-12729 Impulse Valve Pneumatic Operator (IVPO)
2A 02-4535 1/8 in. NPT x 1/4 in. JIC Adaptor Part of 70-280 IVPO Kit
2B 02-4977 1/4 in. JIC x 36 in. (0.9 m) Long Actuation Hose
3 C02-1356 1/4 in. Male JIC x 1/4 in. Male Tube Adaptor
4 02-12696 1/4 in. Tube 90° Elbow
5 N/A 1/4 in. x 0.035 in. Wall, Stainless Steel Tubing Supplied by others
6 C02-1359 1/4 in. Tube Tee
7 02-12695 1/4 in. Tube x 1/4 in. JIC Adaptor
8 02-4977 1/4 in. JIC x 36 in. (0.9 m) Long Actuation Hose
9 02-4530 1/4 in. NPT x 1/4 in. JIC Adaptor
* The IVO shown can be replaced with a IEA (Item 1B); however, there is no strike button provided on the IEA to permit mechanical manual
activation of the container. Electric manual activation must be used to manually activate the container.
Step 2. Install pneumatic tubing between the containers and the nitrogen actuator. See pilot line limitations below.
Terminate tubing within 2 feet (0.61 m) of the container valve and nitrogen actuator.
Step 3. Apply PTFE tape or thread sealant to all items (parts) equipped male NPT threads. Do NOT allow tape or sealant
to overlap end of fitting.
Step 4. Assemble items as shown in the diagram below. Secure wrench tight.
Step 5. Install the UVO or UEA primary completer kit to the nitrogen actuator. See Sections 4.7.6 or 4.7.7 for installation
instructions.
Step 6. Connect IVPO to the containers. See Section 4.7 for details.
See next page for a description of numerical callouts shown in the diagram above.
Step 2. Install pneumatic tubing between the containers and the nitrogen actuators. See pilot line limitations below.
Terminate tubing within 2 feet (0.61 m) of the container valve and nitrogen actuators.
Step 3. Apply PTFE tape or thread sealant to all items (parts) equipped male NPT threads. Do NOT allow tape or
sealant to overlap end of fitting.
Step 5. Install the UVO, UEA or relay actuator completer kit to the nitrogen actuator. See Sections 4.7.6, 4.7.7 or 4.7.8
for installation instructions.
Step 6. Connect IVPO to the containers. See Section 4.7 for details.
If the system is connected to an alarm receiving office, notify the alarm receiving office that a fire system test is to be
conducted and that emergency response by the fire department or alarm station personnel is not required. Notify all
personnel in the areas that could be affected by the testing that a test is to be conducted and instruct them as to the
events that could occur during the test.
CAUTION: The releasing mechanism on each storage container or nitrogen actuator must be disconnected from the
container prior to conducting the acceptance test in order to prevent activation of the suppression system
during testing.
Enclosure Checks
____ 1. Check the hazard area dimensions against those shown on the system plan(s). If the area volume has
changed, the agent weight should be recalculated and compared with the agent weight supplied.
____ 2. Check the hazard area for walls or movable partitions that may have been added or changed. If walls or
partitions have been added, check to see that all areas within the hazard still receive adequate nozzle
coverage and agent distribution.
____ 3. Thoroughly examine the enclosure to verify that it has been properly constructed and sealed to eliminate
any significant air leaks that could result in failure of the enclosure to hold the agent concentration.
____ 4. Perform an Enclosure Integrity Test on all protected enclosures. A Door Fan Test is the accepted method
to estimate worst-case room leakage and agent (concentration) hold time. Refer to NFPA Standard 2001,
latest edition for additional information and door fan test procedures.
Mechanical Checks
____ 1. Inspect the piping distribution system(s) to verify that it has been installed in compliance with the design
drawings. Nozzle locations, nozzle orientation, pipe sizes, pipe size reductions and orientation of tees
shall be checked against the design drawings. If piping system as installed differs from the design
drawings, the system MUST be recalculated to reflect the piping system as installed.
____ 2. Visually inspect all components for signs of damage (i.e., corrosion, dents, twisted, etc.).
____ 3. Check that all agent storage containers are properly located in accordance with the design drawings
____ 4. Check that all agent storage containers are securely fastened with supplied brackets.
____ 5. Check that all piping joints, discharge nozzles, and piping supports are securely fastened to prevent
unacceptable vertical or lateral movement during discharge.
____ 6. Check that all warning and instruction signs are mounted where required.
Pneumatic Checks
Where pneumatic system actuation components are used (i.e., IVPO, Nitrogen Actuator Assembly), the following
pneumatic checks should be made:
____ 1. Remove all Impulse Valve Pneumatic Operators (IVPO) from container valves.
____ 2. Disconnect actuation hose from the master container valve or Nitrogen Actuator Assembly.
____ 3. Provide 100 psi (6.9 bar) pressure to the disconnected actuation hose.
____ 4. Verify all IVPOs are in the fired (piston extended) position. Reset IVPO(s) upon completion of testing.
Electrical Checks
The information contained in this document does not cover service and maintenance procedures for the Detection and
Control System (electrical portion). The electrical portion of the system must be thoroughly checked out according to
the manufacturer's recommendations and the requirements of the AHJ.
IMPORTANT NOTE: Do not arm the Fike Clean Agent Fire Suppression system before the Detection and Control
System has been checked out and all circuits are free of trouble and ground fault conditions. If
control panel checks out, install the releasing mechanism to the container(s).
The results of the system checkout shall be documented in a test report. The test report shall be maintained by the
system owner for the life of the suppression system.
CAUTION: The releasing mechanism on each storage container must be disconnected from the container prior to
conducting the acceptance test in order to prevent activation of the suppression system container during
testing.
Monthly Inspection
____ 1. Check that the releasing panel is powered and is free of supervisory, trouble, or alarm conditions.
____ 2. Check that all manual controls (i.e., manual release, abort, pneumatic actuators, etc.) are unobstructed.
____ 3. Check that the system components show no signs of physical damage, corrosion or a condition that could
prevent operation.
____ 4. Check all piping supports to make sure they are tight and all piping is properly supported.
____ 5. Check all nozzle orifices for signs of corrosion.
____ 6. Check all nozzles to make certain there are no obstructions that could block the discharge of agent from
the nozzles.
____ 7. Check the container gauge to confirm container pressure is in operable range. Pressure should read 500
PSIG at 70°F (34.5 BAR at 21°C). In the range of 50°F to 80°F (10°C to 27°C), the difference is approximately
2 PSIG (15 kPa) per degree. For temperatures other than 70°F (21°C), reference Temperature vs. Pressure
Chart on Page 9. If the pressure loss indicated exceeds 10% of the nominal pressure, check the container
for leaks and repair as necessary.
____ 8. Check that the protected equipment or hazard area has not been changed or modified.
____ 9. Check that all penetrations made through the protected enclosure are properly sealed. Any new
penetration shall be sealed immediately maintaining the original fire resistance rating of the enclosure.
____ 10. Verify that any previously noted deficiencies have been corrected.
If any deficiencies are found, appropriate corrective action shall be taken immediately. When the corrective action
involves maintenance or repair, it shall be conducted by a qualified fire protection service technician.
____ 1. Verify the amount of agent in the container(s) matches the agent weight stamped on the container label,
by either weighing the container or by using the container’s Liquid Level Indictor (LLi), if installed. This
information should be recorded and affixed to the container so it can be used during container
maintenance. If the weight indicates a shortage exceeding 5% of required weight, the container must be
removed from service for repair and/or recharge.
If any deficiencies are found, appropriate corrective action shall be taken immediately. When the corrective action
involves maintenance or repair, it shall be conducted by a qualified fire protection service technician.
____ 1. Perform a complete external visual inspection of each container in accordance with the Code of Federal
Regulations, Title 49 and Compressed Gas Association (CGA) Pamphlet C-6, Section 3. The container does
not need to be emptied or stamped while under pressure for this inspection. The inspection shall be
performed by a CGA/DOT approved inspector only.
Where the external visual inspection indicates that the container has been damaged, addition strength
tests shall be required.
____ 2. All hoses shall be detached from the system and a hydrostatic pressure test shall be performed in
accordance with NFPA 2001, latest edition. Hoses failing the test must be marked and destroyed and
replaced. Hoses passing the test shall be marked to show the date of test prior to reinstallation.
If any deficiencies are found, appropriate corrective action shall be taken immediately. When the corrective action
involves maintenance or repair, it shall be conducted by a qualified fire protection service technician.
For system recharge, contact you system installer or Fike’s Customer Service Department at +001-816-229-3405.
CAUTION: Under no circumstances should personnel, other than a Fike Authorized Service Representative, attempt to
disarm and remove a container for recharge.
IMPORTANT NOTE: This procedure only applies to the 3 inch check valves that have opened due to agent pressure.
Dampers DO NOT need to be replaced in 1 inch and 2 inch check valves.
1. Disconnect the valve operator from the Impulse Valve actuator port by removing the operator supervisor (IVOS or
UVOS) or retaining clip that secures the operator in place.
2. Remove the Safety Cotter Pin and pull the Manual Strike Button until a slight click is heard when the internal
components are realigned. This step does not apply to the IVPO.
Pin Extended
(Fired Position)
Operator
Pull Knob
Safety Pin
3. Align the forked end of the anvil handle around the grooved end of the Operator tip.
4. Squeeze reset tool handles until Operator Pin resets (clicks into place); then, reinsert the Safety Pin. The operator is reset and
ready to be installed.
Pin Reset
(Armed Position)
Operator
Squeeze
Safety Pin
1. Disconnect the valve operator from the Impulse Valve actuator port by removing the operator supervisor (IVOS or
UVOS) or retaining clip that secures the operator in place.
2. Remove the Safety Cotter Pin and pull the Manual Strike Button until the operator resets (clicks into place). This
step does not apply to the IVPO.
3. Insert the valve operator (IVO or UVO) into the end of the Reset Tool and secure in place with the retaining clip
provided.
Reset Tool
Retaining Clip
4. With the Reset Tool resting firmly against a hard surface, push on the valve operator until the firing pin resets (clicks
into place).
Reset Tool
Hard Surface
Retaining Clip
5. Reinsert the Safety Cotter Pin; then remove the Retaining Clip and the Reset Tool. The operator is reset and ready
to be installed.
No Pin Exposed
Step 2. Pull the ring up to open the valve to allow any stored pressure in the selector valve actuator or pneumatic
actuation line to be released.
Step 3. Using a wrench, turn the actuator pinion clockwise (CW) to close the ball valve.
NOTE: This procedure must be performed for each activated selector valve.
Step 7. Check the assembly for leaks using a suitable leak test device.
Refer to Recharge Manual P/N 06-852 for recommendations and leak test procedures.
HAZARD INFORMATION
Design Concentration: 4.5% (Minimum)
Temperature Range: 70° F. to 85° F.
Enclosure Elevation: 0 Feet (Sea Level)
Room Height: 8.0'
Uncloseable Openings: None
No. of Nozzles:
- Control Room: 2 - 360° Nozzles
- Office / Storage Room: 1 - 180° Nozzles
15.0’ 40.0’
10.0’
20.0’
Proposed Container
Control Room
Floor Plan
1) SETUP SCREEN FOR SELECTING UNITS OF MEASURE, TEMPERATURE AND DISCHARGE TIME
2) PROJECT INFORMATION SCREEN FOR SETTING UP CONTACT INFORMATION, JOB NAME, ETC.
Proposed Container
Control Room
8) USE THE “PIPE”, “ELBOW” AND “TEE” ICONS TO LAYOUT THE PIPE NETWORK
10) USE THE “TABLE” SCREEN TO PREPARE TO RUN THE FLOW CALCULATION BY AUTOMATICALLY POPULATING THE
INPUT TABLE
These data sheets are only controlled while on the manufacturer’s website. The controlled version is available for
download from the manufacturer’s website. The manufacturers cannot assure the integrity or accuracy of the SDS
information contained in this document after it has been downloaded from their respective websites.
www.3M.com
www.praxair.com
As long as the quantity of pipe that allows the entrapment of agent does not exceed the allowable pipe length of 31.43
feet, the piping network serving the selector valve is acceptable. If exceeded, the piping network must be modified.