HIMA Output Module
HIMA Output Module
F 3331
F 3331: 8 fold output module, testable
safety related
resistive load or inductive load up to 500 mA (12 W),
lamp connection up to 4 W,
with integrated safety shutdown, with safe isolation,
with line monitoring,
no output signal with break of the L- supply
requirement class AK 1 ... 6
The module is automatically tested during operation. The main test routi-
nes are:
– Reading back of the output signals. The operating point of the 0 signal
read back is ≤ 6.5 V. Up to this value the level of the 0 signal may arise
in case of a fault and this will not be detected
– Switching capability of the test signal and cross-talking (walking-bit-
test)
– line monitoring.
Outputs 500 mA, k short circuit proof
Internal voltage drop max. 2 V at 500 mA load
Admissible line resistance (in + out) max. 11 Ohm
Undervoltage tripping at ≤ 16 V
Operating points (component tolerances effects value diff.)
short circuit current 0.75 ... 1.5 A
line break 0.5 ... 9.5 mA
Outp. leakage current max. 350 µA
Output voltage if output is reset max. 1.5 V
Current input WD max. 30 mA
Duration of the test signal max. 200 µs
Space requirement 4 TE
Operating data 5 V DC: 130 mA
24 V DC: 180 mA in add. load
All rights reserved. The technology is subject to changes without notice: 1/2
HIMA Paul Hildebrandt GmbH + Co KG, Postfach 1261, 68777 Brühl
F 3331 (9912)
q = 1 mm2
l = 750 mm
Lead marking of the cable plug
Z 7138 / 3331 / C.. / P2
2-pole connection
2-pole connection
Planning hints
– line break monitoring requires a minimum load of 10 mA. Use of the
signal "line break" in the user's program up to requirement class 3.
– max. 10 output modules with nominal load may be used in one IO rack
– can be paralleled without external diodes
– Appertaining softw. building block: HB-BLD-. (for current version refer
to the description of the operating system).
2/2