Syslib-Rm015 P VALVESO
Syslib-Rm015 P VALVESO
IMPORTANT This manual applies to the Rockwell Automation Library of Process Objects version 3.5 or earlier.
For Rockwell Automation Library of Process Objects version 5.0, see
• PROCES-RM200
For Rockwell Automation Library of Process Objects version 4.0 or later, use the following manuals:
• PROCES-RM013 contains logic instructions
• PROCES-RM014 contains display elements
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface Software Compatibility and Content Revision. . . . . . . . . . . . . . . . . . . . 5
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Solenoid-operated Valve Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
(P_ValveSO) Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Required Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controller File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Visualization Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controller Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Solenoid-operated Valve Input Structure . . . . . . . . . . . . . . . . . . . . 11
Solenoid-operated Valve Output Structure . . . . . . . . . . . . . . . . . . 16
Solenoid-operated Valve Local Configuration Tags . . . . . . . . . . . 19
Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Programming Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
State Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Status/Quality Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Mode Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Maintenance Bypass Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Using Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Quick Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Solenoid-operated Valve Faceplate Help . . . . . . . . . . . . . . . . . . . . . 45
For the latest compatible software information and to download the Rockwell
Automation® Library of Process Objects, see the Product Compatibility and
Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
Additional Resources These documents contain more information about related products from
Rockwell Automation.
Resource Description
PlantPAx® Distributed Control System Selection Guide, Provides information to assist with equipment procurement
publication PROCES-SG001 for your PlantPAx® system.
PlantPAx Distributed Control System Reference Manual, Provides characterized recommendations for implementing
publication PROCES-RM001 your PlantPAx system.
Rockwell Automation Library of Process Objects, Provides general considerations for the PlantPAx system
publication PROCES-RM002 library of process objects.
FactoryTalk® View Machine Edition User Manual, Provides details on how to use this software package for
publication VIEWME-UM004 creating an automation application.
FactoryTalk View Site Edition User Manual, Provides details on how to use this software package for
publication VIEWSE-UM006 developing and running human-machine interface (HMI)
applications that can involve multiple users and servers,
distributed over a network.
Logix5000™ Controllers Add-On Instructions Provides information for designing, configuring, and
Programming Manual, publication 1756-PM010 programming Add-On Instructions.
Rockwell Automation Library of Process Objects: Common Details how to monitor an input condition to raise an alarm.
Alarm Block (P_Alarm) Reference Manual, publication Information includes acknowledging, resetting, inhibiting,
SYSLIB-RM002 and disabling an alarm. Generally the P_Alarm faceplate is
accessible from the Alarms tab.
Rockwell Automation Library of Process Objects: Explains how to collect (sum up) the interlock conditions
Interlocks with First Out and Bypass (P_Intlk) Reference that stop or de-energize a running or energized piece of
Manual, publication SYSLIB-RM004 equipment or prevent it from starting or being energized.
Rockwell Automation Library of Process Objects: Common Explains how to choose the Mode (owner) of an instruction
Mode Block (P_Mode) Reference Manual, publication or control strategy. The Mode instruction is usually
SYSLIB-RM005 embedded within other instructions to extend their
functionality. It is possible to use a standalone Mode
instruction to enhance a program where modes are wanted.
Rockwell Automation Library of Process Objects: Details how to collect permissive conditions to start a piece
Permissives with Bypass (P_Perm) Reference Manual, of equipment.
publication SYSLIB-RM007
Rockwell Automation Library of Process Objects: 2-state Explains how to monitor stroke times and stroke counts for a
Valve Statistics (P_ValveStats) Reference Manual, 2-state (open and close) valve.
publication SYSLIB-RM036
Global Object
Add-On Instruction
Guidelines Use this instruction when you need to operate a single-solenoid spring-return
valve, either energize-to-open (fail closed) or energize-to-close (fail open). The
valve can have, but does not require, limit switch feedback for either or both ends
of travel.
Functional Description The P_ValveSO instruction includes an Add-On Instruction for use with
Studio 5000 Logix Designer® application, version 18 or later, and Logix
controllers, version 18 or later. P_ValveSO also includes a multi-tabbed faceplate
and several graphic symbols for use in building displays on FactoryTalk View SE
version 7.0 or later.
Required Files Add-On Instructions are reusable code objects that contain encapsulated logic
that can streamline implementing your system. This code lets you create your
own instruction set for programming logic as a supplement to the instruction set
provided natively in the ControlLogix® firmware. An Add-On Instruction is
defined once in each controller project, and can be instantiated multiple times in
your application code as needed.
Controller File
Visualization Files
This Add-On Instruction has associated visualization files that provide a
common user interface. These files can be downloaded from the Product
Compatibility and Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
IMPORTANT The visualization file dependencies require Process Library content imports to
occur in a specific order as reflected in the following tables:
• Images
• Global Objects
• Standard Displays
• HMI Tags
• Macros
Images are external graphic files that can be used in displays. They must be
imported for FactoryTalk View to make use of them.
When PNG files are imported, they are renamed by FactoryTalk View with
a .bmp file extension, but retain a .png format.
The Global Object files (.ggfx file type) in the following table are Process Library
display elements that are created once and referenced multiple times on multiple
displays in an application. When changes are made to a Global Object, all
instances in the application are automatically updated.
Table 3 - Visualization Files: Global Objects (.ggfx)
FactoryTalk View SE Software FactoryTalk View ME Software Description
(RA-BAS) Common Faceplate Objects (RA-BAS-ME) Common Faceplate Objects Global objects used on process object faceplates.
(RA-BAS) Process Alarm Objects (RA-BAS-ME) Process Alarm Objects Global objects used for managing alarms on process
object faceplates.
(RA-BAS) Process Diagnostic Objects (RA-BAS-ME) Process Diagnostic Objects Diagnostic global objects used on process object
faceplates.
(RA-BAS) Process Faceplate Valve Objects (RA-BAS-ME) Process Faceplate Valve Objects Valve global objects used on process object faceplates
(RA-BAS) Process Graphics Library (RA-BAS-ME) Process Graphics Library Process global object device symbols used to build
process graphics
(RA-BAS) Process Help Objects (RA-BAS-ME) Process Help Objects Global objects used for all process objects help displays.
(RA-BAS) Process Interlock Objects (RA-BAS-ME) Process Interlock Objects Global objects used for managing interlocks and
permissives on process object faceplates.
(RA-BAS) Process Mode Objects (RA-BAS-ME) Process Mode Objects Global objects used for managing modes on process
object faceplates.
The Standard Display files (.gfx file type) in the following table are the Process
Library displays that you see at runtime.
Table 4 - Visualization Files: Standard Displays (.gfx)
FactoryTalk View SE Software FactoryTalk View ME Software Description
(RA-BAS) Common-AnalogEdit N/A Faceplate used for analog input data entry. The FactoryTalk
View ME faceplates use the native analog input data entry
so no file is required.
(RA-BAS) P_Alarm-Faceplate (RA-BAS-ME) P_Alarm-Faceplate The faceplate that is used for managing alarms for
the object.
(RA-BAS) P_Alarm-Help (RA-BAS-ME) P_Alarm-Help Alarm Help information that is accessed from the
P_AIarm faceplate.
(RA-BAS) P_Mode-Config (RA-BAS-ME) P_Mode-Config The Configuration Display used to configure the
P_Mode object.
(RA-BAS) P_Mode-Help (RA-BAS-ME) P_Mode-Help Mode Help information that is accessed from the
Help faceplate.
(RA-BAS) P_ValveSO-Faceplate (RA-BAS-ME) P_ValveSO-Faceplate The faceplate that is used for the object
(RA-BAS) P_ValveSO-Quick (RA-BAS-ME) P_ValveSO-Quick The Quick display that is used for the object
(RA-BAS) Process Valve Family-Help (RA-BAS-ME) Process Valve Family-Help The Help display for Valve objects
(RA-BAS) P_Intlk-Faceplate (RA-BAS-ME) P_Intlk-Faceplate Optional
The interlock faceplate used for the object.
Use this file if your Discrete Output has an associated
P_Intlk object and you enable navigation to its faceplate
from the Discrete Output faceplate.
Controller Code This section describes the parameter references for this Add-On Instruction.
Configuration parameters that are array, string, or structure data types cannot be
configured as parameters for Add-On Instructions. Configuration parameters of
these types appear as local tags to the Add-On Instruction. Local tags can be
configured through the HMI faceplates or in Logix Designer application. Open
the instruction logic of the Add-On Instruction instance and then open the Data
Monitor on a local tag to accomplish this configuration. These parameters
cannot be modified by using controller logic or Logix Designer application
export/import functionality.
Operations This section describes the primary operations for Add-On Instructions.
Modes
This instruction uses the following standard modes, which are implemented by
using an embedded P_Mode Add-On Instruction.
Table 10 - Modes
Mode Description
Operator The Operator owns control of the device. Operator commands (OCmd_) and Operator settings
(OSet_) from the HMI are accepted.
Program Program logic owns control of the device. Program commands (PCmd_) and Program settings
(PSet_) are accepted.
Override Priority logic owns control of the device and supersedes Operator and Program control. Override
Inputs (Inp_OvrdCmd and other Inp_OvrdXxxx values) are accepted. If so configured,
bypassable interlocks and permissives are bypassed.
Maintenance Maintenance owns control of the device and supersedes Operator, Program, and Override
control. Operator commands and settings from the HMI are accepted. Bypassable interlocks and
permissives are bypassed, and device timeout checks are not processed.
Hand Hardwired logic or other logic outside the instruction owns control of the device. The instruction
tracks the state of the device for bumpless transfer back to one of the other modes.
No Mode The device is disabled and has no owner because the EnableIn input is false. The main
instruction Logic routine is not being scanned. See Execution section for more information on
EnableInFalse processing.
Alarms
This instruction uses the following alarms, which are implemented by using
embedded P_Alarm and P_Gate Add-On Instructions.
The Full Stall and Transit Stall Alarms have a configurable delay to allow the
open and/or closed feedback time to align with the commanded output. This
delay also provides time for the Motor-operated Valve to actually open or close.
The Full Stall and Transit Stall Alarms have a configurable delay to allow the
open and/or closed feedback time to align with the commanded output. This
delay also provides time for the Solenoid-operated Valve to actually open or close.
Simulation
Set the Inp_Sim parameter in the controller to '1' to enable simulation. The
The delay between a command to Open or Close and the simulated opened or
closed response is configurable (Cfg_SimFdbkT). (This same delay is used if the
Solenoid Valve is configured with no Open/Close feedback.)
When you have finished in simulation, set the Inp_Sim parameter in the
controller to ‘0’ to return to normal operation.
Execution
Condition Description
EnableIn False (false rung) Processing for EnableIn False (False Rung) is handled the
same as if the Solenoid Valve were Disabled by Command.
The Solenoid Valve output is de-energized and the
Solenoid Valve is shown as Disabled on the HMI.
Powerup (prescan, first scan) Processing of Modes and Alarms on Prescan and Powerup
is handled by the embedded P_Mode and P_Alarm Add-
On Instructions - refer to their manuals for details.
On Powerup, the Solenoid Valve is treated as if it had been
commanded to its de-energized position.
Postscan (SFC transition) No SFC Postscan logic is provided.
Display Elements A display element (global object) is created once and can be referenced multiple
times on multiple displays in an application. When changes are made to the
original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, in conjunction with tag structures
in the ControlLogix system, aid consistency and save engineering time.
Display Element Name Display Element Description
P_ValveSO Standard solenoid-operated valve global objects.
P_ValveSO2
P_ValveSO1
P_ValveSO3
Each Graphic Symbol includes a touch field over it that opens the object’s
faceplate. In addition, there is a tooltip on the graphic symbol that displays the
object’s configured Tag and Description.
State Indicators
The state indicator text changes and the graphic symbol color changes depending
on the state of the valve.
The Valve Actuator symbol also changes color depending on the state of
the valve.
Status/Quality Indicators
One of these symbols appears on the graphic symbol when the described
condition is true.
Graphic Symbol Description
Invalid configuration.
TIP When the Invalid Configuration Indicator appears, you can find what
configuration setting is invalid by following the indicators. Click the Graphic
Symbol to open the Faceplate. The Invalid Configuration indicator appears next
to the appropriate tab at the top of the Faceplate to help you find the
configuration error. Once you navigate to the tab, the misconfigured item is
flagged with this indicator or appears in a magenta box.
TIP When the Not Ready indicator appears, you can find what condition is
preventing operation by following the indicators. Click the graphic symbol to
open the faceplate. The Not Ready indicator appears next to the appropriate
tab at the top of the faceplate to help you find the condition. When you
navigate to the tab, the condition preventing operation is flagged.
For the Solenoid-operated Valve instruction, the Device Not Ready indicator
appears under the following conditions:
• Device has been disabled by Maintenance.
• There is a configuration error.
• Interlock or Permissive is not OK.
• Device failure and shed requires reset.
• I/O Fault and shed requires reset.
Mode Indicators
One of these symbols appears on the right side of the graphic symbol to indicate
the mode of the object instruction.
Transparent Program mode (if the default mode is Program and the current mode is Program, the mode
indicator is transparent).
Program mode (if the default mode is Operator).
Override mode
Maintenance mode.
Hand mode
No mode.
TIP The images provided for the Operator and Program default modes are
transparent; therefore, no mode indicators are visible if the device is in its
default mode. This behavior can be changed by replacing the image files for
these mode indicators with images that are not transparent.
Alarm Indicators
One of these symbols appears on the left side of the label to indicate the described
alarm condition and the alarm border and label background change color. The
alarm border and label background blink if acknowledgement of an alarm
condition is required. Once the alarm is acknowledged, the alarm border and
label background remain the color that corresponds to the severity of the alarm.
No symbol No change in color No alarm or alarm inhibit condition, and all alarms
are acknowledged.
This symbol appears to the right of the label to indicate that a maintenance
bypass has been activated.
TIP When the Maintenance Bypass Indicator appears, you can find what condition
was bypassed by following the indicators like a ‘trail of breadcrumbs’. Click the
Graphic Symbol to open the Faceplate. The Maintenance Bypass Indicator
appears next to the appropriate tab at the top of the Faceplate to help you find
the bypass. Once you navigate to the tab, the bypassed item is flagged with
this indicator.
The graphic symbol for P_ValveSO can be found in the global object file
(RA-BAS) Process Graphics Library.ggfx.
1. Copy the global object from the global object file and paste it in the
display file.
2. In the display, right-click the global object and choose Global Object
Parameter Values.
3. Type the tag or value in the Value column as specified in the Description
column.
4. Click OK.
Quick Display The Quick Display screen provides the means for operators to perform simple
interactions with the P_ValveSO instruction instance. From the Quick Display,
you can navigate to the faceplate for full access for operation, maintenance, and
configuration.
Navigate to Full
Faceplate Button
Faceplate The P_ValveSO faceplate consists of five tabs and each tab consists of one or
more pages.
The title bar of each faceplate contains the value of local configuration tags
Cfg_Tag and Cfg_Desc.
The Operator tab is displayed when the faceplate is initially opened. Choose the
appropriate icon at the top of the faceplate to access a specific tab.
Maintenance Diagnostics Exit
The faceplate provides the means for operators, maintenance workers, engineers,
and others to interact with the P_ValveMO instruction instance. You can also
view its status and values and manipulate it through its commands and settings.
When a given input is restricted via FactoryTalk View security, the required user
security code letter is shown in the tables that follow.
Operator Tab
The Faceplate initially opens to the Operator (‘Home’) tab. From here, an
operator can monitor the device status and manually operate the device when it is
in Operator mode.
The Operator tab has buttons to open and close the valve when it is in the proper
mode and shows the following information:
• Current mode (Operator, Program, Override, Maintenance, or Hand)
• Requested modes Indicator (appears if the Operator or Program mode has
been superseded by another mode). Refer to the Maintenance Tab on
page 36 for more information
• Solenoid Valve State (Closing, Closed, Opening, Opened, Disabled, or
I/O Fault)
• Limit Switch Fault (appears over the Valve State when the fault is active)
• Interlock and Permissive States
• Input Source and Quality indicator (See 'SrcQ' in the Output parameters
table on page 16 for details)
The Operator tab also has a button to open the Valve Statistics faceplate if the
valve is configured to use the P_ValveStats object (Cfg_HasValveStats = 1).
When the object is not configured to have an P_ValveStats instruction, the Valve
Statistics button is not displayed.
When the P_ValveSO instruction does not have associated Permissive (P_Perm)
or Interlock (P_Intlk) instructions, the Permissives and Interlock buttons revert
to indicators.
When the P_ValveSO instruction does not have an associated Valve Statistics
(P_ValveStats) instruction, the Valve Statistics button is not shown.
Non-bypassed conditions OK
All conditions OK
Alarm indicators appear on the Operator tab when the corresponding alarm
occurs.
One of these symbols appears to indicate the described alarm condition. The
alarm bell symbol blinks if acknowledgement of an alarm condition is required.
Maintenance Tab
Maintenance personnel use the information and controls on the Maintenance tab
to make adjustments to device parameters. They also troubleshoot and
temporarily work around device problems, and disable the device for routine
maintenance.
Maintenance Mode
Mode Indicator
Acquire and Release
Requested Modes Command Buttons
Indicator
Valve Enable and
Valve Enabled/ Disable Command
Disabled Indicator Buttons
Engineering Tab
Mode Configuration
Button
Configure Valve
Description, Label,
and Tag
The following table lists the functions on page 1 of the Engineering Page tab.
This display lets you select the default mode for the object by clicking the
appropriate mode.
IMPORTANT If no mode is being requested, changing the default mode changes the mode
of the instruction.
To select the default mode on this display, you must have FactoryTalk View
security code E.
The following table lists the functions on page 2 of the Engineering tab.
Diagnostics Tab
The Diagnostics tab displays possible reasons the device is not ready.
The previous image indicates that there has been an I/O fault and the shed needs
to be reset.
Alarms Tab
The Alarms tab displays each configured alarm for the P_ValveSO instruction.
The icon on the tab for the alarms page changes color based on the current active
alarms. A blinking alarm icon indicates that one or more alarms must be
acknowledged or the device must be reset.
Alarm Acknowledge
Command Button
Alarm Names
Alarm Severity Indicators
Click an alarm name to open the P_Alarm faceplate for that alarm. From the
P_Alarm faceplate, you can configure and perform additional operations on
the alarm.
If an alarm is active, the panel behind the alarm changes color to match the
severity of the alarm. The color of the bell icon at the top of the faceplate shows
the severity of the highest active alarm, and the icon blinks if any alarm is
unacknowledged or requires reset.
When the Reset and Acknowledge All Alarms button is enabled, the panel
behind the alarm blinks, indicating the alarm requires acknowledgement or reset.
The Alarm Acknowledge button is enabled if the alarm requires
acknowledgment. Click the button with the check mark to acknowledge the
alarm.
Notes:
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400