*Customers must take note of the following parameters in determining the appropriate equipment and system
design for their facilities.
Effect of Utility Variations on Equipment Ratings
Equipment must operate satisfactorily within the -10% to +10% voltage variation of the
Distribution Utility's nominal service voltage.
Dash (-)
To separate the voltage rating or ratings of separate windings.
Example: 34500 Grd. Y / 19920 V – 240 / 120 V
Cross (X)
To designate separate voltages which can be obtained by reconnecting the
coils of a winding in series or multiple combinations.
Example: 34500 Grd. Y / 19920 V – 240 / 120 V X 139 / 277 V
3600 / 6240Y – Two-bushing DTs for line-to-ground connection on system with line-to-line
voltages of 6.24kV.
2400 / 4160Y – Two-bushing DTs for line-to-ground connection on system with line-to-line
voltages of 4.16kV.
4800 / 8300Y – Two-bushing DTs for line-to-ground connection on system with line-to-line
voltages of 8.3kV or for line-to-line connection on system with line-to-line voltage of 4.8kV.
7620 / 13200Y – Two-bushing DTs for line-to-ground connection on system with line-to-line
voltages of 13.2kV
Secondary voltages are provided by distribution transformers that are connected to the
primary system, which are usually associated with utilization voltages.
EENG 105: DISTRIBUTION SYSTEM & SUBSTATION DESIGN
AVERAGE LOAD
Average load mean of all the demands that have concurred during the day/month/year.
∑ 𝑑𝑒𝑚𝑎𝑛𝑑 𝑜𝑓 𝑡ℎ𝑒 𝑑𝑎𝑦
𝐴𝐿𝑑𝑎𝑦 =
24
LOAD FACTOR
Ratio of average load to the peak load
𝐴𝐿
𝑙𝐹 =
𝑃𝐿
DEMAND FACTOR
Ratio of peak load to the connected load
𝑃𝐿
𝐷𝐹 =
𝐶𝐿
DIVERSITY FACTOR
Ratio of the sum of individual peak load to the peak load of the entire station
∑ 𝑃𝐿
𝑑𝐹 =
𝑃𝐿𝑠𝑡𝑎𝑡𝑖𝑜𝑛
UTILIZATION FACTOR
Ratio of the peak load of the entire station to the total or installed capacity of the station
𝑃𝐿𝑠𝑡𝑎𝑡𝑖𝑜𝑛
𝑈𝐹 =
𝐼𝑛𝑠𝑡𝑎𝑙𝑙𝑒𝑑 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦
PLANT CAPACITY FACTOR
Ratio of the annual energy delivered by the station to the rated energy that the station
can generate or produced in a year
𝐴𝑛𝑛𝑢𝑎𝑙 𝐸𝑛𝑒𝑟𝑔𝑦 𝑖𝑛 𝑘𝑊 − ℎ𝑟
𝑃𝐶𝐹𝑦𝑒𝑎𝑟 =
𝐼𝑛𝑠𝑡𝑎𝑙𝑙𝑒𝑑 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 𝑖𝑛 𝑘𝑊 ∗ 8760
PLANT USE FACTOR
Ratio of the annual energy delivered by the station to the actual energy that the station
can generate or produced in a year
𝐴𝑛𝑛𝑢𝑎𝑙 𝐸𝑛𝑒𝑟𝑔𝑦 𝑖𝑛 𝑘𝑊 − ℎ𝑟
𝑃𝑈𝐹𝑦𝑒𝑎𝑟 =
𝐼𝑛𝑠𝑡𝑎𝑙𝑙𝑒𝑑 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 𝑖𝑛 𝑘𝑊 ∗ 𝑁
L3-TRANSFORMER-CONNECTIONS
DT NAMEPLATE SAMPLE
EXTERNAL TAP-CHANGERS
Operation
1. De-energize the DT
2. Loosen lock screw
3. Rotate switch to desired position
4. Tighten lock screw
5. Energize the DT
POLARITY TESTING OF A DT