PLC Error Codes
PLC Error Codes
Introduction
A The C-more family of touch panels is capable of communicating with a wide variety of
Programmable Logic Controllers. C-more is capable of communicating over RS232, RS422 and
2 RS485 serial networks as well as Ethernet networks. It communicates with all
AutomationDirect PLCs utilizing various protocols. C-more also communicates with other
brands of PLCs by their different protocols. For a complete list of PLCs and protocols, see the
3 table on page 16 of Chapter 1: Getting Started.
As with any network communications, errors will occur. To make it more simple for the user to
4 identify the cause of the possible error, we have provided a error code table for all of the possible
errors that C-more can detect.
5 If a C-more communications error does occur, the error message will appear across the top of
the screen. The C-more touch panel also monitors any errors that are generated by the various
PLCs that are connected to it. If any of the PLC generated errors are detected, they are displayed
6 across the top of the panel’s display embedded as a hexadecimal value in error code P499’s
message. An explanation of how the specific PLC error is identified in the panel error code P499
7 is shown proceeding the specific manufacturer’s PLC error tables. How the hexadecimal error
code value is interrupted is slightly different between manufacturers, so it is important to check
the explanation at the beginning of each manufacturer’s tables.
8
Note: These PLC error codes are provided by the manufacturer of the related PLC and are subject to change
9 by the PLC manufacturer. Please refer to the manufacturers documentation for a more complete and up-to-
date list of error codes.
10 All errors are also logged into the panel’s Error log under the
Information tab in the panel’s System Setup Screens and are
identified by the error code number. See Chapter 5: System
11 Setup Screens for additional details.
STX is not found
Stride™
14 Ethernet Switch
10/100 Base-T
(such as SE-SW5U)
C-more Error Message
A
H0-ECOM/H0-ECOM100
C-more
B Ethernet Module
1
Ethernet
Touch Panel Port
C
(Bottom View)
D DL06 PLC
Ethernet CAT5
Cable - Straight-thru
4 PLC-028 PLC failed to respond The PLC failed to respond after sending a request to the PLC.
An error code specific to Omron Ethernet with a Value of XXXX has
PLC-495 Omron Ethernet Error been returned from the PLC. See the explanation for error code
5 PLC-495 proceeding the Omron CS/CJ FINS Ethernet error code tables.
Allen-Bradley EtherNET/IP specific. Encapsulation Error.
PLC-496 Error code 0xaaaaaaaa returned from PLC See the explanation for error code PLC-496 proceeding the Allen-
6 Bradley EtherNet/IP error code tables.
Allen-Bradley EtherNET/IP specific. CIP Error.
PLC-497 Error code 0xaaaaaaaa returned from PLC See the explanation for error code PLC-497 proceeding the Allen-
7 Bradley EtherNet/IP error code tables.
Allen-Bradley EtherNET/IP specific. Service Packet Error.
PLC-498 Error code 0xaaaaaaaa returned from PLC See the explanation for error code PLC-498 proceeding the Allen-
8 Bradley EtherNet/IP error code tables.
An error code with a value of XXXX has been returned from the PLC.
PLC-499 Error code XXXX returned from PLC See the explanation for error code PLC-499 below for Direct LOGIC and
proceeding each set of PLC error code tables that use this error code.
9 Data cannot write to the Serial port.
PLC-500 Cannot write to Serial Port Data was sent to the PLC via the Serial Port.
If this error shows on the Panel, it indicates a Hardware Problem.
10 PLC-700 Not enough buffer memory There was an error while allocating memory for the read buffer.
When this error is displayed, a memory leak may have occurred.
Request to inaccessible memory from the HMI layer to the PLC protocol
11 PLC-701 Access to inaccessible PLC memory layer. This error is an indication that there is a problem in the HMI layer.
A Read/Write/SetBit request has been sent to an invalid memory area.
PLC-702 Cannot access by different function code This error is an indication that there is a problem in the HMI layer.
12 PLC-703 Write request to PLC Read Only Memory
A PLC Write request was made to the PLC’s Read-Only memory area.This
error is an indication that there is a problem in the HMI layer or the PLC
protocol layer.
13 PLC-704 Bad device-access No device (PLC) exists in the server panel or the device name does not
match between the server and client when using the Panel Pass Through.
PLC-705 Protocol does not match The protocol for the device does Not match between the server and client
14 when using the panel pass through.
A
B
C
D
0x0002
Address out of range. Check to make sure that the C-more tag and System ID match the Productivity3000
Programming Software Tag Name and System ID. The project file in the Productivity3000 system and the
6
imported CSV into C-more must be in sync with each other.
A value contained in the query data field is not an allowable value for the server (or slave). This indicates a fault 7
in the structure of the remainder of a complex request, such as that the implied length is incorrect. It specifically
0x0003 does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the
application program, since the Modbus protocol is unaware of the significance of any particular value of any
particular register.
8
0x0004 An unrecoverable error occurred while the server (or slave) was attempting to perform the requested action.
9
10
11
12
13
14
A
B
C
D
x 0 x
+
x x
x
1 x
x 1 x
+
x x
x
F x
x 1 x
+
x x
x
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0-3 bits
+ + +
7 EXT STS
byte x x 0 9
=
x x 0 0
=
x x 0 9
=
Example of an EXT STS error Error PLC-499
PLC-499 Error Code Message for a “Type mismatch.” Value Displayed F 0 0 9 1 1 0 0 F 1 0 9
F 0 1 7
8 Displayed Hexadecimal Value hex
9
10
Error code 1700 returned from
PLC
11
12
13 Panel error code PLC-499
showing a hexadecimal value
of 1700 indicates “Illegal
14 command or format.”and
“Station is offline.” PLC errors.
A
B
C
D
PLC Errors for Allen-Bradley DF1 and DH485 Protocols, Local STS Errors (0-3 bits) 5
Panel Error Code
PLC-499 Hex Value
0x0 Success; no error.
Description
6
0x1 DST node is out of buffer space.
0x2 Cannot guarantee delivery; link layer. 7
(The remote node specified does not ACK command.)
0x3
0x4
Duplicate token holder detected.
Local port is disconnected.
8
0x5 Application layer timed out waiting for response.
0x6 Duplicate node detected. 9
0x7 Station is offline.
0x8 Hardware fault.
10
PLC Errors for Allen-Bradley DF1 and DH485 Protocols, Remote STS Errors (4-7 bits)
Panel Error Code
PLC-499 Hex Value
Description 11
0x0 Success; no error.
0x10 Illegal command or format. 12
0x20 Host has a problem and will not communicate.
0x30
0x40
Remote node host is missing, disconnected, or shut down.
Host could not complete function due to hardware fault.
13
0x50 Addressing problem or memory protect rungs.
0x60 Function not allowed due to command protection selection. 14
0x70 Processor is in Program Mode.
0x80
0x90
Compatibility mode file missing or communication zone problem.
Remote node cannot buffer command.
A
0xA0 Wait ACK (1775 KA buffer full).
0xB0 Remote node problem due to download. B
0xC0 Wait ACK (1775 KA buffer full).
0xD0
0xE0
not used
not used
C
0xF0 Error code in the EXT STS byte. See the error code table on the next page.
(PLC generated error codes for the Allen-Bradley DF1 protocol continued on the next page.)
D
C
D
(PLC generated error codes for the Allen-Bradley EtherNet/IP protocol for ControlLogix, D
CompactLogix, and FlexLogix continued on the next page.)
0x080000 Service not supported: The requested service was not implemented or was not defined for this Object
4 0x090000
Class/Instance.
Invalid attribute value: Invalid attribute data detected.
0x0a0000 Attribute list error: An attribute in the Get_Attribute_List or Set_Attribute_List response has a non-zero
5 0x0b0000
status.
Already in requested mode/state: The object is already in the mode/state being requested by the service.
0x0c0000 Object state conflict: The object cannot perform the requested service in its current mode/state.
6 0x0d0000
0x0e0000
Object already exists: The requested instance of object to be created already exists.
Attribute not settable: A request to modify non-modifiable attribute was received.
7 0x0f0000
0x100000
Privilege violation: A permission/privilege check failed.
Device state conflict: The device's current mode/state prohibits the execution of the requested service.
0x110000 Reply data too large: The data to be transmitted in the response buffer is larger than the allocated response
8 0x120000
buffer.
Fragmentation of a primitive value: The service specified an operation that is going to fragment a primitive
data value. For example, trying to send a 2 byte value to a REAL data type (4 byte).
9 0x130000
0x140000
Not enough data: The service did not supply enough data to perform the specified operation.
Attribute not supported: The attribute specified in the request is not supported.
0x150000 Too much data: The service supplied more data than was expected.
10 0x160000 Object does not exist: The object specified does not exist in the device.
0x170000 Service fragmentation sequence not in progress: The fragmentation sequence for this service is not
currently active for this data.
11 0x180000 No stored attribute data: The attribute data of this object was no saved prior to the requested service.
0x190000 Store operation failure: The attribute data of this object was not saved due to a failure during the attempt.
12 0x1a0000 Routing failure, request packet too large: The service request packet was too large for transmission on a
network in the path to the destination.
0x1b0000 Routing failure, response packet too large: The service reponse packet was too large for transmission on a
13 0x1c0000
network in the path from the destination.
Missing attribute list entry data: The service did not supply an attribute in a list of attributes that was
needed by the service to perform the requested behavior.
14 0x1d0000 Invalid attribute value list: The service is returning the list of attributes supplied with status information for
those attributes that were invalid.
0x1e0000 Embedded service error: See Service Packet error list (PLC-498 Error codes) below:
A 0x1f0000 Vendor specific error: A vendor specific error has been encountered. This occurs when none of the
specified errors relate to the error in the device.
0x200000 Invalid parameter: A parameter associated with the request was invalid. This code is used when a
B 0x210000
parameter does meet the requirements defined in an Application Object specification.
Write-once value or medium already written: An attempt was made to write to a write-once-medium that
has already been written or to modify a value that cannot be change once established.
C 0x220000 Invalid Reply Received: An invalid reply is received (example: service code sent doesn't match service code
received.).
(PLC generated error codes for the Allen-Bradley EtherNet/IP protocol for ControlLogix,
D CompactLogix and FlexLogix continued on the next page.)
0x2a0000
Group 2 only server general failure: This error code may only be reported by DeviceNet group 2 only
servers with 4K or less code space and only in place of Service not supported, Attribute not supported and
7
Attribute not settable.
0x2b0000 -
0xcf0000 Reserved by CIP for future extensions. 8
Reserved for Object Class and service errors: This range of error codes is to be used to indicate Object
0xd00000 -
0xff0000 Class specific errors. Use of this range should only be used when errors in this table don't accurately
reflect the error encountered.
9
PLC Errors for Allen-Bradley EtherNet/IP Protocol – Service Packet Errors
10
(Error code 0xaaaaaaaa returned from the PLC.)
Panel Error Code Description
11
PLC-498 Hex Value
0x040000 This general status codes that the tag name could not be deciphered. This could mean that the tag name
was entered incorrectly or does not exist in the PLC. 12
0x050000 The particular item referenced (usually instance) could not be found.
0x060000
0x0a0000
The amount of data requested would not fit into the response buffer. Partial data transfer has occurred.
An error has occurred trying to process one of the attributes.
13
0x130000 Not enough command data/parameters were supplied in the command to execute the service requested.
0x1c0000 An insufficient number of attributes were provided compared to the attribute count. 14
0x260000 The tag name length specified did not match what was in the message.
0xff0521
0xff0721
You have tried to access beyond the end of the data object.
The abbreviated type does not match the data type of the data object.
A
0xff0421 The beginning offset was beyond the end of the template.
B
C
D
Allen-Bradley–EtherNet/IPProtocol–PLCErrorCodeTables
A MicroLogix1100,1400&SLC5/05,bothvianativeEthernetport;
2 MicroLogix1000,1100,1200,1400,1500,SLC5/03/04/05,allviaENI
Adapter
3 The following PLC error code tables cover possible errors that are detected by the panel from
Allen-Bradley PLCs using the EtherNet/IP protocol. This includes MicroLogix 1100, 1400 &
4 SLC 5/05, both using their native Ethernet port, and MicroLogix 1000, 1100, 1200, 1400,
1500, SLC 5/03, 5/04 and 5/05 using an Allen-Bradly ENI Adapter.
5 Note: The following errors can be generated from the designated PLC, are monitored by the C-more touch
panel, and displayed on the touch panel’s screen as a hexadecimal value in panel error code PLC-496
message, if active. Please refer to the PLC manufacturer’s documentation for additional information.
6 PLC Errors for Allen-Bradley EtherNet/IP Protocol –Encapsulation Errors
(Error code 0xaaaaaaaa returned from the PLC.)
7 Panel Error Code Description
PLC-496 Hex Value
8 0x00000001 The sender issued an invalid or unsupported encapsulation command.
Insufficient memory resources in the receiver to handle the command. You can get this error if the 1761-
0x00000002 NET-ENI cannot connect to the PLC serially.
9 0x00000003
0x00000004 -
Poorly formed or incorrect data in the data portion of the encapsulation message.
11 0x00000066 -
0x00000068 Reserved for legacy (Rockwell Automation).
0x00000069 Unsupported encapsulation protocol revision.
12 0x0000006a -
0x0000ffff Reserved for future expansion.
D (PLC generated error codes for the Allen-Bradley EtherNet/IP protocol for MicroLogix 1100,
1400, SLC 5/05, or ENI Adapter continued on the next page.)
Allen-Bradley–EtherNet/IPProtocol–PLCErrorCodeTables
MicroLogix1100,1400&SLC5/05,bothvianativeEthernetport; A
MicroLogix1000,1100,1200, 1400,1500,SLC5/03/04/05,allviaENI 2
Adapter
PLC Errors for Allen-Bradley EtherNet/IP Protocol – CIP Errors 3
(Error code 0xaabbbb returned from the PLC.)
Panel Error Code
PLC-497 Hex Value Description 4
0x010113 Connection Manager: Connection Manager cannot support any more connections.
0x010114 Connection Manager: Either the vendor ID or the Product Code in the key segment did not match the
device.
5
0x010115 Connection Manager: Product Type in the key segment did not match the device.
0x010116 Connection Manager: Major or minor revision information in the key segment did not match the device. 6
0x010117 Connection Manager: Invalid connection point.
0x010118
0x010119
Connection Manager: Invalid configuration format.
Connection Manager: Connection request fails since there is no controlling connection currently open.
7
0x01011a Connection Manager: Target application cannot support any more connections.
0x01011b Connection Manager: RPI is smaller than the Production Inhibit Time. 8
0x010203 Connection Manager: Connection cannot be closed since the connection has timed out.
0x010204
0x010205
Connection Manager: Unconnected Send timed out waiting for a response.
Connection Manager: Parameter error in Unconnected send service.
9
0x010206 Connection Manager: Message too large for Unconnected message service.
0x010207 Connection Manager: Unconnected acknowledge without reply. 10
0x010301 Connection Manager: No buffer memory available.
0x010302
0x010303
Connection Manager: Network Bandwidth not available for data.
Connection Manager: No Tag filters available.
11
0x010304 Connection Manager: Not configured to send real-time data.
0x010311 Connection Manager: Port specified in Port segment not available. 12
0x010312 Connection Manager: Link address specified in port segment not available.
0x010315
0x010316
Connection Manager: invalid segment type or segment value in path.
Connection Manager: Path and Connection not equal in close.
13
0x010317 Connection Manager: Ether Segment not present or Encoded Value in Network Segment is invalid.
0x010318 Connection Manager: Link address to self invalid. 14
0x010319 Connection Manager: Resources on Secondary unavailable.
0x01031a
0x01031b
Connection Manager: Connection already established.
Connection Manager: Direct connection already established.
A
0x01031c Connection Manager: Miscellaneous.
0x01031d Connection Manager: Redundant connection mismatch. B
0x01031e Connection Manager: No more consumer resources available in the producing module.
0x01031f
0x010320 -
Connection Manager: No connection resources exist for target path.
Connection Manager: Vendor specific.
C
0x0107ff
(PLC generated error codes for the Allen-Bradley EtherNet/IP protocol for MicroLogix 1100, D
1400, SLC 5/05, or ENI Adapter continued on the next page.)
Allen-Bradley–EtherNet/IPProtocol–PLCErrorCodeTables
A MicroLogix1100,1400&SLC5/05,bothvianativeEthernetport;
2 MicroLogix1000,1100,1200, 1400,1500,SLC5/03/04/05,allviaENI
Adapter
3 PLC Errors for Allen-Bradley EtherNet/IP Protocol – CIP Errors
(Error code 0xaabbbb returned from the PLC.)
4 Panel Error Code
PLC-497 Hex Value Description
0x020000 Resource unavailable: Connection Manager resources are unavailable to handle service request.
5 0x030000 Invalid parameter value.
0x040000 Path segment error: The path segment identifier or the segment syntax was not understood by the
6 0x050000
processing node.
Path destination unknown: The path is referencing an object class, instance or structure element that is not
known or is not contained in the processing node.
7 0x060000
0x070000
Partial transfer: Only part of the expected data was transferred.
Connection lost: The messaging connection was lost.
0x080000 Service not supported: The requested service was not implemented or was not defined for this Object
8 0x090000
Class/Instance.
Invalid attribute value: Invalid attribute data detected.
0x0a0000 Attribute list error: An attribute in the Get_Attribute_List or Set_Attribute_List response has a non-zero
9 0x0b0000
status.
Already in requested mode/state: The object is already in the mode/state being requested by the service.
0x0c0000 Object state conflict: The object cannot perform the requested service in its current mode/state.
10 0x0d0000 Object already exists: The requested instance of object to be created already exists.
0x0e0000 Attribute not settable: A request to modify non-modifiable attribute was received.
11 0x0f0000
0x100000
Privilege violation: A permission/privilege check failed.
Device state conflict: The device's current mode/state prohibits the execution of the requested service.
Reply data too large: The data to be transmitted in the response buffer is larger than the allocated response
12 0x110000 buffer.
Fragmentation of a primitive value: The service specified an operation that is going to fragment a primitive
0x120000 data value. For example, trying to send a 2 byte value to a REAL data type (4 byte).
13 0x130000
0x140000
Not enough data: The service did not supply enough data to perform the specified operation.
Attribute not supported: The attribute specified in the request is not supported.
0x150000 Too much data: The service supplied more data than was expected.
14 0x160000 Object does not exist: The object specified does not exist in the device.
0x170000 Service fragmentation sequence not in progress: The fragmentation sequence for this service is not
A 0x180000
currently active for this data.
No stored attribute data: The attribute data of this object was no saved prior to the requested service.
0x190000 Store operation failure: The attribute data of this object was not saved due to a failure during the attempt.
B 0x1a0000 Routing failure, request packet too large: The service request packet was too large for transmission on a
network in the path to the destination.
0x1b0000 Routing failure, response packet too large: The service reponse packet was too large for transmission on a
C 0x1c0000
network in the path from the destination.
Missing attribute list entry data: The service did not supply an attribute in a list of attributes that was
needed by the service to perform the requested behavior.
D (PLC generated error codes for the Allen-Bradley EtherNet/IP protocol for MicroLogix 1100,
1400, SLC 5/05, or ENI Adapter continued on the next page.)
Allen-Bradley–EtherNet/IPProtocol–PLCErrorCodeTables
MicroLogix1100,1400&SLC5/05,bothvianativeEthernetport; A
MicroLogix1000,1100,1200, 1400,1500,SLC5/03/04/05,allviaENI 2
Adapter
PLC Errors for Allen-Bradley EtherNet/IP Protocol – CIP Errors 3
(Error code 0xaabbbb returned from the PLC.)
Panel Error Code Description
4
PLC-497 Hex Value
0x1d0000 Invalid attribute value list: The service is returning the list of attributes supplied with status information for
those attributes that were invalid. 5
0x1e0000 Embedded service error: See Service Packet error list (PLC-498 Error codes) below:
0x1f0000 Vendor specific error: A vendor specific error has been encountered. This occurs when none of the
specified errors relate to the error in the device. 6
0x200000 Invalid parameter: A parameter associated with the request was invalid. This code is used when a
parameter does meet the requirements defined in an Application Object specification.
0x210000 Write-once value or medium already written: An attempt was made to write to a write-once-medium that
has already been written or to modify a value that cannot be change once established.
7
Invalid Reply Received: An invalid reply is received (example: service code sent doesn't match service code
0x220000 received.). 8
0x230000 Reserved by CIP for future extensions.
0x240000
0x250000
Reserved by CIP for future extensions.
Key failure in path: The key segment was included as the first segment in the path does not match the
9
destination module. The object specific status shall indicate which part of the key check failed.
0x260000 Path Size Invalid: The size of the path which was sent with the Service Request is either not large enough
to allow the Request to be routed to an object or too much routing data was included. 10
0x270000 Unexpected attribute in list: An attempt was made to set an attribute that is not able to be set at this time.
0x280000 Invalid Member ID: The Member ID specified in the request does not exist in the specified
Class/Instance/Attribute. 11
0x290000 Member not settable: A request to modify a non-modifiable member was received.
0x2a0000
Group 2 only server general failure: This error code may only be reported by DeviceNet group 2 only
servers with 4K or less code space and only in place of Service not supported, Attribute not supported and
12
Attribute not settable.
0x2b0000 -
0xcf0000 Reserved by CIP for future extensions. 13
0xd00000 - Reserved for Object Class and service errors: This range of error codes is to be used to indicate Object
0xff0000 Class specific errors. Use of this range should only be used when errors in this table don't accurately
reflect the error encountered. 14
(PLC generated error codes for the Allen-Bradley EtherNet/IP protocol for MicroLogix 1100,
SLC 5/05, or ENI Adapter continued on the next page.)
A
B
C
D
Allen-Bradley–EtherNet/IPProtocol–PLCErrorCodeTables
A MicroLogix1100,1400&SLC5/05,bothvianativeEthernetport;
2 MicroLogix1000,1100,1200, 1400,1500,SLC5/03/04/05,allviaENI
Adapter
3 PLC Errors for Allen-Bradley EtherNet/IP Protocol – Service Packet Errors
(Error code 0xaabbbb returned from the PLC.)
4 Panel Error Code
PLC-498 Hex Value Description
0x010000 DST Node is out of buffer space.
5 0x020000
0x030000
Cannot guarantee delivery; link layer (The remote node specified does not ACK command).
Duplicate token holder detected.
6 0x040000
0x050000
Local port is disconnected.
Application layer timed out waiting for response.
0x060000 Duplicate node detected.
7 0x070000
0x080000
Station is offline.
Hardware fault.
Illegal command or format. Typical error received from PLC when addressed requested to the PLC does not
8 0x100000 exist. Usually occurs if memory map has not been expanded in PLC to the range requested from panel.
0x200000 Host has a problem and will not communicate.
9 0x300000
0x400000
Remote node host is missing, disconnected, or shut down.
Host could not complete function due to hardware fault.
0x500000 Addressing problem or memory protected rungs.
10 0x600000 Function not allowed due to command protection selection.
0x700000 Processor is in Program Mode.
11 0x800000
0x900000
Compatibility mode file missing or communication zone problem.
Remote node cannot buffer command.
0xA00000 Wait ACK (1775 KA buffer full).
12 0xB00000 Not used.
0xC00000 Not used.
13 0xD00000
0xE00000
Error code in the EXT STS byte. See the error code table below.
Fewer levels specified in address than minimum for any address.
0xF00300 More levels specified in address than system supports.
14 0xF00400 Symbol not found.
0xF00500 Symbol is of improper format.
A 0xF00600
0xF00700
Address does not point to something usable.
File is wrong size.
0xF00800 Cannot complete request, situation has changed since start of the command.
B 0xF00900 Data or file size is too large.
0xF00900 Transaction size plus word address is too large.
C 0xF00B00
0xF00C00
Access denied; improper privilege. This will occur if data file is set to constant or protected.
Condition cannot be generated; resource is not available.
0xF00D00 Condition already exists; resource is readily available.
D (PLC generated error codes for the Allen-Bradley EtherNet/IP protocol for MicroLogix 1100,
1400, SLC 5/05, or ENI Adapter continued on the next page.)
Allen-Bradley–EtherNet/IPProtocol–PLCErrorCodeTables
MicroLogix1100,1400&SLC5/05,bothvianativeEthernetport; A
MicroLogix1000,1100,1200,1400,1500,SLC5/03/04/05,allviaENI 2
Adapter
PLC Errors for Allen-Bradley EtherNet/IP Protocol – Service Packet Errors 3
(Error code 0xaabbbb returned from the PLC.)
Panel Error Code
PLC-498 Hex Value Description
4
0xF00E00
0xF00F00
Command cannot be executed.
Histogram overflow.
5
0xF01000 No access.
0xF01100
0xF01200
Illegal data type.
Invalid parameter or invalid data.
6
0xF01300
0xF01400
Address reference exists to deleted area.
Command execution failure for unknown reason; possible histogram overflow.
7
0xF01500 Data conversion error.
0xF01600
0xF01700
Scanner not able to communicate with 1771 rack adapter.
Type mismatch.
8
0xF01800
0xF01900
1771 module response was not valid.
Duplicated label.
9
0xF02200 Remote rack fault.
0xF02300
0xF02400
Timeout.
Unknown error.
10
0xF01A00
0xF01B00
File is open; another node owns it.
Another node is the program owner.
11
0xF01C00 Reserved.
0xF01D00
0xF01E00
Reserved.
Data table element protection violation.
12
0xF01F00 Temporary internal problem.
13
14
Generic EtherNet IP Protocol – PLC Error Codes A
Only errors as listed in the Touch Panel Error Code Table shown on page A-3 can occur when
using the Generic Ethernet IP protocol, there are no PLC generated errors. B
C
D
5 PLC
6
7
8 Panel error code PLC-499
showing a hexadecimal value
9 of 0013 indicates an “Port
configurator error.” PLC error.
10
11
12
13
14
A
B
C
D
A 0x280C
An SNP message has been sent and retried the maximum number of times.
A maximum of two retries are permitted.
A retry is caused by a NAK from from the remote SNP device.
A received SNP message has been NAKed the maximum number of two times.
B 0x290C The NAKed message may be retransmitted a maximum of two times.
(PLC generated error codes for the GE 90-30 SNPX protocol continued on the next page.)
C
D
4 0x410F An SNP-X request was aborted prior to completion due to reception of a Break.
A BCC (Block Check Code) error has occurred on an X-Attach Response message when establishing a new
0x420C SNP-X communication session.
Communications have not been established.
5 SNP Request or Response message exceeds maximum data length of the CMM module. (Total data length
0x420D for Mailbox and all following Buffer messages is 2048 bytes.) The master must use a smaller data length.
Use multiple requests if total data length exceeds the maximum value.
6 0x420F An X-Buffer message was received containing greater than 1000 bytes of data. The data is ignored.
An invalid message type was received when an X-Attach Response was required when establishing a new
7 0x430C SNP-X communication session.
Communications have not been established.
Improper Write Datagram message format. Series 90-70 slave devices use a different format for this
8 0x430D
message than Series 90-30 or Series 90-20 slave devices. The master must use the proper message
format for this SNP slave device. (The SNP master in the CMMmodule sends this message as part of the
Establish Datagram COMMREQ command. The datagram has been partially established, but is not usable;
the datagram should be cancelled by using the Datagram ID returned by the COMMREQ.)
9 0x430F The SNP-X slave did not receive a response from the Service Request Processor in the PLC CPU.
An invalid next message type value was detected in an X-Attach Response message when establishing a
0x440C new SNP-X communication session.
10 Communications have not been established.
0x440D A datagram error occurred in a Series 90-70 slave device (dual-port error).
A 0x510C
A framing or overrun error has occurred on an X-Attach Response message when re-establishing an
existing SNP-X communication session.
Communications have not been established.
0x540C
An invalid Next Message Type value was detected in an X-Attach Response message when re-establishing
an existing SNP-X communication session.
Communications have not been established.
4
An invalid Next Message Type value was detected in a received X-Attach message. (For an X-Attach
0x540F message, the Next Message Length must be zero.)
An invalid response code was detected in an X-Attach Response message when re-establishing an existing
5
0x550C SNP-X communication session.
0x550F
Communications have not been established.
An invalid request code was detected in a received X-Attach message.
6
An expected X-Attach Response message was not received within the response timeout interval when re-
0x560C establishing an existing SNP-X communication session. The master has retried the X-Attach message
twice without receiving a response. Communications have not been established.
7
0x600C A parity error has occurred on an X-Response message.
0x600F A parity error has occurred in a received X-Request message. 8
0x610C A framing or overrun error has occurred on an X-Response message.
0x610F
0x620C
A framing or overrun error has occurred in a received X-Request message.
A BCC (Block Check Code) error has occurred on an X-Response message.
9
0x620F A BCC (Block Check Code) error has occurred in a received X-Request message.
0x630C An invalid message type was received when an X-Response message was required. 10
0x640C An invalid next message type value was detected in an X-Response message.
0x650C
0x660C
An invalid response code was detected in an X-Response message.
An expected X-Response message was not received within the response time.
11
0x700C A parity error has occurred on an Intermediate Response message.
0x700F A parity error has occurred in a received X-Buffer message. 12
0x710C A framing or overrun error has occurred on an Intermediate Response message.
0x710F
0x720C
A framing or overrun error has occurred in a received X-Buffer message.
A BCC (Block Check Code) error has occurred on an Intermediate Response message.
13
0x720F A BCC(Block Check Code) error has occurred in a received X-Buffer message.
0x730C An invalid message type was received when an Intermediate Response message was required. 14
0x730F An expected X-Buffer message was not received.
0x740C
0x750C
An invalid next message type value was detected in an Intermediate Response message.
An invalid response code was detected in an Intermediate Response message.
A
0x760C An expected Intermediate Response message was not received within the response timeout interval.
B
(PLC generated error codes for the GE 90-30 SNPX protocol continued on the next page.)
C
D
D (PLC generated error codes for the GE 90-30 SNPX protocol continued on the next page.)
8
9
10
11 Panel error code PLC-499
showing a hexadecimal value
of 0011 indicates an “Framing
12 error.” PLC error when using
the Omron Host Link protocol.
13
14
A
B
C
D
7 0x0104
0x0105
Local Error: Too many send frames.
Local Error: Node address range error.
0x0106 Local Error: Node Address Duplication.
8 0x0201 Destination Node Error: Destination Node not in network.
0x0202 Destination Node Error: Unit Missing.
9 0x0203
0x0204
Destination Node Error: Third Node missing.
Destination Node Error: Destination Node busy.
0x0205 Destination Node Error: Response Timeout.
10 0x0301 Controller Error: Communications Controller Error.
0x0302 Controller Error: CPU Unit Error.
11 0x0303
0x0304
Controller Error: Controller Error.
Controller Error: Unit number Error.
0x0401 Service Unsupported: Undefined Command.
12 0x0402 Service Unsupported: Not supported by Model/Version.
0x0501 Routing Table Error: Destination address setting error.
13 0x0502
0x0503
Routing Table Error: No routing tables.
Routing Table Error: Routing table error.
0x0504 Routing Table Error: Too many delays.
14 0x1001 Command Format Error: Command too long.
0x1002 Command Format Error: Command too short.
A 0x1003
0x1004
Command Format Error: Elements/Data don't match.
Command Format Error: Command format error.
0x1005 Command Format Error: Header Error.
B 0x1101 Parameter Error: Area classification missing.
0x1102 Parameter Error: Access Size Error.
(PLC generated error codes for the Omron FINS protocol continued on the next page.)
D
4 0x250F
0x2510
Unit Error: Memory Error.
Unit Error: SYSMAC BUS terminator missing.
0x2601 Command Error: No protection.
5 0x2602
0x2604
Command Error: Incorrect password.
Command Error: Protected.
6 0x2605
0x2606
Command Error: Service already executing.
Command Error: Service stopped.
0x2607 Command Error: No execution right.
7 0x2608
0x2609
Command Error: Settings not complete.
Command Error: Necessary items not set.
8 0x260A
0x260B
Command Error: Number already defined.
Command Error: Error will not clear.
0x3001 Access Right Error: No access right.
9 0x4001 Abort: Service aborted.
10
11
12
13
14
A
B
C
D
B
C
D
5 0x0007
0x000A
Write Data size mismatch.
Object does not exist: Occurs when trying to request a Data Block that does not exist.
0x8000 Function being used.
6 0x8001 Action is not allowed in current mode.
0x8101 Hardware fault.
7 0x8103
0x8104
Access not allowed.
Function not supported.
0x8105 Address invalid.
8 0x8106 Data Type not supported.
0x8107 Data Type is not consistent with size.
9 0x810A
0x8500
Object does not exist.
PDU Size is incorrect.
0x8702 Address is invalid.
10 0xD201 Block name syntax error.
0xD202 Error with function parameter.
11 0xD203
0xD204
Error with block type.
No linked block.
12 0xD205
0xD206
Object already exists.
Object already exists.
0xD207 Block already used in EPROM.
13 0xD209 Block does not exist.
0xD20E No Block does not exist.
14 0xD210 Block number incorrect.
A
B
C
D
0x0004
and not BCD.
Context not supported.
3
Address out of range: Occurs when requesting an address within a Data Block that does not exist or is out
0x0005
0x0006
of range.
Address out of range.
4
0x0007
0x000A
Write Data size mismatch.
Object does not exist: Occurs when trying to request a Data Block that does not exist.
5
0x8000 Function being used.
0x8001 Action is not allowed in current mode. 6
0x8101 Hardware fault.
0x8103
0x8104
Access not allowed.
Function not supported.
7
0x8105 Address invalid.
0x8106 Data Type not supported. 8
0x8107 Data Type is not consistent with size.
0x810A
0x8500
Object does not exist.
PDU Size is incorrect.
9
0x8702 Address is invalid.
0xD201 Block name syntax error. 10
0xD202 Error with function parameter.
0xD203
0xD204
Error with block type.
No linked block.
11
0xD205
0xD206
Object already exists.
Object already exists.
12
0xD207 Block already used in EPROM.
0xD209 Block does not exist. 13
0xD20E No Block does not exist.
0xD210 Block number incorrect.
14
A
B
C
D