Simplex 4010 Fire Alarm Panel Programmer Installation Programming Instructions
Simplex 4010 Fire Alarm Panel Programmer Installation Programming Instructions
PC Programmer
Installation and Programming Instructions
574-187
Rev. C
firealarmresources.com
Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights reserved.
Printed in the United States of America.
Information in this document is subject to change without notice. No part of this
document may be reproduced or transmitted in any form or by any means,
electronic or mechanical, for any purpose, without the express written consent of
Simplex Time Recorder Company.
Walk Test is protected by US Patent No. 4,725,818.
MAPNET addressable communications is protected by US Patent No.4,796,025.
IDNet is patent pending.
TrueAlarm Analog Detection is protected by US Patent No. 5,155,468.
TrueAlarm Detector Base is protected by US Patent No. 5,173, 683.
firealarmresources.com
Codes and Standards The 4010 is listed for the following.
• Same as UL above.
Local Approvals:
• CSFM
• MEA
firealarmresources.com
Codes and Standards The installer should be familiar with the relevant codes listed below as well as
(continued) any other applicable local codes and standards, when installing a fire alarm
system.
About this Manual Before you start using the 4010 Fire Alarm Installing, Operating, and
Programming Instructions, it’s important to understand the conventions used in
this publication.
The following conventions are used in this publication to identify special names
or text.
• When a membrane panel key (located below the display) is referenced in
this manual, it is normally shown between left and right arrows. Examples
are <ALARM SILENCE> and <SYSTEM RESET>.
• Italic type indicates important terms or titles of publications, such as the
4010 Fire Alarm - Programming Instructions.
• Bulleted lists, such as this one, provide you with information. They are also
used to indicate alternatives in numbered procedural steps.
• Numbered lists indicate procedures with steps that you must carry out
sequentially.
firealarmresources.com
Table of Contents
Chapter 1. Overview
Overview................................................................................................... 1-1
Related Documents ................................................................................... 1-1
In this Chapter........................................................................................... 1-1
firealarmresources.com
Step 2. Enable Panel for Download ............................................................. 3-4
Procedure .................................................................................................. 3-4
Step 3. Upload and Archive Version 1.x Job Files ...................................... 3-5
Upload, Backup, and Archive Existing Version 1.x Job........................... 3-5
vi
firealarmresources.com
Enabling System Options.............................................................................. 5-3
Introduction............................................................................................... 5-3
Time Format ............................................................................................. 5-3
Depleted Battery ....................................................................................... 5-4
Alarm Silence / Inhibit.............................................................................. 5-4
Alarm Cutout Timer.................................................................................. 5-4
Door Drop on Alarm................................................................................. 5-5
Door Drop on AC Fail .............................................................................. 5-5
Air Handling Units (AHU) Stagger Start.................................................. 5-5
Suppression Release.................................................................................. 5-6
Active Status Reminder ............................................................................ 5-7
Signal Operation ....................................................................................... 5-7
vii
firealarmresources.com
Viewing Card 18 – Digital System Pseudos ........................................... 6-16
Card 19 – User Digital Pseudos .............................................................. 6-17
Card 20 – Analog System Pseudos ......................................................... 6-18
Card 21 – Analog User Pseudos ............................................................. 6-19
Card 22 – System Defined List Pseudos ................................................. 6-20
Card 23 – User Definable List Pseudos .................................................. 6-21
viii
firealarmresources.com
Programming Custom Labels ..................................................................... 7-11
Introduction............................................................................................. 7-11
Procedure ................................................................................................ 7-11
Overview....................................................................................................... 9-2
Introduction............................................................................................... 9-2
Terms and Concepts.................................................................................. 9-2
The Site Tab.............................................................................................. 9-3
firealarmresources.com
Associating Points with Input Statements............................................... 10-9
Input Opcodes and Qualifiers ............................................................... 10-10
Index
firealarmresources.com
Chapter 1
Overview
Overview
Overview The 4010 is a single-channel, addressable, modular FACP that monitors and
controls up to 250 IDNet addressable devices. The Standard Function
Input/Output (SFI/O) card, power supply, and cabinet provide a complete fire
alarm control panel for most applications. Optional modules mount to the
chassis to provide additional outputs, network communication, and additional
power. Additionally, the 4010 can automatically control supplementary
equipment such as fire doors and fans during an alarm condition using its
auxiliary relay outputs.
Related Documents Additional information related to 4010 Version 2.x includes the following:
In this Chapter Refer to the following page for specific information on a topic.
1-1
firealarmresources.com
Programmer Overview
• Icons that allow you to quickly perform routine tasks such as printing,
saving a job, etc. Refer to Figure 1-2 for a quick reference on each icon’s
function.
1-2
firealarmresources.com
Programmer Overview, Continued
Overview
• The Panel Tab allows you to do the following:
- List points
- Edit each point’s hardware device type, point type, or custom label
- AutoFill a point’s custom label field
- Search for a point, based on its name, device type, point type, or label
- Spell check custom labels
• The List Tab allows you to create and edit system lists.
1-3
firealarmresources.com
Programmer Overview, Continued
Icons The Icon Bar contains a set of icons that allow you to quickly perform basic
tasks, such as creating a new job or error checking a job. Figure 1-2 shows the
location of the Icon Bar and identifies the function of each icon.
Menu Structure Figure 1-3 shows the menu structure of the 4010 PC Programmer application.
Note that some of the options contained in the menu structure are not available
elsewhere in the application (i.e., there is no icon or tab for Preferences).
1-4
firealarmresources.com
Transfer Window
File Menu Edit Menu View Menu Build Menu Help Menu
Menu Menu
Help
New Undo Panel Error Check Settings New Window
Topics
Revision
Preview Report
History
Archive Toolbar
Restore
1-5
firealarmresources.com
4010 FACP Version 2.x Feature Enhancements
Summary of Features Table 1-1 summarizes the Version 2.x feature enhancements. Refer to the next
section of this manual for a list of the hardware and software components
required to support these features.
Feature Description
Version 2.x provides the ability to connect the 4009 IDNet NAC Extender
to the 4010. Key features of the new 4009 include:
• Standard unit provides four Class B NACs (rated 2A @ 24 VDC),
power supply (8A) and charger.
• IDNet Communication and Control. Provides status monitoring and
individual NAC control using a single IDNet address.
• Option cards include:
Support for 4009 IDNet
NAC Extender - Class A Adapter
- Four-circuit NAC card provides four additional NACs, rated 1.5A
@ 24 VDC
- IDNet Repeater permits additional 2500’ cable run for IDNet
applications
- IDNet Fiber Optic receiver card accepts IDNet transmission from
up to 3000’ over fiber optic conductors.
TrueAlarm utility temperature sensing achieved by assigning the
TrueAlarm Utility UTILITY point type to a TrueAlarm heat sensor point allows you to
Temperature Sensing create Custom Control equations that monitor the heat sensor and trigger
output(s) when a threshold temperature is reached.
The addition of Day/Night programming to Custom Control allows devices
to be controlled differently at different times of the day. A common
Day/Night Programming application for this type of programming is to decrease the sensitivity of a
TrueAlarm Photo sensor during the day and increase its sensitivity at
night.
60 Equation Custom The number of Custom Control equations allowed by the 4010 has been
Control Capacity increased from 40 to 60.
A discrete Battery Charger Trouble was added to Version 2.x, providing
Discrete Battery Charger
more exact trouble reporting for charger-related problems. Version 1.x of
Trouble
the system reported only a common trouble.
Version 2.x incorporates a revised polling sequence for Earth Fault
Faster Earth Fault
Search Diagnostics, resulting in improved cycle times and faster location
Search Diagnostics
of Earth faults.
1-6
firealarmresources.com
4010 FACP Version 2.x Feature Enhancements, Continued
Summary of Features
Overview
(continued) Table 1-1. Version 2.x Feature Enhancements
Feature Description
Version 2.x adds the ability to reset a City Circuit in the following situation:
Support for AHJ Alarm • If the device(s) in alarm is physically removed.
City Circuit • No other devices are in an alarm state.
Programming • System Reset is performed.
Enabling City Circuit reset is done via Custom Control.
Version 2.x includes support for TrueAlert Non-Addressable NAC devices.
With these devices, horn control occurs over the same two wires that
power and fire the strobe appliances, allowing horns and strobes to exist
on the same NAC and still be controlled separately (i.e., horns on until
silenced while strobes remain on until reset). Important points to
remember about TrueAlert Non-Addressable NAC devices include:
• Hardware Device Type. TrueAlert Non-Addressable NACs use a
hardware device type of either SIGA (Class A NAC) or SIGB (Class B
NAC).
• Software Device Types. Two separate software point types support
two distinct modes of operation:
- QALERT device type has no automatic operation. All operations
for this type of device type must be programmed with Custom
Control.
- SQALERT device type automatically turns on the designated
circuit on alarm detect (general alarm), issues the horn silence
command upon Alarm Silence, and turns off the circuit at the
completion of System Reset. Any point programmed with the
TrueAlert Non- SQALERT point type is not available for use in Custom Control
Addressable Devices programming.
• Quick CFIG. TrueAlert Non-Addressable functionality is not
supported by the front panel Quick CFIG option. You must manually
program TrueAlert hardware and software device types, using either
the front panel interface or the PC Programmer.
• Horn Operation. Operation of TrueAlert Non-Addressable Horns is
through the new “TrueAlert Horn Operation” system option. Possible
selections for this option are STEADY, TEMPORAL, and SLOW
MARCH.
• Alarm Operation. In an alarm condition, any NAC programmed with
the SQALERT device type automatically activates. Horns operate as
defined by the “TrueAlert Horn Operation” system option, and strobes
activate. Pressing Alarm Silence turns off the horns, leaving the
strobes active. System reset automatically turns TrueAlert NACs off.
• SMPL Programming. The QALERT point type provides Custom
Control capability for TrueAlert Non-Addressable devices. Existing
opcodes – such as ON, OFF, S MARCH, F MARCH, and TEMPORAL
– provide standard functionality, and a new opcode – HORN OFF –
provides specific control of TrueAlert Non-Addressable horns.
1-7
firealarmresources.com
4010 Upgrade Compatibility
Introduction Table 1-2 lists the 4010 FACP’s features and indicates whether a specific
hardware or software component is required to support a specific feature or set
of features.
• 4010 Phase 1 features are compatible with any mix of SFIO card, SFIO
firmware, BIN file, and programmer software (BIN and programmer
software must be same revision level).
• The REV. C SFIO board provides improved overload protection for the U9
voltage regulator.
• Discrete battery trouble reporting requires the REV. C SFIO board, Version
2 SFIO firmware, and a Version 2 of the BIN file and programmer
application.
• 4009 IDNet NACs require either the REV. B or REV. C SFIO board,
Version 2 SFIO firmware, and Version 2 of the BIN file and programmer
application.
• All other 4010 Version 2 features are supported by either version of the
SFIO card and SFIO firmware, but you must have Version 2 of the BIN file
and programmer application.
Programmer Programmer
SFIO Board SFIO Board SFIO FW SFIO FW and BIN File and BIN File
Feature Rev. B Rev. C Version 1 Version 2 Version 1 Version 2
565-736 565-736 742-147 742-147 741-108 & 741-108 &
107 107
Phase 1
Yes Yes Yes Yes Yes Yes
Features
IDNet U9
Yes
Overload
Protection
4010 SFIO
Yes Yes Yes
TrueAlert Non-
Addressable
NACs
FM Battery
Yes Yes Yes
Charger TBL
4009 IDNet
Yes Yes Yes Yes
Interface
Other Version 2
Yes Yes Yes Yes Yes
Features
1-8
firealarmresources.com
4010 Upgrade Compatibility, Continued
Using the Version 2.x Using the programmer to edit jobs on a panel containing older versions of the
Overview
Programmer with Version 1.x SFIO chip and board has the following effect:
Jobs
• After saving the job, the panel tags the job as a Phase II job.
• Subsequent editing of the job cannot take advantage of the full set of Phase
II features, despite the job’s Phase II designation.
1-9
firealarmresources.com
BLANK PAGE
firealarmresources.com
Chapter 2
Installing/Upgrading
PC Programmer Software
Overview This chapter lists the system requirements for the PC on which you intend to
install the PC Programmer software and describes installing or upgrading the
Version 2.x programmer software on your PC.
Once you have done this, you must download the BIN file from the distribution
floppy disk to the panel. Refer to Chapter 3 for information on downloading the
Version 2.x BIN file to the 4010 FACP.
PC Programmer Software
Installation/Upgrade
Before You Begin Before getting started, make sure that you have the following:
In this Chapter Refer to the following page for specific information on a topic.
2-1
firealarmresources.com
Before You Begin
System Requirements The Panel Programmer is a Microsoft® Windows 95 application. To install
and use the Panel Programmer, you must have the following:
• An IBM-compatible personal computer with a Pentium Processor and
a free serial communications port
• Microsoft Windows 95 operating system software
• Mouse (with at least two buttons)
• 16 Mb RAM (32Mb recommended)
• 850 Mb (or greater) hard drive
• If a DACT is installed, you will need the SDACT Programmer software
(Part No. 553-807)
2-2
firealarmresources.com
Step 1. Install the Software Key
Overview The Software Key (740-989) controls access to the Panel Programmer. When
the Panel Programmer is started, the software reads the parallel port on the PC
looking for a Software Key before the main programming window is displayed.
If the correct key is not detected, a message box is displayed noting that there is
either a missing or incorrect key and the Panel Programmer will terminate with
no further action.
PC Programmer Software
2. Remove your printer cable from your parallel port (if installed).
Installation/Upgrade
Connect the software key to your parallel port and reconnect your
printer cable to the software key. (See Figure 2-1.)
3. Turn ON power to your computer.
PRINTER CABLE
2-3
firealarmresources.com
Step 2. Create Floppy Disks (If Necessary)
Overview This section describes creating a set of floppy disks that contain the PC
Programmer software. This step is only necessary if the PC on which you
intend to install the PC Programmer does not contain a CD-ROM drive. Skip to
“Step 3. Install or Upgrade the PC Programmer Software,” if the system on
which you intend to install or upgrade the PC Programmer software contains a
CD-ROM drive.
Procedure 1. Insert the CD-ROM (741-107) in the drive of the PC on which the disks
will be made.
2-4
firealarmresources.com
Step 2. Create Floppy Disks (If Necessary), Continued
Procedure (continued)
PC Programmer Software
Installation/Upgrade
Figure 2-3. Welcome Screen
The screen shown in Figure 2-4 appears, prompting you to insert a disk in
Drive A:\.
2-5
firealarmresources.com
Step 2. Create Floppy Disks (If Necessary), Continued
Procedure (continued) A progress thermometer appears, showing the progress of the file copy
operation. A series of prompts, similar to the one shown in Figure 2-5 appear,
prompting you to insert each additional disk.
Disk Builder is complete when the Finished dialog, shown in the next figure,
appears.
2-6
firealarmresources.com
Step 3. Install or Upgrade the PC Programmer Software
Overview This section describes installing Version 2.x of the PC Programmer software. If
the PC on which you are installing the programmer already contains Version 1.x
software, make sure to overwrite the Version 1.x software with the Version 2.x
programmer software.
Procedure 1. Do one of the following, depending on which type of media you are using:
a. Insert the CD in the drive. The initial screen shown in Figure 2-7
PC Programmer Software
automatically appears after approximately 10 to 20 seconds.
Installation/Upgrade
Figure 2-7. Initial Installation Screen
2-7
firealarmresources.com
Step 3. Install or Upgrade the PC Programmer Software, Continued
Procedure (continued)
2. Click Next.
The screen shown in Figure 2-9 appears. As shown in the figure, the
default installation directory is:
C:\Program Files\Simplex\Programmer\
In most cases, it is recommended that you install the software in this
directory. If necessary, use the Browse button to specify a different drive or
directory path.
2-8
firealarmresources.com
Step 3. Install or Upgrade the PC Programmer Software, Continued
PC Programmer Software
Installation/Upgrade
Figure 2-10. Reboot Prompt
2-9
firealarmresources.com
This is Blank
firealarmresources.com
Chapter 3
Downloading a Bin File
Overview This chapter describes downloading a BIN File from the PC on which the PC
Programmer software is installed to the 4010 FACP. You need to do this in the
following situations:
• As revisions to the 4010 FACP are made, you may receive additional copies
of the BIN file to download.
Before You Begin Before getting started, make sure that you have the following:
In this Chapter Refer to the following page for specific information on a topic.
3-1
firealarmresources.com
Step 1. Connect Serial Cable and Set Serial Parameters
Step 1. Connect the Serial Connect the 733-794 serial cable between a free serial port on the service PC
Cable and the service port of the 4010 FACP, as follows:
1. Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 3-1 to the PC. Make sure that the red stripe is aligned to the left
as you connect the cable.
2. Connect the other end to the service port on the 4010 FACP.
9-Pin Connector
goes to PC
Step 2. Set PC Programmer The PC Programmer software requires you to specify settings for the following
Communication Parameters serial communication parameters.
• Port = COMx
• Baud = 9600 or 19200 (recommended)
• Parity = None
• Stop Bits = 1
• Data Bits =8
3-2
firealarmresources.com
Step 1. Connect Serial Cable and Set Serial Parameters, Continued
Step 2. Set PC Programmer Click the Start button. Point to Programs and select Simplex. When the choices
Communication Parameters appear, select Programmer.
(continued)
1. Click on the Programmer application’s Transfer menu and select Settings.
A dialog similar to the one shown in Figure 3-2 appears.
Step 3. Set 4010 FACP Baud Switches 2-1 and 2-2 on the 4010 FACP set the panel’s baud rate. Table 3-1
Rate summarizes the possible settings for these switches, and Figure 3-3 shows their
OFF LINE
9600
19,200
Figure 3-3. Using Switches SW1 and SW2 to Set Panel Baud Rate
3-3
firealarmresources.com
Step 2. Enable Panel for Download
Procedure Follow the steps in this section to enable the 4010 FACP for downloads.
The 4010 displays the following message to indicate that the panel is ready to
accept a download.
3-4
firealarmresources.com
Step 3. Upload and Archive Version 1.x Job Files
Upload, Backup, and Archive If a Version 1.x job is currently loaded on the panel, make sure to upload,
Existing Version 1.x Job backup, and archive this job before downloading the Version 2.x BIN file.
Downloading the Version 2.x BIN file erases the existing Version 1.x job from
the panel.
After uploading and restoring the Version 2.x BIN file, you can restore the
Version 1.x job, rebuild it as a Version 2.x job, and download it back to the
panel.
Refer to the following sections of this manual for information on uploading and
backing up a job.
Topic Refer to
Uploading a Job Chapter 4 – “Uploading a Job from
the Panel”
Backing Up and Archiving a Job Chapter 4 – “Saving, Archiving,
Backing Up, and Restoring Jobs”
3-5
firealarmresources.com
Step 4. Download BIN File
1. Copy the BIN file from the floppy to the PC Programmer computer.
2. Start the download process on the PC.
3. Perform a Warm Start on the 4010 FACP.
Step 1. Copy BIN File from Use Windows Explorer to copy the BIN file from the floppy disk to a directory
Floppy to PC Programmer on the PC Programmer’s hard drive. It is recommended that you copy the file to
Computer the following directory. This is the default directory in which the programmer
looks for BIN files.
\PROGRAM FILES\SIMPLEX\PROGRAMMER
Step 2. Start Download on PC 1. Click on the Transfer menu. When the selections appear, choose Transfer.
Programmer A window similar to the one shown Figure 3-4 appears.
• Download
• Direct
• Panel EXEC
3. Click OK. The dialog shown in Figure 3-5 appears, warning you to backup
the system before continuing.
3-6
firealarmresources.com
Step 4. Download BIN File, Continued
4. Click Yes.
A window similar to the following appears, prompting you for the location
of the EXEC (Bin) file.
5. Select the directory to which the file was copied, click on the name of the
EXEC file, and then select the Open button.
A message appears in the Download Dialog (Figure 3-7), indicating that the
PC Programmer is waiting for the 4010 FACP to begin downloading the
file.
3-7
firealarmresources.com
Step 4. Download BIN File, Continued
Step 3. Warm Start the 4010 Performing a Warm Start of the 4010 FACP triggers the panel to download the
FACP EXEC (Bin) file from the PC Programmer.
5. Press the <NEXT> or <PREV> keys until [Warm Start] is displayed and
press <ENTER>
A warm start initiates the start of the download. At the PC Programmer, the
Download dialog (Figure 3-7) shows the progress of the download.
When the download is complete, you should restore and download the Version
1.x job (if necessary).
3-8
firealarmresources.com
Chapter 4
Getting Started
In this Chapter Refer to the following page for specific information on a topic.
Getting Started
4-1
firealarmresources.com
Using Quick CFIG to Autoconfigure a Panel
Using Quick CFIG to Create a The 4010 FACP includes the Quick CFIG utility, an automatic configuration
New Job tool that automatically detects 4010 points. For most new installations, it is
more efficient to run 4010 Quick CFIG from the front panel and then upload the
CFIG from the 4010 to the PC Programmer, where any changes to the point
types, custom labels, and system options can be made.
Using Quick CFIG on a new panel configures the panel for general alarm
operation as follows:
• All initiating devices found by Quick CFIG are assigned a FIRE point type.
• SIG1 and SIG2 are set to point type SSIGNAL. SIG3 and SIG4 are set to
RSIGNAL.
• AUX1 is set to point type RRELAY. AUX2 is set to TRELAY.
• Remote annunciators are detected at their set address.
• Graphic annunciators
• Suppression points
• Network card
• SDACT or CCDACT card
Quick CFIG Reconfigure All The Quick CFIG Reconfigure All Hardware option, described in this section,
Hardware Option creates a new 4010 configuration.
Note1: If a configuration exists and this option is selected, it clears the current
configuration and adds all currently connected devices to the CFIG.
Note 2: Quick CFIG terminates if duplicate IDNet devices are detected. If this
happens, run Quick CFIG again and watch the LCD. Before the
program terminates, it will list the first seven duplicate addresses
found.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no
longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
4-2
firealarmresources.com
Using Quick CFIG to Autoconfigure a Panel, Continued
Quick CFIG Reconfigure All 5. Press <ENTER> to continue. Another warning appears, indicating that you
Hardware Option (continued) need to press <ENTER> to confirm the deletion.
Upload the Job from the When Quick CFIG completes, you need to upload the job from the panel to the
Panel to the Laptop laptop PC on which the programmer is installed. Once the job is uploaded, you
can open it and customize it as required by the customer, i.e., custom labels,
system options, etc.
See “Uploading a Job from the Panel,” later in this chapter for specific
information on doing this.
Getting Started
4-3
firealarmresources.com
Starting the Programmer
Using the Start Menu Click on the Start menu and point to Programs. When the choices appear, point
to Simplex and then choose Programmer.
4-4
firealarmresources.com
Creating a New Job
Introduction This section describes creating a new job with the PC programmer. Doing this
creates a job with limited definitions for the devices (i.e., no custom labels and
default device type or point types assigned to IDNet points). This is useful for
off-site configuration of a system.
After creating a job in this manner, refer to the subsequent chapters in this book
for information on adding option cards to the job, defining system options,
defining device and point types, and adding custom control equations.
Skip this section if you used Quick CFIG to create a new job and uploaded it to
the laptop.
Note: Each branch is responsible for assigning and archiving jobs. The
exception to this is a network job, in which case the network job
number must be assigned by Simplex Applications Engineering.
Step 1. Invoke New System 1. Start the programmer, as described in the previous section.
Dialog
2. At the initial Programmer Screen (Figure 4-1), click on the File menu and
choose New.
Getting Started
Figure 4-2. New System Dialog
4-5
firealarmresources.com
Creating a New Job, Continued
Step 2. Specify Job Number Enter a name for the job in the Job Number field. It is recommended that you
use a seven-character number with the following format:
BBYMTJJ
Step 3. Specify System Type Examine the entry for the System Type drop down list box. The selection must
read “4010.” Click on this list box and change the currently selected system
type to “4010” if necessary.
Step 4. Specify Standalone or The System Options panel, located at the bottom of Figure 4-2, allows you to
Network System specify whether the 4010 system is operating as a standalone or networked
system. This panel contains the following three choices:
• Standalone System specifies that the 4010 is not connected via a 4120
network to other panels.
• Existing Network specifies that the 4010 is connected to other panels, and
the job has been previously programmed.
4-6
firealarmresources.com
Opening an Existing Job Stored on the PC
Introduction By default, previously programmed jobs are stored in either the \4010JOBS or
the \NETJOBS directory. If the job for the panel that you are currently
programming is stored on the PC, use the following procedure to open it for
additional editing.
You should only do this if you are sure that the job on the PC is exactly the same
as the programming (CFIG) currently in use on the panel. For example, if you
have made changes to the panel’s programming from the 4010 front panel, it
may be more desirable to upload the CFIG from the panel to the laptop PC
before performing additional programming. See the next section for details.
2. Select Open.
3. Open the folder containing the job that corresponds to the panel you are
currently programming.
Getting Started
4. Select the job name and click on the Open button. One of the following
occurs, depending on whether the job has been previously archived.
• Archived Jobs. A prompt appears, indicating that the job has been
previously archived and changes will be saved to a new revision of the
job. Click OK to continue. The next screen displays the main PC
Programmer screen.
4-7
firealarmresources.com
Uploading a Job from the Panel
Introduction This section describes uploading an existing job from a 4010 FACP to the
service PC for editing. An upload occurs over a serial link running between the
panel and the PC. Follow the steps outlined in the following sections to link the
PC and panel and upload the job.
Note: If the panel containing the job that you want to upload is on a network,
you can upload the job, but you cannot edit the job’s attributes (i.e.,
change system options, add points, etc.). Contact Simplex Service for
additional information.
Step 1. Set Panel and PC 1. Set switches SW1 and SW2 to the positions shown in Figure 4-4. These
Baud Rates to 19,200 positions enable a baud rate of 19,200 on the 4010 FACP.
19,200
• Port. Set this radio button to the setting that corresponds to the serial
port to which the serial cable will be connected. In most cases, this will
be COM1.
• Baud Rate. Set to 19,200.
• Parity. Set to None.
• Stop Bits. Set to 1.
• Data Bits. Set to 8.
firealarmresources.com
Uploading a Job from the Panel, Continued
Step 2. Connect Serial Cable Connect a 733-794 serial cable between a free serial port on the service PC and
between PC and Panel the service port of the 4010 FACP.
1. Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 4-6 to the PC.
2. Connect the other end to the service port on the 4010 FACP. Make sure that
the red stripe is aligned to the left as you connect the cable.
9-Pin Connector
goes to PC
Getting Started
4. Press <ENTER>. A screen similar to the following appears.
4-9
firealarmresources.com
Uploading a Job from the Panel, Continued
Step 3. Enable Upload on The 4010 displays the following message to indicate that the panel is ready to
Panel (continued) upload a job.
Step 4. Start Upload at PC 1. Click on the Transfer menu. When the selections appear, choose Transfer.
A window similar to the one shown in Figure 4-7 appears.
The dialog shown in Figure 4-8 appears, prompting you to begin the upload.
4-10
firealarmresources.com
Uploading a Job from the Panel, Continued
Step 4. Start Upload at PC • If Job Name Already Exists on PC. If a job by the same name already
(continued) exists in the 4010JOBS folder on the PC, the programmer generates a
prompt asking whether you want to write over the existing file. If you do
not want to write over the existing file, click on No. Another dialog
appears, giving you the opportunity to rename the job. If you want to
overwrite the existing job, click on Yes button. A dialog similar to the one
shown in Figure 4-9 appears, indicating the progress of the file transfer.
• If Job Name Does Not Exist on PC. If no job with this name exists on the
PC, the programmer begins the download after you click on the Start
button. A dialog similar to the one shown in Figure 4-9 appears, indicating
the progress of the file transfer.
5. Click OK to continue.
The next message indicates that the programmer is unbuilding the job.
Getting Started
Figure 4-11. Unbuilding 4010 Job Message
The programmer displays the next message to indicate that the job has been
successfully unbuilt and is now stored in the 4010JOBS folder.
4-11
firealarmresources.com
Uploading a Job from the Panel, Continued
To open this job, refer to “Opening an Existing Job Stored on the PC,” earlier in
this chapter.
4-12
firealarmresources.com
Saving, Archiving, Backing Up, and Restoring Jobs
Introduction This section discusses the programmer’s file management tools – Save, Archive,
Backup, and Restore. Refer to the appropriate section below for additional
information.
Always backup and archive a job following editing and successful download.
Doing this allows you to return to a known state should critical problems occur
with an edited job file.
Saving a Job This option writes an editable version of the job using the job name specified
by the user, followed by the .MDB file extension to the PC’s hard disk.
• Click on the Save icon, represented by a disk icon on the icon bar.
• Click on the File menu and select the Save option.
A dialog similar to the following appears, allowing you to specify the name
of the file and list the modifications made to the file.
Getting Started
Figure 4-13. Save Dialog
4-13
firealarmresources.com
Saving, Archiving, Backing Up, and Restoring Jobs, Continued
Using Save As To create a copy of the job currently being edited, use the Save As option. To
do this, click on the File menu and choose Save As.
A dialog similar to the one shown in Figure 4-14 appears, allowing you to
specify the new file name, the destination directory, and the destination drive.
Archiving a Job Archive creates a compressed, permanent/non-writable copy of a job, and does
the following with it:
4-14
firealarmresources.com
Saving, Archiving, Backing Up, and Restoring Jobs, Continued
8. When the Programmer Archive Utility dialog reappears, click Exit to close
the Archive utility.
Backing Up a Job Backup stores a read/writable version of the job on either a removable storage
medium or a remote disk. Follow these steps to backup a job.
Getting Started
4-15
firealarmresources.com
Saving, Archiving, Backing Up, and Restoring Jobs, Continued
The progress of the backup appears on the bottom of the Backup dialog.
Restoring a Backed Up or Restore allows previously backed up or archived jobs to be retrieved for
Archived Job subsequent viewing or editing.
4-16
firealarmresources.com
Saving, Archiving, Backing Up, and Restoring Jobs, Continued
Restoring a Backed Up or
Archived Job (continued)
2. Select the drive and directory containing the Backup or Archive files.
3. Choose the file to restore and click on the Restore button. Archived files
are listed with an SDA4010 file extension, and Backup files are listed with
an SDC4010 file extension.
Getting Started
• If the job does not already exist on the PC, the progress of the Restore
operation displays at the bottom of the screen.
• If the job already exists on the PC, Restore asks if you want to
overwrite the existing file. Click Yes to initiate the Restore or No to
exit.
4-17
firealarmresources.com
White text
firealarmresources.com
Chapter 5
Setting General Information,
Introduction This chapter describes setting the system’s general information, system options,
passcodes, and access levels.
In this Chapter Refer to the following page for specific information on a topic.
5-1
firealarmresources.com
Entering General Information
5-2
firealarmresources.com
Enabling System Options
Time Format The Time Format option allows you to display system time in 12- or 24-hour
format. That is, time is displayed in either a 12-hour format that uses an AM
(morning) or PM (afternoon) designation, or in 24-hour (military style) format.
The Time format directly affects how time is displayed on the 4010 not only at
the high-level status screen but in the Historical Logs.
Enable either 12- or 24-hour format by selecting the appropriate check box, as
shown below: Refer to Figure 5-2 for the location of this option.
5-3
firealarmresources.com
Enabling System Options, Continued
Depleted Battery This option selects the mode of operation for the 4010 FACP if an alarm occurs
during an AC power loss while a Depleted Battery trouble exists. The specific
operation of this option differs slightly, depending on whether you have a
domestic or Canadian system.
Domestic Operation. The default setting for the option is OFF and the depleted
battery threshold voltage is 19.4 VDC ± 5%. Operation of this option for a
domestic system is as follows:
• If the system is in alarm and a depleted battery condition occurs, any NACs
that are active remain active.
• If the system in not in alarm and a depleted battery condition occurs, the
NACs are prevented from activating.
Canadian Operation. The default setting for the option is OFF and the depleted
battery threshold voltage is 19.4 VDC ± 5%. Operation of this option for a
Canadian system is as follows:
• When a depleted battery condition occurs, power is turned off to the 4010.
AC power must be restored to re-activate the 4010.
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.
Alarm Silence/Inhibit You can inhibit the Alarm Silence/System Reset on a 4010 FACP for a set
duration. The range for the Silence/Reset Inhibit timer is 0-60 minutes with zero
(No Inhibit) being the default setting.
Enable this option by selecting the following check box, as shown below. Refer
to Figure 5-2 for the location of this option.
Alarm Cutout Timer The Alarm Signal Cutout timer allows you to set a duration for how long
signals sound after an alarm. In other words, when an alarm condition exists,
the signals sound until silenced. With this option set at two minutes, building
signals sound on alarm for two minutes and then stop sounding. However, the
alarm condition remains active in the panel. The default setting for this options
is No Cutout (meaning an Alarm Silence is required to shut off signals).
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.
5-4
firealarmresources.com
Enabling System Options, Continued
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.
Note: To make a relay a door holder relay, you must assign it the DHOLDER
point type.
Door Drop on AC Fail The Door Holder - AC Fail Door Drop Timer allows the 4010 to hold doors
open for a set duration during an AC power loss condition. After that duration
has expired, the 4010 shuts off the door holder devices and the doors close. The
range for the timer is 0-60 minutes, with a default setting of 5 minutes. To have
door holders drop the doors immediately upon AC power loss, set the timer to
zero minutes.
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.
Air Handling Units (AHU) This option allows you to set the 4010 to stagger start any Air Handling Units
Stagger Start (point types AHUR, AHUO, and AHUF) in the 4010 FACP . This option
protects against power spikes that may cause the circuit breakers to trip when
AHUs start simultaneously. The range for stagger starting the AHUs is 0-60
seconds. The default setting for this option is 30 seconds. A setting of zero
allows all AHUs to start immediately.
The 4010 FACP displays an AHU Stagger Start message when the sequence
starts and an AHU Stagger Start Complete message when the sequence ends.
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.
5-5
firealarmresources.com
Enabling System Options, Continued
• Detector Delay. When enabled, this option allows you to specify a delay
between the time that a detector activates and the time that a point within
the L9 list triggers. The range is from 0 to 60 seconds (60 is the default).
• Manual Delay. When enabled, this option allows you to specify a delay,
ranging from 0 to 30 seconds, between the time that a manual release point
is activated and the time that the suppression release points in L10 trigger.
Note 2. Set the Depleted Battery Cut Out Timer system option to ON for
suppression release systems. Refer to “Depleted Battery” earlier in this section
for information.
5-6
firealarmresources.com
Enabling System Options, Continued
Active Status Reminder consists of two parts. Refer to Figure 5-2 for the
location of these options.
Signal Operation Audible and Visible ON ‘til Silence Notification Appliance Circuits (NACs) can
be set to the choices shown in Table 5-1. The default setting for the Audible
NACs is Temporal; the default setting for the Visible NACs is Synchronous; and
the default setting for TrueAlert Non-Addressable Horns is TEMPORAL.
5-7
firealarmresources.com
Enabling System Options, Continued
5-8
firealarmresources.com
Setting Passcodes and Access Levels
5-9
firealarmresources.com
Setting Passcodes and Access Levels, Continued
Setting Access Levels 1. Select the Panel tab, if it is not already selected.
3. For each of the operations listed in Figure 5-4, use the controls to set an
access level of 1, 2, 3, or 4.
5-10
firealarmresources.com
Chapter 6
Programming Cards
Introduction The 4010 allows you to manually add and delete option cards, and to view and
program points and card options (user-defined LEDs and function keys) on a
per-card basis.
In this Chapter Refer to the following page for specific information on a topic.
Programming Cards
Overview – Card Tab 6-2
Adding / Deleting Cards 6-4
Programming Master Controller (SFIO) Card 6-5
Programming the NAC Card 6-9
Programming the AUX Relay Card 6-11
Programming the IDNet Card 6-13
Viewing and Programming Analog and Digital 6-16
Pseudos
Programming a Dual RS-232 Card 6-22
Programming an RS-232 Service Modem Card 6-24
Programming a 4120 Network Card 6-29
Programming a 24 Point I/O Card 6-32
Programming an LCD Annunciator Card 6-37
6-1
firealarmresources.com
Overview – Card Tab
Card Tab Screen Components The Card Tab, shown in Figure 6-1, provides a graphical means of adding,
deleting, and programming 4010 FACP cards. Components of the Card Tab
screen include:
• Active Card List. The left-hand side of the screen lists all cards (hardware
and logical) installed on the 4010 FACP. Green cards represent hardware
components and blue cards represent logical groups of similar points. (For
example, Card 19 represents all Digital User Pseudo Points.)
• Available Card List. The right-hand side of the screen lists available
option cards that can be added to the system.
• Splitter Bar. The width of the Active Card and Available Card lists can be
changed by positioning the cursor directly over the splitter bar, clicking and
holding the left mouse button, dragging the bar to a new location, and then
releasing the bar.
Splitter Bar
Card Configuration Rules The following card configuration rules apply to the 4010 FACP:
6-2
firealarmresources.com
Overview – Card Tab, Continued
Using AutoFill The programmer includes an AutoFill feature that allows you to automatically
add pre-selected text or selections to a point’s device type, point type, or custom
label fields.
2. Click on the point containing the text or selections you want to copy. The
point’s entry highlights to show it is selected.
3. If you want to copy the highlighted text to a range of points, do one of the
Programming Cards
following:
• Range of Adjoining Points. If the points adjoin one and other, hold
down the SHIFT key and click the left mouse button on the topmost
point in the range. Continue to hold down the SHIFT key, move to the
bottom point in the range, and click and release the mouse button.
5. Click on the check boxes (device type, point type, or custom label)
corresponding to the fields that you want to automatically fill. You can
select multiple fields (i.e. device type and custom label).
• All Points. Automatically fills every point with the device type, point
type, or custom label of the point selected in Step 2 above.
6-3
firealarmresources.com
Adding / Deleting Cards
Introduction This section describes manually adding or deleting option cards. Each time you
add a card, the programmer specifies default values for card and point attributes.
After you add a card(s), refer to the appropriate section later in this chapter for
information on editing card-specific information. Refer to “Chapter 7 –
Programming Points” for information on programming a card’s points and
options.
Adding Cards 1. In the Available Cards List, select the card you want to add.
2. Hold the left mouse button down, drag the card to the Active Card List, and
release the mouse button.
The programmer prevents you from adding cards that violate the card
configuration rules.
Deleting Cards 1. In the Active Card List, click the right mouse button on the icon
representing the card you want to delete. A menu, containing the Delete
and Properties choices, appears. Refer to Figure 6-2.
2. Select Delete.
3. Select Yes when the programmer prompts you to confirm the delete
operation.
6-4
firealarmresources.com
Programming Master Controller (SFIO) Card
Introduction The Master Controller card icon, located at the top of the Active Cards List
(refer to Figure 6-1), represents the 4010’s SFIO board. Double clicking on this
icon invokes the Master Controller (SFIO) Card Programming Screen shown in
Figure 6-3.
The top of the screen contains a list of the points associated with the SFIO card.
The point name, device type, and point type – none of which is editable – is
shown for each point.
Programming Cards
LEDs,” later in this section for additional information.
• User Defined Function Key 1 and User Defined Function Key 2. See
“Programming User-Defined Function Keys” later in this section for
additional information.
Programming User-Defined Each user defined LED allows you to monitor the state of a specific system
LEDs point, illuminating when the state of the point changes. For example, LED 1 can
be programmed to light RED when the state (mode) of list point L26 (Waterflow
points) changes to ALARM.
1. Choose the LED color by clicking on the radio button to the left of the
appropriate color.
6-5
firealarmresources.com
Programming Master Controller (SFIO) Card, Continued
Programming User-Defined 2. Click on the Mode drop down list box. Choose the mode (State) that must
LEDs (continued) be true to illuminate the LED. Refer to Table 6-1 for details on the
available modes.
3. Click on the Ref Address list box and associate a point with the mode you
set in Step 2. The list that appears depends on the Mode selection. The Ref
Address list contains either physical points, pseudo points, list points, or no
entries.
Mode Meaning
Disable LED illuminates when the state of the REF ADDR
(point) is DISABLED.
Fire LED illuminates when the state of the REF ADDR
(point) goes into ALARM
LF LED illuminates when the ALARM ACK button on the
panel is pushed.
LS LED illuminates when the SUPV ACK button on the
panel is pushed.
LT LED illuminates when the TROUBLE ACK button on
the panel is pushed.
OFF LED illuminates when the state of the REF ADDR
(point) is OFF.
ON LED illuminates when the state of the REF ADDR
(point) is ON
SMPL LED illuminates when the state of a Custom Control
equation(s) is TRUE.
SUPERV LED illuminates when the state of the REF ADDR
(point) goes into SUPERV.
TROUBLE LED illuminates when the state of the REF ADDR
(point) goes into ALARM
6-6
firealarmresources.com
Programming Master Controller (SFIO) Card, Continued
Programming User-Defined Earth Ground Detect. The following example tracks the state of P76, a user-
LEDs (continued) defined pseudo point, and illuminates the Yellow LED if P76 turns ON.
P76 is, in turn, controlled by an SMPL equation, shown below, that monitors
power supply points 2-2 (+ Earth Ground) and 2-3 (Neg. Earth Ground). If
either point turns ON (i.e., indicates an Earth ground problem, either positive or
negative), the equation turns on P76, which illuminates the Yellow LED to
indicate the problem.
Programming Cards
The SMPL equation for the Earth Ground Detect example is shown below.
INPUT
ON/CODE 2-2
or ON/CODE 2-3
OUTPUT
TRACK ON P76 PRI 9,9
Programming User-Defined Function keys are a way to easily and repeatedly perform a specific function
Function Keys (Mode) on a particular system point (Reference Address).
1. Click on the Mode drop-down list box and choose the appropriate mode.
Refer to Table 6-2 for information on the modes.
2. If the Mode allows, click on the Ref. Address drop-down list box and
choose the point to which the mode applies.
6-7
firealarmresources.com
Programming Master Controller (SFIO) Card, Continued
Programming User-Defined
Function Keys (continued) Table 6-2. Modes for User-Defined Function Keys
Mode Meaning
ACK Function key acknowledges all alarms, troubles, and
supervisories.
DE N/A with user-defined function keys.
LFACK Function key acknowledges all fire alarms.
LSACK Function key acknowledges all supervisory events.
LSR Function key performs a system reset on the local
panel.
LSS Function key performs a signal silence on the local
panel.
LTACK Function key acknowledges all trouble events.
LTEST Function key performs a lamp test.
ONOFF N/A with user-defined function keys.
PBH Pressing the function key turns the specified point
(Ref. Address) ON until the function key is released.
PBT This mode allows the reference address to track the
state of the function key. The point turns ON if the
switch is active and turns OFF if the switch is not
active.
SMPL Used to indicate that an SMPL equation is being
used to program the function key.
TDE Function key toggles (reverses) the Disable/Enable
state of the specified point (Ref. Address).
TOF Function key toggles (reverses) the ON/OFF state of
the specified point (Ref. Address).
6-8
firealarmresources.com
Programming the NAC Card
Introduction The 4010 FACP provides four Notification Appliance Circuits (NACs), each of
which connects one or more Notification Appliances (horns, strobes, bells, etc.)
to the 4010.
The position of the NAC card within the Active Cards List is shown below.
Programming Cards
Figure 6-4. NAC Card Location within Active Cards List
Step 1. Open the NAC Card Double click on the NAC icon shown in Figure 6-4. A window similar to the
following appears. This window displays all standard NACs.
1. Move to the line corresponding to the NAC whose device type you want to
change.
2. Double click on the NAC’s existing device type. A list box appears,
containing the following choices:
6-9
firealarmresources.com
Programming the NAC Card, Continued
1. Double click on the NAC’s existing Point Type. A list box appears,
containing NAC-specific point types.
2. Select the appropriate Point Type. Refer to Table 6-3 for a quick reference
of point types, or refer to Appendix A for detailed point type descriptions.
1. Move to the line corresponding to the NAC whose custom label you want to
change.
2. Double click on the NAC’s existing label and type the appropriate label.
6-10
firealarmresources.com
Programming the AUX Relay Card
Introduction The 4010 FACP includes two auxiliary relays – commonly referred to as AUX
relays. Each relay provides one Form C contact, normally open or normally
closed, rated at 2A (24 VDC) or 0.5 A (120 VAC) with the optional auxiliary
relay kit.
The PC Programmer represents all AUX relays as the AUX Relay card.
Opening this card allows you to view and program the point type and custom
label for these relays. (Note: AUX Relays do not have a programmable device
type.)
Figure 6-6 shows the location of the AUX Relay card within the Active Card
List.
Programming Cards
Figure 6-6. AUX Relay Icon
Step 1. Open the AUX Relay Double click on the AUX Relay icon. A window similar to the following
Card appears.
firealarmresources.com
Programming the AUX Relay Card, Continued
Step 2. Edit the Point Type Edit an AUX Relay’s Point Type, as follows:
Step 3. Edit Custom Label Edit an AUX Relay’s Custom Label, as follows:
1. Move to the line corresponding to the AUX Relay whose custom label you
want to change.
2. Double click on the relay’s custom label field and enter the appropriate
label.
6-12
firealarmresources.com
Programming the IDNet Card
The PC Programmer represents all IDNet points as the IDNet card. Opening
this card allows you to view and program the device type, point type, custom
label, and mode (sounder base smoke detectors only) for each IDNet point.
Figure 6-8 shows the location of the IDNet card within the Active Card List.
Programming Cards
Figure 6-8. IDNet Card Icon
Step 1. Open the IDNet Card Double click on the IDNet icon, shown in Figure 6-8. A window similar to the
following appears.
6-13
firealarmresources.com
Programming the IDNet Card, Continued
Step 2. Edit Each Point’s Edit an IDNet point’s Device Type, as follows:
Device Type
1. Move to the line corresponding to the point whose device type you want to
change.
2. Double click on the point’s device type field. A list box appears, containing
the IDNet-specific choices shown in Table 6-5. Refer to Appendix A for
detailed descriptions of these device types.
6-14
firealarmresources.com
Programming the IDNet Card, Continued
Step 3. Edit Each Point’s Edit an IDNet point’s Point Type, as follows:
Point Type
1. Move to the line corresponding to the IDNet point whose point type you
want to change and double click on the Point Type field.
2. Select the appropriate Point Type. Refer to the Monitor Point Type
descriptions in Appendix A for detailed information on IDNet point types.
Note: Do not use the PC Programmer to change the point type of a suppression
release point; doing this causes the PC Programmer to change the point type
back to its default setting. To change the point type of a suppression release
point, you must use the front panel programmer.
Programming Cards
Step 4. Set Single Station TrueAlarm devices with sounder bases default to Single Station mode. Single
Mode (Detectors with station has the following effect.
Sounder Bases Only)
• Sounder activates when the associated sensor is above its alarm threshold.
Follow these steps to enable or disable Single Station mode for a specific point.
Two choices appear. One choice is blank (disables Single Station mode)
and the other choice is “Single Station” (enables Single Station mode).
2. Select the appropriate mode.
To globally disable Single Station mode, use the front panel programmer
interface (System Options menu).
6-15
firealarmresources.com
Viewing and Programming Analog and Digital Pseudos
Introduction The pseudo point cards, each of which represents a separate and distinct group
of pseudo points, are located at the bottom of the Active Cards List. Figure 6-10
shows the location of these cards.
Viewing Card 18 – Digital Card 18 represents the Digital System Pseudos. These points store a value of
System Pseudos ON or OFF and are used by the system to monitor and control system
components and functions.
Double clicking on the Card 18 icon, shown in Figure 6-11, displays the
system’s 75 digital pseudo points and their pre-assigned label. This is a view-
only screen and cannot be edited.
6-16
firealarmresources.com
Viewing and Programming Analog and Digital Pseudos, Continued
Card 19 – User Digital User-defined Digital Pseudo Points are used within Custom Control equations.
Pseudos The function of a user-defined digital pseudo point is determined by the point
type that you assign it. Table 6-6 lists the point types for user-defined digital
pseudo points and explains their function.
To program the Point Type and Custom Label for each user-defined digital
pseudo point, follow these steps.
1. Double click on the Card 19 icon within the Active Cards List. A window
similar to the following appears.
Programming Cards
Figure 6-12. Card 19 – User-Defined Digital Pseudos
a. Move to the line corresponding to the pseudo point whose point type
you want to change.
b. Double click on the point’s existing point type. A list box appears,
containing the choices shown in Table 6-6. Click on the appropriate
choice.
3. Double click on a point’s Custom Label field to edit its custom label.
6-17
firealarmresources.com
Viewing and Programming Analog and Digital Pseudos, Continued
ON/CODE 2-2
or ON/CODE 2-3
OUTPUT
Card 20 – Analog System Card 20 represents the system’s Analog Pseudo Points. These type of pseudo
Pseudos points store analog values (the number 128, for example), and can be used as a
threshold value within a Custom Control equation. (For example, perform some
action when the value of the Trouble Count analog pseudo point [A2] reaches a
specific value).
Double click on the Card 20 icon, shown in Figure 6-10, to display the system’s
analog pseudo points and their pre-assigned labels. This is a view-only screen
and cannot be edited. Refer to Figure 6-13 for an example of this screen.
6-18
firealarmresources.com
Viewing and Programming Analog and Digital Pseudos, Continued
Programming Cards
Figure 6-13. Card 20 – System Analog Pseudo Points (View Only)
Card 21 – Analog User Analog User Pseudos store analog values that can be used in Custom Control
Pseudos equations. The exact function of an analog user pseudo depends on its point
type – counter, timer, or analog value.
Double clicking on the Card 21 icon within the Active Cards List displays the
system’s user Analog Pseudo points. Refer to Figure 6-14 for an example of
this screen.
6-19
firealarmresources.com
Viewing and Programming Analog and Digital Pseudos, Continued
Card 21 – Analog User Follow the steps below to program an analog user pseudo’s point type or custom
Pseudos (continued) label.
a. Move to the line corresponding to the pseudo point whose point type
you want to change.
b. Double click on the point’s existing point type. A list box appears,
containing the choices shown in the following table. Click on the
appropriate choice.
2. Double click in the Custom Label field to edit the point’s custom label.
Card 22 – System Defined List List Pseudos provide a means of monitoring a range of similar devices. (All
Pseudos Waterflow Alarm Monitor Zones, for example.)
Double clicking on the Card 22 icon within the Active Cards List displays the
System List Pseudo points and their pre-assigned label. This is a view-only
screen and cannot be edited.
firealarmresources.com
Viewing and Programming Analog and Digital Pseudos, Continued
Card 23 – User Definable List User Definable List Pseudos allow you to create a list of similar points for use in
Pseudos Custom Control equations, user-defined LEDs, user-defined function keys, etc.
The list point turns ON if one of the points referenced in the list turns ON. You
can only edit a list’s custom label from the Card Tab.
Follow the steps below to program a user-defined list pseudo’s custom label.
1. Double click on the Card 23 icon. A screen similar to the one shown in
Figure 6-16 appears.
Programming Cards
Figure 6-16. User Defined List Pseudos
2. Move to the line corresponding to the point whose custom label you want to
change. Double click on the line and edit the point’s label.
6-21
firealarmresources.com
Programming a Dual RS-232 Card
Introduction The Dual RS-232 card allows one or two printers to be attached to the 4010
panel. Programming a dual RS-232 card involves setting the communication
parameters and selecting which events are annunciated to the printer(s).
Step 1. Open the RS-232 Card Double click on the icon that represents the RS-232 card. (If the card is not
Screen already in the Active Cards List, you first need to drag it from the Available
Cards list into the Active Cards List.) A screen similar to the one shown in
Figure 6-17 appears.
Step 2. Configure Configure the settings for the printer attached to Port A or Port B, as follows:
Communication Settings
1. Click on the Port A or Port B radio button.
2. Click on the drop-down list box beneath the radio button and specify the
type of printer attached to the port. If no printer is attached to the port,
select Unused. Do not select Command when configuring a printer.
Option Application
Unused Unused port
Print80U 80 character, unsupervised printer
Print80S 80 character, supervised printer
Print40U 40 character, unsupervised printer
Print40S 80 character, supervised printer
Command Used only when a service modem is
connected to an RS-232 Service Modem
Card. See next section of this manual for
details.
firealarmresources.com
Programming a Dual RS-232 Card, Continued
Step 2. Configure 3. Click on the Port Label field, shown below, and specify the location of the
Communication Settings printer.
(continued)
4. Use the drop down list boxes under Communication Settings to specify the
Baud Rate, number of Data Bits and Stop Bits, and the Parity setting in use
on the printer.
Programming Cards
Step 3. Select Events 1. Move to the Event Reporting panel and select the check boxes that
correspond to the types of events you want annunciated at the printer.
Refer to Table 6-9 for information on these checkboxes.
Checkbox Application
Fire Alarm Events Prints an event when an ALARM condition
occurs.
Trouble Events Prints an event when a TROUBLE condition
occurs.
Supervisory Events Prints an event when a SUPERVISORY
condition occurs.
Walk Test Events Prints an event when a WALKTEST occurs.
Silence/Reset Events Prints an event when a System Reset or
Alarm Silence is performed.
SMPL Print Statements Allows SMPL Print statements to print at the
Events printer.
Control Events Prints an event when a control point (signal or
relay) turns ON or OFF.
Utility Events Prints an event when a point with the Utility
point type turns ON or OFF.
Pseudo Events Prints an event when a pseudo point changes
state, either from ON to OFF or vice versa.
Reports Events Specifies whether the printer prints a report
when a report is generated at the panel.
6-23
firealarmresources.com
Programming an RS-232 Service Modem Card
• Service personnel can dial into the 4010 FACP through the RS-232 Service
Modem card and perform basic control and monitoring of the panel, and
request system reports.
• System status and reports can be sent out the service modem port and
displayed on a remote terminal or computer.
This section describes programming the RS-232 Service Modem Card and
provides a brief description of the remote commands used to monitor/control the
4010 FACP.
Step 1. Open the RS-232 Double click on the icon that represents the RS-232 Service Modem card. (If
Service Modem Card Screen the card is not already in the Active Cards List, you first need to drag it from the
Available Cards list into the Active Cards List.)
6-24
firealarmresources.com
Programming an RS-232 Service Modem Card, Continued
Step 2. Configure 3. Click on the Port Label field, shown below, and specify the location of the
Communication Settings for control device.
Port B (continued)
4. Use the drop down list boxes under Communication Settings to specify the
modem’s Baud Rate, number of Data Bits and Stop Bits, and the Parity.
Programming Cards
Step 3. Select Events to Move to the Event Reporting panel and select the check boxes that correspond
Forward to Remote System to the types of events you want annunciated at the remote system. Refer to
Table 6-10 for information on these checkboxes.
Checkbox Application
Fire Alarm Events Displays an event when an ALARM condition
occurs.
Trouble Events Displays an event when a TROUBLE
condition occurs.
Supervisory Events Displays an event when a SUPERVISORY
condition occurs.
Walk Test Events Displays an event when a WALKTEST occurs.
Silence/Reset Events Displays an event when a System Reset or
Alarm Silence is performed.
SMPL Print Statements Displays SMPL Print statements at the remote
Events system.
Control Events Displays an event when a control point (signal
or relay) turns ON or OFF.
Utility Events Displays an event when a point with the Utility
type turns ON or OFF.
Pseudo Events Displays an event when a pseudo point
changes state, either from ON to OFF or vice
versa.
Reports Events Specifies whether the system displays a
report when one is generated at the panel.
6-25
firealarmresources.com
Programming an RS-232 Service Modem Card, Continued
Service Modem Command Service modem commands are either query type commands that request
Summary information or action type commands that direct the panel to perform some
function. The asterisk shown within each command denotes the minimum
number of characters that you must type. For example, to use the TIME
command, you need to type, at a minimum, the T character. In the examples,
the – character represents the prompt.
Returns the current logical point status (ON, OFF, FIRE, etc.) for the requested point.
Viewing Status for a Specific Point. Enter the LIST command, followed by the point’s
address (see Appendix A for a list of point addresses). For example:
-LIST P260
Viewing List of Current Alarms, Troubles, or Supervisories. Enter the LIST command,
L*IST followed by an F (current list of alarms), T (current list of Troubles), or S (current list of
Supervisories). For example:
-LIST F
Viewing Alarm, Trouble, or Supervisory Counts. Enter the List command, followed by
COUNT.
-LIST COUNT
Allows the user to manipulate the status of a control point or digital pseudo point.
Turning a Point ON. Enter the SET command, followed by the point’s address (see
Appendix A for a list of point addresses), and the ON qualifier. For example:
-SET P260 ON
Turning a Point OFF. Enter the SET command, followed by the point’s address (see
S*ET
Appendix A for a list of point addresses), and the OFF qualifier. For example:
-SET P260 OFF
Clearing an Override Trouble. Enter the SET command, followed by the point’s address
(see Appendix A for a list of point addresses), and the AUTO qualifier. For example:
-SET P260 AUTO
6-26
firealarmresources.com
Programming an RS-232 Service Modem Card, Continued
Programming Cards
Help on Parameters. Enter HELP without a parameter to see a list of available
parameters. To see a short text description of a parameter, type HELP, followed by a
parameter.
Help on Commands. Enter HELP, followed by a command to see a short text description
HELP
for one of the service modem commands. Applicable commands are: TIME, LIST
REVISION, SET, DISABLE, HELP, LOGIN, RESTART, ACK, PRINT, CLEAR, TYPE. For
example:
-HELP TYPE
Acknowledging the Highest Priority Abnormal Point. Enter the ACK command with no
qualifiers. For example:
-ACK
ACK
Acknowledging All Points in the Active Alarm (fire), Trouble, or Supervisory List.
Enter the ACK command, followed by F, T, or S. For example:
-ACK F
Logging in to a Remote System. Enter LOGIN at the prompt and wait for the prompt to
reappear. When it does, enter the 4 digit passcode that corresponds to the desired login
level. For example:
LOG*IN -LOGIN
-4000
Logging Out of a Remote System. Enter LOGIN at the prompt and wait for the prompt to
reappear. When it does, enter a carriage return.
6-27
firealarmresources.com
Programming an RS-232 Service Modem Card, Continued
The command allows the user to clear the alarm log, trouble log, supervisory log, or
combined log. Type CLEAR, followed by one of the following:
Sends a report to the terminal (PC) from which the command was issued. The TYPE
command must be followed by one of the following qualifiers:
ALOG Prints the alarm log
TYPE TLOG Prints the trouble log
SLOG Prints the supervisory log
CLOG Prints the combined log
TASERV Prints a TrueAlarm service report
TASTAT Prints a TrueAlarm status report
6-28
firealarmresources.com
Programming a 4120 Network Card
Introduction This section describes programming a 4120 network card -- either an RS485
card (also known as a “Wired Media” card) or a modular card with either RS485
or Fiber.
• You cannot create a network of only 4010 panels. You must connect the
4010 to a network containing either a 4100, GCC, or NPU.
Programming Cards
Step 1. Define Network Job If you are adding a network card to a non-networked job (i.e., you selected
Attributes (If Necessary) Standalone Panel when you originally created the job), the programmer presents
the following screen, which allows you to specify the network job number,
description, and network file. Once a standalone job is changed to a network
job, you can no longer upload the job to the laptop. Make sure you backup the
job before proceeding.
2. If the network job is new, you must specify the Network File number and
Network Description for the job. Refer to Simplex Applications
engineering for information on specifying a network file number.
6-29
firealarmresources.com
Programming a 4120 Network Card, Continued
Step 1. Define Network Job 3. Double click on the icon that represents the 4120 Network card. (If the card
Attributes (If Necessary) is not already in the Active Cards List, you first need to drag it from the
(continued) Available Cards list into the Active Cards List.)
Step 2. Enter Description The Description field specifies what appears in the DBN Node Listing
Description, shown at the bottom of Figure 6-20.
6-30
firealarmresources.com
Programming a 4120 Network Card, Continued
Step 3. Set Node / Loop Choose the appropriate selections for Node Number, Loop Number, and Comm
Number and Comm Style Style, as follows:
Node Number. The Node Number is a unique number used to identify the 4010
panel on the 4120 network. The range for this number is between 1 and 99. If
necessary, first use the Simplex Network Programmer or the network
diagnostics to view the other nodes on the network. Review the node numbers
already in use and select a unique number for this node.
Programming Cards
Comm Style. Style 4 networks represent a single line or star topology. With
these types of networks a single short, ground fault, or open circuit on the
network communications channel reports a trouble and all nodes beyond the
fault operate in local (standalone) mode.
Style 7 networks represent a closed loop ring. With these types of networks, any
single open, short, or ground fault on the network communications channel will
not interrupt communications between nodes on the network.
Step 4. Select Port Media Modular versions of the 4120 card allow the use of either Wired Media (RS485)
(Modular Card Only) or fiber for the card’s left and right ports.
1. Click the drop down list box underneath Left Port and select the choice that
represents the type of module used on the card’s left port.
2. Click the drop down list box underneath Right Port and select the choice
that represents the type of module used on the card’s right port.
6-31
firealarmresources.com
Programming a 24 Point I/O Card
Introduction A 24 Point I/O card allows 24 additional input (either two or three position
switches) or output devices (lamp, piezo, relay, or on until reset relay) to be
connected to the 4010 FACP.
Double click on the icon that represents the 24 Point I/O card. (If the card is not
already in the Active Cards List, you first need to drag it from the Available
Cards list into the Active Cards List.)
Programming an Input Device 1. Click on the Device Type field and select GRAPHIN device type.
(Two- or Three-Position
Switch) 2. Click on the point type field and select one of the following:
3. Select the mode (operation) of the switch. Refer to Table 6-11 for specific
information on the modes.
4. Click on the Ref. Addr field and select the point affected by the mode.
6-32
firealarmresources.com
Programming a 24 Point I/O Card, Continued
Programming Cards
ACK – Programs the switch to Normal Mode OFF.
acknowledge all alarms and Limited Acknowledges all alarms and troubles
troubles SSWITCH
Normal Mode OFF
Normal Mode OFF
TSWITCH Short Acknowledges all alarms and troubles
Limited Acknowledges all alarms and troubles
6-33
firealarmresources.com
Programming a 24 Point I/O Card, Continued
6-34
firealarmresources.com
Programming a 24 Point I/O Card, Continued
Programming Cards
SMPL – Mode indicates that an
SMPL equation is being used to
program the switch. SSWITCH Not Applicable
6-35
firealarmresources.com
Programming a 24 Point I/O Card, Continued
Programming an Output Point 1. Click on the Device Type field and select the GRAPHOUT device type.
2. Click on the point type field and select one of the following:
3. Select the mode (operation) of the output. Refer to Table 6-15 for specific
information on the modes.
4. Click on the Ref Addr field and select the point used to trigger the output.
Mode Application
DISABLE Output activates when the referenced point is
Disabled.
FIRE Output activates when the state of the referenced
point is in an ALARM condition.
LF Output activates when any ALARM condition occurs.
LS Output activates when a Supervisory condition occurs.
LT Output activates when a Trouble condition occurs.
OFF Output activates when the state of the referenced
point is OFF.
ON Output activates when the state of the referenced
point is OFF.
SMPL Output activates when a Custom Control equation
executes.
SUPERV Output activates when a Supervisory condition occurs
to the referenced point.
TROUBLE Output activates when a Trouble condition occurs to
the referenced point.
6-36
firealarmresources.com
Programming an LCD Annunciator Card
Step 1. Open the LCD Double click on the card icon that represents the annunciator. A screen similar
Annunciator Card Screen to the following appears. The names of the points differ if you are programming
Programming Cards
an External LCD Annunciator.
Step 2. Programming The External LCD Annunciator contains push button switches that can be used
External Graphical LCD to control outputs. Programming these switches involves setting a device type,
Annunciator Switches point type, mode (operation for the switch), and reference point (the point
affected by the switches’ mode).
1. Click on the Device Type column to the right of the switch that you want to
program and select the LCDIN choice.
6-37
firealarmresources.com
Programming an LCD Annunciator Card, Continued
Step 2. Programming 2. Click on the Point Type column and select USWITCH (2-position,
External Graphical LCD unsupervised switch.
Annunciator Switches
(continued) 3. Click on the Mode and select the operation of the switch.
Mode Application
ACK Programs the switch to acknowledge all alarms and
troubles.
DE Programs one switch position to disable the point and
another switch position to enable the point.
LFACK Programs the switch to acknowledge Fire Alarms.
LSR Programs the switch to perform a system reset.
LSS Programs the switch to perform a signal silence.
LTACK Programs the switch to acknowledge troubles.
LTEST Programs the switch to perform a lamp test.
ONOFF Programs one position of the switch to turn the point ON
and another switch position to turn the point OFF.
PBH Programs the switch to turn the point ON and hold it ON.
Point must be turned off by Custom Control or system
reset.
PBT Programs the referenced address to track the state of
the switch, turning ON when the switch is active and
turning OFF when the switch is inactive.
SMPL Indicates that an SMPL equation is being used to
program the switch.
TDE Programs the switch to toggle the Disable/Enable state
of the point.
TOF Programs the switch to toggle the ON/OFF state of the
point.
4. Click on the Ref. Addr field and select the point affected by the switch.
6-38
firealarmresources.com
Programming an LCD Annunciator Card, Continued
Step 3. Programming LEDs Both the External Graphical LCD Annunciator and the LCD Annuciator contain
LEDs that can be used to monitor the state of a point, illuminating a specific
color when the state of the point is equal to a specific condition.
1. Click on the Device Type field corresponding to the LED that you want to
program and choose Multicolor.
2. Click on the Point Type field and choose one of the following. Note that
LED1 and LED2 illuminate Yellow or Red, whereas LED3 illuminates
either Yellow or Green.
Programming Cards
LED Available Point Types
LED 1 Select Yellow for a Yellow LED
Select Non Yellow for a Red LED
LED 2 Select Yellow for a Yellow LED
Select Non Yellow for a Red LED
LED 3 Select Yellow for a Yellow LED
Select Non Yellow for a Green LED
3. Click on the Mode drop down list box. Choose the mode (State) that must
be true to illuminate the LED. Refer to the following table for details on the
available modes.
Mode Meaning
Disable LED illuminates when the state of the REF ADDR
(point) is DISABLED.
Fire LED illuminates when the state of the REF ADDR
(point) goes into ALARM
LF LED illuminates when the ALARM ACK button on the
panel is pushed.
LS LED illuminates when the SUPV ACK button on the
panel is pushed.
LT LED illuminates when the TROUBLE ACK button on
the panel is pushed.
OFF LED illuminates when the state of the REF ADDR
(point) is OFF.
ON LED illuminates when the state of the REF ADDR
(point) is ON
SMPL LED illuminates when the state of a Custom Control
equation(s) is TRUE.
SUPERV LED illuminates when the state of the REF ADDR
(point) goes into SUPERV.
TROUBLE LED illuminates when the state of the REF ADDR
(point) goes into ALARM
6-39
firealarmresources.com
Programming an LCD Annunciator Card, Continued
Step 3. Programming LEDs 4 Click on the Ref Address field and associate a point with the mode you set
(continued) in Step 3. The list that appears depends on the Mode selection. The Ref
Address list contains either physical points, pseudo points, list points, or no
entries.
Programming Events The Event Reporting panel of the LCD Annunciator card programming screen
allows you to select which events are reported at the annunciator.
Click on the check boxes that correspond to the events that should be routed to
the annunciator. The list is as follows:
6-40
firealarmresources.com
Chapter 7
Programming Points
Blank Page
Overview This chapter provides instructions for programming each point’s device type,
point type, and custom label.
In this Chapter Refer to the following page for specific information on a topic.
Programming Points
7-1
firealarmresources.com
Overview – Point Tab
Introduction The Point Tab, shown in Figure 7-1, allows you to view all points in the system,
and to add and edit point information. This section describes the general
features – AutoFill, Word Library, etc. – of the Point Tab screen.
Splitter
Bar
Splitter Bar Use the Splitter Bar to adjust the size of the window containing points. Position
the cursor over the Splitter Bar, click and hold the mouse button, drag the bar to
its new position and release the mouse button.
Site, Card, and Point Views The View panel allows you to view points in three ways. Each view is selected
by clicking on the corresponding radio button in the View panel (top right
Figure 7-1).
Sort Order The Sort Order panel, located in the top right of Figure 7-1, allows you to
display points in ascending or descending numerical order. Use the two radio
buttons – Ascending and Descending – to set the sort order.
Word Library The Custom Label Suggestion box displays suggestions from the programmer’s
word library as you create custom labels. If you wish to insert the word
displayed in this box, press CTRL + F and the word is inserted in the correct
position in the custom label.
7-2
firealarmresources.com
Overview – Point Tab, Continued
AutoFill AutoFill allows you to automatically add text to the Custom Label field. It is
possible to select either a single point, a range of adjoining points within the list,
or a group of non-adjoining points.
1. Enter the text that you want to automatically enter in the Custom Label
AutoFill text entry box.
• Single Point. Click on the point to highlight it. Next, click on the
AutoFill button. The text is added to the Custom Label field of the
selected point.
• Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range. Click on the
AutoFill button. The text is added to the Custom Label field for the
range of points.
• Range of Non-Adjoining Points. Hold down the CTRL key and click
on the points. Each point highlights to show it is selected. When all
points have been selected, release the CTRL key and click on the
AutoFill button. The text is added to the Custom Label field for all of
the selected points.
Programming Points
Custom Label Spell Check Spell check allows you to validate the spelling of custom labels, and can be used
to check either selected points or all points.
• Single Point. Click on the Selected Points button in the Custom Label
Spell Check panel and click on the point to highlight it. Next, click on
the AutoFill button. The text is added to the Custom Label field of the
selected point.
• All Points. Click on the All Points button in the Custom Label Spell
Check panel.
7-3
firealarmresources.com
Overview – Point Tab, Continued
Custom Label Spell Check 3. Click on the rectangular Check button, located in the Custom Label Spell
(continued) Check panel.
Words that are not contained in the programmer’s dictionary are flagged by
the following dialog.
7-4
firealarmresources.com
Programming a Point’s Hardware Device Type
Introduction A point’s hardware device type identifies the specific hardware device being
programmed. The programmer supports the following general categories of
hardware device type.
Procedure 1. Move to the point’s device type field and double click with the left mouse
button.
2. Click on the device type that is appropriate for the point being programmed.
Refer to Table 7-1 for quick reference information, or refer to Appendix A
for detailed information on the hardware device types.
Programming Points
Monitor ADRPUL Addressable Pull Station
CANPUL Canadian 2-stage Pull Station
ISO Communicating Line – Powered
ISO
MAZAM Class A Monitor ZAM (T-sense)
MBZAM Class B Monitor ZAM (T-sense)
7-5
firealarmresources.com
Programming a Point’s Hardware Device Type, Continued
Procedure (continued)
Table 7-1. Device Types Quick Reference (continued)
7-6
firealarmresources.com
Programming a Point’s Hardware Device Type, Continued
Procedure (continued)
Table 7-1. Device Types (continued)
Programming Points
Misc. ANALOG Analog Pseudo
Device COMNTBL Network Common Trouble
Types DIGTAL Digital Pseudo
DTMASTERIN Master Switch Input
DTMASTEROUT1 Master LED Output – Red/Yellow
DTMASTEROUT2 Master LED Output – Red/Green
LIST List
STATUS Status
7-7
firealarmresources.com
Programming a Point’s Software Point Type
• The message displayed on the 4010’s LCD when changes occur to the state
of the point’s circuit.
• The way in which the system operates (for example, initiate an Alarm,
Trouble, or Supervisory action) when changes occur to the state of the
point’s circuit.
Example. Compare the FIRE Point type with the SO (normally open sprinkler
monitor) point type. When the circuit state of a point programmed with either type
is Normal, the system operates normally (i.e., no Alarm/Trouble/Supervisory
messages and no system action occurs).
Notice, however, that the operation of the system is different if a Current Limited
condition occurs. When a current limited condition occurs for a device associated
with the FIRE point type, the system displays “Fire Monitor Zone” on the LCD,
illuminates the FIRE LED, and triggers any automatic and custom Alarm response
(i.e., activate NACs, etc.). Contrast this with what happens when a current limited
condition occurs for a device associated with the SO point type. In this case, an
abnormal physical state exists. To have actions occur as a result of the sprinkler
monitor’s change in state, you would need to write a Custom Control equation that
monitors the point for this circuit state and then executes specific output actions if
an abnormal physical state occurs.
Note: Do not use the PC Programmer to change the point type of a suppression
release point; doing this causes the PC Programmer to change the point type
back to its default setting. To change the point type of a suppression release
point, you must use the front panel programmer.
2. Move to the point’s Point Type field and double click with the left mouse
button.
3. Click on the appropriate point type. Refer to Table 7-2 for a quick
reference of the point types; refer to Appendix A for detailed descriptions of
the point types.
7-8
firealarmresources.com
Programming a Point’s Software Point Type, Continued
Procedure (continued)
Table 7-2. Point Types
Programming Cards
SMOKE Smoke detector
SO Sprinkler supervisory (normally open)
Monitor SPULL Combination Smoke/Pull Zone
STYLEC Style –C Monitor Point (current
limit=fire alarm; short/open=trouble)
SUPABRT Suppression release abort zone
SUPDET Suppression release detector zone
SUPDUMP Suppression release manual dump
SUPPRES Suppression release pressure monitor
SUPV Supervisory (generic)
TROUBLE Trouble Monitor
UTILITY Non-alarm utility with Tri-state ability
VSFIRE Verified Smoke/Fire Zone
VSMOKE Verified Smoke Zone
VSPULL Verified combination Smoke/Pull
Zone
WATER Waterflow Switch
WSO Waterflow Switch/Sprinkler
supervision (Normally Open)
7-9
firealarmresources.com
Programming a Point’s Software Point Type, Continued
Procedure (continued)
Table 7-2. Point Types (continued)
7-10
firealarmresources.com
Programming Custom Labels
Introduction Custom Labels provide a means of adding custom text descriptions to a point’s
Custom Label field.
2. Move to the point’s Custom Label field and double click with the left
mouse button.
A flashing cursor appears, indicating that you should enter text.
3. Edit the label. Refer to “Overview” at the beginning of this chapter for
information on using the AutoFill feature to automatically add text to the
Custom Label field.
Programming Points
7-11
firealarmresources.com
This page blank
firealarmresources.com
Chapter 8
Programming Lists
Introduction This chapter describes editing the name of a list, and adding or deleting points
from a list.
In this Chapter Refer to the following page for specific information on a topic.
Programming Lists
8-1
firealarmresources.com
Overview – List Tab
Accessing the List Tab The List Tab allows you to build or edit lists. Click on the List Tab at the top of
the screen to display the list-editing window.
• Lists 8 through 12. These are lists containing suppression release points.
Icons used within the Screen Three icons are used to show the status of a list. These icons appear to the left
of the list’s number.
8-2
firealarmresources.com
Overview – List Tab, Continued
Sorting the Point Display The right side of the List window contains the points that can be added to
system and user-defined lists. You can sort and filter this list as follows:
c. Click on the Device drop down list box. This selection allows you to
Programming Lists
display only points with a specific device type. Choose All to see all
points.
d. Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.
8-3
firealarmresources.com
Naming Lists and Adding/Deleting Points
Naming a List Use the following procedure to edit the name of any user-defined list. (Note that
you cannot change the name of system-defined lists.)
1. Double click on the Description field to the right of the list number that you
want to define.
Adding Points Points contained on the right hand side of the List window are added to a list as
follows:
• Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range.
2. Hold down the left mouse button and drag the points into the list area.
While continuing to hold down the mouse button, position the cursor
directly over the list to which you want to add the points and release the
mouse button.
1. Click on the + sign in the box to the left of the book that represents the list
from which you want to delete points.
• Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range.
3. Press the Delete key, or hold down the right mouse button and select the
Delete option.
8-4
firealarmresources.com
Chapter 9
Creating a Site Tree
In this Chapter The remainder of this chapter discusses the following topics:
9-1
firealarmresources.com
Overview
Introduction A site tree allows you to create labels for specific, physical areas of a building
and assign fire alarm points to these labels. When complete, a site tree
graphically depicts the layout of the site and gives an indication of every point’s
location within the site.
A site tree reads from left to right, with general divisions of the site (such as
Building A or West Wing) listed on the left side and specific areas of the site
(such as R&D lab or Boiler) listed on the right side. Points are listed on the far
right of the tree and are the smallest unit that can be added to a site tree.
Terms and Concepts Important terms and concepts related to a site tree include:
• Book icons represents element of the tree that contain subordinate elements.
In Figure 9-1, for example, the 1ST FLOOR book indicates that some
number of building components (either points or smaller divisions of the
building) are contained within it. A plus (+) sign to the left of a closed book
indicates that the contents of the element are not currently displayed.
Conversely, a minus (-) sign to the left of an open book indicates that the
contents of the element are currently displayed.
9-2
firealarmresources.com
Overview, Continued
The Site Tab Selecting the Site Tab displays a window similar to the one shown in Figure 9-2.
The left side of the window is the area in which the site tree is created. The
right side of the window lists the points that can be added to the site tree.
Use the View button shown at the top of the points list to change, filter,
and sort the way in which points are displayed in the list. You can sort and filter
the Points list as follows:
1. Click on the View button. A dialog similar to the one shown in Figure 9-3
appears.
9-3
firealarmresources.com
Overview, Continued
Figure 9-3
c. Click on the Device drop down list box. This selection allows you to
display only points with a specific device type. Choose All to see all
points.
d. Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.
9-4
firealarmresources.com
Building a Site Tree
• Each building
• Each floor within the building
• Each component (office, lab, hallway, duct, etc.) of each floor that contains
points
Step 1. Add the Buildings 1. Right click on the blank portion of the Site screen. When the list of choices
appears, select Insert Level.
2. Double click on *Level* and type the building name in the text entry box.
The name must be 10 characters or less.
3. To add an additional building, right click on the entry that you just added
(the building ) and select Insert Level.
Insert Level adds an element to the tree that is equal to the currently
selected element. In this case, another entry that is equal to the building.
1. Right click on the entry that represents a building. When the list of choices
appears, click on Insert Leaf.
An entry, containing a Page icon and the word *Leaf*, appears. This entry
is indented to the right of the building entry.
2. Double click on *Leaf* and enter the name of the floor. The text
description must be 10 characters or less.
Repeat Steps 3 and 4, highlighting the icons for other buildings as necessary, to
add all other floors.
9-5
firealarmresources.com
Building a Site Tree, Continued
Step 3. Add Floor Floor components – such as offices, hallways, ducts, etc. – are added by first
Components selecting the floor to which you want to add the components and then selecting
Insert Leaf, as follows:
1. Double click on the floor to which you want to add components. A menu of
options appears.
A line containing a page icon, followed by the label *Leaf*, appears. This
line is beneath and to the right of the highlighted floor.
3. Double click on *Leaf*. Enter a name for the floor in the text entry box.
The name must be 10 characters or less.
Repeat these steps, choosing different floors as required, to add other floor
components.
1. Move to the list of points on the right side of the screen. Click on the point.
A page icon, containing a + sign appears.
2. Drag the point into the site tree, positioning it over the floor component to
which it should be added.
3. Release the mouse button. The point is added to the floor component.
Repeat these steps until all points are added to the site tree.
9-6
firealarmresources.com
Chapter 10
Creating Custom Control Equations
In this Chapter The remainder of this chapter discusses the following topics:
Custom Control
Overview – CC Tab 10-2
Overview – Components of a CC Equation 10-4
Step 1. Add a New Equation to the User Program 10-6
Step 2. Add Additional Inputs and Outputs to an 10-7
Equation
Step 3. Edit Each Input Statement’s Properties 10-8
Step 4. Edit an Output Statement’s Properties 10-19
10-1
firealarmresources.com
Overview – CC Tab
CC Tab The CC Tab, shown in Figure 10-1, provides a graphical means of adding and
editing custom control equations. Points appear in a list on the right side of the
CC window and equations appear on the left side of the window.
Use the View button shown at the top of the points list to change, filter,
and sort the way in which points are displayed in the list. You can sort and filter
the Points list as follows:
1. Click on the View button. A dialog similar to the one shown in Figure 10-2
appears.
10-2
firealarmresources.com
Overview – CC Tab, Continued
Custom Control
c. Click on the Device drop down list box. This selection allows you to
display only points with a specific device type. Choose All to see all
points.
d. Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.
10-3
firealarmresources.com
Overview – Components of a CC Equation
Introduction Up to 60 Custom Control equations can be programmed for the 4010. Each
equation consists of two sides: an INPUT SIDE, containing one or more Input
Statements and an OUTPUT SIDE, containing one or more Output Statements.
The total number of statements, both input and output must be 6 or less.
Input Statement
Input Statement
Equation End of Inputs
Output Statement
Output Statement
End of Outputs
Multiple input statements, located within the same equation, must be separated
by a logical operator (AND or OR). These operators function as follows:
• AND Operator. Use the AND Logical operator to link the current input
statement in Series with all previous input statements in an equation. In the
example below, IF the condition of M1-1 is Fire AND the condition of M1-
2 is Fire, then the INPUT SIDE is true and the Output statements (not
shown) execute. If, however, only M1-1 or M1-2 (not both) is in a Fire
state, the INPUT side is not true and the output statements do not execute.
10-4
firealarmresources.com
Overview – Components of a CC Equation, Continued
Input Statements (continued) • OR Operator. The OR Logical operator links the current statement in
Parallel with all previous statements in an equation. In the example below,
IF the condition of M1-1 is Fire OR the condition of M1-2 is Fire, then the
INPUT SIDE is true. In other words, when the status of either M1-1 or M1-
2 becomes Fire, the output statements execute.
Custom Control
Output Statements Output statements are the actions that occur when the INPUT Side of an
equation is true. An output consists of an Opcode, the point associated with the
Opcode, and a priority.
10-5
firealarmresources.com
Step 1. Add a New Equation to the User Program
Procedure All user-defined CC equations are stored within the User Program, which is
represented by an icon on the left side of the screen. Follow these steps to add a
new equation to the User Program.
1. Right click on the User icon. See Figure 10-4 for its location.
10-6
firealarmresources.com
Step 2. Add Additional Inputs and Outputs to an Equation
Introduction Each equation can have up to 6 inputs or outputs in it. Follow these steps to add
additional inputs/outputs to the equation. If the equation appears as a book with
a plus (+) sign to the left of it, click on the + sign to expand the equation.
Adding Additional Inputs 1. Highlight one of the equation’s existing input statements and click the right
mouse button.
Custom Control
Adding Additional Outputs 1. Highlight one of the equation’s existing output statements and click the
right mouse button.
10-7
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties
Introduction An input’s properties specify the behavior of the input (i.e. what operation or
function does the input perform). Properties also define how inputs function in
relation to other inputs. Input Properties are set through the Custom Control
Input dialog. Follow these steps to open this dialog.
1. Highlight one of the equation’s input qualifiers and click the right mouse
button. A menu of choices appears.
3. Use the AND / OR logical operators to specify whether the input is in series
(AND radio button) or parallel (OR radio button) with all other inputs. If
the Equation has only a single input, skip this step.
4. Use the NOT Operator to specify that the condition must not be true for the
output to execute. In the following example, the input side of the equation
is true if the condition of M1-1 is Fire and the condition of M1-2 is NOT
fire.
5. Click on the Opcode and Qualifier list boxes and choose an Opcode and
qualifier. Refer to Table 10-1 for a list of Opcodes and qualifiers.
10-8
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
Associating Points with Input After defining the Opcode and Qualifier for an input statement, you need to
Statements associate a point with the statement. To do this, follow these steps.
1. In the list on the right side of the screen, click on the name of the point.
2. Hold down the left mouse button and drag the highlighted point from the
list to the appropriate Input Statement.
Custom Control
10-9
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
Input Opcodes and Qualifiers Table 10-1 lists the opcodes and their qualifiers and explains their use.
10-10
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
Custom Control
The input condition is TRUE when the physical state of the
referenced point is abnormal (current limited). One typical
use for this qualifier is to verify the physical location of a fire
in high-rise building. Once the location of the fire is
Physical Abnormal determined (i.e., locate the detectors with a Physical
Abnormal state), the output side of the equation can be
used to pressurize only the floor(s) with detectors in this
state, and ignore any pull stations (which may or may not
be on the fire floor).
The input condition is TRUE when the physical state of the
Physical Open
referenced point (or its wiring) is open.
The input condition is TRUE when the physical state of the
Point Status – Physical Short
referenced point (or its wiring) is short.
Allows the status of
a specific point to be The input condition is TRUE when the state of the
Disable
tested for a specific referenced point is disabled.
condition.
The input condition is TRUE when the state of the
Class A Trouble
referenced point is a Class A Trouble.
The input condition is TRUE when a signal circuit (NAC) or
relay is ON or coding (i.e., sounding/flashing in march time,
ON / Coding
temporal, etc.). A typical use for this qualifier is to use the
relay or NAC as a switch for some other action.
The input condition is TRUE when a signal circuit (NAC) or
OFF
relay is OFF. Also used as a switch for some other action.
The input condition is TRUE when an IDNet sounder or
Control On
relay base is ON.
The input condition is TRUE when an IDNet sounder or
Control Off
relay base is OFF.
Input condition is TRUE when the average value for the
Dirty referenced point exceeds the fixed threshold (120 analog
units).
Input condition is TRUE if the referenced point is a list and
Empty
it is empty.
10-11
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
Fire Detect
ANY/ALL – Used Using a list to implement resound allows a large number of
only with Lists. Note devices to be monitored by a limited number of equations.
that with the ANY Since the maximum number of equations is limited to 60,
Opcode you can lists provide an efficient way of implementing many system
specify how many features.
points within the list
must meet the ALL Opcode. Input condition is TRUE for ½ second only if
criteria for the input ALL points within the list are in alarm.
condition to be true.
ANY Opcode. When any point within the list (pull stations
or detector type device) enters an alarm condition, the input
condition is TRUE until a System Reset is performed.
Fire
ALL Opcode. All devices within the list must enter an
alarm condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until a System Reset is
performed.
10-12
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
Custom Control
supervisory condition for the input condition to be TRUE. If
this occurs, the input condition is TRUE until all problem
conditions are fixed.
ANY Opcode. When any point within the list enters an
alarm condition, the input condition is TRUE until the alarm
is acknowledged.
Fire Ack
ALL Opcode. All devices within the list must enter an
alarm condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until the alarms are
acknowledged.
ANY/ALL – Used ANY Opcode. When any point with the list enters a
only with Lists. Note supervisory condition, the input condition is TRUE until the
that with the ANY problem condition is fixed.
Opcode you can
Supervisory
specify how many ALL Opcode. All devices within the list must enter an
points within the list supervisory condition for the input condition to be TRUE. If
must meet the this occurs, the input condition is TRUE until all problem
criteria for the input conditions are fixed.
condition to be true.
ANY Opcode. When any point within the list enters a
trouble condition, the input condition is TRUE until the
trouble condition is fixed.
Trouble
ALL Opcode. All devices within the list must enter a
trouble condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until all trouble conditions are
fixed.
ANY Opcode. When any point within the list enters a
supervisory condition, the input condition is TRUE until the
supervisory condition is acknowledged.
Supervisory Ack
ALL Opcode. All devices within the list must enter a
supervisory condition for the input condition to be TRUE. If
this occurs, the condition is TRUE until all alarms are
acknowledged.
10-13
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
ALL Opcode. The state of all devices within the list must
be Physical Abnormal for the input condition to be TRUE.
Physical Open ANY Opcode. The input condition is TRUE when the
physical state of any point within the list (or any point’s
wiring) is open.
ALL Opcode. The circuit state of all devices within the list
must be open for the input condition to be TRUE
Physical Short ANY Opcode. The input condition is TRUE when the
physical state of any point within the list (or any point’s
wiring) is shorted.
ALL Opcode. The circuit state of all devices within the list
must be shorted for the input condition to be TRUE
10-14
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
Custom Control
ANY Opcode. The input condition is TRUE when any
signal circuit (NAC) or relay within a list is ON or coding
(i.e., sounding/flashing in march time, temporal, etc.). A
On/Coding typical use for this qualifier is to use the relay or NAC as a
switch for some other action.
ALL Opcode. All signal circuits or NACs within the list
ANY / ALL – Used must be ON or coding for the input condition to be TRUE.
only with Lists. Note
that with the ANY ANY Opcode. Used to override any programming in the
Opcode you can system. Typically used by inspectors to override
specify how many programming that triggers signals, elevator capture, door
points within the list drop, etc. The input condition is TRUE if any point within
must meet the the list is ON.
On Input
criteria for the input All Opcode. Used to override any programming in the
condition to be true. system. Typically used by inspectors to override
programming that triggers signals, elevator capture, door
drop, etc. The input condition is TRUE if all points within
the list are ON.
Any Opcode. The input is TRUE if any point within the list
has been manually overridden (i.e., controlled from the
panel).
Manual Override
All Opcode. The input is TRUE if all points within the list
have been manually overridden (i.e., controlled from the
panel).
10-15
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
10-16
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
Custom Control
referenced photo smoke detector exceeds 1.5 %.
Smoke level 2.0 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 2.0 %.
Smoke level 2.5 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 2.5 %.
Smoke level 3.0 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 3.0 %.
Smoke level 3.7 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 3.7 %.
Smoke level 0.5 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 0.5 %.
ION Smoke Level
Smoke level 0.9 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 0.9 %.
Smoke level 1.3 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 1.3 %.
Smoke level 1.7 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 1.7 %.
Smoke level 0.2 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
XPHOTO Smoke 0.2 %.
Level
Smoke level 0.5 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
0.5 %.
Smoke level 1.0 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
1.0 %.
Smoke level 1.5 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
1.5 %.
10-17
firealarmresources.com
Step 3. Edit Each Input Statement’s Properties, Continued
XPHOTO Smoke Smoke level 2.5 Input statement is TRUE when the smoke level for the
Level referenced extra-sensitive photo smoke detector exceeds
2.5 %.
Smoke level 3.7 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
3.7 %.
10-18
firealarmresources.com
Step 4. Edit Each Output Statement’s Properties
Procedure An output’s properties specify what occurs (for example, a limited set of
strobes/horns activate) when the Input Side of the CC Equation is True. Output
Properties are set through the Custom Control output dialog. Follow these steps
to open this dialog.
1. Highlight one of the equation’s output qualifiers and click the right mouse
button. A menu of choices appears.
Custom Control
Figure 10-6. Custom Control Output Dialog
10-19
firealarmresources.com
Step 4. Edit Each Output Statement’s Properties, Continued
Procedure (continued)
Table 10-2. Output Opcodes and Qualifiers (continued)
ON When the input side of the equation is true, the output turns
ON. When the input is false, the output turns OFF.
OFF When the input side of the equation is true, the output turns
Track OFF. When the input is false, the output turns ON.
PRI When the input side of the equation is true, the priority is
changed to a value that you specify. When the input is
false, the priority returns to its original value.
On When the input side of the equation is True, Set turns the
point referenced on the output side of the equation ON.
The point stays ON until a Set OFF command occurs.
OFF When the input side of the equation is True, Set turns the
Set point referenced on the output side of the equation OFF.
The point stays OFF until a Set ON command occurs.
PRI When the input side of the equation is True, Set turns the
point referenced on the output side of the equation ON.
The point stays ON until a Set OFF command occurs.
10-20
firealarmresources.com
Step 4. Edit Each Output Statement’s Properties, Continued
Procedure (continued)
Custom Control
Constant When the input side of the equation is true, the referenced
Pulse point pulses for the specified amount of time (constant
value).
Variable When the input side of the equation is true, the referenced
point pulses for the specified amount of time (variable).
10-21
firealarmresources.com
Step 4. Edit Each Output Statement’s Properties, Continued
Procedure (continued)
Table 10-2. Output Opcodes and Qualifiers (continued)
117° Fahrenheit When the input side of the equation is true, the threshold
level for the heat detector is set to 117 degrees F.
135° Fahrenheit When the input side of the equation is true, the threshold
Set Heat Threshold
level for the heat detector is set to 135 degrees F.
155° Fahrenheit When the input side of the equation is true, the threshold
level for the heat detector is set to 155 degrees F.
3° C / minute When the input side of the equation is true, the threshold
level for the ROR heat detector is set to 3° C / minute.
15° F / minute When the input side of the equation is true, the threshold
Set ROR
level for the ROR heat detector is set to 15° C / minute.
20° F / minute When the input side of the equation is true, the threshold
level for the ROR heat detector is set to 20° C / minute.
Smoke Level 0.5 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 0.5.
Smoke Level 0.9 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 0.9.
Set ION Threshold
Smoke Level 1.3 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 1.3.
Smoke Level 1.7 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 1.7.
10-22
firealarmresources.com
Step 4. Edit Each Output Statement’s Properties, Continued
Procedure (continued)
(continued) Table 10-2. Output Opcodes and Qualifiers (continued)
Custom Control
Set XPHOTO When the input side of the equation is true, the threshold
Threshold Smoke Level 1.0 level for the extra-sensitive photo smoke detector is set to
1.0.
When the input side of the equation is true, the threshold
Smoke Level 1.5 level for the extra-sensitive photo smoke detector is set to
1.5.
When the input side of the equation is true, the threshold
Smoke Level 2.0 level for the extra-sensitive photo smoke detector is set to
2.0.
Associating Points with After defining the Opcode and Qualifier for an output statement, you need to
Output Statements associate a point with the statement. To do this, follow these steps.
1. In the list on the right side of the screen, click on the name of the point.
2. Hold down the left mouse button and drag the highlighted point from the
list to the appropriate output Statement.
10-23
firealarmresources.com
White text
firealarmresources.com
Chapter 11
Building and Downloading a Job
Introduction This chapter describes building a 4010 job and downloading it to the 4010 panel.
In this Chapter The remainder of this chapter discusses the following topics:
Building/Downloading Jobs
11-1
firealarmresources.com
Building a Job
Introduction This section describes using the PC Programmer’s Job Builder utility to create a
Configuration Data file (CFIG), and download it to the 4010 FACP.
Using Job Builder The Job Builder utility does the following:
The Job Builder dialog appears, displaying the progress of the job build in
the window.
11-2
firealarmresources.com
Downloading a CFG File to the Panel
Introduction This section describes downloading a CFG file (built job file) from a service PC
to the 4010 FACP. A download occurs over a serial link running between the
panel and the PC. Follow the steps outlined in the following sections to link the
PC to the panel and download the job.
Step 1. Set Panel and PC 1. Set switches SW1 and SW2 to the positions shown in Figure 11-2. These
Serial Communication positions enable a baud rate of 19,200 on the 4010 FACP.
Parameters
19,200
Building/Downloading Jobs
2. Start the 4010 Programmer application.
• Port. Set this radio button to the setting that corresponds to the serial
port on the PC to which the serial cable will be connected. In most
cases, this will be COM1.
• Baud Rate. Set to 19,200.
• Parity. Set to None.
• Stop Bits. Set to 1.
• Data Bits. Set to 8.
11-3
firealarmresources.com
Downloading a CFG File to the Panel, Continued
Step 2. Connect Serial Cable Connect a 733-794 serial cable between a free serial port on the service PC and
between PC and Panel the service port of the 4010 FACP.
1. Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 11-4 to the PC.
2. Connect the other end to the service port on the 4010 FACP. Make sure that
the red stripe is aligned to the left as you connect the cable.
9-Pin Connector
goes to PC
11-4
firealarmresources.com
Downloading a CFG File to the Panel, Continued
Step 3. Enable Download on The 4010 displays the following message to indicate that the panel is ready to
Panel (continued) accept a download.
Step 4. Start Download at PC 1. Click on the Transfer menu. When the selections appear, choose Transfer.
A window similar to the one shown in Figure 11-5 appears.
Building/Downloading Jobs
Figure 11-5. Upload/Download Dialog
2. Select the following radio button options in the window’s panels.
• Download
• Direct
• Panel CFIG
3. Click OK.
The dialog shown in Figure 11-6 appears, prompting you to begin the
download.
11-5
firealarmresources.com
Downloading a CFG File to the Panel, Continued
7. When the following prompt appears, choose Yes to restart the panel.
Note: You must restart the panel from the PC, not the panel. Pressing the
panel’s warm start button causes all downloaded information to be lost.
11-6
firealarmresources.com
Appendix A
Hardware Device Types,
Software Point Types, and Point Addresses
• Hardware Device Types. 4010 hardware device types are listed with their
corresponding PIDs, allowing you to exactly match the equipment used
with the available device types.
• Software Point Types. 4010 point types are grouped into two general
categories:
- Monitor point types are used with monitoring devices, such as smoke
detectors, pull stations, heat detectors, fire pump monitors, etc.
- Control point types are used with signal (notification appliance) and
relay devices.
• Point Addresses and definitions. Each 4010 point has a point address, such
as 1-1 (NAC card signal 1 address). A point address and an understanding
of when the point turns ON and OFF are necessary for referencing points in
Custom Control equations.
A-1
firealarmresources.com
Device Types
Sensor/Base Device Types The hardware device type used for a specific sensor/base combination depends
on the combination. The following table summarizes which point types can be
used with the various combinations of sensor and base.
To use this table, first identify the exact sensor/base combination in use for each
IDNet point. The point at which the column (base) and row (sensor) intersect
contains the device type that you should use for that sensor/base combination.
Ion
ION SION IION N/A N/A RION
Sensor
4098-9717
Heat
HEAT SHEAT IHEAT N/A N/A RHEAT
Sensor
OHEAT SOHEAT IOHEAT ROHEAT
4098-9733
IAMs / ZAMs / IDNet The following table lists the PIDs and corresponding device types for IAMs,
Addressable Device Types ZAMS, and IDNet Addressable devices.
A-2
firealarmresources.com
Control Point Types
AHUF AHU off relay – dual relay control. This point type is used with applications
that use two auxiliary relays for AHU control – one relay for ON and one relay
for OFF. Use this point type for the OFF relay. See AHUO also. If you have a
single relay that performs both ON and OFF functions, see AHUR.
AHUO AHU on relay – dual relay control. This point type is used with applications that
use two auxiliary relays for AHU control – one relay for ON and one relay for
OFF. Use this point type for the ON relay. Points assigned with this type
operate on general alarm. See AHUF also. If you have a single relay that
performs both ON and OFF functions, see AHUR.
AHUR AHU on/off relay – single relay control. This point type is used with
applications in which a single relay performs AHU ON and OFF control. Points
assigned with this type operate on general alarm.
A-3
firealarmresources.com
Control Point Types, Continued
ALTERN Elevator capture – alternate. Used for a relay connected to the elevator controls
to provide alternate floor elevator recall.
BSIGNAL Trouble/supervisory “bell” signal. Used when an audible signal should activate
on any supervisory or trouble condition and remain ON until the condition has
been acknowledged.
DHOLDER Door holder control (normally off). Used when the auxiliary relay is connected
to door holders. The relay energizes on alarm, loss of AC Power, or when
programmed.
A-4
firealarmresources.com
Control Point Types, Continued
PRIMARY Elevator capture – primary. Used for any relay connected to the elevator
controls to provide primary floor elevator recall. By default, these relays pick
on any alarm.
SQALERT SQALERT device type automatically turns on the designated circuit on alarm
detect (general alarm), issues the horn silence command upon Alarm Silence,
and turns off the circuit at the completion of System Reset. Any point
programmed with the SQALERT point type is not available for use in Custom
Control programming.
RELAY Generic relay – no default operation. Used for any relay application that is not
defined by a specific point type.
RSIGNAL Alarm signal – on until reset. Used for any signaling device (such as an audible
or visible notification appliance) that is required to be on until a system reset is
performed. Points assigned with this type operate on general alarm.
A-5
firealarmresources.com
Control Point Types, Continued
RVISUAL Used only with visual notification appliances that must be ON until a system
reset is performed. Points assigned with this type operate on general alarm.
SIGNAL Generic Alarm Signal – on until reset. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm.
A-6
firealarmresources.com
Control Point Types, Continued
SSIGNAL Alarm signal – on until silence. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm.
SVISUAL Visual – on until silence. Used only with visual notification appliances that
must remain ON until an Alarm Silence is performed.
A-7
firealarmresources.com
Control Point Types, Continued
A-8
firealarmresources.com
Monitor Point Types
FIRE This is a generic fire alarm point type. A typical application for this point type
is a fire alarm zone containing more than one type of device. For example,
when a combination of smoke detectors, pull stations, waterflow monitors, and
heat detectors is connected to an IAM or ZAM, this point type allows alarms to
report as originating from a zone.
WATER Used to define the operation of a waterflow monitor for all possible circuit
states.
DUCT Used to define the operation of a duct detector for all possible circuit states.
A-9
firealarmresources.com
Monitor Point Types, Continued
EMERG Use for an emergency monitor zone in which two types of alarm devices – for
example, emergency alarm devices such as Nurse Call and fire alarm devices --
are connected to an IAM or ZAM. Emergency devices require the use of a
current limiting resistor. These devices generate an Emergency Alarm condition
at the panel.
SFIRE Used when smoke detectors and shorting type devices are connected to an IAM
or ZAM.
A-10
firealarmresources.com
Monitor Point Types, Continued
VFIRE Used to activate the alarm verification software for all smoke detectors
connected to an IAM or ZAM. Shorting type devices cause an immediate alarm.
SPULL Used when smoke detectors and pull stations are connected to an IAM or ZAM.
VSPULL Used when smoke detectors that must be verified and pull stations are connected
to an IAM or ZAM.
GENMON Used when emergency generator monitoring is required. The shorted condition
of the circuit indicates an abnormal status and is indicated by the Supervisory
Service LED. The current limited condition of the circuit indicates that the
generator is running, and can be tracked with an LED (must be programmed). A
current limiting resistor must be installed for this to happen.
SGENMON Same operation as the GENMON point type, but the generator running condition
automatically displays and requires operator acknowledgment.
A-11
firealarmresources.com
Monitor Point Types, Continued
FPUMP Used to monitor fire pump conditions. The shorted condition indicates that the
fire pump is abnormal. The current limited condition indicates that the fire
pump is running.
SFPUMP Same as the FPUMP point type, except that the fire pump running condition
requires operator acknowledgment.
S2STAGE Used for 2-stage alarms. The current limited operation of any device indicate a
Stage 1 Alarm. A short on the point’s circuit, such as a key switch operation,
causes a Stage 2 Alarm.
A-12
firealarmresources.com
Monitor Point Types, Continued
A-13
firealarmresources.com
Monitor Point Types, Continued
SUPV Used to monitor any supervisory type device where operator acknowledgment is
required.
UTIL Used to monitor and supervise any condition; operator acknowledgment is not
required. No alarm is generated by this point type.
TROUBLE Used for trouble monitoring only. No alarm is generated by this point type.
VSMOKE Used with smoke detectors whose alarm status must be verified.
GVMON Used when the abnormal condition of the circuit must be verified.
A-14
firealarmresources.com
Monitor Point Types, Continued
LATSUPV Supervisory Monitor – latch until reset. Used for generic supervisory alarm.
STYLEC Style-C Fire Alarm Monitor. Used when only current limited devices are
connected to the zone. A short circuit is reported as a Trouble.
A-15
firealarmresources.com
Monitor Point Types, Continued
A-16
firealarmresources.com
24 Point I/O Point Types
USWITCH 2-position switch, unsupervised. Used for a 2-position switch without an EOL
or current limited resistor.
SSWITCH 2-position switch, supervised for opens and shorts. Requires EOL and current
limited resistors.
TSWITCH 3-position (SPDT) switch, supervised for opens. Requires EOL and series
current limiting resistors (up leg).
A-17
firealarmresources.com
Addresses for Hardware Points
The 4010 FACP contains many different types of points -- including read-only
system points, IDNet channel points, points on optional cards, digital and analog
pseudo points, list points, and card status (trouble) points. Many of these points
may be referenced , using the point’s address, in Custom Control equations.
Master Controller (SFIO) The Master Controller (SFIO) card resides at card address 0 and contains 13
Hardware Points hardware points. In the table, each point has a type of R or U. Points listed with
a type of R are reserved system points. Points with a type of U are user-
configurable.
A-18
firealarmresources.com
Addresses for Hardware Points, Continued
NAC Card Hardware Points The NAC has 7 hardware points associated with it. Of the 7 hardware points, 6
are points which may be programmed by the user. The other point is the City
Circuit point which is not available for programming or viewing by the user.
The following table is a list of the points on the NAC card. The type field
denotes which class the point falls into (S=System point that is not available to
the user for viewing or programming , U=User Configurable Points).
Power Supply Card The Power Supply Card is required for all 4010 configurations, and is located at
card address 2. There are 9 hardware points associated with the Power Supply
card, all of which are system points that cannot be modified by the user. The
A-19
firealarmresources.com
Addresses for Hardware Points, Continued
IDNet Card The IDNet Card is required for all 4010 configurations, and is located at card
address 3. The IDNet Card defaults to a configuration with no hardware points
(devices). However, up to 250 devices may be programmed for the IDNet Card.
The IDNet Card also includes eight card status points.
The IDNet card can have up to 250 devices configured. All of the IDNet
devices can be modified by the user. How the point is configured (i.e. software
point type) will determine what action will be taken (trouble, alarm, etc.) when
the point changes state. The following table is a list of the points that may be
included on the IDNet card. The labels indicated for the points are the default
labels assigned when the point is added from the front panel.
RS232\Modem Card Either an RS232 Card or Modem Card may be added to the 4010 system. Even
though these cards are optional, if an RS232 or Modem card is configured, it
must reside at card address 4. There are two hardware points associated with
them. Both of the RS232/Modem points are user configurable. However, the
points have no labels associated with them, because they cannot be viewed on
the front panel. The following table is a list of the points on the RS232/Modem
cards.
A-20
firealarmresources.com
Addresses for Hardware Points, Continued
RS232\Modem Card
(continued) Point Label Description
4-1 None Port A point. Default to unsupervised 80
character Printer port.
4-2 None Port B point. Default to command line port.
SDACT Card The SDACT card is an optional card that may be added to the 4010 system. The
SDACT card is mutually exclusive with the Network card, and if configured,
must reside at address 8. There is one hardware point associated with the
SDACT card. The point does not have a label, and cannot be viewed from the
front panel.
Network Card The Network card is an optional card that may be added to the 4010 system.
The Network card is mutually exclusive with the SDACT card, and if
configured, must reside at address 8. The network card allows the 4010 to serve
as a network node for a 4120 network. Points on the 4010 may be declared
public to the 4120 network. These points are the Network Status points, and
will be described in this section.
The Network card can have up to 511 Network points configured. The
following table is a list of the points that may be configured on the Network
card. The Common Trouble Point is the only default point for the Network card.
A-21
firealarmresources.com
Addresses for Hardware Points, Continued
24 Point I/O Card The 4010 can have up to six annunciator cards added to the system. One of
these cards is the 24IO card. The 24IO card can reside at addresses 9 through
14.
Each 24I/O card has 24 hardware points associated with it. The user can
program all hardware points on the 24I/O card. The functionality of the point
depends on the device type (Input or Output), the point type, and modes
programmed against it. The labels for the points on the 24I/O card are default
labels, and cannot be changed by the user. The following table describes the
organization of points on the 24I/O card. In this table, card represents the card
address (9-14) of the 24 I/O card.
LCD Card The 4010 can have up to six annunciator cards added to the system. One of
these cards is the LCD card. The LCD card can reside at addresses 9 through
14. The LCD card has five hardware points associated with it. Only the first
three hardware points (user LEDs) on the LCD card can be programmed by the
user. The labels for the points on the LCD card are default labels, and cannot be
changed by the user. The following table describes the points included on the
LCD card. In this table, card represents the card address (9-14) of the LCD
Annunciator card.
A-22
firealarmresources.com
Addresses for Hardware Points, Continued
4009A Card The 4009A Card, which always resides at card address 17, is a very unique card
in the 4010 system. The 4009A card itself is a pseudo card, which means that
an actual hardware “card” does not exist at address 17. However, unlike other
pseudo cards in the system, the points on the 4009A pseudo card track the status
of actual hardware points. The points on the 4009A Card are used to control and
track the status of the NAC circuits found on all of the 4009A devices
configured in the system. Therefore, the number of configured points on the
4009A Card may vary, depending on the number of 4009A devices configured
in the system. The 4010 can have up to five 4009A devices programmed into
the system, with each 4009A device having up to 8 NAC points, and 8 card
status points associated with it. An overview of how the 4009A points are
configured, and how these points are associated with a specific 4009A device, is
provided in the following sections.
The 4009A “card” can have up to five 4009A devices associated with it. Each
of the 4009A devices can be configured to have 4 or 8 NACs. Regardless of the
configuration of the 4009A device, the 4009A “card” always has room provided
for 8 NACs per device. The labels shown for the points on the 4009A card are
default labels. However, these labels may be changed by the user. The
following table describes the points included on the 4009A “card.” (S=System
point that is not available to the user for viewing or programming , U=User
Configurable Points.)
A-23
firealarmresources.com
Addresses for Hardware Points, Continued
A-24
firealarmresources.com
Addresses for Pseudo Points
Introduction There are three types of pseudo points that exist in every system. They include
digital, analog, and list pseudo. Each of these types may be referenced in
Custom Control in both the input and output sides of an equation. Reserved
system pseudo points are used to indicate system trouble or alarm indications,
control diagnostics or other system functions, and to communicate information
between the 4010 Master and SMPL. Some pseudos are set by the system and
are read only to the user. Other pseudos are either set from SMPL or from the
front panel as a cue for the system to perform some operation.
Digital Pseudo Points Every 4010 system has two Digital Pseudo “cards” at addresses 18 and 19. The
first card is reserved for system pseudo points while the second is available to
the user. Each contains 75 digital pseudo points which may be programmed as
follows:
Type Description
UTILITY Utility point (ON/OFF - no acknowledge required)
ALARM Fire alarm point. Turning the point on causes an ALARM
condition.
SUPV Supervisory point.
TROUBLE Trouble point.
Each system digital pseudo point falls into one of the following categories:
Class Description
R Point is controlled by the 4010 master and is read only to the
end user.
RW Point is controlled by the 4010 master, but may also be
controlled by the end user (front panel or SMPL).
W Point is controlled by the end user and is read by the 4010
Master in order to accomplish some function or operation.
A-25
firealarmresources.com
Addresses for Pseudo Points, Continued
A-26
firealarmresources.com
Addresses for Pseudo Points, Continued
A-27
firealarmresources.com
Addresses for Pseudo Points, Continued
A-28
firealarmresources.com
Addresses for Pseudo Points, Continued
4010 User Digital Pseudos The user digital pseudo card in the 4010 is at address 19. It has 75 points
available for specialized applications programming. Any point may be
programmed as one of the four types of digital pseudos (i.e. UTILITY, FIRE,
etc.), and each may be assigned a 40 character custom label.
Note that any user pseudo points defined as FIRE type are not auto-generated in
the General Alarm List (L1), and SUPERVISORY points are not generated into
the Supervisory Monitor List (L8).
Analog Pseudo Points Analog pseudo points exist as counters or timers in the 4010 system. SMPL
delay and cycle equations may be written referencing the user Analog pseudo
points on the output side (for delay/cycle operations). Each analog point may
contain a value from 0-65,535 and the point is considered ON when the value is
non-zero. For delay and cycle purposes, the maximum allowable value gives a
real-time range of just over 18 hours. There are two analog pseudo cards in the
4010 system - one reserved for system analogs, and one reserved for user points.
4010 System Analog Pseudos The 4010 system has one analog pseudo card reserved for system use at address
20. It contains a total of 25 points. At present, only the first 12 are used but the
remainder are reserved for future expansion.
4010 User Analog Pseudos The user analog pseudo card in the 4010 is at address 21. It has 25 points
available for specialized applications programming. The analog user pseudos
can have custom labels assigned to them.
A-29
firealarmresources.com
Addresses for Pseudo Points, Continued
List Pseudo Points List psuedo points provide a convenient way to group points in any manner the
user desires. The 4010 contains two list pseudo cards - one reserved for the
system and one for the user. The status of the list is determined by counts which
are maintained for the following states:
• Fire Count
• Trouble Count
• Supervisory Count
• Normal
• Open
• Limited
• Short
• Fire Ack
• Trouble Ack
• Supervisory Ack
• Disable
• On/Input
• On/Coding
• Manual Control
The 4010 restricts the total number of points in any one list to 255. It also
restricts the total number of points available on any one list card to 500 (the total
number of points in all lists on one list card cannot exceed 500).
4010 System Lists The 4010 system reserves one list card at address 22 for system use. Currently,
12 of the 25 system lists are used by the 4010 application. All of these lists
control application specific operation of the 4010 panel. Some are auto-
generated by the system as points are added and may not be edited, while the
remainder are filled by the user to activate pre-defined applications. The system
lists are shown below:
A-30
firealarmresources.com
Addresses for Pseudo Points, Continued
4010 User Lists The user list pseudo card in the 4010 is at address 23. It has 25 points available
that may be filled by the user for specialized applications. The user lists may
have custom labels assigned to them.
A-31
firealarmresources.com
This page intentionally blank
firealarmresources.com
Appendix B
Conversion Table
Conversion Table
Introduction This appendix contains the Base 10 to Base 36 Conversion Table. Use this table
to convert your Base 10 branch and job numbers to the Base 36 format required
by the Programmer (see Chapter 2).
B-1
firealarmresources.com
Base 10 to Base 36 Conversion Table
Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
0 0 50 1E 100 2S 151 47 201 5L
1 1 51 1F 101 2T 152 48 202 5M
2 2 52 1G 102 2U 153 49 203 5N
3 3 53 1H 103 2V 154 4A 204 5O
4 4 54 1I 104 2W 155 4B 205 5P
5 5 55 1J 105 2X 156 4C 206 5Q
6 6 56 1K 106 2Y 157 4D 207 5R
7 7 57 1L 107 2Z 158 4E 208 5S
8 8 58 1M 108 30 159 4F 209 5T
9 9 59 1N 109 31 160 4G 210 5U
10 A 60 1O 110 32 161 4H 211 5V
11 B 61 1P 111 33 162 4I 212 5W
12 C 62 1Q 112 34 163 4J 213 5X
13 D 63 1R 113 35 164 4K 214 5Y
14 E 64 1S 114 36 165 4L 215 5Z
15 F 65 1T 115 37 166 4M 216 60
16 G 66 1U 116 38 167 4N 217 61
17 H 67 1V 117 39 168 4O 218 62
18 I 68 1W 118 3A 169 4P 219 63
19 J 69 1X 119 3B 170 4Q 220 64
20 K 70 1Y 120 3C 171 4R 221 65
21 L 71 1Z 121 3D 172 4S 222 66
22 M 72 20 122 3E 173 4T 223 67
23 N 73 21 123 3F 174 4U 224 68
24 O 74 22 124 3G 175 4V 225 69
25 P 75 23 125 3H 176 4W 226 6A
26 Q 76 24 126 3I 177 4X 227 6B
27 R 77 25 127 3J 178 4Y 228 6C
28 S 78 26 128 3K 179 4Z 229 6D
29 T 79 27 129 3L 180 50 230 6E
30 U 80 28 130 3M 181 51 231 6F
31 V 81 29 131 3N 182 52 232 6G
32 W 82 2A 132 3O 183 53 233 6H
33 X 83 2B 133 3P 184 54 234 6I
34 Y 84 2C 134 3Q 185 55 235 6J
35 Z 85 2D 135 3R 186 56 236 6K
36 10 86 2E 136 3S 187 57 237 6L
37 11 87 2F 137 3T 188 58 238 6M
38 12 88 2G 138 3U 189 59 239 6N
39 13 89 2H 139 3V 190 5A 240 6O
40 14 90 2I 140 3W 191 5B 241 6P
41 15 91 2J 141 3X 192 5C 242 6Q
42 16 92 2K 142 3Y 193 5D 243 6R
43 17 93 2L 143 3Z 194 5E 244 6S
44 18 94 2M 144 40 195 5F 245 6T
45 19 95 2N 145 41 196 5G 246 6U
46 1A 96 2O 146 42 197 5H 247 6V
47 1B 97 2P 147 43 198 5I 248 6W
48 1C 98 2Q 148 44 199 5J 249 6X
49 1D 99 2R 149 45 200 5K 250 6Y
B-2
firealarmresources.com
Base 10 to Base 36 Conversion Table, Continued
Conversion Table
Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
251 6Z 301 8D 351 9R 401 B5 451 CJ
252 70 302 8E 352 9S 402 B6 452 CK
253 71 303 8F 353 9T 403 B7 453 CL
254 72 304 8G 354 9U 404 B8 454 CM
255 73 305 8H 355 9V 405 B9 455 CN
256 74 306 8I 356 9W 406 BA 456 CO
257 75 307 8J 357 9X 407 BB 457 CP
258 76 308 8K 358 9Y 408 BC 458 CQ
259 77 309 8L 359 9Z 409 BD 459 CR
260 78 310 8M 360 A0 410 BE 460 CS
261 79 311 8N 361 A1 411 BF 461 CT
262 7A 312 8O 362 A2 412 BG 462 CU
263 7B 313 8P 363 A3 413 BH 463 CV
264 7C 314 8Q 364 A4 414 BI 464 CW
265 7D 315 8R 365 A5 415 BJ 465 CX
266 7E 316 8S 366 A6 416 BK 466 CY
267 7F 317 8T 367 A7 417 BL 467 CZ
268 7G 318 8U 368 A8 418 BM 468 D0
269 7H 319 8V 369 A9 419 BN 469 D1
270 7I 320 8W 370 AA 420 BO 470 D2
271 7J 321 8X 371 AB 421 BP 471 D3
272 7K 322 8Y 372 AC 422 BQ 472 D4
273 7L 323 8Z 373 AD 423 BR 473 D5
274 7M 324 90 374 AE 424 BS 474 D6
275 7N 325 91 375 AF 425 BT 475 D7
276 7O 326 92 376 AG 426 BU 476 D8
277 7P 327 93 377 AH 427 BV 477 D9
278 7Q 328 94 378 AI 428 BW 478 DA
279 7R 329 95 379 AJ 429 BX 479 DB
280 7S 330 96 380 AK 430 BY 480 DC
281 7T 331 97 381 AL 431 BZ 481 DD
282 7U 332 98 382 AM 432 C0 482 DE
283 7V 333 99 383 AN 433 C1 483 DF
284 7W 334 9A 384 AO 434 C2 484 DG
285 7X 335 9B 385 AP 435 C3 485 DH
286 7Y 336 9C 386 AQ 436 C4 486 DI
287 7Z 337 9D 387 AR 437 C5 487 DJ
288 80 338 9E 388 AS 438 C6 488 DK
289 81 339 9F 389 AT 439 C7 489 DL
290 82 340 9G 390 AU 440 C8 490 DM
291 83 341 9H 391 AV 441 C9 491 DN
292 84 342 9I 392 AW 442 CA 492 DO
293 85 343 9J 393 AX 443 CB 493 DP
294 86 344 9K 394 AY 444 CC 494 DQ
295 87 345 9L 395 AZ 445 CD 495 DR
296 88 346 9M 396 B0 446 CE 496 DS
297 89 347 9N 397 B1 447 CF 497 DT
298 8A 348 9O 398 B2 448 CG 498 DU
299 8B 349 9P 399 B3 449 CH 499 DV
300 8C 350 9Q 400 B4 450 CI 500 DW
B-3
firealarmresources.com
Base 10 to Base 36 Conversion Table, Continued
Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
501 DX 551 FB 601 GP
502 DY 552 FC 602 GQ
503 DZ 553 FD 603 GR
504 E0 554 FE 604 GS
505 E1 555 FF 605 GT
506 E2 556 FG 606 GU
507 E3 557 FH 607 GV
508 E4 558 FI 608 GW
509 E5 559 FJ 609 GX
510 E6 560 FK 610 GY
511 E7 561 FL 611 GZ
512 E8 562 FM 612 H0
513 E9 563 FN 613 H1
514 EA 564 FO 614 H2
515 EB 565 FP 615 H3
516 EC 566 FQ 616 H4
517 ED 567 FR 617 H5
518 EE 568 FS 618 H6
519 EF 569 FT 619 H7
520 EG 570 FU 620 H8
521 EH 571 FV 621 H9
522 EI 572 FW 622 HA
523 EJ 573 FX 623 HB
524 EK 574 FY 624 HC
525 EL 575 FZ 625 HD
526 EM 576 G0 626 HE
527 EN 577 G1 627 HF
528 EO 578 G2 628 HG
529 EP 579 G3 629 HH
530 EQ 580 G4 630 HI
531 ER 581 G5 631 HJ
532 ES 582 G6 632 HK
533 ET 583 G7 633 HL
534 EU 584 G8 634 HM
535 EV 585 G9 635 HN
536 EW 586 GA 636 HO
537 EX 587 GB 637 HP
538 EY 588 GC 638 HQ
539 EZ 589 GD 639 HR
540 F0 590 GE 640 HS
541 F1 591 GF 641 HT
542 F2 592 GG 642 HU
543 F3 593 GH 643 HV
544 F4 594 GI 644 HW
545 F5 595 GJ 645 HX
546 F6 596 GK 646 HY
547 F7 597 GL 647 HZ
548 F8 598 GM 648 I0
549 F9 599 GN 649 I1
550 FA 600 GO 650 I2
B-4
firealarmresources.com
Index
programming, 6-1
programming 24 point I/O, 6-32
Misc. programming AUX relay, 6-11
24 point I/O card, 6-32 programming IDNet, 6-13
24 point I/O cards programming master controller, 6-5
output points, 6-36 programming NAC card, 6-9
4009 IDNet NAC Extender, 1-6 programming pseudo point cards, 6-16
4120 network card CD-ROM
programming, 6-29 installing on a system without, 2-4
installing programmer from CD-ROM, 2-7
CFIG
A building, 11-2
access levels, 5-9 downloading to panel, 11-3
active status reminder system option, 5-7 class A NACs, 6-9
adding cards, 6-4 class B NACs, 6-9
AHJ alarm city circuit programming, 1-7 communication parameters
AHU stagger start system option, 5-5 setting, 3-2
alarm cutout timer system option, 5-4 custom control
alarm pseudo point, 6-18 adding an equation, 10-6
alarm silence/inhibit system option, 5-4 adding inputs and outputs, 10-7
analog system pseudos, 6-18 editing input properties, 10-8
analog user pseudos, 6-19 editing output properties, 10-19
point types for, 6-20 input opcodes, 10-10
AND operator, 10-4 output opcodes, 10-19
archiving jobs, 4-13 overview of equation, 10-4
AutoFill custom control tab, 1-3
and card tab, 6-3 overview, 10-2
and point tab, 7-3 custom labels, 7-11
AUX relay for AUX relays, 6-12
custom labels for, 6-12 for NACs, 6-10
point types for, 6-12 spell check for, 7-3
programming, 6-11
D
B day/night programming, 1-6
backing up jobs, 4-13 deleting cards, 6-4
Base 36 conversion, 4-6 depleted battery system option, 5-4
battery charger trouble, 1-6 and suppression release, 5-6
baud rate, 3-3 device types, 7-5
BIN file, 3-1 for IDNet points, 6-14
connecting download cable, 3-2 NAC, 6-9
default directory for, 3-6 summary of, 1
downloading to panel, 3-1 digital system pseudos, 6-16
required download components, 3-1 door drop on AC fail system option, 5-5
when to download. See door drop on alarm system option, 5-5
building a job, 11-2 download
and warm start, 3-8
BIN file, 3-1
C communication parameters, 3-2
connecting cable, 3-2
card tab, 1-3
connecting cable for, 11-4
and AutoFill, 6-3
enabling on panel, 11-4
overview, 6-2
enabling panel for, 3-4
cards
procedure for, 3-6
4120 network, 6-29
required cable, 3-2
adding and deleting, 6-4
warning about backup and archive, 3-5
dual RS-232 card, 6-22
downloading a CFIG
LCD annunciator, 6-37
IN-1
firealarmresources.com
downloading to panel, 11-3 defined, 9-3
list tab, 1-3
overview, 8-2
E sorting points within, 8-3
Earth ground detect lists
user-defined LED example, 6-7 adding/deleting points, 8-4
EXEC. See BIN file naming, 8-4
existing jobs
opening, 4-7 M
master controller card, 6-5
F menu structure, 1-4
F4 key, 6-3 menus, 1-2
firmware
and compatibility, 1-8 N
floppy disks, 2-4
installing programmer from, 2-7 NACs
function keys and signal operation system option, 5-7
programming user-defined, 6-7 custom labels for, 6-10
device types for, 6-9
point types for, 6-10
G programming NAC card, 6-9
general information
setting, 5-2 O
OR operator, 10-5
I oswitch point type, 6-32
icons, 1-2 overview, 1-1
summary of functions, 1-4 programmer components, 1-2
IDNet card
device types for, 6-14 P
point types for, 6-15
programming, 6-13 panel
installation, 2-1 and Quick CFIG, 4-2
creating floppy disks, 2-4 setting baud rate, 3-3
installing programmer from CD-ROM, 2-7 panel tab, 1-3
required components, 2-1 and general information, 5-3
system requirements, 2-2 and system options, 5-3
passcodes, 5-9
point addresses
J summary of, 1
job number format, 4-6 point tab, 1-3
jobs overview of, 7-2
and older SFIO components, 1-9 point types
archiving, 4-13 24 point I/O input types, 6-32
backing up, 4-13 24 point I/O output types, 6-36
building and downloading, 11-2 defined, 7-8
creating a new job, 4-5 for 24 point I/O, 6-32
downloading to panel, 11-3 for analog user pseudos, 6-20
format of job number, 4-6 for AUX relay, 6-12
opening an existing, 4-7 for IDNet points, 6-15
restoring, 4-13 for user digital pseudos, 6-18
saving, 4-13 NAC, 6-10
uploading from panel, 4-8 summary of, 1
programmer
features of each version, 1-8
L starting, 4-4
LCD annunciator, 6-37 warning about suppression point types, 5-6
leaf pseudo points, 6-16
defined, 9-3 analog system pseudos, 6-18
level analog user pseudos, 6-19
IN-2
firealarmresources.com
digital system pseudos, 6-16 system defined list pseudos, 6-20
system defined list pseudos, 6-20 system options, 5-3
user digital pseudos, 6-17 active status reminder, 5-7
user-defined list pseudo points, 6-21 AHU stagger start, 5-5
alarm cutout timer, 5-4
alarm silence inhibit, 5-4
Q depleted battery, 5-4
QALERT device type, 1-7 door drop on AC fail, 5-5
Quick CFIG, 1-7 door drop on alarm, 5-5
procedure for new panels, 4-2 signal operation, 5-7
TrueAlert Non-Addressable NAC devices, 1-7 suppression release, 5-6
alarm operation, 1-7 time format, 5-3
and Quick CFIG, 1-7
and signal operation system option, 5-7 T
horn operation for, 1-7
SMPL programming of, 1-7 tabs, 1-2
overview of, 1-3
time format system option, 5-3
R trouble pseudo point, 6-18
related documents, 1-1 tswitch point type, 6-32
restoring jobs, 4-13
RS-232 card U
configuring, 6-22
RS-232 service modem card upgrade, 2-1, 2-7
programming, 6-24 compatibility, 1-8
service modem commands for, 6-26 uploading jobs, 4-8
and baud rate, 4-8
communication parameters, 4-8
S procedure for, 4-8
saving jobs, 4-13 user digital pseudos, 6-17
setting baud rate, 3-3 point types for, 6-18
SFIO board user-defined function keys, 6-7
and compatibility, 1-8 user-defined LED
SFIO card, 6-5 Earth ground detect example, 6-7
programming user-defined function keys, 6-7 waterflow indicator example, 6-6
programming user-defined LEDs on, 6-5 user-defined LEDs, 6-5
signal operation system option, 5-7 user-defined list pseudos, 6-21
single station uswitch point type, 6-32
setting, 6-15 utility pseudo point, 6-18
site tab, 1-3 utility temperature sensing, 1-6
overview, 9-3
site tree V
building, 9-5
overview, 9-2 Version 2.x features, 1-6
SMPL programming
QALERT device type, 1-7
software key, 2-3
W
SQALERT device type, 1-7 warm start
sswitch point type, 6-32 and download, 3-8
stagger start system option, 5-5 waterflow indicator
starting the programmer, 4-4 user-defined LED example, 6-6
supervisory pseudo point, 6-18
suppression release system option, 5-6
IN-3
firealarmresources.com
This page intentionally blank
firealarmresources.com
This page intentionally blank
firealarmresources.com
Rev. C Simplex Time Recorder Co., • Simplex Plaza • Westminster, Massachusetts 01441-0001 U.S.A. 574-187
Simplex International Time Equipment, Co., LTD. • Mississauga, Ontario, Canada
firealarmresources.com