CHH 018 13
CHH 018 13
Model Remarks
208 V 230V
CHH018CD-13 R410A
Models & specifications
Model CHH18CD-13
Function Cooling & Heating
Working Temp. Range (Indoor) 60.8o F-86oF
Operation Condition Range (Outdoor)(cooling/heating) 60.8~129/32~75.2
19
o
F
Power supply 208-230V/1Phase/60Hz
Rated current (A)(Cooling/Heating) 6.14/8.18
LRA of compressor (A) 27
Fuse or Breaker (A) 220
Refrigerant and Charge* (Oz) R410a,61.73
Size of power supply wire AWG12
Size of connecting wire between condenser and evaporator AWG18
Piping connection (Gas/Liquid) (inch) (5/8 / 3/8)
Maximum line run (ft) 82
Maximum elevation between condenser and evaporator (ft) 39
Climate type T1
Waterproof level IP×4
Net weight (indoor/outdoor) (lb) 28.7/130
Dimension (inch) Indoor unit 40.15×12.2×8.94Outdoor unit 37.4×13.39×26.93
* The pre-charged refrigerant is good for 26 feet line set. For the system required longer line set than 26 feet, please add
additional 0.27 Oz /ft refrigerant into the system.
*The working pressure of suction line:145PSI(Cooling)/435PSI(Heating)
Comfortstar Plus
Model CHH018CD-13
Function COOLING HEATING
Rated Voltage 208 V̚230V
Frequency(Hz) (High/Standard ) 60HZ
Total Capacity (W) (High/Standard ) 5300 5800
Total Capacity (Btu/h) (High/ Standard) 18000 20000
Nominal Power (W) 1350 1800
Max Input (W) 2440 2440
Rated Current (A) 6.14 8.18
Air Flow Volume (m 3/h) (H/M/L) 800
Dehumidifying Volume (l/h) 1.2
SEER / HSPF 13.2 7.7
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Comfortstar Plus
3 Component Name
Bjs!Jomfu
Indoor unit
Sfdfjwjoh!xjoepx
Xsbqqjoh!Ubqf
GspouQbofm
Hvjef!mpvwfs Bjs!Pvumfu MFE!Cpbse
Xbmm!Qjqf
Xjsfmftt!sfnpuf!dpouspm
Outdoor Unit
Ajs!jomfu
Esbjobhf!iptf
Dpoofdujpo!qjqf
boe! dpoofdujpo! xjsf
Bjs!Pvumfu
Air inlet
Indoor unit
Sfdfjwjoh!xjoepx
GspouQbofm Xsbqqjoh!Ubqf
Hvjef!mpvwfs MFE!Cpbse
Air Outlet
Xbmm!Qjqf
Xjsfmftt!sfnpuf!dpouspm
Outdoor Unit
Ajs!jomfu
Esbjobhf!iptf
Dpoofdujpo!qjqf
boe! dpoofdujpo! xjsf
!
Bjs!Pvumfu
Comfortstar Plus
For: CHH018CD-13
Unit: mm
Rear View
rear panel
Comforstar Plus
Unit: mm
Bolt
Nut
Wrench
5 Electrical Diagram
In case of any chang in the electrical diagram shown above,please follow the drawing on
INCASE
the cabinet
Main functions for indoor unit Main functions for outdoor unit
Mode
COOL HEAT DRY FAN AUTO
Wave filter and protection
Detecting indoor room temp. for power supply
Indoor room temp. sensor (15K ), Detecting outdoor ambient temp.
dispart voltage resistance( 15K )
Outdoor ambient temp. sensor (15K ),
Indoor pipe temp. sensor (20K ),
dispart voltage resistance( 20K ) dispart voltage resistance( 15K )
Temp. control Outdoor pipe temp. sensor (20K ),
Making indoor room temp. reach the preset dispart voltage resistance( 20K )
temp. rapidly and keep at preset temp. Exhaust temp. sensor (50K ),
dispart voltage resistance( 15K )
Remote control signal and manual Outdoor fan
key signal manage high; low
Indoor fan
high; med; low Invertible compressor
Swing 4-way valve
step motor
Indicator
Indicator
Electric heating belt of compressor
Buzzer
Power module protective detection
Timer
Power supply current detection
Sleep
Communicate with indoor unit
Memory
Sleep Function
¾ Under cooling or dehumidifying mode, the preset temperature will automatically rise by 1ć one hour after setting of
sleep function from remote controller and rise by another 1ć after 2 hours. It totally rise 2 in 2 hours, and then will
keep running at this temperature.
preset temperature Tpreset
Tpreset
Tpreset
Tpreset
Tpreset
preset temperature Tpreset
There is no sleep function under Fan and Auto mode.
Timer Function
The unit will automatically be turned on or off according to the timer set by the remote controller.
Memory Function
Contents of memory: Mode , Set fan speed, Set temperature, Swing.
If the system is de-energized under timer or sleep function, when re-energized ,the preset timer or sleep function will be
cancelled. you must reset it.
Indoor fan control
Indoor fan can be set to run at high, middle, low speed by remote controller, also can be set to AUTO FAN, in which
case, the indoor fan will select High, Middle and Low fan speed automatically according to the change of ambient
temperature
There may be about 3.5min delay for changing among the wind speeds.
Swing control
You can set the swing function by pressing the swing key on the remote controller only when the indoor fan is running.
After power on, the guide louver will be closed as shown in below fig. : 0 is close position, D is the min. position and L
is the max. positon.
If set swing function after turn on the unit, the guide louver will swing between D and L.
AUTO key ( emergency key)
At on status, the unit will be stopped when press this key; at off status, the unit will run at Auto mode when press this key
and the swing motor will be started.If there is remote control signal, the unit will run according to the remote control signal.
Buzzer
When the unit is energized,receives signal from press key or receives remote control signal, the buzzer will give out a beep.
Compressor data
Operation procedures/pictures
Fig.7-1
Filter
Push the filter up to unloose the clasp to pull out the
two filters.
8.1.2
As shown in Fig.7-2
Filters
Fig.7-2
Fig.7-3
Comfortstar Plus
Operation procedures/pictures
cl
Fig.7-5
Fig.7-6
cc
Fig.7-7
connecting terminal
Operation procedures/pictures
Fig 7-8
Screw
Fig 7-10
Disassembling the motor
Screw off the 3 pieces of screws that fix the motor
clamp to take off the motor clamp. As shown in Fig.7-
11 Screw
Screw off the fixing nut that fixes the cross flow fan to
Right motor clamp
pull out the motor from the cross flow fan. As shown in
Fig.7-12
Fig 7-11
screws
Disassembling the cross flow fan
Refer to the above steps to take out the cross flow fan
from the base plate after taking out the motor.
motor
unscrew the four screws at the front side plate, front side plate
and remove the front side plate.
(refer to Figure7-13)
Screw
Fig.7-13
Disassemble Top Cover
top cover
Rear Grill
Fig.7-15
Operating Procedures / Photos
Disassemble Cabinet
Fig.7-16
Fig.7-14
Disassemble Right Side Plate
Fig.7-19
Comfortstar Plus
Figure 7-20
Fixing Screw
Figure 7-21
Disassemble 4-Way Valve
(cooling only unit has not 4-way valve)
Disassemble Capillary
Figure 7-23
Disassemble Valves
Screw out the 2 bolts that fixing big valve,
unsolder the soldered dot connecting big valve with
gas return pipe to take off big valve.
(Note: When soldering the soldered dot, wrap big
valve completely by moist cloth to prevent valve
from damaging by high temperature.)
Screw out the 2 bolts that fixing small valve,
unsolder the soldered dot that connected small
small valve bolts big valve
valve and Y-shape pipe to take off small valve.
˄refer to Figure 7-24˅ Figure 7-24
Disassemble Compressor
Foot Nut
Figure 7-25
Comfortstar Plus
9 Troubleshooting
Common section
Analysis in this section is used for D.C. Inverter Series. Before analysis, you can diagnose according
to the indicator display on outdoor unit. (Refer to 9.2 Malfunction display section).
Notice
When repairing, before the voltage between module PN is measured below 50V, do not touch any terminal
to avoid electric shock.
Air conditioner The power plug is not or poorly Check and plug well plug, make
does not response connected
after powered on. loosen contact firm
Air (The buzzer does
conditi not sound after the
plug is connected Controller fuse is burnt out Change control fuse
oner and the unit does
cannot not response after
start up the remote Secure the wire connection: measure
controller is used Loose or poor contact of transformer the output voltage of the transformer
to turn it on) connection, or transformer malfunction and replace it if the value is wrong
Whether cooling (heating) load Check the estimated load of cooling (heating)
is proper
Ensure that both thick pipe and thin pipe are insulated
Poor thermal insulation of connecting well. The exposed part of the connector and copper pipe
pipe of indoor and outdoor unit must be insulated as well.
Fan speed is set too slow Set the fan speed to high or medium
Air circulation speed
is insufficient
Damage of Replace the
capacitor capacitor
Fan speed turns low damaged
Damage of Replace the motor
motor
Outdoor temperature is too high Flashing or awning can be installed appropriately. If the
max. cooling capacity cannot be satisfied, replacement of
the air conditioner is recommended.
Indoor sealability is inadequate; too many Maintain a certain degree of indoor sealability. Try not to
people go in and out frequently; there is use appliance with high amount of heat.
heating unit in the room.
Comfortstar Plus
Abnormal power supply of outdoor unit Check the circuit according to circuit diagram
When cooling or Poor contact of connection between the Re-fasten the connection
heating, outdoor main control board and module
fan runs, but
compressor Abnormal input of power module Check if input is 320V. If not, replace the
doesn't run. rectifier
Compressor temperature is too high Cool the compressor for 30 min before running
When cooling or
heating, outdoor
fan runs, but Wrong wiring Wire according to the circuit diagram
compressor
doesn't run.
Damage of outdoor main control board Replace the outdoor main control board
Burn-out or broken wire of indoor fan Repair or change the fan motor
motor
Indoor unit is mounted in the thin wall To mount the indoor unit in the strong and
cause syntonic sound and thick wall
There is foreign substance in indoor unit Take out the foreign substance
Abnormal sound and shake
Compressor too hot, Check whether the outdoor unit is not mounted yes
just start and stop at properly such as outlet blockage; bad ventilation Change the mounting position
once, or the stop or directly under sunlight
often occur
no
yes
Ambient temperature is too high For safe use
no
yes
Check if the filter or the outdoor condenser dirty Clean them
no
Check if the indoor and outdoor fans do not run Check if the power supply circuit for
yes
or run too slowly and whether the outlet airflow motor on the controller is normal or
is normal replace the motor
no
Check if the cooling system blockage, the frost yes Replace blockage component
on the capillary don't melt
no
yes
The power is abnormal Add voltahe regulator,etc.
no
no
no
no
When malfunction or protection occurs in the air conditioner, the indicators on outdoor main PCB will
blink ( for detail, see "Display and Meaning of Outdoor Indicator". When protection or malfunction is
eliminated, display will be back to normal
Sensor Malfunction
Handling method:
Check if the corresponding resistance of sensors( thermal resistor ) is normal ; plug well; the lead wire is not damage,
otherwise it is the sensor circuit or controller malfunction.
You can judge whether the sensor resistance is normal by measure the resistance or voltage and compare it with the
corresponding sensor resistance or voltage table
Overcurrent Protection
Possible reasons: the input voltage descend suddenly or the system overload.
Communicate Malfunction
Handling method:
Check if the communicate signal wire( indoor and outdoor connecting wire) is connected correctly and reliably.
System Abnormal
i.e. overload protection. When tube temperature (Check the temperature of outdoor heat exchanger when cooling and
check the temperature of indoor heat exchanger when heating) is too high,protection will be activated.
Possible reasons: the outdoor ambient temperature is too high when cooling, insufficient outdoor air circulation; and the
refrigerant flow malfunction.
Exhaust Protection
Possible reasons: 1. exhaust sensor does not connect well; 2.exhaust sensor resistance is abnormal; 3.sensor circuit
malfunction;4.cooling system malfunction: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short
pass for condenser; the system has noncondensing gas (such as air, water etc.); blockage of capillary assy (including
filter); leakage inside four-way valve causes incorrect operation; malfunction of compressor; malfunction of protection
relay; malfunction of discharge sensor; outdoor temperature too high.
Handling method:1.re-plugging the exhaust sensor; 2.replace the exhaust sensor ; 3. replace the circuit board; 4.repair
system .
Comfortstar Plus
Module protection
Handling method:
Check if the voltage between power module P and N is too low and
if the current is too high. In normal condition, voltage between P and
N should be about 320V.
Abnormal
Normal
Abnormal Normal
No voltage Normal voltage
Replace the module Measure the three-phase
Replace the mainboard Replace the fan with correct type resistance of compressor
of outdoor unit motor
Normal Abnormal