DS Catalogue Fuses Redspot English Uk
DS Catalogue Fuses Redspot English Uk
SAFECLIP
NH DIN Standard
Contents
SAFECLIP
NH DIN Standard
Comparative Charts
Commercial
Industrial
With one of the most extensive ranges available and an unsurpassed reputation for quality and reliability, RED SPOT and SAFECLIP Fuse Links can truly offer solutions for all industrial applications. Combine this with experience in the manufacture and application of High Rupturing Capacity (HRC) Fuse Links that can be traced back for over half a century through GEC Alsthom and English Electric and it is easy to understand why the expertise available to GE Power Controls is recognised world-wide. This expertise has been applied to further develop these well respected products using the latest technologies to ensure the range meets the demanding circuit protection requirements of modern installations. In the field of motor protection comprehensive testing has been undertaken to achieve first Type C and now Type 2 co-ordination when RED SPOT Standard Fuse Links are used with GE Power Controls motor control products plus other leading manufacturers. Whatever your HRC Fuse Links industrial application requirements the resources of GE Power Controls are available to provide the best technical and economic solution. With RED SPOT and SAFECLIP you can depend on the best. Please consult GE Power Controls Ltd for advice on applications not covered in this publication.
GE Power Controls
3
up to 440Vac up to 125A
HRC Fuse Links for other applications Protection of Semiconductor Devices (BS88/IEC & DIN) House Service and Street Lighting Cut-outs Electricity Supply Distribution High Voltage Fuse Links up to 34.5kV Railway Signalling, Traction and DC Applications Admiralty, Aircraft and Interservice Pattern Canadian (CSA) and North American Spec. Details available on request
RED SPOT
SAFECLIP
GE Power Controls
NH DIN
RED SPOT
Contents
SAFECLIP
NH DIN Standard
Comparative Charts
A.1
RED SPOT
HRC Fuse Links RED SPOT Standard BS 88-2:1988 RED SPOT Standard IEC 269-2
Applications
Technical Data
Current Rating Voltage Rating ac Voltage Rating dc (A) 2-1250 (V) up to 660 (V) up to 460 (kA) 80 (kA) 40
Breaking Capacity
AC Performance ASTA 20 certified to 80kA, generally at 660 Volts, to BS 88: Part 2: 1988 (IEC 269-2). DC Performance ASTA certified at 40kA, to BS 88:Part 2: 1988 (IEC 269-2).
A.2
GE Power Controls
2A 4A 6A 10A 16A 20A 20M25A 20M32A 25A 32A 32M40A 32M50A 32M63A
250 250 250 250 250 250 250 460 460 460 460 460 460 460 460 460 460 460 460
A.3
RED SPOT
A.4
GE Power Controls
1000A 1250A
TXU1000 TXU1250
400356 400357
660 660
300 300
TZC, TZCP, TZF, and TZLM Fuse Links proved at 460 Volt dc are available for users who need superior dc performance in these dimensional references. Fuse Links for Canada complying with CSA Specification C22-2 No 106-M92 are also available.
A.5
RED SPOT
NIT NET
2 - 20M32 25 - 32M40 32M50, M63 2 - 32M63 35 - 63 63M80, M100 32 - 63 80, 100 100M125 - M200 125 - 200 200M250
36.50 36.50 37.70 56.40 56.40 58.00 56.00 58.00 70.00 70.00 70.00
14.10 14.10 17.50 22.20 22.20 26.00 22.20 26.00 33.70 33.70 40.00
55.60 55.60 55.10 85.80 85.80 90.50 109.00 111.00 111.00 111.00 111.00
11.10 11.10 11.10 8.70 8.70 12.70 19.10 19.10 19.10 19.10 19.10
4.70 4.70 4.70 5.20 5.20 5.20 8.70 8.70 8.70 8.70 8.70
TFP
TC TF
80, 100 100M125 - M200 125 - 200 200M250, M315 250 315, 315M355 250 - 315M355 355 - 400M450
TM TTM TLM
TXU
1000, 1250
88.90
99.50
200.00
63.50
13.50
A.6
GE Power Controls
2 Amp - 63 Amp
Current Rating (Amp) 2 4 6 10 16 20 25 32 35 & 32M35 40 & 32M40 50 & 32M50 63 & 32M63 Pre-Arcing I2t (A2sec) 2 7 22 170 150 300 500 1080 1380 1920 3410 6500 Total I2t (A2sec) Total I2t (A2sec) Total I2t (A2sec) at 415 Volt at 550 Volt at 660 Volt 7 24 73 500 560 930 1730 3200 4100 5200 8000 17000 11 35 110 720 790 1270 2500 4500 5200 5750 10100 21000 15 50 150 1000 1100 1670 3400 5900 6500 8380 13260 25000
Technical data
2 Amp - 63 Amp
A.7
RED SPOT
A.8
GE Power Controls
Notes
A.9
SAFECLIP
NH DIN Standard
Comparative Charts
B.1
Applications
Technical Data
Current Rating Voltage Rating ac Breaking Capacity ac (A) 2-400 (V) up to 440 (kA) 80*
Breaking Capacity
AC Performance ASTA 20 certified to 80kA, generally at 440 Volt, to BS 88: Part 2: 1988 (IEC 269-2).
Short circuit energy limitation RED SPOT 400 Series Fuse Links limit the peak current and energy let through to circuits that experience short circuit faults. This enables significant economies to be made in the design of equipment used in combination with RED SPOT Fuse Links. Discrimination RED SPOT 400 Series Fuse Links will discriminate with each other at fault levels up to 80kA, at 415 Vac, in most cases when the ratio between 'major' and 'minor' current ratings is 1.6:1. Motor Starting Ability All RED SPOT 400 Series Fuse Links are suitable for the protection of motor circuits and have superior withstand to motor starting surges. Motor Circuit Protection RED SPOT 400 Series Fuse Links provide back up protection, including Type 2 co-ordination with the motor starter and associated cables. Protection against electric shock RED SPOT 400 Series Fuse Links protect against electric shock when used in accordance with the IEE Wiring Regulations (BS 7671:1992). Power dissipation All RED SPOT 400 Series Fuse Links have low power loss values, well within the limits specified in BS 88:Part2: (IEC 269-2).
B.2
GE Power Controls
B.3
250A 315A
GTKF250 GTKF315
400390 400391
415 415
250A 315A
GTKM250 GTKM315
402763 402764
415 415
355A 400A
GTMF355 GTMF400
400394 400395
415 415
355A 400A
B.4
GE Power Controls
Dimensions in mm
RED SPOT 400 Series - Offset tags: 2-hole fixing
Type Rating A B D E G Fixing Centres 44.50 73.00 73.00 94.00 94.00 H
Dimensions
GTM
355, 400
50.20
40.40
211.00
25.40
11.00
B.5
B.6
GE Power Controls
Notes
B.7
SAFECLIP
SAFECLIP
SAFECLIP
C. C. C. C. 2 3 4 56 Product introduction Fuse Link selection list Dimensions Technical data
NH DIN Standard
Comparative Charts
C.1
SAFECLIP
SAFECLIP
SAFECLIP
Applications
Technical Data
Current Rating Voltage Rating ac Breaking Capacity ac (A) 2-125 (V) up to 440 (kA) 80
Breaking Capacity
AC Performance The standard ratings are ASTA 20 certified to 80kA, 440 Volt*, to BS 88: Part 1 or Part 6: 1988 (IEC 269-1). * SS types are certified at 16.5kA, 240 Volt, and the NS32M40, ES63M80 and XS125 at 80kA, 415 Volt.
Discrimination SAFECLIP Fuse Links will discriminate with each other at fault levels up to their rated ac performance in most cases when the ratio between major and minor current ratings is 2:1. Motor Starting Ability All SAFECLIP Fuse Links are suitable for the protection of motor circuits and have superior withstand to motor starting surges. Protection against electric shock SAFECLIP Fuse Links protect against electric shock when used in accordance with the IEE Wiring Regulations (BS 7671:1992). Power dissipation All SAFECLIP Fuse Links have low power loss values, well within the limits specified in BS 88: Part 2 (IEC 269-2).
C.2
GE Power Controls
BS Ref. E1
SAFECLIP
BS Ref. F1
BS Ref. F2
C.3
SAFECLIP
SAFECLIP
Dimensions in mm
SAFECLIP - Offset blade tag
Type SS NS ES XS Rating 2 - 20 2 - 32M40 40 - 63M80 2 - 125 A 25.00 35.50 39.00 39.00 B 14.50 14.50 17.50 26.40 D 51.00 62.00 69.00 80.00 E 11.00 11.00 15.00 19.00 G 0.80 0.80 1.25 1.60 H 3.60 3.60 3.60 3.60
SAFECLIP
OS
80 - 100M160
58.00
26.40
90.50
12.70
5.20
C.4
GE Power Controls
2 2.2 9.5 4 7.2 30 6 22 92 10 170 650 16 200 800 20 360 1200 25 650 2500 32 600 3500 40 & 32M40* 2400 6400 50 3200 11500 63 5400 14500 80 & 63M80* 6000 24000 100 12000 54000 125 13000 115000 * Maximum rating of 32M40 and 63M80 is 415 Volt.
Technical data
C
Type NS, ES and XS
C.5
SAFECLIP
SAFECLIP: l2t values
Type OS
Current Rating (Amp) 80 100 100M125 100M160 Pre-Arcing I2t (A2sec) 14000 17000 32000 50000
SAFECLIP
SAFECLIP
C.6
GE Power Controls
Notes
C.7
NH DIN Standard
GE Power Controls
NH DIN
SAFECLIP
NH DIN Standard
D. D. D. D. D. D. 2 34 5 6 7 8 Product introduction Fuse Link selection list NHG (General Purpose) Fuse Link selection list NHA (Motor Starting) Dimensions Technical data NHG (General Purpose) Technical data NHA (Motor Starting)
Comparative Charts
D.1
NH DIN Standard
GE Power Controls
NH DIN
HRC Fuse Links NHG and NHA DIN Standard IEC 269 VDE 0636 NH DIN Standard
Applications
Technical Data
Current Rating Voltage Rating ac Breaking Capacity ac (A) 6-630 (V) 500 (kA) 120
Approvals
AC Performance NH Fuse Links are VDE certified at 120kA RMS, 50Hz, 500 Volt to IEC 269.
NHA Motor Starting Class aM range of DIN Fuse Links are specifically designed for the short circuit protection of equipment in motor circuits. The Fuse Links are used in combination with overload protective devices ensuring total protection of the circuit. The rating of the Fuse Link is selected against the nominal current of the motor. This enables simple and effective selection of Fuse Links for motor circuits.
Technical Standard VDE 0636/22 Class aM IEC 269 Motor Starting Fuse Links Class gM
Note: All Fuse Links are supplied with plain undrilled knife-blade tags and with visual indicator situated in the top end plate.
D.2
GE Power Controls
6A 10A 16A 20A 25A 32A 35A 40A 50A 63A 80A 100A
NH DIN Standard
Body size 00
6A 10A 16A 20A 25A 32A 35A 40A 50A 63A 80A 100A 125A 160A
Body size 0
6A 10A 16A 20A 25A 32A 35A 40A 50A 63A 100A 125A 160A
Body size 1
40A 50A 63A 80A 100A 125A 160A 200A 224A 250A
D.3
NH DIN Standard
GE Power Controls
NH DIN
Body size 2
NH DIN Standard
40A 50A 63A 80A 100A 125A 160A 200A 224A 250A 315A 355A 400A
Body size 3
D.4
GE Power Controls
Body size 00
6A 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A
NH DIN Standard
Body size 0
Body size 1
Body size 2
Body size 3
D.5
NH DIN Standard
Dimensions in mm
GE Power Controls
NH DIN
NH DIN Standard
1 2 3
D.6
GE Power Controls
Technical data
D.7
NH DIN Standard
NHA Motor Starting: l2t values
6 Amp - 160 Amp
Current Rating (Amp) 6 10 16 20 25 32 40 50 63 80 100 125 160 Pre-Arcing I2t (A2sec) 300 500 800 1150 1700 3000 4500 7500 10000 20000 40000 70000 100000 Total I2t (A2sec) at 380 Volt 400 800 1200 1800 2000 4500 7500 10000 17000 35000 60000 100000 170000
GE Power Controls
NH DIN
NH DIN Standard
D.8
GE Power Controls
Notes
D.9
SAFECLIP
NH DIN Standard
Comparative Charts
E. E. E. 23 4 5 660 Volt ac (RED SPOT Standard) 415 Volt ac (RED SPOT 400 Series) Blade tag (SAFECLIP)
E.1
Comparative Charts
E
* For use with Switch Fuse Devices, with A1 dimension fixing centres 550Vac 440Vac
E.2
GE Power Controls
Comparative Charts
E
* For use with Switch Fuse Devices, with A1 dimension fixing centres 550Vac 440Vac Note: The comparative types listed are a guide to interchangeability. There are some minor dimensional differences between manufacturers. The above cross-reference chart is based on comparable voltage and current ratings. It is essential that other performance characteristics are checked to ensure compatibility.
E.3
Comparative Charts
440Vac
Note: The comparative types listed are a guide to interchangeability. There are some minor dimensional differences between manufacturers. The above cross-reference chart is based on comparable voltage and current ratings. It is essential that other performance characteristics are checked to ensure compatibility.
E.4
GE Power Controls
Comparative Charts
Note: The comparative types listed are a guide to interchangeability. There are some minor dimensional differences between manufacturers. The above cross-reference chart is based on comparable voltage and current ratings. It is essential that other performance characteristics are checked to ensure compatibility.
E.5
GE Power Controls
Ref. I/3116/E/E 10.0 Ed. 03/01
GE POWER CONTROLS Hornhouse Lane Knowsley Business Park Liverpool L33 7YQ T 0870 600 4372 F 0151 549 4546 E gepcuk@gepc.ge.com